MICROWELL DRY 300, DRY 500, DRY 300 Plastik, DRY 500 Plastik User Manual

MODEL: DRY 300 & 500 PLASTIK
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER
USER´S MANUAL
EXHAUST GRID
INTAKE GRID
HYGROSTAT
Do not manipulate with the device with wet hands. Do not spray any flammable substances into the equipment; this might lead to fire. Do not clean the device with water. Do not clean the equipment with aggressive cleaning agents, this might lead to damage or deformations. When cleaning plastic parts do not use any cleaning agents unsuitable for the cover of the dehumidifier
(household cleaning agents, solvents, bleaching agents, benzene, diluents, rough cleaning powder, cresol,
chemical agents). Instead, sweep the dehumidifier cover with a soft cloth or a sponge. Never throw or insert any objects into any hose or opening. The cover is made of plastic. Do not manipulate with lighted cigarette, cigarette ashes, or any other kind of fire
in vicinity to this part. Use this device exclusively for the intended purpose, as described in the attached instruction manual. Do not use
parts which are not recommended. Never block the air opening of the product. Protect the air openings from clogging by particles, hair etc. When the device is not running correctly (smoke, smell etc.), shut down the device by a circuit breaker
in the switchboard. Repair and dislocation must be performed exclusively by a service technician. Before cleaning the device, switch off the circuit breaker in the switchboard. Do not place any objects onto the device. When you do not intend to use the device for a longer time, switch off the circuit breaker.
·
·
·
·
·
·
·
·
·
·
·
·
·
·
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Thank you for your decision to purchase our device. Please read this user manual before switching on the device. Please keep the instructions in this practical guide for your quick know-how. We do not take responsibility or warranty in case of damage, loss or impairment caused by incorrect usage, or by usage for other purposes not described in this manual.
carefully
Contents: 1. Safety measures
2. Specifications for use
3. Instructions for use
4. Instructions for maintenance
5. Servicing the unit
6. Installation guide
7. Technical data
1. SAFETY MEASURES
2. SPECIFICATIONS FOR USE
The units are designed especially for use in indoor swimming pools, spas and saunas. They can also be very useful in laundries, drying rooms and elsewhere. The Microwell DRY 300 PLASTIK is designed for halls with a swimming pool surface area of up to 30 m . The Microwell DRY 500 PLASTIC is designed for halls with a swimming pool surface area of up to 60 m . The condition for using the unit is maintaining the room temperature within the range between a minimum of 22°C and a maximum of 35°C. Ideally, the air in the room should be 2-3 °C warmer than the water in the swimming pool.
2
2
2
The built-in humidistat is located at the bottom of the unit, on the left. The built-in hygrostat reads the humidity of the incoming air and, depending on the set value, does or does not switch the compressor on. In the central position of the regulator, the unit secures the average relative humidity of 60%. In indoor swimming pool halls, the correct air humidity should range from 55 to 65%. Decreasing the humidity under this range is not desirable either from the physiological viewpoint orfromtheviewpointof protection of the building. Moreover,itincreasestheelectricity consumption. Thehumidistat can be controlled bythe user.
A view at the hygrostat scale
3.2.
Humidity control by means of a remote humidistat (upon request)
The dehumidifier may be, upon request, equipped with a remote humidistat. In such case, the dehumidifier has two humidistats. One of them is built in the dehumidifier; the other one is remote, in a separate casing. The dehumidifier is primarily controlled by the remote humidistat, provided that the built-in humidistat inthe dehumidifier is set for a higher value than the remote humidistat. If the built-in humidistat were set for a lower value than the remote humidistat, it would take over and the control of the dehumidifier would not react to the signals from the remote humidistat. Therefore, it is best to set the built-in humidistat to the value of 70 % RH or more. The built-in humidistat fulfils a back-up function, should the remote humidistat fail to function or should its battery go flat.It is bestto setthe remotehumidistat tothe value in theextent of55 to65 %RH. Decreasing thehumidity under this range is not desirable either from the physiological viewpoint or from the viewpoint of protection of the building. Moreover, it increases the electricityconsumption.
Left: Remote control receiver, which is built into the dehumidifier by means of distribution connectors Right: External hygrostat with a built-in radio transmitter
Location:
Automatic mode:
Changing the battery:
The remote humidistat is to be located in the most humid area of the room - usually in a corner directly opposite the dehumidifier. This guarantees that the humidity of any area of the swimming pool hall will not exceed the humidity value set in the remote humidistat. The regulator must not be placed on a metal plate because the plate would disturb the high frequency signal and thus prevent the communicationwith the remote-controlled switch inthe unit.
If the airin the room exceeds the desired humidityvalue, the regulatorwill switch the dehumidifier on.
The remote humidistat is charged by a 2 1.5V alkaline battery. Only alkaline batteries may be used, since non-alkaline batteries might leak and damage the whole appliance. The durabilit of a battery is approximately 12 months. The regulator automatically checks the level of its battery. If the battery voltage drops under the permitted value, battery sign on the display of the humidistat comes on. It is then necessary to change the battery as soon as possible. If the battery is not changed and goes flat, the dehumidifier willbe controlled by the built-in humidistat inthe dehumidifier.
y
3. INSTRUCTIONS FOR USE
3.1. Humidity control by means of the built-in humidistat
3
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Automatic function during a power failure:
If the power supplyof thedehumidifier isinterrupted duringthe operation of theremote humidistat,then, oncethe powersupply is renewed, the dehumidifier will automatically return to the latest setting. This recovery will occur within 15 minutes after the power supply return.
Setting:
In the setting modethe brightnessof theLCD display canbe set.By pressing+ or buttons the LCD display' s brightness is added or reduced. This settingis for all displays. Setting of codeand test switching, relay for heatingcontrol and for dehumidificationcontrol. Data display aboutthe manufacturer. Average temperature and humidity display for the last 32 hours. Hysteresis setting for 19% humidity range and 0.1-0.9°C temperature range.
4
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Information about the manufacturer
Statistics
Next Confirmation Back
Humidity hysteresis Temperature
hysteresis Back
Heating switch on/off Dehumididication
switch on/off Back
Add brightness Reduce brightness Back
Technical data:
Switch unit
Control unit
Battery longevity
Power supply
Impact
2 x 1,5 AA alkaline batteries
230 V/0,1 VA
min. 1 year (according to battery type)
from 20 up to 30 m in building
(100 m in public place)
Carrier frequence Setting range of requested humidity Setting range of requested temperature
433,92 Mhz
15 - 85% r.h.
Operating difference Measurement precision Measurement sensivity of humidity
5-39°C
5% r.h.
1,5% r.h.
1% r.h.
Measurement sensivity of temperature Adjustable range hysteresis of humidity switching
Adjustable range hysteresis of temperature switching
Enclose temperature
0,1% °C
1-9%r.h.
+20 - +40
°C
Switching capacity Contact
Dimensions Protection type
250V/8V
voltage, switching
71x71x26mm
81x81x36mm
IP 54
0,1 - 0,9
°C
Under the insidecover ofthe unit,there is a two-position fan mode switch. In the first position, the fan runs even ifthe compressor of the appliance has stopped continuous operation of the fan. In the second position, the fan only runs simultaneously with the compressor periodical duty of the fan. The continuous operation mode of the fan is preferable, since the humidity reader built in the device continuously readshumidity,and therefore agreater accuracy is reached.At the sametime, continuousoperation of the fan results in better air circulation in the room. The installationwork supplier selects themode of the fan according to therequest of the user.
:
:
3.3. Control of the fan
Switch of the fan operation
Start-up of the compressor is, due to its protection, delayed by 3 minutes. Depending on the humidity of the environment, it may take even longer for compressor to start operating. Once the compressor stops operating, the operation is renewed automatically, at the earliestafter three minutes. The user must nothandle the setting element of thedelay-action relay.
3.4. Control of the compressor
It is necessary to make sure that the suction inlet and the exhaust outlet are not covered. It is forbidden to place towels or clothing items onto the exhaust outlets to dry them. The unit's cover can be cleaned with standard cleaning agents using a soft cloth or a sponge. If water dripping out of the unit, please check the condensed water drain and make sure the pipe is not obstructed.
At least once a year, it is necessary to have the unit checked and cleaned by a service specialist. This is inevitable to secure a long service life of the unit. We do notrecommend the user toclean the interior elements of the unit, as thismight cause a damage to the unit. The unit contains mobile elements and live elements, thereforethe interior parts mayonly be cleaned by a certified electrician trained to servicerefrigerating appliances.
The unit must be installed in compliance with the local installation and electrical installation regulations !
6.1. Location of the unit
To ensure maximum efficiency, it is necessary to install the unit as high above the ground as possible. It is forbidden to install the unit onto the ground. It is essential to ensure good air circulation by allowing at least 150 mm of free space under the unit and at least 200 mm offree space above theunit. For the purposesof maintenance,it is further necessaryto allowat least200 mmof free space on bothsides of the unit.
4. MAINTENANCE INSTRUCTIONS
5. SERVICING THE UNIT
6. INSTALLATION GUIDE
5
Continuous duty of the fan
Periodical duty of the fan
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL