Midco RE32 User Manual

INSTALLATION AND SERVICE INSTRUCTIONS
ANSI Z21.17
CONVERSION
BURNERS
ECONOMITE MODEL RE32
Gas Conversion Burner
The ECONOMITE Model RE32 intermittent spark ignition conversion burner is adaptable to most gas utilization equipment, including gravity and forced circulation furnaces and boilers, and is particularly recommended for horizontal and downdraft gas utilization equipment since it needs no draft to maintain a pilot. Power burner design makes it perfectly suited for oil burner replacement. In the United States, installation must conform with local codes or,
in the absence of local codes, with Installation of Domestic Gas
Conversion Burners, ANSI Z21b-latest edition, and National Fuel Gas Code, ANSI Z223.1-latest edition, available from
American National Standard Institute. Further reference should be made to the recommendation of your fuel supplier.
NOTE: Any additions, changes, or conversions required in order for
the gas utilization equipment to satisfactorily meet the application needs must be made by a MIDCO distributor (or other qualified agency) using factory specified and approved parts.
In Canada, installation must conform with local codes or, in the
absence of local codes, with Installation Codes for Gas Burning
Appliances and Equipment, CGA Standard CAN/CGA 1-B149.1 or 2. When the conversion burner is used on Forced Air Central
Furnace, the two yellow and black warning labels in the literature envelope shall be attached in accordance with Installation Code, CGA Standard CAN/CGA 1-B149, Clause 5.4.4.4. Further reference should be made to the recommendation of your fuel supplier.
INSTALLER: Inform and demonstrate to the
user the correct operation and maintenance of this gas utilization equipment. Inform the user
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Do not try to light any appliance
Do not touch any electrical switch;
do not use any phone in your building.
Immediately call your gas supplier
of the hazards of storing flammable liquids and vapors in the vicinity of this gas utilization equipment and remove such hazards. Affix this manual adjacent to the conversion burner.
If you cannot reach your gas
supplier, call the fire department.
CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER.
USER: Retain this manual for future reference.
If other than routine service or maintenance as described in this manual is required,
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
contact a qualified service agency. DO NOT ATTEMPT REPAIRS. An inadvertent service error could result in a dangerous condition.
SAFETY INFORMATION TERMS: The following terms are used to identify hazards, safety precautions or special notations and have standard meanings throughout this manual. When you see the safety alert symbol and one of the safety information terms, as shown below, be aware of the hazard potential.
DANGER: Identifies the most serious hazards which will result in severe personal injury or death. WARNING: Signifies a hazard that could result in personal injury or death. CAUTION: Identifies unsafe practices which would result in minor personal injury or product and property damage.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
WHAT TO DO IF YOU SMELL GAS
from a neighborÕs phone. Follow the gas supplierÕs instructions.
MIDCO International Inc.
4140 WEST VICTORIA STREET, CHICAGO, ILLINOIS 60646 / (773) 604-8700 FAX: (773) 604-4070 / http://www.midco-intl.com
PRINTED IN U.S.A.
197
8470-01
SPECIFICATIONS
NATURAL or PROPANE Gas
AIR DELIVERY
MAXIMUM FIRING RATE**................................300MBH***
MINIMUM FIRING RATE**...................................50MBH***
TUBE DIAMETER................................................4 inches
TUBE LENGTH......................................2
MINIMUM COMBUSTION CHAMBER SIZE
300 MBH...................................7" W x 11" L or 10" dia.
50 MBH.....................................6" W x 10" L or 9" dia.
GAS PRESSURE REQUIRED
NATURAL..........................................4.0" to 14.0"W.C.
PROPANE.........................................4.0" to 14.0"W.C.
STANDARD VOLTAGE..........120 Volts.............60 Cycle
PILOT SAFETY.........................Electronic, 100% shut-off
MAIN AUTOMATIC VALVE...........4 Function Redundant
*SCFM = Standard Cubic Feet/Minute **All Ratings Based on 1000 BTU/Cu. Ft. NATURAL, 2500
BTU/Cu. Ft. PROPANE at Sea Level Derate burner for
altitudes over 2,000 feet by 4% for each 1,000 feet above
sea level ***1 MBH = 1,000 BTU/Hr.
One gallon fuel oil = 140,000 BTU/Hr.
(Approx. Air Delivery at Zero Draft).....62SCFM*
1/2 - 61/4 inches
PART 1 INSTALLATION
CAUTION: The ECONOMITE RE32 is not intended for outdoor installation and must be protected from excessive moisture. Provide adequate clearance for service and proper operation.
I VENTILATION
If the former automatic oil burner gave trouble-free operation, it is probable that the gas utilization equipment area has sufficient infiltration of air for combustion and dilution of flue gas. Nevertheless, the area must be checked:
Open basement or utility areas of normal construction,
without storm windows or tight doors, will generally allow sufficient air infiltration. However, if the gas utilization equipment is located in a tight or separate room, ventilation to an open area as described above will be required. Install two permanently open grilles, each sized on the basis of one square inch free area per 1,000 BTU (but not less than 100 square inches) of the total input ratings of all gas utilization equipment in the combined space. One grille should be located within 12 inches of the ceiling, the other within 12 inches of the floor.
If the gas utilization equipment is located in an area of
unusually tight construction, or if an exhaust fan, kitchen ventilation system, clothes dryer and/or fireplace is installed in the building, provision must be made for an outside air supply near the gas utilization equipment area. Install permanently open grilles sized at not less than one square inch free area per 4,000 BTU of burner input. When ventilating through horizontal ducts, grilles should be sized at not less than one square inch free area per 2,000 BTU of burner input. In any case, the minimum dimension of rectangular air ducts shall not be less than 3 inches.
In Canada, for detailed ventilation requirements, refer to
standard CAN/CGA 1-B149.1 or .2 and/or local codes.
around door frames, to prevent leakage into or out of the combustion chamber.
The access or firing door should open easily to relieve
pressure. If positive latches exist, they should be modified to permit easy opening; a spring loaded door holder is recommended.
On all boilers, make certain the pressure relief safety valve is
in good operating condition.
III COMBUSTION CHAMBER
A combustion chamber liner is normally required to protect non-heat transfer surfaces and to provide a radiant bed for rapid heat transfer to the primary surfaces of the heat exchanger. In most cases an existing oil burner combustion chamber liner can be used, if in good condition.
In the case of wet base boilers, where the entire combustion
chamber is comprised of heat exchange surfaces and no combustion chamber liner was provided for oil firing, a liner is usually not required for the ECONOMITE. However, a liner or target wall may be necessary if the combustion chamber is unusually short, in order to avoid excess flame contact on the heat exchanger walls or flueways.
If a built up combustion liner is required, use 2300
minimum insulating material.
The opening in the combustion chamber must fit the burner
tube. If an existing chamber with an oversized opening is to be used, fill the remaining space around the tube with refractory material and seal air tight.
NOTE: In no case should the burner tube be allowed to extend into the chamber proper; it must be set flush to 1/4" short of the inside surface, because high combustion chamber temperatures will cause premature pilot deterioration.
Burners are shipped with the burner tube at its fully extended
length of 6 following steps (see Figure 1):
1. Uncover the Burner Tube Clamp access port located on the
2. Turn the exposed screw counter-clockwise to loosen
3. Turn the Pilot Tube Clamp Nut (see Figure 1)
4. Push Burner Tube in to desired length and tighten
5. Locate the retention plate at least 7/8 inch but not more
6. Cut the Pilot Tube to the appropriate length and
1/4 inches. To reduce the tube length, complete the
lower right side of the burner box (under motor), adjacent to the mounting flange.
the Burner Tube Clamp.
counterclockwise, to loosen the Pilot Tube.
Burner Tube Clamp and recover access port.
3/8 inch from the end of the burner tube and tighten
than 1 the Pilot Tube Clamp Nut.
reattach tube fitting using compression sleeve supplied in spud-bag.
o
F
II PREPARATION OF THE GAS
UTILIZATION EQUIPMENT
Clean the gas utilization equipment heat exchanger interior,
combustion chamber and flue connections. Remove all adhering tars, scale, dirt and soot. Inspect equipment for actual leaks and/or potential leaks.
Cement all joints, including those in the equipment base and
FIGURE 1 Burner Tube Adjustment
-2-
FIGURE 2 Dry Base Boiler With Combustion Chamber
Liner (Furnace Construction is Similar)
WARNING: BURNER CABINET MUST BE MOUNTED IN ORIENTATION SHOWN IN FIGURES 2 AND 3. ANY OTHER MOUNTINGS MAY CAUSE DANGEROUS CONDITION, AND WILL VOID BURNER WARRANTY AND AGENCY APPROVALS.NON-STANDARD ARRANGEMENTS MAY BE AVAILABLE FOR SOME MODELS; CONSULT FACTORY FOR DETAILS IF REQUIRED.
Before permanently setting the burner in place, check
retention plate and pilot assembly to make sure they are free of foreign materials.
IV CHIMNEY, VENT CONNECTOR, AND
DRAFT CONTROL
WARNING:The chimney shall be inspected for unsafe conditions such as deteriorated masonry and excessive soot or other blockage or potential blockage. Installation must conform with local codes or in the absence of local codes with ANSI Z21.8-latest edition and NFPA, ANSI Z223.1
- latest edition
WARNING: THE VENT CONNECTOR SHALL NOT BE CONNECTED TO A CHIMNEY ALREADY VENTING SOLID FUEL BURNING EQUIPMENT, AN INCINERATOR OR AN OPEN FIREPLACE.
The Vent Connector shall be made of non-combustible
corrosion resistant material capable of withstanding the vent gas temperature produced by the gas utilization equipment and of sufficient thickness to withstand physical damage.
The Vent Connector shall be as short as possible. The
entire length shall be readily accessible for inspection, cleaning and replacement.
The length of horizontal uninsulated Vent Connector
between chimney and a single gas utilization equipment shall not exceed 75% of the height of the chimney above the connector, or 100% if the Vent Connector is insulated.
Maximum Input Flue Pipe Diameter
64 MBH 4" 100 MBH 5"
143 MBH 6"
195 MBH 7" 225 MBH 8" 300 MBH 9"
TABLE 1: Recommended Flue Pipe Sizes
Source: ANSI Z21.8A-1990, Installation of Domestic Gas
Conversion Burners. For Other Applications, Consult
Appropriate Standards.
The Vent Connector shall be installed so as to avoid turns or
other construction features which create excessive resistance to flow of vent gas. It shall be installed without any dips or sags and shall slope upward at least 1/4" per foot.
A manually operated damper shall not be placed in the Vent
Connector or chimney of any gas utilization equipment.
The Vent Connector shall be firmly attached to draft hood
outlets and flue collars. Joints between sections of connector
FIGURE 3 Wet Base Boiler with Unlined
Combustion Chamber
piping shall be fastened by sheet-metal screws or other approved means. The Vent Connector shall be supported for the design and weight of the material employed to maintain clearance and prevent physical damage and separation of joints.
A draft hood or a barometric draft regulator shall be installed
in the same room or enclosure as the equipment in such a manner as to prevent any difference in the pressure between the hood or regulator and the combustion air supply. In no case shall the relief opening of the draft hood or barometric draft regulator be located at a point lower than the top of the highest flue passage in the equipment.
Gas utilization equipment requiring controlled draft may be
equipped with a listed double acting barometric draft regulator installed and adjusted in accordance with the manufacturerÕs instructions if approved by local codes.
A device which will automatically shut off gas to the burner in
the event of sustained backdraft is required. It shall be of the listed manual reset type and installed and adjusted by a qualified service technician in accordance with the manufacturerÕs instructions.
FIGURE 4 Draft Hood
FIGURE 5 Barometric Dampers
Figure 4 and 5 : Copyright by the American Gas
Association. Used by permission of the copyright holder.
-3-
V ELECTRICAL
Installation wiring and grounding of the burner must conform to local codes, or, in their absence in the United States to National Electric Code, ANSI/NFPA No. 70-1 latest edition; in Canada, to Canadian Electrical Code Part 1, CSA Standard C22.1.
Use 14 gage copper wire for line voltage wiring. Be sure to
hook up to permanently live circuit. Provide a fused on-off dis­connect switch carrying a minimum 3 amp fuse.
The frame of the burner should be well grounded. A terminal
is provided on the strip for positive grounding.
Confirm that the polarity is correct -- hot wire to strip terminal
1, neutral 2 -- and that the neutral line is not subject to induced low voltage (check 2 to earth ground) from other equipment, as that can cause the flame safeguard to malfunction.
Each installation must include suitable limit control(s).
Existing oil burner combination operating and limit controls are normally NOT SUITABLE for gas burner use.
Set the thermostat heat anticipator for the total current draw
handled by the thermostat. The current draw of the Economite 24V operating circuit is 0.9 amps.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing
the low voltage circuit as it could overload the transformer. Do not use Motor Relay to operate any external devices as the extra load could damage the relay contacts. NOTE: If any of the original wiring as supplied with the
conversion burner must be replaced, it must be replaced with type TFF wire or its equivalent.
.
COMBINATION
VALVE
SPLICE
BR
PV
MV/PV
MV
TERMINAL
STRIP
Y
BL
TRANSFORMER
Y
BL(Y)
W(BK)
BK
TT12
GND
THERMOSTAT OR 24V OPERATING CONTROL. IF NOT USED, JUMPER T-T
MOTOR WITH INTERNAL
INTERLOCK SWITCH
BK
R(Y)
MOTOR
2 1
BK(W) BK
W(BK)
GROUND
BAR
MOTOR RELAY
SPST N.O.
SPLICE
Y
GND
MV
BL
MV/PV
PV
WIRING AND
COMPONENTS:
TERMINALS:
BK
Y BL(Y)
CONNECTION DIAGRAM
BL
Y
W(BK)
R(Y)
MOTOR RELAY
2
1
4
3
SERIES CONNECT ALL 120V OPERATING AND/OR LIMIT CONTROLS
BR
Y
Y
BL
BK
FUSED DISCONNECT
SCHEMATIC
M I
42
24V
13
BL
Y
BR
120 V CONTROLS
BK
BK
THERMOSTAT OR 24V CONTROL
IF NOT USED, JUMPER T-T
T(LEFT) T(RIGHT)
BLY
M
INTERLOCK SWITCH
R(Y)
24V
24V
GND
MV
SENSE
MV/PV
SPARK
PV
BK
LEGEND
BY MIDCO BY INSTALLER
TERMINAL STRIP COMPONENT ELECTRONIC CONTROL
SPLICE
S8600 ELECTRONIC CONTROL
MV
MV PV
PV
GND
(NOT USED)
BURNER
24V
GND
24V
SENSE
SPARK
SPARK ELECTRODE
SENSOR ROD
NEUTRAL
120/1/60
HOT
NEUTRAL
120/1/60
HOT
R(Y)
SENSE ROD
SPARK ROD
FIGURE 6 Wiring Diagram
CAUTION: Do not add any power consuming devices in
VI PIPING
CAUTION: The available gas pressure should be within the limits shown in the SPECIFICATIONS section. Excessive pressure will damage Combination Valve and Regulator. If the supply pressure exceeds the 14.0" W.C. maximum, a suitable intermediate main regulator rated for main and pilot loads must be installed ahead of the Main Manual Shut-Off Valve shown in Figure 7.
The burner gas supply piping should branch off from the
main line as close to the gas meter as possible. Do not connect to the bottom of a horizontal section. Use new black pipe and malleable fittings free of cutting and threading burrs or defects.
Provide a sediment trap, union and 1/8" pressure tap in
piping close to burner as shown in Figure 7.
Use pipe joint compound approved for use with Liquid
Petroleum Gases.
Piping must comply with local codes.
To obtain the maximum firing rate of 300 MBH, the gas
supply piping must be sized to provide a minimum of 4.0" W.C. pressure to the inlet of the combination valve when the burner and all other gas utilization equipment are on. For a firing rate of 225 MBH or less, 3.5" W.C. inlet pressure is sufficient.
When selecting the burner supply pipe size per Table 2, the
permissible pressure drop must be based on the pressure available at the inlet to the supply pipe branch line when all other gas utilization equipment is on.
NOTE: If there is more than 1.0" W.C. differential in the inlet pressure to the burner compared to when all other gas utilization equipment is off, refer to Section IX, last paragraph.
CAUTION: Because it is difficult to accurately control pressure during supply pipe leak test, it is recommended that the Combination Valve be disconnected. Exposing the Combination Valve to a pressure over 1/2 (14" W.C.) PSIG will damage the valve and void all warranties.
DANGER: Explosion hazard. Do not use oxygen for pressure testing. An explosion could occur during initial start-up.
If the burner piping must be rearranged because of space
limitations, be sure to carry out the general arrangement shown in Figure 7. Install the combination valve in any position except up-side down.
When the burner is installed in the vestibule of jacketed
equipment, it is recommended that the combination valve be left adjacent to the burner within the vestibule. Install the Main Manual Shut-Off Valve in the piping outside the jacket of the equipment.
APPROX. CAPACITY-MBH
LENGTH OF PIPE
10
130 200 275 300
300
20
90 145 190 300
300
40
60 100 130 200
245 300
300
60 50
80 105 165 195 300 300
Ú2
Ú4
1
TYPE OF
GAS
NATURAL
PROPANE
NATURAL
PROPANE
NATURAL
PROPANE
NATURAL
PROPANE
PIPE SIZE
1
3
11Ú4
TABLE 2: Supply Pipe Capacities in MBH
Capacities shown are for a total pressure drop of 0.3" W.C. For higher permissible pressure drops, consult your fuel supplier.
Source: Gas Engineers Handbook-1974
-4-
100
60
80 125 150 235 300 300
VII MAIN GAS SPUD
Standard burners are approved for use with NATURAL or PROPANE gas and should be used only with the gas specified on the rating plate.
As shipped, the installed NATURAL gas spud has a #8
(.199) drill orifice size (PROPANE a #25 [.149]), for an input capacity range of approximately 85 to 125 MBH (PROPANE 75 to 110 MBH). The combination valve main gas pressure regulator is set to provide 2.0" W.C. manifold gas pressure for a minimum spud input and the blower air shutter is set for maximum spud input, 11 turns from full closed (PROPANE 9 turns), to provide a lean gas/air mixture for initial start up.
If a standard NATURAL gas Model RE32 is to be used with
PROPANE gas, a conversion kit which contains a .025 Pilot Spud, a 1/8" main spud and a PROPANE label is available. Change the pilot spud, affix the PROPANE label over the NAT designation on the rating plate and install the appropriate size main spud as detailed below.
If the required firing rate does not fall within the range of the
installed spud, or if converting to PROPANE gas, select the correct capacity range from Table 3 and, if so indicated, the spud with the correct orifice size (stamped with inch diameter) from the spare spud bag. If the required firing rate is at the minimum of capacity range, select the next lower range.
Remove the installed spud and spring assembly, select new
spud and assemble to spring, install assembly (spud first), spring only or neither, as shown for the capacity range selected per Table 3.
WARNING: Reposition the primary air shutter for the maximum firing rate of the selected capacity range. Do not change the combination valve main gas pressure regulator setting at this time.
CAUTION: The approximate air and gas settings described above are for initial start up only. Final settings must be made in accordance with Section VIII. Instructions for adjustment of the manifold gas pressure are detailed in Section XI.
*Spud orifice size and approximate shutter and manifold gas pressure settings; as shipped.
Orifice range with 4.0" W.C. inlet pressure
Orifice range with 5.0" W.C. inlet pressure Data shown is approximate and based on "0" overfire pressure at sea level.
TABLE 3: Spud Capacity and Preliminary Gas
and Air Settings
FIGURE 7 Piping Connections
VIII INITIAL START UP/ADJUSTMENT
WARNING: Ignition is automatic. Make spark observations into combustion chamber only with Main Manual Shut-Off Valve closed. Confirm that gas utilization equipment does not contain any accumulated gases. Purge as described in Step 3 below.
NOTE: Standard burners are shipped with the combination valve pilot adjustment set to provide a permissible pilot flame gas pressure when the gas pressure at the inlet to the combination valve is within 4.0" - 6.0" W.C. NATURAL and PROPANE. If the inlet gas pressure is not suitable, refer to TROUBLE CHART, Section II.C.
1. Check the burner piping and valves for gas leaks by applying a weak liquid soap solution to unions and joints with the gas supply on. Leakage will be indicated by the appearance of soap bubbles. Locate and correct all gas leaks before proceeding.
WARNING: DO NOT USE OPEN FLAME.
2. Purging the air from the gas line at this point will expedite the first start as described below.
CAUTION: Purge outside the building. Do not
purge into the gas utilization equipment.
3. To purge the gas utilization equipment and chimney of any accumulated gases, turn Manual Gas Cock Knob on the Combination Valve to OFF, turn burner power ON and set the operating control to ON or thermostat to call for heat. Let the blower run long enough to accomplish four air changes but not less than five minutes.
4. CAUTION: Make sure that the capacity range of
the installed spud, and the preliminary gas pressure is suitable for the input rating of the gas utilization equipment. See Section VII and Table 3.
5. Reset the Electronic Control by setting the operating control to OFF or the thermostat below room temperature for at least 60 seconds. See Section XII.
6. Turn Manual Gas Cock Knob on Combination Valve to ON.
7. Turn operating control to ON or set thermostat above room temperature. A few seconds after the motor reaches operating speed the pilot should light, followed by the main
flame. If the burner fails to light within 90 seconds, the
Electronic Control will shut off the pilot and main valves and will lock out. To reset the Electronic Control for restart, de-energize the control by setting the operating
-5-
control to OFF or thermostat below room temperature for
at least 60 seconds. If burner still fails to light, turn it off and repeat from step 4. Then, if necessary, refer to the
trouble chart to isolate the problem.
WARNING: Repeated unsuccessful attempts to light will result in accumulated gases in combustion chamber. To prevent these gases from reaching an explosive level, periodically purge the combustion chamber as described in step 4 above.
8. To make a preliminary setting of the burner input, determine the manifold gas pressure required from Table 3 and adjust the combination valve main gas pressure regulator accordingly. See Section XI.
9. To determine the firing rate for NATURAL gas: Accurately time test dial for the number of seconds for one revolution and use the following formula. All other gas utilization equipment must be off.
3600 x test dial size x BTU value No. of seconds for one rev. test dial
Then divide by 1,000 for MBH value.
Example: 3600 x 1 x 100
20
For PROPANE gas, consult your supplier for method of determining firing rate.
10. Readjust the primary air shutter to provide a quiet, soft blue flame with well defined orange and yellow tips for NATURAL gas or with well defined yellow tips for PROPANE gas.
= 180,000 BTU/Hr = 180 MBH
= BTU/Hr
Check the operation of the burner; start and stop it
11. several times with the thermostat or operating control. With the burner running, check the operation of all limit
12. and associated controls. PERFORM THE FOLLOWING FINAL ADJUSTMENTS
13. for combustion and flue gas temperature. Take the flue gas samples and temperature immediately ahead of the draft control. A. The flue gas temperature should be above 325¡ but
not exceeding 550¡F. Excessive flue gas temperatures will result in low efficiencies. Low flue gas temperature may causes excessive condensation. Reset gas input if necessary to adjust stack temperature.
B. Make the final setting of the primary air shutter by
checking the flue gases with an ORSAT or similar combustion testing instrument. The carbon monoxide content should conform to local codes or, in their absence, to the level specified in the United States or Canadian Standard reference on the front cover of this manual; the carbon dioxide content should be approxiamately 9.5% for NATURAL and 12.1% for PROPANE, or within the limits prescribed by the local codes.
Check the draft control to make sure there is no spillage
14. of flue products into the room.
FILL OUT THE INSTALLATION ADJUSTMENT DATA
15. TAG and affix to the burner or gas utilization equipment.
NOTE: For subsequent normal starting and shut-off procedure, refer to CONSUMER INSTRUCTIONS or to the instruction plate mounted on the burner.
PART 2 SERVICE
DANGER: Be sure the manual Main Shut-Off Valve combination valve and Burner Power Switch are turned OFF before
removing any parts for service.
IX DRAWER ASSEMBLY
When the pilot flame gas pressure is in the proper range (see Table 4), lint, dust, or corrosion is the most common cause of pilot problems.
The retention plate and pilot are part of the drawer
assembly which can be removed as a unit. Remove the four back plate screws; then, disconnect the pipe union, pilot tube and control wires and pull out the drawer assembly.
When servicing, clean the retention plate ports and pilot
assembly including the pilot spud and electrode porcelain on sensor rod and/or spark electrode. Examine the sensor rod. If there is any serious corrosion or loss of metal at the tip replace the sensor rod.
Make sure that the pilot mica peepsight is not damaged or
missing as air leakage through the peepsight hole could mimic some of the conditions described below. See Figure 7.
Check that the pilot orifice diameter is correct.
Make sure that the burner tube is properly positioned in the
combustion chamber entry. It must be set flush to 1/4" short of the inside of the combustion chamber as shown in Figure 2 or
3. It must not protrude into the combustion chamber.
If cleaning does not eliminate the lighting problem, further
checks are required:
CAUTION: Do not indiscriminately increase pilot orifice diameter. Pilot troubles are rarely cured in this manner and new troubles may be introduced by causing the pilot flame to float and lose contact with the sensor rod.
If the standby gas pressure is over 14.0" W.C., or less than
4.0" W.C., refer to Section VI.
If the standby gas pressure is between 4.0" W.C. and 14.0"
W.C. and does not vary more than 1.0" W.C., use the pilot adjustment screw in the combination valve (Section XI) to set the pilot flame gas pressure at 4.0" W.C.
If the inlet pressure varies more than 1.0" W.C., a 1/8 inch
Maxitrol RV12 series(or equal) pressure regulator set for an
outlet pressure of 3.5" W.C. must be installed in the pilot gas line and the pilot adjustment screw set full open.
Nominal BTU /Cu. ft. Value
Orifice Diameter .032 .025 Pilot Flame Gas Pressure Approx. Capacity 2400 BTU/Hr.
TABLE 4 Pilot Specifications
NAT-1000 PROPANE-2500
3.0"-4.0" W.C.
X BLOWER ASSEMBLY
Cleaning of the blower wheel is usually the only service required. Need for cleaning is indicated if the inlet screen or blower wheel shows an accumulation of dust and lint, or if the character of the flame indicates a deficiency of air. Motor cooling air vents if present, should also be cleaned at this time.
If the motor must be replaced: Disconnect motor leads,
remove inlet ring and screen, blower wheel and the three motor mount retainer clips. Pull motor out of keyhole brackets. Remount in reverse order noting that brass flanges of rubber motor mounts are located against motor. The wheel should be located 1/4 inch inside the edge of the inlet side of the blower housing.
XI COMBINATION GAS VALVE
The 24 volt combination valve serves four functions: 1) Main Manual Gas Shut-Off, 2) Manifold gas pressure regulation, 3) Automatic electric pilot gas valve, and 4) Automatic electric redundant main gas valve. A pilot adjustment screw and filter are also included.
The pilot adjustment screw is located on the combination
valve. Remove plug for access and turn clockwise to reduce flow.
The main gas pressure regulator, which has an outlet
pressure setting range of 2.0 " to 4.0 " W.C. is factory set for a
-6-
FIGURE 8 Drawer Assembly
manifold gas pressure of 2.0" W.C. If pressure adjustment is required for setting capacity, remove regulator cap for access to slotted adjustment screw. Turning of adjustment screw counterclockwise reduces pressure; clockwise increases pressure. Do not adjust past point where no change in pressure is noted.
CAUTION: If the combination valve has been moved or replaced, soap bubble test for leaks with the burner running.
If leakage through the valve occurs, as evidenced by
presence of pilot and/or main flame on standby, the entire valve must be replaced.
NOTE: Pressure setting must be made with burner running and main gas ON.
CAUTION: If gas supply pressure is below its specified range during regulator adjustment, an overfire condition could result when pressure returns to normal, particularly if the regulator adjustment screw is bottomed out. ALWAYS confirm that at least the minimum rated gas pressure
is being supplied to the burner during regulator adjustments, and NEVER bottom out regulator screw.
The tap for manifold gas pressure measurement is located
in the Burner Inlet Block (see Figure 7 or 8). Remove plug for access.
If the gas pressure regulator fails to maintain a constant
manifold gas pressure within +
0.1" W.C., and it is confirmed that the inlet gas pressure to the combination valve is 14.0" W.C. maximum during standby, and 4.0" W.C. minimum with
XII ELECTRONIC CONTROL SYSTEM
The Electronic Control is a solid state device that automatically ignites and monitors the pilot flame. It has an integral high voltage transformer and upon a call for heat, applies high voltage to the spark electrode and 24 volts to the pilot valve. When the pilot flame is established and proven, the control powers the main automatic valve.
If the pilot flame is not proven within 90 seconds, or if the
proof of flame is lost during the burner run and the pilot is not re-established within 90 seconds, the control will shut off the combination valve and lock out. To reset the control for restart, de-energize the control by setting the operating control to OFF or thermostat below room temperature for at least 60 seconds.
If the Electronic Control is changed, the replacement must
be identical to the make and model number, or must be an authorized substitute.
the main flame on, the regulator portion of the valve is defective and entire valve must be replaced.
If, on a call for heat, the main flame ignition does not occur
even though the pilot is burning, failure of the electric main valve operator may be indicated. Refer to the trouble chart for further information.
CONSUMER INSTRUCTIONS
MAINTENANCE
Keep the area around the burner clear and free of combustible
materials, gasoline or other flammable liquids or vapors. Do not obstruct burner air openings or ventilation grilles for combustion air.
The motor features permanently lubricated ball bearings and
requires no routine oiling maintenance.
IMPORTANT: Check the burner flame periodically. A proper NATURAL gas flame will appear blue at the burner face with orange and yellow tips. A proper PROPANE gas flame will appear blue at the burner face with yellow tips. If the flame is too rich, it will appear billowy and yellow with hazy tips. If too lean, it will appear short and all blue. If the flame does not appear proper, CONTACT A QUALIFIED SERVICE TECHNICIAN FOR CLEANING AND/OR READJUSTMENT.
WARNING: If any flame is observed when the burner is on standby, or if the ignition spark or valve operator is heard to come on before the motor reaches operating speed, immediately turn off the manual gas control and burner power. A dangerous condition has developed and must be corrected. CONTACT A QUALIFIED SERVICE
WARNING: If PROPANE gas is used and the burner is located in a basement, crawl space or confining space, contact your gas supplier about installing a GAS LEAK warning device. PROPANE gas is heavier than air and can settle in low areas or confined spaces. This would create a danger of explosion or fire. If you suspect a gas leak, follow instructions on front cover of this manual.
WARNING: EXPLOSION HAZARD. CAN CAUSE SERIOUS INJURY OR DEATH. THIS DEVICE CAN MALFUNCTION IF IT GETS WET. NEVER TRY TO USE A DEVICE THAT HAS BEEN WET - REPLACE IT.
LIGHTING INSTRUCTIONS
TECHNICIAN FOR READJUSTMENT OR REPAIR
1.
SET OPERATING CONTROL TO OFF OR THERMOSTAT BELOW
2.
3.
ROOM TEMPERATURE.
4.
TURN MANUAL GAS COCK KNOB ON COMBINATION VALVE TO ON.
5.
TURN BURNER POWER ON. SET OPERATING CONTROL TO ON OR THERMOSTAT TO CALL FOR HEAT.IF THE PILOT FLAME IS NOT PROVEN WITHIN 90 SECONDS, OR IF THE PROOF OF FLAME IS LOST DURING BURNER RUN AND THE PILOT IS NOT RE-ESTABLISHED WITHIN 90 SECONDS, THE CONTROL WILL SHUT OFF COMBINATION VALVE AND LOCK OUT. TO RESET FOR RESTART, DE-ENERGIZE THE CONTROL BY
6.
SETTING THE OPERATING CONTROL TO OFF OR THERMOSTAT BELOW ROOM TEMPERATURE FOR AT LEAST 60 SECONDS.
1.
REPEAT STEP 4 FOR RESTART.
2.
TO SHUT OFF
TURN MANUAL GAS COCK KNOB ON COMBINATION VALVE TO OFF. TURN BURNER POWER OFF
1.
SHOULD OVERHEATING OF THE GAS UTILIZATION EQUIPMENT
2.
OCCUR:
.
.
-7-
TROUBLE CHART
Make sure the thermostat and operating controls are calling for heat. Defective wiring or loose connections can simulate the
component defects outlined below. Check associated wiring before replacing a component.
ELECTRICAL AND FLAME CHECKS MUST BE MADE IN THE ORDER LISTED.
Shut off the manual gas control to the gas utilization equipment. Do not shut off the control switch to the pump or blower.
I. MOTOR WILL NOT RUN OR MOTOR RUNS IN
REPEATED CYCLES.
A. Confirm 120V between strip terminals 1 and 2 and
verify the circuit polarity and electrical ground between strip terminal 1 and burner chassis metal.
B. Check 24V* operating control circuit:
1. Between left strip terminal T and GND.
a. No voltage, transformer defective. b. Very low voltage,* circuit is overloaded or
transformer defective.
2. Between right strip terminal T and GND. a. No voltage, circuit between T and T is open.
C. Confirm 120V between strip terminal 2 and motor relay
terminal 4:
1. No voltage, motor relay is defective.
2. Voltage present, motor is defective.
II. MOTOR RUNS CONTINUOUSLY, BUT NO FLAME.
A. Confirm that both Main Manual Shut-Off and
combination gas shut-off valves are in the ON position.
B. If the pilot flame is not proven within 90 seconds, or if
the proof of flame is lost during the burner run and the pilot is not re-established within 90 seconds, the Electronic Control will lock out. To reset the control for restart, de-energize the Electronic Control by setting the operating control to OFF or thermostat below room temperature for at least 60 seconds.
1. No pilot flame.
a. Check for 24V* between Electronic Control
terminal 24V and strip terminal GND. No voltage, Blower Motor Interlock Switch is defective.
C. For each of the following tests, reset the Electronic
Control per step II.B. TESTS ARE VALID ONLY
DURING THE 90 SECOND TRIAL FOR IGNITION.
1. TURN MANUAL GAS COCK KNOB OFF. Check
for 24V* between Electronic Control terminal PV and strip terminal GND. No voltage, Electronic Control is defective.
2. Check for 24V* between pilot valve terminal PV on the
combination valve and terminal strip GND. No voltage, defective valve wire harness. Voltage present, pilot valve operator is defective; replace valve.
3. Connect manometer to pilot flame gas pressure tap.
TURN MANUAL GAS COCK KNOB ON. Separate main valve wire at harness splice. During trial for pilot ignition period, check gas pressure.
a. No pressure, confirm that both Main Manual
Shut-Off and combination gas shut-off valves and pilot adjustment screw are full open. Repeat step 3, and if still no pressure, pilot valve operator is defective.
b. Pilot flame pressure is 3.0" to 4.0" W.C., continue
with step 4.
c. Refer to Standby Gas Pressure requirements in
Section IX and adjust or regulate the pilot gas pressure as indicated.
4. Check for ignition spark (spark gap is approx. 5/32
±1/32) Since this is a capacitor discharge system, observe closely when visually checking the spark as it
is faint and thread-like and may be overlooked in bright light.
a. Between Electronic Control high voltage
terminal and strip terminal GND. No spark, defective Electronic Control.
b. Check for ignition spark at electrode tip. No
spark, defective electrode or cable.
c. Check for gas flow at pilot tip. No flow, clogged
pilot spud or pilot tube.
III. FLAME ON ONLY DURING TRIAL FOR IGNITION
PERIOD.
A. With motor running and flame off, check line voltage
terminals for voltage as follows:
1. Between strip terminals 1 and 2 - 120V; voltage
OK.
2. Between strip terminals 1 and GND - 120V; ground
OK.
3. Between strip terminals 2 and GND - "0" V; no
backfeed OK.
B. Follow reset procedure as specified in step II.B.
1. Check sensor wire for continuity.
2. Separate main valve wire at harness splice. Connect DC microamp meter in series with sensor wire and Electronic Control. With pilot only burning, flame signal should not be less than 2 microamps. Adjust pilot flame gas pressure per Section IX to obtain acceptable signal and note gas pressure and resultant signal for future reference.
3. Reconnect separated main valve wire at harness. After main flame comes on, flame signal should increase. If signal does not increase, a rich flame is indicated. Refer to Table 3 for approximate air shutter and/or manifold gas pressure settings (see step VI).
C. IMPORTANT: If changes are made in the main
spud orifice size, manifold gas pressure or primary air adjustment, change the installation data tag accordingly.
IV. PILOT FLAME ON BUT NO MAIN FLAME.
A. Check for 24V* between Electronic Control terminal
MV and strip terminal GND. No voltage, Electronic Control is defective.
B. Check for 24V* between main valve terminal MV on
combination valve and strip terminal GND. No voltage, defective valve wire harness. Voltage present, main gas valve operator is defective.
V. SHORT FLAME.
A. Low gas pressure. B. Primary air adjustment open too far. C. Main spud orifice too small.
VI. LONG HAZY FLAME.
A. High gas pressure. B. Primary air adjustment closed too far. C. Dirty blower wheel. D. Main spud orifice too large.
VII. GAS FAILS TO SHUT OFF.
A. Defective combination valve.
* Normal low voltage: Burner in standby - 24V min. Burner running (main gas valve
energized) - 21V min.
-8-
Loading...