Midco G56 Service Manual

Page 1
Installation and Service Instructions
Unipower G-Series
Power Burn e r s
in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1-latest edition available from American National Standard Institute. Further reference should be made to the recommendation of your fuel supplier.
In Canada, installation must conform with local codes or in the
absence of local codes, with Installation Codes for Gas
Burning Appliances and Equipment, CGA Standard CAN/CGA 1-B-149.1 or 2. When the conversion burner is used
on a Forced Air Central Furnace, the two yellow and black warning labels in the literature envelope shall be attached in accordance with Installation Code, CGA Standard CAN/CGA 1-B149, Clause 5.4.4.4. Further reference should be made to the recommendation of your fuel supplier.
WARNING: Additions, changes, conversions and service must be performed by an authorized Midco representative, service agency or the fuel supplier. Use only MIDCO specified and approved parts.
I N S TALLER: Inform and demonstrate to the user the
correct operation and maintenance of the gas utilization equipment. Inform the user of the hazards of storing flammable liquids and vapors in the vicinity of this gas utilization equipment and remove such hazards. Affix this manual and associated literature to the conversion burner.
CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE I N S T A L L E R .
Warning: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury or death.
Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in the building.
• Immediately call your gas supplier from another building's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
BURNER MODEL
BILL OF MAT'L NUMBER
DATE CODE WIRING DIAGRAM
FOR SERVICE CONTACT:
USER: Retain this manual for future reference. If o t h e r
than routine service or maintenance as described in this manual and associated literature is required, contact a qualified service agency. DO NOT ATTEMPT REPAIRS. An inadvertent service error could result in a dangerous condition.
SAFETY INFORMATION TERMS: The following terms are used to identify hazards, safety precautions or special notations
and have standard meanings throughout this manual. When you see the safety alert symbol and one of the safety information terms as shown below, be aware of the hazard potential.
DANGER: Identifies the most serious hazards which will result in severe personal injury or death. WARNING: Signifies a hazard that could result in personal injury or death. CAUTION: Identifies unsafe practices which would result in minor personal injury or product and property damage.
Midco International Inc.
4140 West Victoria Street Chicago, Illinois 60646
name address
phone
4 0 0
8 4 4 9 - 0 6
Page 2
Part 1 Installation
Specifications
Burner Style Power Type Pilot Type Intermittent, Spark Ignition (Standard)
Interrupted, Spark Ignition (Optional) Pilot Safety Instantaneous Electronic Flame Safeguard Standard Voltage
C o n t r o l s 1 2 0 / 1 / 6 0 M o t o r 115/1/60 (except G69-115/230/1/60) U.L. Listed-U.L.C. Listed
Table 1: Burner Specifications
1. Values given based on 0" W.C. firebox pressure, altitudes to 2,000 feet. Derate burner for
altitudes over 2,000 feet by 4% for each 1,000 feet over sea level.
2. Maximum inlet pressure both gases: 14" W.C. Refer to Section VI Piping for high
pressure.
3. Modulating and two-step burners are limited to a 3 to 1 turndown ratio.
4. Manifold pressures are approximate and will vary slightly according to job condition. See
Section VII Initial Start-Up paragraph 11.
5. Pressures are based on 25% excess combustion air.
6. SCFM=Standard Cubic Feet/Minute
*1 MBH=1,000 BTU/HR.
CAUTION: Unipower G-Series are not intended for outdoor installation and must be protected from excessive moisture. Provide adequate clearance for service and proper o p e r a t i o n .
■■
Open basements will generally allow sufficient air infiltration, so special provisions will seldom be
required. If the heating plant is located in a separate furnace room or in an unusually tight basement, permanent means must be provided to supply an ample volume of fresh air for combustion and boiler room ventilation. A direct opening to the outside air should be provided sized on the basis of 1/2 square foot of free opening for each 1,000,000 BTU of burner rating when the vent connector is equipped
I Ventilation
Natural Gas
(1,000
BTU/cu.ft.)
G56 G57 G58 G69
G56P G57P G58P G69P
1075 1500 1850 2500
224 313 385 521
5.0" W.C.
7.0" W.C.
6.7" W.C.
7.5" W.C.
5.0" W.C.
5.0" W.C.
6.0" W.C.
8.0" W.C.
Propane Gas
(2,500
BTU/cu.ft.) Natural Propane
Maximum
Input
1
MBTU/HR.*
Maximum
Air
SCFM
6
Model
Inlet Gas Pressure
Required
2
Natural Gas
(1,000
BTU/cu.ft.)
G56 G57 G58 G69
G56P G57P G58P G69P
300 300 500 800
1
/6
1
/3
1
/2
3
/4
2.2" W.C.
4.1" W.C.
4.6" W.C.
4.2" W.C.
1.2" W.C.
2.6" W.C.
3.8" W.C.
3.3" W.C.
Propane Gas
(2,500
BTU/cu.ft.) Natural Propane
Minimum
Input
3
MBTU/HR.*
Motor HP
(3450 RPM)
42" x 18" 48" x 21" 50" x 24" 60" x 27"
Recommended
Combustion
Chamber
Size
Model
Burner Manifold
Pressure
1,4,5
Model
G56 G57 G58 G69
300 300 500 800
1075 1500 1850 2500
950 1400 1750 2375
875 1325 1650 2275
0.7
0.8
1.0
1.0
700 1325 1400 2100
Maximum Capacity in MBH at
Combination Chamber-
Back Pressure
0" W.C. .25" W.C. .50" W.C.
Minimum
Firing
Rate
MBH*
Maximum
Back
Pressure
in " W.C.
Maximum
MBH* at
Maximum
B.P.
Table 2: Maximum Capacity at Specified Back Pressures
Page 3
I Ventilation
Figure 2: Typical Floor and Wall Construction
For 275,000 BTU Per Square Foot
II Gas Utilization
Equipment
III Combustion Chamber
Continued
with a barometric draft control, 11/2 square feet when equipped with a draft hood. If the ventilation opening is screened, it should be of 1
ground level to prevent accidental obstruction. If a direct opening to the outside air is not available, an amply sized air duct can be run to the nearest outside air source or if practical, open stairwells or building corridors connecting to an outside wall having a ventilating opening can be used for this purpose, provided that no possibility of accidental closure exists.
While the spark ignition pilot system performs successfully under moderate or momentary back draft
conditions, it is not intended for operation under sustained reverse draft, for example, in a building with large ventilating fans but with insufficient make-up air. Even if burner operation is successful under these conditions, they must be corrected to prevent the hazard of drawing flue gases into the building. Consult your local gas company when doubt exists concerning boiler room ventilation.
The heating system, both the gas utilization equipment and the distribution system, should be in
good repair and sufficient to properly heat the building. It should be determined if any serious faults are present that would cause excessive fuel consumption, unsafe operation or improper heating, and measures taken to correct them.
After the grates and grate operating parts have been removed from the firebox, the boiler interior
should be thoroughly cleaned, removing all adhering dirt, tars, scale and soot. All joints should be cemented to prevent excess air infiltration into the boiler. Clean out doors should be checked for close fit, and sealed with furnace cement if they fit poorly.
Firing door catches should be filed off or otherwise arranged so that the door will open easily to
relieve pressure. No positive catches should be used. The use of a spring-type door holder is r e c o m m e n d e d .
The Unipower gas burner is designed for "in-shot" firing. It can be fired into the ashpit of a boiler
designed for solid fuels, or it can be fired into the primary heat exchanger of a boiler designed for liquid or gaseous fuels. The ashpit installation requires a refractory lining.
The combustion chamber serves to contain and promote combustion and to protect non-heat
exchange surfaces from direct flame contact. Built-up combustion chambers should be made of 2600° insulating firebrick. As an alternative, a monolithic floor can be cast in place, using a high temperature (2400°) light weight insulating refractory. Check with your supplier to determine the thickness which will yield equivalent insulating qualities.
1
/4" mesh. The opening should be located at least six feet over
Figure 1: Typical Floor and Wall Construction
For 225,000 BTU Per Square Foot (Standard)
Page 4
III Combustion Chamber
Continued
Figure 3: Typical Floor and Wall Construction For 350,000 BTU Per Square Foot (Maximum)
The top of the combustion chamber should be positioned 2" to 6" above the base of the heat
exchanger. If the combustion chamber is to be set directly on the floor, provide a minimum of insulating millboard or magnesia block underlay for floor protection. Use high temperature fill such as vermiculite in voids around the combustion chamber. Any portion of the heat exchanger not exposed to circulating air of water should be covered with insulating firebrick.
The combustion chamber sizes given in Table 1 are based on the maximum rated burner capacity. If
the input is to be permanently set at a reduced rate the combustion chamber floor area can be reduced proportionately to the proposed input, with the length as closely proportioned to twice the width as p o s s i b l e .
Where recommended size combustion chambers (225,000 BTU/sq. ft.) can be accommodated, the
type of construction shown in Figure 1 should be used. If lack of space prohibits use of this construction, higher BTU values per square foot can be allowed for by using the constructions shown in Figures 2 and 3 .
The back wall of the combustion chamber should be carried 2 or 3 courses higher and overhung to
deflect the flames from direct impingement on the rear heat exchanger surface. Hard firebrick should be used to prevent erosion of the brick by high velocity gases.
The burner is equipped with a mounting flange for direct attachment to the boiler front, and
mounting brackets for legs. Use both if necessary for rigid installation. The burner nozzle must not extend into the combustion chamber. It should be sealed into the opening as shown in Figure 4.
WARNING: Burner cabinet must be mounted in orientation in Figures 4 and 7. Any other mountings may cause a dangerous condition, and will void burner warranty and agency approvals. Non-standard arrangements may be available for some models. Consult factory for details if required.
The refractory lined combustion chamber can be omitted in "Scotch Marine" and "Steam
Generator" boilers or warm air furnaces that do not include ashpits.The burner is fired directly into the heat exchanger, requiring no refractory unless the combustion chamber is so short that flame would impinge excessively on the rear heat exchanger wall (this is particularly important in a warm air furnace). Refractory protection is recommended if the length of the primary chamber is less than 20% larger than
the length given in Table 1. In any case, the burner entry wall must be refractory lined if it is not a heat exchanger surface.
Firing Door Installations
It is advantageous, on
■■
occasion, to fire through the boiler firing door. For example, pitting can be avoided on low base boilers, damage to the burner can be avoided if basement flooding is prevalent or the combustion chamber volume can be reduced in boilers with unusually large
Figure 4: Construction at Burner Entrance
required for firing door applications since flame impingement on boiler surfaces is more probable. Do not fire a boiler containing a drop section directly in the path of the flame, or over the water grate in a smokeless type boiler. The firebox length must be great enough to exceed the combustion chamber lengths given in Table 1 by at least 20%.
a s h p i t s .
Great care in planning will be
1
/2"
Page 5
III Combustion Chamber
Figure 5: Conventional Boiler-Small Firebox
Figure 7: Tubular Combustion Chambers
Continued
When raising the floor,
maintain sufficient firebox volume to limit the heat release to 50,000 BTU per hour per cubic foot or less. Use the entire floor as a combustion chamber and cover the water leg base to 6" from the bottom. Floor construction should conform to Figures 1, 2 or 3.
Firing door installations will
usually entail removal of the grates. Figure 8 shows a typical installation. A steel plate floor can be supported from the grate lugs, if suitable. In any case, the floor must be rigid enough to prevent sagging,
Figure 6: Conventional Boiler-Large Firebox
a leveling surface of sand. The external stoker parts should be removed to eliminate clutter under the b u r n e r .
The burner mounting in the door must be rigid and refractory lined as shown in Figure 8. The burner
nozzle must not protrude directly into the combustion chamber. The refractory liner must be flush with or extend beyond the burner face as shown in Figure 4. A sheet metal rim should encase the refractory up to the inside of the boiler wall. It should be intermittently bent inward to retain the refractory or other means of anchoring should be provided.
being supported by brick piers as necessary.
If firing over the grate, level it
off with rubble of common brick or firebrick if necessary; then cover over with insulating block before laying the refractory floor.
The hearth of worm feed
stokers can be used as a floor base. Level off the hearth to a suitable height, remove worm feed mechanism and fill the tuyere with rubble. Cover at least the tuyere area with block insulation; if using castable refractory, pour a new floor over
As an alternate, the burner mounting plate can be extended externally to locate the nozzle face and
refractoy wholly within the door opening. Seal carefully to prevent flue products from entering the boiler r o o m .
In double door boilers it is recommended that the openings be enlarged to a single opening by
removing the center post so that the burner can fire in the center. If a pressure part of the boiler must be cut away, be sure to make modifications in accordance with your local code covering boiler repairs.
Since firing door installations will generally leave no openings for flame observation, a peep sight
Page 6
III Combustion Chamber
Continued
Figure 8: Firing Door Installation in Three Pass Boiler
IV Chimney, Vent Connector
and Draft Control
WARNING: The chimney shall be inspected for unsafe conditions such as deteriorated masonry and excessive soot or other blockage or potential blockage. Installation must conform with local codes or in the absence of local codes with NFPA, ANSI Z223.1-latest e d i t i o n .
WARNING: No movable vent connector damper is permitted on any gas conversion installation. The chimney should be inspected for unsafe conditions such as deteriorated masonry and excessive soot or other blockage or potential blockage. Check your local authorities for regulations covering barometric draft regulators on gas equipment.
WARNING: The vent connector shall not be connected to a chimney already venting solid fuel burning equipment, an incinerator or an open fire place.
The Unipower burner does not depend on chimney draft. Combustion air is supplied by the forced air
blower, which is sufficient to supply adequate air for any normal boiler. This reduces the function of the chimney to removal of flue products from the boiler. A chimney height of 15' above the boiler flue outlet will generally prove ample if the recommended or larger vent connector and chimney diameters are used. The chimney must of course, extend several feet over the roof of the building, or adjacent buildings. Vent connector material should be 24 gauge or heavier steel, galvanized to resist corrosion. The horizontal run of vent connector should be pitched upward from the appliance flue outlet at least
1
/4" to the foot. Avoid excess elbows or other constructional features that would create excessive resistance to flow of flue products. Fasten joints with sheet metal screws to prevent sagging. The vent connector should be maintained at least 6" from combustible building materials; more if it is uninsulated. Where it passes through partitions constructed of combustible materials a ventilated thimble should be used. Refer to your local building codes. The vent connector should be firmly
cemented into the chimney but must not extend beyond the inner face. Where two or more appliances use the same chimney, be sure not to enter the chimney with both flue pipes at the same l e v e l .
Do not arbitrarily reduce the
vent connector size, since a boiler back pressure can build up, leading to possible leakage of flue products into the boiler room.
Chimney construction can be
either of brick, preferably tile lined, or of steel. Joints in the chimney should be smooth and leak free to prevent uncontrollable air infiltration. They should be made so that condensation if any, will
Figure 9: Recommended Locations for Draft Hoods
If the vent connector must be extra long, the area of the pipe and chimney should be increased or
the chimney height must be increased, or both. Never allow the horizontal length of the vent connector to exceed the height of the chimney.
not collect in the joints or leak to the outside.
Page 7
Two kinds of draft control are acceptable;
an A.G.A. type draft hood as illustrated in Figure 9, or a barometric damper as shown in Figure 10. Use of a draft hood is usually limited to burners with lower range capacities, while a barometric draft control is suitable for all capacities. Application should depend on the requirements of the installation.
If a draft hood is used, it should be of the
same size as the vent connector and should be located higher than the highest part of the heating appliance flue passage.
If a barometric damper is used, it should be
of the double-swing type, which opens freely outward to afford downdraft protection irrespective of settings made to the balancing weights for updraft control. The damper should be located so it is free to swing without interference from surrounding objects so that the velocity pressure of the
flue gases does not interfere with its operation. See Figure 10 for proper installation.
When any vent connector passes through a partition the draft control must be located in the same
room as the heating appliance. A device which will automatically shut off gas to the burner in the event of sustained backdraft is recommended if such backdraft might adversely affect burner operation or if flue gas spillage might introduce a hazard. If such a device is used, it shall be of the listed type and installed and adjusted by a qualified service technician in accordance with the manufacturer's i n s t r u c t i o n s .
The burner when installed, must be wired and grounded in accordance with local codes or in the
absence of local codes, with the National Electric Code ANSI/NFPA No. 70-latest edition. In Canada, refer to CSA Standard C22.1, "Canadian Electrical Code Part 1".
C A U T I O N : Refer to the separate wiring diagram included with each burner.
When wiring, be sure that the electrical power take-off is connected to a permanently live circuit and
use multiple 14 gage copper wire conductors. Provide a fused disconnect switch in the burner circuit. Each installation must include a limit control to guard against excess temperature or steam pressure. Steam or vapor systems will require a low water cut-off.
■■
For the usual low pressure gas supply system, 5" to 14" W.C. NATURAL (11" to 14" W.C. PROPANE)
use Table 3 to find the recommended gas supply line size.
Piping follows normal practices and should be connected to the burner in the manner shown in
Figure 11. If the piping must be rearranged because of space limitations be sure to carry out the sequence of components illustrated. While the pilot regulator can be mounted in any position, the main regulator should be mounted upright and in a horizontal run of pipe.
Run full size pipe or tubing from regulator vent openings to outside of building. Provide no traps in
the vent lines and terminate away from all doors and windows; also make provisions for keeping rain and foreign objects from entering the vent piping.
V Electrical
Figure 10: Location for Barometric
Barometric Dampers
Figures 9 and 10: Copyright by the
American Gas Association.
Used by permission of the copyright holder.
VI Piping
Figure 11: Piping Connections
Page 8
VI Piping Continued.
When high supply gas pressure is encountered, as in the case in many industrial plants, the gas line
size can be reduced to allow for a greater pressure drop; however, the size must be sufficient to deliver necessary burner gas pressure.
CAUTION: High gas pressure supply lines require the proper pressure reducing regulators. Install two separate high pressure regulators, of the Tight Shut-Off type upstream of the low pressure regulators. One sized for main gas input, and one suitable for the minimum flow regulating capacity of the pilot.
The high pressure regulators may be substituted for the low pressure regulators. If high pressure
regulators are used as substitutes, they must be adjustable down to a minimum of 2" W.C. outlet pressure for the pilot and 5" W.C. for the main gas. They must be adjustable down to the maximum burner inlet pressure rating (14" W.C.).
DANGER: Explosion hazard.
Do not use oxygen for pressure testing. An
explosion could occur during initial start-up.
When the gas supply line is about to be put into service it must be tested to insure that it is gas tight.
Use air or inert gas under pressure and test with soap and water or other liquids to locate leaks.
CAUTION: Because it is difficult to accurately control pressure, disconnect all low pressure (14" W.C. max.)components (main and pilot) during supply pipe leak testing. Exposing low pressure regulators and valves to a pressure over 1/2 PSIG (14" W.C.) will damage components and void their warranties.
Gas Supply
Pipe Size
N.P.T.
1"
11/4"
11/2"
2"
21/2"
3
Type
of
Gas 20
Natural
Propane
Natural
Propane
Natural
Propane
Natural
Propane
Natural
Propane
Natural
Propane
Approximate Capacity-MBH
Length of Pipe-Feet
40
60
350 550
730
1150 1100
1730
2100 2500
2500
385 500
785 760
1200 1450
2280 2300
2500 2500
300 400
630 610
960
1150 1800
1850 2500
2500
100
300 480
460 725
870
1370 1400
2200 2500
2500
200
330 320
500 610
960 980
1550 1700
2500
Source: Gas Engineers Handbook—1974
Table 3: Schedule 40 Pipe Capacity Chart
line at this step will expedite the first light-off.
CAUTION: Purge outside the building. Do not purge into the gas utilization equipment combustion chamber.
CAUTION: Do not exceed maximum rated capacity of burner model-See Tables 1 and 2 .
Capacities shown are for total pressure drop of .3" W.C. For higher permissible pressure drops consult your fuel supplier.
Before gas is introduced
to the system, a check must be made to see that there are no open fittings and to make sure the burner main and pilot manual valves are closed. After checking above, purge the gas line up to the burner inlet. Purging the air from the gas supply
VII Initial Start-Up
WARNING: Repeated unsuccessful attempts to light may result in accumulated gases in gas utilization equipment and chimney. To prevent these gases from reaching an explosive level, periodically purge the gas utilization equipment.
CAUTION: All cover plates, guards, and enclosures must be maintained in place at all times except during maintenance and servicing.
CAUTION: Optional equipment and/or special limit controls such as high/low gas pressure switches can alter the start-up procedure. See Section XIV Special Equipment.
1 . Check the piping for leaks. A quick way to do this is to close the Main Manual Shut-off Valve and
manual pilot valve, then turn on the gas pressure to the gas supply line and observe the meter test
dial. There should be no movement of the test dial hand for at least twenty minutes. All other gas
appliances must be completely shut off during this test (including pilots). If a leak is detected it
should be located with a soap suds test. Test the main automatic valve for tightness. See Section
XII Main Automatic Valves for instructions. The ball valve is intended to be open at all times
except when testing for main valve leakage. The Main Manual Shut-Off Valve must be used for
manual gas shut-off. 2 . Make sure that the burner main and pilot gas lines are completely purged of air. Do not purge into
the combustion chamber. Purge outside the building. 3 . Make sure the burner power switch is off, manual valve is closed, pilot manual valve is closed,
motor is free to rotate, and flame safeguard reset button is set. 4 . Make the proper settings on all limit controls and set controller to call for heat.
Page 9
VII Initial Start-Up
Continued
5 . Set blower air shutter wide open. On 2-Step and Modulating burners, disconnect air shutter
connecting rod at blower shutter shaft, and lock shutter wide open. 6 . Turn on the line switch, and allow motor to run through the pre-purge and ignition cycle. Check
the blower wheel for proper rotation. Viewing from the motor shaft end (Blower Inlet side),
rotation should be counter clockwise. After a short run, the flame safeguard will lock out, stopping
the motor. Wait one minute, then reset the flame safeguard. 7 . Turn on pilot manual valve. With Main Manual Shut-Off Valve still closed, turn on main line switch.
Motor will start. When pre-purge period has elapsed, flame safeguard will energize pilot solenoid
valve and spark generator. When flamerod senses pilot flame, the flame safeguard will energize
the main valves. No main flame will occur due to closed Main Manual Shut-Off Valve. Quickly
observe pilot flame, if no flame or if weak, screw in pilot regulator adjustment. If the flame is rich
and floating from the pilot tip, back off the pilot regulator. Set to achieve the largest stable blue
flame with a base that burns firmly within the pilot tip. The best operating pressure is usually 3
to 4" W.C. Test for ignition and stability several times, cycling the burner with both open and
closed air shutter. Ignition and relay response will be prompt with a good flame. Check flame
signal with a DC voltmeter. Pilot should be set to yield the highest steady reading, at least 2 volts
DC and as high as 5 volts. Plug-in jacks are provided in the amplifier section of the flame safeguard
for voltmeter connection. 8 . Check operation of the electronic flame detection circuit by turning off the pilot manual valve with
pilot burning and Main Manual Shut-Off Valve still closed. The circuit to the main automatic valve
should be broken when the pilot goes out. * 9 . Turn off line switch to stop the burner. Rest flame safeguard. Set blower air shutter about
open. With On-Off and 2-Step burners, loosen gland nut on Butterfly Valve and temporarily lock air
shutter wide open (slot in shaft parallel to flow). On modulating burners, remove wires of
modulating controller from "B" and "W" terminals on the modulating motor. Jumper terminals
"R-B" to drive input adjuster to high fire position when energized. The high fire adjustment screw
on the input adjuster should be backed off to the wide open position. On 2-Step burners, jumper
terminals "3-4" on valve actuator so valve will open to high fire position when energized. 1 0 . Turn on main line switch. After the main valve is energized, slowly open Main Manual Shut-Off
Valve until the main flame ignites. Then opening the air shutter as required to maintain a suitable
flame, slowly open the Main Manual Shut-Off Valve to the wide open position or until, with the air
shutter wide open, the main flame becomes excessively rich.
3600 x test dial size x BTU value
no. of seconds for one rev. test dial
= BTU/HR.
1
/2"
1
/4
Then divide by 1,000 for MBH value. Example: 3600 x 1 x 1000
5
= 720,000 BTU/HR.=720 MBH
For Propane gas, consult your supplier for method of determining firing rate.
* 1 1 . The manifold pressures shown in Tables 1 and 5 may be used to determine the approximate gas
input settings. The gas input for Natural gas models can be determined by timing the gas meter.
Accurately time test dial for the number of seconds for one revolution and use the following
formula. All other gas utilization equipment must be off.
CAUTION: The manifold pressures shown in tables are both the blower air pressure and the gas pressure. Air shutter adjustments will effect manifold pressure and i n p u t .
The effective gas pressure is the difference between the total pressure which registers when the
gas valve is closed. Clock the meter gas rate and (if necessary) reset the main regulator to control
gas flow at about 10% over burner rating or over desired input with Main Manual Shut-Off Valve
wide open. Turning the adjustment screw clockwise on main regulator increases pressure and flow
rate, reverse decreases. Do not adjust the regulator past the point where no further change in gas
flow is noted. For On-Off and 2-Step burners, "close" off Butterfly Valve to the desired maximum
input rate, secure gland nut, and replace cap. For Modulating burners, screw in the high fire
adjustment screw on the input adjuster to set the maximum firing rate. Reset the blower air shutter
to provide fairly long flame, blue at the burner face, orange or red at the tips. Flashes of yellow
may be visible. Close firing door for a few seconds; then open and quickly observe fire. If a purple
haze is noted at the rear of the firebox, lack of air is indicated and air shutter should be opened
wider. Refer to Table 1 if the manifold pressure is to be used as a guide to gas input. 1 2 . Check the flue gas temperature at the boiler flue outlet. It should be above 325° but not exceeding
550°. Excessive flue temperatures result in low efficiencies. Low flue gas temperatures may cause
excessive condensation. Reset input if necessary to adjust stack temperature; or if temperature is
too low, portions of the heat exchanger surface can be blocked off with insulating firebrick. 1 3 . Make the final setting of the air shutter by checking the flue gases with an "Orsat" or similar
combustion testing instrument. There should be no carbon monoxide and the carbon dioxide
content should be approximately 9.5% for NATURAL and 12.1% for PROPANE, or within the
limits prescribed by the local fuel supplier.
Page 10
VII Initial Start -Up
Continued
1 4 . Check the draft control to make sure there is no spillage of flue products into the boiler room. This
test is should be performed under the most severe possible ventilating conditions. For example,
perform this test with all doors and windows tightly shut and any ventilating fans in the building
o p e r a t i n g . 1 5 . Start and stop the burner several times with the controller and the limit controls to check
their operation. 1 6 . Reset controller and limits controls to their desired settings. Replace wires and remove jumper on
Modulating or 2-Step burners. * Refer to trouble chart.
Low Fire Adjustment:
2-Step Burners
With damper arm type motorized main automatic valves, see Figure 12.
1 . With the burner power off, remove jumper from terminals "3-4" of fluid power actuator, and
remove wire of the high/low controller from terminal 4 of the actuator. The actuator is factory set
to a maximum low fire input of 50% of the high fire setting. Check to make sure the low fire
adjustment cam (located in the lower left hand corner of the actuator wiring compartment) is set
at MAX. 2 . Lock blower shutter
the cam with the special wrench taped to the inside of the actuator wiring compartment cover.
Keeping the wrench seated in the setscrew, rotate the cam slightly downward toward the base of
the actuator. Actuator will start to close. 3 . When the actuator reaches approximately the desired low fire position, quickly tighten the setscrew
and remove the wrench. Determine the gas input for the low fire setting by timing the meter gas
rate and reset blower shutter to achieve a stable flame as described in paragraph 11. Do not allow
input to fall below one-third of the high fire input rate or the recommended minimum input as
shown in Table 1, whichever is higher. If further adjustments are required, raise or lower the cam
and adjust the blower air shutter until a satisfactory flame is reached. Check combustion per
paragraph 13, page 9, and mark the position of the low fire shutter setting with a pencil or scratch
mark on the blower housing. 4 . Reconnect the blower air shutter connecting rod to the blower air shutter shaft. Turn burner off
1
/2 open, start the burner and establish the main flame. Loosen the setscrew in
Low Fire Adjustment:
Modulating or Optional
2-Step Burners
Figure 12: Damper Arm Type Motorized Main Automatic Valve Linkage
and, operating linkages manually, adjust to index marked air shutter positions with high and low
positions of the main automatic valve. Cycle the burner several times with the on-off controller to
assure proper operation and correct linkage of the air shutter connecting rod. Conclude start-up
procedure per paragraph 14.
With motorized input adjuster, see Figure 13.
1 . Screw in low fire adjustment screw on
input adjuster as far as it will go. With
burner power off, transfer jumper from
Figure 13: Motorized Input Adjuster Linkage
terminals "R-B" to "R-W" and lock the blower shutter about
2 . Start the burner and establish the main
burner flame. Back off the low fire adjustment screw on the input adjuster until the flame reaches the approximate desired low fire position. Determine the gas input for the low fire setting by timing the meter gas rate and reset blower shutter to achieve a stable flame as described in paragraph 12. Do not allow input to fall below one-third of the high
1
/2 o p e n .
Page 11
fire input rate or the recommended minimum input as shown in Table 1, whichever is higher. If further adjustments are required, screw in or back off the low fire adjustment screw and adjust the air shutter until a satisfactory flame is achieved. Check combustion per paragraph 13, page 9, and mark the position of the low fire shutter setting with a pencil or scratch mark on the blower housing.
3 . With burner switch off, remove jumper from modulating motor terminals "R-W" and reconnect
controller wires to terminals "B" and "W". Reconnect the air shutter connecting rod. Operating linkage manually, adjust to index marker air shutter positions with high and low positions of the input adjuster.
4 . Restart the burner and cycle it several times using the modulating control and the on-off control to
assure proper operation and correct linkage of the air shutter connecting rod. Conclude start-up procedure per paragraph 15.
After the initial start-up procedure, the following steps can be followed for routine start-up and shut­down on a seasonal or extended basis.
This table is provided as a guide to use the INPUT ADJUSTING METHOD to approximate final settings. The valve train M U S T be tested for tightness and the pilot adjusted for proper operation before proceeding. Refer to Section VIII Burner Box and Firing Head of the this manual.
1 . Install a Manometer (not a
pressure gauge) in the manifold pressure tap.
2 . Close the Main Manual Gas
V a l v e .
3 . Close the Input Adjuster
(butterfly valve). 4 . Turn the burner on. 5 . Adjust the air shutter to the "Air
Only" pressure shown for the
desired MBH. 6 . Open the Main Manaual Gas
V a l v e . 7 . Slowly open the Input Adjuster
until the observed manifold
pressure equals the Gas On
pressure for the desired MBH. 8 . Take combustion readings and
confirm the input rate by
clocking the gas meter. 9 . Adjust the air shutter and/or the
Input Adjuster as needed. 1 0 . Repeat steps 8 and 9 until you
have the desired input rate with
clean combustion**. 1 1 .Refer to section VIII Burner Box
and Firing Head of this manual
for final Main Gas Regulator
adjustment procedures. For capacities not shown:
P
2
= P
1
x (
M B H
2 M B H
1
)
2
*1 MBH=1000 BTU/HR.
ALL FIGURES ARE APPROXIMATE. Actual figures will vary depending upon application and ambient conditions. Based on 0 pressure over the fire at Standard Air and S p e c i f i c G r a v i t i e sof .64 for NATURAL GAS,
and 1.52 for PROPANE GAS. It is the responsibility of the installer to make final adjustments to insure proper and safe operating conditions, and to comply with all codes and guidelines that may apply at the installation site. Contact the local Utility for any requirements and recommendations
they may have. In the absence of any local codes, guidelines or requirements,
Model
Capacity
MBH*
Air
Only Natural Propane
Manifold Pressures ("W.C.)
Gas On
G56
G57
G58
G69
1075 1000
900 800 700 600 500
300 1500 1300 1200
1000
900
700
600
300
1850 1700 1600 1500 1200 1000
800
500
2500 2200 2000 1800 1500 1200 1000
800
1.00
0.87
0.70
0.55
0.42
0.31
0.22
0.08
1.90
1.43
1.22
0.84
0.68
0.41
0.30
0.08
2.65
2.24
1.98
1.74
1.11
0.77
0.50
0.19
2.25
1.74
1.44
1.17
0.81
0.52
0.36
0.23
2.10
1.82
1.47
1.16
0.89
0.65
0.45
0.16
4.10
3.08
2.62
1.82
1.48
0.89
0.66
0.16
4.60
3.88
3.44
3.02
1.94
1.34
0.86
0.34
4.15
3.21
2.66
2.15
1.49
0.96
0.66
0.42
1.45
1.25
1.01
0.80
0.61
0.45
0.31
0.11
2.79
2.10
1.79
1.24
1.01
0.61
0.45
0.11
3.75
3.17
2.80
2.47
1.58
1.10
0.70
0.27
3.65
2.83
2.34
1.89
1.31
0.84
0.58
0.37
Table 4: Approximate G-Series Capacities at
Burner Start Up
1 . Make sure line switch is off 2 . Set controller to call for heat 3 . Open firing door 4 . Open Main and Pilot Manual Valves 5 . Reset flame safeguard 6 . Turn on line switch 7 . Close firing door after main flame ignites 8 . Reset control to desired setting
Burner Shut down
1 . Turn off main line switch 2 . Close Main Manual Valve 3 . Close pilot manual
Page 12
Part 2 Service
VIII Burner Box
and Firing Head
IX Pilot and Flame Sensor
CAUTION: Be sure that the Main Manual Shut-off, Manual Pilot Valve and Disconnect
Burner Switch are off before removing any parts for service.
CAUTION: Cover plates, guards and enclosures must be in place at all times except during
maintenance and service.
The Unipower burner head is of the nozzle mixing (non-premix) flame retention type. This design
accommodates a high capacity without flame lift off and a low capacity without flash back.
The burner box serves as an air plenum chamber and a frame to which all other parts are assembled.
Blower air enters the box and passes around the outside of the gas manifold and through the retention plate. Gas passes through ports in the manifold, then through the retention plate where it is mixed with the blower air by turbulence caused by the retention plate and into the combustion chamber for burning. The gas ports are not adjustable. Variation in capacity is accomplished by a variation in gas p r e s s u r e .
Maintenance of the burner box and firing head is minimal, due to the simplicity of the parts and
absence of small air or gas passages. An occasional inspection of the parts in contact with the flame will suffice. The flame retention plate must show no loss of metal or severe warping. If the heads of the retention plate mounting screws show loss of metal they must be replaced. Use only stainless steel s c r e w s .
Stainless nozzle sleeve must extend at least
If the burner mounting flange or adjacent furnace wall show signs of overheating, check the
tightness of the burner mounting. The burner is intended to be sealed into the boiler opening both at the face and at the mounting flange as shown in Figure 4, to prevent blow-back of hot flue products around the nozzle and flange.
The pilot is of the premix, blast type. Blower air is diverted from the blower housing through an air
orifice into the pilot mixing tee mounted on the burner back plate, where the proper amount of gas is added through the pilot orifice. Both orifices are located at the end of their own respective tubes in brass fittings leading into the mixing tee. The gas/air mixture is then discharged through the heat resistant alloy flame retention pilot tip.
The spark rod is located on the center line of the pilot and is arranged to arc to the inside of the central port. Spark current is supplied by a spark generator to ignite pilot gas.
The pilot regulator is factory set for an outlet pressure of about 3
PROPANE, which will be suitable for average conditions. Pressure can be varied to suit particular job conditions. Do not increase orifice sizes indiscriminately. Pilot troubles may be introduced by causing the pilot to float and lose contact with the flamerod or flame grounding area. Adjust the pilot per paragraph 7 of Section VII Initial Start-Up.
Service of the pilot will generally consist only of inspection and cleaning. Check that the pilot tip
ports, air tube and mixing tee are free of lint and dirt and that the pilot tip is free of corrosion. Make
1
/2" beyond flame retention plate.
Wire Drill Sizes
Approx.
Capacity
3500 3500 5000
5000
Burner Air
G56 G57 G58
G69
#26
(.147)
#30
(.128)
#26
(.147)
#26
(.147)
Natural
Pilot
Orifice
#60
(.040)
#60
(.040)
#55
(.052)
#55
(.052)
Propane
Pilot
Orifice
#64
(.036)
#64
(.036)
#56
(.046)
#56
(.046)
Table 5: Pilot Specifications
is made of heat resistant alloy, it may eventually deteriorate at the point of flame contact and should be replaced if it is seriously corroded. See Figure 14 for the proper alignment of the flamerod. DO NOT BEND FLAMEROD TO REDUCE THE DISTANCE FROM THE PILOT TIP.
1
/2" W.C. for NATURAL gas and
sure that the air tube is re-inserted into the blower housing pilot air tube hole. The spark insulator and cable must be clean, dray and free from cracks and abrasions. Make spark gap settings per Figure 14.
Proper operation of the flame
safeguard depends on a reliable current flow through the flamerod, pilot flame and the flame grounding area. The flamerod must be free of any contact with conductive burner parts. The insulator must be clean, dry and free of cracks. While the rod
X Blower and Motor
The blower functions to supply a constant and positive supply of air for complete combustion. Air
volume is controlled by an adjustable shutter in the blower outlet. A small supply of air is diverted ahead of the shutter for the pilot and for operation of the blower air proving switch.
No routine service is necessary on the blower other than an occasional cleaning the blower wheel. If
the blower wheel must be replaced, be sure to check the replacement for proper rotation. The concave sides of the blades must face the blower outlet, and rotation of the wheel must be toward the outlet. See Section VII Initial Start-Up, page 8 paragraph 6. Motor sizes and specifications are given in Table 1.
3
The
/4 HP single phase motor used on the G69 burner uses a motor switching relay to handle the motor load. All motors contain integral motor overload protection, usually manual, occasionally automatic reset.
Page 13
X Blower and Motor
Proof of blower operation is provided by the diaphragm air switch, which must close its contacts and
maintain them closed when the blower is running. In case of malfunction, the air switch should be r e p l a c e d .
The gas pressure regulator is used to automatically reduce and maintain constant gas pressure to the
burner. To vary the outlet pressure, remove the seal cap for access to the adjusting screw. Turning the screw clockwise will increase outlet pressure, counter-clockwise will decrease outlet pressure.
Maximum and minimum allowable gas pressures are shown in Table 1. Because these regulators are
of the low pressure type with metal seats, leakage through the seat will cause outlet pressure to rise equal to inlet pressure during burner shutdown. Therefore do not subject the burner to inlet pressures above those listed (14" W.C.). For higher inlet pressure, See Section VI P i p i n g for instruction on installing alternate regulators.
The vent in the upper diaphragm case normally breathes air but should be vented to the outside for
protection in the event of a punctured diaphragm. See Section VI P i p i n g for proper venting procedures. Never connect the regulator to the diaphragm valve vent.
When the regulator is to be installed or replaced, take care not to distort the body casting. Apply
wrench only to the heavy body section adjacent to the pipe thread. N o t e : All burners are equipped with dual valves. Select the type you have and reference. Burner
construction for special codes and/or insurance requirements such as Factory Mutual or Industrial Risk Insurers may require alternate construction. (Refer to Section XIV Special Equipment.)
Employed with Redundant Solenoid Valve.
The Honeywell V48A diaphragm valve supplied on standard On-Off and Full Modulating Unipower
burners is of the slow opening, fast closing type and requires venting to the bleed connection on the burner box. Closing force combines a gas pressure differential, diaphragm weight and spring.
When the controller is not calling for heat, the coil is de-energized. The plunger of the three way
actuator is in the down position, so that the bleed is closed and the supply port is open. Gas flows to the top diaphragm, causing the gas pressure and spring to hold the valve closed.
With a call for heat, the flame safeguard energizes the coil. This pulls the plunger to the up position,
opening the bleed valve and closing the supply port. The gas then bleeds off the top of the diaphragm, allowing the gas pressure below to lift the diaphragm, allowing the gas pressure below to lift the diaphragm and open the valve. When all the gas has bled off the top of the diaphragm, the valve is fully opened. In the event of a power failure during operation, the valve will close. Normal operation will resume upon restoration of power.
For general service, tests for gas tightness and proper operation will suffice. If leakage is observed,
replace valve. If the valve will not open, make sure that normal gas pressure is available at the valve, the bleed line is unobstructed and power is available at the terminals.
If the valve fails to close, make sure power is off at the terminals and gas flow is in the direction of
the arrow on the valve body. When a malfunction is found to be caused by the valve operator head, the entire valve must be replaced.
If the valve will not open, make sure normal gas pressure is available at the valve, the bleed line is
unobstructed, and power is available at the terminals.
Employed with Redundant Solenoid Valve, or Second Motorized Valve.
Motorized Main On-Off Valves are available on special order. A 2-Step actuator combined with a
characterized guide is standard on 2-Step Unipower burners.
When the actuator is energized, hydraulic fluid is pumped from a reservoir to a metal bellows. The
bellows transfers the resulting pressure through the drive stem to open the valve. A separate spring return drive arm operates the blower shutter if burner is supplied as On-Off, Low Fire Start, or as a 2-
Continued
XI Gas Pressure Regulator
XII Main Automatic Valves
Figure 14: Drawer Assembly
1. Diaphragm Main Automatic Valve
2. Motorized Main Automatic Valve
Page 14
XII Main Automatic Valves
Continued
3. Redundant Solenoid Gas Safety Valve
Unipower burners may feature a redundant solenoid gas safety valve. This valve is an On-Off (2
position) valve.
When the valve operator is electrically energized, a plunger lifts the valve disk off the valve seat,
allowing gas to flow. When the current is broken the valve closes. It will normally require no service. If the operator malfunctions or the valve leaks replace the entire valve. After replacement check for l e a k a g e .
XIII Flame Safeguard
WARNING: Explosion hazard. Do not use this device if it gets wet. It can malfunction and
cause serious injury or death. Replace any device that has been wet.
Standard Unipower G-Series burners are equipped with a Honeywell RM7895 microprocessor based
burner control, employing a flame rectification system of flame detection. Burner construction for special codes and/or insurance requirements such as Factory Mutual or Industrial Risk Insurers (IRI) may require alternate controls. Refer to Section XIV Special Equipment. A safe start and run control sequence is provided with instantaneous response to presence or loss of flame signal. Flame failure response time is 3 seconds. Pilot Flame Establishing Period (PFEP) is field selectable from 4 or 10-seconds. The RM7895 features a pre-purge time (30-seconds for On-Off, 90-seconds for 2-Step or Modulating burners) and a plug-in amplifier. An airflow circuit is also field selectable to allow either lockout or recycle upon loss of airflow. Five LED's (light emitting diodes) are provided to display sequence information. Refer to the Honeywell RM7895 literature for detailed operating information, configuration requirements, testing and service.
INITIATE ("POWER" LED is lit).
The RM7895 enters the I N I T I A T E sequence when it is powered. The I N I T I A T E sequence lasts for ten
seconds unless the voltage or frequency tolerances are not met (refer to Honeywell RM7895 literature for criteria). When tolerances are met, the I N I T I A T Esequence will restart. If the condition is not corrected and the hold condition exists for four minutes, the RM7895 will lock-out. Causes for hold conditions in the I N I T I A T E sequence are in the Honeywell RM7895 literature.
STANDBY ("POWER" LED is lit).
The RM7895 is idle in this state of sequencing. When the burner switch, limits, operating limit
controls and all microprocessor monitored circuits are in the correct state for the RM7895 to continue, sequencing will advance to P R E P U R G E.
PREPURGE ("POWER" LED is lit).
The RM7895 in this application features a prepurge time of 30-seconds for On-Off, 90-seconds for 2-
Step or Modulating burners.
Once the S T A N D B Y sequence has a "CALL FOR HEAT" input, normal start-up prepurge will be
i n i t i a t e d .
A . The blower motor is powered to start the prepurge sequence. B . The airflow interlock switch must close in ten seconds of prepurge or within the
specified purge card timing. Otherwise a recycle to the beginning of prepurge or lockout will occur, depending on how the airflow switch selectable jumper is configured. Refer to Honeywell RM7895 literature for configuration requirements.
IGNITION TRIAL
1 . PILOT FLAME ESTABLISHING PERIOD (PFEP)
A . The pilot valve and spark generator are energized. B . Flame must be proven by the end of the 4 or 10-second PFEP to allow the sequence to
continue. If flame is not proven by the end of PFEP, a safety shutdown occurs.
2 . MAIN FLAME ESTABLISHING PERIOD (MFEP)
After the ignition trials, and with the presence of flame, the main valve is energized.
("MAIN" LED will be lit.) If a flame-out occurs, the RM7895 will lockout or recycle within 3­seconds, depending on "jumper" configuration. Refer to Honeywell literature for proper c o n f i g u r a t i o n .
R U N
The RM7895 is now in R U N mode and will remain in run mode until the controller input opens,
indicating that the call for heat has been satisfied or a limit has opened. Once this occurs the RM7895 will sequence back to the S T A N D B Y m o d e . N o t e s : 1 . During S T A N D B Y and during RM7895 sequencing the "P O W E R" LED will blink
every four seconds. This is normal. 2 . The "A L A R M" LED will be lit in the event of any flame failure. 3 . To maintain proper operation of this device it M U S Tbe electrically grounded. Refer
to Honeywell RM7895 literature for criteria.
Page 15
XIV Special Equipment
ouble Char
I. Motor Fails
II. Motor Fails to Start, Flame
Safeguard Energized
III. Motor Runs Continuously,
No Lighting Attempt
IV. Pilot Does Not Light, Flame
Safeguard Locks Out
V. Pilot Lights, Flame
Safeguard Locks Out
(OEM Versions)
Special equipment, either factory or field installed, can cause variations in the procedures and
descriptions given in this manual. Generally, any burner ordered with special factory installed equipment will be supplied with the appropriate wiring diagram and related instruction manuals from the special equipment manufacturer. Consult these manuals to identify any differences in construction, operation and testing. Field installed special equipment is the responsibility of the installing contractor.
For example, when a high/low gas pressure switch is used, the high gas pressure setting must be
higher than the maximum manifold pressure during initial start-up and the low pressure setting must be set below the normal minimum inlet pressure to prevent nuisance shutdowns during the start-up p r o c e d u r e .
After the burner is started, the low pressure setting should be raised until the burner shuts off.
Reduce the setting and set the low pressure switch to restart the burner. Reduce the high pressure setting until the burner shuts off. Then raise the setting slightly and reset the high pressure switch to restart the burner. Do not make the adjustments too close to trip points or nuisance shut downs may occur. Anytime the burner gas supply is shut off with the main manual valve, the low pressure switch will require resetting.
If any doubt exists concerning burner operation when special equipment is involved, contact the
installing contractor or MIDCO INTERNATIONAL INC. (front cover).
Tr
Make sure the thermostat and operating controls are calling for heat. Defective wiring or loose connecting can simulate the component defects outlined below. Check associated wiring before replacing a component. ELECTRICAL AND FLAME CHECKS MUST BE MADE IN THE ORDER
L I S T E D .
A . No power to flame safeguard B . Flame safeguard locked out C . Defective flame safeguard D . Defective motor relay E . Motor overload "out"
A . Motor overload "out" B . Defective motor C . Defective flame safeguard
A . Defective air switch B . No air pressure at air switch C . Defective purge timer D . Defective flame safeguard
A . No pilot gas B . Low pilot gas pressure C . Defective pilot gas regulator D . Misadjusted pilot regulator E . Blocked pilot regulator vent F . Defective pilot solenoid valve G . Defective spark electrode H . Misadjusted spark electrode I . Defective spark cable J . Defective spark generator K . Clogged or incorrect pilot orifice L . Defective pilot tip M . Excess pilot air N . Air orifice missing O . Clogged pilot air tube P . Defective flame safeguard
A . Poor flame signal B . Poor pilot flame C . Misadjusted pilot regulator D . Low gas pressure E . No pilot air (see above) F . Excess pilot air (see above) G . Defective pilot tip
Page 16
Trouble Chart Continued
H . Defective flamerod wire I . Defective or misadjusted flamerod J . Defective amplifier K . Defective flame safeguard
A . Low gas pressure B . Misadjusted main regulator C . Blocked regulator vent D . Defective main regulator E . No power at main valve(s) F . Blocked main valve bleed line (if equipped) G . Defective main valve(s) H . Closed test cock I . Input adjuster closed J . Defective flame safeguard
A . Poor pilot B . Pilot gas pressure drops severely when main gas valve opens
A . Too little gas B . Low gas pressure C . Defective main regulator D . Misadjusted main regulator E . Too much air F . Partially closed test cock
A . Too much gas B . High gas pressure C . Defective main regulator D . Misadjusted main regulator E . Misadjusted input adjuster F . Too little air G . Dirty blower wheel
A . Defective valve(s) B . Defective valve actuator C . Dirty valve seat
A . Low voltage B . Spasmodic start C . Defective motor D . High ambient temperature
A . See IV above B . See V above C . See VI above
N o t e : Some of the probable causes listed above apply only to certain models as indicated,
therefore some may not apply to your particular case.
VI. Pilot Lights, No Lockout on
Flame Safeguard, No Main Gas
VII. Main Flame Lights, But Goes
Out, Pilot Relights
VIII. Short Main Flame
IX. Long, Hazy Flame
XII. Flame Safeguard Needs
Frequent Resetting
X. Main Valve(s) Fails
to Shut Off or Leaks
XI. Motor Overload
Frequently Trips Out
V. Pilot Lights, Flame
Safeguard Locks Out
Continued
Loading...