Serial Channel Interface ..................................................................................................................................... 6
CHAPTER 3 – THEORY OF OPERATION........................................................................................................... 8
G
ATEWAY OPERATION
DeviceNet Object Model ..................................................................................................................................... 8
Serial Channel Interface ................................................................................................................................... 10
Asynchronous Serial Communication .............................................................................................................................11
Status Information ...........................................................................................................................................................11
Returning Received Data............................................................................................................................................13
Padding Message Data ...............................................................................................................................................13
Re-sending Received Data .........................................................................................................................................14
Transmit Sequence Number .......................................................................................................................................15
MAC ID Switches.............................................................................................................................................. 18
Serial Channel Baud Rate / Option Switch ....................................................................................................... 19
DeviceNet Status LEDs ..................................................................................................................................... 19
Serial Channel Status LEDs.............................................................................................................................. 20
Poll Produce Size..............................................................................................................................................26
SERIAL STREAM OBJECT................................................................................................................................. 34
Bar Code Scanner ............................................................................................................................................. 65
Bar Code Scanner ............................................................................................................................................. 67
APPENDIX B – DEVICENET TEMPLATE.........................................................................................................70
APPENDIX C – ASCII CHARACTER CODES.................................................................................................... 71
Microscan Systems, Inc.
3
DN120 DeviceNet Gateway User’s Manual
(
)
(
)
y
y
M
y
Chapter 1 – Overview
This document describes how to install, configure, and operate the DN120 series of serial to
DeviceNet gateways. The following products are covered in this user manual:
Part Number Serial Channel
DN120RS232 full duplex
The DN120 gateways allow you to easily interface a wide variety of serial devices to any
DeviceNet industrial control network. Each gateway contains the feature-packed D.I.P.
DeviceNet core. Standard DN120 products are tightly packaged and sealed in a rugged
industrial case. Board-level and customized gateways are also available upon request.
Serial Status LEDs
Serial Baud Rate
Switch
Rotar
DeviceNet MAC ID
Switches
Rotar
DeviceNet Status LEDs
(NET, MOD)
(RX, TX)
DeviceNet Baud Rate
Switch
Rotar
DN120
Isolated Serial Channel
male DB9 connector
Product Features
• 500V isolated serial channel
• RS232 with RTS/CTS flow control
• XON/XOFF software flow control
• 300, 600, 1200, 2400, 4800, 9600, 19200 bps serial data rates
• Configurable parity
• 64 byte transmit and receive FIFO buffers
• Powered from DeviceNet 24VDC
• Loss-of-ground protection circuitry
• DeviceNet slave mode supports POLL and EXPLICIT messages
• Rotary switches set DeviceNet baud rate and MAC ID
• Rotary switch sets serial data rate
• 4 bi-color status LEDs
• Encapsulated circuit board in compact industrial case
ounting Holes
DeviceNet Channel
male 5-pin micro connector
Microscan Systems, Inc.
4
DN120 DeviceNet Gateway User’s Manual
A
Chapter 2 – Installation
This chapter describes how to install and connect the DN120 gateway to a DeviceNet network
and your serial device.
Mounting
Mount on a horizontal or vertical surface. While the RTV encapsulation protects its circuitry,
the DN120 serial channel connector is not rated for NEMA4 / IP65 environments. Mount the
gateway in a suitable location or enclosure for your application. The gateway will generate up to
1.4W of heat, so provide sufficient clearance and airflow to maintain 0°C to 70°C operating
temperature range. Use two screws (not provided) in the 0.19 inch mounting holes shown below
to fasten the DN120 to the mounting surface.
1.25
ll dimensions
are inches
0.650.45
3.80
4.30
3.30
0.50
0.12
Mtg. Ho les1.225
(2) 0.19 DIA.
0.725
0.625 DIA. On Case Wall
1.225
Microscan Systems, Inc.
0.70
0.542
1.10
5
DN120 DeviceNet Gateway User’s Manual
_
Wiring
The DN120 requires two connections – one to the DeviceNet network (male 5-pin micro
connector) and one to the target serial device (male DB9 connector). Follow all applicable
electrical codes in your area when mounting and wiring any electrical device.
All power is received from the DeviceNet network. The DN120 draws up to 50mA from the
24VDC power supply. Select your DeviceNet cables and power supply so that it can provide
sufficient current for all networked devices at their peak operating power.
DeviceNet Interface
Male 5-Pin Micro Connector
V+
V-
PIN SIGNAL COLOR DESCRIPTION
1DRAINNONECable shield or drain wire.
2V+REDDeviceNet 24VDC(+) power.
3V-BLACKDeviceNet 24VDC(-) power.
4CAN_HWHITECommunication signal.
5CAN_LBLUECommunication signal.
Serial Channel Interface
Male DB9 Serial Connector
1
23
6
78
DN120 (RS232)
PIN SIGNAL DESCRIPTION
1NCNo Connect. Do not connect any wires to NC pins.
2RXDReceive Data. RS232 input signal.
3TXDTransmit Data. RS232 output signal.
4NCNo Connect.
5GNDGround. Common for RS232 signals.
6NCNo Connect.
7RTSRequest To Send. RS232 output signal.
8CTSClear To Send. RS232 input signal.
9NCNo Connect.
4
DRAIN
CAN_L
CAN
5
9
H
Microscan Systems, Inc.
6
DN120 DeviceNet Gateway User’s Manual
Wiring Examples
The following are typical DN120 gateway wiring configurations. Your RS232 or RS422/485
interface may vary. Refer to your device’s documentation for the required data and control
signals.
Simple RS232 Interface
2
RS232
Serial
Device
RXD
3
TXD
5
GND
RXD
TXD
GND
2
3
5
DN120
1
2
3
4
5
DRAIN
VDC+
VDC-
CAN H
CAN L
RS232 Interface, HW Flow Control
RS232
Serial
Device
2
RXD
3
TXD
5
GND
RTS
7
CTS
8
RXD
TXD
GND
RTS
CTS
2
3
5
7
8
DN120
1
2
3
4
5
DRAIN
VDC+
VDC-
CAN H
CAN L
Microscan Systems, Inc.
7
DN120 DeviceNet Gateway User’s Manual
M
R
l
Chapter 3 – Theory of Operation
This chapter describes how the DN120 gateway operates. You should have a working
knowledge of DeviceNet and asynchronous serial communications before continuing. The Open
DeviceNet Vendors Association (www.odva.com) is a good source for general DeviceNet
information. Refer to your serial device documentation for its protocol information.
Gateway Operation
The DN120 gateway receives asynchronous serial messages over its serial channel and returns
the received bytes as input data to the DeviceNet master. The gateway transmits bytes sent as
output data from the DeviceNet master out its serial channel. The following diagram shows the
major gateway components.
DC:DC Power Conversion
• 24VDC DeviceNet power input
DeviceNet Poll Command
output data
• VDC for Core & DeviceNet channel
• isolated VDC for serial channel
5-pin male
micro connector
DeviceNet Poll Response
input data
DeviceNet Channel
• 24VDC power
• communications
DeviceNet Object
or Rotary Switches
Configures the DeviceNet
interface baud rate and
AC ID address.
Gateway Core
• microcontroller
• RAM
• Flash ROM
Serial Channel
• communications
• flow control
Serial Stream Object
Configures the serial channel.
eceives and transmits seria
messages. Controls optional
synchronization.
Male DB9
connector
serial
messages
DeviceNet Object Model
The DeviceNet Specification defines an Object Model that consists of Objects and Attributes.
An Object is a predefined software process, and an Object Attribute is a data value used or
generated by that process. An Object Instance is one occurrence of an Object, operating on its
unique set of Attribute values. The DN120 gateway has six different Object Classes, or types.
Five are standard objects defined by the DeviceNet Specification (Identity, Router, DeviceNet,
Assembly, Connection). One is a device-specific object defined for the DN120 gateway (Serial
Stream). The Serial Stream Object configures and controls the serial channel. It receives and
packages serial data into DeviceNet input bytes, and transmits DeviceNet output bytes as serial
data. Chapter 5 contains detailed information on each DeviceNet object class, instance, and their
associated attributes.
Microscan Systems, Inc.
8
DN120 DeviceNet Gateway User’s Manual
DeviceNet Interface
The DN120 gateway operates as a DeviceNet slave. It supports Explicit Messages and Polled
I/O Messages of the predefined master/slave connection set. The Explicit Unconnected Message
Manager (UCMM) is not supported.
There are four independent processes operating in a DN120 gateway application. The first
process is the exchange of input and output data between the user application program and the
DeviceNet master. The second process is the exchange of input and output data between the
gateway and DeviceNet master, using Polled I/O messaging. The third process is receiving serial
messages and converting it to input data. The fourth process is converting output data and
transmitting it as serial messages.
The DeviceNet Polled I/O Message process consists of the DeviceNet master sending output data
to the DN120 in the form of a Poll Command message, and the DN120 returning input data to
the DeviceNet master in a Poll Response message. The output and input data bytes are typically
mapped into data files inside the DeviceNet master. These data files are exchanged with the user
application program. The application processes the received input data from the gateway and
writes new output data to the DeviceNet master, which sends them to the gateway.
The Polled I/O data exchange typically occurs at a faster rate than the serial transmit and receive
operation, because the DeviceNet baud rate is much greater than the serial channel baud rate.
The DN120 has transmit and receive buffers to handle the slower serial processes. The gateway
also provides synchronization features to ensure delivery of received messages to the application
program, and transmission of application messages out the serial channel.
DeviceNet Poll Response
input data
DeviceNet Poll Command
output data
DeviceNet
Master
Application
Program
DN120
Gateway
Receive
Message Packet
Transmit
Message Packet
Serial
Device
Microscan Systems, Inc.
9
DN120 DeviceNet Gateway User’s Manual
The DN120 configuration defines the number of output bytes in a Poll Command message, and
the number of input bytes in a Poll Response message. Each Poll Command and Poll Response
message can contain up to 2 overhead bytes for DN120 status and data synchronization
information. The remaining bytes contain output data to be transmitted out the serial channel, or
input data received by the serial channel.
The following diagram shows how the input and output bytes map into the Poll Response and
Poll Command messages. The gateway supports a maximum of 67 output bytes in a Poll
Command message, and a maximum of 67 input bytes in a Poll Response message.
DeviceNet Master Mapping of DeviceNet Poll Command and Poll Response Data
DeviceNet Master OutputsDeviceNet Poll Command Message Data
The DN120 serial channel consists of an asynchronous serial transmitter and receiver. The serial
interface is configured and controlled by the Serial Stream Object. The Serial Stream Object
attributes configure the serial channel baud rate, parity, and flow control. This configuration
applies to both the serial transmitter and receiver. The DN120 gateway has separate 64-byte
serial transmit and receive FIFO buffers, allowing full duplex operation when supported by the
physical layer media.
Microscan Systems, Inc.
10
DN120 DeviceNet Gateway User’s Manual
Asynchronous Serial Communication
Devices communicating on an asynchronous serial link exchange information one bit at a time.
Each bit is transmitted for a specific period of time, defined by the baud rate. Devices use
internal timing circuitry to generate the baud rate. There is no clocking signal between devices
to synchronize the serial data flow, hence the term asynchronous serial communications.
Serial data bits are organized into bytes. When a data byte is asynchronously transmitted, it is
preceded by a start bit, followed by the data bits, an optional parity bit, and one or more stop bits.
There can be a variable transmission delay between successive data bytes, since each byte is
framed by its own start and stop bits. The receiver starts saving bits after is receives a valid start
bit (0), and stops when it receives the expected number of stop bits (1). The data byte’s leastsignificant bit is transmitted first (data bit 0), and the most-significant bit is last (data bit N).
[ start bit ] [ data bit 0 ] [ data bit 1 ] … [ data bit N ] [ optional parity bit ] [ stop bit(s) ]
The parity bit detects single-bit errors in the transmission. The parity bit is calculated and
inserted by the transmitter. The receiver calculates the parity of an incoming byte, and compares
it to the parity bit sent by the transmitter. If the two bit values do not match, then at least one
serial bit value was corrupted during transmission.
Flow control enables the receiving device to regulate the rate of incoming data. Hardware flow
control uses RTS/CTS signals between the devices to control the rate of transmission. Software
flow control uses serial characters XON/OFF to control the rate. CTS Detect Mode uses the
CTS signal to enable serial communications. Flow control helps prevent data loss, if the
receiving device cannot store incoming data fast enough, or if its Receive Buffer is full and
cannot accept more data until existing data is processed.
The DN120 supports baud rates from 300 to 19200 bits per second. It supports 8 data bits with
no parity, 7 data bits with parity, and 1 stop bit. The DN120 model supports RTS/CTS,
XON/XOFF, and CTS Detect Mode flow control options.
Status Information
The gateway can be configured to return serial channel status information in the Poll Response
message, and receive error-clearing commands in the Poll Command message. When enabled,
the Status byte is returned as an input byte, and the Status Clear byte is received as an output
byte. These bytes contain 8 status bits, defined below. Each bit represents either an error or
state condition for the serial transmitter and receiver. Clearing the associated error bit in the
Status Clear output byte will reset Receive Parity Error, Receive Buffer Overflow, Framing
Error, and Transmit Buffer Overflow error conditions.
Microscan Systems, Inc.
Status / Status Clear Bytes
11
DN120 DeviceNet Gateway User’s Manual
M
Bit Status (1st input byte) Status Clear (1st output byte)
0Transmit Channel Blockednot used
1Transmit Buffer Emptynot used
2Receive Parity ErrorSet = 0 to clear Receive Parity Error condition
3Receive Buffer Emptynot used
4Receive Buffer OverflowSet = 0 to clear Receive Buffer Overflow condition
5Framing ErrorSet = 0 to clear Framing Error condition
6Transmit Buffer OverflowSet = 0 to clear Transmit Buffer Overflow condition
7CTS Signal State (1 = asserted)not used
A user application can use the Transmit Buffer Empty and Receive Buffer Empty status bits to
monitor the transmitter and receiver states. However, the DN120 gateway also has three data
synchronization features (Receive Sequence Number, Transmit Sequence Number, Handshake
Protocol) that an application can use to better monitor the serial operations.
Receiving Messages
The DN120 gateway has two modes for receiving serial data: Stream Mode and Block Mode.
Stream Mode is best suited for applications with fixed-length serial messages, but it can also be
used to capture any stream of serial data. Block Mode is intended for both fixed and variable-
length message applications, where a Delimiter byte denotes the beginning or end of a message.
Stream Mode
StreamMode saves all received message bytes in the Receive Buffer. There is no defined
beginning or end to the message stream. The only limitation is the gateway must send bytes
from the Receive Buffer to the DeviceNet master (Poll Response message) faster than it saves
new message bytes in the Receive Buffer, or the 64-byte buffer may eventually overflow.
Block Mode uses a configurable Delimiter byte to signal the start or end of a new message
packet. The Delimiter cannot be used in any other part of the message, or it would be incorrectly
interpreted as the start or end of a message. The gateway can be configured to save the Delimiter
byte in the Receive Buffer, or discard it. In Block Mode, the gateway does not return any new
message data to the DeviceNet master until the entire serial message has been received.
The Pre-Delimiter Block Mode configuration expects the Delimiter at the start of a message.
When a Delimiter byte is received, the gateway saves all subsequent bytes in the Receive Buffer
until another Delimiter is received (signaling the start of another message), or until the Maximum
Receive Size number of bytes has been saved. All bytes received after the Maximum Receive
Size and before the next Delimiter are discarded. In this mode, the maximum number of bytes ina single message is defined by the Maximum Receive Size attribute.
The Post-Delimiter Block Mode configuration expects the Delimiter at the end of a message.
The gateway saves all received bytes in the Receive Buffer until a Delimiter is received. In this
mode, the maximum number of bytes in a single message is limited by the Receive Buffer size
(64 bytes), not the Maximum ReceiveSize attribute.
When the gateway receives a Poll Command message, it removes some or all of the bytes
currently in the Receive Buffer and returns them as input bytes in a Poll Response message.
The Maximum Receive Size attribute defines the maximum number of bytes that can be returned
in a single Poll Response message. If the Receive Buffer contains more bytes than can fit into
one Poll Response message, the remaining bytes are returned in subsequent Poll Response
messages. RX Message is the string of valid message bytes returned in a single Poll Response
message. The RX Message byte string can be formatted as either a Short_String (byte array with
st
1
byte = length) or a Byte Array (no length byte). The number of bytes in an RX Message string
can be less than or equal to the Maximum Receive Size, but never larger. When the number is
less, the remaining Poll Response input bytes are either padded or undefined.
In Stream Mode, the gateway will always try to fill Poll Response message with bytes from the
Receive Buffer. The only time the RX Message size is less than the Maximum Receive Size is
when there are no more bytes in the Receive Buffer.
In Block Mode, the gateway will not return any data in a Poll Response message unless it has a
complete serial message saved in the Receive Buffer. If the message sizes are small, the gateway
may have several messages saved in the Receive Buffer, depending upon how fast the DeviceNet
master polls the gateway for data. The messages are returned one at a time in a Poll Response
message, regardless of their size. If the message is large, then it is returned in multiple Poll
Response messages.
Padding Message Data
Microscan Systems, Inc.
13
DN120 DeviceNet Gateway User’s Manual
R
r
B
P
R
R
R
If the number of RX Message bytes currently in the Receive Buffer is less than the Maximum
Receive Size number, then the remaining input bytes are undefined. The gateway can optionally
fill the unused input bytes with a Pad character. The Pad characters can be added at the
beginning or end of the message.
oll Response Message Data
Status
1. The are enough message bytes in Receive
uffer to fill Poll Response.
2. The are not enough message bytes in
eceive Buffer to fill Poll Response. Unused
input bytes are undefined.
3. The are not enough message bytes in
eceive Buffer to fill Poll Response. Pad bytes
are added after message bytes.
4. The are not enough message bytes in
eceive Buffer to fill Poll Response. Pad bytes
are added before message bytes.
eceive Sequence Numbe
other input bytes
RX Message bytes
RX Message bytesundefined
RX Message bytes
Pad Bytes
RX Message Bytes
Pad Bytes
If configured for Pre-Delimiter Block Mode and the Delimiter byte is saved, the Pad characters
are added either after the last valid message byte (right justification) or before the Delimiter byte
(left justification).
If configured for Post-Delimiter Block Mode and the Delimiter byte is saved, the Pad characters
are added either before the first valid message byte (left justification), or after the last valid
message byte but before the Delimiter byte (right justification).
Re-sending Received Data
The DN120 gateway can be configured to return received message bytes only once in a Poll
Response message, and return no data (null value) in subsequent Poll Response messages until
new message bytes are received. For the Short_String data type, a null value consists of the
length byte = 0. For the Byte Array data type, a null value consists of no data.
The gateway can also be configured to always return received message bytes in a Poll Response
message. If no new bytes in the Receive Buffer, then the last received bytes are returned. If new
bytes are in the Receive Buffer, then they are returned. The gateway provides Receive SequenceNumber or Handshake Protocol synchronization options to indicate whether the returned bytes
represent old or new data.
Microscan Systems, Inc.
14
DN120 DeviceNet Gateway User’s Manual
P
Transmitting Messages
The Serial Stream Object receives output bytes (TX Message) from the DeviceNet master in a
Poll Command message. It saves the output bytes in the Transmit Buffer, to be transmitted when
the serial channel is available. The maximum number of bytes that can be sent in one Poll
Command message is defined by the Maximum Transmit Size attribute. The Transmit Buffer can
hold up to 64 bytes. Because the DeviceNet Polled I/O data exchange may occur many times
faster than the transmission of serial data, the application may need to synchronize the transmit
data exchange with the gateway.
The number of output bytes in the Poll Command message is fixed. The Status Clear and
Transmit Sequence Number bytes are always sent, if enabled. The remaining number of bytes in
the Poll Command is defined by the Maximum Transmit Size attribute. If the number of TXMessage bytes sent is less than the MaximumTransmit Size number, then the remaining output
bytes are undefined. The gateway uses the Short_String length to determine the valid number of
bytes to transmit. If Byte Array format is used, all the bytes are transmitted.
oll Command Message Data
Status ClearTransmit Sequence Numberother output bytes
1. TX Message bytes fill Poll Command
message.
2. TX Message is smaller than Poll Command
message. Unused output bytes are undefined.
TX Message bytes
TX Message bytesundefined
Synchronization
To ensure that no information is lost between the gateway’s serial channel and the user
application program, the DN120 has three synchronization options: Receive Sequence Number,Transmit Sequence Number, and Handshake Protocol.
Receive Sequence Number
When enabled, the gateway returns a Receive Sequence Number input byte in the DeviceNet Poll
Response message. The 8-bit Receive Sequence Number is incremented by the gateway
whenever it returns new data in the input bytes. The user application uses the Receive SequenceNumber to signal the receipt of new message data. Valid numbers are 0-255.
Transmit Sequence Number
When enabled, the gateway receives a Transmit Sequence Number output byte in the DeviceNet
Poll Command message. The gateway will not send the TX Message bytes out the serial channel
unless the 8-bit Transmit Sequence Number is different than the last received value. Valid
numbers are 0-255.
Microscan Systems, Inc.
15
DN120 DeviceNet Gateway User’s Manual
R
D
t
N
Synchronous Handshake Protocol
The gateway can be configured with a more robust transmit and receive synchronization process.
The Handshake protocol requires the user application to acknowledge the receipt of new RXMessage input bytes. The protocol also requires the gateway to acknowledge the transmission of
the last TX Message output bytes. When enabled, both the Receive Sequence Number input byte
and Transmit Sequence Number output byte are used. They are segmented into four 4-bit
numbers, shown below. Valid numbers are 1 to 15, with 0 reserved to reset the gateway’s
numbers.
Transmit Sequence Number byte
Receive Acknowledge NumberTransmit Request Number
Bits 4-7 (upper nibble)Bits 0-3 (lower nibble)
eceive Sequence Number byte
Receive Request NumberTransmit Acknowledge Number
Bits 4-7 (upper nibble)Bits 0-3 (lower nibble)
The Receive Request Number is incremented by the gateway when it returns new RX Message
input bytes in the Poll Response Message. The gateway will increment from 15 to 1, skipping 0.
The user application acknowledges receipt of this RX Message by setting the Receive
Acknowledge Number equal to the Receive Request Number. The updated Receive Acknowledge
Number is sent back to the gateway in the next Poll Command Message. When the Receive
Acknowledge Number equals the Receive Request Number, the gateway can return the next set of
RX Message. If the user application sends 0 as the Receive Acknowledge Number, the gateway
resets its Receive Request Number to 0.
The following ladder-logic rung shows how the user application program can monitor the
gateway’s Receive Request Number (RX Rqst Num), save the new RX Message bytes, and set
Receive AcknowledgeNumber (RX Ack Num) equal to Receive Request Number (RX Rqst
Num).
id gateway increment the RX Rqs
um, indicating new data?
Compare Function:
RX Rqst Num <> RX Ack Num
Copy Function:
<byte array> = RX Message
Copy Function:
RX Ack Num = RX Rqst Num
Microscan Systems, Inc.
16
DN120 DeviceNet Gateway User’s Manual
D
I
I
The Transmit Request Number is incremented by the user application when it sends new TX
Message output bytes in the Poll Command Message. After the gateway transmits these TX
Message bytes, it sets the Transmit Acknowledge Number equal to the Transmit Request Number,
acknowledging the transmission. The updated Transmit Acknowledge Number is returned in the
next Poll Response Message. If the user application sends 0 as the Transmit Request Number,
the gateway ignores the TX Message output bytes and resets its Transmit Acknowledge Number
to 0.
The following ladder-logic rungs show how the user application program writes a new TX
Message value, increments the Transmit Request Number (TX Rqst Num), and waits for the
Transmit Acknowledge Number (TX Ack Num) to equal the Transmit Request Number (TX RqstNum). Note the application must wrap the Transmit Request Number from 15 to 1.
id gateway finish (acknowledge)
transmitting the last message?
Compare Function:
TX Ack Num == TX Rqst Num
Write next output bytes to transmit.
Copy Function:
TX Message = <byte array>
f TX Rqst Number greater than 15,
then reset number to 1 (1-15 range)
Compare Function:
TX Rqst Num == 16
ncrement TX Rqst Num (new data)
Addition Function:
TX Rqst Num = TX Rqst Num + 1
Write Function:
TX Rqst Num = 1
Microscan Systems, Inc.
17
DN120 DeviceNet Gateway User’s Manual
Chapter 4 – Gateway Configuration
This chapter describes how to configure and operate the DN120 gateway. You configure the
gateway by reading and writing attribute values over its DeviceNet interface. There are a variety
of DeviceNet configuration tools available. Simple configuration tools use GET_ATTRIBUTE
and SET_ATTRIBUTE explicit message commands to read and write attribute values,
addressing each attribute by its Object, Instance, and Attribute numbers. This information is
contained in Chapter 5. More sophisticated configuration tools use EDS files to simplify
attribute configuration. You can configure the gateway using pull-down menus, buttons, and
data entry fields from the gateway’s Electronic Data sheet (EDS) file. Chapter 6 contains a
configuration example using the Rockwell Software RSNetworx program.
Configure DeviceNet Interface
Set the DeviceNet Baud Rate and MAC ID Address using the rotary switches. Configure
switches before connecting to the DeviceNet network. There is either a small triangular
indicator or white indicator on the switch. Use a small screwdriver to align that indicator with
the desired setting. Remove the DN120 cover if necessary to access the rotary switches.
DeviceNet Baud Rate Switch
Valid settings are 125K, 250K, 500K, or PGM. When PGM is selected, the DN120 uses the
baud rate saved in its retentive memory. A valid baud rate must be stored before the PGM
selection can be used. The baud rate is stored from the previous DN120 power cycle. It can also
be set over the network (DeviceNet Object Baud Rate attribute).
POSITION SETTING POSITION SETTING
0125 Kbps5invalid
1250 Kbps6invalid
2500 Kbps7invalid
3invalid8invalid
4invalid9PGM
MAC ID Switches
The two MAC ID switches represent decimal numbers from 00 to 99. The LSB switch selects
the Ones digit and the MSB switch selects the Tens digit. Valid MAC IDs are 00 to 63. Setting
a MAC ID address greater than 63 forces the gateway to use the MAC ID saved in retentive
memory. A valid MAC ID must first be stored before this feature can be used. The MAC ID is
stored from the previous DN120 power cycle. It can also be set over the network (DeviceNet
Object MAC ID attribute).
MSB LSB Address MSB LSB Address
00 to 900 to 0964 to 9stored address
10 to 910 to 1970 to 3stored address
20 to 920 to 2980 to 9stored address
30 to 930 to 3990 to 9stored address
40 to 940 to 49
50 to 950 to 59
60 to 360 to 63
Microscan Systems, Inc.
18
DN120 DeviceNet Gateway User’s Manual
Serial Channel Baud Rate / Option Switch
The DN120 gateway has a rotary switch for the serial channel. This switch has different
functions for the DN120 models.
The DN120 model uses the rotary switch to select the RS232 channel baud rate. Valid settings
are 300, 600, 1200, 2400, 4800, 9600, 19200 bits per second, and PRG (table below). When
PRG is selected, the DN120 uses the Baud Rate attribute in the Serial Stream Object. A valid
baud rate must be written over DeviceNet to this attribute.
POSITION SETTING POSITION SETTING
09600 bps5300 bps
14800 bps619200 bps
22400 bps7invalid
31200 bps8invalid
4600 bps9PRG
Power Up Gateway
Connect the gateway to a DeviceNet network to power up the gateway.
DeviceNet Status LEDs
The DN120 gateway has two bi-color status LEDs (NET and MOD) that indicate operational
status. During power-up, the LEDs cycle through a sequence of alternating red and green. After
power-up, the NET LED should be flashing green (or solid green if allocated to a DeviceNet
master) and the MOD LED should be solid green. If this does not occur, disconnect from
DeviceNet and verify all the switch settings. See Chapter 8 for additional troubleshooting topics.
The gateway has two bi-color LEDs to indicate serial channel activity. The TX LED flashes
green when a packet is being transmitted. The RX LED flashes green when a packet is being
received. A fault is indicated by solid red. After power-up, both LEDs should be off.
StateTransmit Status LED (TX)
OffNo data being transmitted
Flashing RedNot defined
Solid RedTransmit error (parity or overrun error)
Flashing GreenData being transmitted
Solid GreenNot defined
StateReceive Status LED (RX)
OffNo data being received
Flashing RedNot defined
Solid RedReceive error (parity or overrun error)
Flashing GreenData being received
Solid GreenNot defined
Register EDS File
If using a DeviceNet configuration tool that supports Electronic Data Sheet (EDS) files, you
should now register the gateway’s EDS file with the software. The latest EDS file versions can
be downloaded from www.mksinst.com. Select the EDS file that matches your gateway’s part
number and firmware version. Follow your configuration tool instructions to register EDS file.
Microscan Systems, Inc.
20
DN120 DeviceNet Gateway User’s Manual
Configure Serial Channel
The Serial Stream Object attributes control the DN120 serial channel. These settings apply to all
serial transmit and receive operations. Before you can set or change any gateway configuration
settings, make sure the gateway is not in the DeviceNet master scanlist.
Serial Stream Object Instance Attributes (Class Code 64)
NumberNameData TypeValue
3Receive DataShort_String
or
Byte Array
4Transmit DataShort_String
or
Byte Array
5StatusUSINTBit 0 – Transmit Channel Blocked
6Baud RateUSINT0 = 9600 bps 4 = 600 bps
7ParityUSINT0 = no parity 5 = mark (force to 1)
8Data SizeUSINTRead-only. 7 bits if parity enabled, 8 bits if no parity.
9Stop BitsUSINTRead-only. Fixed at 1 bit.
10Flow ControlUSINT0 = none 2 = CTS / RTS
11Receive CountUSINTNumber of bytes in Receive Buffer. Any write clears buffer.
12Transmit CountUSINTNumber of bytes in Transmit Buffer. Any write clears buffer.
13Maximum Receive SizeUSINTDefines the maximum #bytes returned by RX Message read.
14Data FormatUSINTBit 0 – String Format (0 = Short_String, 1 = Byte Array)
16DelimiterUSINTDelimiter byte value
17Pad CharacterCHARPad byte value
18Maximum Transmit SizeUSINTDefines the maximum # bytes that can be transmitted.
19Idle StringShort_String 1-16 byte string transmitted when gateway receives a null Poll
Received message data. Returned in Poll Response Message.
Message data to transmit. Received in Poll Command Message.
Bit 1 – Transmit Buffer Empty
Bit 2 – Receive Parity Error (set = 0 to clear)
Bit 3 – Receive Buffer Empty
Bit 4 – Receive Buffer Overflow Error (set = 0 to clear)
Bit 5 – Framing Error (set = 0 to clear)
Bit 6 – Transmit Buffer Overflow Error (set = 0 to clear)
Bit 7 – CTS Signal State (1 = asserted)
1 = even parity 6 = space (force to 0)
2 = odd parity
1 = XON / XOFF 4 = CTS Detect Mode
Bit 1 – Strip Parity Bits (0 = retain, 1 = strip)
Bit 2 – Pad Justification (0 = left justify, 1 = right justify)
Bit 3 – Pad Received Message (0 = no, 1 = yes)
Bit 1 – Strip Delimiter (0 = keep delimiter, 1 = strip delimiter)
Bit 2 – Delimiter Enable (0 = no, 1 = yes)
Bit 3 – Enable Receive Sequence Number (0 = no, 1 = yes)
Bit 4 – Enable Transmit Sequence Number (0 = no, 1 = yes)
Bit 5 – Re-send (0 = no, 1 = yes)
Bit 6 – Synchronization (0 = no, 1 = handshake protocol)
(no input bytes). Short_String length = 0 for no Idle String.
Microscan Systems, Inc.
21
DN120 DeviceNet Gateway User’s Manual
R
r
D
D
R
D
D
20Fault StringShort_String 1-16 byte string transmitted when gateway’s Polled I/O
connection times out. Short_String length = 0 for no Fault String.
21Status EnableUSINTSet to any nonzero value to enable Status input byte.
22Status Clear EnableUSINTSet to any nonzero value to enable Status Clear output byte.
23Four WireUSINTNA
24Option SwitchUSINTNA
Receive Data – Data from the last valid message packet. Receive Data includes the Status and
Receive Sequence Number bytes if enabled, and the RX Message bytes. The RX Message format
is either Short_String or Byte Array, defined by Data Format attribute. If no message data is
available, the RX Message will be a null packet or Short_String with length = 0. Receive Data is
returned in the DeviceNet Poll Response Message.
eceive Data
Status
eceive Sequence Numbe
ata Format =
xxxxxxx0
Short_String data bytesByte Array data bytesLength
RX Message
ata Format =
xxxxxxx1
Transmit Data – Data to transmit out the serial channel by the gateway. Transmit Data includes
the Status Clear and TransmitSequence Number bytes if enabled, and the TX Message bytes.
Format is either Short_String or Byte Array, defined by Data Format attribute. Transmit Data is
typically received in the DeviceNet Poll Command Message. Reading Transmit Data returns the
last byte in the Transmit Buffer.
Transmit Data
Status ClearTransmit Sequence NumberTX Message
ata Format =
xxxxxxx0
Short_String data bytesByte Array data bytesLength
ata Format =
xxxxxxx1
Status – Contains bit-mapped serial channel status and error bits for transmit and receive
operations. Clearing the bits indicated will clear the error condition.
Baud Rate – Sets the serial channel’s data or baud rate. Enter number from 1-6 to select
corresponding baud rate value. For DN120, the RS232 Baud Rate switch must be set to PRG
before this attribute can be used to set the baud rate.
Microscan Systems, Inc.
22
Loading...
+ 49 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.