MICROWELL DRY SIREN User Manual

Page 1
SWIMMING POOL DEHUMIDIFIER DRY SIREN
SWIMMING POOL
DEHUMIDIFIER
User´s and installation manual
Version: 01/2018
Model: DRY SIREN mono
DRY SIREN due
Page 2
2 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 2 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Thank you for purchasing Microwell swimming pool dehumidifier DRY SIREN. You hold in your hands probably the most advanced and most futuristic device for your pool. Before you use this device, it is necessary to carefully read the entire User’s manual. Please keep the User’s manual available in the case a reference is required in the future. Please provide this information also to each user of the device. Please mind local regulations in your country regarding installation and usage of this
dehumidifier which are valid in addition to this User’s manual.
1. CONTENT ................................................................................................................................................. 2
2. WASTE DISPOSAL INFORMATION............................................................................................................. 4
3. SAFETY MEASURES................................................................................................................................... 4
3.1 ELECTRICAL SAFETY ................................................................................................................................ 4
3.2 USAGE PRECAUTIONS ............................................................................................................................ 5
3.3 HANDLING PRECAUTIONS ...................................................................................................................... 6
4. PARTS LIST ............................................................................................................................................... 7
5. TOOL LIST ............................................................................................................................................... 10
6. INSTALLATION – CEILING UNIT ............................................................................................................... 12
6.1 BASIC MANIPULATION ......................................................................................................................... 12
6.2 APPROPRIATE POSITION OF CEILING UNIT ........................................................................................... 15
6.3 FIXATION ON A CEILING CONCRETE / WOOD .................................................................................... 17
7. INSTALLATION – COMPRESSOR UNIT ..................................................................................................... 33
8. INSTALLATION – ELECTRICAL CONNECTION ........................................................................................... 34
9. DRAINAGE OF CONDENSATE WATER ..................................................................................................... 38
10. INSTALLATION – REFRIGERANT CONNECTION ........................................................................................ 40
10.1 DETERMINING THE PIPE LENGTH AND REFRIGERANT CHARGE. ............................................................................. 40
10.2 REFRIGERANT PIPING ................................................................................................................................. 41
10.3 FLARING WORK ........................................................................................................................................ 42
11. UNIT TEST – PAIRING ............................................................................................................................. 46
11.1 AFTER PAIRING, TEST RUN ................................................................................................................... 53
12. MOBILE APPLICATION - INSTRUCTIONS FOR USE.................................................................................. 54
12.1 CONTROL ................................................................................................................................................ 54
13. TECHNICAL DATA .................................................................................................................................. 58
13.1 TECHNICAL DATA TABLE ............................................................................................................................. 58
13.2 EXTRACTION RATE DIAGRAM ....................................................................................................................... 59
13.3 WIRING DIAGRAM .................................................................................................................................... 59
14. HINTS & TIPS .......................................................................................................................................... 60
14.1 ERROR MESSAGES ..................................................................................................................................... 60
Page 3
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 3 P a g e 3 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
14.2 TROUBLESHOOTING SAVE TIME AND MONEY ................................................................................................ 60
14.3 MAINTENANCE ......................................................................................................................................... 63
14.4 SUMMER SHUT-DOWN............................................................................................................................... 63
14.5 SUPER-CHLORINATION CLEANING ................................................................................................................. 63
14.6 START-UP DURING CONSTRUCTION ............................................................................................................... 64
14.7 MICROLIGHT+ ........................................................................................................................................ 64
15. WARRANTY ............................................................................................................................................ 64
15.1 INSTALLATION CHECK-LIST AND WARRANTY CARD ............................................................................. 66
Page 4
4 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 4 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
When using this dehumidifier in the European countries, the following information must be followed: DISPOSAL: Do not dispose this product as unsorted municipal waste. It is prohibited to dispose this dehumidifier in domestic / household waste. It is prohibited to dispose this appliance into forests or natural landscape. This could lead into local soil pollution. Collection of such waste must be treated individually.
DISPOSAL POSSIBILITIES:
1. The municipality has established a collection system where electronic waste can be
disposed.
2. When buying a new product, the retailer or the manufacturer may take back the old
appliance free of charge.
3. As old appliance may contain valuable resources which could be sold to scrap material
dealers.
4. Disposal of packaging materials such as carton box or plastic / bubble foil can be recycled.
This device is primarily designed for use in indoor swimming pool, sauna or spa. Alternative use is in laundries, drying rooms or other humid areas requiring dehumidification.
Model Microwell DRY SIREN is designed for halls with swimming pool surface of up to 60m
2
.
It is necessary to follow instructions in this User’s manual and local regulations in your country that regulate the installation and usage of this device. Incorrect, improper or operations contradictory to this User’s manual may lead to an injury or property damage and will lead to loss of warranty. To prevent injury or property damage the following instructions must be followed:
3.1 ELECTRICAL SAFETY
The device operates at dangerous electrical current. Only authorized person with particular electro-technical qualification can manipulate with unit. Danger of electrical shock.
For proper and optimal operations of the device is it necessary to maintain the air temperature in the swimming pool room / hall 2-3°C higher than actual water temperature in the pool. It is also necessary to keep the air temperature in the swimming pool room / hall in operational temperature range of the dehumidifier (specified in Technical data section). Higher temperatures than operational temperature range may cause damage to the unit resulting from overheating of the unit.
Page 5
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 5 P a g e 5 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Do not exceed the required power supply. Do not turn the device on that shows signs of possible damage such as broken packaging, broken or
otherwise damaged unit’s chassis or cover, smoke, smell, etc.
It is necessary to use appropriate Residual current circuit breaker (RCD) for connection of the dehumidifier to
main power supply.
Do not manipulate with the device with wet hands. Do not clean the device with water. Before cleaning the device, switch off the circuit breaker of the unit’s power supply. Installation, service or repair must be performed by qualified technician. When the device is not intended to be used for a longer time, we recommend switching the circuit breaker of
the unit’s power supply off.
Compressor unit must be installed in vertical position. Ceiling unit must be leveled to avoid condensate
water to enter electrical part of the unit.
It is forbidden to install the unit close to devices that may cause electrical or frequency disturbance such as
welding machines, motors or rotors, WIFI/WLAN routers or repeaters.
It is forbidden to alter electrical installation of the device. It is also forbidden to alter any other part or
functionality of the device.
3.2 USAGE PRECAUTIONS
Please read the entire User’s and Installation Manual prior you proceed with installation or usage of this
product. Do not continue or proceed if you have doubts, uncertainty or not full clarity about any step(s) described in this User’s and Installation Manual.
Do not cover or block the intake or exhaust openings. It is forbidden to block or cover the intake or exhaust
openings with clothes, towels, buckets, canoes, ceiling beams, etc.
Do not install or place any heating appliances close to intake grilles / louvers. It could continually
overheat the dehumidifier and result in its malfunction or damage.
Do not climb up on or sit on the unit. Do not place any objects on the top of the unit (e.g. boxes, flower vases, etc.). Do not hang any objects on the unit. Do not spray any flammable substances into the equipment; this might lead to fire. Do not clean the equipment with aggressive cleaning agents, this might lead to damage or deformations. When cleaning plastic parts do not use any cleaning agents unsuitable for the cover of the dehumidifier
(household cleaning agents, solvents, bleaching agents, benzene, diluents, rough cleaning powder, cresol, chemical agents). Instead, sweep the dehumidifier cover with a soft cloth or a sponge.
Never throw or insert any objects into any hose or opening. The cover of ceiling unit is made from acryl. The cover of compressor unit is made from powder coated
metal. Do not manipulate with lighted cigarette, cigarette ashes, or any other kind of fire in vicinity to this part.
Use this device exclusively for the intended purpose, as described in the attached instruction manual. Do not
use parts which are not recommended.
Do not drink or use the condensate water drained from the unit. Do not return the water back to the
swimming pool. The water may be contaminated with bacteria.
Children are not allowed to operate, touch or play with the unit. Children are not allowed to manipulate with packaging, plastic / bubble foil. Risk of suffocation! Prevent the children from injury or harm caused by any manipulation with the unit, its parts or its
packaging. Small parts like screws may be swallowed and cause suffocation or harm to health.
Do not leave the children in the swimming pool hall unattended.
The dehumidifier should be sized correctly and run max. 18 hours a day, optimum max. 12 hours a day. In
the case it runs more than 18 hours a day in long term it may fail, malfunction or get damaged. Warranty does not cover such damages as the machine is considered undersized if running longer than 18 hours a day.
Page 6
6 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 6 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
3.3 HANDLING PRECAUTIONS
Leave the compressor unit in vertical upright position for at least 2 hours before the installation. This will
level the oil inside the compressor.
Transport of the compressor unit in lying position or turning the compressor unit over may harm the
compressor and will lead to loss of warranty.
The device must be handled with care and special attention avoiding any mechanical damage. It is forbidden to apply any improper mechanical force onto the unit. This may cause mechanical damage to
the device.
It is forbidden to let the device fall freely onto the ground or any solid surface resulting in hard impact. Please notify your reseller or distributor if you suspect that the unit was delivered damaged. Unit may seem
to work well at start but small damage can make the unit go out-of-order in short time. In such case the unit must be inspected and approved for further use by your reseller.
Please notify your reseller or distributor if directly after installation you suspect that unit is not working in
perfect order.
In the case of device failure resulting from improper handling or mechanical damage (impact, hit, fall, etc.),
the manufacturer reserves the right to evaluate the continuity of warranty.
Page 7
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 7 P a g e 7 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
4. PARTS LIST
The unit was delivered in 2 boxes on a wooden palette(s). After you unpack the boxes, please check the content. It should include the following:
Name/Code
Picture
Name/Code
Picture
1 - Ceiling unit
1x
2 - Compressor unit
1x
3 - Tablet with charger
1x
4 - User’s Manual
1x 5 - F8 fastener
4x
6 - ML1 D8 fixation double nut
4x
7 - MX8 hex nut
d8
8x
12x if installation on wooden beam
8 - TR8 threaded bar
M8x1000mm
2x
9 - MB8 flat washer
8x
12x if installation on wooden beam, additional washers may be supplied MX10
10 - Scheme diagram
1x
Page 8
8 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 8 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
11 - Eight core cable with markings 123456 (mono), 12346 (due)
1x
12 - Three core cable with markings L1,N1,Earth
1x
13 - Back lift assembly (1) with anchor
1x
14 - Condensate drain for compressor unit
1x
15 - Rope
14.5m
1x
16 - Front lift assembly with locking mechanism (2) with anchor
1x
17 - Wall console for compressor unit
1 set
(on demand)
18 - Key set for compressor unit
2x
19 – Bluetooth receiver cable
(only DRY SIREN due)
-
-
The pictures and drawings in Parts list may differ from those actually delivered. Some parts may have been delivered upper hand and are thus not included in this shipment. If you are unable to locate all parts or are unsure if the supplied parts are complete, please contact your distributor.
Please note that the screws and dowels supplied with this dehumidifier are to be used only with solid concrete. Please check your ceiling material and choose appropriate screw and dowel.
Page 9
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 9 P a g e 9 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
CEILING UNIT
1. Main cover
2. Air intake
3. Air outake
4. LED lamp + microLIGHT+
5. Bluetooth speaker
6. Auto dimmable light sensor, LED pairing indicator
7. Refrigerant connection Suction (1)
8. Refrigerant connection Discharge (2)
9. Electrical connection – L1, N1, Earth, 12346
10. Lifting mechanism
11. Fixation hooks and Fixation ropes
12. Condensate drain
13. Serial number plate
COMPRESSOR UNIT
1. Main cover
2. Door
3. Lock + keys
4. Condensate drain
5. Silent blocks
6. Refrigerant connection Suction (1)
7. Refrigerant connection Discharge (2)
8. Communication cable to ceiling unit – 12346
9. Refrigerant plate
10. Serial number plate
11. Main power supply – L, N, Earth
12. Ceiling unit power supply – L1, N1, Earth
13. Serial RS port
14. Pairing button
15. Terminal connection for main power supply (L, N, Earth) and
ceiling unit power supply (L1, N1, Earth)
1 2 3 4 5 6 7 8 9
10
11
12
13
11 1 2 3 4 5 6 7 8
11
12 9 10
Page 10
10 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 10 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
16. Terminal for connection of communication cable –
123456
17. Compressor
18. Main PCB
5. TOOL LIST
In order to perform the installation correctly, you will need following tools:
Name/Code
Picture
Name/Code
Picture
19 - Drill
1x
20 - Drill bit 10mm
1x
If installation on a wooden beam:
9mm and 11mm drill bit
8
11
12
15
18
16
17
Page 11
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 11 P a g e 11 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
21 - Screwdriver Phillips PH2
1x
22 - Screwdriver Slot 5/32
1x
23 - Small hammer
1x
24 - Tape measure
1x
25 - Spirit level
1x
26 - Combination wrench / open-end wrench ­2x13mm, 1x16mm, 1x17mm, 1x19mm, 1x22mm, 1x24mm or adjustable
multiple
27 - Charging and testing hoses with valve, ½“ – 20UNF
2x
28 - Vacuum Pump 170l/min
1x
29 - Charging scales
+/-2g
1x
30 - Manifold valve R410A
31 - R410A Bottle
1x
32 - Flaring tool – tube 1/2, 3/8
1x
Page 12
12 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 12 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
33 - Cutter – tube 1/2, 3/8
1x
34 - Tube Bender – tube 1/2, 3/8
35 – Saw for iron
1x
6. INSTALLATION – CEILING UNIT
Ceiling unit is designed for an installation at the ceiling or at lower ceiling. Typically the ceiling unit is fixed into the concreted structure of the upper floor or wooden roof. Please make sure that the material into which the ceiling unit is to be fixed is suitable for such installation. Manufacturer is not responsible for damages or losses caused by an incorrect installation or inappropriate concrete or wood type. Ideally it should be installed above the evaporation source. It should be installed on easy accessible spot to allow maintenance and service. Please view following concrete types and strengths.
Pressure class
f
ck,cyl
(MPa)
f
ck,cube
(MPa)
Appropriate
Threaded bar TR8 L1 drill depth
Anchor for lifting mechanism
C8/10
8
10
No
N/A
N/A
C12/15
12
15
No
N/A
N/A
C16/20
16
20
Yes
80mm
60mm
C20/25
20
25
Yes
60mm
60mm
C25/30 and more
25 and more
30 and more
Yes
40mm
60mm
Concrete marking with additional request for seepage resistance: STN EN 206-1 –C25/30-XF2,XC2 (SK) – Cl 0,4 – Dmax 16 – S3, seepage 50mm according to STN EN 12390-8.
6.1 BASIC MANIPULATION
The unit is designed to be located on the ceiling. We, at Microwell, had to ensure a perfect balance between weight and long-term durability with focus on reliability of the product. It is thus necessary to mind below manipulation information and comply with them. Non-compliance may lead to product damage, malfunction or failure. Manufacturer is not resosonsible for incorrect manipulation or for manipulation not compliant to this User’s manual.
Ceiling unit is delivered in a box with polystyrene support from the bottom at sides.
Page 13
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 13 P a g e 13 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Do not place ceiling unit on side. The unit is not designed to stand on its side. Main cover damage may occur in such position.
Do not place ceiling unit on the ground. Do not put the unit on an object or support holding the unit in the center.
Do not place any objects such as drill tools, boxes, vacuum cleaners, etc. on the top of the ceiling unit.
Do not hold ceiling in areas where forbidden (bluetooth speaker, LED lamp, air outlet). For manipulation hold the unit on the side which is supported by metal structure. Do not hold in places where plastic cover does not have metal support.
Page 14
14 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 14 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
DO NOT INSTALL THE CEILING UNIT IN BETWEEN THE WOODEN BEAMS OR SIMILAR OBJECTS. Air flow on the outlet will be reflected from the object (wooden beam) and
redirected back to the unit. Thus the water collection process will be dramatically reduced and the unit will be exposed to the risk of overheat.
Page 15
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 15 P a g e 15 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
6.2 APPROPRIATE POSITION OF CEILING UNIT
Page 16
16 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 16 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Please mind electrical safety requirement below to locate an electrical device close to pool water.
ZONE 1, IPX4
ZONE 2, IPX2
OUTSIDE THE ZONES
In the distance of 1250 mm or less from the swimming pool edge, the bottom edge of the unit must be in
the height of 2500 mm from the swimming pool surface; if it is embedded under the floor, then 2500 mm from the floor.
At least 1250 mm (i.e. out of the reach of the hand) from the lateral edge of the wash basin, in the minimum height of 1200 mm above ground. It cannot be placed above the wash basin.
In the distance of at least 1500 mm from the vertical plane a roun d th e jumping platforms, diving boards
and 2500 mm above the highest surface, where persons are likely to stay.
If the unit is in the distance of less or equal to 1250 mm horizontally from the edge of the swimming
pool, then it must be raised up to the height of 2500 mm from the swimming pool surface; if the pool is embedded under the floor,
then the unit must be raised up to the height of 2500 mm from the floor.
SWIMMING POOL
SWIMMING POOL
Swimming pools which are not
cleaned by jet water
in the distance of 1250 to 2000 mm from the swimming pool edge,
the unit must adhere to the standard and in the height
of at least 300 mm from the floor
HD, IEC
Swimming pools which
are not cleaned by jet water
In the distance of 2000 to 3500 mm from the swimming pool edge, the
unit must adhere to the HD, IEC standard and a minimum 150 mm elevation above th e groun d is
required for su fficient air flow. Installing the unit on the floor is prohibited.
At least 1250 mm (i.e. out of the reach of the hand) from the lateral edge of the shower cabinet. It cannot be placed above the shower cabinet.
OUTSIDE THE ZONES
OUTSIDE THE ZONES
Page 17
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 17 P a g e 17 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
6.3 FIXATION ON A CEILING – CONCRETE / WOOD
1. Locate appropriate
location for the ceiling unit.
2. Mark the drilling holes according to Scheme
diagram (Part number 10). Position the drill hole for lifting mechanism 800mm from the center in between the 2 threaded bars (TR8 – part number 8)
800mm
Page 18
18 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 18 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
3a. Drill 6 holes (4 for TR8, 2 for Lifting mechanism).
/We advise to use vacuum cleaner simultaneously when drilling to avoid dust and particles be spread into entire room./
Page 19
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 19 P a g e 19 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
CONCRETE
3b. Drill 4 holes (TR8) using 10mm bit by
concrete and 9mm bit by wood beam. Drill 2 holes (Lifting mechanism – Part number 13 and 16). Please refer to needed drilling depth – section 6 INSTALLATION – CEILING UNIT – table Concrete types and strength. For wood we advise to drill completely through. Please mind that wooden beam must be statically resistant to hold weight of DRY SIREN unit (53kg) and it must be possible to drill 9mm hole through it without changing the static conditions of the wooden beam
4. By concrete insert 4 fasteners into the
holes for threaded bars. Fastener is part number 5. Use small hammer or appropriate.
5. Assemble 4 mounting threaded bars for ceiling unit
fixation. Use part numbers 5, 6, 7, 8, and 9. Please refer to picture below.
MX
Page 20
20 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 20 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
WOOD
Page 21
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 21 P a g e 21 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
6. Please refer to picture below in order to fix the final length of
threaded bars.
CONCRETE
Page 22
22 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 22 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
WOOD
Page 23
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 23 P a g e 23 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Example:
LTR= L1+L
2
L1 = depth in concrete of TR8 – please refer to section 6 INSTALLATION – CEILING UNIT or height of the wooden beam LC = depth in concrete of lifting mechanism – please refer to section 6 INSTALLATION – CEILING UNIT L2 =L – 55mm L3= distance above wooden beam. Due to security buffer minimum 40mm.
Practical example CONCRETE:
Lower ceiling is 150mm below the main concrete. Concrete type is C25/30. (see concrete types and strengths in 6 INSTALLATION – CEILING UNIT).
L=150mm L1=40mm
L2=150-55mm; L2=95mm LTR= L1+L2; LTR=40+95=135mm
Maximum length of the 4 threaded bars is 135mm.
Practical example WOODEN BEAM:
Lower ceiling is 150mm below the main wooden beam. Wooden beam is 100x100mm.
L=150mm
L1=100mm
L3=40mm
L2=150-55mm; L2=95mm
LTR= L1+L2+L3; LTR=100+95+40=235mm
Page 24
24 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 24 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Maximum length of the 4 threaded bars is 235mm.
CONCRETE WOOD
7a. Lifting mechanism fixation. Please refer to part numbers 13 and 16
Part number 13 (1)
Part number 16 (2)
7b. Please mind the necessary depth in concrete (6 INSTALLATION – CEILING UNIT). Both parts
are equipped with concrete anchors. These must be put inside the hole by force and then the respective nut inside the part must be tightened until the part is securely fixed into the concrete. PLEASE NOTE THAT BY WOODEN BEAM WE ADVISE TO FIX THE LIFTING MECHANISM COMPLETELY THROUGH THE WOODEN BEAM.
7c. Please mind the direction of part 13 and 16 as a rope will be used to lift the ceiling unit.
Thus the direction of rope should be direct from Back lift assembly (part 13 -1) to Front lift assembly with locking mechanism (16-2). Please refer to picture below showing view from the
Page 25
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 25 P a g e 25 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
CONCRETE
WOOD
13 (1)
16 (2)
16 (2)
16 (2)
13 (1)
Page 26
26 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 26 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
8. Bring the DRY SIREN box with ceiling unit in it under the spot where it will be installed. Take
supplied rope (part number 15) and fix it step-by-step onto the lifting mechanism and DRY SIREN ceiling unit. Please take the hitch and fix it into the clip (1) of the Back lift assembly (part number 13). Untangle the rope and with the other end continue through the lifting mechanism of ceiling unit (2). Continue guiding the end of the rope through the wheel of Back lift assembly (3) out in direction of Front lift assembly (4). Please make sure that the rope is correctly guided through the locking mechanism (5). Pull the rope towards yourself until the rope is tight. Do not lift the ceiling unit yet. Rope is 14.5m long, you can thus use it for a maximum ceiling-to­floor distance of 4.5m.
1 2 3 4 5
9a. Perform test of lifting mechanism. Please note that a force of 500N
is required to pull the ceiling unit effectively up to the ceiling. A person performing the task must weigh minimum 70kg. A person with lower weight may be outweighed by the weight of the ceiling unit and accident may occur with result in person’s injury and unit’s damage.
500N
min. 70kg
Max. ceiling
height 4.5m
Page 27
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 27 P a g e 27 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
11. Test the functionality of locking mechanism. Please refer to picture
below. Once you tested the tightness of lifting mechanism and locking mechanism you are ready to proceed to lifting the unit. This is designed as one man job.
10. Check the final distance of threaded bars and locking hooks on the
ceiling unit. Should correction be needed, untight the hex screws and position to the correct position. Tight with hex screw.
Move right-left.
Page 28
28 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 28 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
12. Next step will be actual fixation of the ceiling unit to its final position. Please note this step
and its process but do not lift or fix the unit yet as you need space to connect wires, refrigerant pipes and condensate drain. You need to have the installation of other parts ready
to proceed with following steps. Please fix the hooks onto the threaded bars 4x. Please fix the hooks with MX8 on each threaded bar. Secondly attach the steel rope clips onto the ML1 d8 to secure the ceiling unit 4x. Below picture shows fixed hook and steel rope clip on a threaded bar.
Unit must be perfectly levelled using spirit level! Uneven position may cause condensate drain leak and malfunction. Allowed tolerance is +/-0.3%.
MX8
max. +/-0.3%.
MX8
CONCRETE
Page 29
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 29 P a g e 29 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
max. +/-0.3%.
WOOD
Page 30
30 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 30 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Clip
Hook
Please view the final fixation of the ceiling unit. The ceiling
unit must be fixed on 4 hooks which are tightened onto 4
threaded bars. Each fixation point is secured with a steel rope
WOOD
Page 31
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 31 P a g e 31 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Hook
Clip
Please view the final fixation of the ceiling unit. The ceiling
unit must be fixed on 4 hooks which are tightened onto 4
threaded bars. Each fixation point is secured with a steel rope
CONCRETE
Page 32
32 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 32 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
13. It is advised to construct 2 service hatches 400x400 next to DRY SIREN ceiling unit as per
below drawing.
When installing you may use help of scaffold base or ladder. Mind all local work, health and safety requirements. Manufacturer is not responsible for injuries caused by inappropriate tools, equipment or work procedures.
400mm
400mm
400mm
400mm
Page 33
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 33 P a g e 33 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
7. INSTALLATION – COMPRESSOR UNIT
Compressor unit is designed for an installation in technical room. It is a metal box with 4 silent blocks ideally to be installed on a wall console. This part describes the fixation on a wall console.
Please refer to position of the compressor unit in terms of surrounding walls and objects.
1. Locate the appropriate location for compressor unit. Drill 4 holes for fixation screws and fix
the wall consoles on a wall. Make sure the wall console is leveled with spirit level with max. deviation of +/- 0.3%
197mm
max. +/-0.3%.
min. 500mm
min. 100mm
min. 300mm
min. 300mm
min. 300mm
max. 100mm
Page 34
34 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 34 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
8. INSTALLATION – ELECTRICAL CONNECTION
Connection of the unit onto the mains must conform to relevant safety standards valid in your country.
Main power connection is lead to Compressor unit. Compressor unit then powers the ceiling unit.
Connection requirements: Power supply: 220-240V / 50Hz. Protection: 16A, type C, by a protective switch (RCD) with nominal differential drop-out current not exceeding 30 mA.
Main power supply cable: 2.5mm2 CYSY, three core – Live, Neutral, Earth.
The main circuit breaker switch of the compressor unit must be situated outside of the swimming pool hall. The main switch of the unit must be bipolar, with switch-out breaking of conductors L and N. An appliance for disconnecting the unit from the mains must be embedded into a firm surface. The distance of contacts, when switched off, must be at least 3 mm for all poles.
In order to protect the unit from weather anomalies it is recommended to install power surge protection class 1. B+C+D.
2. Mount the compressor onto the wall console. Please refer to below drawings. All nuts and
screws are supplied.
Nut M8
300mm
The connection of the appliance to the electric mains must be carried out by a certified electrician.
max. +/-0.3%.
Page 35
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 35 P a g e 35 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Please mind all electrical safety precautions from section 3.1 ELECTRICAL SAFETY
1. Please use supplied eight core cable (part number 11 with markings 1,2,3,4,6) and three core
cable (part number 12 with markings L1,N1,Earth). Both cables are to be connected to both ceiling and compressor unit.
Ceiling unit electrical and communication connection.
2. Open the black connection box with hand pushing from the sides and pull up.
3. Please connect all connections with respective markings – L1, N1, Earth, 1, 2, 3, 4, 6 for
DRY SIREN mono and L1, N1, Earth, 1, 2, 3, 4, 6 for DRY SIREN due. The connections 5 and 7 are for Bluetooth receiver which in DRY SIREN due connects the ceiling units with each other – part 19 - Bluetooth cable receiver. Once connected, please close the black box.
Page 36
36 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 36 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
4. Take both cables and connect them onto terminals into compressor unit.
Compressor unit electrical and
communication connection.
5a. Lead the cables through the cable joint connectors. Unscrew the plastic top.
Top
Bottom
Female connector for bluetooth receiver cable.
Male connector for bluetooth receiver cable.
Page 37
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 37 P a g e 37 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
5b. Lead the cable through the top to bottom. Then tighten the top back.
6. Please connect the ceiling unit
power supply cable (L1, N1, Earth) and compressor unit main power supply cable (L, N, Earth) onto the compressor terminal connection.
7. Please connect the
communication cable (1, 2, 3, 4,
6) for DRY SIREN mono. 1,2,3,4,6 for DRY SIREN due.
Page 38
38 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 38 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
9. DRAINAGE OF CONDENSATE WATER
Condensed water is pumped from the unit upwards with total vertical discharge of 40cm (netto out
of the unit 20cm) and then by the force of gravity (downwards). Unit’s condensate tray is levelled to
have sufficient declivity when the ceiling unit is perfectly levelled (using spirit level) with tolerance +/- 0.3%. Compressor unit uses only the force of gravity. The condensation water must be drained through a siphon into a municipality sewage system or into the outside environment. Please do not place the drainage hose upwards (against gravity); this will lead in unit’s inability to drain the
condensate water. This will subsequently cause water leakage from underneath the unit’s cover and may lead to unit’s malfunction, damage or failure. Also it may cause the underlying floor be wet,
which creates danger of accident and harm to health resulting from unwanted slip. Manufacturer, distributor or reseller are not responsible for such damages.
Incorrect drain installation.
Avoid ‘waving’. Accumulated water in downslope
‘waves’ avoids normal condensate drain and will
result in water leakage.
Incorrect drain installation.
Do not increase the drain after it was in
downward slope.
Do not drink the condensate water. Do not pour or let the condensate water back to the swimming pool. It may be contained with bacteria.
Downward slope.
max. 200mm
Siphon.
TR8
Fix the condensate drain
onto the TR8.
Page 39
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 39 P a g e 39 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Compressor unit is supplied with a condensate drain hose. Please follow instructions below to correctly install the condensate drainage.
Correct drain hose Incorrect drain hose installation.
CONDENSATE DISCHARGE
Condensate drain
Condensate drain
Condensate drain
Condensate drain
tub
Bath tub
basin
plumbing
Overflow
Page 40
40 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 40 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
10. INSTALLATION – REFRIGERANT CONNECTION
DRY SIREN requires refrigerant circuit connection in order to operate normally. This section explains the refrigerant installation in detail. Refrigerant circuit must be sealed.
IMPORTANT: Please note that refrigerant connection can be performed by an authorized person only. The person must have a valid refrigeration license.
Compressor unit is not pre-charged with refrigerant R410A from the factory. The pre-charged amount of refrigerant is =0.00kg= R410A. The unit must be filled with 1.05kg R410A as nominal charge. This charge is enough for 8 meter long refrigerant connection. Certain amount of refrigerant must be added to the system per each meter exceeding 8m of connecting distance.
Please note that it is needed to add 30g of R410A per 1 meter for
exceeding 8m connecting distances above nominal charge 1.05kg.
Piping length and elevation
Heat
pump
model
Pipe size
Factory pre-
charged
connection
distance
Max.
vertical
distance
(B)
Max.
distance
(A)
Additional
refrigerant
Gas (diameter)
Liquid (diameter)
inch
mm
inch
mm
DRY SIREN
1/2
12.7
3/8
9.52
=0.0=
8m
20m
30g/m above 8m
10.1 Determining the pipe length and refrigerant charge.
It is important to correctly measure the refrigerant pipe length and calculate the necessary refrigerant charge. Please refer to picture below as an example. Pipe length is 15 meters.
Factory pre-charge: 0.00kg
Nominal charge needed: 1.05kg
Additional charge: 12+3-8= 7m; 7 x 0.03=0.21kg
Total final charge needed: 1.05+0.21= 1.26kg R410A
Compressor
unit
Ceiling unit
Ceiling unit
Compressor unit
Page 41
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 41 P a g e 41 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Note: The picture is illustratory and is not designed to reflect the exact measures and distances correctly.
10.2 Refrigerant piping
I. Align the center of the pipes and sufficiently tighten the flare nut by hand. Please do so for
both Suction and Discharge pipes. Suction pipe has bigger diameter. Discharge pipe has smaller diameter.
II. Tighten the flare nuts with torque wrench until the wrench clicks. Please make sure that the
direction for tightening follows the arrow on the wrench.
Pipe connection on compressor unit.
Pipe connection on ceiling unit.
Please review below table for torque force.
Compressor unit
Ceiling unit
12m
3m
Page 42
42 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 42 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Outside diameter
Torque kgf
m
inch
mm
3/8
9.52
3.4-4.2
1/2
12.7
5.5-6.6
III. Forming and insulation the piping.
The pipes must be insulated and secured with vinyl tapes. This is done in order to prevent condensation on the piping.
It is highly advised to place the piping into a plastic protector when installed in the ground (soil).
On places where piping goes through a wall or similar it is advised to use gum type sealer or construction foam to seal the openings.
1. Compressor unit below ceiling unit
Tape the piping and interconnecting cable from down upwards. Fix the tapped piping with cable binder or equivalent onto the exterior wall. It is important to make a trap to prevent water from entering into the electro installation of the condensing unit.
2. Compressor unit above ceiling unit
Tape the piping and interconnecting cable from down upwards. Fix the tapped piping with cable binder or equivalent onto the exterior wall. It is important to make a trap to prevent water from entering into the electro installation of the compressor unit. On refrigerant side it is important to form a
syphon to avoid compressor’s oil leakage into ceiling unit coils.
10.3 Flaring work
It is important to perform the flaring work correctly. This will have positive effect towards long-term reliability and functionality of the DRY SIREN. Defective or incorrect flaring work is the most common cause for gas leakage or other refrigerant circuit defect. Both then result in continuous decrease of DRY SIREN efficiency and eventually lead into security turning off, malfunction, failure or damage.
Warranty does not cover any product, property or personal damages or losses that are a result of incorrect flaring work, gas leakage, incorrect welding work or improper material used.
Insulation
Suction
Discharge
Syphon
Please use refrigerant copper pipes with
insulation only.
min.
500mm
Page 43
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 43 P a g e 43 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
When cutting the pipes and cables, please mind the following:
1. Measure the distance between the water and the condensing unit.
2. Cut the pipes a little longer than measured distance.
3. Cut the cable 1.5m longer than the pipe length.
Pressure test / Air purging / Filling the refrigerant
Sometimes bits of air and moisture remains in the refrigerant circuit. If this is not treated, following symptoms may appear on DRY SIREN:
1. Pressure in the system rises.
2. Operating current rises.
3. Dehumidification efficiency drops.
4. Blockage of Electronic expansion valve due to frozen moisture resulting in complete failure of
the unit.
5. Corrosion of refrigerant circuit.
It is thus highly advised to take a leak test after evacuating the complete system. Leak test can be performed with usual methods using manifold valve and/or soap water. Air purging can be performed by most commonly applied methods with vacuum pump. This Installation and user manual elaborates vacuum pump method.
Air purging with vacuum pump / Filling the refrigerant
1. Preparation
CORRECT
INCORRECT Even
Slanted
Uneven
Rough
Smooth, shiny without scratches
Same length all around
INCORRECT FLARING
Inclined / Surface damaged / Cracked / Uneven
thickness
Page 44
44 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 44 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
a. Check that each tube (both suction and discharge) between the ceiling and
compressor units have been properly connected and all wiring for the test run has been completed.
b. Remove the service valve caps from the suction side on the compressor unit. Please
note that both the suction and the discharge side service valves on the compressor unit are kept closed at this stage.
2. Vacuum test a. With a service valve wrench (imbus wrench), turn the suction and discharge valve
counter-clockwise to fully open both valves.
b. Connect the charge hose end described in the preceding steps to the vacuum pump
to evacuate the piping. Confirm the “Lo” knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation when using a vacuum pump of 30 gal/h power.
Required time for evacuation when 30 gal/h vacuum pump model is used
Tube length less than 10m
Tube length more than 10m
Minimum 20 minutes
Minimum 30 minutes
c. When the desired vacuum is reached, close the “Lo” knob of the manifold valve and
stop the vacuum pump.
d. Close the valve on charging hose at vacuum pump.
3. Refrigerant filling a. Now remove the vacuum pump and bring the refrigerant bottle and charging scales.
Connect the disconnected hose (point d above) to refrigerant bottle (liquid side). Place the bottle on charging scales and turn the scales on. Please make sure no object, pipe, cable or other touches the bottle or charging scales. Otherwise weight misreading may occur.
b. Please close the valve at hose at suction side of compressor unit. c. Open the manifold ‘Lo’. d. Open the valve at hose at refrigerant bottle. e. Open the bottle’s valve. f. Zero the charging scales out. g. Open the valve at hose at suction side of compressor unit. Please mind that the
compressor unit is still off.
h. Wait until the unit sucks necessary amount of refrigerant. Charging scales typically
shows the weight as negative number (how much was taken out from the bottle).
i. Sometimes the necessary amount of refrigerant is not sucked into the system by
itself. The reason can be:
room air temperature / bottle temperature too low Low bottle pressure (low amount of gas in bottle) Restriction in copper pipes
Page 45
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 45 P a g e 45 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Incorrect copper pipe installation Malfunctioning / defective valve, hose or manifold valve
To resolve, please proceed step-by-step:
- Ensure stable room and bottle temperature of +20°C to + 30°C, ideal is when bottle
temperature is higher than air temperature
- Make sure that bottle contains at least a double amount of required amount of refrigerant
- Check the entire copper pipe installation and make sure it all complies this User’s manual
- Check the functionality of valves, hoses and manifold valve
- If all OK, you need to help the filling with a compressor ON. This is done by turning the power
supply to the unit on and actually turning the unit on into a dehumidification mode (i.e. compressor on). This can be done only by an Android application. Please see section 11 UNIT TEST PAIRING for more details. Please DO NOT RUN THE UNIT WITHOUT REQUIRED AMOUNT OF REFRIGERANT.
j. When the required amount of refrigerant has been filled into the system, first close
the valve at suction at compressor unit and remove the valve from compressor unit. Please make sure you close the valve on bottle and ‘Lo’ knob on manifold valve.
k. Put service valve caps back at both suction and discharge side service valves and
fasten them tight. Please note those suction and discharge valves are to be kept open for the unit’s operation. Make sure all copper pipes are properly insulation against external conditions to prevent condensation and water leakage and also burnt.
l. This completes the refrigerant work.
Please note that above flaring and refrigerant work must be performed correctly with utmost care. Any non-compliance with above may and will likely lead into unit’s malfunction, failure or damage. Such state means complete warranty void and manufacturer, distributor or reseller cannot be taken responsible in such case for any property or personal damage or loss.
Always use charging scales for refrigerant filling. Do not use pressure as indicator of the correct refrigerant amount.
Page 46
46 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 46 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
VACUUMING REFRIGERANT FILLING
Refrigerant filling
With a service
11. UNIT TEST – PAIRING
1. DRY SIREN is designed to be controlled exclusively via a mobile device application. In order
to control the unit you need pair it with your mobile device. You will need mobile device (e.g. supplied tablet), WIFI connection and DRY SIREN LICENCE information. DRY SIREN’s pairing is protected by double password entry. This is to avoid third parties logging into your DRY SIREN device. DRY SIREN licence plate is located on the inside of the compressor unit’s door. The plate looks like following:
DRY SIREN LICENCE EXAMPLE
SN: XXXXXXXX SN: 17164001 Real ID: YYYYYYYY Real ID: 9LheRL6q PASSWORD: ********* PASSWORD: 123456789 APP LOGIN: XXXXXXXX APP LOGIN: 17164001 APP PASSWORD: ****** APP PASSWORD: 123456 BLUETOOTH SPEAKER ID: JPM2021 BLUETOOTH SPEAKER ID: JPM2021
DATE: XX.XX.XXXX DATE: 01.01.2017
Ceiling unit
Compressor
unit
Pressure
gauge
Vacuum pump
Hose with valve
Refrigerant
bottle
Charging scales
Please note that 1.05kg is in this picture illustratory.
Page 47
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 47 P a g e 47 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
2. Turn the supplied tablet on via pressing and holding upper right button on the side. Supplied
tablet type may be Acer Iconia One 7 or similar. Please wait until tablet starts and goes to home screen.
3. Connect the tablet to your WIFI.
Go to Wi-Fi
Select your WIFI hotspot network
(in our case ‘MicrowellAP’)
Go to settings
Page 48
48 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 48 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
4. Open the ‘Microwell’ application on home screen. Wait until you enter the application.
If necessary insert network
password and press
connect
After you are successfully
connected proceed to next
step
Page 49
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 49 P a g e 49 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
5. Now you need to pair DRY SIREN.
6. It is necessary to activate DRY SIREN access point. This is
activated by pressing and holding the PAIR button on compressor unit for 3 seconds. White colored LED light flashing on ceiling unit will signalize that the unit is ready to pair. You will also notice increased performance of the fan on the ceiling unit.
Wait until the
application starts, then
press ‘PAIR AGAIN’.
At this moment please
Confirm by pressing
‘PAIR’
Page 50
50 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 50 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
7. Step 1/5
7.
8. In the next screen (Step 2/5) choose your internet connection
Choose DRY SIREN+Real ID,
in our case ‘DRY SIREN
9LheRL6q’
Press ‘FIND DRY SIREN’
Press ‘FIND HOME WIFI’
WIFI hotspot, in our case
‘MicrowellAP’
Press CONNECT
If the device requires password, insert
password 9 digit password from
Licence plate. Please mind that ‘0’ is
zero key and ‘3’ is number 3 key. Then
press CONNECT.
Once it shows „Connected“ you have to jump back with „Back“
screen button to proceed to the next screen.
Once it shows „Connected“ you have to jump back with „Back“
screen button to proceed to the next screen.
Page 51
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 51 P a g e 51 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
9. Wait for password window and insert password.
10. Step 3/5
Press SELECT DRY SIREN
Press CONNECT
Then press CONNECT
Select DRY SIREN 9LheRL6q
Once it shows „Connected“ you have to jump back with „Back“
screen button to proceed to the next screen.
Once it shows „Connected“ you have to jump back with „Back“
screen button to proceed to the next screen.
Page 52
52 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 52 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
11. Step 4/5
12. If there is working internet connection, correct password and all working properly, your set up is
complete.
Select your internet connection WIFI
hotspot, in our case ‘MicrowellAP’
Press CONNECT
Press SELECT HOME WIFI
Press START USING
DRY SIREN.
Once it shows „Connected“ you have to jump back with „Back“
screen button to proceed to the next screen.
Page 53
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 53 P a g e 53 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
13. Now you are in Microwell application home screen.
To exit the application, simply close it in Android. Do not use Sign out for this purpose. Sign out will sign you out of the application. You will need the application Login ID and Password to sign again. Please note that if you are signed out of the application you cannot control the DRY SIREN.
11.1 AFTER PAIRING, TEST RUN
After you have successfully paired the device you can run it for testing. When the unit is given command to dehumidify (required humidity below actual) in order to protect the compressor, the units starts to collect water after 3minutes. Minimum water collection time (compressor on) is 5 minutes.
Please turn to next section for more information about application description and control.
DRY SIREN remembers the pairing. If there is a power supply cut or you turn the unit off. After the unit is turned back on it will be connected automatically to the server. This does not apply if your WIFI NETWORK ID has changed, or your WIFI NETWORK PASSWORD has changed.
RECOMMENDATION: Cover your pool when not used. It will reduce the amount of vapor in the air and energy costs needed to operate your dehumidifier.
DRY SIREN is paired and
working properly.
Page 54
54 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 54 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
12. MOBILE APPLICATION - INSTRUCTIONS FOR USE
12.1 Control
DRY SIREN is controlled by an Android DRY SIREN application over WIFI. When DRY SIREN is plugged into the mains and is correctly installed, it will turn on and work on factory preset settings. The unit will operate to achieve 60% relative humidity with auto light and microLIGHT+. Bluetooth speaker will be also activated. Control over WIFI and mobile application allows the user to take over full control of the unit, dehumidification process, LED lamp, microLIGHT+ and Bluetooth speaker.
Do not run the unit without required amount of refrigerant. Before you proceed
make sure that all installation (electrical, refrigerant, etc.) According to this user’s manual had been done correctly and in full compliance to this user’s manual.
Description of the home screen
microLIGHT+
indication of
current humidity
Current humidity
Current air
temperature
DRY SIREN serial
number
Status of the DRY SIREN
- Connected
- DS unreachable
- DS error
- Pair again
If water drops are shown, DRY SIREN is in the process of dehumidifying
Humidity control
Lamp control
Speaker control
Application
settings
Page 55
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 55 P a g e 55 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Humidity control
Humidity settings.
You can set any from
1% to 99%. The
system will advise
you when set under
40% or above 70%.
Back to Home screen button
Current humidity
microLIGHT+
indication of
current humidity
Status of the DRY SIREN
microLIGHT+
indication of
requested humidity
Page 56
56 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 56 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Lamp control
Back to Home screen button
LED lamp ON/OFF
LED lamp manual
brightness (disabled
when auto
brightness is on)
LED lamp Auto
brightness ON/OFF
LED lamp color
temperature
microLIGHT+
ON/OFF
microLIGHT+
indication of
current humidity
Page 57
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 57 P a g e 57 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Speaker
If you hear the sound playing from DRY SIREN, your Bluetooth speaker works properly In order to play music go to home screen and turn the Music player on. (Music can be played from any source – streaming like youtube, Spotify, memory card, etc.).
Turn the speaker
To activate the speaker go to
Tablet’s Bluetooth settings and
turn the Bluetooth on.
Device will find and pair itself with
DRY SIREN speaker (Bluetooth
speaker ID, e.g. JPM2021). By DRY
SIREN due please mind MASTER and
SLAVE units. Master unit is visible for
Bluetooth pairing.
After pairing is successful, go
back to application and test
sound.
Page 58
58 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 58 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
13. TECHNICAL DATA
13.1 Technical data table
DATA
UNIT
DRY SIREN MONO
For swimming pools with max. water surface
m2
60
Extraction rate at 30°C and 60 % RH
l/24hrs
67
Extraction rate at 30°C and 70 % RH
l/24hrs
88
Extraction rate at 30°C and 80 % RH
l/24hrs
104
Operational temperature - standard
°C
5-35
Operational humidity range
% RH
20-100
Air flow
m3/h
1000
Noise level (in 1m distance) Ceiling unit
dB (A)
35
Heat output
W
4500
Energy consumption
W
1000
Voltage
V/Hz/f
230/50/1
Operating / Starting current
A
5.2 / 15
Protection
A
16
Conductor
mm2
CYSY 3C x 2,5
Condensed water pipe
mm
d 18
Dimensions netto (width x height x depth)
mm
Ceiling unit round shape (1210x278),
Compressor unit (251x467x404)
Dimensions brutto (width x height x depth)
mm
1400 x 1550 x 850
Weight
kg
Ceiling 53 / Condensing 20
Amount of refrigerant - R 410 A
kg
minimum 1.05kg; 2.088t CO2 ekv. = 1.0kg R410A
Max. pressures in the system HP/LP
bar
28,5/8,5
WIFI specification
-
Standard worldwide
IEEE802.11b/g/n
2.412~2.484 GHz
Internet connection
-
minimum 40kB/s, 13GB per month data volume
Bluetooth speaker
-
80W stereo, 80Hz-20kHz, 4-8,
Bluetooth 3.0 + EDR
LED lamp
-
50W, Warm 3.000K, COLD 5.500K, 4000lm
dimmable 0-100%
energy class A+
* Manufacturer reserves the right to change above data without notice. For DRY SIREN DUE the data apply in duplicity.
Gas circuit is filled with refrigerant R410A which is two-content refrigerant (R32/R125). Based on ES No. 842/2006 are these contents considered to be a fluorocarbon greenhouse gases. The unit contains fluorocarbon greenhouse gases included in Kyoto Protocol:
R410A with global warming potential (GWP) 1720: (R-32/125 50/50) CH F +CF CHF
1.0kg = 2.088t CO2 ekv.
For exact amount of refrigerant in your device; please turn to serial number sticker (located in the upper right corner of the unit from the back).
Page 59
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 59 P a g e 59 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
13.2 Extraction rate diagram
13.3 Wiring diagram
CEILING UNIT SIREN
TO COMPRESSOR UNIT L1 N1 1 2 3 4 6
COMPRESSOR UNIT
POWER SUPPLY
POWER SUPPLY
UNIT
COMMUNICATION
230VAC /
TO CEILING
L N - L1 N1
FUSE
....
....
RS232
PAIR
R BR BL
CM
16A „C“
Page 60
60 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 60 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
14. HINTS & TIPS
14.1 Error messages
DRY SIREN is equipped with Microwell unique feature microSAFETY+ which enables the manufacturer to see actual technical data of your DRY SIREN in real time. In the case the data indicate technical problem on your DRY SIREN, the manufacturer will advise the distributor/reseller to take appropriate action. Most of error messages are visible only to the manufacturer and also can be accessed via a serial port on compressor unit. This access should be performed by a trained technician with proper equipment. This User’s Manual is not designed to deal with serial port access.
Please find here list of error messages visible to end User.
Error message
Description
DS UNREACHABLE
Loss of communication. This error occurs if in last 70 seconds there is no response from DRY SIREN to the server. Once you see this error, please wait 5-10 seconds. Sometimes when response from server due to internet connection is slower, temporarily (max.
10seconds) the DRY SIREN may be ‘UNREACHABLE’. This error
relates to WIFI connection, server error or internet connection in general. Please turn to section 14.2 Troubleshooting – save time and money for more information how to resolve this error.
ERROR IN SENDING COMMAND
User will be notified by a short pop-up message in the application if the requested command experienced error in processing. Normally when a command is successfully processed, a short pop-up
message appears ‘SENDING COMMAND’. Typically this error occurs
due to insufficient internet connection or momentary unavailability of internet connection. To resolve, please repeat the command again.
PAIR AGAIN
This is a status shown in application for a particular DRY SIREN. DRY SIREN is not paired with your device and you are unable to control the DRY SIREN. To resolve please pair the device. Please turn to section 11 UNIT TEST – PAIRING. After the pairing is complete, status bar will show ‘CONNECTED’.
DS ERROR
Technical error on the device. Error relates to hardware malfunction. This situation requires professional service. Manufacturer is able to see this error message online if the unit is connected to the internet. Also the error message is accessible by serial port.
14.2 Troubleshooting – save time and money
Problem
Cause / Description
Solution
I am unable to pair the DRY SIREN
Pairing mode is not activated
Press and hold the pairing button for 3 seconds.
DRY SIREN is not visible (mobile device cannot
Press and hold the pairing button for 3 seconds.
Page 61
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 61 P a g e 61 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
locate the DRY SIREN – ‘DRY SIREN ID’
No internet connection
Check your internet connection. Check your WIFI network password. Check that you have internet connection. Sometimes your WIFI network signals properly but your WIFI router does not have internet access. This may the case of malfunction of your ISP (Internet Service Provider) service, hardware problem, etc. Some ISPs tend to turn your internet connection off if your bill is overdue. Alternatively restart your WIFI router.
Incorrect internet password
Check your WIFI network password.
Incorrect DRY SIREN or Mobile application log­in password
Check the passwords on DRY SIREN LICENCE PLATE.
Temporary server unavailability
Please wait 5 minutes and repeat the procedure. If you wait longer than 15minutes and the pairing does not work, contact your distributor or reseller.
I am unable to control my DRY SIREN.
Internet connection problem / pairing problem.
Failure ‘DS UNREACHABLE’ shown in application. Once you see this error, please wait 5-10 seconds. Sometimes when response from server due to internet connection is slower, temporarily (max. 10seconds) the DRY SIREN may be ‘UNREACHABLE’.
1. Check your WIFI network is working and that is it connected to the internet. Sometimes your WIFI network signals properly but your WIFI router does not have internet access. This may the case of malfunction of your ISP (Internet Service Provider) service, hardware problem, etc. Some ISPs tend to turn your internet connection off if your bill is overdue.
2. Check power supply to the ceiling and compressor unit.
3. Restart the DRY SIREN by turning the circuit breaker off and on again. Please allow 60 seconds to boot the unit.
4. Perform pairing process. Please turn to section 11 UNIT TEST – PAIRING.
DRY SIREN does not respond to commands set by application.
You change settings in application but DRY SIREN does not react.
1. Please allow between 1 and 5 seconds to process a command. The time needed to process a command depends on your internet connection. If command is not processed correctly you are advised by a pop-up message ‘ERROR IN SENDING COMMAND’.
2. Make sure you are commanding correct DRY SIREN – please turn to DRY SIREN Serial Number shown in application and compare it to the serial number on a Compressor unit.
Page 62
62 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 62 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
3. Make sure you are not in DEMO Application. DEMO application by ‘TRY ME’.
4. Make sure your DRY SIREN is connected to mains. You can check this by a circuit breaker. Also at ceiling unit you should hear the fan running. Please note that the fan is extremely quiet at normal operations.
5. Alternatively restart your WIFI router.
DRY SIREN does not start although connection seems OK.
The heat pump is not connected to the mains or does not have power supply or circuit breaker is off.
Check the heat pump’s connection to the
mains and circuit breaker. Check order of the phases.
DRY SIREN does not seem to work. I have condensation on windows, humid air, etc.
Desired humidity equals current.
Everything is OK. It is normal that DRY SIREN does not operate because it has reached requested humidity level. If you feel that the air is humid or you have condensation, decrease the requested level of humidity.
DRY SIREN does not work for 3 minutes and then it starts.
This is normal. It is time protection for compressor.
DRY SIREN operates too short
Please allow DRY SIREN to run 24 hours and then check the humidity again.
DRY SIREN is not connected to the mains or does not have power supply or circuit breaker is off.
Check the DRY SIREN’s connection to the
mains and circuit breaker.
DRY SIREN has a technical problem. In such case error
message ‘DS ERROR’ is
shown in application.
Call for service.
Refrigerant leak, not enough refrigerant, restriction or other problem on refrigerant connection.
Check the refrigerant connection and amount of refrigerant. Call for service.
DRY SIREN works but the air is humid, there is condensation on windows, etc.
The pool size is too big for DRY SIREN.
Speak with your distributor or reseller and double check the correct capacity for your pool.
Page 63
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 63 P a g e 63 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Insufficient air flow.
DRY SIREN’s evaporator
or air flow is blocked by dirt, objects, etc.
Please check the DRY SIREN’s ceiling unit
positioning for correct positioning 6.2
APPROPRIATE POSITION OF CEILING UNIT.
Other
Other
Please call for service.
14.3 Maintenance
At least once a year it is necessary to have the unit checked to maintain its service and sustain reliability. Following objects/items to be checked:
- Ceiling unit fixation – threaded bars and nuts holding OK? No crack/damage/bend?...
- Condensate drain – does it drain OK? Clean of dust? No waving? No leakage?...
- Copper pipes – connection OK? No leak? Pressures OK?....
Unit is equipped with 24/7 protection system microSAFETY+. Unless the unit shows error message or unless manufacturer advises your supplier of an error or seeming malfunction, the unit is fully operational and working in order.
14.4 Summer shut-down
Some swimming pool users use to shut the dehumidifier for the summer down. This is mainly due to favorable weather conditions with dry and warm weather. In such case, good air ventilation / natural air exchange does the job of humidity control for few weeks of the year. Although following rapid change in weather (e.g. into rainy days) may result in high humidity in your pool.
In this case please make sure that:
1. Dehumidifier's circuit breaker is off (i.e. dehumidifier does not have any power supply)
2. Dehumidifier is cleaned of dust, fluff or other dirt that may harden / stiffen its structure during
the shutdown period making it hard to remove afterwards.
3. Make sure air inlet and outlet are covered properly so no chlorine or other chemicals are not input into dehumidifier body, especially ventilator bearings. Failing to do so may result in bearings corrosion and failure of the dehumidifier.
4. Manufacturer does not suggest any planned shutdown of the system because during shut down period the humidity is not controlled effectively and automatically.
14.5 Super-chlorination cleaning
Although DRY SIREN is constructed from the most durable and chemically resistant materials, chlorine is a very aggressive substance. Typical pool air chlorine content is up to 1.0ppm. DRY SIREN is equipped with special anti-chlorine protections but cannot protect the unit in environment of higher chlorine than 3.0ppm. When cleaning the pool hall premises by super chlorination please note that DRY SIREN must be off as chlorine concentrations go beyond warranty 3ppm up to 24ppm during super chlorination. The unit must be off and ideally covered.
Page 64
64 | U s e r ´ s a n d i n s t a l l a t i o n m a n u a l D R Y S I R E N
P a g e 64 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
14.6 Start-up during construction
When you start the device at pool which is still under construction, please start the device for a minimum time. Do not run the device longer than few minutes. Dust present in air may be gathered on coils and reduce the water collection capacity. Perform the start-up test and demonstration but keep the unit off and covered until the pool is fully constructed.
14.7 microLIGHT+
DRY SIREN is equipped with Microwell unique system microLIGHT+. This is built into the LED lamp and if activated (mobile application LIGHT settings) microLIGHT+ will signalize the actual level of humidity through color. BLUE – humidity low GREEN – humidity OK YELLOW – humidity is rising above critical level ORANGE – humidity is rising above critical level RED – humidity too high
Ideal humidity in pools is between 55% and 65% RH. Humidity above 70% is too high and continuously deteriorates the materials in the pool and creates a favorable environment for bacteria.
Humidity below 40% dries mucous tissue and is typically considered ‘dry’. With microLIGHT+ you do
not need to understand the figures. When there is green you have no problem. Where there is continuous red, you have a problem.
microLIGHT+ will also signalize your humidity is rising. For example if you have your pool covered and humidity OK, you have green light. When you uncover it and start swimming, it is possible that after some time the microLIGHT+ will turn to some gradient of yellow, orange or red. This signalizes that your humidity is rising. Do not be disturbed, this is normal. Once you stop using the pool for the day and cover it, DRY SIREN should dry the air out in maximum few hours (depending on actual sizing of your pool) and the color should go back to normal, i.e. green. If red persists for longer than 1 day, please check the device.
15. WARRANTY
This dehumidifier is subject to a warranty period of 2 years. It may have been prolonged in your country or by your distributor or reseller. Please contact your reseller or distributor in the case a warranty should be claimed for this dehumidifier.
Please note that no claims will be accepted (warranty void) if:
1. The dehumidifier has been used in an incorrect way, not as described in this manual or in
contrary to this User’s manual or against Safety measures of this User’s manual.
2. The dehumidifier is installed in an incorrect way, not as described in this User’s manual or in
contrary to this User’s manual.
3. The dehumidifier was put to operation by an unauthorized person.
4. The air flow through the dehumidifier is out of the defined borders.
5. The unit has been exposed to a mechanical damage / force or any unauthorized action was
performed on construction of a unit - welding, brazing or has been mechanically damaged resulting in scratches, blends, compressions, pipe ruptures, etc. No mechanical damage is accepted as warranty claim. Transport damages must be claimed in written with transporting agent delivering the device.
Page 65
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 65 P a g e 65 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
6. Chemical conditions in the pool or pool hall have not been within the defined borders (please
see below table Allowed chemical conditions).
7. The dehumidifier suffered frost or overheating damage resulting from ambient air
temperatures out of Temperature operational range.
8. The electric tension source is insufficient or improper in any other way.
Allowed chemical conditions:
Acidity / pH level: pH 7,4 +/- 0,4 Total alkalinity, as CaCO3 ppm 80-120 Total hardness, as CaCo3 ppm 100-300 Total melted dry mass ppm max. 3000
Maximal saline content wt/wt 6% Free chlorine range ppm 1,0-3,0
Superchlorination ppm max. 30 ppm/max. 24 hours Bromine ppm 2-3 Baquacil ppm 25-50 Ozone ppm 0,8-1,0 Maximum copper content ppm max. 2 Aquamatic single purifier ppm max. 2 Tarn clean purifier ppm max. 2 Sherwood purifier ppm max. 2
Table: Allowed chemical conditions
TRANSPORT INSTRUCTIONS
When applying for warranty, please contact your distributor and indicate dehumidifier model and serial number. Please describe the genesis of the failure.
The compressor unit must be transported in the original packaging only and in a vertical upright position. Make sure that the compressor unit cannot turn over or fall down during transport. Never put the compressor unit aside! It may lead to serious compressor damage, unit’s malfuction, damage or failure. This is warranty void. No mechanical damage is accepted as warranty claim unless a written claim had been made with transporting agent delivering the device. When receiving the product please check whether the package is not damaged. Please make a proper documentation of any damage immediately after delivery and claim all
transport damage in written form with the forwarding agent at the delivery.
Page 66
SWIMMING POOL DEHUMIDIFIER DRY SIREN
15.1 INSTALLATION CHECK-LIST AND WARRANTY CARD
FOR THE INSTALLER:
After the installation please go through below check-list. Fill it in, sign, stamp and hand over to customer please.
Ceiling unit fixed and secured with hooks and clips (total 8x)
YES NO
Eventual disruptions in vapor barrier fixed. Vapor barrier not disrupted.
YES NO
Condensate drain of ceiling unit installed correctly (max. 20cm upward, then declivity, no waving, no elevation; end by siphon)
YES NO
Electrical connection done OK YES NO
Refrigerant connection done OK YES NO
Leak test performed without leakage(s) detected
YES NO
System vacuuming performed YES NO
Connecting refrigerant distance
…………………………………… meters
Final refrigerant charge
……………………………………kg R410A
Mobile application successfully paired and tested
YES NO
Bluetooth speaker successfully paired and tested
YES NO
Date: ……………………………………………………
Name:…………………………………………………..
Company stamp:…………………………………………………………. Signature:…………………………………………
SWIMMING POOL DEHUMIDIFIER DRY SIREN MANUFACTURER: MICROWELL, SPOL. S R.O., SNP 2018/42, 92701 SALA, SLOVAKIA. www.microwell.eu, export@microwell.sk.
Page 67
D R Y S I R E N U s e r ´ s a n d i n s t a l l a t i o n m a n u a l | 67 P a g e 67 o f 68 V e r s i o n : 0 1 / 2 0 1 8
SWIMMING POOL DEHUMIDIFIER DRY SIREN
NOTES:
Page 68
SWIMMING POOL DEHUMIDIFIER DRY SIREN
Manufacturer: MICROWELL, spol. s r.o. SNP 2018/42, 927 01 Šaľa, Slovakia tel.: +421/31/702 0540 fax: +421/31/702 0542 e-mail: microwell@microwell.sk w w w . m i c r o w e l l . e u
M a d e i n E U
Distributed by:
Loading...