Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Emerson Flow customer service
Email:
•Worldwide: flow.support@emerson.com
•Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
United States800-522-6277U.K.0870 240 1978Australia800 158 727
F.2MID flow computer and power supply requirements ............................................................... 218
F.3Flow computer density calculations ........................................................................................218
F.4TPS and external input connections to the flow computer ....................................................... 220
F.5MID support ............................................................................................................................ 220
F.6Read revision and checksum data ............................................................................................221
F.7Secure the meter .....................................................................................................................221
F.8Switch to unsecured mode ...................................................................................................... 224
Configuration and Use Manual v
Contents
viMicro Motion® Compact Density Meters (CDM)
Part I
Getting Started
Chapters covered in this part:
•Before you begin
•Quick start
Getting Started
Configuration and Use Manual 1
Getting Started
2Micro Motion® Compact Density Meters (CDM)
1Before you begin
Topics covered in this chapter:
•About this manual
•Model codes and device types
•Communications tools and protocols
•Additional documentation and resources
1.1About this manual
This manual provides information to help you configure, commission, use, maintain, and
troubleshoot the Micro Motion Compact Density Meter (CDM).
The following versions of the CDM are documented in this manual:
•Compact Density Meter with Analog Outputs
•Compact Density Meter with Analog Output and Discrete Output
•Compact Density Meter with Time Period Signal Output
Before you begin
For the Compact Density Meter with FOUNDATION™ Fieldbus, see Micro Motion® Compact
Density Meters with FOUNDATION™ Fieldbus: Configuration and Use Manual.
Important
This manual assumes that the following conditions apply:
•The meter has been installed correctly and completely, according to the instructions in the
installation manual.
•The installation complies with all applicable safety requirements.
•The user is trained in all government and corporate safety standards.
1.2Model codes and device types
Your device can be identified by the model code on the device tag.
Model codes and device typesTable 1-1:
Model codeDevice nicknameI/O
CDM100M****CCDM mA• Two mA outputs
• RS-485 terminals
CDM100M****DCDM DO• One mA output
• One discrete output
• RS-485 terminals
Electronics mounting
Integral
Integral
Configuration and Use Manual 3
Before you begin
Model codes and device types (continued)Table 1-1:
Model codeDevice nicknameI/O
CDM100M****BCDM TPS• One mA output
• One Time Period Sig-
nal output
• RS-485 terminals
CDM100M****ACDM FF• FOUNDATION™ field-
bus
Restriction
The CDM mA, CDM DO, and CDM FF support a complete set of application and configuration
options. The CDM TPS supports a subset of configuration options. Refer to the product data sheet for
details.
1.3Communications tools and protocols
Electronics mounting
Integral
4-wire remote
transmitter
You can use several different communications tools and protocols to interface with the
device. You may use different tools in different locations or for different tasks.
Communications tools, protocols, and related informationTable 1-2:
Communications toolSupported protocolsScopeIn this manualFor more information
DisplayNot applicableBasic configuration and
commissioning
ProLink III• Modbus/RS-485
• HART/Bell 202
• Service port
Field Communicator
• HART/Bell 202Complete configuration
Complete configuration
and commissioning
and commissioning
Complete user information. See Appendix B.
Basic user information.
See Appendix C.
Basic user information.
See Appendix D.
Not applicable
User manual
• Installed with soft-
ware
• On Micro Motion
user documentation
CD
• On Micro Motion
web site
(www.micromo‐
tion.com)
User manual on
Micro Motion web site
(www.micromo‐
tion.com )
4Micro Motion® Compact Density Meters (CDM)
Tip
You may be able to use other communications tools from Emerson Process Management, such as
AMS Suite: Intelligent Device Manager, or the Smart Wireless THUM™ Adapter. Use of AMS or the
Smart Wireless THUM Adapter is not discussed in this manual. For more information on the Smart
Wireless THUM Adapter, refer to the documentation available at www.micromotion.com.
1.4Additional documentation and resources
Micro Motion provides additional documentation to support the installation and operation
of the device.
Additional documentation and resourcesTable 1-3:
TopicDocument
Device installationMicro Motion Compact Density Meters (CDM): Installation Manual
Product data sheetMicro Motion Compact Density Meters: Product Data Sheet
Before you begin
All documentation resources are available on the Micro Motion web site at
www.micromotion.com or on the Micro Motion user documentation DVD.
Configuration and Use Manual 5
Before you begin
6Micro Motion® Compact Density Meters (CDM)
2Quick start
Topics covered in this chapter:
•Power up the transmitter
•Check meter status
•Make a startup connection to the transmitter
•Zero the meter
2.1Power up the transmitter
The transmitter must be powered up for all configuration and commissioning tasks, or for
process measurement.
1.Ensure that all transmitter and sensor covers and seals are closed.
Quick start
WARNING!
To prevent ignition of flammable or combustible atmospheres, ensure that all covers
and seals are tightly closed. For hazardous area installations, applying power while
housing covers are removed or loose can cause an explosion.
2.Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. During this period,
Alert 009 is active. The diagnostic routines should complete in approximately
30 seconds.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics
can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the initial
startup, or if power has been off long enough to allow components to reach ambient
temperature, allow the electronics to warm up for approximately 10 minutes before
relying on process measurements. During this warm-up period, you may observe minor
measurement instability or inaccuracy.
2.2Check meter status
Check the meter for any error conditions that require user action or that affect
measurement accuracy.
1.Wait approximately 10 seconds for the power-up sequence to complete.
Immediately after power-up, the transmitter runs through diagnostic routines and
checks for error conditions. During the power-up sequence, Alert A009 is active.
This alert should clear automatically when the power-up sequence is complete.
Configuration and Use Manual 7
Quick start
2.Check the status LED on the transmitter.
Transmitter status reported by status LEDTable 2-1:
LED stateDescriptionRecommendation
GreenNo alerts are active.Continue with configuration or process meas-
urement.
YellowOne or more low-severity alerts are active.A low-severity alert condition does not affect
measurement accuracy or output behavior.
You can continue with configuration or process measurement. If you choose, you can identify and resolve the alert condition.
Flashing yellowCalibration in progress, or Known Density Veri-
fication in progress.
RedOne or more high-severity alerts are active.A high-severity alert condition affects meas-
The measurement can fluctuate during the
calibration process or change as a result of the
calibration process. The alert will clear when
the calibration is complete. Check the calibration results before continuing.
urement accuracy and output behavior. Resolve the alert condition before continuing.
•View and acknowledge status alerts (Section 8.3)
•Status alerts, causes, and recommendations (Section 10.6)
2.3Make a startup connection to the transmitter
For all configuration tools except the display, you must have an active connection to the
transmitter to configure the transmitter.
Identify the connection type to use, and follow the instructions for that connection type in
the appropriate appendix. Use the default communications parameters shown in the
appendix.
Communications toolConnection type to useInstructions
ProLink IIIModbus/RS-485
HART/Bell 202
Field CommunicatorHART/Bell 202Appendix D
Postrequisites
(Optional) Change the communications parameters to site-specific values.
Appendix C
•To change the communications parameters using ProLink III, choose Device Tools >
Configuration > Communications.
8Micro Motion® Compact Density Meters (CDM)
•To change the communications parameters using the Field Communicator, choose
Configure > Manual Setup > HART > Communications.
Important
If you are changing communications parameters for the connection type that you are using, you will
lose the connection when you write the parameters to the transmitter. Reconnect using the new
parameters.
2.4Zero the meter
Zeroing the meter establishes a baseline for the velocity indicator by analyzing the sensor's
output when there is no flow through the sensor tubes.
Note
Do not zero the meter if a high-severity alert is active. Correct the problem, then zero the meter. You
may zero the meter if a low-severity alert is active.
In most cases, the default value (0) is adequate for flow indication. Do not zero the meter unless the
velocity switch is being triggered incorrectly and you need to apply an offset to the velocity
measurement.
Quick start
•Zero the meter using the display (Section 2.4.1)
•Zero the meter using ProLink III (Section 2.4.2)
•Zero the meter using the Field Communicator (Section 2.4.3)
2.4.1Zero the meter using the display
Restriction
You cannot change the Zero Time setting from the display. The current setting of Zero Time will be
applied to the zero procedure. The default value is 20 seconds. If you need to change Zero Time, you
must make a connection to the transmitter from a communications tool such as ProLink III.
Procedure
1.Prepare the meter:
a. Stop flow through the sensor by shutting the downstream valve, and then the
upstream valve if available.
b. Verify that the sensor is blocked in, that flow has stopped, and that the sensor is
completely full of process fluid.
c. Verify that the process fluid is not flashing or condensing, and that it does not
contain particles that can settle out.
d. Remove or reduce sources of electromechanical noise if appropriate.
2.Start the zero process.
a. Navigate to the Zero menu: OFFLINE MAINT > OFFLINE CALIB > VEL ZERO.
Configuration and Use Manual 9
Quick start
b. Scroll to CAL VEL/ZERO and activate Select, then select CAL/YES?.
The status LED changes to flashing yellow while the zero is in progress.
3.Read the zero result on the display.
The display reports CAL PASS if the zero was successful, or CAL FAIL if it was not.
Postrequisites
Restore normal flow through the sensor by opening the valves.
Need help? If the zero fails:
•Ensure that there is no flow through the sensor, then retry.
•Remove or reduce sources of electromechanical noise, then retry.
•Set Zero Time to a lower value, then retry.
•If the zero continues to fail, contact Micro Motion.
•If you want to return the meter to operation using a previous zero value, choose OFFLINE
MAINT > CAL > RESTORE VEL/ZERO.
2.4.2Zero the meter using ProLink III
1.Prepare the meter:
a. Stop flow through the sensor by shutting the downstream valve, and then the
upstream valve if available.
b. Verify that the sensor is blocked in, that flow has stopped, and that the sensor is
completely full of process fluid.
c. Verify that the process fluid is not flashing or condensing, and that it does not
contain particles that can settle out.
d. Remove or reduce sources of electromechanical noise if appropriate.
2.Choose Device Tools > Calibration > Zero Velocity.
3.Modify Zero Time, if desired.
Zero Time controls the amount of time the transmitter takes to determine its zeroflow reference point. The default Zero Time is 20 seconds. For most applications, the
default Zero Time is appropriate.
4.Click Calibrate Zero.
The Calibration in Progress message is displayed. When the calibration is
complete:
• If the zero procedure was successful, a Calibration Success message and a
new zero value are displayed.
• If the zero procedure failed, a Calibration Failed message is displayed.
Postrequisites
Restore normal flow through the sensor by opening the valves.
10Micro Motion® Compact Density Meters (CDM)
Need help? If the zero fails:
•Remove or reduce sources of electromechanical noise, then retry.
•If the zero continues to fail, contact Micro Motion.
•If you want to return the meter to operation using a previous zero value, choose Device Tools >
Calibration > Zero Velocity > Restore Prior Zero. Restore Prior Zero is available only while the Zero
Velocity window is open. If you close the Zero Velocity window, you will no longer be able to
restore the prior zero.
2.4.3Zero the meter using the Field Communicator
1.Prepare the meter:
a. Stop flow through the sensor by shutting the downstream valve, and then the
upstream valve if available.
b. Verify that the sensor is blocked in, that flow has stopped, and that the sensor is
completely full of process fluid.
c. Verify that the process fluid is not flashing or condensing, and that it does not
contain particles that can settle out.
d. Remove or reduce sources of electromechanical noise if appropriate.
2.Choose Service Tools > Maintenance > Calibration > Zero Calibration.
3.Modify Zero Time, if desired.
Quick start
Zero Time controls the amount of time the transmitter takes to determine its zeroflow reference point. The default Zero Time is 20 seconds. For most applications, the
default Zero Time is appropriate.
4.Press Perform Auto Zero to start the zero, and wait while the zero calibration is
performed.
5.When the zero is complete, data from the zero calibration is displayed.
• Press OK to accept the data and store the values.
• Press ABORT to discard the data and return to the previous zero values.
Postrequisites
Restore normal flow through the sensor by opening the valves.
Need help? If the zero fails:
•Ensure that there is no flow through the sensor, then retry.
•Remove or reduce sources of electromechanical noise, then retry.
•Set Zero Time to a lower value, then retry.
•If the zero continues to fail, contact Micro Motion.
Configuration and Use Manual 11
Quick start
12Micro Motion® Compact Density Meters (CDM)
Configuration and commissioning
Part II
Configuration and commissioning
Chapters covered in this part:
•Introduction to configuration and commissioning
•Configure process measurement
•Configure device options and preferences
•Integrate the meter with the control system
•Complete the configuration
Configuration and Use Manual 13
Configuration and commissioning
14Micro Motion® Compact Density Meters (CDM)
Introduction to configuration and commissioning
3Introduction to configuration and
commissioning
Topics covered in this chapter:
•Default values
•Enable access to the off‐line menu of the display
•Disable HART security
•Set the HART lock
•Restore the factory configuration
3.1Default values
Default values for your meter are configured at the factory.
Important
Default values are based on your purchase order options. Therefore, the default values described in
the following tables may not be the factory default values configured for your system. For absolute
accuracy, refer to the configuration sheet that was shipped with your meter.
3.1.1CDM default values
CDM default mA scaling valuesTable 3-1:
VariableDefault 4 mADefault 20 mA
Line density0.500 g/cm31.500 g/cm3
Line temperature-50°C
Tube-case temperature differential
Drive gain0.000 %100.000 %
External temperature-50.000°C
External pressure0.000 PSIg1450.377 PSIg
Case temperature-50°C200°C
Sensor time period5000 us
Velocity-10 m/s10 m/s
-58°F
0°C
32°F
-58.00000°F
0 us
200.000°C
392°F
10°C
50°F
200.000°C
392.0000°F
10000 us
5000 us
Configuration and Use Manual 15
Introduction to configuration and commissioning
CDM default mA scaling values (continued)Table 3-1:
VariableDefault 4 mADefault 20 mA
User-defined calculation output
Volume flow rate-0.2 l/s0.2 l/s
API Referral option enabled
Referred density (API)500 kg/m31500 kg/m3c
Concentration Measurement option enabled
Concentration0 %100 %
Referred density (concentration)
Specific gravity0.5 SGU1.5 SGU
CDM default variablesTable 3-2:
Default variableOutput option AOutput options B and C
Field Communicator Configure > Manual Setup > Display > Display Menus > Offline Menu
Overview
By default, access to the off-line menu of the display is enabled. If it is disabled, you must
enable it if you want to use the display to configure the transmitter.
Restriction
You cannot use the display to enable access to the off-line menu. You must make a connection from
another tool.
16Micro Motion® Compact Density Meters (CDM)
3.3Disable HART security
A
If you plan to use HART protocol to configure the device, HART security must be disabled.
HART security is disabled by default, so you may not need to do this.
Prerequisites
•Strap wrench
•3 mm hex key
Procedure
1.Power down the meter.
2.Using the strap wrench, loosen the grub screws and remove the transmitter end-
cap.
Transmitter with end-cap removedFigure 3-1:
Introduction to configuration and commissioning
A. Transmitter end‐cap
3.Using the hex key, remove the safety spacer.
Configuration and Use Manual 17
A
B
A
B
Introduction to configuration and commissioning
Transmitter with end-cap and safety spacer removedFigure 3-2:
A. Transmitter end‐cap
B. Safety spacer
4.Move the HART security switch to the OFF position (up).
The HART security switch is the switch on the left.
HART security switchFigure 3-3:
A. HART security switch
B. Unused
18Micro Motion® Compact Density Meters (CDM)
5.Replace the safety spacer and end-cap.
6.Power up the meter.
3.4Set the HART lock
If you plan to use a HART connection to configure the device, you can lock out all other
HART masters. If you do this, other HART masters will be able to read data from the device
but will not be able to write data to the device.
Restrictions
•This feature is available only when you are using the Field Communicator or AMS.
•This feature is available only with a HART 7 host.
2.If you are locking the meter, set Lock Option as desired.
Introduction to configuration and commissioning
OptionDescription
Permanent Only the current HART master can make changes to the device. The device will
remain locked until manually unlocked by a HART master. The HART master can
also change Lock Option to Temporary.
Temporary Only the current HART master can make changes to the device. The device will
remain locked until manually unlocked by a HART master, or a power-cycle or
device reset is performed. The HART master can also change Lock Option to Perma-
nent.
Lock AllNo HART masters are allowed to make changes to the configuration. Before
changing Lock Option to Permanent or Temporary, the device must be unlocked. Any
HART master can be used to unlock the device.
Postrequisites
To avoid future confusion or difficulties, ensure that the device is unlocked after you have
completed your tasks.
3.5Restore the factory configuration
DisplayNot available
ProLink IIIDevice Tools > Configuration Transfer > Restore Factory Configuration
Field Communicator Service Tools > Maintenance > Reset/Restore > Restore Factory Configuration
Configuration and Use Manual 19
Introduction to configuration and commissioning
Overview
Restoring the factory configuration returns the transmitter to a known operational
configuration. This may be useful if you experience problems during configuration.
Tip
Restoring the factory configuration is not a common action. You may want to contact Micro Motion
to see if there is a preferred method to resolve any issues.
20Micro Motion® Compact Density Meters (CDM)
Configure process measurement
4Configure process measurement
Topics covered in this chapter:
•Verify the calibration factors
•Configure line density measurement
•Configure temperature measurement
•Configure the pressure input
•Set up the API referral application
•Set up concentration measurement
•Set up flow monitoring
4.1Verify the calibration factors
DisplayNot available
ProLink IIIDevice Tools > Calibration Data
Field Communicator Configure > Manual Setup > Calibration Factors
Overview
The calibration factors are used to adjust measurement for the unique traits of the sensor.
Your device was calibrated at the factory. However, you should verify that the calibration
factors that are configured in your device match the factory values.
Prerequisites
You will need the factory values for the calibration factors. These are provided in two
locations:
•The calibration certificate shipped with your meter
•The label inside the transmitter's end-cap
Important
If the transmitter is not the original component, do not use the values from the transmitter label.
Procedure
1.View the calibration factors that are stored in the device.
2.Compare them to the factory values.
• If the values match, no action is required.
• If the values do not match, contact Micro Motion customer service.
Configuration and Use Manual 21
Configure process measurement
Related information
Sample calibration certificates
4.1.1Calibration factors
The original calibration factors are obtained from factory calibration, and are unique to
each device. They are used to adjust measurements for the specific physical properties of
the device.
Contents of the calibration certificate
The calibration certificate contains several sets of factors:
Density calibration
coefficients
Temperature
compensation coefficients
Pressure compensation
coefficients
Flow compensation
coefficient
The calibration certificate also provides the results of the Known Density Verification
procedure that was performed at the factory.
For each calibration performed at the factory, the calibration certificate contains the data
used to calculate the calibration coefficients.
CDM format and legacy format (A factors and K factors)
The calibration factors are provided on three calibration certificates:
•The first certificate provides the calibration factors in the CDM format, An, in SI units.
These are obtained from factory calibration of your device.
•The second certificate provides the calibration factors in the legacy format, Kn, in SI
units. These factors represent the current calibration factors converted to the
format used by the 7835 and 7845 meters.
•The third certificate provides the calibration factors in the legacy format, Kn, in
imperial units. These factors represent the current calibration factors converted to
the format used by the 7835 and 7845 meters, and then converted to imperial units.
Define the relationship between density and the response
of your sensor
Adjust density measurement for the effect of temperature
on sensor response
Adjust density measurement for the effect of pressure on
sensor response
Adjusts density measurement for the effect of flow on
sensor response
If you have existing programs that use the K factors, update your programs with the new K
values in the appropriate units. In all other situations, use the A-format calibration factors.
Related information
Sample calibration certificates
22Micro Motion® Compact Density Meters (CDM)
Configure process measurement
4.2Configure line density measurement
The density measurement parameters control how density is measured and reported.
•Configure Density Measurement Unit (Section 4.2.1)
DisplayOFF-LINE MAINT > OFF-LINE CONFG > UNITS > DENS
ProLink IIIDevice Tools > Configuration > Process Measurement > Line Density > Density Unit
Field Communicator Configure > Manual Setup > Measurements > Density > Density Unit
Overview
Density Measurement Unit controls the measurement units that will be used in density
calculations and reporting.
Restriction
If the API referral application is enabled, you cannot change the density measurement unit here. The
density measurement unit is controlled by the API table selection.
Procedure
Set Density Measurement Unit to the option you want to use.
The default setting for Density Measurement Unit is g/cm3 (grams per cubic centimeter).
Related information
Set up the API referral application
Options for Density Measurement Unit
The transmitter provides a standard set of measurement units for Density Measurement Unit.
Different communications tools may use different labels.
Options for Density Measurement UnitTable 4-1:
Label
Unit description
Specific gravitySGUSGUSGU
Grams per cubic centimeterG/CM3g/cm3g/Cucm
Grams per literG/Lg/lg/L
Configuration and Use Manual 23
Display (standard)ProLink IIIField Communicator
Configure process measurement
Options for Density Measurement Unit (continued)Table 4-1:
Label
Unit description
Grams per milliliterG/mLg/mlg/mL
Kilograms per literKG/Lkg/lkg/L
Kilograms per cubic meterKG/M3kg/m3kg/Cum
Pounds per U.S. gallonLB/GALlbs/Usgallb/gal
Pounds per cubic footLB/CUFlbs/ft3lb/Cuft
Pounds per cubic inchLB/CUIlbs/in3lb/CuIn
Short ton per cubic yardST/CUYsT/yd3STon/Cuyd
Degrees APID APIdegAPIdegAPI
Special unitSPECLspecialSpcl
Display (standard)ProLink IIIField Communicator
Define a special measurement unit for density
DisplayNot available
ProLink IIIDevice Tools > Configuration > Process Measurement > Line Density > Special Units
Field Communicator Configure > Manual Setup > Measurements > Special Units
Overview
A special measurement unit is a user-defined unit of measure that allows you to report
process data in a unit that is not available in the transmitter. A special measurement unit is
calculated from an existing measurement unit using a conversion factor.
Procedure
1.Specify Density Special Unit Base.
Density Special Unit Base is the existing density unit that the special unit will be based
on.
2.Calculate Density Special Unit Conversion Factor as follows:
a. x base units = y special units
b. Density Special Unit Conversion Factor = x÷y
3.Enter Density Special Unit Conversion Factor.
The original density value is divided by this conversion factor.
4.Set User-Defined Label to the name you want to use for the density unit.
The special measurement unit is stored in the transmitter. You can configure the
transmitter to use the special measurement unit at any time.
24Micro Motion® Compact Density Meters (CDM)
Example: Defining a special measurement unit for density
You want to measure density in ounces per cubic inch.
1.Set Density Special Unit Base to g/cm3.
2.Calculate Density Special Unit Conversion Factor:
a. 1 g/cm3 = 0.578 oz/in3
b. 1÷0.578 = 1.73
3.Set Density Special Unit Conversion Factor to 1.73.
4.Set User-Defined Label to oz/in3.
4.2.2Configure Density Damping
DisplayNot available
ProLink IIIDevice Tools > Configuration > Process Measurement > Line Density > Density Damping
Field Communicator Configure > Manual Setup > Measurements > Density > Density Damping
Configure process measurement
Overview
Density Damping controls the amount of damping that will be applied to the line density
value.
Damping is used to smooth out small, rapid fluctuations in process measurement. DampingValue specifies the time period (in seconds) over which the transmitter will spread changes
in the process variable. At the end of the interval, the internal value will reflect 63% of the
change in the actual measured value.
Tip
Density damping affects all process variables that are calculated from line density.
Procedure
Set Density Damping to the value you want to use.
The default value is 1.6 seconds. The range is 0 to 60 seconds.
Interaction between Density Damping and Added Damping
When the mA output is configured to report density, both Density Damping and Added
Damping are applied to the reported density value.
Density Damping controls the rate of change in the value of the process variable in
transmitter memory. Added Damping controls the rate of change reported via the mA
output.
Configuration and Use Manual 25
Configure process measurement
If mA Output Process Variable is set to Density, and both Density Damping and Added Damping are
set to non-zero values, density damping is applied first, and the added damping
calculation is applied to the result of the first calculation. This value is reported over the
mA output.
Related information
Interaction between mA Output Damping and process variable damping
4.2.3Configure Density Cutoff
DisplayNot available
ProLink IIIDevice Tools > Configuration > Process Measurement > Line Density > Density Cutoff Low
Field Communicator Configure > Manual Setup > Measurements > Density > Density Cutoff
Overview
Density Cutoff Low specifies the lowest density value that will be reported as measured. All
density values below this cutoff will be reported as 0.
Procedure
Set Density Cutoff Low to the value you want to use.
The default value is 0.2 g/cm³. The range is 0.0 g/cm³ to 0.5 g/cm³.
4.2.4Configure two-phase flow parameters
DisplayNot available
ProLink IIIDevice Tools > Configuration > Process Measurement > Line Density
Field Communicator Configure > Manual Setup > Measurements > Density
Overview
The two-phase flow parameters control how the transmitter detects and reports twophase flow (gas in a liquid process or liquid in a gas process).
Note
Two-phase flow is sometimes referred to as slug flow.
Procedure
1.Set Two-Phase Flow Low Limit to the lowest density value that is considered normal in
your process.
Values below this will cause the transmitter to post Alert A105 (Two-Phase Flow).
26Micro Motion® Compact Density Meters (CDM)
Configure process measurement
Tip
Gas entrainment can cause your process density to drop temporarily. To reduce the
occurrence of two-phase flow alerts that are not significant to your process, set Two-Phase FlowLow Limit slightly below your expected lowest process density.
You must enter Two-Phase Flow Low Limit in g/cm³, even if you configured another unit
for density measurement.
The default value for Two-Phase Flow Low Limit is 0.0 g/cm³. The range is 0.0 to
3.0 g/cm³.
2.Set Two-Phase Flow High Limit to the highest density value that is considered normal in
your process.
Values above this will cause the transmitter to post Alert A105 (Two-Phase Flow).
Tip
To reduce the occurrence of two-phase flow alerts that are not significant to your process, set
Two-Phase Flow High Limit slightly above your expected highest process density.
You must enter Two-Phase Flow High Limit in g/cm³, even if you configured another
unit for density measurement.
The default value for Two-Phase Flow High Limit is 3.0 g/cm³. The range is 0.0 to
3.0 g/cm³.
3.Set Two-Phase Flow Timeout to the number of seconds that the transmitter will wait for
a two-phase flow condition to clear before posting the alert.
The default value for Two-Phase Flow Timeout is 0.0 seconds, meaning that the alert
will be posted immediately. The range is 0.0 to 60.0 seconds.
Detecting and reporting two-phase flow
Two-phase flow (gas in a liquid process or liquid in a gas process) can cause a variety of
process control issues. By configuring the two-phase flow parameters appropriately for
your application, you can detect process conditions that require correction.
Tip
To decrease the occurrence of two-phase flow alerts, lower Two-Phase Flow Low Limit or raise Two-Phase
Flow High Limit.
A two-phase flow condition occurs whenever the measured density goes below Two-Phase
Flow Low Limit or above Two-Phase Flow High Limit. If this occurs:
•A two-phase flow alert is posted to the active alert log.
•Line density is held at its last pre‐alert value for the number of seconds configured in
Two-Phase Flow Timeout.
If the two-phase flow condition clears before Two-Phase Flow Timeout expires:
Configuration and Use Manual 27
Configure process measurement
•Line density reverts to actual process density.
•The two-phase flow alert is deactivated, but remains in the active alert log until it is
acknowledged.
If the two-phase flow condition does not clear before Two-Phase Flow Timeout expires, line
density reverts to actual process density, but the two-phase flow alert remains active.
If Two-Phase Flow Timeout is set to 0.0 seconds, two-phase flow will cause a two-phase flow
alert but will have no effect on how the meter measures or reports line density.
4.3Configure temperature measurement
The temperature measurement parameters control how temperature data from the
sensor is reported.
•Configure Temperature Measurement Unit (Section 4.3.1)
•Configure Temperature Damping (Section 4.3.2)
•Configure Temperature Input (Section 4.3.3)
4.3.1Configure Temperature Measurement Unit
DisplayOFF-LINE MAINT > OFF-LINE CONFG > UNITS > TEMP
ProLink IIIDevice Tools > Configuration > Process Measurement > Line Temperature > Temperature Unit
Field Communicator Configure > Manual Setup > Measurements > Temperature > Temperature Unit
Overview
Temperature Measurement Unit specifies the unit that will be used for temperature
measurement.
Restriction
If the API referral application is enabled, the API table selection automatically sets the temperature
measurement unit. Configure the API referral application first, then change the temperature
measurement unit if desired.
Procedure
Set Temperature Measurement Unit to the option you want to use.
The default setting is Degrees Celsius.
Related information
Set up the API referral application
28Micro Motion® Compact Density Meters (CDM)
Options for Temperature Measurement Unit
The transmitter provides a standard set of units for Temperature Measurement Unit. Different
communications tools may use different labels for the units.
Options for Temperature Measurement UnitTable 4-2:
Unit description
Degrees Celsius°C°CdegC
Degrees Fahrenheit°F°FdegF
Degrees Rankine°R°RdegR
Kelvin°K°KKelvin
DisplayProLink III
4.3.2Configure Temperature Damping
Configure process measurement
Label
Field Communicator
DisplayNot available
ProLink IIIDevice Tools > Configuration > Process Measurement > Line Temperature > Temperature Damping
Field Communicator Configure > Manual Setup > Measurements > Temperature > Temp Damping
Overview
Temperature Damping controls the amount of damping that will be applied to the line
temperature value, when the on-board temperature data is used (RTD).
Damping is used to smooth out small, rapid fluctuations in process measurement. DampingValue specifies the time period (in seconds) over which the transmitter will spread changes
in the process variable. At the end of the interval, the internal value will reflect 63% of the
change in the actual measured value.
Tip
Temperature Damping affects all process variables, compensations, and corrections that use
temperature data from the sensor.
Procedure
Enter the value you want to use for Temperature Damping.
• Default: 4.8 seconds
Tips
• A high damping value makes the process variable appear smoother because the reported value
changes slowly.
Configuration and Use Manual 29
Configure process measurement
• A low damping value makes the process variable appear more erratic because the reported value
changes more quickly.
• Whenever the damping value is non-zero, the reported measurement will lag the actual
measurement because the reported value is being averaged over time.
• In general, lower damping values are preferable because there is less chance of data loss, and less
lag time between the actual measurement and the reported value.
The value you enter is automatically rounded down to the nearest valid value.
4.3.3Configure Temperature Input
Temperature data from the on-board temperature sensor (RTD) is always available.
Optionally, you can set up an external temperature device and use external temperature
data.
Tip
Use an external device only if it is more accurate than the internal RTD.
Important
Line temperature data is used in several different measurements and calculations. It is possible to
use the internal RTD temperature in some areas and an external temperature in others. The
transmitter stores the internal RTD temperature and the external temperature separately. However,
the transmitter stores only one alternate temperature value, which may be either an external
temperature or the configured fixed value. Accordingly, if you set up polling for temperature in one
area, and digital communications in another, and configure a fixed temperature value in a third, the
fixed value will be overwritten by polling and digital communications, and polling and digital
communications will overwrite each other.
Prerequisites
If you plan to poll an external device, the primary mA output (Channel A) must be wired to
support HART communications.
•Configure Temperature Input using ProLink III
•Configure Temperature Input using the Field Communicator
Configure Temperature Input using ProLink III
ProLink IIIDevice Tools > Configuration > Process Measurement > Line Temperature > Line Temperature Source
Procedure
Choose the method to be used to supply temperature data, and perform the required
setup.
30Micro Motion® Compact Density Meters (CDM)
OptionDescriptionSetup
Internal RTD temperature data
PollingThe meter polls an external de-
Digital communications
Temperature data from the onboard temperature sensor
(RTD) is used.
vice for temperature data. This
data will be available in addition to the internal RTD temperature data.
A host writes temperature data
to the meter at appropriate intervals. This data will be available in addition to the internal
RTD temperature data.
a. Set Line Temperature Source to Internal RTD.
b. Click Apply.
a. Set Line Temperature Source to Poll for External Value.
b. Set Polling Slot to an available slot.
c. Set Polling Control to Poll as Primary or Poll as Secondary.
OptionDescription
Poll as PrimaryNo other HART masters will be on the
Poll as SecondaryOther HART masters will be on the net-
d. Set External Device Tag to the HART tag of the temperature
device.
e. Click Apply.
a. Set Line Temperature Source to Fixed Value or Digital Communica-
tions.
b. Click Apply.
c. Perform the necessary host programming and communica-
tions setup to write temperature data to the meter at appro-
priate intervals.
Configure process measurement
network. The Field Communicator is not
a HART master.
work. The Field Communicator is not a
HART master.
Postrequisites
If you are using external temperature data, verify the external temperature value displayed
in the Inputs group on the ProLink III main window.
Need help? If the value is not correct:
•For polling:
-Verify the wiring between the meter and the external device.
-Verify the HART tag of the external device.
•For digital communications:
-Verify that the host has access to the required data.
-Verify that the host is writing to the correct register in memory, using the correct data
type.
Configure Temperature Input using the Field Communicator
Choose the method to be used to supply temperature data, and perform the required
setup.
Configuration and Use Manual 31
Configure process measurement
MethodDescriptionSetup
Internal RTD temperature data
PollingThe meter polls an external de-
Temperature data from the onboard temperature sensor
(RTD) is used.
vice for temperature data. This
data will be available in addition to the internal RTD temperature data.
If Line Pressure Source is set to Fixed, you cannot configure Pressure Type. You must enter the
pressure value in the required form. To set Pressure Type, you may need to change the setting
of Line Pressure Source.
The meter requires gauge pressure. If you select Absolute, the device will convert the
input pressure value to the equivalent gauge pressure.
3.Set Pressure Unit to the unit used by the external pressure device.
Restriction
If the API referral application is enabled, the API table selection automatically sets the
pressure measurement unit. Configure the API referral application first, then change the
pressure measurement unit if necessary.
Configuration and Use Manual 33
Configure process measurement
4.Choose the method used to supply pressure data and perform the required setup.
OptionDescriptionSetup
PollingThe meter polls an external de-
vice for pressure data.
Digital communications
A host writes pressure data to
the meter at appropriate intervals.
a. Set Pressure Source to Poll for External Value.
b. Set Polling Slot to an available slot.
c. Set Polling Control to Poll as Primary or Poll as Secondary.
OptionDescription
Poll as PrimaryNo other HART masters will be on the
Poll as SecondaryOther HART masters will be on the net-
d. Set External Device Tag to the HART tag of the temperature
a. Set Pressure Source to Fixed Value or Digital Communications.
b. Perform the necessary host programming and communica-
network. The Field Communicator is not
a HART master.
work. The Field Communicator is not a
HART master.
device.
tions setup to write pressure data to the meter at appropriate intervals.
Postrequisites
The current pressure value is displayed in the External Pressure field. Verify that the value is
correct.
Need help? If the value is not correct:
•Ensure that the external device and the meter are using the same measurement unit.
•For polling:
-Verify the wiring between the meter and the external device.
-Verify the HART tag of the external device.
•For digital communications:
-Verify that the host has access to the required data.
-Verify that the host is writing to the correct register in memory, using the correct data
type.
•If necessary, apply an offset.
Note
Do not use the offset in conjunction with the fixed pressure value. Enter the adjusted value.
Related information
Set up the API referral application
34Micro Motion® Compact Density Meters (CDM)
4.4.2Configure the pressure input using the
Field Communicator
If Line Pressure Source is set to Fixed, you cannot configure Pressure Type. You must enter the
pressure value in the required form. To set Pressure Type, you may need to change the setting
of Line Pressure Source.
Configure process measurement
The meter requires gauge pressure. If you select Absolute, the device will convert the
input pressure value to the equivalent gauge pressure.
4.Set Pressure Unit to the unit used by the external pressure device.
Restriction
If the API referral application is enabled, the API table selection automatically sets the
pressure measurement unit. Configure the API referral application first, then change the
pressure measurement unit if necessary.
c. Set Polling Control to Poll as Primary or Poll as Secondary.
OptionDescription
Poll as PrimaryNo other HART masters will be on the network. The
Field Communicator is not a HART master.
Poll as SecondaryOther HART masters will be on the network. The
Field Communicator is not a HART master.
d. Set External Device Tag to the HART tag of the external pressure device.
e. Set Polled Variable to Pressure.
Postrequisites
Choose Service Tools > Variables > External Variables and verify the value for External Pressure.
Configuration and Use Manual 35
Configure process measurement
Need help? If the value is not correct:
•Ensure that the external device and the meter are using the same measurement unit.
•For polling:
-Verify the wiring between the meter and the external device.
-Verify the HART tag of the external device.
•For digital communications:
-Verify that the host has access to the required data.
-Verify that the host is writing to the correct register in memory, using the correct data
type.
•If necessary, apply an offset.
Related information
Set up the API referral application
4.4.3Options for Pressure Measurement Unit
The transmitter provides a standard set of measurement units for Pressure Measurement Unit.
Different communications tools may use different labels for the units. In most
applications, Pressure Measurement Unit should be set to match the pressure measurement
unit used by the remote device.
Options for Pressure Measurement UnitTable 4-3:
Label
Unit description
Feet water @ 68 °FFTH2OFt Water @ 68°FftH2O
Inches water @ 4 °CINW4CIn Water @ 4°CinH2O @4DegC
Inches water @ 60 °FINW60In Water @ 60°FinH2O @60DegF
Inches water @ 68 °FINH2OIn Water @ 68°FinH2O
Millimeters water @ 4 °CmmW4Cmm Water @ 4°CmmH2O @4DegC
Millimeters water @ 68 °FmmH2Omm Water @ 68°FmmH2O
Kilograms per square centimeterKG/SCMkg/cm2kg/Sqcm
PascalsPApascalsPa
KilopascalsKPAKilopascalskPa
MegapascalsMPAMegapascalsMPa
DisplayProLink IIIField Communicator
36Micro Motion® Compact Density Meters (CDM)
Configure process measurement
Options for Pressure Measurement Unit (continued)Table 4-3:
Label
Unit description
Torr @ 0 °CTORRTorr @ 0°Ctorr
AtmospheresATMatmsatms
DisplayProLink IIIField Communicator
4.5Set up the API referral application
The API referral application corrects line density to reference temperature and reference
pressure according to American Petroleum Institute (API) standards. The resulting process
variable is referred density.
•Set up the API referral application using ProLink III (Section 4.5.1)
•Set up the API referral application using the Field Communicator (Section 4.5.2)
4.5.1Set up the API referral application using ProLink III
This section guides you through the tasks required to set up and implement the API
referral application.
1.Enable the API referral application using ProLink III
2.Configure API referral using ProLink III
3.Set up temperature and pressure data for API referral using ProLink III
Enable the API referral application using ProLink III
The API referral application must be enabled before you can perform any setup. If the API
referral application was enabled at the factory, you do not need to enable it now.
2.If the concentration measurement application is enabled, disable it and click Apply.
The concentration measurement application and the API referral application cannot
be enabled simultaneously.
3.Enable API Referral and click Apply.
Configure API referral using ProLink III
The API referral parameters specify the API table, measurement units, and reference values
to be used in referred density calculations.
Prerequisites
You will need API documentation for the API table that you select.
Configuration and Use Manual 37
Configure process measurement
Depending on your API table, you may need to know the thermal expansion coefficient
(TEC) for your process fluid.
You must know the reference temperature and reference pressure that you want to use.
Procedure
1.Choose Device Tools > Configuration > Process Measurement > API Referral.
2.Specify the API table to use.
Each API table is associated with a specific set of equations.
a. Set Process Fluid to the API table group that your process fluid belongs to.
API table groupProcess fluids
A tablesGeneralized crude and JP4
B tablesGeneralized products: Gasoline, jet fuel, aviation fuel, kerosene,
heating oils, fuel oils, diesel, gas oil
C tablesLiquids with a constant base density or known thermal expansion
coefficient (TEC). You will be required to enter the TEC for your
process fluid.
D tablesLubricating oils
E tablesNGL (Natural Gas Liquids) and LPG (Liquid Petroleum Gas)
Restriction
The API referral application is not appropriate for the following process fluids: propane
and propane mixes, butane and butane mixes, butadiene and butadiene mixes,
isopentane, LNG, ethylene, propylene, cyclohexane, aeromatics, asphalts, and road tars.
b. Set Referred Density Measurement Unit to the measurement units that you want to
use for referred density.
c. Click Apply.
These parameters uniquely identify the API table. The selected API table is displayed,
and the meter automatically changes the density unit, temperature unit, pressure
unit, reference temperature, and reference pressure to match the API table.
Restriction
Not all combinations are supported by the API referral application. See the list of API tables in
this manual.
3.Refer to the API documentation and confirm your table selection.
a. Verify that your process fluid falls within range for line density, line temperature,
and line pressure.
38Micro Motion® Compact Density Meters (CDM)
Configure process measurement
If your process fluid goes outside any of these limits, the meter will post a status
alert and will report line density instead of referred density until the process fluid
goes back within range.
b. Verify that the referred density range of the selected table is adequate for your
application.
4.If you chose a C table, enter Thermal Expansion Coefficient (TEC) for your process fluid.
5.Set Reference Temperature to the temperature to which density will be corrected in
referred density calculations. If you choose Other, select the temperature
measurement unit and enter the reference temperature.
6.Set Reference Pressure to the pressure to which density will be corrected in referred
density calculations.
API tables supported by the API referral application
The API tables listed here are supported by the API referral application.
API tables, process fluids, measurement units, and default reference valuesTable 4-4:
These tables are not appropriate for the following process fluids: propane and propane mixes,
butane and butane mixes, butadiene and butadiene mixes, isopentane, LNG, ethylene, propylene,
cyclohexane, aeromatics, asphalts, and road tars.
temperature
Default reference
pressure
Set up temperature and pressure data for API referral using
ProLink III
The API referral application uses temperature and, optionally, pressure data in its
calculations. You must decide how to provide this data, then perform the required
configuration and setup.
Tip
Fixed values for temperature or pressure are not recommended. Using a fixed temperature or
pressure value may produce inaccurate process data.
Important
Line temperature data is used in several different measurements and calculations. It is possible to
use the internal RTD temperature in some areas and an external temperature in others. The
transmitter stores the internal RTD temperature and the external temperature separately. However,
the transmitter stores only one alternate temperature value, which may be either an external
temperature or the configured fixed value. Accordingly, if you set up polling for temperature in one
area, and digital communications in another, and configure a fixed temperature value in a third, the
fixed value will be overwritten by polling and digital communications, and polling and digital
communications will overwrite each other.
Important
Line pressure data is used in several different measurements and calculations. The transmitter stores
only one pressure value, which may be either the external pressure or the configured fixed value.
Accordingly, if you choose a fixed pressure for some uses, and an external pressure for others, the
external pressure will overwrite the fixed value.
Prerequisites
•If you plan to poll an external device, the primary mA output (Channel A) must be
wired to support HART communications.
•The pressure measurement must be gauge pressure, not atmospheric pressure. If
your pressure input is absolute, you can set the pressure type to absolute and it will
be converted to gauge for the API calculations.
•The pressure device must use the pressure unit that is configured in the transmitter.
40Micro Motion® Compact Density Meters (CDM)
•If you are using an external temperature device, it must use the temperature unit
that is configured in the transmitter.
Procedure
1.Choose Device Tools > Configuration > Process Measurement > API Referral.
2.Choose the method to be used to supply temperature data, and perform the
required setup.
OptionDescriptionSetup
Internal RTD temperature data
PollingThe meter polls an external de-
Temperature data from the onboard temperature sensor
(RTD) is used.
vice for temperature data. This
data will be available in addition to the internal RTD temperature data.
a. Set Line Temperature Source to Internal RTD.
b. Click Apply.
a. Set Line Temperature Source to Poll for External Value.
b. Set Polling Slot to an available slot.
c. Set Polling Control to Poll as Primary or Poll as Secondary.
OptionDescription
Poll as PrimaryNo other HART masters will be on the
Poll as SecondaryOther HART masters will be on the net-
Configure process measurement
network. The Field Communicator is not
a HART master.
work. The Field Communicator is not a
HART master.
Digital communications
d. Set External Device Tag to the HART tag of the temperature
device.
e. Click Apply.
A host writes temperature data
to the meter at appropriate intervals. This data will be available in addition to the internal
RTD temperature data.
a. Set Line Temperature Source to Fixed Value or Digital Communica-
tions.
b. Click Apply.
c. Perform the necessary host programming and communica-
tions setup to write temperature data to the meter at appro-
priate intervals.
3.Choose the method used to supply pressure data and perform the required setup.
Configuration and Use Manual 41
Configure process measurement
OptionDescriptionSetup
PollingThe meter polls an external de-
vice for pressure data.
Digital communications
A host writes pressure data to
the meter at appropriate intervals.
a. Set Pressure Source to Poll for External Value.
b. Set Polling Slot to an available slot.
c. Set Polling Control to Poll as Primary or Poll as Secondary.
OptionDescription
Poll as PrimaryNo other HART masters will be on the
Poll as SecondaryOther HART masters will be on the net-
d. Set External Device Tag to the HART tag of the temperature
a. Set Pressure Source to Fixed Value or Digital Communications.
b. Perform the necessary host programming and communica-
network. The Field Communicator is not
a HART master.
work. The Field Communicator is not a
HART master.
device.
tions setup to write pressure data to the meter at appropri-
ate intervals.
Postrequisites
If you are using external temperature data, verify the external temperature value displayed
in the Inputs group on the ProLink III main window.
The current pressure value is displayed in the External Pressure field. Verify that the value is
correct.
Need help? If the value is not correct:
•Ensure that the external device and the meter are using the same measurement unit.
•For polling:
-Verify the wiring between the meter and the external device.
-Verify the HART tag of the external device.
•For digital communications:
-Verify that the host has access to the required data.
-Verify that the host is writing to the correct register in memory, using the correct data
type.
•If necessary, apply an offset.
4.5.2Set up the API referral application using the
Field Communicator
This section guides you through the tasks required to set up and implement the API
referral application.
42Micro Motion® Compact Density Meters (CDM)
Configure process measurement
1.Enable the API referral application using the Field Communicator
2.Configure API referral using the Field Communicator
3.Set up temperature and pressure data for API referral using the Field Communicator
Enable the API referral application using the
Field Communicator
The API referral application must be enabled before you can perform any setup. If the API
referral application was enabled at the factory, you do not need to enable it now.
1.Choose Overview > Device Information > Applications > Enable/Disable Applications.
2.If the concentration measurement application is enabled, disable it.
The concentration measurement application and the API referral application cannot
be enabled simultaneously.
3.Enable the API referral application.
Configure API referral using the Field Communicator
The API referral parameters specify the API table, measurement units, and reference values
to be used in referred density calculations.
Prerequisites
You will need API documentation for the API table that you select.
Depending on your API table, you may need to know the thermal expansion coefficient
(TEC) for your process fluid.
You must know the reference temperature and reference pressure that you want to use.
Procedure
1.Choose Configure > Manual Setup > Measurements > API Referral.
2.Choose API Referral Setup.
3.Specify the API table that you want to use for measurement.
Each API table is associated with a specific set of equations.
a. Set API Table Number to the number that matches the API table units that you
want to use for referred density.
Your choice also determines the measurement units to be used for temperature
and pressure, and the default values for reference temperature and reference
pressure.
Measurement
unit for referred
API Table Number
5°API°Fpsi (g)60 °F0 psi (g)
density
Temperature
measurement
unit
Pressure measurement unit
Default reference temperature
Default reference pressure
Configuration and Use Manual 43
Configure process measurement
API Table Number
(1)
6
Measurement
unit for referred
density
°API°Fpsi (g)60 °F0 psi (g)
Temperature
measurement
unit
Pressure measurement unit
Default reference temperature
Default reference pressure
23SGU°Fpsi (g)60 °F0 psi (g)
(1)
24
SGU°Fpsi (g)60 °F0 psi (g)
53kg/m³°CkPa (g)15 °C0 kPa (g)
(1)
54
(1) Used only with API Table Letter = C.
kg/m³°CkPa (g)15 °C0 kPa (g)
b. Set API Table Letter to the letter of the API table group that is appropriate for your
ENGL (Natural Gas Liquids) and LPG (Liquid Petroleum Gas)
Liquids with a constant base density or known thermal expansion
coefficient (TEC). You will be required to enter the TEC for your
process fluid.
(1) Used only with API Table Number = 6, 24, or 54.
Restriction
The API referral application is not appropriate for the following process fluids: propane
and propane mixes, butane and butane mixes, butadiene and butadiene mixes,
isopentane, LNG, ethylene, propylene, cyclohexane, aeromatics, asphalts, and road tars.
API Table Number and API Table Letter uniquely identify the API table. The selected API
table is displayed, and the meter automatically changes the density unit,
temperature unit, pressure unit, reference temperature, and reference pressure to
match the API table.
Restriction
Not all combinations are supported by the API referral application. See the list of API tables in
this manual.
4.If you chose a C table, enter Thermal Expansion Coefficient (TEC) for your process fluid.
5.Refer to the API documentation and confirm your table selection.
a. Verify that your process fluid falls within range for line density, line temperature,
and line pressure.
44Micro Motion® Compact Density Meters (CDM)
Configure process measurement
If your process fluid goes outside any of these limits, the meter will post a status
alert and will report line density instead of referred density until the process fluid
goes back within range.
b. Verify that the referred density range of the selected table is adequate for your
application.
6.If required, set Ref Temperature to the temperature to which density will be corrected
in referred density calculations.
The default reference temperature is determined by the selected API table.
a. Choose Service Tools > Maintenance > Modbus Data > Write Modbus Data.
b. Write the desired reference temperature to Registers 319–320, in the
measurement unit required by the selected API table. Use 32-bit IEEE floatingpoint format.
7.If required, set Ref Pressure (Gauge) to the pressure to which density will be corrected
in referred density calculations.
The default reference pressure is determined by the selected API table. API referral
requires gauge pressure.
a. Choose Service Tools > Maintenance > Modbus Data > Write Modbus Data.
b. Write the desired reference pressure to Registers 4601–4602, in the
measurement unit required by the selected API table. Use 32-bit IEEE floatingpoint format.
API tables supported by the API referral application
The API tables listed here are supported by the API referral application.
API tables, process fluids, measurement units, and default reference valuesTable 4-5:
These tables are not appropriate for the following process fluids: propane and propane mixes,
butane and butane mixes, butadiene and butadiene mixes, isopentane, LNG, ethylene, propylene,
cyclohexane, aeromatics, asphalts, and road tars.
6CUnit: °API60 °F0 psi (g)
24CUnit: SGU60 °F0 psi (g)
54CUnit: kg/m³15 °C0 kPa (g)
Range: −10 to +40 °API
23DUnit: SGU
Range: 0.8520 to 1.1640
SGU
53DUnit: kg/m³
Range: 825 to 1164 kg/m³
temperature
60 °F0 psi (g)
60 °F0 psi (g)
15 °C0 kPa (g)
Default reference
pressure
Set up temperature and pressure data for API referral using
the Field Communicator
The API referral application uses temperature and, optionally, pressure data in its
calculations. You must decide how to provide this data, then perform the required
configuration and setup.
Tip
Fixed values for temperature or pressure are not recommended. Using a fixed temperature or
pressure value may produce inaccurate process data.
Important
Line temperature data is used in several different measurements and calculations. It is possible to
use the internal RTD temperature in some areas and an external temperature in others. The
transmitter stores the internal RTD temperature and the external temperature separately. However,
the transmitter stores only one alternate temperature value, which may be either an external
temperature or the configured fixed value. Accordingly, if you set up polling for temperature in one
area, and digital communications in another, and configure a fixed temperature value in a third, the
fixed value will be overwritten by polling and digital communications, and polling and digital
communications will overwrite each other.
46Micro Motion® Compact Density Meters (CDM)
Configure process measurement
Important
Line pressure data is used in several different measurements and calculations. The transmitter stores
only one pressure value, which may be either the external pressure or the configured fixed value.
Accordingly, if you choose a fixed pressure for some uses, and an external pressure for others, the
external pressure will overwrite the fixed value.
Prerequisites
If you plan to poll an external device, the primary mA output (Channel A) must be wired to
support HART communications.
The pressure measurement must be gauge pressure, not atmospheric pressure. If your
pressure input is absolute, you can set the pressure type to absolute and it will be
converted to gauge for the API calculations.
The pressure device must use the pressure unit that is configured in the transmitter.
If you are using an external temperature device, it must use the temperature unit that is
configured in the transmitter.
Procedure
1.Choose the method to be used to supply temperature data, and perform the
required setup.
MethodDescriptionSetup
Internal temperature
Temperature data from the onboard temperature sensor
(RTD) will be used for all measurements and calculations. No
external temperature data will
be available.
> Pressure.
b. Set Pressure Input to Enable.
c. Perform the necessary host programming and communica-
tions setup to write pressure data to the transmitter at ap-
propriate intervals.
Configure process measurement
network. The Field Communicator is not
a HART master.
work. The Field Communicator is not a
HART master.
Postrequisites
Choose Service Tools > Variables > External Variables and verify the values for External
Temperature and External Pressure.
Need help? If the value is not correct:
•Ensure that the external device and the meter are using the same measurement unit.
•For polling:
-Verify the wiring between the meter and the external device.
-Verify the HART tag of the external device.
•For digital communications:
-Verify that the host has access to the required data.
-Verify that the host is writing to the correct register in memory, using the correct data
type.
•If necessary, apply an offset.
Configuration and Use Manual 49
Configure process measurement
4.6Set up concentration measurement
The concentration measurement application calculates concentration from line density
and line temperature.
Related information
Preparing to set up concentration measurement
Set up concentration measurement using ProLink III
Set up concentration measurement using the Field Communicator
4.6.1Preparing to set up concentration measurement
The procedure for setting up concentration measurement application depends on how
your device was ordered and how you want to use the application. Review this information
before you begin.
Requirements for concentration measurement
To use the concentration measurement application, the following conditions must be met:
•The concentration measurement application must be enabled.
•One or more concentration matrices must be stored in your transmitter.
Tip
In most cases, the concentration matrix that you ordered was loaded at the factory. If you
need to add concentration matrices and you are using ProLink III, you can load concentration
matrices from a file or you can build a custom matrix. If you are using the
Field Communicator, you can build a custom matrix but you cannot load a matrix from a file.
This manual does not discuss building a custom matrix. For information on building a custom
matrix, see Micro Motion Enhanced Density Application: Theory, Configuration, and Use.
•If your concentration matrices use Specific Gravity as the derived variable, the
reference temperature values must be set.
•Temperature Source must be configured and set up.
•One matrix must be selected as the active matrix (the matrix used for
measurement).
Optional tasks in setting up concentration measurement
The following tasks are optional:
•Modifying names and labels
•Configuring operational parameters
-Extrapolation alerts
-Calculation method (matrix or equation)
-Matrix switching
50Micro Motion® Compact Density Meters (CDM)
Configure process measurement
4.6.2Set up concentration measurement using ProLink III
This section guides you through the tasks required to set up, configure, and implement
concentration measurement.
Restriction
This section does not cover building a concentration matrix. See Micro Motion Enhanced Density
Application: Theory, Configuration, and Use for detailed information on building a matrix.
1.Enable the concentration measurement application using ProLink III
2.Load a concentration matrix using ProLink III
3.Set reference temperature values for specific gravity using ProLink III
4.Set up temperature data for concentration measurement using ProLink III
5.Modify matrix names and labels using ProLink III
6.Modify operational parameters for concentration measurement using ProLink III
7.Select the active concentration matrix using ProLink III
Enable the concentration measurement application using
ProLink III
The concentration measurement application must be enabled before you can perform any
setup. If the concentration measurement application was enabled at the factory, you do
not need to enable it now.
2.If the API referral application is enabled, disable it and click Apply.
The concentration measurement application and the API referral application cannot
be enabled simultaneously.
3.Set Concentration Measurement to Enabled and click Apply.
Load a concentration matrix using ProLink III
At least one concentration matrix must be loaded onto your transmitter. You can load up
to six.
Tip
In many cases, concentration matrices were ordered with the device and loaded at the factory. You
may not need to load any matrices.
Prerequisites
Standard matrices for the concentration measurement application
Concentration measurement matrices available by order
The concentration measurement application must be enabled on your device.
For each concentration matrix that you want to load, you need a file containing the matrix
data. The ProLink III installation includes a set of standard concentration matrices. Other
matrices are available from Micro Motion.
Configuration and Use Manual 51
Configure process measurement
Tips
•If you have a custom matrix on another device, you can save it to a file, then load it to the
•If you have a matrix file in ProLink II format, you can load it using ProLink III.
You must know the following information for your matrix:
•The derived variable that the matrix is designed to calculate
•The density unit that the matrix was built with
•The temperature unit that the matrix was built with
Important
•All concentration matrices on your transmitter must use the same derived variable.
•If you change the setting of Derived Variable, all existing concentration matrices will be deleted
•If you want the meter to calculate Net Mass Flow Rate, the derived variable must be set to
•If you want the meter to calculate Net Volume Flow Rate, the derived variable must be set to
current device.
from transmitter memory. Set Derived Variable before loading concentration matrices.
Mass Concentration (Density). If your matrix is not set up for Mass Concentration (Density),
contact Micro Motion for assistance or for a custom matrix.
Volume Concentration (Density). If your matrix is not set up for Volume Concentration
(Density), contact Micro Motion for assistance or for a custom matrix.
If you plan to use matrix switching, you must identify the two matrices to be used for
switching and load them into Slot 1 and Slot 2.
Procedure
1.Choose Device Tools > Configuration > Process Measurement > Line Density and set Density
Unit to the density unit used by your matrix.
Important
When you load a matrix, if the density unit is not correct, concentration data will be incorrect.
The density units must match at the time of loading. You can change the density unit after
the matrix is loaded.
2.Choose Device Tools > Configuration > Process Measurement > Line Temperature and set
Temperature Unit to the temperature unit used by your matrix.
Important
When you load a matrix, if the temperature unit is not correct, concentration data will be
incorrect. The temperature units must match at the time of loading. You can change the
temperature unit after the matrix is loaded.
The Concentration Measurement window is displayed. It is organized into steps that
allow you to perform several different setup and configuration tasks. For this task,
you will not use all the steps.
52Micro Motion® Compact Density Meters (CDM)
Configure process measurement
4.In Step 1, ensure that the setting of Derived Variable matches the derived variable
used by your matrix. If it does not, change it as required and click Apply.
Important
If you change the setting of Derived Variable, all existing concentration matrices will be deleted
from transmitter memory. Verify the setting of Derived Variable before continuing.
5.Load one or more matrices.
a. In Step 2, set Matrix Being Configured to the location (slot) to which the matrix will
be loaded.
b. Click Load Matrix from a File, navigate to the matrix file on your computer, and load
it.
c. Repeat until all required matrices are loaded.
6.(Optional) Set the density and temperature units to the units you want to use for
measurement.
Related information
Matrix switching
Derived variables and calculated process variables
Configure Temperature Measurement Unit
Configure Density Measurement Unit
Set reference temperature values for specific gravity using
ProLink III
When Derived Variable is set to Specific Gravity, you must set the reference temperature to be
used for density measurement and the reference temperature of water, and then verify
the density of water at the configured reference temperature. The two reference
temperature values affect specific gravity measurement.
Additionally, the two reference temperature values affect any concentration process
variable that is calculated by equation, rather than by matrix, because the equations are
based on specific gravity.
Typically, the two reference temperature values are the same, but this is not required.
Restriction
If Derived Variable is not set to Specific Gravity, do not change any of these values. These are set by the
active concentration matrix.
The Concentration Measurement window is displayed. It is organized into steps that
allow you to perform several different setup and configuration tasks. For this task,
you will not use all the steps.
Configuration and Use Manual 53
Configure process measurement
2.Scroll to Step 2, set Matrix Being Configured to the matrix you want to modify, and click
3.Scroll to Step 3, then perform the following actions:
4.Click the Apply button at the bottom of Step 3.
Related information
Change Matrix.
a. Set Reference Temperature for Referred Density to the temperature to which line
density will be corrected for use in the specific gravity calculation.
b. Set Reference Temperature for Water to the water temperature that will be used in
the specific gravity calculation.
c. Set Water Density at Reference Temperature to the density of water at the specified
reference temperature.
The transmitter automatically calculates the density of water at the specified
temperature. The new value will be displayed the next time that transmitter
memory is read. You can enter a different value if you want to.
Using equations to calculate specific gravity, °Baumé, °Brix, °Plato, and °Twaddell
Set up temperature data for concentration measurement
using ProLink III
The concentration measurement application uses line temperature data in its calculations.
You must decide how to provide this data, then perform the required configuration and
setup. Temperature data from the on-board temperature sensor (RTD) is always available.
You can set up an external temperature device and use external temperature data if you
want to.
The temperature setup that you establish here will be used for all concentration
measurement matrices on this meter.
Important
Line temperature data is used in several different measurements and calculations. It is possible to
use the internal RTD temperature in some areas and an external temperature in others. The
transmitter stores the internal RTD temperature and the external temperature separately. However,
the transmitter stores only one alternate temperature value, which may be either an external
temperature or the configured fixed value. Accordingly, if you set up polling for temperature in one
area, and digital communications in another, and configure a fixed temperature value in a third, the
fixed value will be overwritten by polling and digital communications, and polling and digital
communications will overwrite each other.
Prerequisites
If you plan to poll an external device, the primary mA output (Channel A) must be wired to
support HART communications.
The Concentration Measurement window is displayed. It is organized into steps that
allow you to perform several different setup and configuration tasks. For this task,
you will not use all the steps.
2.Scroll to Step 4.
3.Choose the method to be used to supply temperature data, and perform the
required setup.
OptionDescriptionSetup
Internal RTD temperature data
PollingThe meter polls an external de-
Temperature data from the onboard temperature sensor
(RTD) is used.
vice for temperature data. This
data will be available in addition to the internal RTD temperature data.
a. Set Line Temperature Source to Internal RTD.
b. Click Apply.
a. Set Line Temperature Source to Poll for External Value.
b. Set Polling Slot to an available slot.
c. Set Polling Control to Poll as Primary or Poll as Secondary.
OptionDescription
Poll as PrimaryNo other HART masters will be on the
Poll as SecondaryOther HART masters will be on the net-
Configure process measurement
network. The Field Communicator is not
a HART master.
work. The Field Communicator is not a
HART master.
Digital communications
d. Set External Device Tag to the HART tag of the temperature
device.
e. Click Apply.
A host writes temperature data
to the meter at appropriate intervals. This data will be available in addition to the internal
RTD temperature data.
a. Set Line Temperature Source to Fixed Value or Digital Communica-
tions.
b. Click Apply.
c. Perform the necessary host programming and communica-
tions setup to write temperature data to the meter at appro-
priate intervals.
Postrequisites
If you are using external temperature data, verify the external temperature value displayed
in the Inputs group on the ProLink III main window.
Need help? If the value is not correct:
•Ensure that the external device and the meter are using the same measurement unit.
•For polling:
-Verify the wiring between the meter and the external device.
-Verify the HART tag of the external device.
•For digital communications:
Configuration and Use Manual 55
Configure process measurement
•If necessary, apply an offset.
Modify matrix names and labels using ProLink III
For convenience, you can change the name of a concentration matrix and the label used
for its measurement unit. This does not affect measurement.
2.Scroll to Step 2, set Matrix Being Configured to the matrix you want to modify, and click
3.Scroll to Step 3, then perform the following actions:
4.Click the Apply button at the bottom of Step 3.
-Verify that the host has access to the required data.
-Verify that the host is writing to the correct register in memory, using the correct data
type.
The Concentration Measurement window is displayed. It is organized into steps that
allow you to perform several different setup and configuration tasks. For this task,
you will not use all the steps.
Change Matrix.
a. Set Concentration Units Label to the label that will be used for the concentration
unit.
b. If you set Concentration Units Label to Special, enter the custom label in User-Defined
Label.
c. In Matrix Name, enter the name to be used for the matrix.
Modify operational parameters for concentration
measurement using ProLink III
You can enable and disable extrapolation alerts, set extrapolation alert limits, and control
matrix switching. These parameters control the behavior of the concentration
measurement application but do not affect measurement directly. Additionally, for certain
types of concentration measurement, you can select the calculation method to be used.
The Concentration Measurement window is displayed. It is organized into steps that
allow you to perform several different setup and configuration tasks. For this task,
you will not use all the steps.
2.Scroll to Step 2, set Matrix Being Configured to the matrix you want to modify, and click
Change Matrix.
3.Scroll to Step 4.
4.Set up extrapolation alerts.
Each concentration matrix is built for a specific density range and a specific
temperature range. If line density or line temperature goes outside the range, the
transmitter will extrapolate concentration values. However, extrapolation may
56Micro Motion® Compact Density Meters (CDM)
Configure process measurement
affect accuracy. Extrapolation alerts are used to notify the operator that
extrapolation is occurring, and can also be used to initiate matrix switching. Each
concentration matrix has its own extrapolation alert settings.
a. Set Extrapolation Alert Limit to the point, in percent, at which an extrapolation alert
will be posted.
b. Enable or disable the high and low limit alerts for temperature and density, as
desired, and click Apply.
Important
If you plan to use matrix switching, you must enable the appropriate extrapolation alerts.
Example: If Extrapolation Alert Limit is set to 5%, High Extrapolation Limit (Temperature) is
enabled, and the matrix is built for a temperature range of 40 °F to 80 °F, an
extrapolation alert will be posted if line temperature goes above 82 °F.
5.If applicable, use the Equation Selection parameter to specify the type of calculation to
be used, and click Apply.
This option is available only when Derived Variable is set to Specific Gravity.
OptionDescription
Specific
Gravity
BaumeSpecific gravity is calculated as described above, and the result is used in the
BrixSpecific gravity is calculated as described above and the result is used in the
PlatoSpecific gravity is calculated as described above, and the result is used n the
TwaddellSpecific gravity is calculated as described above, and the result is used in the
Referred density is calculated from the matrix. The result is used in the specific
gravity equation. The output is specific gravity.
°Baumé equation. The output is specific gravity and °Baumé (light or heavy).
°Brix equation. The output is specific gravity and °Brix.
°Plato equation. The output is specific gravity and °Plato.
°Twaddell equation. The output is specific gravity and °Twaddell.
6.Enable or disable Matrix Switching as desired, and click Apply.
When matrix switching is enabled and an extrapolation alert occurs, the transmitter
automatically switches from the matrix in Slot 1 to the matrix in Slot 2, or vice versa.
This occurs only if no extrapolation alert would be generated by the other matrix.
Matrix switching is not applicable to any other slots.
Related information
Using equations to calculate specific gravity, °Baumé, °Brix, °Plato, and °Twaddell
Matrix switching
Configuration and Use Manual 57
Configure process measurement
Select the active concentration matrix using ProLink III
You must select the concentration matrix to be used for measurement. Although the
transmitter can store up to six concentration matrices, only one matrix can be used for
measurement at any one time.
2.Scroll to Step 2, set Active Matrix to the matrix you want to use and click Change Matrix.
Related information
The Concentration Measurement window is displayed. It is organized into steps that
allow you to perform several different setup and configuration tasks. For this task,
you will not use all the steps.
Note
To support matrix switching, you must select the matrix in Slot 1 or the matrix in Slot 2.
Matrix switching
4.6.3Set up concentration measurement using the
Field Communicator
This section guides you through most of the tasks related to setting up and implementing
the concentration measurement application.
Restrictions
•This section does not cover building a concentration matrix. See Micro Motion Enhanced
Density Application: Theory, Configuration, and Use for detailed information on building a
matrix.
•You cannot load a concentration matrix using the Field Communicator. If you need to load a
matrix, you must use ProLink III.
1.Enable the concentration measurement application using the Field Communicator
2.Set reference temperature values for specific gravity using the Field Communicator
3.Provide temperature data for concentration measurement using the Field Communicator
4.Modify matrix names and labels using the Field Communicator
5.Modify concentration measurement operational parameters using the
Field Communicator
6.Select the active concentration matrix using the Field Communicator
Enable the concentration measurement application using
the Field Communicator
The concentration measurement application must be enabled before you can perform any
setup. If the concentration measurement application was enabled at the factory, you do
not need to enable it now.
1.Choose Overview > Device Information > Applications > Enable/Disable Applications.
58Micro Motion® Compact Density Meters (CDM)
Configure process measurement
2.If the API referral application is enabled, disable it.
The concentration measurement application and the API referral application cannot
be enabled simultaneously.
3.Enable the concentration measurement application.
Set reference temperature values for specific gravity using
the Field Communicator
When Derived Variable is set to Specific Gravity, you must set the reference temperature to be
used for density measurement and the reference temperature of water, and then verify
the density of water at the configured reference temperature. The two reference
temperature values affect specific gravity measurement.
Additionally, the two reference temperature values affect any concentration process
variable that is calculated by equation, rather than by matrix, because the equations are
based on specific gravity.
Typically, the two reference temperature values are the same, but this is not required.
Restriction
If Derived Variable is not set to Specific Gravity, do not change any of these values. These are set by the
active concentration matrix. To check the setting of Derived Variable, choose Configure > Manual Setup >
Measurements > Conc Measure (CM) > CM Configuration.
Important
Do not change the setting of Derived Variable. If you change the setting of Derived Variable, all existing
concentration matrices will be deleted from transmitter memory.
2.Set Matrix Being Configured to the matrix you want to modify.
3.Choose Reference Conditions, then perform the following actions:
a. Set Reference Temp to the temperature to which line density will be corrected for
use in the specific gravity calculation.
b. Set Water Ref Temp to the water temperature that will be used in the specific
gravity calculation.
c. Set Water Ref Density to the density of water at the specified reference
temperature.
The transmitter automatically calculates the density of water at the specified
temperature. The new value will be displayed the next time that transmitter
memory is read. You can enter a different value if you want to.
Related information
Using equations to calculate specific gravity, °Baumé, °Brix, °Plato, and °Twaddell
Configuration and Use Manual 59
Configure process measurement
Provide temperature data for concentration measurement
using the Field Communicator
The concentration measurement application uses line temperature data in its calculations.
You must decide how to provide this data, then perform the required configuration and
setup. Temperature data from the on-board temperature sensor (RTD) is always available.
You can set up an external temperature device and use external temperature data if you
want to.
The temperature setup that you establish here will be used for all concentration
measurement matrices on this meter.
Important
Line temperature data is used in several different measurements and calculations. It is possible to
use the internal RTD temperature in some areas and an external temperature in others. The
transmitter stores the internal RTD temperature and the external temperature separately. However,
the transmitter stores only one alternate temperature value, which may be either an external
temperature or the configured fixed value. Accordingly, if you set up polling for temperature in one
area, and digital communications in another, and configure a fixed temperature value in a third, the
fixed value will be overwritten by polling and digital communications, and polling and digital
communications will overwrite each other.
Prerequisites
If you plan to poll an external device, the primary mA output (Channel A) must be wired to
support HART communications.
Procedure
Choose the method to be used to supply temperature data, and perform the required
setup.
MethodDescriptionSetup
Internal RTD temperature data
Temperature data from the onboard temperature sensor
(RTD) is used.
2.Set Matrix Being Configured to the matrix you want to modify.
3.Set Matrix Name to the name to be used for the matrix.
4.Set Concentration Units to the label that will be used for the concentration unit.
5.If you set Concentration Units to Special, choose Concentration Label and enter the custom
Modify concentration measurement operational parameters
using the Field Communicator
You can enable and disable extrapolation alerts, set extrapolation alert limits, and control
matrix switching. These parameters control the behavior of the concentration
measurement application but do not affect measurement directly. Additionally, for certain
types of concentration measurement, you can select the calculation type to be used.
2.Set Matrix Being Configured to the matrix you want to modify.
3.If applicable, set Equation Type to the type of calculation to be used.
label.
OptionDescription
Specific
Gravity
BaumeSpecific gravity is calculated as described above, and the result is used in the
BrixSpecific gravity is calculated as described above and the result is used in the
PlatoSpecific gravity is calculated as described above, and the result is used n the
TwaddellSpecific gravity is calculated as described above, and the result is used in the
This option is available only when Derived Variable is set to Specific Gravity.
4.Set up extrapolation alerts.
Each concentration matrix is built for a specific density range and a specific
temperature range. If line density or line temperature goes outside the range, the
transmitter will extrapolate concentration values. However, extrapolation may
affect accuracy. Extrapolation alerts are used to notify the operator that
extrapolation is occurring, and can also be used to initiate matrix switching. Each
concentration matrix has its own extrapolation alert settings.
Referred density is calculated from the matrix. The result is used in the specific
gravity equation. The output is specific gravity.
°Baumé equation. The output is specific gravity and °Baumé (light or heavy).
°Brix equation. The output is specific gravity and °Brix.
°Plato equation. The output is specific gravity and °Plato.
°Twaddell equation. The output is specific gravity and °Twaddell.
62Micro Motion® Compact Density Meters (CDM)
Configure process measurement
a. Set Extrapolation Alert Limit to the point, in percent, at which an extrapolation alert
c. Enable or disable the high and low alerts for temperature and density, as desired.
Important
If you are using matrix switching, you must enable the appropriate extrapolation alerts.
Example: If Extrapolation Alert Limit is set to 5%, High Extrapolation Limit (Temperature) is
enabled, and the matrix is built for a temperature range of 40 °F to 80 °F, an
extrapolation alert will be posted if line temperature goes above 82 °F.
5.Choose Configure > Manual Setup > Measurements > Conc Measure (CM) > CM Configuration,
then enable or disable Matrix Switching as desired.
When matrix switching is enabled and an extrapolation alert occurs, the transmitter
automatically switches from the matrix in Slot 1 to the matrix in Slot 2, or vice versa.
This occurs only if no extrapolation alert would be generated by the other matrix.
Matrix switching is not applicable to any other slots.
Related information
Using equations to calculate specific gravity, °Baumé, °Brix, °Plato, and °Twaddell
Matrix switching
Select the active concentration matrix using the
Field Communicator
You must select the concentration matrix to be used for measurement. Although the
transmitter can store up to six concentration matrices, only one matrix can be used for
measurement at any one time.
2.Set Active Matrix to the matrix you want to use.
Related information
Matrix switching
4.6.4Using equations to calculate specific gravity, °Baumé,
°Brix, °Plato, and °Twaddell
Whenever the derived variable is set to Specific Gravity, you have the option of using
equations to calculate °Baumé, °Brix,°Plato, and °Twaddell, instead of matrix referral.
Whenever the equation method is used, the active matrix is used to measure referred
density. This value is used to calculate specific gravity. The result of the specific gravity
calculation is then used in the equations used to calculate °Baumé, °Brix, °Plato, or
°Twaddell.
Configuration and Use Manual 63
Configure process measurement
Specific gravity is always calculated using the two reference temperatures that are
specified during concentration measurement configuration.
If you are measuring in °Baumé, the meter will automatically select the appropriate
equation according to the specific gravity of the process fluid, and will switch equations
when specific gravity crosses 1.0.
Equations used for specific gravity, °Baumé, °Brix, °Plato, and °TwaddellTable 4-6:
Current value of
Equation
Specific GravityN/A
°Baumé1.0 or greater
°BrixN/A
°PlatoN/A
°TwaddellN/A
specific gravityEquation
(°Baumé heavy)
Less than 1.0
(°Baumé light)
ρ
SG =
°Baumé = 145 −
°Baumé =
°Brix = 318.906 −
RefTemp
ρ
WaterRefTemp
140
− 130
SG
145
SG
(
384.341
SG
66.1086
+
)
(
SG
)
2
°Plato =(668.72 × SG)− 463.37 −(205.347 × SG
°Twaddell = 200 ×(SG − 1
)
2
)
SG
ρ
RefTemp
ρ
WaterRefTemp
Specific gravity of process fluid
Density of process fluid at Reference Temperature for Referred Density, as measured
using the active concentration matrix
Density of water at Reference Temperature for Water
Related information
Set reference temperature values for specific gravity using ProLink III
Set reference temperature values for specific gravity using the Field Communicator
4.6.5Matrix switching
Matrix switching can be used to measure different process fluids without resetting the
active matrix manually. Matrix switching can also be used to increase measurement
accuracy.
When matrix switching is enabled, the meter automatically switches between the matrices
in Slot 1 and Slot 2 whenever an extrapolation alert is present for the active matrix but
would not be generated by the other matrix. For example:
•The matrix in Slot 2 is active, the high-density extrapolation alert is enabled, and
matrix switching is enabled. Line density goes above the range of the matrix plus the
extrapolation limit. The meter posts an alert, then checks the range of the matrix in
Slot 1. No extrapolation alert would be posted, so the meter automatically switches
to the matrix in Slot 1.
64Micro Motion® Compact Density Meters (CDM)
Configure process measurement
•The matrix in Slot 2 is active, the high-density extrapolation alert is enabled, and
matrix switching is enabled. Line density goes above the range of the matrix plus the
extrapolation limit. The meter posts an alert, then checks the range of the matrix in
Slot 1. The current line density would also generate an extrapolation alert for this
matrix, so the meter does not switch.
You can control the conditions that trigger matrix switching by enabling or disabling
specific extrapolation alerts. For example, if the low-density and high-density extrapolation
alerts are enabled, but the low-temperature and high-temperature extrapolation alerts are
disabled, matrix switching will be triggered only by changes in line density. Changes in line
temperature will not trigger matrix switching.
Depending on your application, you may need to set up your matrices and extrapolation
limits so that there is no overlap in density and/or temperature, or so that there is slight
overlap.
On the display, the matrix number for the active matrix will alternately flash with the
concentration and referred density units.
Example: Using matrix switching to measure different process fluids
The line may contain either of two process fluids, depending on the current product. The
matrix in Slot 1 is appropriate for the first process fluid. The matrix in Slot 2 is appropriate
for the second process fluid. Whenever the line is switched, an extrapolation alert is posted
for the current matrix, and the meter automatically switches to use the other matrix.
To ensure that the correct matrix is used, there can be no overlap between the ranges of
the two matrices. In other words:
•If you are using density to trigger matrix switching, there can be no density values
that are within the ranges of both matrices, after the extrapolation limits are
applied.
•If you are using temperature to trigger matrix switching, there can be no
temperature values that are within the ranges of both matrices, after the
extrapolation limits are applied.
•If you are using both density and temperature to trigger matrix switching, there can
be no density or temperature values that are within the ranges of both matrices,
after the extrapolation limits are applied.
Example: Using matrix switching to increase measurement accuracy
For some process fluids, measurement accuracy is increased when the matrix has a
narrower temperature or density range. By using two matrices with adjacent or slightly
overlapping ranges, increased accuracy is available over a wider range of process variation.
To ensure continuous process measurement, there should be no gap between the ranges,
after the extrapolation limits are applied.
Configuration and Use Manual 65
Configure process measurement
4.7Set up flow monitoring
Flow monitoring is used to ensure sample integrity, especially for slipstream installations.
You can monitor either the volume flow rate or the velocity of your process.
The meter provides a basic velocity measurement. Velocity is typically used as a flow
indicator or diagnostic variable, to ensure that the flow rate is high enough to provide
good sample integrity.
Velocity is calculated from the measured volume flow rate and the cross-section of the
meter tube. If the calculated velocity is greater than the maximum velocity limit of the
sensor, Alert A005 is posted.
Tip
For diagnostic purposes, you can use either velocity measurement or volume flow rate
measurement. Although you can set up both, it is not necessary.
Procedure
1.Set Velocity Measurement Unit to the desired unit.
Velocity Measurement Unit controls the measurement unit used to report velocity.
• Default: m/sec
2.Set Velocity Damping to the value you want to use.
Velocity Damping controls the amount of damping that is applied to the velocity
measurement.
• Default: 0.8 seconds
• Range: 0.0–51.2 seconds
The value is automatically rounded down to the nearest valid value. Valid values are
as follows: 0, 0.2, 0.4, 0.8, … 51.2.
3.Enter the desired value for Velocity Cutoff.
Velocity Cutoff defines the point below which velocity will be reported as 0.
• Default: 0.0
• Range: Unlimited
4.Set Velocity Switch Setpoint to the value at which the velocity switch will be triggered
(after the 5% hysteresis is applied).
66Micro Motion® Compact Density Meters (CDM)
Configure process measurement
The velocity switch is typically used to indicate that flow is too low for to ensure
sample integrity.
• If the velocity is below the setpoint, the velocity switch is ON.
• If the velocity is above the setpoint, the velocity switch is OFF.
• Default: 0.0
• Range: 0.0 or any positive number
At the default value, the velocity switch will never be ON.
Tip
Depending on the communications tool you are using, you may need to configure Channel B
to operate as a discrete output, then set Discrete Output Source to Velocity Switch before you can
configure Velocity Switch Setpoint.
Postrequisites
Complete the setup using one of the following methods:
•Configure an mA output to report velocity.
•Configure a discrete output to report the state of the velocity switch.
•Set up HART burst mode to report velocity.
•Query the velocity value at regular intervals, using digital communications.
Options for Velocity Measurement Unit
The transmitter provides a standard set of measurement units for Velocity Measurement Unit.
Different communications tools may use different labels.
Options for Velocity Measurement UnitTable 4-7:
Label
Field Communica-
Unit description
Feet per secondFT/Sft/secft/s
Meters per secondM/Sm/secm/s
DisplayProLink III
tor
Velocity switch
The velocity switch is used to indicate whether velocity is above or below a user-configured
setpoint.
The velocity switch is based on the absolute value of the velocity, so it is not affected by
flow direction.
The velocity switch is implemented with a 5% hysteresis. Hysteresis defines a range around
the setpoint within which the velocity switch will not change.
Configuration and Use Manual 67
Configure process measurement
Example: Velocity switch in operation
If Velocity Switch Setpoint = 5 m/sec and the first measured velocity is above 5 m/sec, the
velocity switch is OFF. It will remain OFF unless the velocity drops below 4.75 m/sec. If this
happens, the velocity switch will turn ON, and remain ON until the velocity rises above
5.25 m/sec. At this point it turns OFF and will remain OFF until the velocity drops below
4.75 m/sec.
4.7.2Configure volume flow rate measurement
The meter provides a basic volume flow measurement. Volume flow rate is typically used
as a flow indicator or diagnostic variable, to ensure that the flow rate is high enough to
provide good sample integrity.
Tip
For diagnostic purposes, you can use either velocity measurement or volume flow rate
measurement. Although you can set up both measurements, it is not necessary.
Procedure
1.Set Volume Flow Rate Unit to the desired unit.
Volume Flow Rate Unit controls the measurement unit used to report the volume flow
rate.
• Default: liters/sec
2.Enter the desired value for Volume Flow Cutoff.
Volume Flow Cutoff defines the point below which volume flow rate will be reported as
0.
• Default: 0.0
• Range: Greater than 0
3.Set Volume Flow Rate Meter Factor to the value by which the measured volume flow rate
will be multiplied.
The meter factor is used to scale the volume flow.
• Default: 1.0
• Range: 0.8 to 1.2
At the default value, the meter factor will not change the measured value.
Postrequisites
Complete the setup using one of the following methods:
•Configure an mA output to report volume flow rate.
•Set up HART burst mode to report volume flow rate.
•Set up a display variable.
•Query the volume flow rate at regular intervals using digital communications.
68Micro Motion® Compact Density Meters (CDM)
Configure process measurement
•Configure flow-direction handling using the same parameter as velocity. Both will
both have the same flow-direction handling.
•Options for Volume Flow Measurement Unit
Options for Volume Flow Measurement Unit
The transmitter provides a standard set of measurement units for Volume Flow Measurement
Unit.
Options for Volume Flow Measurement Unit for liquid applicationsTable 4-8:
Label
Unit description
DisplayProLink IIIField Communicator
Cubic feet per secondCUFT/Sft3/secCuft/s
Cubic feet per minuteCUF/MNft3/minCuft/min
Cubic feet per hourCUFT/Hft3/hrCuft/h
Cubic feet per dayCUFT/Dft3/dayCuft/d
Cubic meters per secondM3/Sm3/secCum/s
Cubic meters per minuteM3/MINm3/minCum/min
Cubic meters per hourM3/Hm3/hrCum/h
Cubic meters per dayM3/Dm3/dayCum/d
U.S. gallons per secondUSGPSUS gal/secgal/s
U.S. gallons per minuteUSGPMUS gal/mingal/min
U.S. gallons per hourUSGPHUS gal/hrgal/h
U.S. gallons per dayUSGPDUS gal/daygal/d
Million U.S. gallons per dayMILG/Dmil US gal/dayMMgal/d
Liters per secondL/Sl/secL/s
Liters per minuteL/MINl/minL/min
Liters per hourL/Hl/hrL/h
Million liters per dayMILL/Dmil l/dayML/d
Imperial gallons per secondUKGPSImp gal/secImpgal/s
Imperial gallons per minuteUKGPMImp gal/minImpgal/min
Imperial gallons per hourUKGPHImp gal/hrImpgal/h
Imperial gallons per dayUKGPDImp gal/dayImpgal/d
(1)
(1)
(1)
(1)
(2)
(2)
BBL/Sbarrels/secbbl/s
BBL/MNbarrels/minbbl/min
BBL/Hbarrels/hrbbl/h
BBL/Dbarrels/daybbl/d
BBBL/SBeer barrels/secbbbl/s
BBBL/MNBeer barrels/minbbbl/min
Barrels per second
Barrels per minute
Barrels per hour
Barrels per day
Beer barrels per second
Beer barrels per minute
Configuration and Use Manual 69
Configure process measurement
Options for Volume Flow Measurement Unit for liquid applications (continued)Table 4-8:
Label
Unit description
Beer barrels per hour
Beer barrels per day
(1) Unit based on oil barrels (42 U.S. gallons).
(2) Unit based on U.S. beer barrels (31 U.S. gallons).
(2)
(2)
DisplayProLink IIIField Communicator
BBBL/HBeer barrels/hrbbbl/h
BBBL/DBeer barrels/daybbbl/d
4.7.3Configure Flow Direction
DisplayNot available
ProLink IIIDevice Tools > Configuration > Process Measurement > Velocity > Flow Direction
Field Communicator Configure > Manual Setup > Measurements > Velocity/Volume > Flow Direction
Overview
Flow Direction controls how forward flow and reverse flow affect velocity measurement and
reporting.
Flow Direction is defined with respect to the flow arrow on the sensor:
•Forward flow (positive flow) moves in the direction of the flow arrow on the sensor.
•Reverse flow (negative flow) moves in the direction opposite to the flow arrow on
the sensor.
Tip
Micro Motion sensors are bidirectional. Measurement accuracy is not affected by actual flow
direction or the setting of the Flow Direction parameter.
Procedure
Set Flow Direction to the value you want to use.
The default setting is Forward.
•Options for Flow Direction
•Effect of Flow Direction on mA outputs
•Effect of Flow Direction on digital communications
70Micro Motion® Compact Density Meters (CDM)
Options for Flow Direction
Options for Flow DirectionTable 4-9:
Flow Direction setting
Configure process measurement
ProLink IIIField Communica-
tor
ForwardForwardAppropriate when the Flow Direction ar-
ReverseReverseAppropriate when the Flow Direction ar-
Absolute ValueAbsolute ValueFlow Direction arrow is not relevant.The absolute value of the proc-
BidirectionalBi directionalAppropriate when both forward and re-
Negate ForwardNegate/Forward OnlyAppropriate when the Flow Direction ar-
Negate Bi-directionalNegate/Bi-directionalAppropriate when both forward and re-
Relationship to Flow Direction arrow on
sensor
row is in the same direction as the majority of flow.
row is in the opposite direction from the
majority of flow.
verse flow are expected, and forward flow
will dominate, but the amount of reverse
flow will be significant.
row is in the opposite direction from the
majority of flow.
verse flow are expected, and reverse flow
will dominate, but the amount of forward
flow will be significant.
Effect on velocity measurement
No effect
No effect
ess variable is used.
No effect
The sign of the process variable
is reversed.
The sign of the process variable
is reversed.
Effect of Flow Direction on mA outputs
Flow Direction affects how the transmitter reports velocity via the mA outputs. The mAoutputs are affected by Flow Direction only if mA Output Process Variable is set to Velocity.
Flow Direction and mA outputs
The effect of Flow Direction on the mA outputs depends on Lower Range Value configured for
the mA output:
•If Lower Range Value is set to 0, see Figure 4‐1.
•If Lower Range Value is set to a negative value, see Figure 4‐2.
Configuration and Use Manual 71
Configure process measurement
Effect of Flow Direction on the mA output: Lower Range Value = 0Figure 4-1:
Flow Direction = Forward
20
12
mA output
4
-x0x
Reverse flowForward flow
•Lower Range Value = 0
•Upper Range Value = x
Effect of Flow Direction on the mA output: Lower Range Value < 0Figure 4-2:
Flow Direction = Forward
20
Flow Direction = Reverse, Negate Forward
20
12
mA output
4
-x0x
Reverse flowForward flow
Flow Direction = Reverse, Negate Forward
20
Flow Direction = Absolute Value, Bidirectional,
Negate Bidirectional
20
12
mA output
4
-x0x
Reverse flowForward flow
Flow Direction = Absolute Value, Bidirectional,
Negate Bidirectional
20
12
mA output
4
-x0x
Reverse flowForward flow
•Lower Range Value = −x
•Upper Range Value = x
Example: Flow Direction = Forward and Lower Range Value = 0
Configuration:
•Flow Direction = Forward
•Lower Range Value = 0 m/sec
•Upper Range Value = 10 m/sec
Result:
•Under conditions of reverse flow or zero flow, the mA output is 4 mA.
12
mA output
4
-x0x
Reverse flowForward flow
12
mA output
4
-x0x
Reverse flowForward flow
72Micro Motion® Compact Density Meters (CDM)
Configure process measurement
•Under conditions of forward flow, up to a velocity of 10 m/sec, the mA output varies
between 4 mA and 20 mA in proportion to the velocity.
•Under conditions of forward flow, if the velocity equals or exceeds 10 m/sec, the mA
output will be proportional to the velocity up to 20.5 mA, and will be level at
20.5 mA at higher velocity values.
Example: Flow Direction = Forward and Lower Range Value < 0
Configuration:
•Flow Direction = Forward
•Lower Range Value = −10 m/sec
•Upper Range Value = +10 m/sec
Result:
•Under conditions of zero flow, the mA output is 12 mA.
•Under conditions of forward flow, for velocity values between 0 and +10 m/sec, the
mA output varies between 12 mA and 20 mA in proportion to (the absolute value of)
the velocity.
•Under conditions of forward flow, if (the absolute value of) the velocity equals or
exceeds +10 m/sec, the mA output is proportional to the velocity up to 20.5 mA,
and will be level at 20.5 mA at higher velocity values.
•Under conditions of reverse flow, for velocity values between 0 and −10 m/sec, the
mA output varies between 4 mA and 12 mA in inverse proportion to the absolute
value of the velocity.
•Under conditions of reverse flow, if the absolute value of the velocity equals or
exceeds +10 m/sec, the mA output is inversely proportional to the velocity down to
3.8 mA, and will be level at 3.8 mA at higher velocity values.
Example: Flow Direction = Reverse
Configuration:
•Flow Direction = Reverse
•Lower Range Value = 0 m/sec
•Upper Range Value = 10 m/sec
Result:
•Under conditions of forward flow or zero flow, the mA output is 4 mA.
•Under conditions of reverse flow, for velocity values between 0 and +10 m/sec, the
mA output level varies between 4 mA and 20 mA in proportion to the absolute value
of the velocity.
•Under conditions of reverse flow, if the absolute value of the velocity equals or
exceeds 10 m/sec, the mA output will be proportional to the absolute value of the
velocity up to 20.5 mA, and will be level at 20.5 mA at higher absolute values.
Configuration and Use Manual 73
Configure process measurement
Effect of Flow Direction on digital communications
Flow Direction affects how flow values are reported via digital communications.
Table 4-10:
Effect of the Flow Direction parameter and actual flow direction on velocity
values reported via digital communications
Flow Direction setting
ForwardPositive0Negative
ReversePositive0Negative
BidirectionalPositive0Negative
Absolute ValuePositive
Negate ForwardNegative0Positive
Negate BidirectionalNegative0Positive
(1) Refer to the digital communications status bits for an indication of whether flow is positive or negative.
Flow Damping controls the amount of damping that is applied to the measured process flow.
Flow Damping affects both velocity and volume flow rate.
Damping is used to smooth out small, rapid fluctuations in process measurement. Damping
Value specifies the time period (in seconds) over which the transmitter will spread changes
in the process variable. At the end of the interval, the internal value will reflect 63% of the
change in the actual measured value.
Procedure
Set Flow Damping to the value you want to use.
• Default: 0.8 seconds
• Range: 0.0–51.2 seconds
The value is automatically rounded down to the nearest valid value. Valid values are as
follows: 0, 0.2, 0.4, 0.8, … 51.2.
74Micro Motion® Compact Density Meters (CDM)
Configure device options and preferences
5Configure device options and
preferences
Topics covered in this chapter:
•Configure the transmitter display
•Enable or disable the Acknowledge All Alerts display command
•Configure security for the display menus
•Configure alert handling
•Configure informational parameters
5.1Configure the transmitter display
You can control the process variables shown on the display and a variety of display
behaviors.
•Configure the language used for the display (Section 5.1.1)
•Configure the process variables and diagnostic variables shown on the display
(Section 5.1.2)
•Configure the number of decimal places (precision) shown on the display
(Section 5.1.3)
•Configure the refresh rate of data shown on the display (Section 5.1.4)
•Enable or disable automatic scrolling through the display variables (Section 5.1.5)
5.1.1Configure the language used for the display
DisplayOFF-LINE MAINT > OFF-LINE CONFG > DISPLAY > LANG
ProLink IIIDevice Tools > Configuration > Transmitter Display > General
Field Communicator Configure > Manual Setup > Display > Language
Overview
Display Language controls the language used for process data and menus on the display.
Procedure
Select the language you want to use.
The languages available depend on your transmitter model and version.
Configuration and Use Manual 75
Configure device options and preferences
5.1.2Configure the process variables and diagnostic variables
shown on the display
You can control the process variables and diagnostic variables shown on the display, and
the order in which they appear. The display can scroll through up to 15 variables in any
order you choose. In addition, you can repeat variables or leave slots unassigned.
Restriction
You cannot set Display Variable 1 to None or to a diagnostic variable. Display Variable 1 must be set to a
process variable.
Procedure
For each display variable you want to change, assign the process variable you want to use.
5.1.3Configure the number of decimal places (precision)
shown on the display
You can specify the number of decimal places (precision) that are shown on the display for
each process variable or diagnostic variable. You can set the precision independently for
each variable.
The display precision does not affect the actual value of the variable or the value used in
calculations.
Procedure
1.Select a variable.
2.Set Number of Decimal Places to the number of decimal places you want shown when
the process variable or diagnostic variable appears on the display.
For temperature and density process variables, the default value is 2 decimal places.
For all other variables, the default value is 4 decimal places. The range is 0 to 5.
76Micro Motion® Compact Density Meters (CDM)
Configure device options and preferences
Tip
The lower the precision, the greater the change must be for it to be reflected on the display.
Do not set the precision too low or too high to be useful.
5.1.4Configure the refresh rate of data shown on the display
You can set Refresh Rate to control how frequently data is refreshed on the display.
Procedure
Set Refresh Rate to the desired value.
The default value is 1000 milliseconds. The range is 100 milliseconds to
10,000 milliseconds (10 seconds).
5.1.5Enable or disable automatic scrolling through the
display variables
DisplayOFF-LINE MAINT > OFF-LINE CONFG > DISPLAY > AUTO SCRLL
ProLink IIIDevice Tools > Configuration > Transmitter Display > General
Field Communicator Configure > Manual Setup > Display > Display Behavior > Auto Scroll
Overview
You can configure the display to automatically scroll through the configured display
variables or to show a single display variable until the operator activates Scroll. When you
set automatic scrolling, you can also configure the length of time each display variable is
displayed.
Procedure
1.Enable or disable Auto Scroll as desired.
OptionDescription
EnabledThe display automatically scrolls through each display variable as specified
by Scroll Rate. The operator can move to the next display variable at any
time using Scroll.
Configuration and Use Manual 77
Configure device options and preferences
OptionDescription
Disabled (default)
The display shows Display Variable 1 and does not scroll automatically. The
operator can move to the next display variable at any time using Scroll.
2.If you enabled Auto Scroll, set Scroll Rate as desired.
The default value is 10 seconds.
Tip
Scroll Rate may not be available until you apply Auto Scroll.
5.2Enable or disable the Acknowledge All Alerts display
command
Fault Timeout controls the delay before fault actions are performed.
Restriction
Fault Timeout is applied only to the following alerts (listed by Status Alert Code): A003, A004, A005,
A008, A016, A017, A033. For all other alerts, fault actions are performed as soon as the alert is
detected.
Procedure
Set Fault Timeout as desired.
The default value is 0 seconds. The range is 0 to 60 seconds.
If you set Fault Timeout to 0, fault actions are performed as soon as the alert condition is
detected.
The fault timeout period begins when the transmitter detects an alert condition. During
the fault timeout period, the transmitter continues to report its last valid measurements.
If the fault timeout period expires while the alert is still active, the fault actions are
performed. If the alert condition clears before the fault timeout expires, no fault actions
are performed.
Field Communicator Configure > Manual Setup > Inputs/Outputs > Channels > Channel B
Overview
Depending on your device, you can configure Channel B to operate as either an mA output
or a discrete output.
Restriction
You cannot configure Channel B on the CDM TPS device. On this device, Channel B always operates
as a TPS output.
Prerequisites
The configuration of Channel B must match the wiring. See the installation manual for your
device.
To avoid causing process errors:
•Configure Channel B before configuring the mA output or discrete output.
•Before changing the channel configuration, ensure that all control loops affected by
the channel are under manual control.
Procedure
Set Channel B as desired.
Configuration and Use Manual 85
Integrate the meter with the control system
OptionDescription
mA outputChannel B will operate as the secondary mA output.
Discrete outputChannel B will operate as a discrete output.
6.2Configure the mA output
The mA output is used to report the configured process variable. The mA output
parameters control how the process variable is reported.
The CDM mA device has two mA outputs: Channel A and Channel B. Both outputs are fully
configurable.
The CDM DO device has one mA output: Channel A. The output is fully configurable.
The CDM TPS device has one mA output: Channel A. The output is partially configurable.
Important
Whenever you change an mA output parameter, verify all other mA output parameters before
returning the meter to service. In some situations, the transmitter automatically loads a set of stored
values, and these values may not be appropriate for your application.
•Configure mA Output Process Variable (Section 6.2.1)
•Configure Lower Range Value (LRV) and Upper Range Value (URV) (Section 6.2.2)
•Configure Added Damping (Section 6.2.3)
•Configure mA Output Fault Action and mA Output Fault Level (Section 6.2.4)
6.2.1Configure mA Output Process Variable
DisplayOFF-LINE MAINT > OFF-LINE CONFG > IO > CONFIG MAO 1 > AO 1 SRC
OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > MAO 2 > CONFIG MAO 2 > AO 2 SRC
ProLink IIIDevice Tools > Configuration > I/O > Outputs > mA Output > mA Output 1 > Source
Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 2 > Source
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output 1 > Primary Variable
Use mA Output Process Variable to select the variable that is reported over the mA output.
Prerequisites
If you are using the HART variables, be aware that changing the configuration of mA Output
Process Variable will change the configuration of the HART Primary Variable (PV) and/or the
HART Secondary Variable (SV).
86Micro Motion® Compact Density Meters (CDM)
Integrate the meter with the control system
Procedure
Set mA Output Process Variable as desired.
Default settings are shown in the following table.
Default settings for mA Output Process VariableTable 6-1:
Default process variable assign-
DeviceChannelmA output
CDM mAChannel APrimary mA outputDensity
Channel BSecondary mA outputTemperature
CDM DOChannel APrimary mA outputDensity
CDM TPSChannel APrimary mA outputTemperature
ment
Postrequisites
If you changed the setting of mA Output Process Variable, verify the settings of Lower Range
Value (LRV) and Upper Range Value (URV).
Options for mA Output Process Variable
The transmitter provides a basic set of options for mA Output Process Variable, plus several
application-specific options. Different communications tools may use different labels for
the options.
Options for mA Output Process VariableTable 6-2:
Label
Process variable
Standard
Line DensityDENSLine DensityDensity
Line TemperatureTEMPLine TemperatureTemperature
Case TemperatureTCASECase TemperatureCase Temperature
Tube-Case Temperature Difference
Line Temperature (External
or Fixed)
Line Pressure (External or
Fixed)
Drive GainDGAINDrive GainDrive Gain
Sensor Time PeriodTP BSensor Time PeriodSensor Time Period
VelocityVELVelocityVelocity
User-Defined Calculation
Output
DisplayProLink IIIField Communicator
TDIFFTube-Case Temperature Dif-
ference
EXT TLine Temperature (External
or Fixed)
EXTPLine Pressure (External or
Fixed)
UCALCUser-Defined Calculation
Output
Tube-Case Temp Difference
External Temperature
External Pressure
User-Defined Calculation
Output
Configuration and Use Manual 87
Integrate the meter with the control system
Options for mA Output Process Variable (continued)Table 6-2:
Label
Process variable
API referral
Referred Density (API)RDENSReferred Density (API)Density at Reference (API)
Concentration measurement
Specific GravitySGSpecific GravitySpecific Gravity (CM)
ConcentrationCONCConcentrationConcentration (CM)
Referred Density (Concentration)
DisplayProLink IIIField Communicator
RDENSReferred Density (Concen-
tration)
Density at Reference (CM)
6.2.2Configure Lower Range Value (LRV) and Upper Range Value
(URV)
DisplayOFF-LINE MAINT > OFF-LINE CONFG > IO > CONFIG MAO 1 > 4 mA
OFF-LINE MAINT > OFF-LINE CONFG > IO > CONFIG MAO 1 > 20 mA
OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > MAO 2 > CONFIG MAO 2 > 4 mA
OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > MAO 2 > CONFIG MAO 2 > 20 mA
ProLink IIIDevice Tools > Configuration > I/O > Outputs > mA Output > mA Output 1 > Lower Range Value
Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 1 > Upper Range Vaue
Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 2 > Lower Range Value
Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 2 > Upper Range Vaue
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output 1 > mA Output Settings > PV LRV
Configure > Manual Setup > Inputs/Outputs > mA Output 1 > mA Output Settings > PV URV
Configure > Manual Setup > Inputs/Outputs > mA Output 2 > mA Output Settings > SV LRV
Configure > Manual Setup > Inputs/Outputs > mA Output 2 > mA Output Settings > SV URV
Overview
The Lower Range Value (LRV) and Upper Range Value (URV) are used to scale the mA output,
that is, to define the relationship between mA Output Process Variable and the mA output
level.
Important
Your device may have been ordered with predefined values for LRV and URV that are appropriate for
specific applications. However, you can change these settings if you want to.
88Micro Motion® Compact Density Meters (CDM)
Integrate the meter with the control system
Prerequisites
Ensure that mA Output Process Variable is set to the desired process variable. Each process
variable has its own set of LRV and URV values. When you change the values of LRV and
URV, you are configuring values for the currently assigned mA output process variable.
Ensure that the measurement unit for the configured process variable has been set as
desired.
Procedure
Set LRV and URV as desired.
• LRV is the value of mA Output Process Variable represented by an output of 4 mA. The
default value for LRV depends on the setting of mA Output Process Variable. Enter LRV in
the measurement units that are configured for mA Output Process Variable.
• URV is the value of mA Output Process Variable represented by an output of 20 mA. The
default value for URV depends on the setting of mA Output Process Variable. Enter URV in
the measurement units that are configured for mA Output Process Variable.
Tip
For best performance:
• Set LRV ≥ LSL (lower sensor limit).
• Set URV ≤ USL (upper sensor limit).
• Set these values so that the difference between URV and LRV is ≥ Min Span (minimum span).
Defining URV and LRV within the recommended values for Min Span, LSL, and USL ensures that the
resolution of the mA output signal is within the range of the bit precision of the D/A converter.
Note
You can set URV below LRV. For example, you can set URV to 50 and LRV to 100.
The mA output uses a range of 4–20 mA to represent mA Output Process Variable. Between
LRV and URV, the mA output is linear with the process variable. If the process variable
drops below LRV or rises above URV, the transmitter posts an output saturation alert.
6.2.3Configure Added Damping
DisplayNot available
ProLink IIIDevice Tools > Configuration > I/O > Outputs > mA Output > mA Output 1 > Added Damping
Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 2 > Added Damping
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output 1 > mA Output Settings > PV Added Damping
Configure > Manual Setup > Inputs/Outputs > mA Output 2 > mA Output Settings > SV Added Damping
Overview
Added Damping controls the amount of damping that will be applied to the mA output.
Configuration and Use Manual 89
Integrate the meter with the control system
Damping is used to smooth out small, rapid fluctuations in process measurement. DampingValue specifies the time period (in seconds) over which the transmitter will spread changes
in the process variable. At the end of the interval, the internal value will reflect 63% of the
change in the actual measured value.
Added Damping affects the reporting of mA Output Process Variable through the mA output
only. It does not affect the reporting of that process variable via any other method (e.g., a
frequency output or digital communications), or the value of the process variable used in
calculations.
Note
Added Damping is not applied if the mA output is fixed (for example, during loop testing) or if the mA
output is reporting a fault. Added Damping is applied while sensor simulation is active.
Procedure
Set Added Damping to the desired value.
The default value is 0.0 seconds. The range is 0.0 to 440 seconds.
When you specify a value for Added Damping, the transmitter automatically rounds the value
down to the nearest valid value.
Interaction between mA Output Damping and process variable
damping
When mA Output Process Variable is set to density or temperature, Added Damping interacts
with Density Damping or Temperature Damping.
Example: Damping interaction
Configuration:
•mA Output Process Variable = Density
•Density Damping = 1 second
•Added Damping = 2 seconds
Result: A change in density will be reflected in the mA output over a time period that is
greater than 3 seconds. The exact time period is calculated by the transmitter according to
internal algorithms which are not configurable.
Related information
Interaction between Density Damping and Added Damping
90Micro Motion® Compact Density Meters (CDM)
Integrate the meter with the control system
6.2.4Configure mA Output Fault Action and mA Output Fault Level
DisplayNot available
ProLink IIIDevice Tools > Configuration > I/O > Outputs > mA Output > mA Output 1 > Fault Action
Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 2 > Fault Action
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output 1 > mAO1 Fault Settings > MAO1 Fault Action
mA Output Fault Action controls the behavior of the mA output if the transmitter encounters
an internal fault condition.
Note
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement the
fault action until the timeout has elapsed.
Procedure
1.Set mA Output Fault Action to the desired value.
The default setting is Downscale.
Restriction
If Digital Communications Fault Action is set to NAN (not a number), you cannot set mA Output Fault
Action to None. If you try to do this, the device will not accept the configuration.
2.If you set mA Output Fault Action to Upscale or Downscale, set mA Output Fault Level as
desired.
Postrequisites
CAUTION!
If you set mA Output Fault Action to None, be sure to set Digital Communications Fault Action to None. If you
do not, the output will not report actual process data, and this may result in measurement
errors or unintended consequences for your process.
Options for mA Output Fault Action and mA Output Fault Level
Options for mA Output Fault Action and mA Output Fault LevelTable 6-3:
OptionmA output behaviormA Output Fault Level
UpscaleGoes to the configured fault levelDefault: 21.5 mA
Range: 21.0 to 21.5 mA
Configuration and Use Manual 91
Integrate the meter with the control system
Options for mA Output Fault Action and mA Output Fault Level (continued)Table 6-3:
OptionmA output behaviormA Output Fault Level
Downscale (default)Goes to the configured fault levelDefault: 3.2 mA
Internal ZeroGoes to the mA output level associated
with a process variable value of 0 (zero),
as determined by Lower Range Value and
Upper Range Value settings
NoneTracks data for the assigned process vari-
able; no fault action
6.3Configure the discrete output
The discrete output is used to report specific meter or process conditions. The discrete
output parameters control which condition is reported and how it is reported. Depending
on your purchase option, your transmitter may have one discrete output or no discrete
outputs.
Range: 3.2 to 3.6 mA
Not applicable
Not applicable
Important
Whenever you change a discrete output parameter, verify all other discrete output parameters
before returning the meter to service. In some situations, the transmitter automatically loads a set of
stored values, and these values may not be appropriate for your application.