IMPORTANT NOTE: This instrument is manufactured and calibrated to meet product specifications.
Please read this manual carefully before installation and operation. Any unauthorized repairs or
modifications may result in a suspension of the warranty.
Available in Adobe Acrobat pdf format
Page 3
UF AV5000 Area-Velocity Flow Meter
CONNECTIONS:
POWER INPUT: 100 to 240 VAC 50/60Hz. No adjustments are necessary for voltages within this
range. Connect L (Live) N (Neutral) and AC Ground.
Optional DC: 9-32 VDC. Connect to + and -terminals.
Optional Thermostat and Heater modules are available rated for 115 VAC or 230 VAC.
IMPORTANT NOTE: AC power input and relay connection wires must have conduit entry to the
instrument enclosure. Installation requires a switch, overcurrent fuse or circuitbreaker in the building (in
close proximity to the equipment) that is marked as the disconnect switch.
Risk of electric shock. Loosen cover screw to access connections. Only qualified personnel
!
should access connections.
Note: Use of instrumentation over 40°C ambient requires special field wiring.
Note: User replaceable fuse is 2 Amp 250V (T2AL250V).
FUNCTION TEST:
Connect the sensor to the TDCR terminals as shown below, then apply
power. Allow 30 seconds for the UF AV5000 to initialize.
A. Place QZ02L sensor (flat to the bottom) in a bucket of water
about 6” deep and select Level mode (from UNITS/MODE
menu) to see a level reading.
B. Select
reading.
Velocity mode and stir the water to see a velocity
From
mode displays the flow rate in engineering units (e.g. gpm, litres/sec, etc.) Press
the 9to store your selection then the ª to the next menu item.
item and ¨ to enter. When settings are completed press 9 to store and return to
the Calibration menu.
20mA Flo
[5V Flo]
Note
: Analogue output can be selected as 4-20mA or 0-5V in Special Functions.
Press ¨and enter the flow rate value for 20mA.
4mA Flo
[0V Flo]
20mA Vel
[5V Vel]
4mA Vel
[0V Vel]
20mA Level
[5V Level]
Press ¨and enter the flow rate value for 4mA.
Press ¨and enter the velocity value for 20mA.
Press ¨and enter the velocity value for 4mA.
Optional for QZ02L-A type transducer. Press ¨and enter the
level value for 20mA.
4mA Level
[0V Level]
Optional for QZ02L-A type transducer. Press ¨and enter the
level value for 4mA.
MaxRg
Only for PZ12LP/QZ02L-B type transducer. Press ¨and enter
the zero water level (distance from the PZ12-LP sensor to the
zero water level).
MinRg
Only for PZ12LP/QZ02L-B type transducer. Press ¨and enter
the max level (distance from the PZ12-LP sensor to the max
water level).
Min Vel
Press ¨and enter a minimum velocity cutoff. Forward and
reverse velocities less than
Min Velwill be forced to zero.
Min Level
Optional for QZ02L-A type transducer. Press ¨and enter a
minimum level cutoff. Level reading less than
Min Level will
be forced to zero.
Page 11
UF AV5000 Area-Velocity Flow Meter
Lvl Offset
Optional for QZ02L-A type transducer. Press ¨and enter an
offset to level measurement. Set to 0.00 when sensor mounted
on floor of channel. When sensor is mounted above the floor
of the channel enter the distance between channel floor and
bottom of sensor.
Note: 4mA is not affected by
Lvl Offset settings. 4mA is the
bottom of the channel or pipe.
LEVEL
SENSOR
SENSOR ELEVATED
ABOVE FLOOR OF
TOP VIEW
USE THE MB-QZ
STAINLESS STEEL
MOUNTING BRACKET
(SUPPLIED)
PIPE OR CHANNEL
SENSOR
SIDE VIEW
Damping
Increase damping to stabilize readings under turbulent flow
readings or to reject spurious level readings. Decrease for
faster response to changes in flow.
LOE Time
Press ¨and enter the number of seconds allowed without
receiving an echo before the UF AV5000 displays
, and Control relays change state as calibrated under
LOSS
Relay Parameters.
Press 9 from the
Calibrationdisplay to return to Menu Selections.
SENSOR
END VIEW
U-SHAPE STAINLESS STEEL
18 GA. RECOMMENDED
HEIGHT AS REQUIRED
ECHO
Page 12
UF AV5000 Area-Velocity Flow Meter
--Channel Setup-----TypeRound
}
Max Height0.75ft
CHANNEL SETUP
Round SelectRoundfor open pipes. SetMax Height to the inner diameter
of the pipe.
Rectangle Select Rectangle for rectangular channels. Enter the channel
width.
Trapezoid Select Trapezoidfor trapezoidal shaped channels. Specify the
Width and Slope of the channel as shown in the following
illustration.
TRAPEZOIDAL
Egg Select Egg for Egg shaped channels. Enter the Max Heightof the
channel.
CHANNEL
WIDTH
SLOPE = x
y
x
y
HEIGHT
=3R
Page 13
R
2R
3R
R/2
UF AV5000 Area-Velocity Flow Meter
--Custom Channel----TypeCustom
}
Reset DataNo
Max Height0.75 ft
Division0.05 ft
Increment #0
Width0.000 ft
Level0.000 ft
CUSTOM CHANNELS
Reset DataOld data MUST be removedbefore enteringdata for a new
Max HeightEnter the maximum height of the channel.
DivisionDivide the maximum height into equal increments (maximum
of 40) and enter this division value (example 1”, 1 cm etc.)
Increment #Enter the increment number if you want to edit aprevious
entry or to skip entering widths for some levels (Note: The
custom channel will interpolate widths between entry points).
WidthEnter the measured width of the channel at the level shown
(Note: To enter 0 width you must press ¨ and then 9 to store
a 0 width data point).
LevelDisplays the level of the channel for each increment and width
entry.
MAX
HEIGHT
Note
:
Custom channel data in equal width increments with variable height
measurements must be converted to the format shown above using the “Channel
Data Translator” PC software.
Offset digits to the Off set point.
LOE mode Specify the state of the relay for loss of echo
condition:
Press 9 to return to
On set point.
On set point.
Onset point.
Off, Onor Hold.
Menu Selections
Page 15
UF AV5000 Area-Velocity Flow Meter
--Special FunctionsLanguageEnglish
}
Analog Out4-20mA
BacklightHigh
Reset TotalizerNO
Negative TotalsNO
Reverse FlowNO
Cal Constant1.000
--Special Functions-
LanguageEnglish
BacklightHig
}h
Medium
Low
Key Hi/Lo
Key High
Key Med
Key Low
Off
DATA LOGGING (OPTIONAL)
Refer to Options section of this manual.
SPECIAL FUNCTIONS
Language Select English, Frenchor Spanish
Analog Out Select 4-20mAor0-5V mode for the analog output.
Backlight Select High, Medium orLow for continuous backlight.
Select
keypress and then
again.
Select
and then backlight off until a key is pressed again.
Reset Totalizer Press ¨ and select Yes to erase and restart the totalizer
at zero.
Negative Totals Select Yesto have reverse flow readings deducted from
the totalizer. Select
ignore reverse flow.
Reverse Flow Select Yesto invert the sign of the flow measurement.
Cal ConstantScales the velocity reading. Set to 1.000 for QZ02L
transducer.
Restore Defaults Select Yes and press 9 to erase all user settings and
return the instrument to factory default settings.
New PasswordSelect any number from0000 to9999 and press 9.
Default setting of 0000 will allow direct access to the
calibration menus. Setting of any password greater than
0000 will require the password to be entered to access
the calibration menus.
Press 9 to return to
Menu Selections.
KeyHi/Lo for high backlight (for 1 minute) after a
Simulate a level reading and a velocity reading (Press ¨ to change value
and9 to store).
Review the resulting Flow reading, the three analog outputs (A: Flow, B:
Velocity, C: Level) and the relay states. Note: Outputs will follow the
displayed values.
Exercises the 4-20mA output, digital display and control relays (does not
affect the totalizer or optional data logger).
Press the 9 to terminate simulation and return to the
Menu Selections screen.
Page 17
UF AV5000 Area-Velocity Flow Meter
INSTALLATION - SENSOR LOCATION
1. Choose a sensor mounting location where silt or deposits are least likely to accumulate.
2. For best results flow should be evenly distributed across the channel and relatively free of turbulence.
(The UF AV5000 is very effective at averaging level and velocity readings in turbulent conditions, but
best accuracy and response time is achieved with evenly distributed flow.)
3. Avoid vertical drops, obstructions or elbows immediately up and downstream from the sensor. Locate
the QZ02L sensor at least 10 times maximum Head (level) and 10 times the channel width from these
flow disturbances.
QZ02L VELOCITY-LEVEL SENSOR MOUNTING
Mount the QZ02L sensor with the
stainless steel bracket and hardware
supplied. Ensure that the sensor is
parallel to the water surface (check with
a level). Mount with the tapered end of
the sensor pointing upstream and the
sensor cable pointing downstream.
FASTEN MOUNTING
BRACKET WITH A
SET SCREW
Clip or tie wrap the sensor cable securely
to the pipe or channel wall.
Note: The mounting bracket is designed
to release the sensor if weeds or rags are
caught by the sensor.
MB-QZ
MOUNTING
BRACKET
TOP VIEW
SIDE VIEW
FASTEN SENSOR
CABLE TO PIPE OR
CHANNEL WITH
METAL CLIPS OR
TIE WRAPS
VELOCITY/LEVEL SENSOR
LEVEL
SENSOR
INSERT SENSOR INTO
MOUNTING BRACKET
END VIEW
SENSOR
QZ02L
FLOW
FLOW
Page 18
UF AV5000 Area-Velocity Flow Meter
GOOD
END VIEW
SENSOR
SENSOR
BAD
END VIEW
SENSOR
SENSOR
FLOW
FLOW
SENSOR
SENSOR
END VIEW
SENSOR
SENSOR
END VIEW
Page 19
UF AV5000 Area-Velocity Flow Meter
OPTIONAL PIPE BAND MOUNTING WITH QZ02L SENSOR
Install the stainless steel pipe band with the sensor mounting
bracket at the invert (bottom) of the pipe. Ensure that the
sensor bracket is parallel to the water surface (check with a
level). Mount so the tapered end of the sensor will point
upstream and the sensor cable will point downstream. (Turn
the ¼” adjustment nut clockwise to expand the bracket and secure to the pipe wall by friction fit.)
Insert the sensor into the mounting bracket and tie-wrap the sensor cable securely to the pipe band using
the holes provided.
BAND
ADJUSTMENT JACK
VSJ PIPEMOUNTING BAND
DETAIL
BAND ADJUSTMENT
SENSORMOUNTING
BRACKET
JACK
OPTIONAL QZ02L-DP VELOCITY SENSOR MOUNTING
Mount the velocity sensor at or near the bottom of the channel or pipe in a position where it will be
continuously submerged. The QZ02L-DP velocity sensor does not have to be parallel to the water
surface. Position where silt or solids will not build-up on the sensor.
Page 20
UF AV5000 Area-Velocity Flow Meter
OPTIONAL PZ12-LP LEVEL SENSOR MOUNTING
Mount the PZ12-LP non-contacting ultrasonic level sensor in an unobstructed position at least 203.2mm
(8”) above the high water level. Install the stainle ss steel mounting bracket in a horizontal position
(check with a level) and then insert the PZ12-LP sensor.
PZ12-LP SENSOR
MB12 - MOUNTING BRACKET
PZ12-LP MANHOLE MOUNTING
QZ02L-DP VELOCITY SENSOR
PZ12-LP PIPE MOUNTING
PZ12-LP
PZ12-LP
WATER
WATER
Page 21
UF AV5000 Area-Velocity Flow Meter
ENCLOSURE INSTALLATION
Locate the enclosure within 6 m (20 ft) of the sensor (up to 150 m - 500 ft optional). The enclosure can
be wall mounted with the four mounting screws (included) or panel mounted with Option PM Panel
Mount kit from Micronics Limited.
Avoid mounting the enclosure in direct sunlight to protect the electronics from damage due to
overheating and condensate. In high humidity atmospheres, or where temperatures fall below freezing,
Option TH Enclosure Heater and Thermostat is recommended. Seal conduit entries to prevent moisture
from entering enclosure.
NEMA4X (IP66) WITH CLEAR COVER
1. Open hinged enclosure cover.
2. Insert #8 screws (supplied) through the four enclosure mounting holes
to secure the enclosure to the wall or mounting stand.
Additional conduit holes can be cut in the bottom of the enclosure with a
hole saw or Greenlee-type hole cutter.
DO NOT make conduit/wiring entries into the top of the enclosure.
Note: This non-metallic enclosure does not automatically provide
grounding between conduit connections. Grounding must be provided as
part of the installation. Ground in accordance with the requirements of the
National Electrical Code. System grounding is provided by connecting
grounding wires from all conduit entries to the steel mounting plate or
another point which provides continuity.
CLEANING
Cleaning is not required as a part of normal maintenance.
COVER
ENCLOSURE
MOUNTING
HOLES
ENCLOSURE
END VIEW
Page 22
UF AV5000 Area-Velocity Flow Meter
FIELD TROUBLESHOOTING
The UF AV5000 uses an ultrasonic level sensor to determine channel AREA and an ultrasonic Doppler
sensor to measure flow VELOCITY.
The QZ02L transducer combines both sensors in one housing.
An optional configuration uses the PZ12-LP “down-looking” level sensor and a QZ02L-DP velocity
sensor.
To troubleshoot the UF AV5000, verify correct operation of LEVEL and VELOCITY measurements
separately.
Note: Selecting “Defaults” in theSPECIAL FUNCTION menu will return the instrument to “as-shipped”
factory settings.
LEVEL (QZ02L SENSOR)
SYMPTOMS FAULTS SOLUTIONS
EC bar graph at zero - very turbulent flow - IncreaseLOE time (SPECIAL
FUNCTION
- very aerated flow - relocate sensor or use PZ12-LP
- sensor not level - level sensor with “Bullseye” level
- sediment/dirt/grease build-up on
sensor
-Level display reads 1.0 inches - Level at or less than 1.0 inches
VELOCITY (QZ02L SENSOR)
SYMPTOMS
- No velocity reading - Grease/sediment on sensor
FAULTS SOLUTIONS
- Improper hook-up
- clean sensor with liquid soap
- Clean sensor with detergent
- Check sensor connections
)
Page 23
UF AV5000 Area-Velocity Flow Meter
SENSOR CABLE RESISTANCE TEST
Unplug the green sensor terminal from the Doppler board and connect the sensor wires as shown. With a
multimeter, perform resistance checks for each set of wires. One single loose terminal may cause false
readings.
Test across shield and core of each wire: TMTR (black/white) and RCVR (black). Resistance should be
approximately 82.5K ohms for any cable length. High readings indicate an open circuit and low readings
indicate a short or partial short in the sensor cable.
Page 24
UF AV5000 Area-Velocity Flow Meter
PRODUCT RETURN PROCEDURE
Instruments may be returned to Micronics for service or warranty repair.
1) Obtain an RMA Number from Micronics -
Before shipping a product to the factory please contact Micronics by tele
RMA number (Returned Merchandise Authorization). This ensures fast service and correct billing or
credit.
When you contact Micronics please have the following information available:
1. Model number / Software Version
2. Serial number
3. Date of Purchase
4. Reason for return (description of fault or modification required)
5. Your name, company name, address and phone number
phone, fax or email to obtain an
2) Clean the Sensor/Product -
Important: unclean products will not be serviced and will be returned to the sender at their expense.
1. Rinse sensor and cable to remove debris.
2. If the sensor has been exposed to sewage, immerse both sensor and cable in a solution of 1 part
household bleach (Javex, Clorox etc.) to 20 parts water for 5 minutes. Important: do not immerse open
end of sensor cable.
3. Dry with paper towels and pack sensor and cable in a sealed plastic bag.
4. Wipe the outside of the enclosure to remove dirt or deposits.
5. Return to Micronics for service.
3) Ship to Micronics -
After obtaining an RMA number please ship the product to the appropriate address below:
:sremotsuC
Micronics
Knaves Beech Business Centre,
Davies Way, Loudwater,
High Wycombe, Buckinghamshire,
United Kingdom, HP10 9QR
Limited.
#AMR
Page 26
UF AV5000 Area-Velocity Flow Meter
AREA-VELOCITY FLOW DATA SHEET
Micronics
Knaves Beech Business Centre,
Davies Way, Loudwater,
High Wycombe, Buckinghamshire,
United Kingdom, HP10 9QR
Please complete and return this form to Micronics. It is
important. We use this information to check our database
for performance of Micronics flow meters in similar
applications, and to provide advice and recommendations
to you. Thanks for your cooperation.
Page 27
UF AV5000 Area-Velocity Flow Meter
LIMITED WARRANTY
_____________________
Micronics
to be free from defects in material and workmanship for
of one year from date of invoice. will replace
repair, free of charge, any product if it has been
proven to be defective within the warranty period. This warranty
does not cover any expenses incurred in the removal and
re-installation of the product.
If a product manufactured by should prove defective
within the first year, return it freight prepaid to
along with a copy of your invoice.
This warranty does not cover damages due to improper
installation or handling, acts of nature, or unauthorized service.
Modifications to or tampering with any part shall void this
warranty. This warranty does not cover any equipment used in
connection with the product or consequential damages due to a
defect in the product.
All implied warranties are limited to the duration of this
warranty. This is the complete warranty by
other warranty is valid against .
allow limitations on how long an
limitation of incidental or consequential damages, so the above
limitations or exclusions may not apply to you.
warrants, to the original purchaser, its
Micronics
Micronics
Micronics
Micronics
implied warranty last
Some states do not
products
a period
Micronics
Micronics
or
and no
s or
This warranty gives you specific legal rights, and you may also
have other rights which vary from state to state.
Micronics Limited.
Page 28
UF AV5000 Area-Velocity Flow Meter
APPENDIX A – OPTIONS
EXTRA SENSOR CABLE
(OPTION VXC)
Each Micronics UF AV5000 flow meter includes 7.6 m. (25 ft), 15 m. (50 ft) or 30 m. (100 ft) tri-coaxial
sensor cable. This cable is shielded from electrical interference and is watertight with a polyurethane
jacket. Additional cable and Cable Junction Box (Option VJB) may be ordered with the Flow Meter, or
the cable may be spliced and extended up to 152 m (500 ft) total length as required during installation.
No adjustment is required when the sensor cable is extended or shortened. Use only Micronics tricoaxial VXC shielded cable, or run three RG174U coaxial cables in a metal conduit.
Extended sensor cable can be installed in conduit for mechanical protection. Recommended installation
with a metal junction box is illustrated below:
EXTENDED SENSOR
CABLE TO ELECTRONICS
ENCLOSURE
CONDUIT (BY CUSTOMER)
If Required For Mechanical Protection
TRI-COAXIAL
SHIELDED CABLE
500 ft (152m)
MAX. LENGTH
OPTION VJB SENSOR CABLE JUNCTION BOX
GND
NEMA4 (IP55) STEEL
BLK/WHT
BLK/WHT
BLK/GRN
BLK/GRN
SHIELD
BLK
BLK
CORE
SENSOR CABLE
25 ft (7.6m) SHIELDED
TRI-COAXIAL
GND WIRES
MUST BE CONNECTED
TO GND TERMINAL
SENSOR
COAXIAL CABLE PREPARATION
VXC Doppler sensor cable can be cut and spliced up to a maximum length of 152 m (500 ft). Cable ends
must be prepared as illustrated below.
GOOD
BAD
BLACK
(CONDUCTIVE)
SLEEVE
HAS BEEN
REMOVED
BLACK
(CONDUCTIVE)
SLEEVE
HAS NOT BEEN
REMOVED
Page 29
UF AV5000 Area-Velocity Flow Meter
SENSOR CABLE JUNCTION BOX
(OPTION VJB)
Optional Watertight steel NEMA4 (IP55) Junction Boxes with terminal strips are available from
Micronics Limited.
DIMENSIONS
OPTION VJB - JUNCTION BOX
140mm
(5.5”)
73mm
28mm
(1.12”)
84mm
(3.31”)
(2.86”)
127mm ( 5”)
Page 30
SS PIPE MOUNTING BAND – OPTION VSJ
Use optional VSJ stainless steel Pipe Mounting Bands
for easy Sensor installation in round pipes.
Each Pipe Band includes:
Band Adjustment Jack allowing ±0.5” (13 mm) adjustment from
DETAIL
BAND ADJUSTMENT
JACK
BAND
ADJUSTMENT JACK
VSJ PIPE MOUNTING BAND
SENSOR MOUNTING
BRACKET
the nominal band size
Stainless steel bracket for Sensor mounting
Pre-drilled for tie wraps (included) to secure Sensor cable
UF AV5000 Area-Velocity Flow Meter
CODEBAND SIZE
VSJ66”/150 mm ID pipes
VSJ88”/200 mm ID pipes
VSJ1010”/250 mm ID pipes
VSJ1212”/300 mm ID pipes
VSJ1414”/350 mm ID pipes
VSJ1515”/375 mm ID pipes
VSJ1616”/400 mm ID pipes
VSJ1818”/450 mm ID pipes
VSJ2020”/500 mm ID pipes
VSJ2424”/600 mm ID pipes
VSJ3030”/750 mm ID pipes
END
BRACKET
VSJ HALF-PIPE
MOUNTING BAND
ADJUSTMENT
FLOW
SENSOR MOUNTING
BRACKET
JACK
Mounting Instructions:
Install the stainless steel pipe band with the
sensor mounting bracket at the invert (bottom)
of the pipe. Ensure that the sensor bracket is
parallel to the water surface (check with a
level). Mount so the tapered end of the sensor
will point upstream and the sensor cable will
point downstream. Turn the ¼” adjusting nut
clockwise to expand the bracket and secure to
the pipe wall by friction fit.
Insert the sensor into the mounting bracket and
tie wrap the sensor cable securely to the
stainless steel pipe band.
Page 31
VSJ32-40 32-40”/800-1000 mm ID pipes
VSJ42-54 42-54”/1100-1375 mm ID pipes
VSJ56-72 56-72”/1400-1800 mm ID pipes
FASTEN SENSOR
CABLE TO P IPE OR
CHANNEL WITH
TIE WRAPS
END VIEW
SENSOR
UF AV5000 Area-Velocity Flow Meter
ENCLOSURE HEATER AND THERMOSTAT - Option TH
Instruments can be factory-equipped with an Enclosure Heater and Thermostat or the module can be
customer-installed. The Thermostat is factory set to turn ON at 4.5°C (40°F) and OFF at 15.5°C (60°F).
Power consumption is 15 Watts.
TO AC POWER SUPPLY
ENCLOSURE SUNSCREEN - Option SCR
Do not mount instrument electronics in direct sunlight. Overheating will reduce the life of electronic
components and condensate may form during the heat/cool cycles and cause electrical shorts.
280 mm / 11”
Note:
Exposure to direct sunlight can cause
overheating and moisture condensation
which will reduce the operating life of
electronics.
Protect Instruments from direct sunlight
with this iridite finished aluminum sun
screen (Micronics Option SCR).
Seal conduit entries with caulking
compound to further reduce moisture
condensation.
280 mm
11”
127 mm
5”
Page 32
Page 33
UF AV5000 Area-Velocity Flow Meter
POWER INPUT OPTION
9-32VDC
UF AV5000 Flow Meters may be ordered factory-configured for 9-32VDC power input.
QUICK BENCH TEST:
Connect Sensor as shown below, then Power. Test operation of the UF AV5000 by holding the sensor in
one hand and rubbing your thumb or fingers briskly across the face (plastic surface) of the sensor.
Allow 15 seconds for the UF AV5000 to process the signal and display a flow value.
CONNECTIONS:
POWER INPUT: Connect 9-32VDC to the + and - terminals. The Power Input GND terminal must be
connected to the nearest Ground pole. A 1-amp fuse in line is recommended.
UF AV5000 Area-VelocityFlow Meter
NO
C
NC
NO
C
NC
–
+
4-20mA
FLOW
RLY2
RLY1
CN
C
NO
CN
C
NO
CN
C
NO
CN
C
NO
RLY3
RLY4
RLY5
RLY6
EXTRA RELAYS OPTION
SNESOR
GND
RVCR
GND
TMTR
GND
G NR
THW
BLK
DC
+–
+–
+–
VELOCITY
LEVEL
4-20mA
VELOCITY
4-20mA
LEVEL
AC
GND
TRANSDUCER
GND
UF AV5000 Area-Velocity Flow Meter
Page 34
UF AV5000 Area-VelocityFlow Meter
ENCLOSURE HEATER AND THERMOSTAT - Option TH
Instruments can be factory-equippedwith an Enclosure Heater and Thermostat or the module can be customer-installed.The Thermostat is factory set to turn ON at 4.5°C (40°F) and OFF at 15.5°C (60°F). Power consumption is 15 Watts.
ENCLOSURE SUNSCREEN - OptionSCR
Do not mount instrument electronics in directsunlight. Overheating will reduce the life ofelectronic components and condensate may form during the heat/coolcycles and causeelectricalshorts.
Log Site IDEnter a number from00 to99. The site ID will become part of
the downloaded file name to help distinguish downloads from
different instruments. Press
to store the setting.
ModeSelect Velocity, LevelorFlow. Press to store the setting.
Set DatePress or to scroll and select Month, Day and Year. Press
to store the setting.
Set TimePress or to select the current time in Hours, Minutes and
Seconds. Press
to store the setting.
IntervalPress or to select the logging interval. Flow rate reading
will be stored at each time interval. Press
to store the
setting.
NOCNC
NOCNC
–+
4-20mA
FLOW
RLY2
RLY1
CN
C
NO
CN
C
NO
CN
C
NO
CN
C
NO
RLY3
RLY4
RLY5
RLY6
EXTRARELAYSOPTION
SNESOR
GND
RVCR
GND
TMTR
GND
GNR
THW
BLK
DC
+–
+–
+–
VELOCITY
LEVEL
4-20mA
VELOCITY
4-20mALEVEL
ACGND
TRANSDUCER
GND
UF AV5000 Area-VelocityFlow Meter
Note: Press
to Log and or to Delete and to delete
the log file. Press
and or to Start and to restart the
logger.
LogStop,Startor Deletethe log file. You MUST delete old file and
start a new log to apply any changes that have been made to
the
Log Site ID, Mode or Interval.
View 24-hr formatted Reports on the UF AV5000 display. Press
from the RUN
display to view a formatted flow report from instruments with a built-in data
logger. Press
to pan through
Level,Velocityand Flow summaries. Press to
scroll down one day or repeatedly to scroll to a specific date. Up to 365 days can
be stored. Newest date will overwrite the oldest. Press
to return to the main
display.
UF AV5000 Area-VelocityFlow Meter
Note: Press
to Logand ortoDelete and to delete
the log file. Press
and orto Start and to restart the
logger.
LogStop,StartorDeletethe log file. You MUST delete old file and
start a new log to apply any changes that have been made to the
Log Site ID, Mode orInterval.
View 24-hr formatted Reports on the UF AV5000 display. Press
fromthe RUN display to view a formattedflow report from instruments with a built-in datalogger. Press
to pan through
Level,VelocityandFlowsummaries. Press to
scroll down one day or repeatedlyto scroll to a specific date. Up to 365 dayscan be stored. Newest date willoverwrite the oldest. Press
to return tothe main
display.
RETRIEVE LOG FILE
Plug a USB Flash Memory Drive (not supplied by Micronics) into the USB output
cable from the instrument. The instrument display will show the message
Downloading until the log file is transferred to the memory card and then display
Completed. The USB flash drive may be removed.
Download file names will appear in this format:
AVFM� �00A.LOG
MODELTAG DOWNLOAD
Tag is set according to the
Log Site IDentered in the instrument Data Logging
menu.
Download letter will be A for the first download from an instrument. B for the
second, then C etc. At the letter Z a - character will appear indicating that the
maximum number of downloads for that instrument are on the USB flash drive.
Older files can be erased or moved from the flash memory drive or a new memory
drive can be used.
OPENING LOG FILES
UF AV5000 Area-Velocity Flow Meter
Page 35
UF AV5000 Area-VelocityFlow Meter
Note: Press
to Logand ortoDelete and to delete
the log file. Press
and orto Start and to restart the
logger.
LogStop,StartorDeletethe log file. You MUST delete old file and
start a new log to apply any changes that have been made to the
Log Site ID, Mode orInterval.
View 24-hr formatted Reports on the UF AV5000 display. Press
fromthe RUN display to view a formattedflow report from instruments with a built-in datalogger. Press
to pan through
Level,VelocityandFlowsummaries. Press to
scroll down one day or repeatedlyto scroll to a specific date. Up to 365 dayscan be stored. Newest date willoverwrite the oldest. Press
to return tothe main
display.
RETRIEVE LOG FILE
Plug a USB Flash MemoryDrive (not supplied by Micronics) into the USB output cable fromthe instrument. The instrument displaywill show the message
Downloading until the log file is transferred to the memory card and then display Completed. The USB flashdrive maybe removed.
Download filenames will appear in this format:
AVFM��00A.LOG
MODELTAGDOWNLOAD
Tag is set according tothe
Log Site IDentered in the instrument Data Logging
menu.
Download letter will be A for the first download froman instrument. B for the second, then C etc. At the letter Z a - character will appear indicating that the maximum number of downloads for that instrument are on the USB flash drive.Older files can be erased or moved fromthe flash memorydrive or a new memorydrive can be used.
OPENING LOG FILES
UF AV5000 Area-VelocityFlow Meter
Install Micronics Logger on your PC or laptop. Refer to the Help menu in the
program for detailed instructions.
Select File/Open/Instrument Log (.log) to open the log file from your USB flash
drive.
UF AV5000 Area-Velocity Flow Meter
SPECIFICATIONS
Electronics Enclosure:NEMA4X (IP 66), watertight and dust tight, polycarbonate with clear,
shatterproof hinged Lexan cover
Accuracy:Level: ± 0.25% of Range Velocity: ± 2% of Reading Repeatability: 0.1%
Programming:Built-in 5-key calibrator with English, French or Spanish language
selection
Power Input:100-240VAC, 50/60 Hz, (30 W max.)
).xam W 9( CDV23-9 : l ano i tpO
Output:2Isolated 4-20mA, 1000 ohm load maximum or 2 Isolated 0-5V
Control Relay:Qty 2, rated 5 ampere SPDT
Temperature Compensation:Automatic, temperature probe built in to level Sensor
Electrical Surge Protection:Sensor, 4-20mA, AC power input
Environmental Conditions:Relative humidity up to 80%
-23 to 60°C ambient temperature,
maximum 5000 m altitude, pollution degree 4, Installation Category
II.Optional Enclosure Heater recommended for condensation protection
below -1°C (32°F)
UF AV5000 Area-VelocityFlow Meter
188mm/ 7.4”
164 mm / 6.46”
CONDUIT ENTRY
LOCATION
SIDE VIEW
UF AV5000
Area-Velocity
Flow Meter
130mm / 5.12”
254mm / 10”
278mm / 10.94”
Page 36
UF AV5000 Area-Velocity Flow Meter
UF AV5000 Area-VelocityFlow Meter
Velocity/Level Sensor QZ02L
Minimum Velocity:0.03 m/sec (0.1 ft/sec)
Maximum Velocity:6.2 m/sec (20 ft/sec) [reverse flow to -1.5 m/sec (-5 ft/sec)]
Minimum Head:25.4 mm. (1 in)
Maximum Head:4.88 m. (16 ft)
Operating Temperature:-15 to 65°C (5 to 150°F)
Exposed Materials: PVC, epoxy resin, polyurethane, ultem Sensor Cable:7.6 m. (25 ft) submersible polyurethane jacket, shielded, 3 coaxial
Hazardous Rating:CSA rated Intrinsically Safe Class I, Groups C,D, Class II, Groups E,F,G
with optional Intrinsic Safety Barrier
188mm/7.4”
164mm /6.46”
CONDUITENTRY
LOCATION
SIDEVIEW
UF AV5000
Area-VelocityFlowMeter
130mm / 5.12”
254mm / 10”
278mm / 10.94”
UF AV5000 Area-VelocityFlow Meter
Velocity/Level Sensor QZ02L
Minimum Velocity:0.03 m/sec(0.1 ft/sec) MaximumVelocity:6.2m/sec(20ft/sec) [reverse flowto-1.5m/sec (-5ft/sec)]Minimum Head:25.4 mm. (1 in) Maximum Head:4.88 m. (16 ft) Operating Temperature:-15 to 65°C (5 to 150°F)Exposed Materials:PVC, epoxy resin, polyurethane, ultem Sensor Cable:7.6 m. (25 ft) submersible polyurethane jacket, shielded, 3 coaxialHazardous Rating:CSA ratedIntrinsically Safe ClassI, GroupsC,D, ClassII, GroupsE,F,G
with optional IntrinsicSafetyBarrier
188mm/7.4”
164mm /6.46”
CONDUITENTRY
LOCATION
SIDEVIEW
UF AV5000
Area-VelocityFlowMeter
130mm / 5.12”
254mm / 10”
278mm / 10.94”
UF AV5000 Area-VelocityFlow Meter
MB-QZ-MOUNTING BRACKETQZ02L VELOCITY/LEVEL SENSOR
SensorCable
SIDE VIEW
LEVEL
SENSOR
412 mm
41.2 mm
0.56”
162”
76.2 mm
3.00”
12.7 mm
0.5”
16 mm
0.63”
38.1 mm
1.50”
7.6m (25ft)
127 mm
5.00”
Page 37
UF AV5000 Area-Velocity Flow Meter
Optional (Velocity only) Sensor QZ02L-DP
Minimum Velocity:0.03 m/sec (0.1 ft/sec)
Maximum Velocity:6.2 m/sec (20 ft/sec) [reverse flow to -1.5 m/sec (-5 ft/sec)]
Operating Temperature:-15 to 65°C (5 to 150°F)
Exposed Materials: PVC, epoxy resin, polyurethane, ultem Sensor Cable:7.6 m. (25 ft) submersible polyurethane jacket, shielded, 3-coaxial
Hazardous Rating:CSA rated Intrinsically Safe Class I, Groups C,D, Class II, Groups
E,F,G, with optional Intrinsic Safety Barrier
MB-QZ - MOUNTING BRACKET
mm2.14
1.62"
3.00"
76.2 mm
mm2.41
0.56"
25ft (7.6 m)
SensorCable
QZ02L-DP VELOCITY SENSOR
5.00”
SIDE VIEW
127 mm
"05.0
mm7.21
Optional Sensor PZ12-LP
Maximum Range:3.66m (12 ft)
Minimum Range:203.2 mm (8”)
Beam Angle: 8° Operating Temperature:-40 to 65°C (-40 to 150°F)
Exposed Materials: Sensor - PVC, Mounting Bracket - 316 Stainless
nI detar ASC :gnitaR suodrazaH trinsically Safe Class I, Groups
C,D,Class II, Groups E,F,G with
optional Intrinsic Safety Barrier
ROSNESCINOSARTLUPL-21ZPTEKCARBGNITNUOM-21BM
1.50
"
38.1 mm
0.63"
16 mm
25ft (7.6 m)
Coaxial Cable
mm2.97
"21.3
0.218 DIA
(5.5 mm)
3.00"
76.2 mm
mm3.71
"86.0
FACE
VIEW
SIDE
0.25 DIA
(6.35 mm)
4.00"
101.6 mm
mm2.67
"00.3
mm57.51
"26.0
VIEW
Page 38
Thank you for reading this data sheet.
Please contact us for a quotation:
Head Office (UK)
P.O. Box 2124
Chelmsford
Essex CM1 3UP
England
Tel: +44 (0)1245 600 560
Fax: +44 (0)1245 600 030
Email:
General Information/Sales:
info@keison.com
Accounts Department:
accounts@keison.com
USA Office
233 Rogue River Highway #425
Grants Pass
Oregon 97527-5429
USA
Switzerland Office
Zugerstrasse 46
6314 Unterägeri
Zug
Switzerland
Tel: +41 41 541 5877
Fax: +41 41 541 5878
Email:
General Information/Sales:
info@kesn.ch
Accounts Department:
accounts@kesn.ch
Latin America Office
World Trade Centre
Apartado 0832-00708
Ciudad de Panamá
República de Panamá
Tel: +1 503 206 0941
Fax: +1 541 610 1646
Email:
General Information/Sales:
info@keison.com
Accounts Department:
accounts@keison.com
Tel: +507 836 5304
Fax: +507 399 1804
Email:
General Information/Sales:
ventas@keison.com
Accounts Department:
cuentas@keison.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.