Micro Motion™ T-Series Coriolis Flow and
Density Sensors
February 2020
Page 2
Safety messages
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration
of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available
on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion
Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States800-522-6277U.K.0870 240 1978Australia800 158 727
2.2 Best practices................................................................................................................................... 8
2.3 Temperature limits...........................................................................................................................8
2.4 Recommendations for hygienic and self-draining applications......................................................... 9
6.1 Purge the sensor case .................................................................................................................... 25
Installation Manualiii
Page 4
ContentsInstallation Manual
February 202020002172
ivMicro Motion T-Series
Page 5
Installation ManualBefore you begin
20002172February 2020
1Before you begin
1.1About this document
This document provides information on planning, mounting, wiring, and grounding the TSeries sensor.
The information in this document assumes that users understand basic transmitter and
sensor installation, configuration, and maintenance concepts and procedures.
1.2Hazard messages
This document uses the following criteria for hazard messages based on ANSI standards
Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a
situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration
of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access to protect users' assets. This is true for all
systems used within the facility.
1.3Related documentation
You can find all product documentation on the product documentation DVD shipped with
the product or at www.emerson.com.
See any of the following documents for more information:
• The hazardous area approvals documentation shipped with the sensor or available at
www.emerson.com/flowmeasurement.
• Micro Motion T-Series Flow and Density Meters Product Data Sheet
Installation Manual5
Page 6
Before you beginInstallation Manual
February 202020002172
• Micro Motion 9-Wire Flowmeter Cable Preparation and Installation Guide
• The transmitter installation and configuration and use guides
6Micro Motion T-Series
Page 7
Installation Manual
20002172February 2020
Planning
2Planning
2.1Installation checklist
□ Make sure that the hazardous area specified on the approval tag is suitable for the
environment in which the meter will be installed.
WARNING
Failure to abide by approvals can cause an explosion resulting in injury or death.
□ Verify that the local ambient and process temperatures are within the limits of the
meter.
□ If your sensor has an integral transmitter, no wiring is required between the sensor and
transmitter. Follow the wiring instructions in the transmitter installation manual for
signal and power wiring.
□ If your transmitter has remote-mounted electronics, follow the instructions in this
manual for wiring between the sensor and the transmitter, and then follow the
instructions in the transmitter installation manual for power and signal wiring.
Table 2-1: Maximum cable lengths
Cable typeTo transmitterMaximum length
Micro Motion
9-wire
Micro Motion
4-wire
Table 2-2: Maximum lengths for user-supplied 4-wire cable
Wire functionWire sizeMaximum length
Power (VDC)22 AWG (0.326 mm²)300 ft (91 m)
Signal (RS-485)22 AWG (0.326 mm²) or larger 1,000 ft (305 m)
9739 MVD and 5700
transmitter
All other MVD transmitters60 ft (18 m)
All 4-wire MVD transmitters1,000 ft (305 m) without Ex-approval
20 AWG (0.518 mm²)500 ft (152 m)
18 AWG (0.823 mm²)1,000 ft (305 m)
1,000 ft (305 m)
500 ft (152 m) with IIC-rated sensors
1,000 ft (305 m) with IIB-rated sensors
□ For optimal performance, install the sensor in the preferred orientation. The sensor will
work in any orientation as long as the flow tubes remain full of process fluid.
□ Install the meter so that the flow direction arrow on the sensor case matches the actual
forward flow of the process. (Flow direction is also software-selectable.)
Installation Manual7
Page 8
PlanningInstallation Manual
February 202020002172
2.2Best practices
The following information can help you get the most from your sensor.
• There are no pipe run requirements for Micro Motion sensors. Straight runs of pipe
upstream or downstream are unnecessary.
• If the sensor is installed in a vertical pipeline, liquids and slurries should flow upward
through the sensor. Gases should flow downward.
• Keep the sensor tubes full of process fluid.
• For halting flow through the sensor with a single valve, install the valve downstream
from the sensor.
• Minimize bending and torsional stress on the meter. Do not use the meter to align
misaligned piping.
• The sensor does not require external supports. The flanges will support the sensor in
any orientation.
2.3Temperature limits
Sensors can be used in the process and ambient temperature ranges shown in the
temperature limit graphs. For the purposes of selecting electronics options, temperature
limit graphs should be used only as a general guide. If your process conditions are close to
the gray area, consult with your Micro Motion representative.
Note
• In all cases, the electronics cannot be operated where the ambient temperature is
below -40 °F (-40.0 °C) or above 140 °F (60.0 °C). If a sensor is to be used where the
ambient temperature is outside of the range permissible for the electronics, the
electronics must be remotely located where the ambient temperature is within the
permissible range, as indicated by the shaded areas of the temperature limit graphs.
• Temperature limits may be further restricted by hazardous area approvals. Refer to the
hazardous area approvals documentation shipped with the sensor or available at
www.emerson.com/flowmeasurement.
• The extended-mount electronics option allows the sensor case to be insulated without
covering the transmitter, core processor, or junction box, but does not affect
temperature ratings. When insulating the sensor case at elevated process
temperatures above 140 °F (60.0 °C), ensure electronics are not enclosed in insulation
as this may lead to electronics failure.
8Micro Motion T-Series
Page 9
122 (50)
D
A
B
C
125.5
(52)
140 (60)
-40 (-40)
-60 (–51)
-20 (-29)
20 (7)
60 (16)
100 (38)
-60 (-51)
300 (149)
-20 (-29)
20 (7)
60 (16)
100 (38)
140 (60)
200 (93)
280 (138)
240 (116)
320 (160)
Installation Manual
Planning
20002172February 2020
Ambient and process temperature limits for all models
A. Ambient temperature of core processor or transmitter in °F (°C)
B. Maximum process temperature in °F (°C)
C. Mount transmitter remotely and use a junction box
D. Temperature is below -40 °F (-40 °C); mount transmitter remotely and use a junction box
2.4Recommendations for hygienic and selfdraining applications
For optimal cleanability and drainability:
• If possible, install the sensor in a vertical pipeline with the process fluid flowing upward
through the sensor.
• The minimum angle of inclination of the sensor depends on the process fitting. See
Figure 2-1 and Table 2-3.
• For clean-in-place (CIP) applications, Micro Motion recommends using the generally-
accepted flow velocity of at least 1.5 m/s for cleaning the sensor.
• If the process piping must be larger than the sensor, eccentric reducers may be used to
ensure full drainability. In this case, the process end connections for the piping and
sensor must be the same size. See Figure 2-2.
Note
As part of the cleaning process, you can purge skid-based systems with nitrogen at the
end of the cleaning cycle. When using eccentric reducers, it is possible to trap gas in
the section of process piping adjacent to the reducer. Sensor performance can be
impacted by intermittent flow of the captured gas in a liquid fluid stream.
Installation Manual9
Page 10
$
%
PlanningInstallation Manual
February 202020002172
• The gap between the electronics housing and sensor body should be inspected
periodically. Manually clean this gap when necessary.
• Tri-Clamp® and DIN 11851 style process connections require special gaskets to comply
with EHEDG requirements for hygienic design.
Figure 2-1: Sensor inclination
A. Angle of inclination
B. Direction of gravity
Table 2-3: Minimum angle of inclination
Model
T025F, T025T6210.5 in (13 mm) Tri-Clamp compatible sanitary
T050F, T050T6210.5 in (13 mm) Tri-Clamp compatible sanitary
T075F, T075T6220.75 in (19.0 mm) Tri-Clamp compatible sanitary
Fitting
code
670DN10 DIN 11851 sanitary coupling47°
671DN15 DIN 11851 sanitary coupling47°
676DN15 DIN 11864-1A sanitary coupling47°
671DN15 DIN 11851 sanitary coupling47°
676DN15 DIN 11864-1A sanitary coupling47°
6231 in (25 mm) Tri-Clamp compatible sanitary clamp47°
662DN25 ISO 2853 (IDF) sanitary coupling47°
DescriptionMin. angle
clamp
clamp
clamp
47°
0°
0°
672DN25 DIN 11851 sanitary coupling47°
677DN25 DIN 11864-1A sanitary coupling47°
692DN25 SMS 1145 sanitary coupling32°
T100F, T100T6231 in (25 mm) Tri-Clamp compatible sanitary clamp0°
10Micro Motion T-Series
Page 11
B
C
A
Installation ManualPlanning
20002172February 2020
Table 2-3: Minimum angle of inclination (continued)
Model
Fitting
code
DescriptionMin. angle
6241.5 in (38 mm) Tri-Clamp compatible sanitary
clamp
672DN25 DIN 11851 sanitary coupling0°
677DN25 DIN 11864-1A sanitary coupling0°
T150F, T150T6241.5 in (38 mm) Tri-Clamp compatible sanitary
clamp
6252 in (51 mm) Tri-Clamp compatible sanitary clamp46°
663DN51 ISO 2853 (IDF) sanitary coupling47°
673DN40 DIN 11851 sanitary coupling0°
674DN50 DIN 11851 sanitary coupling47°
678DN50 DIN 11864-1A sanitary coupling47°
693DN51 SMS 1145 sanitary coupling32°
Figure 2-2: Eccentric reducer
46°
0°
A. Eccentric reducer
B. Process end connection is the same size as the sensor connection
C. Sensor case
Installation Manual11
Page 12
PlanningInstallation Manual
February 202020002172
12Micro Motion T-Series
Page 13
Installation Manual
20002172February 2020
Mounting
3Mounting
3.1Mount the sensor
Use common practices to minimize torque and bending load on process connections.
NOTICE
• Lifting the sensor by the electronics or purge connections can damage the device.
• To reduce the risk of collecting liquid in the electronics housing, do not orient
transmitters or sensor junction boxes with their conduit openings pointing upward.
Procedure
Mount the sensor.
Notes
• Do not use the sensor to support the piping.
• The sensor does not require external supports. The flanges will support the sensor in
any orientation.
3.2Attach extended electronics
If your installation has a sensor with extended electronics, you will need to install the
extender onto the sensor case.
Extended core processors are matched at the factory to specific sensors. Keep each core
processor together with the sensor with which it was shipped.
Installation Manual13
Page 14
G
H
E
D
C
A
B
F
Mounting
Installation Manual
February 202020002172
NOTICE
Keep the extender and feedthrough clean and dry. Moisture or debris in the extender or
feedthrough can damage electronics and result in measurement error or flowmeter
failure.
Procedure
1. Remove and recycle the plastic cap from the feedthrough on the sensor.
Figure 3-1: Feedthrough and extender components
A. Transmitter or core processor
B. Extender
C. O-ring
D. Feedthrough
E. Clamping ring
F. Clamping screw
G. Plastic plug
H. Plastic cap
2. Loosen the clamping screw and remove the clamping ring. Leave the O-ring in place
on the feedthrough.
3. Remove and recycle the plastic plug from the extender.
4. Fit the extender onto the feedthrough by carefully aligning the notches on the
bottom of the extender with the notches on the feedthrough.
5. Close the clamping ring and tighten the clamping screw to 13 in lbf (1.47 N m) to
18 in lbf (2.03 N m).
14Micro Motion T-Series
Page 15
Installation ManualMounting
20002172February 2020
3.3Rotate junction box or 800 core processor
(optional)
An integrally mounted junction box or 800 core processor can be rotated to one of eight
possible positions in 45 degree increments.
Figure 3-2: Parts for rotating the junction box or 800 core processor on the sensor
A
B
D
C
E
A. Housing
B. Clamping ring
C. Clamping ring screw
D. Feedthrough
E. Alignment notches
Note
The 800 core processor is shown in this figure. The junction box has a somewhat different
appearance.
Procedure
1. Loosen the clamping ring screw and remove the clamping ring.
2. Gently separate the housing from the feedthrough, but only until there is sufficient
clearance from the alignment notches to rotate the housing.
3. Rotate the housing to the desired position and in line with the alignment notches.
4. Seat the housing onto the feedthrough.
5. Replace the clamping ring and tighten the clamping ring screw.
Installation Manual15
Page 16
MountingInstallation Manual
February 202020002172
16Micro Motion T-Series
Page 17
Installation ManualTransmitter power and I/O wiring
20002172February 2020
4Transmitter power and I/O wiring
4.1Options for wiring
The wiring procedure you follow depends on which electronics option you have.
Table 4-1: Wiring procedures by electronics option
Electronics optionWiring procedure
Integral transmitterThe transmitter is already connected to the sensor. No wiring is
required between sensor and transmitter. See the transmitter
installation manual for wiring the power and signal cable to the
transmitter.
MVD™ Direct Connect
™
There is no transmitter to wire. See the Micro Motion MVD DirectConnect Meters manual for wiring the power and signal cable
between the sensor and the direct host.
Integral core processor with
remote transmitter
Remote core processor
attached to transmitter
Remote core processor
separate from transmitter –
double-hop
WARNING
The core processor is already connected to the sensor. Connect a
4-wire cable between the core processor and transmitter. Refer
to Connect 4-wire cable.
Connect a 9-wire cable between the sensor and the transmitter/
core processor. Refer to Connect the 9-wire cable , as well as the
Micro Motion Micro Motion 9-Wire Flowmeter Cable Preparationand Installation Guide.
• Connect a 4-wire cable between the core processor and
transmitter. Refer to Connect 4-wire cable.
• Connect a 9-wire cable between the sensor and the core
processor. Refer to Connect the 9-wire cable , as well as the
Micro Motion Micro Motion 9-Wire Flowmeter Cable Preparation
and Installation Guide
Make sure the hazardous area specified on the sensor approval tag is suitable for the
environment in which the sensor will be installed. Failure to comply with the
requirements for intrinsic safety in a hazardous area could result in an explosion
resulting in injury or death.
NOTICE
Fully close and tighten all housing covers and conduit openings. Improperly sealed
housings can expose electronics to moisture, which can cause measurement error or
flowmeter failure. Inspect and grease all gaskets and O-rings.
Installation Manual17
Page 18
Transmitter power and I/O wiringInstallation Manual
February 202020002172
4.2Connect 4-wire cable
4.2.14-wire cable types and usage
Micro Motion offers two types of 4-wire cable: shielded and armored. Both types contain
shield drain wires.
The cable supplied by Micro Motion consists of one pair of red and black 18 AWG
(0.823 mm²) wires for the VDC connection, and one pair of white and green 22 AWG
(0.326 mm²) wires for the RS-485 connection.
User-supplied cable must meet the following requirements:
• Twisted pair construction.
• Applicable hazardous area requirements, if the core processor is installed in a
hazardous area.
• Wire gauge appropriate for the cable length between the core processor and the
transmitter, or the host.
Wire gaugeMaximum cable length
VDC 22 AWG (0.326 mm²)300 ft (91 m)
VDC 20 AWG (0.518 mm²)500 ft (152 m)
VDC 18 AWG (0.823 mm²)1,000 ft (305 m)
RS-485 22 AWG (0.326 mm²) or larger1,000 ft (305 m)
4.2.2Prepare a cable with a metal conduit
Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Run the conduit to the sensor.
3. Pull the cable through the conduit.
4. Cut the drain wires and let them float at both ends of the conduit.
4.2.3
Prepare a cable with user-supplied cable glands
Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Pass the wires through the gland nut and gland body.
18Micro Motion T-Series
Page 19
Installation ManualTransmitter power and I/O wiring
20002172February 2020
A. Gland body
B. Gland nut
3. Terminate the RS-485 shield and drain wires to the housing internal grounding
screw.
4. Assemble the gland according to vendor instructions.
4.2.4Prepare a cable with Micro Motion-supplied cable glands
Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Pass the wires through the gland nut and clamping insert.
A. Gland nut
B. Clamping insert
3. Strip the cable jacket.
Option
NPT gland typeStrip 4.5 in (114 mm)
M20 gland typeStrip 4.25 in (108 mm)
4. Remove the clear wrap and filler material.
5. Strip most of the shielding.
Option
NPT gland typeStrip all but 0.75 in (19 mm)
M20 gland typeStrip all but 0.5 in (13 mm)
Description
Description
Installation Manual19
Page 20
Transmitter power and I/O wiringInstallation Manual
February 202020002172
6. Wrap the drain wires twice around the shield and cut off the excess drain wires.
A. Drain wires wrapped around shield
7. For foil (shielded cable) only:
Note
For braided (armored cable) skip this step and contine to the next step.
OptionDescription
NPT
gland
type
M20
gland
type
a. Slide the shielded heat shrink over the drain wires. Ensure that the
wires are completely covered.
b. Apply 250 °F (121.1 °C) heat to shrink the tubing. Do not burn the
cable.
c. Position the clamping insert so the interior end is flush with the
braid of the heat shrink.
A. Shielded heat shrink
B. After heat is applied
Trim 0.3 in (8 mm).
A. Trim
8. Assemble the gland by folding the shield or braid back over the clamping insert and
0.125 in (3 mm) past the O-ring.
A. Shield folded back
20Micro Motion T-Series
Page 21
A
B
D
C
AA
Installation ManualTransmitter power and I/O wiring
20002172February 2020
9. Install the gland body into the conduit opening on the core processor housing.
10. Insert the wires through the gland body and tighten the gland nut onto the gland
body.
A. Shield folded back
B. Gland body
4.2.5Connect the wires to the core processor terminals
After the 4-wire cable has been prepared and shielded (if required), connect the individual
wires of the 4-wire cable to the terminals on the core processor.
Procedure
1. Connect the wires to the core processor terminals.
• If you are connecting to a standard core processor, use the following image and
connections:
A. Terminal 1 (Power supply +): Red wire
B. Terminal 2 (Power supply -): Black wire
C. Terminal 3 (RS-485/A): White wire
D. Terminal 4 (RS-485/B): Green wire
• If you are connecting to an enhanced core processor, use the following image
and connections:
Installation Manual21
Page 22
D
A
B
C
Transmitter power and I/O wiringInstallation Manual
February 202020002172
A. Terminal 1 (Power supply +): Red wire
B. Terminal 2 (Power supply -): Black wire
C. Terminal 3 (RS-485/A): White wire
D. Terminal 4 (RS-485/B): Green wire
2. Reinstall the core processor cover.
3. Torque the cover screws to:
• For aluminum housing: 10 in lbf (1.13 N m) to 13 in lbf (1.47 N m)
• For stainless steel housing: minimum 19 in lbf (2.15 N m)
If properly seated, there will be no gap between cover and base.
4. Connect the wires to the transmitter terminals using the transmitter installation
manual.
4.3Connect the 9-wire cable
Procedure
1. Prepare and install the cable according to the instructions in the Micro Motion 9-Wire
Flowmeter Cable Preparation and Installation Guide.
2. Insert the stripped ends of the individual wires into the terminal blocks of the
junction box. Ensure that no bare wires remain exposed.
3. Match the wires color for color. For wiring at the transmitter or remote core
processor, refer to the transmitter documentation.
4. Tighten the screws to hold the wires in place.
5. Ensure integrity of gaskets, then tightly close and seal the junction box cover and all
housing covers.
6. Refer to the transmitter installation manual for signal and power wiring
instructions.
22Micro Motion T-Series
Page 23
Installation ManualGrounding
20002172February 2020
5Grounding
The meter must be grounded according to the standards that are applicable at the site.
The customer is responsible for knowing and complying with all applicable standards.
Prerequisites
Use the following guides for grounding practices:
• In Europe, IEC 60079-14 is applicable to most installations, in particular sections
16.2.2.3 and 16.2.2.4.
• In the U.S.A. and Canada, ISA 12.06.01 Part 1 provides examples with associated
applications and requirements.
If no external standards are applicable, follow these guidelines to ground the sensor:
• Use copper wire, 14 AWG (2.08 mm²) or larger wire size.
• Keep all ground leads as short as possible, less than 1 Ω impedance.
• Connect ground leads directly to earth, or follow plant standards.
NOTICE
Ground the flowmeter to earth, or follow ground network requirements for the facility.
Improper grounding can cause measurement error.
Procedure
• Check the joints in the pipeline.
• If the joints in the pipeline are ground-bonded, the sensor is automatically
grounded and no further action is necessary (unless required by local code).
• If the joints in the pipeline are not grounded, connect a ground wire to the
grounding screw located on the sensor electronics.
Tip
The sensor electronics may be a transmitter, core processor, or junction box. The
grounding screw may be internal or external.
Installation Manual23
Page 24
GroundingInstallation Manual
February 202020002172
24Micro Motion T-Series
Page 25
Installation ManualSupplementary information
20002172February 2020
6Supplementary information
6.1Purge the sensor case
Prerequisites
Make sure the following are available before beginning the purge procedure:
• Teflon™ tape
• Argon or nitrogen gas sufficient to purge the sensor case
If the sensor has purge fittings, they should remain sealed at all times. The sensor is
purged of all oxygen and sealed at the factory. If the purge plugs are never removed, it is
not necessary to purge or re-seal the sensor. For more information, contact customer
support.
Whenever a purge plug is removed from the sensor case, you must purge the case again.
Procedure
1. Shut down the process, or set control devices for manual operation.
NOTICE
Before performing the case purging procedure, shut down the process or set the
control devices for manual operation. Performing the purge procedure while the
flowmeter is operating could affect measurement accuracy, resulting in inaccurate
flow signals.
2. Remove both purge plugs from the sensor case. If purge lines are being used, open
the valve in the purge lines.
WARNING
• If a rupture disk has been installed on the purge fitting, stay clear of the
rupture disk pressure relief area. High-pressure fluid escaping from the sensor
can cause severe injury or death. Orient the sensor so that personnel and
equipment will not be exposed to any discharge along the pressure relief path.
• Take all necessary precautions when removing purge plugs. Removing a purge
plug compromises the secondary containment of the sensor and could expose
the user to process fluid.
• Improper pressurization of the sensor case could result in injury.
NOTICE
If a rupture disk has been installed on the purge fitting, use thread protectors when
removing the purge fitting so as not to damage the disk membrane surrounding
the rupture disk.
3. Prepare the purge plugs for reinstallation by wrapping them with 2–3 turns of
Teflon tape.
Installation Manual25
Page 26
Supplementary informationInstallation Manual
February 202020002172
4. Connect the supply of nitrogen or argon gas to the inlet purge connection or open
inlet purge line. Leave the outlet connection open.
NOTICE
• Exercise caution to avoid introducing dirt, moisture, rust, or other contaminants
into the sensor case.
• If the purge gas is heavier than air (such as argon), locate the inlet lower than the
outlet, so that the purge gas will displace air from bottom to top.
• If the purge gas is lighter than air (such as nitrogen), locate the inlet higher than
the outlet, so that the purge gas will displace air from top to bottom.
5. Make sure that there is a tight seal between the inlet connection and sensor case, so
that air cannot be drawn by suction into the case or purge line during the purging
process.
6. Run purge gas through the sensor.
The purge time is the amount of time required for full exchange of atmosphere to
inert gas. The larger the line size, the greater amount of time is required to purge
the case. If purge lines are being used, increase the purge time to fill the additional
volume of the purge line.
Important
Keep the purge gas pressure below 7.25 psi (0.5 bar).
Table 6-1: Purge time
Sensor modelPurge rateTime, in minutes
T02520 ft3/h (566.3 l/h)1
T05020 ft3/h (566.3 l/h)1
T07520 ft3/h (566.3 l/h)3
T10020 ft3/h (566.3 l/h)5
T15020 ft3/h (566.3 l/h)10
7. At the appropriate time, shut off the gas supply, then immediately seal the purge
outlet and inlet connections with the purge plugs.
Avoid pressurizing the sensor case. If pressure inside the case elevates above
atmospheric pressure during operation, the flowmeter density calibration will be
inaccurate.
8. Make sure that the purge fitting seals are tight so that air cannot be drawn by
suction into the sensor case.
26Micro Motion T-Series
Page 27
Installation Manual
20002172February 2020
Installation Manual27
Page 28
*20002172*
20002172
Rev. BC
2020
Micro Motion Inc. USA
Worldwide Headquarters
7070 Winchester Circle
Boulder, Colorado USA 80301
T +1 303-527-5200
T +1 800-522-6277
F +1 303-530-8459
www.emerson.com
Micro Motion Asia
Emerson Automation Solutions
1 Pandan Crescent
Singapore 128461
Republic of Singapore
T +65 6363-7766
F +65 6770-8003
The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE,
ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of their respective owners.
Micro Motion Europe
Emerson Automation Solutions
Neonstraat 1
6718 WX Ede
The Netherlands
T +31 (0) 318 495 555
T +31 (0) 70 413 6666
F +31 (0) 318 495 556
www.emerson.com/nl-nl
Micro Motion United Kingdom
Emerson Automation Solutions
Emerson Process Management Limited
Horsfield Way
Bredbury Industrial Estate
Stockport SK6 2SU U.K.
T +44 0870 240 1978
F +44 0800 966 181
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.