Microsonic lcs+340-F User Manual

Operating Instructions
Ultrasonic proximity switch with one switched output and IO-Link interface
lcs+340/F lcs+600/F
Product description
The lcs+ sensor offers a non-contact measurement of the distance to an object which must be positioned within the sensor’s detection zone. The switched output is set condi­tional upon the adjusted detect dis­tance. Via the Teach-in procedure, the de­tect distance and operating mode can be adjusted. One LED indicates operation and the state of the swit­ched output. The lcs+ sensors are IO-Link-capable in accordance with IO-Link specifica­tion V1.0.
Safety instructions
Read the operating instructions
prior to start-up.
Connection, installation and ad-
Sensor adjustment with Teach-in procedure
Set detect point
– method A
Place object at position 1.
Press T2 for about
3 s, until both LEDs flash
simultaneously
.
Both LEDs:
flash alternately
Set detect point +8 %
– method B
Place object at position 1.
Press T2 for about
3 s, until both LEDs flash
simultaneously
.
Both LEDs:
flash alternately
Set window mode
Set two way reflective
barrier
Set NOC/NCC
Place object at position 1.
Place reflector at
position 1.
Press T2 for about
3 s, until both LEDs flash
simultaneously
.
Both LEDs:
flash alternately
Press T2 for about
3 s, until both LEDs flash
simultaneously
.
Both LEDs:
flash alternately
Press T2 for about 13 s,
until both LEDs flash
mutually
.
LED D1: LED D2:
flashes
on: NOC off: NCC
Activate/deactivate
Teach-in
Switch off operating
voltage.
Reset to factory setting
Switch off operating
voltage.
While pressing T1 turn on
operating voltage.
Keep T1 pressed for about
3 s, until both LEDs flash
simultaneously
.
LED D2:
LED D1:
flash
on: Teach-in activated off: Teach-in deactivated
While pressing T1 turn on
operating voltage.
Keep T1 pressed for about
13 s, until both LEDs
flash mutually
.
Press T2 for about 1 s.
Normal mode operating
Press T2 for about
3 s, until both LEDs flash
mutually
again.
Place object at position 2.
Both LEDs:
flash mutually
Press T2 for about 1 s.
Press T2 for about 10 s.
To change output
characteristic press T2 for
about 1 s.
Wait for 10 s.
To activate/deactivate
Teach-in press T1 for
about 1 s.
Wait for 10 s
Normal mode operating
justments may only be carried out by qualified staff.
No safety component in
accordance with the EU Machine Directive.
Use for intended purpose only
lcs+ ultrasonic sensors are used for non-contact detection of objects.
Installation
Mount the sensor at the place of
fitting.
Connect a connection cable to the
M12 device plug.
Start-up
Connect the power supply.Carry out sensor adjustment in
accordance with the diagram.
Fig. 1: Pin assignment with view onto sensor
plug and colour coding of the microsonic connection cables
Factory setting
Switched output on NOC.
Detect distance at operating range.
Operating modes
Three operating modes are available for the switched output:
1
3
colour
+U
B
-U
B
brown
blue
4 2 5
F
-
black white
Sync grey
1
5
2
34
Operation with one detect point
The switched output is set when the object falls below the set detect point.
Window mode
The switched output is set when the object is within the set window.
Two-way reflective barrier
The switched output is set when the object is between sensor and fixed reflector.
Fig. 2: Assembly distances
2,00 m 18,00 m
4,00 m
30,00 m
A
B
Synchronisation
If under multiple sensor operation the assembly distance falls below the values shown in Fig. 2, the internal synchronisation should be used. For this purpose interconnect each pin 5 of max. 10 sensors.
Maintenance
microsonic sensors are maintenance­free. In case of excess caked-on dirt we recommend cleaning the white sensor surface.
Notes
The sensors of the lcs+ family have
a blind zone, within which a dis­tance measurement is not possi­ble.
The lcs+ sensors are equipped
with an internal temperature com­pensation. Due to the sensors self heating, the temperature compen­sation reaches its optimum work­ing-point after approx. 30 minutes of operation.
In the normal operating mode, an il-
luminated yellow LED signals that the switched output is switched through.
The lcs+ sensors have a push-pull
switched output.
In the »Two-way reflective barrier«
operating mode, the object has to be within the range of 0-85 % of the set distance.
In the »Set detect point – method
A« Teach-in procedure the actual distance to the object is taught to the sensor as the detect point. If the object moves towards the sensor (e.g. with level control) then the taught distance is the level at which the sensor has to switch the output.
If the object to be scanned moves
into the detection area from the side, the »Set detect point +8 % – method B« Teach-in procedure should be used. In this way the switching distance is set 8 % fur­ther than the actual measured dis­tance to the object. This ensures a reliable switching distance even if the height of the objects varies slightly.
Ultrasonic Sensors
Set switched output
Further Settings
Technical data
blind zone
operating range
maximum range
angle of beam spread
0 to 350 mm
0 to 600 mm
see »detection zones«
see »detection zones«
transducer frequency
resolution
reproducibility
120 kHz
0.18 mm
80 kHz
0.18 mm
± 0.15 %
± 0.15 %
accuracy
operating voltage U
B
voltage ripple
±1 % (temperature drift internally compensated; may
±1 % (temperature drift internally compensated; may
no-load current consumption
housing
class of protection per EN 60 529
60 mA
60 mA
type of connection
controls
programmable
indicators
synchronisation
operating temperature
storage temperature
weight
switching hysteresis
1)
switching frequency
1)
response time
1)
time delay before availability
1)
norm conformity
order no.
switched output
1) Can be programmed with LinkControl and IO-Link
Push-Pull, UB-3 V, -UB+3 V, I
max
= 100 mA
Push-Pull, UB-3 V, -UB+3 V, I
max
= 100 mA
+U
B
-U
B
F Com
1 2 4 5 3
Push-Pull output in pnp circuit
U
+U
B
-U
B
F Com
1 2 4 5 3
Push-Pull output in npn circuit
U
lcs+340...
lcs+600...
detection zones
The dark grey areas represent the zone
where it is easy to recognise the normal
reflector (round bar). This indicates the typical
operating range of the sensors. The light
grey areas represent the zone where a
plate – can still be regognised.. The
requirement here is for an optimum
alignment to the sensor. It is not
for different objects:
good reflector – for instance a
possible to evaluate ultrasonic
reflections outside this area.
3,400 mm 5,000 mm
1.6 m
0.8 m
0 m
0.8 m
Plate
Round bar ø 27 mm
1.6 m 0 m
0.8 m
1.6 m
2.4 m
6,000 mm 8,000 mm
2.4 m
1.2 m
0 m
1.2 m
Plate
Round bar ø 27 mm
2.4 m 0 m
1.2 m
2.4 m
3.6 m
Fig. 4: Setting the detect point for different
directions of movement of the object
The sensor can be reset to its fac­tory setting (see »Further set­tings«).
Using the LinkControl adapter (op-
tional accessory) and the LinkCon­trol software for Windows, all Teach-in and additional sensor pa­rameter settings can be optionally undertaken.
3.2 m
3.4 m
4 m
4.8 m
5.6 m
be deactivated, 0.17 %/K without compensation) 9 V to 30 V DC, reverse polarity protection ±10 %
PBT, Polyester; ultrasonic transducer: polyurethane foam, epoxy resin with glass content IP 67 5-pin M12 circular plug, PBT 2 push-buttons
• Teach-in via push-buttons
• LCA-2 with LinkControl LED yellow/green (switched output set/not set) internal synchronisation up to 10 sensors
-25°C to +70°C
-40°C to +85°C 180 g 50 mm
4 Hz
microsonic GmbH | Hauert 16 | 44227 Dortmund | Germany | telephone +49 2 31 / 97 51 51-0 | telefax +49 2 31 / 97 51 51-51 | e-mail: info@microsonic.de | www.microsonic.eu The content of this document is subject to technical changes. Specifications in this document are presented in a descriptive way only. They do not confirm any product fea­tures.
172 ms < 380 ms EN 60947-5-2
lcs+340/F lcs+600/F
NOC/NCC adjustable, short-circuit-proof
be deactivated, 0.17 %/K without compensation) 9 V to 30 V DC, reverse polarity protection ±10 %
PBT, Polyester; ultrasonic transducer: polyurethane foam, epoxy resin with glass content IP 67 5-pin M12 circular plug,. PBT 2 push-buttons
• Teach-in via push-buttons
• LCA-2 with LinkControl LED yellow/green (switched output set/not set) internal synchronisation up to 10 sensors
-25°C to +70°C
-40°C to +85°C 240 g 100 mm
3 Hz 240 ms < 450 ms EN 60947-5-2
NOC/NCC adjustable, short-circuit-proof
4.8 m
6 m
7.2 m
8.4 m
The lcs+ sensors are IO-Link-capable in accordance with IO-Link specifica­tion V1.0.
Pointer
In IO-Link mode LinkControl is not
available.
Process data
The lcs+ cyclically transmits the mea­sured distance value with a resoluti­on of 1 mm and the logical state of the switched output.
Service data
The following sensor parameters may be set via IO-Link interface using the IO-Link device description (IODD).
Detect point 1
The switched output is activated
when the distance to an object is smaller than the present detect point.
Return detect point 1
The switched output is reactivated when the distance to an object is greater than the present return de­tect point (detect point + hysteresis).
Pointer
The return detect point 1 must al-
ways be greater than the detect point 1.
Detect point 2, return detect point 2 By programming these two detect distances to a value smaller than the actual maximum distance the win­dow mode is activated. The window lies between detect point 1 and de­tect point 2.
Pointer
The return detect point 2 must al-
ways be smaller than the detect point 2.
Foreground suppression
Spurious reflections, caused by ob­jects in the foreground of the sensor may be blocked out by the fore­ground suppression.
Pointer
The object in the foreground can
cause multiple reflections that lead to invalid measurement.
The object in the foreground must
not cover the sensor in a way that the detection zone is influenced.
Maximum range
The value specifies the maximum measurement range.
Teach-in via push-buttons T1/T2
The push-buttons can be locked/un­locked for the Teach-in procedures.
Set NOC/NCC
The NCC or NOC output function can be present for the switched output.
Measurement filter
lcs+ ultrasonic sensors provide for a choice of 5 filter settings:
F00 (no filter)
Each ultrasonic measurement acts in an unfiltered manner on the output.
F01 (standard filter)
On the object continuously ap­proaching the sensor, the ongoing interval is immediately taken on and the output correspondingly activated. The effect of the object abruptly moving away from the sensor is for the existing distance to be saved for a retaining time dependent on the filter strength and for the switched output state to be maintained.
F02 (Average value filter)
Forms the arithmetic mean across a number of measurements. The output is activated in keeping with the average value. The number of measurements, from which the average value is formed, depends on the selected filter strength.
F03 (
foreground filter
) This filter reacts very fast on sensor close measurement values and gi­ves a straightened output on this sensor close level. Disturbances from objects in the background or momentary loss of echoes from the object to be detected are filte­red out.
F04 (
background filter
) This filter reacts very fast on sensor far measurement values and gives a straightened output on this sen­sor far level. Disturbances from obstacles in front of the object to be detected are filtered out.
Filter strength
A filter strength between 0 – weak filter effect – and 9 – pronounced fil­ter effect – can be selected for each measurement filter.
Temperature compensation
The temperature compensation im­proves the measurement accuracy at changing ambient temperature and may be deactivated.
Pointer
The measurement accuracy
amounts to 0,17 %/K change of temperature without compensa­tion.
Switch-on delay
If the switch-on delay is activated, the switched output will not be set before the programmed time once the measurement value falls below the set detect point. If the measure­ment value increases to the detect point again, the switched output will be reset after 50 % of the program­med on-delay time.
Detection zone sensitivity
The size of the detection zone can be varied in three steps.
Synchronisation and multiplex in IO-Link mode
As in SIO mode up to 10 sensors can be synchronised by interconnecting the sync-channel (Pin 5) of each sen­sor. Additionally the multiplex mode is available.
Multiplex mode device address
In multiplex mode for every sensor connected via the sync-channel a unique device address has to be set. The sensors then perform there measurement in increasing order of the device addresses. With multiplex address »0« the sensors work syn­chronous, with address »11« syn­chronisation/multiplex is disabled.
Pointer
In multiplex mode the response
time of each sensor extends corre­sponding to the number of con­nected sensors.
Multiplex mode highest address
To optimise the multiplex speed the highest assigned device address may be set instead of the default value »10«.
Interference noise suppression
This filter keeps the state of the out­put for the time a ultrasonic interfe­rence noise, e.g. leaking compressed air, makes a measurement impossib­le.
Pointer
The Interference noise suppression
filter extends the measurement cy­cle of the sensor and for this it's response time.
Echo quality
To simplify the adjustment of the sensor towards the measurement ob­ject the echo quality can be obser­ved. The value gives back the strength of the reflected echo.
System commands
With 6 system commands the follo­wing settings may be carried out:
Teach-in detect point.Teach-in detect point +8 %.Teach-in window mode detect
point 1.
Teach-in window mode detect
point 2.
Teach-in two way reflective barrier.Reset sensor to factory settings.
IODD file
The latest IODD file you will find on
the internet under
www.microsonic.de/en/IODD.
For further informations on IO-Link see www.io-link.com.
IO-Link data
physical layer
SIO mode support
min cycle time
baud rate
format of process data
yes 43 ms COM 2 (38.400 Bd) 16 Bit, R, UNI16
content of process data
service data IO-Link specific
Bit 0: logical state of switched output, Bit 1-15: distance value with 1 mm resolution
index
Vendor name
Vendor text
Product name
Product ID
0x10 0x11 0x12 0X13
Product text
service data sensor specific
detect point 1
0x15
index
0x40
format
UINT16
return detect point 1
detect point 2
return detect point 2
0x41 0x42
UINT16 UINT16
0x43
1)
> 58.162:
window mode deactivated
UINT16
foreground suppression
maximum range
Teach-in via push-button T1/T2
set NOC/NCC
0x44 0x45
UINT16
UINT16 0x46 0x47
UINT8
UINT8
measurement filter
filter strength
temperature compensation
switch-on delay
0x48 0x49
UINT8
UINT8 0x4A 0x4B
UINT8
UINT8
detection zone sensitivity
multiplex mode device addressing
multiplex mode highest address
interference noise suppression
0x4C 0x4D
UINT8
UINT8 0x4E 0x4F
UINT8
UINT8
system commands
Teach-in detect point
Teach-in detect point + 8 %
Index
0x02 0x02
Teach-in window mode detect point 1 Teach-in window mode detect point 2
Teach-in two way reflective barrier
reset to factory settings
0x02 0x02 0x02 0x02
observe
distance value
echo quality
Index
0x51 0x50
UINT16
UINT16
1) Distance values as e.g. detect points are given as a multiple of the internal measurement resolution = 0,172 mm (example: 2.038 350 mm).
yes 60,8 ms COM 2 (38.400 Bd) 16 Bit, R, UNI16
access value
Bit 0: logical state of switched output, Bit 1-15: distance value with 1 mm resolution
index
RRmicrosonic GmbH
www.microsonic.de
RRlcs+
340/F
0x10 0x11 0x12 0X13
R Ultraschall-Sensor
access
R/W
range (dez)
2.038-29.098 (350-4.998 mm)
0x15
index
0x40
format
UINT16 R/W R/W
2.044-29.104 (351-4.999 mm)
2.049-58.214 (352-4.999 mm)
1)
R/W
2.044-58.214 (351-4.998 mm)
1)
0x41 0x42
UINT16
UINT16
0x43
1)
> 58.162:
window mode deactivated
UINT16
R/W R/W
0-4.256 (0-1.050 mm)
29.110-58.162 (5.000-9.990 mm) R/W R/W
0: deactivated, 2: activated 0: NCC, 2: NOC
0x44 0x45
UINT16
UINT16 0x46 0x47
UINT8
UINT8
R/W R/W
0-4: F00 - F04
0-9: P00 - P09 R/W R/W
0: deactivated, 2: activated
0-20: 0-20 s
0x48 0x49
UINT8
UINT8 0x4A 0x4B
UINT8
UINT8
R/W R/W
1: high, 2: standard, 3: low
0-11: 0: sync, 11: deactivated R/W R/W
1-10
0: deactivated, 2: activated
0x4C 0x4D
UINT8
UINT8 0x4E 0x4F
UINT8
UINT8
access value
WW161
162
Index
0x02 0x02
WW163
164
WW165
166
0x02 0x02 0x02 0x02
access
R R
Index
0x51 0x50
UINT16
UINT16
access value
RRmicrosonic GmbH
www.microsonic.de
RRlcs+
600/F
R Ultraschall-Sensor
access
R/W
range (dez)
3.493-46.564 (600-7.998 mm) R/W R/W
3.499-46.570 (601-7.999 mm)
3.505-58.214 (602-7.999 mm)
1)
R/W
3.499-58.214 (601-7.998 mm)
1)
R/W R/W
0-7.295 (0-1.800 mm)
46.576-58.162 (8.000-9.990 mm) R/W R/W
0: deactivated, 2: activated
0: NCC, 2: NOC R/W R/W
0-4: F00 - F04
0-9: P00 - P09 R/W R/W
0: deactivated, 2: activated
0-20: 0-20 s R/W R/W
1: high, 2: standard, 3: low
0-11: 0: sync, 11: deactivated R/W R/W
1-10
0: deactivated, 2: activated
access value
WW161
162 WW163
164 WW165
166
access
R R
lcs+340...
lcs+600...
MV-DO-121023-437453
Sensor adjustment in IO-Link mode
Loading...