MICROWELL DRY 300, DRY 500, DRY 300 Plastik, DRY 500 Plastik User Manual

Page 1
MODEL: DRY 300 & 500 PLASTIK
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER
USER´S MANUAL
Page 2
EXHAUST GRID
INTAKE GRID
HYGROSTAT
Do not manipulate with the device with wet hands. Do not spray any flammable substances into the equipment; this might lead to fire. Do not clean the device with water. Do not clean the equipment with aggressive cleaning agents, this might lead to damage or deformations. When cleaning plastic parts do not use any cleaning agents unsuitable for the cover of the dehumidifier
(household cleaning agents, solvents, bleaching agents, benzene, diluents, rough cleaning powder, cresol,
chemical agents). Instead, sweep the dehumidifier cover with a soft cloth or a sponge. Never throw or insert any objects into any hose or opening. The cover is made of plastic. Do not manipulate with lighted cigarette, cigarette ashes, or any other kind of fire
in vicinity to this part. Use this device exclusively for the intended purpose, as described in the attached instruction manual. Do not use
parts which are not recommended. Never block the air opening of the product. Protect the air openings from clogging by particles, hair etc. When the device is not running correctly (smoke, smell etc.), shut down the device by a circuit breaker
in the switchboard. Repair and dislocation must be performed exclusively by a service technician. Before cleaning the device, switch off the circuit breaker in the switchboard. Do not place any objects onto the device. When you do not intend to use the device for a longer time, switch off the circuit breaker.
·
·
·
·
·
·
·
·
·
·
·
·
·
·
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Thank you for your decision to purchase our device. Please read this user manual before switching on the device. Please keep the instructions in this practical guide for your quick know-how. We do not take responsibility or warranty in case of damage, loss or impairment caused by incorrect usage, or by usage for other purposes not described in this manual.
carefully
Contents: 1. Safety measures
2. Specifications for use
3. Instructions for use
4. Instructions for maintenance
5. Servicing the unit
6. Installation guide
7. Technical data
1. SAFETY MEASURES
2. SPECIFICATIONS FOR USE
The units are designed especially for use in indoor swimming pools, spas and saunas. They can also be very useful in laundries, drying rooms and elsewhere. The Microwell DRY 300 PLASTIK is designed for halls with a swimming pool surface area of up to 30 m . The Microwell DRY 500 PLASTIC is designed for halls with a swimming pool surface area of up to 60 m . The condition for using the unit is maintaining the room temperature within the range between a minimum of 22°C and a maximum of 35°C. Ideally, the air in the room should be 2-3 °C warmer than the water in the swimming pool.
2
2
2
Page 3
The built-in humidistat is located at the bottom of the unit, on the left. The built-in hygrostat reads the humidity of the incoming air and, depending on the set value, does or does not switch the compressor on. In the central position of the regulator, the unit secures the average relative humidity of 60%. In indoor swimming pool halls, the correct air humidity should range from 55 to 65%. Decreasing the humidity under this range is not desirable either from the physiological viewpoint orfromtheviewpointof protection of the building. Moreover,itincreasestheelectricity consumption. Thehumidistat can be controlled bythe user.
A view at the hygrostat scale
3.2.
Humidity control by means of a remote humidistat (upon request)
The dehumidifier may be, upon request, equipped with a remote humidistat. In such case, the dehumidifier has two humidistats. One of them is built in the dehumidifier; the other one is remote, in a separate casing. The dehumidifier is primarily controlled by the remote humidistat, provided that the built-in humidistat inthe dehumidifier is set for a higher value than the remote humidistat. If the built-in humidistat were set for a lower value than the remote humidistat, it would take over and the control of the dehumidifier would not react to the signals from the remote humidistat. Therefore, it is best to set the built-in humidistat to the value of 70 % RH or more. The built-in humidistat fulfils a back-up function, should the remote humidistat fail to function or should its battery go flat.It is bestto setthe remotehumidistat tothe value in theextent of55 to65 %RH. Decreasing thehumidity under this range is not desirable either from the physiological viewpoint or from the viewpoint of protection of the building. Moreover, it increases the electricityconsumption.
Left: Remote control receiver, which is built into the dehumidifier by means of distribution connectors Right: External hygrostat with a built-in radio transmitter
Location:
Automatic mode:
Changing the battery:
The remote humidistat is to be located in the most humid area of the room - usually in a corner directly opposite the dehumidifier. This guarantees that the humidity of any area of the swimming pool hall will not exceed the humidity value set in the remote humidistat. The regulator must not be placed on a metal plate because the plate would disturb the high frequency signal and thus prevent the communicationwith the remote-controlled switch inthe unit.
If the airin the room exceeds the desired humidityvalue, the regulatorwill switch the dehumidifier on.
The remote humidistat is charged by a 2 1.5V alkaline battery. Only alkaline batteries may be used, since non-alkaline batteries might leak and damage the whole appliance. The durabilit of a battery is approximately 12 months. The regulator automatically checks the level of its battery. If the battery voltage drops under the permitted value, battery sign on the display of the humidistat comes on. It is then necessary to change the battery as soon as possible. If the battery is not changed and goes flat, the dehumidifier willbe controlled by the built-in humidistat inthe dehumidifier.
y
3. INSTRUCTIONS FOR USE
3.1. Humidity control by means of the built-in humidistat
3
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Page 4
Automatic function during a power failure:
If the power supplyof thedehumidifier isinterrupted duringthe operation of theremote humidistat,then, oncethe powersupply is renewed, the dehumidifier will automatically return to the latest setting. This recovery will occur within 15 minutes after the power supply return.
Setting:
In the setting modethe brightnessof theLCD display canbe set.By pressing+ or buttons the LCD display' s brightness is added or reduced. This settingis for all displays. Setting of codeand test switching, relay for heatingcontrol and for dehumidificationcontrol. Data display aboutthe manufacturer. Average temperature and humidity display for the last 32 hours. Hysteresis setting for 19% humidity range and 0.1-0.9°C temperature range.
4
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Information about the manufacturer
Statistics
Next Confirmation Back
Humidity hysteresis Temperature
hysteresis Back
Heating switch on/off Dehumididication
switch on/off Back
Add brightness Reduce brightness Back
Technical data:
Switch unit
Control unit
Battery longevity
Power supply
Impact
2 x 1,5 AA alkaline batteries
230 V/0,1 VA
min. 1 year (according to battery type)
from 20 up to 30 m in building
(100 m in public place)
Carrier frequence Setting range of requested humidity Setting range of requested temperature
433,92 Mhz
15 - 85% r.h.
Operating difference Measurement precision Measurement sensivity of humidity
5-39°C
5% r.h.
1,5% r.h.
1% r.h.
Measurement sensivity of temperature Adjustable range hysteresis of humidity switching
Adjustable range hysteresis of temperature switching
Enclose temperature
0,1% °C
1-9%r.h.
+20 - +40
°C
Switching capacity Contact
Dimensions Protection type
250V/8V
voltage, switching
71x71x26mm
81x81x36mm
IP 54
0,1 - 0,9
°C
Page 5
Under the insidecover ofthe unit,there is a two-position fan mode switch. In the first position, the fan runs even ifthe compressor of the appliance has stopped continuous operation of the fan. In the second position, the fan only runs simultaneously with the compressor periodical duty of the fan. The continuous operation mode of the fan is preferable, since the humidity reader built in the device continuously readshumidity,and therefore agreater accuracy is reached.At the sametime, continuousoperation of the fan results in better air circulation in the room. The installationwork supplier selects themode of the fan according to therequest of the user.
:
:
3.3. Control of the fan
Switch of the fan operation
Start-up of the compressor is, due to its protection, delayed by 3 minutes. Depending on the humidity of the environment, it may take even longer for compressor to start operating. Once the compressor stops operating, the operation is renewed automatically, at the earliestafter three minutes. The user must nothandle the setting element of thedelay-action relay.
3.4. Control of the compressor
It is necessary to make sure that the suction inlet and the exhaust outlet are not covered. It is forbidden to place towels or clothing items onto the exhaust outlets to dry them. The unit's cover can be cleaned with standard cleaning agents using a soft cloth or a sponge. If water dripping out of the unit, please check the condensed water drain and make sure the pipe is not obstructed.
At least once a year, it is necessary to have the unit checked and cleaned by a service specialist. This is inevitable to secure a long service life of the unit. We do notrecommend the user toclean the interior elements of the unit, as thismight cause a damage to the unit. The unit contains mobile elements and live elements, thereforethe interior parts mayonly be cleaned by a certified electrician trained to servicerefrigerating appliances.
The unit must be installed in compliance with the local installation and electrical installation regulations !
6.1. Location of the unit
To ensure maximum efficiency, it is necessary to install the unit as high above the ground as possible. It is forbidden to install the unit onto the ground. It is essential to ensure good air circulation by allowing at least 150 mm of free space under the unit and at least 200 mm offree space above theunit. For the purposesof maintenance,it is further necessaryto allowat least200 mmof free space on bothsides of the unit.
4. MAINTENANCE INSTRUCTIONS
5. SERVICING THE UNIT
6. INSTALLATION GUIDE
5
Continuous duty of the fan
Periodical duty of the fan
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Page 6
The units havea self-supporting structure and are remarkably easy to install.
A part of the unit accessories is also an installation bracket, which must be fixed onto the wall. The axis of the fixation openings is 210 mm lowerthan the top edge of the unit. The fixation openings are420 mm apart (DRY 300 PLASTIK) or 360mm apart (DRY 500 PLASTIK). Once thebracket is mountedto the wall, itis possible to mount the unitwithout disassembling its cover.
6.2. Mounting the unit
Model DRY 300 PLASTIK
Model DRY 500 PLASTIK
The cover can bedismounted after releasing two screws (DRY 300) or three screws (DRY 500) at the bottom of the unit. Release the screws, pull the bottom part of the cover toward yourself and then, by lifting it shortly, rake down the cover from the rear plate. To mount the cover, carry theprocedure out in reverse order.
6.3. Dismounting and mounting the cover
The unit is designed in such a way that it can be securely mounted and will hold in its place even if lifted accidentally. In the top edges of the back plate, there are screw holes for safety screws, which are accessible after dismounting the front fibreglass cover. Arrows indicate the safety screw holes in the backplate. A safety screw is fastened through a screwhole in the back plateinto a wall plug in thewall. Thiswill prevent the unit from being accidentally pulled out and falling offthe mounting bracket. At the same time, it will securethe perpendicular position of the unit andalign the unit with the wall.
6.4. Securing the position of the unit
6
TOP EDGE OF THE UNIT
BRACKET
SPIRIT LEVEL
MOUNTING HOLES
BACK PLATE
SAFETY SCREW HOLES
TOP EDGE OF THE UNIT
BRACKET
SPIRIT LEVEL
MOUNTING HOLES
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Page 7
Condensed water is drained from the unit by the force of gravity. It is necessary to situate the unit in such a way that there is sufficient declivity forthe drainage of condensed water. Thecondensation product must be drained through a siphon into a sewer or into the outside environment. It is strictly forbidden to drain the condensed water back into the swimming pool, as it may be polluted by bacteria.A pipefor condensatedrainage is ledout at the bottomof the unit, on the left. This pipe is to be inserted into a sewerage pipe withthe inside diameter of atleast 16 mm.
6.5. Drainage of condensate
CONNECTIONS ARE VALID FOR MODELS DRY 300 PLASTIK AS WELL DRY 500PLASTIK - FRONT VIEW
Connection of the unit onto the mains must conform to relevant safety standards. Connection requirements: Power supply: 220­240V / 50Hz. Protection: 10A (DRY 300 PLASTIK) or 16A (DRY 500i) by a protective switch with nominal differential drop-out current not exceeding 30mA. The unit's terminal board for connection onto the electric mainsis situated on the left hand-side of the unit. The main switch of the unit must be situated outside of the swimming pool hall. The main switch of the unit must be bipolar, with switch-out breaking of conductors L and N. An appliance for disconnecting the unit from the mains must be embedded into a firm surface. The distance of contacts, when swithched off, must be at least 3 mm for all poles. The connection of the appliance to the electric mainsmust be carried out by a certified electrician.
6.6 Connection of the unit onto the mains
An example of preparation of electric power supply, condensate drainage
and mounting of the bracket
7
ATTACHMENT OF THE LPHW HEATER ELEMENT TO THE DISTRIBUTION OF THE HEATING WATER (FROM THE SIDE)
- MODELS WITH THE LPHW HEATER ELEMENT ONLY
THREAD G ½ '’ MALE
CONDENSATE DRAINAGE (FROM THE REAR) PIPING WITH MINIMUM INTERNAL DIAMETER OF 16 mm
POWER SUPPLY CYSY WIRE 3C x 1.5 mm
(FROM THE REAR)
2
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Page 8
LOCATION OF THE EQUIPMENT
ZONE 1, IPX4
ZONE 2, IPX2
OUTSIDE THE ZONES
In the distance of1250 mmor less from theswimming pool edge, the bottom edge of the unit must be in the height of 2500 mm from the swimming pool surface; if it is embedded under the floor, then 2500 mm fromthe floor.
At least 1250mm (i.e. outof the reachof the hand)from the lateral edge of the washbasin, in theminimum height of 1200 mm above ground. It cannot be placedabove the wash basin.
In the distance of at least 1500 mm from the verticalplane around the jumping platforms, diving boards and 2500 mm above the highest surface, where persons are likely to stay.
If the unitis in the distance of less or equal to 1250 mm horizontally from the edge of the swimming pool, then it must be raised up to the height of 2500 mm from the swimming pool surface; if the pool is embedded under the floor, then the unit must be raised up to the height of 2500 mm from the floor.
It is inevirable to locatethe unitoutside thezones, wherecleaning byjet water issupposed. Connectionof theunit tothe mainsand its protection must correspond with the applicable standards. Electrical supply of the unit must be carried out by a protective isolating transformer or it must be protected by a current protective switch with a nominal differential cut-off current not exceeding 30 mA.
SWIMMING POOL
The location must be in compliance with the HD 384.7.702 S1, IEC 60364-7-702 standard.
It is recommended to situate the unit outside zones 0, 1 and 2. In case the unit is situated into zones 2 or 1, it must be adhered to the HD, IEC standard.
SWIMMING POOL
Swimming pools which are not
cleaned by jet water
in the distance of 1250 to 2000 mm from the swimming pool edge,
the unit must adhere to the standard and in the height
of at least 300 mm from the floor
HD, IEC
Swimming pools which
are not cleaned by jet water
In the distance of 2000 to 3500 mm from the swimming pool edge, the unit must adhere to the HD, IEC standard and a minimum 150 mm elevation above the ground is required for sufficient air flow. Installing the unit on the floor is prohibited.
At least 1250 mm (i.e. out of the reach of the hand) from the lateral edge of the shower cabinet. It cannot be placed above theshower cabinet.
OUTSIDE THE ZONES
OUTSIDE THE ZONES
8
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Page 9
The LPHW heater elements are supplied only to order. Connection of the hot water heater element onto the LPHW plumbing is carried out similarlyto the installation of radiators. On the feeder pipe, it is connected by a control valve and onthe return pipe by a closing screw joint. The LPHW is not supplied with a control valve and a screw joint; these are supplied by the supplier of the heating.
6.7. LPHW heater element - to order
Attachment threading of the hot water heating element
After installing the LPHW plumbing and leading the LPHW into the element under pressure, it is necessary to bleed the heater element. The bleeding valve is located on the feeder pipe of the LPHW heater element. To secure that the LPHW heater element works always at full heat output, blowing onto the unit by a fan must be provided even when no dehumidification is being performed. Therefore, when using the LPHW heater element, the switch of fan operation must be switched into the position of continuous operation.
6.8. -Mounting behind the wall to order
The dehumidifiers are simply adapted also to installation behind the wall into the adjacent room. In such case, only two grids are visible in the swimming pool area. These are the same grids which are, in the basic configuration, installed on the dehumidifier's cover. In the configuration for installation behind the wall, conduit adapters are screwed onto the dehumidifier's cover. The adapters are delivered for passage through the wall of the length of 400 mm. In the place of installation, they are shortened from the side ofthe swimming pool as necessary.
View from the adjacent room
View from the swimming pool hall
9
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Page 10
DRY 500 PLASTIK
DRY 300 PLASTIK
TYPE UNITS
m
2
30 60
For swimming pools with a maximum surface area
at 30°C and 70% RH
at 30°C and 60% RH
at 30°C and 80% RH
l/24 h l/24 h
l/24 h
33
66 42 82 47
101
Operating temperature range Operating humidity range Air flow
°C
%
m/h
3
22-35
20-100
440
22-35
20-100
740
Sound pressure level at 1 m free field Heat output Power consumption Voltage
dB (A)
42 42
W
W
1900
700
3500 1000
V/Hz/f 230/50/1 230/50/1
Operating current / Starting current Protection
Conductor
A
4,4 / 15,8
7,5/30
A
mm
2
10 16
CYSY 3C x 1,5
CYSY 3C x 1,5
Condensate drain - minimum inside diameter Dimensions (width x height x depth)
Dimensions of package (width x height x depth) Weight - net / in package
d16 d16
mm
780 x 653 x 255
mm mm
kg
850 x 810 x 345
40/46
1245 x 653 x 255 1315 x 810 x 345
60/69
Remote control - wireless - with an adjustable dial
LPHW heater element - heat output at water temp. 90/70°C
Connecting thread of the LPHW heater element
yes/no
yes
yes
W
thread
2000
4000
male G 1/2”
male G 1/2”
OPTIONAL EXTRAS
Dehumidifier efficiency rate
DER
2,4
2,7
Max. pressures in the system HP/LP
bar
20,6/10,6 20,6/10,6
Refrigerant - R 407 C
kg
0,5 0,75
Coverage
IP
44 44
DEHUMIDIFICATION PERFORMANCE:
7. TECHNICAL DATA
PIPING 615x65mm - DRY 300 PLASTIK (PIPING 1075x65mm - DRY 500 PLASTIK)
FLANGED CONNECTION
R100
ELBOW 135° 615x65mm - DRY 300i (ELBOW 135° 1075x65mm - DRY 500i)
25 mm WIDE FLANGE
DEHUMIDIFIER
R100
SHORTEN THE PIPING AS NECESSARY
PIPING 615x65mm - DRY 300 PLASTIK (PIPING 1075x65mm - DRY 500 PLASTIK)
FLANGED CONNECTION
ELBOW 135° 615x65mm - DRY 300PLASTIK (ELBOW 135° 1075x65mm - DRY 500 PLASTIK)
25 mm WIDE FLANGE
SHORTEN THE PIPING AS NECESSARY
MOUNTING FROM INSIDE: REINFORCE THE PIPING TO THE VALUE OF 65 MM AND FROM THE OUTER SIDE - PUR FOAM HAS TO BE GLUED TO THE MASONRY. AFTER HARDENING OF THE PUR FOAM, REMOVE THE FORTIFICATION AND MOUNT THE GRID.
MOUNTING FROM INSIDE: REINFORCE THE PIPING TO THE VALUE OF 65 MM AND FROM THE OUTER SIDE - PUR FOAM HAS TO BE GLUED TO THE MASONRY. AFTER HARDENING OF THE PUR FOAM, REMOVE THE FORTIFICATION AND MOUNT THE GRID.
10
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Page 11
DIMENSIONS DRY 300 PLASTIK
DIMENSIONS DRY 500 PLASTIK
FRONT VIEW
VIEW FROM BELOW
SIDE VIEW
FRONT VIEW
VIEW FROM BELOW
SIDE VIEW
BRACKET
BRACKET
ATTACHMENT OF THE LPHW HEATER ELEMENT TO THE DISTRIBUTION OF THE HEATING WATER
- (MODELS WITH THE LPHW HEATER ELEMENT ONLY)
THREADG½'’
ATTACHMENT OF THE LPHW HEATER ELEMENT TO THE DISTRIBUTION OF THE HEATING WATER
- (MODELS WITH THE LPHW HEATER ELEMENT ONLY)
THREADG½'’
THE POSITION AGAINST GETTING LOOSE FROM THE BRACKET (FROM THE REAR)
THE POSITION AGAINST GETTING LOOSE FROM THE BRACKET (FROM THE REAR)
THE POSITION AGAINST GETTING LOOSE FROM THE BRACKET (FROM THE REAR)
THE POSITION AGAINST GETTING LOOSE FROM THE BRACKET (FROM THE REAR)
CONDENSATE DRAINAGE (FROM THE REAR) PIPING WITH MINIMUM INTERNAL DIAMETER OF 16 mm
CONDENSATE DRAINAGE (FROM THE REAR) PIPING WITH MINIMUM INTERNAL DIAMETER OF 16 mm
POWER SUPPLY CYSY WIRE 3C x 1.5 mm
(FROM THE REAR)
2
POWER SUPPLY CYSY WIRE 3C x 1.5 mm
(FROM THE REAR)
2
11
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Page 12
STARTING RELAY
THERMOSTAT
-1 Ѱ
HUMIDISTAT
WIRING DIAGRAM (DRY 300 PLASTIK)
WIRING DIAGRAM (DRY 500 PLASTIK)
12
CIRCUIT LAYOUT AND DETAILED WIRING DIAGRAM OF MODEL MICROWELL DRY 300 PLASTIK
NOTE: Dashed line indicates conductors which are to be connected during a subsequent installation of a remote humidistat
HUMIDISTAT
THERMOSTAT
-1 Ѱ
HIGH PRESSURE SAFETY CUTOUT 2,5 ÌÐà
LOW PRESSURE SAFETY CUTOUT 0,2 ÌÐà
DELAY-ACTIONRELAY 3 min.
STARTING RELAY
RECEIVER ONLY MODELS WITH
REMOTE CONTROL
-
PERIODICITY DUTY
CONTINUOUS OPERATION
FAN MODE SWITCH
CONDENSER OF FAN
COMPRESSOR
CONDENSER OF COMPRESSOR
TERMINAL BOARD
HEAT PROTECTION
COMPRESSOR
STARTING RELAY
CONDENS. COMPRES.
CONTINUOULSY
SWITCH
PERIODICALLY
THERMOSTAT
HUMIDISTAT
DELAY­ACTION RELAY
HIGH PRESSURE SAFETY CUTOUT
LOW PRESSURE SAFETY CUTOUT
FAN
FAN
CONDENS. FAN
CONNECTOR
CONDUCTOR COLOURS
CI BLACK M BLUE
S GRAY O ORANGE
H BROWN
CE RED B WHITE F PURPLE Z GREEN-YELLOW Z GREEN  YELLOW
CIRCUIT LAYOUT AND DETAILED WIRING DIAGRAM OF MODEL MICROWELL DRY 500 PLASTIK
HIGH PRESSURE SAFETY CUTOUT 2,5 ÌÐà
LOW PRESSURE SAFETY CUTOUT 0,2 ÌÐà
DELAY-ACTIONRELAY 3 min.
RECEIVER ONLY MODELS WITH REMOTE CONTROL-
RECEIVER ONLY MODELS WITH
REMOTE CONTROL
-
PERIODICITY DUTY
CONTINUOUS OPERATION
FAN MODE SWITCH
COMPRESSOR
CONDENSER OF COMPRESSOR
TERMINAL BOARD
HEAT PROTECTION
COMPRESSOR
STARTING RELAY
CONDENS. COMPRES.
CONTINUOULSY
SWITCH
PERIODICALLY
THERMOSTAT
HUMIDISTAT
DELAY­ACTION RELAY
HIGH PRESSURE SAFETY CUTOUT
LOW PRESSURE SAFETY CUTOUT
FAN
FAN
RECEIVER ONLY MODELS WITH REMOTE CONTROL-
CONDUCTOR COLOURS
CI BLACK M BLUE
S GRAY O ORANGE
H BROWN
CE RED B WHITE F PURPLE Z GREEN-YELLOW Z GREEN  YELLOW
CONNECTOR
NOTE: Dashed line indicates conductors which are to be connected during a subsequent installation of a remote humidistat
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Page 13
OUTPUT DIAGRAM OF DEHUMIDIFICATION (DRY 300 PLASTIK)
Dehumidification output
Relative humidity
Dehumidification output
Air temperature
OUTPUT DIAGRAM OF DEHUMIDIFICATION (DRY 500 PLASTIK)
Air temperature
Relative humidity
13
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
0
10
20
30
40
50
60
15 20 25 30 35
(°C)
(l/24h)
0
20
40
60
80
100
120
15 20 25 30 35
(°C)
(l/24h)
Page 14
EN - WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
14
8. WARRANTY CONDITIONS
The following exceptions stated by Microwell, Ltd. apply within the warranty. No claims will be accepted if:
1. The dehumidifier is used in an incorrect way, not as described in this manual.
2.
3. The dehumidifier was put to operation by an unauthorized person.
4. The air flow through the dehumidifier is out of the defined borders.
5. The water flow
6.
The dehumidifier is installed in an incorrect way, not as described in this manual.
through the dehumidifier is out of the defined borders.
´s
7.
8.
The water pH level and/or chemical condition is out of the defined borders:
The dehumidifier suffered frost damage.
The electric tension source is insufficient or improper in any other way.
IN CASE OF ANY UNCERTAINTY YOU MAY HAVE, PLEASE FEEL FREE TO CONTACT US !
Acidity / pH level: pH 7,4 +/- 0,4
Total alkalinity, as CaCO3 ppm 80-120
Total hardness, as CaCo3 ppm 100-300
Total melted dry mass ppm max. 3000
Maximal saline content wt/wt 6%
Free chlorine range ppm 1,0-3,0
Superchlorination ppm max. 30 ppm/max. 24 hours
Bromine ppm 2-3
Baquacil ppm 25-50
Ozone ppm 0,8-1,0
Maximum copper content ppm max. 2
Aquamatic single purifier ppm max. 2
Tarn clean purifier ppm max. 2
Sherwood purifier ppm max. 2
TRANSPORT INSTRUCTIONS:
The dehumidifiers must be transported only in the original packaging and in a vertical position. Make sure that the dehumidifier cannot turn over or fall down during transportation. Do never put the dehumidifier aside! It may lead to serious No claims are acceptedin caseof any damagecaused bytransportation. When receiving the product delivered toyou, please check whether the package is not damaged.If anykind of objections occurs, please make a proper documentation of them.
compressor damage!
NOTE:
When applying
number of your dehumidifier. The registration card will be then sent to you for
filling in. In case you
These information will help usin makingproper diagnosing ofyour unit andthe servicecan
be performed with a minimumtime delay.
applicable warranty, the registration card that ensures applicable warranties must be returned. In case you cannot find the registration card of your dehumidifier, please contact the Service department of Microwell, Ltd. ­indicated your name, address and serial
have any service or technique related questions, please specify the model number and serial
number of your dehumidifier.
Page 15
Page 16
SNP 2018/42 927 01 Ša¾a, Slovakia Phone: +421 31 7020 540-1 Fax: +421 31 7020 542 E-mail: microwell@microwell.sk www.microwell.sk