MICROWELL DRY 300, DRY 400, DRY 500 PLASTIK User Manual

MODEL: DRY 300/400/500 PLASTIK
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER
USER´S MANUAL
l Do not manipulate with the device with wet hands. l Do not spray any flammable substances into the equipment; this might lead to fire. l Do not clean the device with water. l Do not clean the equipment with aggressive cleaning agents, this might lead to damage or deformations. l When cleaning plastic parts do not use any cleaning agents unsuitable for the cover of the dehumidifier (household
cleaning agents, solvents, bleaching agents, benzene, diluents, rough cleaning powder, cresol, chemical agents). Instead, sweep the dehumidifier cover with a soft cloth or a sponge.
l Never throw or insert any objects into any hose or opening. l The cover is made of plastic. Do not manipulate with lighted cigarette, cigarette ashes, or any other kind of fire in
vicinity to this part.
l Use this device exclusively for the intended purpose, as described in the attached instruction manual. Do not use
parts which are not recommended.
l Never block the air opening of the product. Protect the air openings from clogging by particles, hair etc. l When the device is not running correctly (smoke, smell etc.), shut down the device by a circuit breaker in the
switchboard.
l Repair and dislocation must be performed exclusively by a service technician. l Before cleaning the device, switch off the circuit breaker in the switchboard. l Do not place any objects onto the device. l When you do not intend to use the device for a longer time, switch off the circuit breaker.
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Thank you for your decision to purchase our device. Please read this user manual carefully before switching on the device. Please keep the instructions in this practical guide for your quick know-how. We do not take responsibility or warranty in case of damage, loss or impairment caused by incorrect usage, or by usage for other purposes not described in this manual.
Contents: 1. Safety measures
2. Specifications for use
3. Instructions for use
4. Instructions for maintenance
5. Servicing the unit
6. Installation guide
7. Technical data
1. SAFETY MEASURES
2. SPECIFICATIONS FOR USE
The units are designed especially for use in indoor swimming pools, spas and saunas. They can also be very useful in laundries, drying rooms and elsewhere.
2
The Microwell DRY 300 PLASTIK is designed for halls with a swimming pool surface area of up to 30 m .
2
The Microwell DRY 500 PLASTIK is designed for halls with a swimming pool surface area of up to 60 m . The condition for using the unit is maintaining the room temperature within the range between a minimum of 22°C and a maximum of 35°C. Ideally, the air in the room should be 2-3 °C warmer than the water in the swimming pool.
Microwell DRY 400 PLASTIK is designed for rooms with a swimming pool, which surface is up to 45 m².
2
INTAKE GRID
HYGROSTAT
UNIT COVER
EXHAUST GRID
The built-in humidistat is located at the bottom of the unit, on the left. The built-in hygrostat reads the humidity of the incoming air and, depending on the set value, does or does not switch the compressor on. In the central position of the regulator, the unit secures the average relative humidity of 60%. In indoor swimming pool halls, the correct air humidity should range from 55 to 65%. Decreasing the humidity under this range is not desirable either from the physiological viewpoint or from the viewpoint of protection of the building. Moreover, it increases the electricity consumption. The humidistat can be controlled by the user.
A view at the hygrostat scale
3.2. Remote control
On demand a dehumidifier can be controlled by remote humidistat & thermostat DRY EASY 300. If so, User’s manual is attached to this Manual.
3. INSTRUCTIONS FOR USE
3.1. Humidity control by means of the built-in humidistat
3
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Under the inside cover of the unit, there is a two-position fan mode switch. In the first position, the fan runs even if the compressor of the appliance has stopped: continuous operation of the fan. In the second position, the fan only runs simultaneously with the compressor: periodical duty of the fan. The continuous operation mode of the fan is preferable, since the humidity reader built in the device continuously reads humidity, and therefore a greater accuracy is reached. At the same time, continuous operation of the fan results in better air circulation in the room. The installation work supplier selects the mode of the fan according to the request of the user.
3.3. Control of the fan
Switch of the fan operation
Continuous duty of the fan
Periodical duty of the fan
4
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Under the inside cover of the unit, there is a two-position fan mode switch. In the first position, the fan runs even if the compressor of the appliance has stopped: continuous operation of the fan. In the second position, the fan only runs simultaneously with the compressor: periodical duty of the fan. The continuous operation mode of the fan is preferable, since the humidity reader built in the device continuously reads humidity, and therefore a greater accuracy is reached. At the same time, continuous operation of the fan results in better air circulation in the room. The installation work supplier selects the mode of the fan according to the request of the user.
3.3. Control of the fan
Switch of the fan operation
Start-up of the compressor is, due to its protection, delayed by 3 minutes. Depending on the humidity of the environment, it may take even longer for compressor to start operating. Once the compressor stops operating, the operation is renewed automatically, at the earliest after three minutes. The user must not handle the setting element of the delay-action relay.
3.4. Control of the compressor
It is necessary to make sure that the suction inlet and the exhaust outlet are not covered. It is forbidden to place towels or clothing items onto the exhaust outlets to dry them. The unit's cover can be cleaned with standard cleaning agents using a soft cloth or a sponge. If water dripping out of the unit, please check the condensed water drain and make sure the pipe is not obstructed.
At least once a year, it is necessary to have the unit checked and cleaned by a service specialist. This is inevitable to secure a long service life of the unit. We do not recommend the user to clean the interior elements of the unit, as this might cause a damage to the unit. The unit contains mobile elements and live elements, therefore the interior parts may only be cleaned by a certified electrician trained to service refrigerating appliances.
The unit must be installed in compliance with the local installation and electrical installation regulations !
6.1. Location of the unit
The unit is to be installed on the wall or on the mobile stand. To ensure the right operations of the dehumidifier and its maximum efficiency in terms of humidity control, it is necessary to ensure proper air circulation into and from the dehumidifier. This requires the actual unit placement appropriately into the swimming pool hall respecting basic prerequisites of air circulation and air flow. It is strictly forbidden to install the unit just below the ceiling. At least 200mm of a free space must be kept above the unit and at least 150mm below the unit. Each swimming pool hall is individual thus a special care needs to be taken to choose a proper dehumidifier placement. It is forbidden to install the unit on the ground. It is also strictly forbidden to block the air inlet and outlet with any objects (canoe, buckets, ceiling beams, etc.). For maintenance purposes please keep free space of 200mm on both sides of the dehumidifier.
4. MAINTENANCE INSTRUCTIONS
5. SERVICING THE UNIT
6. INSTALLATION GUIDE
Continuous duty of the fan
Periodical duty of the fan
5
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
The units have a self-supporting structure and are remarkably easy to install.
A part of the unit accessories is also an installation bracket, which must be fixed onto the wall. The axis of the fixation openings is 210 mm lower than the top edge of the unit. The fixation openings are 420 mm apart (DRY 300/400 PLASTIK) or 360 mm apart (DRY 500 PLASTIK). Once the bracket is mounted to the wall, it is possible to mount the unit without disassembling its cover.
6.2. Mounting the unit
Model DRY 300/400 PLASTIK
Model DRY 500 PLASTIK
The cover can be dismounted after releasing two screws (DRY 300/400) or three screws (DRY 500) at the bottom of the unit. Release the screws, pull the bottom part of the cover toward yourself and then, by lifting it shortly, rake down the cover from the rear plate. To mount the cover, carry the procedure out in reverse order.
6.3. Dismounting and mounting the cover
The unit is designed in such a way that it can be securely mounted and will hold in its place even if lifted accidentally. In the top edges of the back plate, there are screw holes for safety screws, which are accessible after dismounting the front fibreglass cover. Arrows indicate the safety screw holes in the back plate. A safety screw is fastened through a screw hole in the back plate into a wall plug in the wall. This will prevent the unit from being accidentally pulled out and falling off the mounting bracket. At the same time, it will secure the perpendicular position of the unit and align the unit with the wall.
6.4. Securing the position of the unit
TOP EDGE OF THE UNIT
BRACKET
SPIRIT LEVEL
MOUNTING HOLES
BACK PLATE
SAFETY SCREW HOLES
TOP EDGE OF THE UNIT
BRACKET
SPIRIT LEVEL
MOUNTING HOLES
6
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
Condensed water is drained from the unit by the force of gravity. It is necessary to situate the unit in such a way that there is sufficient declivity for the drainage of condensed water. The condensation product must be drained through a siphon into a sewer or into the outside environment. It is strictly forbidden to drain the condensed water back into the swimming pool, as it may be polluted by bacteria. A pipe for condensate drainage is led out at the bottom of the unit, on the left. This pipe is to be inserted into a sewerage pipe with the inside diameter of at least 18 mm.
6.5. Drainage of condensate
CONNECTIONS ARE VALID FOR MODELS DRY 300/400 PLASTIK AS WELL DRY 500 PLASTIK - FRONT VIEW
Connection of the unit onto the mains must conform to relevant safety standards. Connection requirements: Power supply: 220­240V / 50Hz. Protection: 10A (DRY 300/400 PLASTIK) or 16A (DRY 500 PLASTIK) by a protective switch with nominal differential drop-out current not exceeding 30 mA. The unit's terminal board for connection onto the electric mains is situated on the left hand­side of the unit. The main switch of the unit must be situated outside of the swimming pool hall. The main switch of the unit must be bipolar, with switch-out breaking of conductors L and N. An appliance for disconnecting the unit from the mains must be embedded into a firm surface. The distance of contacts, when swithched off, must be at least 3 mm for all poles. The connection of the
appliance to the electric mains must be carried out by a certified electrician.
6.6 Connection of the unit onto the mains
An example of preparation of electric power supply, condensate drainage
and mounting of the bracket
ATTACHMENT OF THE HEATER ELEMENT TO THE DISTRIBUTION OF THE HEATING WATER
THREAD G ½ '’ MALE
OPTIONS LOCATION OF CONNECTION
POWER SUPPLY
2
CYSY WIRE 3C x 1.5 (3C x 2.5) mm
(FROM THE REAR)
1
17
1
17
50
15
35
50
100
35
40
50
CONDENSATE DRAINAGE (FROM THE REAR) PIPING WITH MINIMUM INTERNAL DIAMETER OF 18 mm
A1 - FROM LEFT SIDE A2 - FROM RIGHT SIDE A3 - FROM BACK SIDE
7
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
LOCATION OF THE EQUIPMENT
ZONE 1, IPX4
ZONE 2, IPX2
OUTSIDE THE ZONES
In the distance of 1250 mm or less from the swimming pool edge, the bottom edge of the unit must be in the height of 2500 mm from the swimming pool surface; if it is embedded under the floor, then 2500 mm from the floor.
At least 1250 mm (i.e. out of the reach of the hand) from the lateral edge of the wash basin, in the minimum height of 1200 mm above ground. It cannot be placed above the wash basin.
In the distance of at least 1500 mm from the vertical plane around the jumping platforms, diving boards and 2500 mm above the highest surface, where persons are likely to stay.
If the unit is in the distance of less or equal to 1250 mm horizontally from the edge of the swimming pool, then it must be raised up to the height of 2500 mm from the swimming pool surface; if the pool is embedded under the floor, then the unit must be raised up to the height of 2500 mm from the floor.
It is inevirable to locate the unit outside the zones, where cleaning by jet water is supposed. Connection of the unit to the mains and its protection must correspond with the applicable standards. Electrical supply of the unit must be carried out by a protective isolating transformer or it must be protected by a current protective switch with a nominal differential cut-off current not exceeding 30 mA.
SWIMMING POOL
The location must be in compliance with the HD 384.7.702 S1, IEC 60364-7-702 standard.
It is recommended to situate the unit outside zones 0, 1 and 2. In case the unit is situated into zones 2 or 1, it must be adhered to the HD, IEC standard.
SWIMMING POOL
Swimming pools which are not
cleaned by jet water
in the distance of 1250 to 2000 mm from the swimming pool edge,
the unit must adhere to the HD, IEC standard and in the height
of at least 300 mm from the floor
Swimming pools which
are not cleaned by jet water
In the distance of 2000 to 3500 mm from the swimming pool edge, the unit must adhere to the HD, IEC standard and a minimum 150 mm elevation above the ground is required for sufficient air flow. Installing the unit on the floor is prohibited.
At least 1250 mm (i.e. out of the reach of the hand) from the lateral edge of the shower cabinet. It cannot be placed above the shower cabinet.
OUTSIDE THE ZONES
OUTSIDE THE ZONES
8
WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - USER´S MANUAL
The LPHW heater elements are supplied only to order. Connection of the hot water heater element onto the LPHW plumbing is carried out similarly to the installation of radiators. On the feeder pipe, it is connected by a control valve and on the return pipe by a closing screw joint. The LPHW is not supplied with a control valve and a screw joint; these are supplied by the supplier of the heating.
6.7. LPHW heater element - to order
Attachment threading of the hot water heating element
Attachment of the heater element to the distribution of the heating water
After installing the LPHW plumbing and leading the LPHW into the element under pressure, it is necessary to bleed the heater element. The bleeding valve is located on the feeder pipe of the LPHW heater element. To secure that the LPHW heater element works always at full heat output, blowing onto the unit by a fan must be provided even when no dehumidification is being performed. Therefore, when using the LPHW heater element, the switch of fan operation must be switched into the position of continuous operation.
6.9. Mounting behind the wall - on demand
The dehumidifiers are simply adapted also to installation behind the wall into the adjacent room. In such case, only two grids are visible in the swimming pool area. These are the same grids which are, in the basic configuration, installed on the dehumidifier's cover. In the configuration for installation behind the wall, conduit adapters are screwed onto the dehumidifier's cover. The adapters are delivered for passage through the wall of the length of 400 mm. In the place of installation, they are shortened from the side of the swimming pool as necessary.
View from the adjacent room
View from the swimming pool hall
THREAD G ½ '’ MALE
OPTIONS LOCATION OF CONNECTION
1
17
1
17
50
15
35
50
100
35
40
50
CONDENSATE DRAINAGE (FROM THE REAR) PIPING WITH MINIMUM INTERNAL DIAMETER OF 18 mm
A1 - FROM LEFT SIDE A2 - FROM RIGHT SIDE A3 - FROM BACK SIDE
POWER SUPPLY
2
CYSY WIRE 3C x 1.5 (3C x 2.5) mm
(FROM THE REAR)
6.8. Hot gas defrost - on demand
Hot gas defrost allows the dehumidifier to operate effectively at air temperatures down to 5°C. The gas circuit is equipped with 4­way valve. When temperature on evaporator drops below zero, system starts to count 30 minutes of time. After this period the evaporator temperature is checked again and if the current temperature is still below zero, a compressor and a ventilator are turned off. Gas circuit is reversed and after 3 min a compressor starts. System now defreezes the unit for 3 minutes. After another 3 minutes, if the defrost cycle is completed, the unit goes into usual operations. In extremely low temperatures and in still humid enough air it is normal to take 2 or 3 defreezing cycles to complete the procedure.
NOTE: It is normal for a compressor to turn itself off and on again during defreezing cycle.