Micro Motion RFT9739 Field-Mount Transmitter for Commercial Trade Configuration Manual

Configuring the RFT9739 Field-Mount Transmitter for Commercial Trade
Introduction
Securing the transmitter configuration
These instructions explain how to configure a Version 3 field-mount RFT9739 transmitter for use in custody transfer and other commercial trade applications.
For commercial trade applications, the transmitter has security switches and an optional lockout clamp.
• Security switches enable the user to write-protect all configuration and calibration parameters and/or disable flowmeter zeroing and resetting of totalizers.
• The lockout clamp prevents access to the transmitter's wiring terminals and electronics module.
Before securing the transmitter configuration or installing the lockout clamp, make sure the transmitter has been properly installed and the flowmeter has been zeroed, according to the appropriate sections in the instruction manual that is shipped with the transmitter.
A Version 3 field-mount RFT9739 has three security switches.
• To access switches, unscre w the cov er fro m the base of th e transm itter , then unlatch the hinged cover of the electronics module.
Figure 1 illustrates the switches, which are labeled SECURE 1, SECURE 2, and SECURE 3.
Figure 1. Switches
Switches 1 through 10 at left are shown in the OFF position.
Security modes
Table 1. Security modes
Switches 1, 2, and 3 enable the user to disable flowmeter zeroing, disable resetting of totalizers, and write-protect all configuration and calibration parameters.
Switch settings enable any of eight possible security modes. Different modes determine which functions are disabled and whether configuration and calibration parameters are write-protected. The following functions can be disabled:
• Flowmeter zeroing using digital communications
• Flowmeter zeroing using the zero button and, if the transmitter has a display, the Scroll and Reset knobs
• Totalizer reset, with flow, using digital communications
• Totalizer reset, with flow, using the Scroll and Reset knobs, if the transmitter has a display
• Totalizer control, with zero flow, using digital communications
• Totalizer control, with zero flow, using the Scroll and Reset knobs, if the transmitter has a display
Table 1 lists the parameters that are write-protected and functions that are disabled for each security mode. Security modes 1 through 7 are entered immediately when switches 1 through 3 are set.
For information about security mode 8, see page 3.
Switch settings
Switch 1 Switch 2 Switch 3
Function/ parameter
Flowmeter zeroing
Totalize r control, no flow
Totalize r control, with flow
Configuration and calibration parameters
(1)
Changing the settings of switches 1, 2, and 3 does not immediately implement security m ode 8. For more information about
security mode 8, see page 3.
Performed with
Zero but t on or Reset knob
HART or Modbus
Scroll and Reset knobs
HART or Modbus
Scroll and Reset knobs
HART or Modbus
Mode
1
OFF OFF OFF
Mode
1
Mode
2
OFF OFF
ON
Mode
2
Disabled Disabled Disabled Disabled Disabled Disabled Disabled
Disabled Disabled Disabled Disabled
Disabled Disabled Disabled Disabled Disabled Disabled Disabled
Mode
3
OFF
ON
OFF
Mode
3
Disabled Disabled Disabled Disabled
Disabled Disabled Disabled
Disabled Disabled Disabled Disabled Disabled Disabled
Write-
protected
Mode
4
OFF
ON ON
Mode
4
Write-
protected
Mode
5
ON OFF OFF
Mode
5
Write-
protected
Mode
6
ON
OFF
ON
Mode
6
Write-
protected
Mode
7
ON ON
OFF
Mode
7
Write-
protected
protected
Mode
(1)
8
ON ON ON
Mode
8
Write-
2
Security mode 8
When transmitter security is set for mode 8, the transmitter meets security requirements for custody transfer described in National Institute of Standards and Technology (NIST) Handbook 44.
Once the transmitter is configured for security mode 8, the security mode cannot be changed unless a master reset is performed. A master reset causes all configuration parameters to return to their default values, and
requires complete characterization and reconfiguration
of the trans m i tt e r.
If the user attempts to enter a new security mode or change the transmitter configuration after entering security mode 8:
• Internal totalizers stop counting
• The frequency/pulse output goes to 0 Hz
• mA outputs go to 4 mA
• The optional display reads, "SECURITY BREACH; SENSOR OK"
• Custody transfer event registers record each change made to defined configuration and calibration parameters. (For a list of these parameters, see the instruction manual that is shipped with the transmitter.)
The security breach continues, and totalizers and outputs remain inactive, until the transmitter is reconfigured for security mode 8, or until a master reset has been performed. Custody transfer ev ent registers are not affected by a master reset. For information about event registers, or to perform a master reset, see the instruction manual that is shipped with the transmitter.
Milliamp output trim, milliamp output test, and frequency/pulse output test procedures cannot be performed after security mode 8 is entered.
Before entering security mode 8,
procedures, if necessary , as described in any of the following manuals or in AMS on-line help:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
perform milliamp trim and/or test
• Using Modbus Protocol with Micro Motion Transmitters
3
To enter security mode 8:
1. Note the position of switch 5.
2. Set switch 10 to the ON position. The diagnostic LED on the
transmitter electronics module flashes on 3 times and pauses, which indicates the transmitter is in the configuration mode.
3. Set switches 1, 2, and 3 to the ON position.
4. Set switches 4, 5, and 6 to the OFF position.
5. Locate the ZERO button on the transmitter electronics module.
6. Press and hold the ZERO button for five seconds. The diagnostic LED
will remain on for two to three seconds to indicate security mode 8 has been entered.
7. Reset switch 5 to the desired position (as noted in Step 1).
8. Reset switch 10 to the OFF (OPERATE) position. The diagnostic LED
flashes on once per second (25% on, 75% off), which indicates the transmitter is in the normal operating mode.
9. Leave switches 1, 2, and 3 in the ON position to remain in security
mode 8.
To verify the transmitter is in security mode 8:
• If the transmitter has a display, use the Scroll knob to scroll through process variable screens to event register screens. If event register screens appear, the transmitter is in security mode 8.
• If the transmitter does not have a display:
1. Configure the transmitter.
2. Wait until the diagnostic LED blinks ON once per second.
3. Move switch 1, 2, or 3 to the OFF position.
4. If the diagnostic LED blinks ON 4 times per second, the transmitter
is in security mode 8.
To make changes to configuration or calibration parameters once security mode 8 is entered:
1. Set switches 1, 2, and 3 to the OFF position.
2. Make changes through digital communication or, if the transmitter has
a display, with the Scroll and Reset knobs. Custody transfer event registers record changes made to defined configuration and calibration parameters. For more information about digital communications, see the following instruction manuals or AMS on-line help:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
3. Reset switches 1, 2, and 3 to the ON position.
To reenter security mode 8:
If security mode 8 has been established previously, and the security mode has been temporarily changed, it is not necessary to use the ZERO button to reenter security mode 8. In such a case, resetting switches 1, 2, and 3 to the ON position will reenter security mode 8 immediately.
If a master reset has been performed, it is necessary to use the ZERO button method to reenter security mode 8. See the procedure at the top of this page.
4
Lockout clamp installation procedure
The lockout clamp kit includes a clamp, a mounting screw, and a cap, as shown in Figure 2.
• For custody transfer applications in the United States and Europe, the clamp, mounting screw, and cap are required (see Figure 2).
• To avoid losing individual parts, install the mounting screw and lockout clamp, then make sure a weights and measures inspector immediately installs the cap and performs the inspection. Once installed, the cap can only be removed by the inspector.
Figure 2. Parts in lockout kit
Clamp
Mounting screw
Cap
To install the lockout clamp, refer to Figure 3, page 6, and follow these steps:
1. Make sure the transmitter cover is securely screwed onto the trans-
mitter base.
2. Insert the mounting screw through the largest hole in the clamp, so
the screw head fits into the recess in the clamp.
3. On the transmitter, find the threaded hole for the mounting screw. The
hole is located in the transmitter base, on the side opposite from the conduit openings.
4. Position the clamp so the groove in the clamp fits over the lip on the
cover of the transmitter and the mounting screw aligns with the base.
5. Using a 5/32-inch Allen wrench (4 mm hexagonal key wrench), screw
the mounting screw into the threaded hole in the transmitter base. The mounting screw is a 5 mm screw.
6. The weights and measures inspector must put the cap in place over
the screw head, so the holes in the cap align with the two small holes in the clamp. To complete the installation, the inspector runs a wire seal through the aligned holes in the clamp and cap, then secures the seal.
5
Figure 3. Installation diagram for lockout clamp
Transmitter
cover
Lip
Clamp
Mounting screw
Cap
Threaded hole
Transmitter base
Visit us on the Internet at www.micromotion.com
Micro Motion Europe
Groeneveldselaan 8 3903 AZ Veenendaal The Netherlands Tel+31 (0) 318 549 549 Fax+31 (0) 318 549 559
Micro Motion Inc. USA Worldwide Headquarters
7070 Winchester Circle Boulder, Colorado 80301 Tel(303) 530-8400
(800) 522-6277
Fax(303) 530-8459
©2000, Micro Motion, Inc.
All rights reserved P/N 3002320, Rev. B (3/00)
recycled paper
Micro Motion Asia
1 Pandan Crescent Singapore 128461 Republic of Singapore Tel(65) 777-8211 Fax(65) 770-8003
Micro Motion Japan
Shinagawa NF Bldg. 5F 1-2-5, Higashi Shinagawa Shinagawa-ku Tokyo 140-0002 Japan Tel(81) 3 5769-6803 Fax(81) 3 5769-6843
Loading...