Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration
of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available
on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion
Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States800-522-6277U.K.0870 240 1978Australia800 158 727
9.1 Booster amplifiers with CMF400 sensors.........................................................................................76
9.2 Booster amplifiers with D600 sensors............................................................................................. 78
Installation Instructionsiii
Page 4
ContentsInstallation Manual
November 201920001969
ivMicro Motion UL-D-IS 9-Wire
Page 5
Installation ManualBefore you begin
20001969November 2019
1Before you begin
1.1About this document
Use this manual to ensure that any applicable Micro Motion flow meter installation
complies with Underwriter Laboratories (UL) safety standards.
The information in this document assumes that users understand basic transmitter and
sensor installation concepts and procedures.
This manual provides only information associated with installation of transmitters through
UL-D-IS, 9-wire instructions. For complete information on flow meter installation, see the
documentation provided with your sensor and transmitter.
1.2Hazard messages
This document uses the following criteria for hazard messages based on ANSI standards
Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a
situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration
of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access to protect users' assets. This is true for all
systems used within the facility.
Installation Instructions5
Page 6
Before you beginInstallation Manual
November 201920001969
1.3Hazardous area installations
If your cable will be installed in a hazardous area, ensure that it meets the hazardous area
requirements.
WARNING
Failure to maintain intrinsic safety in a hazardous area could cause an explosion
resulting in injury or death.
To keep sensor wiring intrinsically safe:
• Keep intrinsically safe (IS) sensor wiring separate from power supply wiring and output
wiring.
• Do not install power cable in the same conduit or cable tray as flow meter cable.
• Use this document with the appropriate approvals documentation. These manuals are
shipped with the flow meter or available at www.emerson.com.
• For hazardous area installations in Europe, refer to standard EN 60079-14 if national
standards do not apply.
6Micro Motion UL-D-IS 9-Wire
Page 7
Installation Manual1700 and 2700 transmitters
20001969November 2019
21700 and 2700 transmitters
2.11700 and 2700 transmitter outputs
List of drawings
TransmitterDrawing
1700/2700 mA OutputsEB-3600478, Revision DA
1700/2700 intrinsically safe outputsEB-3600630, Revision EA
2700 configurable inputs and outputsEB-3600666, Revision CA
1700/2700 FOUNDATION™ fieldbus outputsEB-3600475, Revision G
1700/2700 Profibus-PA outputsEB-3600472, Revision G
Installation Instructions7
Page 8
1700 and 2700 transmittersInstallation Manual
November 201920001969
2.1.11700/2700 mA Outputs
8Micro Motion UL-D-IS 9-Wire
Page 9
Installation Manual1700 and 2700 transmitters
20001969November 2019
2.1.21700/2700 intrinsically safe outputs
Installation Instructions9
Page 10
1700 and 2700 transmittersInstallation Manual
November 201920001969
2.1.32700 configurable inputs and outputs
10Micro Motion UL-D-IS 9-Wire
Page 11
G
Installation Manual1700 and 2700 transmitters
20001969November 2019
2.1.41700/2700 FOUNDATION™ fieldbus outputs
Installation Instructions11
Page 12
1700 and 2700 transmittersInstallation Manual
November 201920001969
2.1.51700/2700 Profibus-PA outputs
12Micro Motion UL-D-IS 9-Wire
Page 13
Installation Manual1700 and 2700 transmitters
20001969November 2019
2.21700/2700 integral core processor installations
List of drawings
InstallationDrawing
1700/2700 with integral core processor and
CMF, F, T, D, or DL sensors
1700/2700 with integral core processor and
CMF300A sensor
1700/2700 with integral core processor and
CMF400 sensor with booster amplifier
1700/2700 with integral core processor and
D600 sensor
1700/2700 with integral core processor and DT
sensor
EB-3600420, Rev EA
EB-3600533, Revision D
EB-3006198, Revision C
EB-1005116, Revision B
EB-3600532 Rev D
Installation Instructions13
Page 14
1700 and 2700 transmittersInstallation Manual
November 201920001969
2.2.11700/2700 with integral core processor and CMF, F, T,
D, or DL sensors
This drawing does not apply to the D600, DT, CMF300A, or CMF400 with booster amplifier
sensors.
14Micro Motion UL-D-IS 9-Wire
Page 15
Installation Manual1700 and 2700 transmitters
20001969November 2019
2.2.21700/2700 with integral core processor and CMF300A
sensor
Installation Instructions15
Page 16
1700 and 2700 transmittersInstallation Manual
November 201920001969
2.2.31700/2700 with integral core processor and CMF400
sensor with booster amplifier
16Micro Motion UL-D-IS 9-Wire
Page 17
Installation Manual1700 and 2700 transmitters
20001969November 2019
2.2.41700/2700 with integral core processor and D600
sensor
Installation Instructions17
Page 18
1700 and 2700 transmittersInstallation Manual
November 201920001969
2.2.51700/2700 with integral core processor and DT sensor
18Micro Motion UL-D-IS 9-Wire
Page 19
Installation Manual1700 and 2700 transmitters
20001969November 2019
2.31700/2700 remote core processor installations
List of drawings
InstallationDrawing
1700/2700 with remote core processor and
CMF, F, T, D, or DL sensors
1700/2700 with remote core processor and
CMF300A sensor
1700/2700 with remote core processor and
CMF400 sensor with booster amplifier
1700/2700 with remote core processor and
D600 sensor
1700/2700 with remote core processor and DT
sensor
EB-3600676 Revision DA
EB-3600678, Revision D
EB-3007060, Revision C
EB-1005118, Revision B
EB-3600677, Revision C
Installation Instructions19
Page 20
1700 and 2700 transmittersInstallation Manual
November 201920001969
2.3.11700/2700 with remote core processor and CMF, F, T, D,
or DL sensors
This drawing does not apply to the D600, DT, CMF300A, or CMF400 with booster amplifier
sensors.
20Micro Motion UL-D-IS 9-Wire
Page 21
Installation Manual1700 and 2700 transmitters
20001969November 2019
2.3.21700/2700 with remote core processor and CMF300A
sensor
Installation Instructions21
Page 22
1700 and 2700 transmittersInstallation Manual
November 201920001969
2.3.31700/2700 with remote core processor and CMF400
sensor with booster amplifier
22Micro Motion UL-D-IS 9-Wire
Page 23
Installation Manual1700 and 2700 transmitters
20001969November 2019
2.3.41700/2700 with remote core processor and D600
sensor
Installation Instructions23
Page 24
1700 and 2700 transmittersInstallation Manual
November 201920001969
2.3.51700/2700 with remote core processor and DT sensor
24Micro Motion UL-D-IS 9-Wire
Page 25
Installation Manual3300 transmitters
20001969November 2019
33300 transmitters
Nonincendive parameters
Installation Instructions25
Page 26
3300 transmittersInstallation Manual
November 201920001969
26Micro Motion UL-D-IS 9-Wire
Page 27
Installation Manual3350 transmitters
20001969November 2019
43350 transmitters
Nonincendive parameters
Installation Instructions27
Page 28
3500 transmittersInstallation Manual
November 201920001969
53500 transmitters
5.13500 core processor installations
List of drawings
InstallationDrawing
3500 with core processor and CMF, F, or T
sensors
3500 with core processor and CMF300A sensorEB-3002933, Revision F
3500 with core processor and CMF400 sensor
with booster amplifier
3500 with core processor and D600 sensorEB-1005073, Revision B
3500 with core processor and D or DL sensorsEB-3300553, Revision D
3500 with core processor and DT sensorEB-3300554, Revision C
EB-3300529, Revision D
EB-3005807, Revision C
28Micro Motion UL-D-IS 9-Wire
Page 29
Installation Manual3500 transmitters
20001969November 2019
5.1.13500 with core processor and CMF, F, or T sensors
This drawing does not apply to the CMF300A sensor or to the CMF400 sensor with booster
amplifier.
Installation Instructions29
Page 30
3500 transmittersInstallation Manual
November 201920001969
5.1.23500 with core processor and CMF300A sensor
30Micro Motion UL-D-IS 9-Wire
Page 31
Installation Manual3500 transmitters
20001969November 2019
5.1.33500 with core processor and CMF400 sensor with
booster amplifier
Installation Instructions31
Page 32
3500 transmittersInstallation Manual
November 201920001969
5.1.43500 with core processor and D600 sensor
32Micro Motion UL-D-IS 9-Wire
Page 33
Installation Manual3500 transmitters
20001969November 2019
5.1.53500 with core processor and D or DL sensors
This drawing does not apply to D600 or DT sensors.
Installation Instructions33
Page 34
3500 transmittersInstallation Manual
November 201920001969
5.1.63500 with core processor and DT sensor
34Micro Motion UL-D-IS 9-Wire
Page 35
Installation Manual3500 transmitters
20001969November 2019
5.23500 remote core processor installations
List of drawings
InstallationDrawing
3500 with remote core processor and CMF, D,
DL, F, or T sensors
3500 with remote core processor and CMF300A
sensor
3500 with remote core processor and CMF400
sensor with booster amplifier
3500 with remote core processor and D600
sensor
3500 with remote core processor and DT sensor EB-20000240, Revision B
EB-20000234, Revision BA
EB-20000237, Revision C
EB-20000228, Revision B
EB-20000231, Revision B
Installation Instructions35
Page 36
3500 transmittersInstallation Manual
November 201920001969
5.2.13500 with remote core processor and CMF, D, DL, F, or T
sensors
This drawing does not apply to the D600, DT, CMF300A, or CMF400 with booster amplifier
sensors.
36Micro Motion UL-D-IS 9-Wire
Page 37
Installation Manual3500 transmitters
20001969November 2019
5.2.23500 with remote core processor and CMF300A sensor
Installation Instructions37
Page 38
3500 transmittersInstallation Manual
November 201920001969
5.2.33500 with remote core processor and CMF400 sensor
with booster amplifier
38Micro Motion UL-D-IS 9-Wire
Page 39
Installation Manual3500 transmitters
20001969November 2019
5.2.43500 with remote core processor and D600 sensor
Installation Instructions39
Page 40
3500 transmittersInstallation Manual
November 201920001969
5.2.53500 with remote core processor and DT sensor
40Micro Motion UL-D-IS 9-Wire
Page 41
Installation Manual3500 transmitters
20001969November 2019
Installation Instructions41
Page 42
3700 transmittersInstallation Manual
November 201920001969
63700 transmitters
6.13700 core processor installations
List of drawings
InstallationDrawing
3700 with core processor and CMF, F, or T
sensors
3700 with core processor and D or DL sensorsEB-3300572, Revision D
3700 with core processor and D600 sensorEB-1005074, Revision B
3700 with core processor and DT sensorEB-3300574, Revision C
EB-3300564, Revision D
42Micro Motion UL-D-IS 9-Wire
Page 43
Installation Manual3700 transmitters
20001969November 2019
6.1.13700 with core processor and CMF, F, or T sensors
This drawing does not apply to the CMF300A sensor or to the CMF400 sensor with booster
amplifier.
Installation Instructions43
Page 44
3700 transmittersInstallation Manual
November 201920001969
6.1.23700 with core processor and D or DL sensors
This drawing does not apply to D600 or DT sensors.
44Micro Motion UL-D-IS 9-Wire
Page 45
Installation Manual3700 transmitters
20001969November 2019
6.1.33700 with core processor and D600 sensor
Installation Instructions45
Page 46
3700 transmittersInstallation Manual
November 201920001969
6.1.43700 with core processor and DT sensor
46Micro Motion UL-D-IS 9-Wire
Page 47
Installation Manual3700 transmitters
20001969November 2019
6.23700 remote core processor installations
List of drawings
InstallationDrawing
3700 with remote core processor and CMF, D,
DL, F, H, or T sensors
3700 with remote core processor and CMF300A
sensor
3700 with remote core processor and CMF400
sensor with booster amplifier
3700 with remote core processor and D600
sensor
3700 with remote core processor and DT sensor EB-20000214, Revision B
EB-20000208, Revision BA
EB-20000211, Revision C
EB-20000202, Revision B
EB-20000205, Revision B
Installation Instructions47
Page 48
3700 transmittersInstallation Manual
November 201920001969
6.2.13700 with remote core processor and CMF, D, DL, F, H,
or T sensors
This drawing does not apply to the D600, DT, CMF300A, or CMF400 with booster amplifier
sensors.
48Micro Motion UL-D-IS 9-Wire
Page 49
Installation Manual3700 transmitters
20001969November 2019
6.2.23700 with remote core processor and CMF300A sensor
Installation Instructions49
Page 50
3700 transmittersInstallation Manual
November 201920001969
6.2.33700 with remote core processor and CMF400 sensor
with booster amplifier
50Micro Motion UL-D-IS 9-Wire
Page 51
Installation Manual3700 transmitters
20001969November 2019
6.2.43700 with remote core processor and D600 sensor
Installation Instructions51
Page 52
3700 transmittersInstallation Manual
November 201920001969
6.2.53700 with remote core processor and DT sensor
52Micro Motion UL-D-IS 9-Wire
Page 53
Installation Manual3700 transmitters
20001969November 2019
Installation Instructions53
Page 54
9701 transmittersInstallation Manual
November 201920001969
79701 transmitters
List of drawings
InstallationDrawing
9701 with CMF or F sensorsEB-3100714, Revision K
9701 with CMF300A sensorEB-3003299, Revision C
9701 with CMF400 sensor with booster
amplifier
9701 with D or DL sensorsEB-3100715, Revision H
EB-3005805, Revision C
54Micro Motion UL-D-IS 9-Wire
Page 55
Installation Manual9701 transmitters
20001969November 2019
7.19701 with CMF or F sensors
This drawing does not apply to the CMF300A sensor or to the CMF400 sensor with booster
amplifier.
Installation Instructions55
Page 56
9701 transmittersInstallation Manual
November 201920001969
7.29701 with CMF300A sensor
56Micro Motion UL-D-IS 9-Wire
Page 57
Installation Manual9701 transmitters
20001969November 2019
7.39701 with CMF400 sensor with booster
amplifier
Installation Instructions57
Page 58
9701 transmittersInstallation Manual
November 201920001969
7.49701 with D or DL sensors
This drawing does not apply to D600 or DT sensors.
58Micro Motion UL-D-IS 9-Wire
Page 59
Installation Manual9701 transmitters
20001969November 2019
Installation Instructions59
Page 60
9739 transmittersInstallation Manual
November 201920001969
89739 transmitters
8.19739 field mount installations
List of drawings
InstallationDrawing
9739 field mount groundingEB-3001547 Rev E
9739 field mount with CMF or F sensorsEB-3002205, Revision GA
9739 field mount with CMF300 sensorEB-3002929, Revision F
9739 field mount with CMF400 sensor and a
booster amplifier
9739 field mount with D or DL sensorsEB-3002206, Revision GA
9739 field mount with D600 sensorEB-1005069, Revision B
9739 field mount with DT sensorEB-3002208, Revision EA
EB-3005802, Revision C
60Micro Motion UL-D-IS 9-Wire
Page 61
Installation Manual9739 transmitters
20001969November 2019
8.1.19739 field mount grounding
Installation Instructions61
Page 62
9739 transmittersInstallation Manual
November 201920001969
8.1.29739 field mount with CMF or F sensors
This drawing does not apply to the CMF300A sensor or to the CMF400 sensor with booster
amplifier.
62Micro Motion UL-D-IS 9-Wire
Page 63
Installation Manual9739 transmitters
20001969November 2019
8.1.39739 field mount with CMF300 sensor
Installation Instructions63
Page 64
9739 transmittersInstallation Manual
November 201920001969
8.1.49739 field mount with CMF400 sensor and a booster
amplifier
64Micro Motion UL-D-IS 9-Wire
Page 65
Installation Manual9739 transmitters
20001969November 2019
8.1.59739 field mount with D or DL sensors
This drawing does not apply to D600 or DT sensors.
Installation Instructions65
Page 66
9739 transmittersInstallation Manual
November 201920001969
8.1.69739 field mount with D600 sensor
66Micro Motion UL-D-IS 9-Wire
Page 67
Installation Manual9739 transmitters
20001969November 2019
8.1.79739 field mount with DT sensor
Installation Instructions67
Page 68
9739 transmittersInstallation Manual
November 201920001969
8.29739 rack mount installations
List of drawings
InstallationDrawing
9739 rack mount groundingEW-3002535, Revision A
9739 rack mount with CMF or F sensorsEB-3002519, Revision E
9739 rack mount with CMF300A sensorEB-3002931, Revision E
9739 rack mount with CMF400A sensor and a
booster amplifier
9739 rack mount with D or DL sensorsEB-3002520, Revision E
9739 rack mount with D600 sensorEB-1005070, Revision B
9739 rack mount with DT sensorEB-3005606, Revision B
EB-3005803, Revision C
68Micro Motion UL-D-IS 9-Wire
Page 69
Installation Manual9739 transmitters
20001969November 2019
8.2.19739 rack mount grounding
Installation Instructions69
Page 70
9739 transmittersInstallation Manual
November 201920001969
8.2.29739 rack mount with CMF or F sensors
This drawing does not apply to the CMF300A sensor or to the CMF400 sensor with booster
amplifier.
70Micro Motion UL-D-IS 9-Wire
Page 71
Installation Manual9739 transmitters
20001969November 2019
8.2.39739 rack mount with CMF300A sensor
Installation Instructions71
Page 72
9739 transmittersInstallation Manual
November 201920001969
8.2.49739 rack mount with CMF400A sensor and a booster
amplifier
72Micro Motion UL-D-IS 9-Wire
Page 73
Installation Manual9739 transmitters
20001969November 2019
8.2.59739 rack mount with D or DL sensors
This drawing does not apply to D600 or DT sensors.
Installation Instructions73
Page 74
9739 transmittersInstallation Manual
November 201920001969
8.2.69739 rack mount with D600 sensor
74Micro Motion UL-D-IS 9-Wire
Page 75
Installation Manual9739 transmitters
20001969November 2019
8.2.79739 rack mount with DT sensor
Installation Instructions75
Page 76
Booster amplifiersInstallation Manual
November 201920001969
9Booster amplifiers
9.1Booster amplifiers with CMF400 sensors
List of drawings
InstallationDrawing
Booster amplifier with junction box and CMF400
sensor
EB-3005811, Revision D
76Micro Motion UL-D-IS 9-Wire
Page 77
Installation ManualBooster amplifiers
20001969November 2019
9.1.1Booster amplifier with junction box and CMF400 sensor
Installation Instructions77
Page 78
Booster amplifiersInstallation Manual
November 201920001969
9.2Booster amplifiers with D600 sensors
List of drawings
InstallationDrawing
Booster amplifier with junction box and D600
sensor
EB-1005077, Revision C
78Micro Motion UL-D-IS 9-Wire
Page 79
Installation ManualBooster amplifiers
20001969November 2019
9.2.1Booster amplifier with junction box and D600 sensor
Installation Instructions79
Page 80
*20001969*
20001969
Rev. BB
2019
Micro Motion Inc. USA
Worldwide Headquarters
7070 Winchester Circle
Boulder, Colorado USA 80301
T +1 303-527-5200
T +1 800-522-6277
F +1 303-530-8459
www.emerson.com
Micro Motion Asia
Emerson Automation Solutions
1 Pandan Crescent
Singapore 128461
Republic of Singapore
T +65 6363-7766
F +65 6770-8003
The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE,
ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of their respective owners.
Micro Motion Europe
Emerson Automation Solutions
Neonstraat 1
6718 WX Ede
The Netherlands
T +31 (0) 318 495 555
T +31 (0) 70 413 6666
F +31 (0) 318 495 556
www.emerson.com/nl-nl
Micro Motion United Kingdom
Emerson Automation Solutions
Emerson Process Management Limited
Horsfield Way
Bredbury Industrial Estate
Stockport SK6 2SU U.K.
T +44 0870 240 1978
F +44 0800 966 181
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.