Micropelt iTRV MVA 005 Specifications

Wireless heating valve actuator
MVA005 EnOcean
User manual and device specification
EnOcean Equipment Profile A5-20-06
Annex: List of adapters and theft protection
MAR2019 Autor: Micropelt - Eine Marke der EH4 GmbH - DokumentenNr.: MVA005_1DS_0319v2e.docx
MVA005 User manual and Datasheet
INDEX
INDEX 1
1 Document history 2
2 ERRATA 2
3 Use and safety recommendations 3
4 System description 4
4.1 Picture MVA005 with dial for local control 6
5 Energy-supply through thermal Energy Harvesting 7
6 User Control - Quick overview table 8
6.1 Installation with Manual Pairing (Teach-In) 8
6.2 Local offset 8
6.3 Deactivation and RESET 10
6.4 Installation through SIGNAL telegram and Remote Commissioning 11
6.5 Remarks Remote Commissioning 12
6.6 Flowchart Remote Commissioning 13
6.7 Flowchart Manual RESET 14
6.8 Flowchart Teach-In, Mounting position and activation 15
7 Notes on radio operation 16
7.1 Transmission range 16
7.2 Other interference sources 16
7.3 Loss of communication with the room controller 16
8 EnOcean Equipment Profile EEP A5-20-06 17
8.1 Protocol data overview 17
8.2 Description of individual functions 20
8.2.1Setpoint Selection (SPS) 20
8.2.2Operating mode (SP) 20
8.2.3Local offset (LO) 20
8.2.4Radio communication interval (RFC) 20
8.2.5Summer bit (SB) 21
8.2.6Valve recognition and ACO 21
8.2.7Window open detection (DWO) 21
8.2.8Radio strength and com. error (RSS & RCE) 21
8.2.9Reference Run (Maintenance) 21
8.3 Radio telegram example 22
9 EnOcean Remote Management (ReMan), Remote Commissioning (ReCom) 23
9.1 EnOcean Link Table 23
9.2 Outbound Teach-In 23
9.3 ReMan supported functions 23
9.4 ReCom Standard Functions 24
9.5 ReCom internal MVA Parameter 25
10Extended Features and Functions 27
11Product ID and Label 28
12Performance data 29
13Mechanical Interface to Radiator Valve 31
14Annex 1: Adapter list 32
15Annex 2: Theft protection 33
MAR 2019 Page 1 / 33 MVA005_1DS_0319v2e.docx
MVA005
V
User manual and Datasheet
1 Document history
Date Description
31.08.2018
01.10.2018
01.03.2019
Transfer from released German version and first
release English version
Section 10:
Product ID 0x004900000001  Added product label picture  Added SEC CODE default valve
Dissolved Errata MVA005_V5.15.b.3
Added manual RESET SEC CODE  Freeze protection sensor changed from ambient
to flow
Radio loss set point changed  Added 2nd freeze protection value 0°C (SPS=1
and Setpoint 0°C)
Additional flow charts and descriptions  Added LED-signal with temperature sensor
failures (Short circuit, disconnection)
ersion Status
0818_v1e Released
0818_v1e Released
0319v2e.docx Released
2 ERRATA
VERSION
MVA005_V5.15.b.3 RECOM Standard Command RESET TO
RESET SEC CODE TO DEFAULT not
MVA005_V5.26.a.7 4BS radio communication interval 120min
THEMA WORKAROUND
Execute RECOM Operation and write
DEFAULT not supported
supported
not supported
Default values <>
<>
MAR 2019 Page 2 / 33 MVA005_1DS_0319v2e.docx
MVA005 User manual and Datasheet
3 Use and safety recommendations
Dear valued customer,
Thank you for choosing our product. To operate the self-powered radiator actuator, please read this manual carefully. Keep the instructions for future reference. In case of questions, please contact:
Micropelt - a brand of EH4 GmbH. Email: info@micropelt.com. Telephone +49 7665 932183 0
Use and safety instructions:
The metallic part of the unit’s housing serves as a heat sink. Be sure that the air circulation around it
is not obstructed by furniture, curtains, plants, or other objects.
If the device has been stored in a cold environment, make sure that it resumes close to room
temperature before use. This is to prevent damaging due to condensation.
The thermostatic radiator valve is designed for indoor use only. Do not allow the thermostatic radiator
valve to get wet. Its sensitive electronics can be affected.
The unit is best cleaned with a dry or slightly damp cloth. Do not use aggressive cleaning agents or
solvents.
Refrain from exposing the unit to environmental stress such as high mechanical forces (do not step
on it), strong vibrations, direct sunlight or extreme temperatures.
The unit must not be disassembled or modified. In case you are unsure how to use the unit, please
get in touch with Micropelt.
Be aware that correct operation can be affected by strong electromagnetic fields. Typical sources of
such are mobile phones, 2-way radios, RC transmitters, microwave ovens, electric motors.
The housing contains actuated springs that can lead to injuries if released. For servicing, refer to
qualified service personnel.
The thermostatic radiator valve has been designed and must solely be used for the purpose of
controlling a M30 x 1.5 heater valve. Any other use may pose a hazard to the device itself, to the equipment involved, or to the health of the user.
When operating the device in a workplace environment, be sure to observe the workplace regulations
that may apply.
Intended use: The self-powered thermostatic radiator valve is suitable solely for controlling water-filled heating radiators. Any other use – including control of floor heating systems - is not permitted and can result in damage. Do not disassemble or modify any part of the product. It is important to comply with the safety notice included in these operating instructions.
MAR 2019 Page 3 / 33 MVA005_1DS_0319v2e.docx
MVA005 User manual and Datasheet
4 System description
This document defines the properties of Micropelt’s battery free, intelligent thermostatic radiator valve (iTRV). MVA005 is an 868MHz EnOcean wireless actuator, which is self-powered through thermal energy harvesting. It is used to single room control heating radiators with standard valve connection M30x1.5 (Section 13). To operate the device, the unit must be paired with a compatible room controller or gateway unit supporting EEP A5-20-06. The pairing is done either via manual 4BS Teach-In or trough EnOcean Remote Commissioning. Once mounted and activated on the valve body, a calibration cycle starts to automatically adapt itself to the individual valve and is ready for use. Adapter are available for a majority of non M30x1.5 valve bodies (Section
14).
Room controller time schedules can be conveniently used to set individual room temperatures at different times and to a desired °C value. By lowering room temperatures in times of absence, heating costs can be saved without any loss of comfort. Reducing the room temperature by only a few °C does further add to reduction of heating energy consumption and respective CO2 pollution.
The actuator generates the required electrical energy for operation (motor, sensors and radio communication) by means of a built-in thermoelectric generator (TEG) and therefore operates maintenance-free. It is powered from the temperature difference between the radiator heat and ambient temperature (usually room temperature). An additional energy source such as a battery or external power supply is not required. The internal energy storage is fully charged upon delivery, so that sufficient energy is available for installation and up to approximately one year of operation. In winter and heating season, the actuator then supplies itself independently trough the converted heat of the heating circuit. Due to the surplus of generated energy in winter, the internal storage provides sufficient energy for 365 days per year operation including transition periods and summer.
The product is delivered in mounting position (off) with the valve plunger completely retracted. The drive does recognize when installed on a valve body by means of internal force and travel distance measurement. Unmounted activation does allow to execute Remote Commissioning operation (Instant SIGNAL telegram is transmitted immediately after each activation from mounting position) but will always return the device back to mounting position to switch off. The drive does have a built-in motor error detection "ACO". The ACO bit does signal incomplete or unsuccessful reference runs from mounting, motor issues during normal operation as well as motor runs from mounting position and back to mounting position (Section 8.2.6).
The actuator operates with the EnOcean equipment profiles EEP A5-20-06 in either valve position (% value transmitted) or temperature setpoint using its internal temperature control loop (°C setpoint transmitted). The device has a built-in flow temperature sensor to automatically switch its Radio communication cycle (2, 5 or 10 minutes) based on available radiator temperatures. Installation and activation will immediately set the radio communication interval to every 2 minutes and for an installation period of 30 minutes to provide quicker feedback (Section 8.2.9). The ambient temperature value transmitted during such installation period is the raw and actual temperature (Without approximation and smoothing). The device transmits a variety of information to the room control unit including flow and ambient temperature, received radio signal strength, radio communication failure, window open detection (Refer to Section 8). The control units responds either with a new position value in the range 0% (valve closed) to 100% (valve open) or temperature setpoint (0 ... 40°C). Setpoint changes will be instantly processed and new position values are calculated.
The MVA005 has a red and a green LED to support and indicate successful or failed operations for activation and deactivation (More details in Section 6).
The device is equipped with a dial for local user setpoint changes that are instantly transmitted to the room controller. The controller however decides whether or not and how these local changes are accepted and processed by responding with a corresponding telegram answer that includes or ignores the local change request. In valve position mode, all local changes are transmitted as relative values. Changes in temperature setpoint mode are added or subtracted to the current set point temperature and transmitted as absolute temperature value on the controller (Section 8). Successful local inputs are confirmed by a corresponding number of discreet ton signals. Successive inputs within a maximum time period of 5 seconds time are transmitted as a result value to the room controller. Example: 2 x right (+ 2°C) followed by 2 tone signals. Within the 5 seconds period 3 x left (-3°C) followed by 3 tones. The result of -1°C is transferred after 5 seconds
MAR 2019 Page 4 / 33 MVA005_1DS_0319v2e.docx
MVA005 User manual and Datasheet
on the room control unit. There will be no further tone signal to confirm the result of -1°C. Incorrect inputs will be displayed by an approx. 2 seconds long red LED signal. Failed attempts will require a waiting period of 2 seconds. Local changes will lead to an instant telegram transmission to the room controller. In case of no response from the correspondent room controller, another telegram will be transmitted 1 second later.
Integrated temperature sensors (valve body and environment) are both used to control the radio interval and internal temperature controller, window-detection as well as freeze protection. The ambient sensor is used to measure the room temperature. During heating operation, the ambient sensor is influenced by the near-field of the radiator as well as self-heating of the metallic device housing. The resulting temperature failure due to offset is compensated on the basis of the flow sensor and a built-in temperature compensation (approximation), as well as a subsequent smoothing function. Within the first 30 minutes after activation, the actuator sends the actual ambient temperature without any corrections. After 30 minutes, the device sets the ambient temperature to its smoothing start value to 20°C that will be kept as long as the calibration cycle takes. The approximation process in a non-heating cycle takes 3 x 10 minutes. Device activation in an active heating cycle will extend the start value and smoothing cycle to as long as the measured ambient and flow sensor values stabilize with deviations smaller than 1°C. When operated in temperature setpoint, the use of an external room temperature sensor is recommended which is then transmitted to the MVA005 with every 4BS telegram through the room controller. Without external room sensor, the built-in ambient sensor is used with the respective in accuracy given the nearfield radiator environment or any other related effects such as mounting position, curtains, furniture. (See picture 4.1).
Anti-freeze protection uses the flow sensor integrated in the metallic valve connection. Standard freeze protection is active at <6°C. With a temperature setpoint transmission of 0°C, than the freeze protection temperature is also lowered to 0°C. It does not matter if the 0°C setpoint value was requested by radio or by manual adjustment.
Alternate flashing of red and green LEDs in 0.5 second intervals signals a sensor error (short circuit or interruption). In this condition, normal operation is not possible.
Window open detects any temperature drop within a time period of 2 minutes on the local ambient temperature sensor. Once a given negative temperature change is detected, the device sets the DWO bit (Section 8.2.7) and immediately reports the state transmitting a 4BS telegram to the room controller. Its transmitted ambient temperature is the actual temperature value (no approximation or smoothing). The window open detection function is limited to the transmission of data telegrams and setting the DWO bit, no further internal reactions by the actuator apply. The detection of a temperature drop depends on a recognizable stream of cold air in the close environment of the actuator. For a reliable detection, the drive must be installed in unspoilt situation and on radiators below the respective window. Fully opened windows in winter season are usually reliably detected at low outside ambient temperatures. Window in tilt position and heaters in faraway distance to the window cannot be detected reliable. The window open function is independent of the selected communication interval and automatically runs every 2 minutes. Should the temperature fall further and below freeze protection temperature of 6°C (respectively 0°C), the drive automatically opens to prevent from freeze related damages.
Radio failures after 6 unsuccessful 4BS communication attempts in paired situation are reported with its status bit RCE. The actuator automatically switches to its internal temperature control using the last received and valid temperature setpoint from the control unit. With the lack of a valid temperature setpoint °C value (e.g. SPS=0 operation), the internal default value of 21°C is used. Radio signal strength of the received telegram (RSS) is also activated due to lack of incoming data telegrams. There is no change on the radio communication cycle. The local offset function of the dial remains active and any local adjustments are calculated from a default value 21°C. E.g. 5 x left decreases the setpoint from 21°C to 16°C, independent from the last received setpoint value. Due to lack of response from the master control unit keeps the drive this setpoint and regulates accordingly. Consecutive local changes are again calculated from the default value of 21°C, e.g. 3 x right = 24°C followed by 1x right = 22°C. The drive returns to normal operation, once the radio communication is re­established.
When permanently use in unheated rooms, the internal storage will be ultimately discharged. In such circumstance, the drive automatically opens to 50% for recharging. For operation in unheated rooms, the valve and its EEP A5-20-06 provide options to reduce and minimize energy consumption through either stand-by operation (SBY Bit) or summer bit (SB) 8 hours radio interval. Using the local offset input, the drive can at any time be activated from standby (SBY) and returns to normal operation.
MAR 2019 Page 5 / 33 MVA005_1DS_0319v2e.docx
MVA005 User manual and Datasheet
The MVA005 is equipped with hard - and software functions to simplify installation, control and real-time monitoring. Apart from standard, manual 4BS teach-in are EnOcean Remote Commissioning (ReCom) operations available to teach and configure the device prior deployment or during operation. ReCom is operated with separate from 4BS and periodically transmitted SIGNAL (0x09) telegrams. Single or multiple ReCom commands must be executed within an 8 seconds time period after the UNLOCK command. ReCom can be used to set its link-table and change device-internal parameters such as control loop gain, temperature offset parameter or readout of its internal storage value (Refer to Section 9.5).
The drive can be restarted by means of manual RESET (Section 6.5). Holding the dial in one of the two end positions for 10 seconds restarts the drive, runs a reference run and activates the 30-minute maintenance interval. The drive then communicates for the next 30 minutes in a 2 minute interval. The ambient temperature is the effective measured temperature of the ambient sensor. After the maintenance interval, the temperature approximation and smoothing function restarts. Existing teach-in connections to the room controller and remote commissioning settings are retained during manual RESET.
4.1 Picture MVA005 with dial for local control
Dial for local control with +/- marking. One Red and Green LED are positioned below the cover at marked positions. The ambient temperature sensor is centrally positioned between both LEDs.
LED RED
Dial
LED GREEN
Temperature Sensor
below the cover
MAR 2019 Page 6 / 33 MVA005_1DS_0319v2e.docx
MVA005 User manual and Datasheet
5 Energy-supply through thermal Energy Harvesting
The actuator generates the necessary electrical energy for operation by means of a thermoelectric generator (TEG), which gains electrical energy from the temperature difference between radiator flow and room temperature. During the heating season, excess energy is accumulated in the internal storage for operation in transition periods and summer. The energy balance of the actuator is designed to allow operation through 365 days per year when used in typical radiator heating installations.
If, in exceptional cases, the storage voltage drop below a certain limit, the actuator reports this status to the room controller and takes the protection position (50% valve opening or maintains the set value, whichever is the higher). Subsequently, the actuator goes to sleep and waits until the memory is re-charged by the thermoelectric generator back to a sufficient level. As soon as enough energy is available, the actuator resumes normal operation.
The protection position ensures that the heating valve cannot calcify in an end position and freeze protection is ensured. Unexpected room temperatures will occur.
MAR 2019 Page 7 / 33 MVA005_1DS_0319v2e.docx
MVA005 User manual and Datasheet
6 User Control - Quick overview table
6.1 Installation with Manual Pairing (Teach-In)
No Objective Button
No.
1 Pairing from
mounting position (OFF) OR from normal operation
2 Mounting Mount the actuator before
3 Reference run
and normal operation
Turn dial to end position Left OR Right and hold 5 seconds.
Turn to end position Left OR Right for short press (< 1 second)
Action LED or Tone
Unit transmits a teach telegram (1x green LED), connects with the controlling unit and confirms the successful teach-in with a second flash green LED. The unit remains in mounting position. Any actuator not in mounting position will activate the motor and return to mounting position to switch off the device.
executing run-in sequence and normal operation. Consider required adapter (Section 14) Unit executes run-in sequence and enters normal operation.
Radio communication will occur every 2 minutes and for a time duration of 30 minutes after activation. Communication after 30 minutes follow the 4BS settings transmitted by the room control unit.
Reasons for
activity
After 5 seconds 1x green LED for teach sent
Teach-in successful: 1x green LED
Failure (not teached): 3x red LED
No tone signals.
Success: 1x green LED
Failure: 3x red LED
No tone signals
failure
Controller or gateway either not present or not in pairing mode, so that pairing fails
Mounting failure (e.g. missing adapter), Motor failure, Gear failure Unmounted will return the motor to mounting position and switch off the device.
6.2 Local offset
1 Local Offset
Operation in Temperature Setpoint (°C) (Internal control loop)
MAR 2019 Page 8 / 33 MVA005_1DS_0319v2e.docx
Turn to end position Left OR Right for short press.
Turn dial left for 1 or up to 5 times until its end position: Every successful actuation will decrease the actual setpoint temperature by 1°C and transmit the new setpoint as absolute value.
Turn dial right for 1 or up to 5 times until its end position: Every successful actuation will increase the target temperature by 1°C.
Success: 1 … 5 tone signals according the number of inputs
Failure: Red flashing LED for 2 seconds. (Left and right
No tone signals:
No local actuation detected or accepted.
Device is in mounting position.
MVA005 User manual and Datasheet
2 Local Offset
Operation in Valve Position (%)
Turn to end position Left OR Right for short press.
The temperature setpoint may be changed by up to +/- 5°C. Multiple local inputs within one cycle time frame of 5 seconds are internally cumulated to one desired target value.
Individual local input cycles are open for a max. time window of 5 seconds and concluded with a telegram transmit including the desired target temperature as absolute °C temperature value.
Resulting changes in motor position will only be executed when the room controller confirms the local change with its responding and next data telegram. Turn dial left for 1 or up to 5 times until its end position: Every successful actuation will signalize the controller the desired reduction in target temperature with a relative value (e.g. 0x7F for -1)
Turn dial right for 1 or up to 5 times until its end position: Every successful actuation will signalize the controller the desired increase in target temperature with a relative value. (0x01 when +1)
The desired temperature setpoint change communicated to the controller may be changed by up to +/- 5. Multiple local inputs within one cycle time frame of 5 seconds are internally cumulated to one desired target value.
Individual local input cycles are open for a max. time window of 5 seconds and concluded with a telegram transmit including the desired target temperature as absolute °C temperature value.
Resulting changes in motor position will be executed when the room controller confirms the local change with its responding and next data telegram.
inputs in one cycle).
Wait for 10 seconds.
Success: 1 … 5 tone signals according the number of inputs
Failure: Red flashing LED for 2 seconds. (Left and right inputs in one cycle).
Wait for 10 seconds.
No tone signals:
No local actuation detected or accepted.
Device is in mounting position.
MAR 2019 Page 9 / 33 MVA005_1DS_0319v2e.docx
MVA005 User manual and Datasheet
6.3 Deactivation and RESET
1 Deactivate,
Move to mounting position, Switch off
Disassembly
2 RESET
followed by normal operation.
Turn to end position Left OR Right and hold for at least 5 sec.
Turn to end position Left OR Right and hold for 10sec.
Green LED appears, than release.
3x red LED indicates teach-in failure which however does not play any role when deactivating the device. Motor moves back to mounting position and device switches off.
Reactivation in mounted position will restart the device with no changes to previously set parameters including link table settings to enter normal operation.
Turn dial to left or right until its end position and hold for at least 10 seconds until the 2nd green LED appears, than release.
When mounted, teached and active: Device enters installation radio cycle of 2 minutes for a 30 minutes duration. Transmitted ambient temperature is the raw and actual temperature (no approximation, no smoothing).
In case of Radio communication failure: Device switches to Temperature setpoint and 21°C.
Success: After 5 seconds 1x green LED followed by 3x red LED
Failure: No LED
No tone signals
Success:
1x green LED after 5 seconds followed by a 2nd green LED after another 5 seconds (10 seconds in total).
No LEDs:
Try again and hold the dial end position tight. Do not release during the 5 seconds time period.
No LEDs:
Try again and hold the dial end position tight. Do not release during the 10 seconds time period.
MAR 2019 Page 10 / 33 MVA005_1DS_0319v2e.docx
Loading...
+ 23 hidden pages