Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are
available: the EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings
and Instructions. In addition the IECEx Installation Instructions for installations outside of the European Union and the CSA
Installation Instructions for installations in North America are available on the internet at www.emerson.com or through your local
Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com. For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion
Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States800-522-6277U.K. and Ireland0870 240 1978Australia800 158 727
B.3 Density determination...............................................................................................................44
Supplement3
Page 4
ContentsSupplement
January 2022MMI-20026578
4Micro Motion Multiphase Applications
Page 5
SupplementBefore you begin
MMI-20026578January 2022
1Before you begin
1.1About this application manual
This application manual explains how to configure the Production Volume Reconciliation
application (PVR), the Transient Bubble Remediation application (TBR), and the Transient
Mist Remediation application (TMR), using ProLink III.
These three applications are available for Micro Motion MVD™ Coriolis meters in an MVD
Direct Connect installation.
PVR, TMR, and TBR are also available for Micro Motion Model 1500, Model 1700,
Model 2500, and Model 2700 transmitters.
This application manual does not provide information on installation of any sensors or
transmitters, or on general configuration. This information can be found in the applicable
sensor installation manual, transmitter installation manual, or transmitter configuration
manual.
Related information
Additional documentation from Micro Motion
1.2ProLink III requirements
To use this manual, you must have ProLink III Professional v4.0 or later, and you must be
able to connect from ProLink III to the transmitter or core processor.
Supplement5
Page 6
Before you beginSupplement
January 2022MMI-20026578
1.3Ordering options
For 800 core processor direct connect installations, PVR, TBR, and TMR are available as
Engineering To Order (ETO) applications. PVR and TMR are available individually or in
combination with Smart Meter Verification.
PVR, TMR, and TBR features are now available in the standard product when ordered on
1500, 1700, and 2500 Transmitter Models. The ETO is not required on the 800 core
processor when used with a transmitter.
To order one of these applications, an ETO must be purchased for the core processor (see
Table 1-1). This ETO enables use of the application in an MVD™ Direct Connect installation.
Table 1-1: Core processor ETOs for PVR, TBR, and TMR
ApplicationDirect connect
core processor
PVREnhanced2216622701Mixture of oil and
TBREnhanced1338625699Liquid with gasLiquid flow rate and
Standard12806Not available.Liquid with gasLiquid flow rate and
TMREnhanced1892222706Gas with entrained
Individual
application
ETO numberProcess fluidDesired
Application
with
Smart
Meter
Verification
(SMV)
water
liquid (mist)
measurement
Net oil (dry oil at
reference conditions)
and net water flow
totals
totals
Gas flow rate and
totals
Restriction
Only one ETO can be installed in the transmitter or core processor at a time.
1.4Additional documentation from Micro Motion
Table 1-2: Additional documentation for PVR, TBR, and TMR installations
DocumentUse
Micro Motion® MVD™ Direct Connect Meters:
Installation Manual
Sensor installation manual for your sensorInstallation and wiring for the sensor
Configuration manual for your transmitterConfiguration, operation, maintenance, and
ProLink III User Manual
Modbus Interface Tool
6Micro Motion Multiphase Applications
Installation and wiring for the MVD Direct
Connect flowmeter
troubleshooting for features that are not related
to PVR, TBR, or TMR
Installation and use of ProLink III
Programming the Modbus host
Page 7
SupplementBefore you begin
MMI-20026578January 2022
1.5Terms and definitions
The terms used to describe Multiphase applications vary widely. This manual, and the PVR,
TBR, and TMR applications, use the terms defined here.
Terms used in PVR,
TBR, and TMR
at Reference
At Line
At Reference
density
At Line volume
At Reference
volume
Mixture
Water cut
Entrained,
entrainment
Remediation
Shrinkage
The process of calculating the value of a process variable at
reference temperature, starting from the value of the process
variable at line temperature (the measured value)
The density of the process fluid at line temperature
The density of the process fluid at reference temperature (60 °F)
that is equivalent to its density at line temperature
The volume of the process fluid at line temperature
The volume of the process fluid at reference temperature (60 °F)
that is equivalent to its volume at line temperature
The process fluid before separation, such as a combination of oil
and water, or gas, oil, and water
The volume fraction of water in the liquid mixture, in %
The presence of small amounts of gas in a liquid stream, or liquid
in a gas stream
An adjustment applied to a process variable during periods of
entrained gas or mist when a substitute density value has been
used for volume calculation (PVR and TBR) or the flow rate has
been increased or decreased to compensate for unmeasured flow
(TMR).
The change in liquid volume between the measurement point and
a stock tank due to lighter hydrocarbons evaporating. This is
caused by the stock tank being at a lower pressure, further below
the bubble point of the oil. The shrinkage factor is a user-input
factor, based on a PVT (pressure-volume-temperature) test of the
oil.
Shrinkage Meter
Factor
These terms can be combined in several ways to describe different process variables. The
following table provides several examples, but is not a complete list of possibilities.
Table 1-3: Examples of process variable names
Process variable nameDescription
Volume Total (unremediated)The total, by volume, of the mixture (oil/water/gas combination),
Volume Total (remediated)The total, by volume, of the oil/water minus the volume
Supplement7
Used just like the normal Meter Factor, when proving the meter
against liquid measurement at stock tank conditions.
as measured
attributable to gas
Page 8
Before you begin
January 2022MMI-20026578
Table 1-3: Examples of process variable names (continued)
Process variable nameDescription
Oil Total at LineThe total amount of oil measured since the last totalizer reset, at
line temperature, with no adjustment for temperature variation
Water Cut at ReferenceThe percentage of water in the oil, as if the measurement had
been taken at 60 °F
Supplement
1.6PVR, TBR, and TMR applications
PVR, TBR, and TMR are applications designed to provide more accurate process data in the
presence of multiple phases. For example, if bubbles are present in the process fluid, or the
process fluid is flashing, the volume measurements are often incorrect.
Production Volume Reconciliation (PVR)
• Provides oil and water volumes through density-based calculations for both line and
reference conditions
• Detects bubble entrainment or flashing in the sensor, and can correct volumes
accordingly
• Best for undersized three-phase separators that frequently have intermittent gas or
water contamination in the oil leg
• Offers a simple, low-cost solution for net oil and net water measurement for two-phase
separators
Transient Bubble Remediation (TBR)
• Used with single-component liquid streams that may experience intermittent low
levels of gas entrainment, that is, gas carryunder
• Enables accurate measurement of a single fluid during periods of entrained gas by
providing a substitute density value based on the immediately preceding process
density (standard configuration)
• Tracks total time of aerated flow to assist in diagnosing process issues that may cause
aeration
Transient Mist Remediation (TMR)
• Used with gas streams that may experience intermittent low levels of liquid
entrainment, i.e., liquid carry-over
• Allows gas measurement to continue during periods of entrained liquid (mist) by
providing a substitute flow rate value based on the immediately preceding process
flow rate
• Returns to reporting the measured flow rate when the mist interval is over, increased
or decreased by a maximum of 10%, until flow totals are appropriately adjusted for the
unmeasured flow
• Provides an indication of the amount of time that liquid was present in the stream —
identifying process improvements to reduce gas stream contamination
8Micro Motion Multiphase Applications
Page 9
SupplementBefore you begin
MMI-20026578January 2022
1.6.1Illustrations of PVR, TBR, and TMR installations
PVR, TBR, and TMR can be used with two-phase separators and three-phase separators.
Note
These illustrations do not show all possible combinations.
Figure 1-1: PVR, TBR, or TMR with two-phase separator
A. From wellhead
B. Separator
C. Gas leg
D. Oil/water leg
E. Coriolis sensor with PVR or TBR
F. Coriolis sensor with TMR
G. Modbus host (flow computer)
Supplement9
Page 10
Before you beginSupplement
January 2022MMI-20026578
Figure 1-2: PVR, TBR, or TMR with three-phase separator
A. From wellhead
B. Separator
C. Water leg
D. Oil leg
E. Gas leg
F. Coriolis sensor with PVR or TBR
G. Coriolis sensor with PVR (optional, used in applications where oil measurement is needed in the water leg to
detect a malfunctioning separator)
H. Coriolis sensor with TMR
I. Modbus host (flow computer)
10Micro Motion Multiphase Applications
Page 11
A
B
C
t
ρ
D
SupplementProduction Volume Reconciliation (PVR)
MMI-20026578January 2022
2Production Volume Reconciliation
(PVR)
2.1Understanding the PVR application
PVR is used in oil and gas separation applications to compensate for gas and/or water
contamination in the oil leg of a three-phase separator. It is also used to quantify the oil
and water volumes in the liquid leg of a two-phase separator.
PVR uses the meter's drive gain to indicate if there is entrained gas or transient bubbles in
the liquid stream, and adjust the measurement accordingly. Under normal circumstances,
i.e., no entrained gas or bubbles, the application uses the Net Oil Computer (NOC)
algorithm to calculate and quantify the volumes of oil and water in the liquid stream.
Net Oil Computer (NOC)
The Net Oil Computer algorithm calculates the water fraction of the liquid stream so that
the amount of oil and the amount of water can be determined. The algorithm measures
the volume of oil, corrected to a reference temperature, that is contained within the gross
volume of produced fluid.
Compensating for gas in the liquid
Entrained gas, or bubbles in the process fluid, has a negative effect on liquid volume
measurement accuracy. The Coriolis sensor calculates volume based on direct density and
mass measurements. When a bubble is present, mixture density is reduced, causing the
reported volume to be higher than the actual liquid volume. The presence of bubbles is
reflected in the drive gain. The following figure shows how the change in drive gain affects
density measurement.
Figure 2-1: Effect of transient bubbles on drive gain and density measurement
A. Density
B. Drive gain (actual)
C. Transient bubble condition
D. Drive gain (%)
Supplement11
Page 12
Production Volume Reconciliation (PVR)Supplement
January 2022MMI-20026578
A transient bubble condition is defined in terms of the sensor's drive gain: If the drive gain
exceeds the configured threshold for more than a specified interval, the selected PVR
action is performed. The transient bubble interval persists until drive gain is below the
configured threshold for the specified interval.
PVR volume calculation during bubble events
If the drive gain threshold is exceeded, the volume calculation for the period of high drive
gain can be handled in one of three ways.
OptionDescription
Hold Last Value
Use Input Density of
Dry Oil Converted to
Line Conditions
Alert Only
Use an average density value from an earlier point in the process
to calculate volume. If this option is chosen, the water cut from
the point just before the bubble event is effectively held
constant throughout the bubble event.
Convert the density of dry oil at reference temperature (a userconfigured value) to density at line temperature, and calculate
volume. This option assumes that all volume during the bubble
event is dry oil.
Post an alert.
12Micro Motion Multiphase Applications
Page 13
C
B
E
A
F
DD
SupplementProduction Volume Reconciliation (PVR)
MMI-20026578January 2022
Processing for Hold Last Value
This option directs the application to retrieve measured density data from an earlier point
in the process. The earlier point is identified by the configured PVR Lookback Period. The
density values around this point are averaged, and this average is then used in oil
calculations.
The following figure shows the substitution of average density data during the transient
bubble interval.
Figure 2-2: Hold Last Value in operation
A. Density
B. PVR Drive Gain Threshold
C. Drive gain (actual)
D. PVR Lookback Period
E. Averaged density values
F. Drive gain (%)
Note
If the point defined by PVR Lookback Period happens to fall into a previous transient
bubble interval, the application automatically extends the lookback interval as required so
that the average is calculated from measured density data rather than substituted density
values. In the illustration, the first average is applied to several transient bubble events.
Supplement13
Page 14
Production Volume Reconciliation (PVR)Supplement
January 2022MMI-20026578
2.2Density determination
To configure Production Volume Reconciliation (PVR), you must know the density of dry
oil at reference temperature, and the density of produced water at reference temperature.
Related information
Density determination using the data log from ProLink III
Density determination using a petroleum laboratory
2.2.1Density determination using the data log from ProLink III
To configure Production Volume Reconciliation (PVR), you must know the density of dry
oil at reference temperature, and the density of produced water at reference temperature.
You can use log data from ProLink III, with the Oil & Water Density Calculator, to obtain
these values.
Note
Even after separation, oil typically contains some amount of interstitial water. The water
cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil.
This procedure assumes the following:
• The highest density value in the logged data represents produced water.
• The lowest density value in the logged data represents dry oil.
Prerequisites
You must be able to connect to the transmitter or core processor with ProLink III.
You must know how to use the data logging feature in ProLink III.
You must be able to run data logging for the necessary time period, which may be a few
minutes or a few hours, depending on your separator.
You must have the Oil & Water Density Calculator. This is a spreadsheet tool developed by
Micro Motion. You can obtain a copy from your Micro Motion representative.
Procedure
1. Connect to the core processor or transmitter with ProLink III.
• For two-phase separators, connect to the core processor or transmitter on the
oil/water leg. See Figure 1-1.
• For three-phase separators, connect to the core processor or transmitter on the
oil leg. See Figure 1-2.
2. Set up data logging to record the following process variables, with a logging interval
of 1 second:
• Mass flow rate
• Volume flow rate
• Density
• Temperature
14Micro Motion Multiphase Applications
Page 15
SupplementProduction Volume Reconciliation (PVR)
MMI-20026578January 2022
• Drive gain
3. Collect data.
a) Open the level control valve on the separator, and allow the separator to
drop to the lowest safe level, or until gas is first drawn into the liquid leg.
b) Close the level control valve and allow the level to rise to the maximum safe
level.
This will increase the residence time for the liquid in the separator, and may
allow the water to settle to the bottom and the oil to rise to the top.
c) Open the level control valve partially, so that the level drops slowly.
d) Start data logging.
e) Allow the separator to drop to the lowest safe level, or until gas is first drawn
into the liquid leg.
f) Stop data logging.
g) Return the separator to automatic level control.
4. Obtain maximum and minimum density data from the log.
Shortly after the control valve is opened or the dump phase begins, you should see
the temperature stabilizing and the density rising to a maximum value and
stabilizing. This may represent produced water. Just before the lowest safe level, or
before the point where gas is drawn into the liquid leg, you should see the density
falling to a minimum value and stabilizing. This may represent dry oil.
a) Record the maximum density and the corresponding temperature.
b) Record the minimum density and the corresponding temperature.
Important
Never use an unstable density value, or any density value that has an elevated drive
gain.
5. Use the Oil & Water Density Calculator to calculate the density of dry oil at reference
temperature and the density of produced water at reference temperature.
Tip
Unless the oil is light hot condensate, the oil will almost always contain some
interstitial water. This is generally acceptable for allocation measurements.
However, if further accuracy is desired, you can determine the water cut and use it
in the calculation. To determine or estimate the water cut, take a shakeout sample
from one of the following:
• The current flow/dump cycle, at the time of minimum density
• Similar oils produced from the same reservoir
• The tank or tanks that the separator flows into
Enter this water cut into the Oil & Water Density Calculator to calculate the density
of dry oil at reference temperature.
Supplement15
Page 16
Production Volume Reconciliation (PVR)Supplement
January 2022MMI-20026578
2.2.2Density determination using a petroleum laboratory
To configure Production Volume Reconciliation (PVR), you must know the density of dry
oil at reference temperature, and the density of produced water at reference temperature.
You can obtain this values from a petroleum laboratory.
Note
Even after separation, oil typically contains some amount of interstitial water. The water
cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil.
Important
If you are using a three-phase separator, you can collect the oil sample and the water
sample separately, after separation, or you can collect one sample before separation and
have the laboratory perform the separation.
If you are using a two-phase separator, you should collect one sample before separation
and have the laboratory perform the separation.
Prerequisites
The petroleum laboratory must be able to meet these requirements:
• The laboratory density meter must be able to keep the oil sample pressurized at line
pressure during the density measurement.
• The sample cylinder must be a constant-pressure type, and must be properly rated for
the oil–water composition and for sample pressure.
• The oil density measurement units should be in g/cm³ at reference temperature and/or
°API at reference temperature. The water density measurement should be in g/cm³ at
reference temperature. PVR requires a reference temperature of 60 °F. Be sure to
specify this to the petroleum laboratory, as some countries use other reference
temperatures.
• The laboratory report must include the oil density, water density, and the reference
temperature.
The sample must be collected by a qualified person, using industry-accepted safety
standards.
You must know the minimum required sample size. This varies depending on the water
cut and the volume of the sample cylinder. Consult the petroleum laboratory for specific
values.
You must be able to collect and maintain the oil sample at line pressure, so that the oil will
not lose pressure and outgas.
If you collect the water sample separately, you must be able to protect it from
contamination and evaporation.
Procedure
1. Communicate the handling and measurement requirements to the petroleum
laboratory.
2. If you are collecting one sample that contains both oil and water, identify the point
in the line where the sample will be taken.
16Micro Motion Multiphase Applications
Page 17
SupplementProduction Volume Reconciliation (PVR)
MMI-20026578January 2022
Recommendations:
• Collect the sample upstream from the separator, at a point where the fluid is
well mixed. Fluid in the oil/water leg exiting the separator may not be well
mixed.
• The process fluid at the sample point should be representative of the process
fluid flowing through the sensor on the oil/water leg.
• The line pressure at the sample point should be close to the line pressure at the
sensor.
• Collect the sample from the bottom of the pipe to minimize the amount of gas
in the sample.
3. If you are using a three-phase separator and collecting the oil and water samples
separately, identify the points where the samples will be taken.
Recommendations:
• The sample point for oil must be on the oil leg, as close to the sensor as possible.
See Figure 1-2.
• The line pressure at the oil sample point should be similar to the line pressure at
the sensor.
• The sample point for water must be on the water leg, as close to the sensor as
possible. See Figure 1-2.
Note
If you have a Micro Motion sensor on the water leg, you may be able to use the
data logging procedure described in Density determination using the data log
from ProLink III to determine the water density.
4. If you are using a three-phase separator and collecting the oil and water samples
separately, wait until separation has occurred.
5. Collect the sample or samples, meeting all requirements for pressure and
protection from contamination or evaporation.
6. Mark and tag the sample or samples with the well name or number, time and date,
sample type, and line pressure.
7. Transport the samples to the laboratory safely, as soon as is practical.
Postrequisites
If the laboratory measurements were not corrected to your reference temperature, use
the Oil & Water Density Calculator to calculate density at reference temperature. This is a
spreadsheet tool developed by Micro Motion. You can obtain a copy from your
Micro Motion representative.
Supplement17
Page 18
Production Volume Reconciliation (PVR)Supplement
January 2022MMI-20026578
2.3Configure Production Volume Reconciliation
(PVR) using ProLink III
PVR is used with three-phase separators to remove gas and/or water contamination from
oil measurement on the oil leg, and to quantify the net oil and net water in the liquid leg of
a two-phase separator.
Prerequisites
You must know the density of dry oil from this well, at reference temperature and
reference pressure.
You must know the density of water at reference temperature.
Procedure
1. Choose Device Tools → Configuration → Process Measurement → Production
Volume Reconciliation (PVR).
2. Enable the PVR application.
3. Set Reference Temperature to the temperature to be used to calculate standard
density.
In most cases, this is the reference temperature used during density determination.
4. Enter the density of dry oil from this well at the configured reference temperature.
5. Enter the density of produced water at the configured reference temperature.
6. Set PVR Drive Gain Threshold to the value of drive gain, in percent, that indicates
the presence of bubbles in the process fluid.
At drive gain values above this threshold, the transmitter will implement the
configured PVR action.
7. Set PVR Drive Gain Threshold High to the value of drive gain, in percent, that
indicates a significant amount of gas in the process fluid.
At drive gain values above this threshold, the transmitter will post an alert.
8. Set PVR Action to the action that the transmitter will perform when PVR
remediation is active.
Option
Hold Last ValueThe transmitter will calculate volume using a
Use Input Density of Dry
Oil Converted to Line
Conditions
Description
substitute density value. The substitute value is an
average of the data around a recent point in the
process.
The transmitter will calculate volume using the
configured value for oil density, converted to line
temperature.
Alert OnlyThe transmitter will post an alert.
18Micro Motion Multiphase Applications
Page 19
SupplementProduction Volume Reconciliation (PVR)
MMI-20026578January 2022
As soon as the drive gain drops below PVR Drive Gain Threshold, the transmitter
returns to reporting standard density.
9. If you set PVR Action to Hold Last Value, set PVR Lookback Period to the number of
seconds the transmitter will go back in process history to retrieve and average
process data.
10. Enable or disable PVR Timeout as desired.
OptionDescription
Enabled If PVR actions are applied for the number of seconds specified in PVR
Timeout Value, the transmitter performs the configured TBR Timeout
Action.
Disabled PVR actions continue until the drive gain drops below PVR Drive Gain
Threshold.
11. If you enabled PVR Timeout:
a) Set PVR Timeout Value to the number of seconds that the transmitter will
perform the PVR action before implementing PVR Timeout Action.
b) Set PVR Timeout Action to the action that the transmitter will perform if the
PVR timeout is reached.
Option
AlertThe transmitter posts an alert, and continues PVR
Normal MeasurementThe transmitter returns to normal measurement, and
Description
actions.
does not post an alert.
Note
For the location of parameters not exclusive to the PVR software, refer to the
transmitter configuration and use manual.
Supplement19
Page 20
Production Volume Reconciliation (PVR)Supplement
January 2022MMI-20026578
20Micro Motion Multiphase Applications
Page 21
SupplementTransient Bubble Remediation (TBR)
MMI-20026578January 2022
3Transient Bubble Remediation (TBR)
3.1Understanding the TBR application
Transient Bubble Remediation (TBR) is indicated for use with liquid streams that may
experience intermittent low levels of gas entrainment, i.e., gas carry-under. In the
standard configuration, TBR enables accurate oil measurement during periods of
entrained gas by providing a substitute density value based on the immediately preceding
process density.
Liquid with gas measurement process
The presence of entrained gas (or bubbles) can cause significant errors when measuring
the volume flow of liquid through a Coriolis meter. Because bubbles displace some of the
liquid in a flow stream, the measured volume of the mixture may differ from the actual
amount of liquid that emerges from the pipe downstream.
So how can you tell when a liquid contains gas? When bubbles are present in a liquid
stream, Coriolis meters will report an increase in drive gain coinciding with a decrease in
both fluid density
liquid-gas mixture. Therefore, in order to measure only the liquid portion of the stream,
the volume of the bubbles must be ignored or subtracted from the mixture total.
software performs exactly this function, using drive gain as the diagnostic indication that
bubbles or entrained gas is present in the liquid flow stream, and then substituting a
liquid-only density in place of the live measurement until the gaseous event has subsided.
When the gassy portion has passed, indicated by an associated drop in drive gain, the
software returns to reporting the live measured volume flow rate.
(1)
and mass flow rate due to the lower amount of mass contained in the
(2)
TBR
Compensating for gas in the liquid
Entrained gas, or bubbles in the process fluid, has a negative effect on measurement
accuracy, because entrained gas causes abrupt increases in drive gain, and the density
measurement of the mixture is temporarily low. The following figure shows how the
change in drive gain affects density measurement.
(1) High frequency sensors may erroneously report a higher fluid density when entrained gas is present, and therefore are not
recommended for use on liquids with entrained gas. High frequency sensors include F300, H300, and all T-Series sensors.
(2) The unmeasured gases can be (and are often) collected and processed separately downstream if desired (using a separator
for example).
Supplement21
Page 22
A
B
C
t
ρ
D
Transient Bubble Remediation (TBR)Supplement
January 2022MMI-20026578
Figure 3-1: Effect of transient bubbles on drive gain and density measurement
A. Drive gain (actual)
B. Density
C. Transient bubble condition
D. Drive gain (%)
A transient bubble condition is defined in terms of the sensor's drive gain: If the drive gain
exceeds the configured threshold, the selected TBR action is performed. The transient
bubble interval persists until drive gain is below the configured threshold.
TBR actions
The TBR application can perform either of the following actions if transient bubbles are
detected:
Alert Only
Hold Last Value
Post an alert
Report an average value from an earlier point in the process
Processing for Hold Last Value
This option directs the application to retrieve measured density data from an earlier point
in the process. The earlier point is identified by the configured TBR Lookback Period. The
density values around this point are averaged, and this average is then used in net oil
calculations.
The following figure shows the substitution of average density data during the transient
bubble interval.
22Micro Motion Multiphase Applications
Page 23
C
B
E
A
F
DD
SupplementTransient Bubble Remediation (TBR)
MMI-20026578January 2022
Figure 3-2: Hold Last Value in operation
A. Density
B. TBR Drive Gain Threshold
C. Drive gain (actual)
D. TBR Lookback Period
E. Averaged density values
F. Drive gain (%)
Note
If the point defined by TBR Lookback Period happens to fall into a previous transient
bubble interval, the application automatically extends the lookback interval as required so
that the average is calculated from measured density data rather than substituted density
values.
3.2Configure Transient Bubble Remediation (TBR)
using ProLink III
TBR is used with liquid streams that may experience intermittent low levels of gas
entrainment. TBR allows the system to detect transient bubble conditions, and to take
either of two actions in response.
2. Set TBR Drive Gain Threshold to the value of drive gain, in percent, that indicates
the presence of bubbles in the process fluid.
Supplement23
Page 24
Transient Bubble Remediation (TBR)Supplement
January 2022MMI-20026578
At drive gain values above this threshold, the transmitter will implement the
configured TBR actions.
3. Set TBR Action to the action that the transmitter will perform when TBR is active.
OptionDescription
Hold Last Value The transmitter will calculate volume using a substitute density
value. The substitute value is an average of the data around a
recent point in the process.
Alert OnlyThe transmitter will post an alert.
4. If you set TBR Action to Hold Last Value, set Lookback Period to the number of
seconds the transmitter will go back in process history to retrieve and average
process data.
5. Enable or disable TBR Timeout as desired.
OptionDescription
Enabled If TBR is active for the number of seconds specified in TBR Timeout
Value, the transmitter performs the configured TBR Timeout Action.
Disabled TBR actions continue until the drive gain drops below TBR Drive Gain
Threshold.
6. If you enabled TBR Timeout:
a) Set TBR Timeout Value to the number of seconds that the transmitter will
perform TBR before implementing TBR Timeout Action.
b) Set TBR Timeout Action to the action that the transmitter will perform if the
TBR timeout is reached.
Option
AlertThe transmitter returns to normal measurement and
Normal MeasurementThe transmitter returns to normal measurement, and
Description
an alert is posted..
does not post an alert.
Note
For the location of parameters not exclusive to the TBR software, refer to the
transmitter configuration and use manual.
24Micro Motion Multiphase Applications
Page 25
SupplementTransient Mist Remediation (TMR)
MMI-20026578January 2022
4Transient Mist Remediation (TMR)
4.1Understanding the TMR application
TMR is designed for use with gas streams that may experience intermittent low levels of
liquid entrainment, i.e., liquid carry-over.
Entrained liquid, or mist in the process fluid, has a negative effect on measurement
accuracy, because entrained liquid causes abrupt increases in drive gain, and the density
measurement is temporarily low. TMR allows gas measurement to continue during
periods of entrained liquid (mist) by providing a substitute flow rate value based on the
immediately preceding process flow rate. When the mist interval is over, TMR returns to
reporting the measured flow rate, increased or decreased by a maximum of 10%, until flow
totals are appropriately adjusted for the unmeasured flow.
A transient mist condition is defined in terms of the sensor's drive gain: If the drive gain
exceeds the configured threshold, the transmitter automatically performs transient mist
remediation. The transient mist interval persists until drive gain is below the configured
threshold.
The following figure illustrates TMR processing.
Supplement25
Page 26
A
H
H
GG
E
E
FF
B
C
DD
Transient Mist Remediation (TMR)Supplement
January 2022MMI-20026578
Figure 4-1: TMR in operation
A. Flow rate
B. TMR Drive Gain Threshold
C. Drive gain (actual)
D. Pre-Mist Averaging Period and source of M1
E. Averaged flow rate values
F. Post-Mist Adjustment Delay and source of M2
G. Adjustment period
H. Adjusted flow rate values
When TMR is detected, the transmitter substitutes an average flow rate value, M1, for the
measured flow rate, for the entire transient mist interval. The substitute flow rate is
calculated from the actual flow rate data for the previous n seconds, where n is
determined by the setting of Pre-Mist Averaging Period.
When the transient mist interval is over, the transmitter waits for the number of seconds
specified by Post-Mist Adjustment Delay. During that period, the transmitter calculates a
second average flow rate, M2. M1 and M2 are then averaged, producing an approximate
value for the actual flow rate during the transient mist interval. The measured flow rate is
then increased or decreased by a maximum of 10% until the flow total has been
compensated for all of the unmeasured flow.
26Micro Motion Multiphase Applications
Page 27
SupplementTransient Mist Remediation (TMR)
MMI-20026578January 2022
4.2Configure Transient Mist Remediation (TMR)
using ProLink III
TMR is designed for use with gas streams that may experience intermittent low levels of
liquid entrainment.
3. Set TMR Drive Gain Threshold to the value of drive gain, in percent, that indicates
the presence of mist in the process fluid.
At drive gain values above this threshold, the transmitter will initiate TMR.
4. Set Pre-Mist Averaging Period to the number of seconds over which flow rate will
be averaged to produce a substitute flow rate.
When mist is detected, the transmitter retrieves the most recent flow rate data for
the specified number of seconds, averages the data, and reports the result rather
than the measured flow rate.
5. Set Post-Mist Adjustment Delay to the number of seconds that the transmitter will
wait, after mist is detected, before beginning TMR adjustment.
During TMR adjustment, the transmitter increases or decreases the measured flow
rate by a maximum of 10%. The TMR adjustment continues until the flow total has
been completely compensated for the unmeasured flow.
Note
For the location of parameters not exclusive to the TMR software, refer to the
transmitter configuration and use manual.
Supplement27
Page 28
Transient Mist Remediation (TMR)Supplement
January 2022MMI-20026578
28Micro Motion Multiphase Applications
Page 29
SupplementDisplay variables
MMI-20026578January 2022
5Display variables
5.1Display variables available with PVR, TBR, and
TMR
When PVR, TBR, or TMR is implemented on your transmitter, additional applicationspecific process variables are available to configure as display variables.
The following table lists the process variables that are available for configuration as display
variables. For instructions on configuring display variables, see the configuration manual
for your transmitter.
Table 5-1: Process variables available as display variables
Process variableApplication
PVRTBRTMR
Oil Total At Line✓
Water Total At Line✓
Water Cut At Line✓
Accumulated TBR Time✓✓
Mass Flow (unremediated)✓✓✓
Mass Total (unremediated)✓✓✓
Mass Inventory (unremediated)✓✓✓
Mass Flow (remediated)✓
Mass Total (remediated)✓
Mass Inventory (remediated)✓
Meastured Oil Density At Reference
(Fixed API Units)
Meastured Oil Density At Reference
(Fixed SGU Units)
Oil Flow Rate At Line✓
Oil Flow Rate At Reference✓
Oil Total At Reference✓
Unremediated Density At Line✓✓
Unremediated Volume Flow At Line✓✓
✓
✓
Unremediated Volune Total At Line✓✓
Volume Flow (remediated)✓✓✓
Volume Total (remediated)✓✓✓
Volume Inventory (remediated)✓✓✓
Supplement29
Page 30
Display variablesSupplement
January 2022MMI-20026578
Table 5-1: Process variables available as display variables (continued)
Process variableApplication
PVRTBRTMR
Water Cut At Reference✓
Water Flow Rate At Line✓
Water Flow Rate At Reference✓
Water Total At Reference✓
30Micro Motion Multiphase Applications
Page 31
SupplementApplication parameters and data
MMI-20026578January 2022
AApplication parameters and data
To use Modbus to configure other parameters, see the Micro MotionModbus Interface Tool.
This information is provided for completeness.
A.1PVR parameters and data
Table A-1: PVR configuration parameters
ParameterDescriptionModbus location and data type
Application StatusEnabled/disabledCoil 75, coil 246 (write to both coils)
• 0=Disabled
• 1=Enabled
Density of Dry Oil at
Reference Temperature
Density of Water at
Reference Temperature
PVR Drive Gain ThresholdThe drive gain, in %, that
PVR Drive Gain Threshold
High
PVR ActionThe remediation action to
Density of dry oil from this
well, in g/cm³, at 60 °F
Density of produced
water from this well, in
g/cm³, at 60 °F
triggers the configured
PVR remediation action
The drive gain, in %, that
represents a significant
amount of gas in the
liquid stream. The
transmitter sets a flag.
be implemented
1959–1960, Float
1831–1832, Float
617–618, Float
343–344, Float
ETO ≤ v3.95624 Bit 0, U16
• 0=Calculate volume from a substitute
density value, derived from averaged
density values from an earlier point in
the process
• 1=Alert only
ETO > v3.954450, U16
• 0=Calculate volume from a substitute
density value, derived from averaged
density values from an earlier point in
the process
• 1=Alert only
• 2=Calculate volume using the
configured value for oil density,
converted to line temperature
Enables a set of variables
that are adjusted for userdefined oil shrinkage
value, using a no-flow
computer.
shrinkage value using the
meter/transmitter. Users
can restrict the meter
factor to the shrinkage
factor level for easier
record keeping.
624 Bit 6, U16
• 0=Disabled
• 1=Enabled
619, U16
624 Bit 1, U16
• 0=Normal Measurement
• 1-Alert
Coil 376
1689-1960, Float
3992-3993, Float
Sales DensityEnables comparison of
produced density to sales
density to determine the
shrinkage factor.
Table A-2: PVR application status
Modbus location and
data type
52–55,
8–byte ASCII
ValueDescription
DENSHIThe calculated uncorrected water cut is greater than 100%. Water
DENSLOThe calculated uncorrected water cut is less than 0%. Water cut is
GVF_HIThe GVF is high; drive gain is higher than PVR Drive Gain Threshold
GVF_LOThe GVF is low; drive gain is between PVR Drive Gain Threshold and
(eight space
characters)
4465-4466, Float
cut is reported as 100%.
reported as 0%.
High.
PVR Drive Gain Threshold High.
No condition is active.
32Micro Motion Multiphase Applications
Page 33
SupplementApplication parameters and data
MMI-20026578January 2022
Table A-3: PVR process variables
Process variableValueModbus location
No entrained
gas detected
Entrained gas detected
and data type
Water Cut At LineCalculated water cut at line
conditions
Water Cut At Reference
Water Flow Rate At Line
(1)
Calculated water cut at 60 °F Core Processor ETO < v4.13:01557–1558, Float
(1)
Net volume flow rate of the
water at line conditions
Core Processor ETO < v4.13:01555–1556, Float
Core Processor ETO ≥ v4.13:
• PVR Action=0 or 1:
Calculated water cut at
line conditions
• PVR Action=2: 0
Core Processor ETO ≥ v4.13:
• PVR Action=0 or 1:
Calculated water cut at
60 °F
• PVR Action=2: 0
Core Processor ETO < v4.13:01561–1562, Float
Core Processor ETO ≥ v4.13:
• PVR Action=0 or 1: Net
volume flow rate at line
conditions
• PVR Action=2: 0
Water Total At Reference
(1)
Net volume flow rate of the
01549–1550, Float
water at 60 °F
Water Total At LineNet volume total of the
water at line conditions,
incrementing
Core Processor ETO < v4.13:
Net volume total of the
water at line conditions held
1667–1668, Float
at previous value; total does
not increment
Core Processor ETO ≥ v4.13:
• PVR Action=0 or 1: Net
volume flow rate at line
conditions,
incrementing
• PVR Action=2: Net
volume total of the
water at line conditions
held at previous value;
total does not increment
Supplement33
Page 34
Application parameters and dataSupplement
January 2022MMI-20026578
Table A-3: PVR process variables (continued)
Process variableValueModbus location
and data type
1663–1664, Float
Water Total At Reference
No entrained
gas detected
(1)
Net volume total of the
water at 60 °F, incrementing
Entrained gas detected
Core Processor ETO < v4.13:
Net volume total of the
water at 60 °F held at
previous value; total does
not increment
Core Processor ETO ≥ v4.13:
• PVR Action=0 or 1: Net
volume flow rate at
60 °F, incrementing
• PVR Action=2: Net
volume total of the
water at 60 °F held at
previous value; total
does not increment
Oil Density At Line (Fixed
SGU Units)
(1)
Density of the oil at 60 °F
(user-specified), converted
to line conditions using line
temperature and API Even
Table Correction for “A
Tables” (Temp
DensityOil
@60F
,
@Line
), then
reported in SGU units
Oil Density At Line (Fixed API
(1)
Units)
Density of the oil at 60 °F
(user-specified), converted
to line conditions using line
temperature and API Even
Table Correction for “A
Tables” (Temp
DensityOil
@60F
,
@Line
), reported in
°API
Oil Flow Rate At Line
(1)
Volume flow rate of oil at
line conditions
Oil Flow Rate At
Reference
(1)
Volume flow rate of oil at
60 °F
Oil Total Rate At LineNet volume total of the oil at
line conditions
Oil Total At Reference
(1)
Net volume total of the oil at
60 °F
Density of the oil at 60 °F
(user-specified), converted
to line conditions using line
temperature and API Even
Table Correction for “A
Tables” (Temp
DensityOil
@60F
,
@Line
), then
reported in SGU units
Density of the oil at 60 °F
(user-specified), converted
to line conditions using line
temperature and API Even
Table Correction for “A
Tables” (Temp
DensityOil
@60F
,
@Line
), reported in
°API
Volume flow rate of oil at
line conditions
Volume flow rate of oil at
60 °F
Net volume total of the oil at
line conditions
Net volume total of the oil at
60 °F
345–346, Float
347–348, Float
1553–1554, Float
1547–1548, Float
1665–1666, Float
1661–1662, Float
DensityDensity of the oil and water
mixture, at line conditions
Core Processor ETO < v4.13:
Remediated density of the
249–250, Float
mixture at line conditions,
with the configured TBR
action applied
34Micro Motion Multiphase Applications
Page 35
SupplementApplication parameters and data
MMI-20026578January 2022
Table A-3: PVR process variables (continued)
Process variableValueModbus location
No entrained
gas detected
Entrained gas detected
Core Processor ETO ≥ v4.13:
• PVR Action=0 or 1:
Remediated density of
the mixture at line
conditions, with the
configured TBR action
applied
• PVR Action=2: User-
specified density of oil at
60 °F, converted to line
conditions
and data type
Mass Flow RateMass flow rate of the liquid
mixture, unremediated for
PVR
Mass TotalMass total of the liquid
mixture, unremediated for
PVR
Mass InventoryMass inventory of the
mixture, unremediated for
PVR
Volume Flow RateVolume flow rate of the
mixture, remediated for PVR
Volume TotalTotal volume of the mixture
at line conditions,
remediated
Volume InventoryVolume inventory of the
mixture, remediated for PVR
Unremediated Volume Flow
Rate At Line
(1)
Volume flow rate of the
mixture at line conditions,
with TBR correction
(unremediated)
Volume Total At Line
(1)
Total volume of the mixture
at line conditions, without
TBR correction
(unremediated)
Accumulated TBR Time
(2)
Total number of seconds
that TBR correction has
been active, since the last
master reset
Mass flow rate of the liquid
mixture, unremediated for
PVR
Mass total of the liquid
mixture, unremediated for
PVR
Mass inventory of the
mixture, unremediated for
PVR
Volume flow rate of the
mixture, remediated for PVR
Total volume of the mixture
at line conditions,
remediated
Volume inventory of the
mixture, remediated for PVR
Volume flow rate of the
mixture at line conditions,
with TBR correction
(unremediated).
Total volume of the mixture
at line conditions, without
TBR correction
(unremediated)
Total number of seconds
that TBR correction has
been active, since the last
master reset
247–248, Float
259–260, Float
263–264, Float
253–254, Float
261–262, Float
265–266, Float
2265–2266, Float
349-350, Float
2267–2268, INT32
Shrinkage Factor Oil Flow
Rate At Line
(3)
Volume flow of oil at line
conditions, adjusted by
shrinkage factor and
shrinkage meter factor
Volume flow of oil at line
conditions, adjusted by
shrinkage factor and
shrinkage meter factor
1733–1734, Float
Supplement35
Page 36
Application parameters and dataSupplement
January 2022MMI-20026578
Table A-3: PVR process variables (continued)
Process variableValueModbus location
No entrained
gas detected
Entrained gas detected
and data type
Shrinkage Factor Oil Flow
Rate At Reference
(3)
Shrinkage Factor Volume
Flow Rate At Reference
Shrinkage Factor Oil Total at
(3)
Line
Shrinkage Factor Oil Total at
Reference
Shrinkage Factor Volume
Total At Reference
(3)
(3)
Measured Oil Density At
Reference (Fixed SGU
(3)
Units)
Measured Oil Density At
Reference (Fixed API
(3)
Units)
Unremediated Density
Volume flow of oil at
reference conditions,
adjusted by shrinkage factor
and shrinkage meter factor
Volume flow of the mix at
(3)
reference conditions
Volume Total of the mix at
line conditions
Oil Total of the mix at
reference conditions
Volume Total of the mix at
reference conditions
Density of the mixture at 60
°F, assuming the mixture is
all oil. reported in SGU Units
Density of the mixture at 60
°F, assuming the mixture is
all oil. reported in °API.
(4)
Density of the mixture at
Volume flow of oil at
reference conditions,
adjusted by shrinkage factor
and shrinkage meter factor
Volume flow of the mix at
reference conditions
Volume Total of the mix at
line conditions
Oil Total of the mix at
reference conditions
Volume Total of the mix at
reference conditions
1735–1736, Float
1737–1738, Float
4616–4617, Float
4618–4619, Float
4796–4797, Float
1655–1666, Float
4465–4466, Float
1539–1540, Float
line conditions
(unremediated for PVR)
(1) Not available when connected to a transmitter.
(2) Requires the enhanced core processor v4.11 or later with ETO 22166 or ETO 22701.
(3) Requires the enhanced core processor v4.31 or later with ETO 22166 or ETO 22701.
(4) Requires the enhanced core processor v4.40 or later with ETO 22166 or ETO 22701. If for direct connect, use ETO
13386 or the standard 800 v4.42 or greater if connected to a Model 2700 Transmitter.
36Micro Motion Multiphase Applications
Page 37
SupplementApplication parameters and data
MMI-20026578January 2022
A.2TBR parameters and data
Table A-4: TBR configuration parameters
ParameterDescriptionModbus location and data type
Drive Gain ThresholdThe drive gain, in %, that triggers TBR617–618, Float
TBR ActionThe remediation action to be implemented624, U16
• Bit #0: Initial Action
— 0=Hold Last Value
— 1=Alert Only
• Bit #2: Drive Gain Averaging
— 0=1 second
— 1=4 seconds
• Bit #3: Apply to Mass Flow (affects volume
flow)
— 0=Yes
— 1=No
• Bit #4: Apply to Density (affects volume
flow)
— 0=Yes
— 1=No
• Bit #5: Timeout Alert Type
— 0=Two-Phase Flow
— 1=Density Out of Range
TBR Lookback Period
TBR TimeoutEnable or disable a timeout on the TBR
TBR Timeout ValueThe number of seconds that TBR remediation
TBR Timeout ActionThe action to be performed if TBR remediation
The time period (seconds) that the application
goes back in time to determine the substitute
density to use in calculations
remediation action
will be performed before timing out
times out
620, U16
624 Bit #6, U16
• 0=Disabled
• 1=Enabled
619, U16
624 Bit #1, U16
• 0=Normal Measurement
• 1=Alert
Table A-5: TBR application status parameters
Application statusDescriptionModbus location and data type
TBR ActiveIndicates whether TBR is active or inactive433 Bit #10, U16
TBR Total TimeThe duration of the TBR interval, in seconds989, U32
Supplement37
Page 38
Application parameters and dataSupplement
January 2022MMI-20026578
Table A-6: TBR process variables
Process variableDescriptionModbus location and
data type
Mixture Mass Flow Rate (unremediated)Mass flow rate of the mixture, unremediated247–248, Float
Mixture Mass Total (unremediated)Mass total of the mixture, unremediated259–260, Float
Mixture Mass Inventory (unremediated)Mass inventory of the mixture, unremediated263–264, Float
Mixture Uncorrected Volume Flow Rate
(remediated)
Mixture Uncorrected Volume Total
(remediated)
Mixture Uncorrected Volume Inventory
(remediated)
Unremediated Density
(1) Requires the enhanced core processor v4.40 or later with ETO 13386 for direct connect, or the standard 800 v4.42 or
greater if connected to a Model 2700 Transmitter.
(1)
Volume flow rate of the mixture, remediated253–254, Float
Total volume of the mixture at line conditions,
remediated
Volume inventory of the mixture at line
conditions, remediated
Volume inventory of the mixture at line
conditions, remediated
261–262, Float
265–266, Float
1539-1540, Float
A.3TMR parameters and data
Table A-7: TMR configuration parameters
ParameterDescriptionModbus location and data type
Application StatusEnabled/disabledCoil 75 (Core processor version less than
v4.40)
Coil 473 (Core processor version 4.40 or
greater.)
• 0=Disabled
• 1=Enabled
Drive Gain ThresholdThe drive gain, in %, that triggers TMR617–618, Float
Pre–Mist Averaging
Period
Post–Mist Adjustment
Delay
TMR ActionThe remediation action to be implemented624, U16
The time period (seconds) that the application
goes back in time to determine the density to
use in TMR remediation
The time period (seconds) that the transmitter
waits before beginning density adjustment
619, U16
620, U16
• Bit #5: Timeout Alert Type
— 0=Two–Phase Flow
— 1=Density Out of Range
Table A-8: TMR application status parameters
Application statusDescriptionModbus location and data type
TMR ActiveIndicates whether TMR is active or inactive433 Bit #12, U16
38Micro Motion Multiphase Applications
Page 39
SupplementApplication parameters and data
MMI-20026578January 2022
Table A-8: TMR application status parameters (continued)
Application statusDescriptionModbus location and data type
TMR Total TimeThe duration of the TMR interval, in seconds989, U32
Table A-9: TMR process variables
Process variableDescriptionModbus location and
data type
Mass Flow Rate (remediated)Mass flow rate of the process fluid, remediated 973–974, Float
Mass Total (remediated)Mass total of the process fluid, remediated975–976, Float
Mass Inventory (remediated)Mass inventory of the process fluid,
977–978, Float
remediated
Mass Flow Rate (unremediated)Mass flow rate of the process fluid,
247–248, Float
unremediated
Mass Total (unremediated)Mass total of the process fluid, unremediated259–260, Float
Mass Inventory (unremediated)Mass inventory of the process fluid,
263–264, Float
unremediated
Uncorrected Liquid Volume Flow Rate
(remediated)
Uncorrected Liquid Volume Total
(remediated)
Uncorrected Liquid Volume Inventory
(remediated)
(1)
(1)
(1)
Corrected GSV Flow Rate (remediated)
(2)
Volume flow rate of the process fluid,
remediated
Total volume of the process fluid at line
conditions, remediated
Volume inventory of the process fluid at line
conditions, remediated
Corrected GSV flow rate of the process fluid,
253–254, Float
261–262, Float
265–266, Float
455–456, Float
remediated
Corrected GSV Total (remediated)
(2)
Corrected GSV total of the process fluid,
457–458, Float
remediated
Corrected GSV Inventory (remediated)
(2)
Corrected GSV inventory of the process fluid,
459–460, Float
remediated
(1) Applicable if Volume Flow Type = Liquid.
(2) Applicable if Volume Flow Type = Gas Standard Volume. GSV is available with TMR for transmitters v6.62 and later.
Supplement39
Page 40
Application parameters and dataSupplement
January 2022MMI-20026578
40Micro Motion Multiphase Applications
Page 41
SupplementBest practices for two-phase measurement performance
MMI-20026578January 2022
BBest practices for two-phase
measurement performance
B.1Entrained gas performance
Measurement accuracy for liquids with entrained gas is a complex function of GVF,
viscosity, velocity, sensor geometry, drive frequency, and orientation. The best
measurement performance will always be achieved if fluid can be measured in singlephase. Add a free-gas knockout upstream if possible. The following guidelines apply
regardless if APM options are licensed or not. When gas entrainment is inevitable, APM will
improve the measurement performance.
Common sources for unintentional gas entrainment
• Long drops from fill point to liquid level in tanks
• Agitators and mixers
• Leaks in seals or pumps
• Pumping out of nearly empty tanks
• Pressure loss (flashing) for volatile liquids
• Pumping through nearly empty piping
Ways to minimize flow errors
• Use ELITE® (low frequency) sensors whenever possible. F-Series and H-Series sensors
are also acceptable, but less accurate.
• Do not use T-Series sensors or Models F300/H300 compact because they have a high
operating frequency.
• Use the enhanced core processor (Model 800) either as direct connect or with the
1000-2000 Transmitter family: they perform best in applications with entrained gas.
• Orient the meter properly:
Table B-1: Preferred sensor orientation for liquids with entrained gas
Best practices for two-phase measurement performanceSupplement
January 2022MMI-20026578
Table B-1: Preferred sensor orientation for liquids with entrained gas (continued)
ProcessPreferred orientation
Any F-Series or CMFS sensor, and CMF200 or
larger (flow should go up)
• Ensure sensor is filled as quickly as possible, and stays full during measurement:
— For horizontal pipes, maintain a minimum flow velocity of 1 m/s to purge air from
an empty pipe and keep it full.
— For vertical pipes, flow upward and maintain minimum velocity of 1 m/s to prevent
solids from settling out of the fluid.
• Add back pressure, or increase line pressure, to minimize size of bubbles in flow
stream.
• Size the meter appropriately to operate normally as close to the sensor nominal flow
rate as is practical. Higher velocity leads to better performance, as long as pressure
drop does not cause liquids flash.
• Ensure fluid is well mixed. If needed, you can install a blind “T” and/or static mixer just
upstream of the sensor to evenly distribute bubbles through both sensor tubes. If using
a blind “T”, install it in the same plane as the sensor tubes.
• If re-zeroing in the field is necessary, zeroing must be done on a pure liquid without
bubbles in order to avoid error. If this cannot be done, use the factory zero.
• Minimize damping on outputs to minimize processing delay from electronics.
• Do not stop the totalizer immediately after batch; allow the totalizer to stabilize for
approximately 1 second.
• Set Flow Cutoff as high as is practical to avoid totalizing at no flow condition if bubbles
remain in the sensor.
B.2Entrained liquid (mist) performance
Measurement accuracy for gases with entrained liquids (mist) is mostly related to the
amount of mass contained in liquid droplets compared to an equivalent volume of gas
containing the same mass. It is important to choose the correct sensor. Otherwise, sensor
geometry, drive frequency, and orientation can cause errors that reduce performance. The
best measurement performance will always be achieved if fluid can be measured in singlephase. Add a liquid trap upstream if possible. The following guidelines apply regardless if
APM options are licensed or not. When liquid entrainment is inevitable, APM will improve
the measurement performance.
42Micro Motion Multiphase Applications
Page 43
SupplementBest practices for two-phase measurement performance
MMI-20026578January 2022
Common sources for unintentional liquid entrainment
• Temperature loss (condensation)
• Pressure increase
• Poorly managed level control in separators or GLCCs
• Malfunctioning or over-filled liquid traps
Ways to minimize measurement errors
• Use ELITE® (low frequency) sensors whenever possible. F-Series and H-Series sensors
are also acceptable, but less accurate.
• Size the meter appropriately for gas flow. Avoid high turndowns where sensor
sensitivity may be reduced.
• Do not use T-Series sensors or compact Models F300/H300 because they have a high
operating frequency.
• Use the enhanced core processor (Model 800) or the 1000-2000 transmitter family:
they perform best in applications with entrained liquid.
• Use the enhanced core processor (Model 800) either as direct connect or with the
1000-2000 transmitter family: they perform best in applications with entrained liquid.
• Orient the meter properly:
Table B-2: Preferred sensor orientation when there could be entrained liquid
Any F-Series or CMFS sensor, and CMF200 or
larger (flow should go down)
• Ensure sensor is dried (blown-out) as quickly as possible, and stays dry during
measurement.
• Avoid temperature losses; insulation is highly recommended if condensate is caused by
cooling temperatures.
• Avoid pressure increases in the system; Ensure that pressure regulators are functioning
properly.
Supplement43
Page 44
Best practices for two-phase measurement performanceSupplement
January 2022MMI-20026578
• If entrained liquid is unavoidable, try to ensure that the process is well mixed.
• Avoid elbows, valves, or other components that may introduce a flow profile affecting
one tube (for example, a swirling motion entering the flow tubes)
• If re-zeroing in the field is necessary, zeroing must be done on a pure gas without liquid
in order to avoid error. If this cannot be done, use the factory zero.
• Minimize damping on outputs to minimize processing delay from electronics.
• Do not stop the totalizer immediately after batch; allow the totalizer to stabilize for
approximately 1 second.
• Set Flow Cutoff as high as is practical to avoid totalizing at no flow condition if droplets
remain in the sensor.
B.3Density determination
If you are using either the PVR application or the , you must know the density of water
from the well, corrected to reference temperature, and the density of dry oil from the well,
corrected to reference temperature.
B.3.1
Important
Micro Motion recommends working with a laboratory to obtain the most accurate values.
The accuracy of the PVR data depends upon the accuracy of these two density values.
Density determination using a petroleum laboratory
To configure PVR for net oil measurement, you must know the density of oil at reference
temperature, and the density of produced water at reference temperature. You can obtain
these values from a petroleum laboratory.
Note
Even after separation, oil typically contains some amount of interstitial water. The water
cut may be as high as 1% to 3%.
Important
If you are using a three-phase separator, you can collect the oil sample and the water
sample separately, after separation, or you can collect one sample before separation and
have the laboratory perform the separation.
If you are using a two-phase separator, you should collect one sample before separation
and have the laboratory perform the separation.
Prerequisites
Sample collection must meet these requirements:
• You must be able to collect a sample that is representative of your process.
• The sample must be collected by a qualified person, using industry-accepted safety
standards.
• You must know the minimum required sample size. This varies depending on the water
cut and the volume of the sample cylinder. Consult the petroleum laboratory for
specific values.
44Micro Motion Multiphase Applications
Page 45
SupplementBest practices for two-phase measurement performance
MMI-20026578January 2022
• If the sample contains oil, you must be able to collect and maintain the sample at line
pressure, so that the oil will not lose pressure and outgas. This will change the
laboratory-measured density.
• If you collect the water sample separately, you must be able to protect it from
contamination and evaporation.
You must know the reference temperature that you plan to use.
The petroleum laboratory must be able to meet these requirements:
• The laboratory density meter must be able to keep the oil sample pressurized at line
pressure during the density measurement.
• The sample cylinder must be a constant-pressure type, and must be properly rated for
the oil–water composition and for sample pressure.
• The oil and water density measurement units must be entered into the PVR software in
g/cm³ at reference temperature (always 60 °F with an enhanced core processor direct
connect or with the 1000-2000 transmitter family).
• The laboratory report must include the oil density, water density, and the reference
temperature.
Procedure
1. Communicate the handling and measurement requirements and the reference
temperature to the petroleum laboratory.
2. If you are collecting one sample that contains both oil and water, identify the point
in the line where the sample will be taken.
Recommendations:
• Collect the sample at a point where the fluid is well mixed.
• The line pressure at the sample point should be close to the line pressure at the
sensor.
• The line temperature at the sample point should be close to the line
temperature at the sensor.
3. If you are using a three-phase separator and collecting the oil and water samples
separately:
a) Identify the points where the samples will be taken.
Recommendations:
• The sample point for oil must be on the oil leg, as close to the sensor as
possible.
• The line pressure at the oil sample point should be similar to the line
pressure at the sensor.
• The sample point for water must be on the water leg, as close to the
sensor as possible.
• The line temperature at the water sample point should be similar to the
line temperature at the sensor.
Supplement45
Page 46
Best practices for two-phase measurement performanceSupplement
January 2022MMI-20026578
b) Wait until separation has occurred.
4. Collect the sample or samples, meeting all requirements for pressure and
protection from contamination or evaporation.
5. Mark and tag the sample or samples with the well name or number, time and date,
sample type, line pressure, and line temperature.
6. Transport the samples to the laboratory safely, as soon as is practical.
Postrequisites
If the laboratory measurements were not corrected to your reference temperature, use
the Oil & Water Density Calculator to calculate density at reference temperature. This is a
spreadsheet tool developed by Micro Motion. You can obtain a copy by visiting https://
www.emersonflowsolutions.com/oildensityref or from your Micro Motion representative.
B.3.2
Density determination using a three-phase separator
To configure net oil measurement, you must know the density of dry oil at reference
temperature, and the density of produced water at reference temperature. If you have a
three-phase separator, you can use density data and the Oil & Water Density Calculator to
obtain these values.
Note
Even after separation, oil typically contains some amount of interstitial water. The water
cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil.
Prerequisites
You must have a three-phase separator in the process. You can use a mobile three-phase
test separator.
You must have a sensor and transmitter installed on the oil leg, and a sensor and
transmitter installed on the water leg or determine the water density separately by manual
sampling.
You must know the reference temperature that you plan to use (always 60 °F (15.6 °C)
with an enhanced core processor direct connect or with the 1000-2000 transmitter
family).
You must have the Oil & Water Density Calculator. This is a spreadsheet tool developed by
Micro Motion. You can obtain a copy from your Micro Motion representative or by visiting
The accuracy of net oil data depends on the accuracy of the density data. Never use an
unstable density value, or any density value that has an elevated drive gain.
Procedure
1. Wait until separation has occurred.
2. At the transmitter on the oil leg, do one of the following options:
• Read and record the density value and the temperature value
46Micro Motion Multiphase Applications
Page 47
SupplementBest practices for two-phase measurement performance
MMI-20026578January 2022
• If logging the live variable data, monitor the live density at line conditions, or the
corrected density at 60 °F (15.6 °C) (modbus register 1655)
3. At the transmitter on the water leg, read and record the density value and the
temperature value. Alternatively, enter the density of the water obtained by
another method, such as sampling.
4. Use the Oil & Water Density Calculator to calculate the density of dry oil at reference
temperature and the density of produced water at reference temperature. You can
obtain a copy from your Micro Motion representative or by visiting https://
www.emersonflowsolutions.com/oildensityref.
Tip
Unless the oil is light hot condensate, the oil will almost always contain some
interstitial water. This is generally acceptable for allocation measurements.
However, if further accuracy is desired, you can determine the water cut and use it
in the calculation. To determine or estimate the water cut, take a shakeout sample
from one of the following:
• The current flow/dump cycle, at the time of minimum density
• Similar oils produced from the same reservoir
• The tank or tanks that the separator flows into
Enter this water cut into the Oil & Water Density Calculator to calculate the density
of dry oil at reference temperature.
The Emerson logo is a trademark and service mark of Emerson
Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct
Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of
their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.