Operating Instructions
Ultrasonic proximity switch with
one switched output
pms+15/CF/A1
pms+25/CF/A1
pms+35/CF/A1
pms+100/CF/A1
Product description
The pms sensor has a stainless steel
housing and is designed for applications with hygienic requirements.
The ultrasonic transducer surface of
the pms sensors is laminated with a
PTFE film. The transducer itself is
sealed against the housing by a joint
ring.
The pms sensor with D12 adapter
shaft can be fitted in a mounting clip
which meets hygiene standards like
the sensor srew connection BF-pms/
A1.
The special housing design ensures
that any cleaning fluids are able to
run off completely, regardless of the
installation situation.
The pms sensor is ECOLAB certified.
The pms sensor variant D12 adapter
shaft offers a non-contact measure-
Sensor adjustment with Teach-in procedure
Set detect point
– method A
Place object at position
Connect Com for about
3 s to +U
B
Set detect point +8 %
– method B
Place object at position
Connect Com for about
3 s to +U
B
Set two way reflective
barrier
Place object at position
Install reflector at
position
Connect Com for about
3 s to +U
B
Connect Com for about
3 s to +U
B
Connect Com for about
13 s to +U
B
Switch off operating
voltage
Switch on
operating voltage
Keep Com connected to
-U
B
for about 13 s
Connect Com for about
1 s to +U
B
Connect Com for about
3 s to +U
B
Place object at position
Connect Com for about
1 s to +U
B
Connect Com for about
10 s to +U
B
To change output
characteristic connect
Com for about 1 s to +U
B
Disconnect Com from -U
B
before switching off supply
voltage
ment of the distance to an object
present within the sensors's detection zone. The switched output is set
conditional upon the adjusted detect
distance.
For sensor setting, the accessory
LinkControl adapter LCA-2 is recommended in combination with LinkControl software for Windows©. Alternatively, the sensor can also be set
by Teach-in via pin 2.
The pms sensors are IO-Link-capable
in accordance with IO-Link specification V1.1.
Safety Notes
Read the operating instructions
prior to start-up.
Connection, installation and ad-
justment works should be carried
out by expert personnel only.
No safety component in
accordance with the EU Machine
Directive.
Proper Use
pms ultrasonic sensors are used for
non-contact detection of objects.
The sensor must be mounted in an
EHEDG-approved mounzing clip,
such as the sensor screw connection
BF-pms/A1 for a EHEDG-complaint
use.
Installation
Assemble the sensor and its hygi-
enic D12 sensor screw connection
BF-pms/A1 or an equivalent sensor
mounting clip at the instation location.
Pull sensor cable through the sen-
sor gland, connect it to the M8
sensor plug.
Push the sensor with its shaft into
the sensor screw connection BFms/A1 and adjust (see figure 4-6).
Tighten with lock nut (maximum
tightening torque 12 Nm).
Fig. 1: Pin assignment with view onto sensor
plug and colour coding of the
microsonic connection cables
Start-up
Connect the power supply.
Carry out sensor adjustment with
brown
blue
4
2
F
Com
black
white
LinkControl or alternatively Teachin procedure in accordance with
the diagram.
Factory Setting
Detect point operation
Switched output on NOC
Detect distance at operating range
Filter at F01
Filter strength at P00
Operating Modes
Three operating modes are available
for the switched output:
Operation with one detect point
The switched output is set when the
object falls below the set detect
point.
Window mode
The switched output is set when the
object is within the set window.
Two-way reflective barrier
The switched output is set when the
object is between sensor and fixed
reflector.
Fig. 2: Assembly distances
Maintenance
microsonic sensors are maintenancefree. For cleaning in areas with hygienic requirements, access to the sensor must be guaranteed from all
sides. Cleaning is permitted up to a
cleaning temperature of 85°C. Do
not use a high-pressure cleaner to
clean the sensor.
Notes
The sensors of the pms family
have a blind zone, within which a
distance measurement is not possible.
If several pms sensors are operated
in a small space, the minimum
mounting for parallel or opposite
HM-1809

Technical data
no-load current consumption
±1 % (temperature drift internally compensated)
10 - 30 V DC, reverse polarity protection (Class 2)
±1 % (temperature drift internally compensated)
10 - 30 V DC, reverse polarity protection (Class 2)
class of protection per EN 60 529
stainless steel 1.4404/316L;
ultrasonic transducer: PTFE, FKM
stainless steel 1.4404/316L;
ultrasonic transducer: PTFE, FKM
Push-Pull, UB-3 V, -UB+3 V, I
max
= 100 mA
Push-Pull, UB-3 V, -UB+3 V, I
max
= 100 mA
switchable NOC/NCC, short-circuit-proof
switchable NOC/NCC, short-circuit-proof
time delay before availability
1)
1) Can be programmed with LinkControl
±1 % (temperature drift internally compensated)
10 - 30 V DC, reverse polarity protection (Class 2)
±1 % (temperature drift internally compensated))
10 - 30 V DC, reverse polarity protection (Class 2)
stainless steel 1.4404/316L;
ultrasonic transducer: PTFE, FKM
stainless steel 1.4404/316L;
ultrasonic transducer: PTFE, FKM
Push-Pull, UB-3 V, -UB+3 V, I
max
= 100 mA
Push-Pull, UB-3 V, -UB+3 V, I
max
= 100 mA
switchable NOC/NCC, short-circuit-proof
switchable NOC/NCC, short-circuit-proof
+U
B
-U
B
F
1
2
4
3
Push-Pull output in pnp circuit
U
+U
B
-U
B
F
1
2
4
3
Push-Pull output in npn circiut
U
Com
Com
detection zones
The dark grey areas represent the zone
where it is easy to recognise the normal
reflector (round bar). This indicates the typical
operating range of the sensors. The light
grey areas represent the zone where a
very large reflector – for instance a
plate – can still be regognized. The
requirement here is for an optimum
alignment to the sensor. It is not
for different objects:
possible to evaluate ultrasonic
reflections outside this area.
arrangement of the sensors shown
in figure 2 must be maintained.
The pms sensors are equipped
with an internal temperature compensation. Due to the sensors self
heating, the temperature compensation reaches its optimum working-point after approx. 45 seconds
of operation.
In the »Set detect point – method
A« Teach-in procedure the actual
distance to the object is taught to
the sensor as the detect point. If
the object moves towards the
sensor (e.g. with level control) then
the taught distance is the level at
which the sensor has to switch the
output.
4 cm
0 cm
0 cm
0 cm
0 cm
4 cm
4 cm
4 cm
Rohr ø 10 mm
Rohr ø 10 mm
Rohr ø 10 mm
Round bar ø 10 mm
ausgerichtete Platte
ausgerichtete Platte
Plate
8 cm
8 cm
8 cm
8 cm
0 cm
0 cm
0 cm
4 cm
4 cm
4 cm
8 cm
8 cm
8 cm
12 cm
12 cm
12 cm
16 cm
16 cm
16 cm
20 cm
20 cm
20 cm
24 cm
24 cm
24 cm
4 cm
4 cm
8 cm
8 cm
4 cm
4 cm
8 cm
8 cm
10 cm
Plate
Round bar ø 10 mm
0 cm
5 cm
10 cm
15 cm
20 cm
25 cm
30 cm
35 cm
20 cm
10 cm
5 cm
0 cm
5 cm
10 cm
0 cm
10 cm
Plate
Round bar ø 27 mm
20 cm
0 cm
10 cm
20 cm
30 cm
35 cm
40 cm
50 cm
60 cm
0,4 m
0 m
0,2m
Plate
0,4 m
0,6 m
Round bar ø 27 mm
0,8 m
1,0 m
1,0 m
1,3 m
1,4 m
0,4 m
0,2 m
0 m
0,2 m
If the object to be scanned moves
into the detection area from the
side, the »Set detect point +8 % –
method B« Teach-in procedure
should be used. In this way the
switching distance is set 8 % further than the actual measured distance to the object. This ensures a
reliable switching distance even if
the height of the objects varies
slightly.
yes
IP 67
4-pin M8 initiator plug
yes
IP 67
4-pin M8 initiator plug
yes
IP 67
4-pin M8 initiator plug
www.hemomatik.se
yes
IP 67
4-pin M8 initiator plug
Ordertel 08-771 00 04 Växel 08-771 02 20
Orderfax 08-771 62 00 Teknisk 08-771 35 80
Länna, S-142 50 SKOGÅS (Stockholm)
Fig. 4: Setting the detect point for different
directions of movement of the object
The sensor can be reset to its fac-
tory setting (see »Further settings«).
For Teach-in procedure when us-
ing the LinkControl adapter (optional accessory) the additional
adapter 5G/M12-4G/M12/M8 is
needed.
If the sensor is cleaned wet during
operation, all surfaces must be inclined at least 3° from the horizontal alignment so that the cleaning agents can run off completely
(see figure 3).