Micro Motion Oil and Gas Production Applications-PVR, TBR, TMR Manuals & Guides

Page 1
Supplement
MMI-20026578, Rev AD
January 2022
Micro Motion™ Multiphase Applications
Production Volume Reconciliation (PVR) | Transient Bubble Remediation (TBR) | Transient Mist Remediation (TMR)
Page 2
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are available: the EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions. In addition the IECEx Installation Instructions for installations outside of the European Union and the CSA Installation Instructions for installations in North America are available on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com. For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. and Ireland 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 70 413
Mexico +52 55 5809 5010 France +33 (0) 800 917
Argentina +54 11 4809 2700 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy +39 8008 77334 China +86 21 2892 9000
Chile +56 2 2928 4800 Central & Eastern +41 (0) 41 7686
Peru +51 15190130 Russia/CIS +7 495 995 9559 South Korea +82 2 3438 4600
Europe and Middle East Asia Pacific
New Zealand 099 128 804
6666
India 800 440 1468
901
Japan +81 3 5769 6803
111
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
2
Page 3
Supplement Contents
MMI-20026578 January 2022

Contents

Chapter 1 Before you begin........................................................................................................5
1.1 About this application manual..................................................................................................... 5
1.2 ProLink III requirements............................................................................................................... 5
1.3 Ordering options......................................................................................................................... 6
1.4 Additional documentation from Micro Motion ............................................................................6
1.5 Terms and definitions.................................................................................................................. 7
1.6 PVR, TBR, and TMR applications...................................................................................................8
Chapter 2 Production Volume Reconciliation (PVR).................................................................. 11
2.1 Understanding the PVR application............................................................................................11
2.2 Density determination...............................................................................................................14
2.3 Configure Production Volume Reconciliation (PVR) using ProLink III ......................................... 18
Chapter 3 Transient Bubble Remediation (TBR)........................................................................ 21
3.1 Understanding the TBR application............................................................................................21
3.2 Configure Transient Bubble Remediation (TBR) using ProLink III ................................................23
Chapter 4 Transient Mist Remediation (TMR)........................................................................... 25
4.1 Understanding the TMR application...........................................................................................25
4.2 Configure Transient Mist Remediation (TMR) using ProLink III ...................................................27
Chapter 5 Display variables...................................................................................................... 29
5.1 Display variables available with PVR, TBR, and TMR....................................................................29
Appendix A Application parameters and data............................................................................. 31
A.1 PVR parameters and data.......................................................................................................... 31
A.2 TBR parameters and data...........................................................................................................37
A.3 TMR parameters and data..........................................................................................................38
Appendix B Best practices for two-phase measurement performance......................................... 41
B.1 Entrained gas performance........................................................................................................41
B.2 Entrained liquid (mist) performance.......................................................................................... 42
B.3 Density determination...............................................................................................................44
Supplement 3
Page 4
Contents Supplement
January 2022 MMI-20026578
4 Micro Motion Multiphase Applications
Page 5
Supplement Before you begin
MMI-20026578 January 2022

1 Before you begin

1.1 About this application manual

This application manual explains how to configure the Production Volume Reconciliation application (PVR), the Transient Bubble Remediation application (TBR), and the Transient Mist Remediation application (TMR), using ProLink III.
These three applications are available for Micro Motion MVD™ Coriolis meters in an MVD Direct Connect installation.
PVR, TMR, and TBR are also available for Micro Motion Model 1500, Model 1700, Model 2500, and Model 2700 transmitters.
This application manual does not provide information on installation of any sensors or transmitters, or on general configuration. This information can be found in the applicable sensor installation manual, transmitter installation manual, or transmitter configuration manual.
Related information
Additional documentation from Micro Motion

1.2 ProLink III requirements

To use this manual, you must have ProLink III Professional v4.0 or later, and you must be able to connect from ProLink III to the transmitter or core processor.
Supplement 5
Page 6
Before you begin Supplement
January 2022 MMI-20026578

1.3 Ordering options

For 800 core processor direct connect installations, PVR, TBR, and TMR are available as Engineering To Order (ETO) applications. PVR and TMR are available individually or in combination with Smart Meter Verification.
PVR, TMR, and TBR features are now available in the standard product when ordered on 1500, 1700, and 2500 Transmitter Models. The ETO is not required on the 800 core processor when used with a transmitter.
To order one of these applications, an ETO must be purchased for the core processor (see
Table 1-1). This ETO enables use of the application in an MVD™ Direct Connect installation.
Table 1-1: Core processor ETOs for PVR, TBR, and TMR
Application Direct connect
core processor
PVR Enhanced 22166 22701 Mixture of oil and
TBR Enhanced 13386 25699 Liquid with gas Liquid flow rate and
Standard 12806 Not available. Liquid with gas Liquid flow rate and
TMR Enhanced 18922 22706 Gas with entrained
Individual application
ETO number Process fluid Desired
Application with Smart Meter Verification (SMV)
water
liquid (mist)
measurement
Net oil (dry oil at reference conditions) and net water flow
totals
totals
Gas flow rate and totals
Restriction
Only one ETO can be installed in the transmitter or core processor at a time.

1.4 Additional documentation from Micro Motion

Table 1-2: Additional documentation for PVR, TBR, and TMR installations
Document Use
Micro Motion® MVD™ Direct Connect Meters: Installation Manual
Sensor installation manual for your sensor Installation and wiring for the sensor
Configuration manual for your transmitter Configuration, operation, maintenance, and
ProLink III User Manual
Modbus Interface Tool
6 Micro Motion Multiphase Applications
Installation and wiring for the MVD Direct Connect flowmeter
troubleshooting for features that are not related to PVR, TBR, or TMR
Installation and use of ProLink III
Programming the Modbus host
Page 7
Supplement Before you begin
MMI-20026578 January 2022

1.5 Terms and definitions

The terms used to describe Multiphase applications vary widely. This manual, and the PVR, TBR, and TMR applications, use the terms defined here.
Terms used in PVR, TBR, and TMR
at Reference
At Line
At Reference density
At Line volume
At Reference volume
Mixture
Water cut
Entrained, entrainment
Remediation
Shrinkage
The process of calculating the value of a process variable at reference temperature, starting from the value of the process variable at line temperature (the measured value)
The density of the process fluid at line temperature
The density of the process fluid at reference temperature (60 °F) that is equivalent to its density at line temperature
The volume of the process fluid at line temperature
The volume of the process fluid at reference temperature (60 °F) that is equivalent to its volume at line temperature
The process fluid before separation, such as a combination of oil and water, or gas, oil, and water
The volume fraction of water in the liquid mixture, in %
The presence of small amounts of gas in a liquid stream, or liquid in a gas stream
An adjustment applied to a process variable during periods of entrained gas or mist when a substitute density value has been used for volume calculation (PVR and TBR) or the flow rate has been increased or decreased to compensate for unmeasured flow (TMR).
The change in liquid volume between the measurement point and a stock tank due to lighter hydrocarbons evaporating. This is caused by the stock tank being at a lower pressure, further below the bubble point of the oil. The shrinkage factor is a user-input factor, based on a PVT (pressure-volume-temperature) test of the oil.
Shrinkage Meter Factor
These terms can be combined in several ways to describe different process variables. The following table provides several examples, but is not a complete list of possibilities.
Table 1-3: Examples of process variable names
Process variable name Description
Volume Total (unremediated) The total, by volume, of the mixture (oil/water/gas combination),
Volume Total (remediated) The total, by volume, of the oil/water minus the volume
Supplement 7
Used just like the normal Meter Factor, when proving the meter against liquid measurement at stock tank conditions.
as measured
attributable to gas
Page 8
Before you begin
January 2022 MMI-20026578
Table 1-3: Examples of process variable names (continued)
Process variable name Description
Oil Total at Line The total amount of oil measured since the last totalizer reset, at
line temperature, with no adjustment for temperature variation
Water Cut at Reference The percentage of water in the oil, as if the measurement had
been taken at 60 °F
Supplement

1.6 PVR, TBR, and TMR applications

PVR, TBR, and TMR are applications designed to provide more accurate process data in the presence of multiple phases. For example, if bubbles are present in the process fluid, or the process fluid is flashing, the volume measurements are often incorrect.
Production Volume Reconciliation (PVR)
Provides oil and water volumes through density-based calculations for both line and
reference conditions
Detects bubble entrainment or flashing in the sensor, and can correct volumes
accordingly
Best for undersized three-phase separators that frequently have intermittent gas or
water contamination in the oil leg
Offers a simple, low-cost solution for net oil and net water measurement for two-phase
separators
Transient Bubble Remediation (TBR)
Used with single-component liquid streams that may experience intermittent low
levels of gas entrainment, that is, gas carryunder
Enables accurate measurement of a single fluid during periods of entrained gas by
providing a substitute density value based on the immediately preceding process density (standard configuration)
Tracks total time of aerated flow to assist in diagnosing process issues that may cause
aeration
Transient Mist Remediation (TMR)
Used with gas streams that may experience intermittent low levels of liquid
entrainment, i.e., liquid carry-over
Allows gas measurement to continue during periods of entrained liquid (mist) by
providing a substitute flow rate value based on the immediately preceding process flow rate
Returns to reporting the measured flow rate when the mist interval is over, increased
or decreased by a maximum of 10%, until flow totals are appropriately adjusted for the unmeasured flow
Provides an indication of the amount of time that liquid was present in the stream —
identifying process improvements to reduce gas stream contamination
8 Micro Motion Multiphase Applications
Page 9
Supplement Before you begin
MMI-20026578 January 2022

1.6.1 Illustrations of PVR, TBR, and TMR installations

PVR, TBR, and TMR can be used with two-phase separators and three-phase separators.
Note
These illustrations do not show all possible combinations.
Figure 1-1: PVR, TBR, or TMR with two-phase separator
A. From wellhead B. Separator C. Gas leg
D. Oil/water leg
E. Coriolis sensor with PVR or TBR F. Coriolis sensor with TMR
G. Modbus host (flow computer)
Supplement 9
Page 10
Before you begin Supplement
January 2022 MMI-20026578
Figure 1-2: PVR, TBR, or TMR with three-phase separator
A. From wellhead B. Separator C. Water leg
D. Oil leg
E. Gas leg F. Coriolis sensor with PVR or TBR
G. Coriolis sensor with PVR (optional, used in applications where oil measurement is needed in the water leg to
detect a malfunctioning separator)
H. Coriolis sensor with TMR
I. Modbus host (flow computer)
10 Micro Motion Multiphase Applications
Page 11
A
B
C
t
ρ
D

Supplement Production Volume Reconciliation (PVR)

MMI-20026578 January 2022
2 Production Volume Reconciliation
(PVR)

2.1 Understanding the PVR application

PVR is used in oil and gas separation applications to compensate for gas and/or water contamination in the oil leg of a three-phase separator. It is also used to quantify the oil and water volumes in the liquid leg of a two-phase separator.
PVR uses the meter's drive gain to indicate if there is entrained gas or transient bubbles in the liquid stream, and adjust the measurement accordingly. Under normal circumstances, i.e., no entrained gas or bubbles, the application uses the Net Oil Computer (NOC) algorithm to calculate and quantify the volumes of oil and water in the liquid stream.
Net Oil Computer (NOC)
The Net Oil Computer algorithm calculates the water fraction of the liquid stream so that the amount of oil and the amount of water can be determined. The algorithm measures the volume of oil, corrected to a reference temperature, that is contained within the gross volume of produced fluid.
Compensating for gas in the liquid
Entrained gas, or bubbles in the process fluid, has a negative effect on liquid volume measurement accuracy. The Coriolis sensor calculates volume based on direct density and mass measurements. When a bubble is present, mixture density is reduced, causing the reported volume to be higher than the actual liquid volume. The presence of bubbles is reflected in the drive gain. The following figure shows how the change in drive gain affects density measurement.
Figure 2-1: Effect of transient bubbles on drive gain and density measurement
A. Density
B. Drive gain (actual) C. Transient bubble condition D. Drive gain (%)
Supplement 11
Page 12
Production Volume Reconciliation (PVR) Supplement
January 2022 MMI-20026578
A transient bubble condition is defined in terms of the sensor's drive gain: If the drive gain exceeds the configured threshold for more than a specified interval, the selected PVR action is performed. The transient bubble interval persists until drive gain is below the configured threshold for the specified interval.
PVR volume calculation during bubble events
If the drive gain threshold is exceeded, the volume calculation for the period of high drive gain can be handled in one of three ways.
Option Description
Hold Last Value
Use Input Density of Dry Oil Converted to Line Conditions
Alert Only
Use an average density value from an earlier point in the process to calculate volume. If this option is chosen, the water cut from the point just before the bubble event is effectively held constant throughout the bubble event.
Convert the density of dry oil at reference temperature (a user­configured value) to density at line temperature, and calculate volume. This option assumes that all volume during the bubble event is dry oil.
Post an alert.
12 Micro Motion Multiphase Applications
Page 13
C
B
E
A
F
D D
Supplement Production Volume Reconciliation (PVR)
MMI-20026578 January 2022
Processing for Hold Last Value
This option directs the application to retrieve measured density data from an earlier point in the process. The earlier point is identified by the configured PVR Lookback Period. The density values around this point are averaged, and this average is then used in oil calculations.
The following figure shows the substitution of average density data during the transient bubble interval.
Figure 2-2: Hold Last Value in operation
A. Density
B. PVR Drive Gain Threshold C. Drive gain (actual) D. PVR Lookback Period
E. Averaged density values
F. Drive gain (%)
Note
If the point defined by PVR Lookback Period happens to fall into a previous transient bubble interval, the application automatically extends the lookback interval as required so that the average is calculated from measured density data rather than substituted density values. In the illustration, the first average is applied to several transient bubble events.
Supplement 13
Page 14
Production Volume Reconciliation (PVR) Supplement
January 2022 MMI-20026578

2.2 Density determination

To configure Production Volume Reconciliation (PVR), you must know the density of dry oil at reference temperature, and the density of produced water at reference temperature.
Related information
Density determination using the data log from ProLink III Density determination using a petroleum laboratory

2.2.1 Density determination using the data log from ProLink III

To configure Production Volume Reconciliation (PVR), you must know the density of dry oil at reference temperature, and the density of produced water at reference temperature. You can use log data from ProLink III, with the Oil & Water Density Calculator, to obtain these values.
Note
Even after separation, oil typically contains some amount of interstitial water. The water cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil.
This procedure assumes the following:
The highest density value in the logged data represents produced water.
The lowest density value in the logged data represents dry oil.
Prerequisites
You must be able to connect to the transmitter or core processor with ProLink III.
You must know how to use the data logging feature in ProLink III.
You must be able to run data logging for the necessary time period, which may be a few minutes or a few hours, depending on your separator.
You must have the Oil & Water Density Calculator. This is a spreadsheet tool developed by Micro Motion. You can obtain a copy from your Micro Motion representative.
Procedure
1. Connect to the core processor or transmitter with ProLink III.
For two-phase separators, connect to the core processor or transmitter on the
oil/water leg. See Figure 1-1.
For three-phase separators, connect to the core processor or transmitter on the
oil leg. See Figure 1-2.
2. Set up data logging to record the following process variables, with a logging interval of 1 second:
Mass flow rate
Volume flow rate
Density
Temperature
14 Micro Motion Multiphase Applications
Page 15
Supplement Production Volume Reconciliation (PVR)
MMI-20026578 January 2022
Drive gain
3. Collect data.
a) Open the level control valve on the separator, and allow the separator to
drop to the lowest safe level, or until gas is first drawn into the liquid leg.
b) Close the level control valve and allow the level to rise to the maximum safe
level.
This will increase the residence time for the liquid in the separator, and may allow the water to settle to the bottom and the oil to rise to the top.
c) Open the level control valve partially, so that the level drops slowly.
d) Start data logging.
e) Allow the separator to drop to the lowest safe level, or until gas is first drawn
into the liquid leg.
f) Stop data logging.
g) Return the separator to automatic level control.
4. Obtain maximum and minimum density data from the log.
Shortly after the control valve is opened or the dump phase begins, you should see the temperature stabilizing and the density rising to a maximum value and stabilizing. This may represent produced water. Just before the lowest safe level, or before the point where gas is drawn into the liquid leg, you should see the density falling to a minimum value and stabilizing. This may represent dry oil.
a) Record the maximum density and the corresponding temperature.
b) Record the minimum density and the corresponding temperature.
Important
Never use an unstable density value, or any density value that has an elevated drive gain.
5. Use the Oil & Water Density Calculator to calculate the density of dry oil at reference temperature and the density of produced water at reference temperature.
Tip
Unless the oil is light hot condensate, the oil will almost always contain some interstitial water. This is generally acceptable for allocation measurements. However, if further accuracy is desired, you can determine the water cut and use it in the calculation. To determine or estimate the water cut, take a shakeout sample from one of the following:
The current flow/dump cycle, at the time of minimum density
Similar oils produced from the same reservoir
The tank or tanks that the separator flows into
Enter this water cut into the Oil & Water Density Calculator to calculate the density of dry oil at reference temperature.
Supplement 15
Page 16
Production Volume Reconciliation (PVR) Supplement
January 2022 MMI-20026578

2.2.2 Density determination using a petroleum laboratory

To configure Production Volume Reconciliation (PVR), you must know the density of dry oil at reference temperature, and the density of produced water at reference temperature. You can obtain this values from a petroleum laboratory.
Note
Even after separation, oil typically contains some amount of interstitial water. The water cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil.
Important
If you are using a three-phase separator, you can collect the oil sample and the water sample separately, after separation, or you can collect one sample before separation and have the laboratory perform the separation.
If you are using a two-phase separator, you should collect one sample before separation and have the laboratory perform the separation.
Prerequisites
The petroleum laboratory must be able to meet these requirements:
The laboratory density meter must be able to keep the oil sample pressurized at line
pressure during the density measurement.
The sample cylinder must be a constant-pressure type, and must be properly rated for
the oil–water composition and for sample pressure.
The oil density measurement units should be in g/cm³ at reference temperature and/or
°API at reference temperature. The water density measurement should be in g/cm³ at reference temperature. PVR requires a reference temperature of 60 °F. Be sure to specify this to the petroleum laboratory, as some countries use other reference temperatures.
The laboratory report must include the oil density, water density, and the reference
temperature.
The sample must be collected by a qualified person, using industry-accepted safety standards.
You must know the minimum required sample size. This varies depending on the water cut and the volume of the sample cylinder. Consult the petroleum laboratory for specific values.
You must be able to collect and maintain the oil sample at line pressure, so that the oil will not lose pressure and outgas.
If you collect the water sample separately, you must be able to protect it from contamination and evaporation.
Procedure
1. Communicate the handling and measurement requirements to the petroleum
laboratory.
2. If you are collecting one sample that contains both oil and water, identify the point
in the line where the sample will be taken.
16 Micro Motion Multiphase Applications
Page 17
Supplement Production Volume Reconciliation (PVR)
MMI-20026578 January 2022
Recommendations:
Collect the sample upstream from the separator, at a point where the fluid is
well mixed. Fluid in the oil/water leg exiting the separator may not be well mixed.
The process fluid at the sample point should be representative of the process
fluid flowing through the sensor on the oil/water leg.
The line pressure at the sample point should be close to the line pressure at the
sensor.
Collect the sample from the bottom of the pipe to minimize the amount of gas
in the sample.
3. If you are using a three-phase separator and collecting the oil and water samples separately, identify the points where the samples will be taken.
Recommendations:
The sample point for oil must be on the oil leg, as close to the sensor as possible.
See Figure 1-2.
The line pressure at the oil sample point should be similar to the line pressure at
the sensor.
The sample point for water must be on the water leg, as close to the sensor as
possible. See Figure 1-2.
Note
If you have a Micro Motion sensor on the water leg, you may be able to use the data logging procedure described in Density determination using the data log
from ProLink III to determine the water density.
4. If you are using a three-phase separator and collecting the oil and water samples separately, wait until separation has occurred.
5. Collect the sample or samples, meeting all requirements for pressure and protection from contamination or evaporation.
6. Mark and tag the sample or samples with the well name or number, time and date, sample type, and line pressure.
7. Transport the samples to the laboratory safely, as soon as is practical.
Postrequisites
If the laboratory measurements were not corrected to your reference temperature, use the Oil & Water Density Calculator to calculate density at reference temperature. This is a spreadsheet tool developed by Micro Motion. You can obtain a copy from your Micro Motion representative.
Supplement 17
Page 18
Production Volume Reconciliation (PVR) Supplement
January 2022 MMI-20026578

2.3 Configure Production Volume Reconciliation (PVR) using ProLink III

PVR is used with three-phase separators to remove gas and/or water contamination from oil measurement on the oil leg, and to quantify the net oil and net water in the liquid leg of a two-phase separator.
Prerequisites
You must know the density of dry oil from this well, at reference temperature and reference pressure.
You must know the density of water at reference temperature.
Procedure
1. Choose Device Tools Configuration Process Measurement Production Volume Reconciliation (PVR).
2. Enable the PVR application.
3. Set Reference Temperature to the temperature to be used to calculate standard density.
In most cases, this is the reference temperature used during density determination.
4. Enter the density of dry oil from this well at the configured reference temperature.
5. Enter the density of produced water at the configured reference temperature.
6. Set PVR Drive Gain Threshold to the value of drive gain, in percent, that indicates the presence of bubbles in the process fluid.
At drive gain values above this threshold, the transmitter will implement the configured PVR action.
7. Set PVR Drive Gain Threshold High to the value of drive gain, in percent, that indicates a significant amount of gas in the process fluid.
At drive gain values above this threshold, the transmitter will post an alert.
8. Set PVR Action to the action that the transmitter will perform when PVR remediation is active.
Option
Hold Last Value The transmitter will calculate volume using a
Use Input Density of Dry Oil Converted to Line Conditions
Description
substitute density value. The substitute value is an average of the data around a recent point in the process.
The transmitter will calculate volume using the configured value for oil density, converted to line temperature.
Alert Only The transmitter will post an alert.
18 Micro Motion Multiphase Applications
Page 19
Supplement Production Volume Reconciliation (PVR)
MMI-20026578 January 2022
As soon as the drive gain drops below PVR Drive Gain Threshold, the transmitter returns to reporting standard density.
9. If you set PVR Action to Hold Last Value, set PVR Lookback Period to the number of seconds the transmitter will go back in process history to retrieve and average process data.
10. Enable or disable PVR Timeout as desired.
Option Description
Enabled If PVR actions are applied for the number of seconds specified in PVR
Timeout Value, the transmitter performs the configured TBR Timeout Action.
Disabled PVR actions continue until the drive gain drops below PVR Drive Gain
Threshold.
11. If you enabled PVR Timeout:
a) Set PVR Timeout Value to the number of seconds that the transmitter will
perform the PVR action before implementing PVR Timeout Action.
b) Set PVR Timeout Action to the action that the transmitter will perform if the
PVR timeout is reached.
Option
Alert The transmitter posts an alert, and continues PVR
Normal Measurement The transmitter returns to normal measurement, and
Description
actions.
does not post an alert.
Note
For the location of parameters not exclusive to the PVR software, refer to the transmitter configuration and use manual.
Supplement 19
Page 20
Production Volume Reconciliation (PVR) Supplement
January 2022 MMI-20026578
20 Micro Motion Multiphase Applications
Page 21
Supplement Transient Bubble Remediation (TBR)
MMI-20026578 January 2022

3 Transient Bubble Remediation (TBR)

3.1 Understanding the TBR application

Transient Bubble Remediation (TBR) is indicated for use with liquid streams that may experience intermittent low levels of gas entrainment, i.e., gas carry-under. In the standard configuration, TBR enables accurate oil measurement during periods of entrained gas by providing a substitute density value based on the immediately preceding process density.
Liquid with gas measurement process
The presence of entrained gas (or bubbles) can cause significant errors when measuring the volume flow of liquid through a Coriolis meter. Because bubbles displace some of the liquid in a flow stream, the measured volume of the mixture may differ from the actual amount of liquid that emerges from the pipe downstream.
So how can you tell when a liquid contains gas? When bubbles are present in a liquid stream, Coriolis meters will report an increase in drive gain coinciding with a decrease in both fluid density liquid-gas mixture. Therefore, in order to measure only the liquid portion of the stream, the volume of the bubbles must be ignored or subtracted from the mixture total. software performs exactly this function, using drive gain as the diagnostic indication that bubbles or entrained gas is present in the liquid flow stream, and then substituting a liquid-only density in place of the live measurement until the gaseous event has subsided. When the gassy portion has passed, indicated by an associated drop in drive gain, the software returns to reporting the live measured volume flow rate.
(1)
and mass flow rate due to the lower amount of mass contained in the
(2)
TBR
Compensating for gas in the liquid
Entrained gas, or bubbles in the process fluid, has a negative effect on measurement accuracy, because entrained gas causes abrupt increases in drive gain, and the density measurement of the mixture is temporarily low. The following figure shows how the change in drive gain affects density measurement.
(1) High frequency sensors may erroneously report a higher fluid density when entrained gas is present, and therefore are not
recommended for use on liquids with entrained gas. High frequency sensors include F300, H300, and all T-Series sensors.
(2) The unmeasured gases can be (and are often) collected and processed separately downstream if desired (using a separator
for example).
Supplement 21
Page 22
A
B
C
t
ρ
D
Transient Bubble Remediation (TBR) Supplement
January 2022 MMI-20026578
Figure 3-1: Effect of transient bubbles on drive gain and density measurement
A. Drive gain (actual)
B. Density C. Transient bubble condition D. Drive gain (%)
A transient bubble condition is defined in terms of the sensor's drive gain: If the drive gain exceeds the configured threshold, the selected TBR action is performed. The transient bubble interval persists until drive gain is below the configured threshold.
TBR actions
The TBR application can perform either of the following actions if transient bubbles are detected:
Alert Only
Hold Last Value
Post an alert
Report an average value from an earlier point in the process
Processing for Hold Last Value
This option directs the application to retrieve measured density data from an earlier point in the process. The earlier point is identified by the configured TBR Lookback Period. The density values around this point are averaged, and this average is then used in net oil calculations.
The following figure shows the substitution of average density data during the transient bubble interval.
22 Micro Motion Multiphase Applications
Page 23
C
B
E
A
F
D D
Supplement Transient Bubble Remediation (TBR)
MMI-20026578 January 2022
Figure 3-2: Hold Last Value in operation
A. Density
B. TBR Drive Gain Threshold C. Drive gain (actual) D. TBR Lookback Period
E. Averaged density values
F. Drive gain (%)
Note
If the point defined by TBR Lookback Period happens to fall into a previous transient bubble interval, the application automatically extends the lookback interval as required so that the average is calculated from measured density data rather than substituted density values.

3.2 Configure Transient Bubble Remediation (TBR) using ProLink III

TBR is used with liquid streams that may experience intermittent low levels of gas entrainment. TBR allows the system to detect transient bubble conditions, and to take either of two actions in response.
Procedure
1. Choose Device Tools Configuration Process Measurement Transient Bubble Remediation (TBR).
2. Set TBR Drive Gain Threshold to the value of drive gain, in percent, that indicates the presence of bubbles in the process fluid.
Supplement 23
Page 24
Transient Bubble Remediation (TBR) Supplement
January 2022 MMI-20026578
At drive gain values above this threshold, the transmitter will implement the configured TBR actions.
3. Set TBR Action to the action that the transmitter will perform when TBR is active.
Option Description
Hold Last Value The transmitter will calculate volume using a substitute density
value. The substitute value is an average of the data around a recent point in the process.
Alert Only The transmitter will post an alert.
4. If you set TBR Action to Hold Last Value, set Lookback Period to the number of seconds the transmitter will go back in process history to retrieve and average process data.
5. Enable or disable TBR Timeout as desired.
Option Description
Enabled If TBR is active for the number of seconds specified in TBR Timeout
Value, the transmitter performs the configured TBR Timeout Action.
Disabled TBR actions continue until the drive gain drops below TBR Drive Gain
Threshold.
6. If you enabled TBR Timeout:
a) Set TBR Timeout Value to the number of seconds that the transmitter will
perform TBR before implementing TBR Timeout Action.
b) Set TBR Timeout Action to the action that the transmitter will perform if the
TBR timeout is reached.
Option
Alert The transmitter returns to normal measurement and
Normal Measurement The transmitter returns to normal measurement, and
Description
an alert is posted..
does not post an alert.
Note
For the location of parameters not exclusive to the TBR software, refer to the transmitter configuration and use manual.
24 Micro Motion Multiphase Applications
Page 25
Supplement Transient Mist Remediation (TMR)
MMI-20026578 January 2022

4 Transient Mist Remediation (TMR)

4.1 Understanding the TMR application

TMR is designed for use with gas streams that may experience intermittent low levels of liquid entrainment, i.e., liquid carry-over.
Entrained liquid, or mist in the process fluid, has a negative effect on measurement accuracy, because entrained liquid causes abrupt increases in drive gain, and the density measurement is temporarily low. TMR allows gas measurement to continue during periods of entrained liquid (mist) by providing a substitute flow rate value based on the immediately preceding process flow rate. When the mist interval is over, TMR returns to reporting the measured flow rate, increased or decreased by a maximum of 10%, until flow totals are appropriately adjusted for the unmeasured flow.
A transient mist condition is defined in terms of the sensor's drive gain: If the drive gain exceeds the configured threshold, the transmitter automatically performs transient mist remediation. The transient mist interval persists until drive gain is below the configured threshold.
The following figure illustrates TMR processing.
Supplement 25
Page 26
A
H
H
G G
E
E
F F
B
C
D D
Transient Mist Remediation (TMR) Supplement
January 2022 MMI-20026578
Figure 4-1: TMR in operation
A. Flow rate
B. TMR Drive Gain Threshold C. Drive gain (actual) D. Pre-Mist Averaging Period and source of M1
E. Averaged flow rate values
F. Post-Mist Adjustment Delay and source of M2 G. Adjustment period H. Adjusted flow rate values
When TMR is detected, the transmitter substitutes an average flow rate value, M1, for the measured flow rate, for the entire transient mist interval. The substitute flow rate is calculated from the actual flow rate data for the previous n seconds, where n is determined by the setting of Pre-Mist Averaging Period.
When the transient mist interval is over, the transmitter waits for the number of seconds specified by Post-Mist Adjustment Delay. During that period, the transmitter calculates a second average flow rate, M2. M1 and M2 are then averaged, producing an approximate value for the actual flow rate during the transient mist interval. The measured flow rate is then increased or decreased by a maximum of 10% until the flow total has been compensated for all of the unmeasured flow.
26 Micro Motion Multiphase Applications
Page 27
Supplement Transient Mist Remediation (TMR)
MMI-20026578 January 2022

4.2 Configure Transient Mist Remediation (TMR) using ProLink III

TMR is designed for use with gas streams that may experience intermittent low levels of liquid entrainment.
Procedure
1. Choose Device Tools Configuration Process Measurement Transient Mist Remediation (TMR).
2. Enable the TMR application.
3. Set TMR Drive Gain Threshold to the value of drive gain, in percent, that indicates the presence of mist in the process fluid.
At drive gain values above this threshold, the transmitter will initiate TMR.
4. Set Pre-Mist Averaging Period to the number of seconds over which flow rate will be averaged to produce a substitute flow rate.
When mist is detected, the transmitter retrieves the most recent flow rate data for the specified number of seconds, averages the data, and reports the result rather than the measured flow rate.
5. Set Post-Mist Adjustment Delay to the number of seconds that the transmitter will wait, after mist is detected, before beginning TMR adjustment.
During TMR adjustment, the transmitter increases or decreases the measured flow rate by a maximum of 10%. The TMR adjustment continues until the flow total has been completely compensated for the unmeasured flow.
Note
For the location of parameters not exclusive to the TMR software, refer to the transmitter configuration and use manual.
Supplement 27
Page 28
Transient Mist Remediation (TMR) Supplement
January 2022 MMI-20026578
28 Micro Motion Multiphase Applications
Page 29
Supplement Display variables
MMI-20026578 January 2022

5 Display variables

5.1 Display variables available with PVR, TBR, and TMR

When PVR, TBR, or TMR is implemented on your transmitter, additional application­specific process variables are available to configure as display variables.
The following table lists the process variables that are available for configuration as display variables. For instructions on configuring display variables, see the configuration manual for your transmitter.
Table 5-1: Process variables available as display variables
Process variable Application
PVR TBR TMR
Oil Total At Line
Water Total At Line
Water Cut At Line
Accumulated TBR Time
Mass Flow (unremediated)
Mass Total (unremediated)
Mass Inventory (unremediated)
Mass Flow (remediated)
Mass Total (remediated)
Mass Inventory (remediated)
Meastured Oil Density At Reference (Fixed API Units)
Meastured Oil Density At Reference (Fixed SGU Units)
Oil Flow Rate At Line
Oil Flow Rate At Reference
Oil Total At Reference
Unremediated Density At Line
Unremediated Volume Flow At Line
Unremediated Volune Total At Line
Volume Flow (remediated)
Volume Total (remediated)
Volume Inventory (remediated)
Supplement 29
Page 30
Display variables Supplement
January 2022 MMI-20026578
Table 5-1: Process variables available as display variables (continued)
Process variable Application
PVR TBR TMR
Water Cut At Reference
Water Flow Rate At Line
Water Flow Rate At Reference
Water Total At Reference
30 Micro Motion Multiphase Applications
Page 31
Supplement Application parameters and data
MMI-20026578 January 2022

A Application parameters and data

To use Modbus to configure other parameters, see the Micro Motion Modbus Interface Tool.
This information is provided for completeness.

A.1 PVR parameters and data

Table A-1: PVR configuration parameters
Parameter Description Modbus location and data type
Application Status Enabled/disabled Coil 75, coil 246 (write to both coils)
0=Disabled
1=Enabled
Density of Dry Oil at Reference Temperature
Density of Water at Reference Temperature
PVR Drive Gain Threshold The drive gain, in %, that
PVR Drive Gain Threshold High
PVR Action The remediation action to
Density of dry oil from this well, in g/cm³, at 60 °F
Density of produced water from this well, in g/cm³, at 60 °F
triggers the configured PVR remediation action
The drive gain, in %, that represents a significant amount of gas in the liquid stream. The transmitter sets a flag.
be implemented
1959–1960, Float
1831–1832, Float
617–618, Float
343–344, Float
ETO ≤ v3.95 624 Bit 0, U16
0=Calculate volume from a substitute
density value, derived from averaged density values from an earlier point in the process
1=Alert only
ETO > v3.95 4450, U16
0=Calculate volume from a substitute
density value, derived from averaged density values from an earlier point in the process
1=Alert only
2=Calculate volume using the
configured value for oil density, converted to line temperature
PVR Lookback Period The number of seconds to
go back to determine a substitute density value
Supplement 31
620, U16
Page 32
Application parameters and data Supplement
January 2022 MMI-20026578
Table A-1: PVR configuration parameters (continued)
Parameter Description Modbus location and data type
PVR Timeout Enable or disable a
timeout on the PVR remediation action
PVR Timeout Value The number of seconds
that PVR remediation will be performed before timing out
PVR Timeout Action The action to be
performed if PVR remediation times out
Enable Shrinkage Factor Adjusted Volume Flow Outputs
Shrinkage Factor User-defined oil shrinkage
Shrinkage Meter Factor User-defiined oil
Enables a set of variables that are adjusted for user­defined oil shrinkage
value, using a no-flow computer.
shrinkage value using the meter/transmitter. Users can restrict the meter factor to the shrinkage factor level for easier record keeping.
624 Bit 6, U16
0=Disabled
1=Enabled
619, U16
624 Bit 1, U16
0=Normal Measurement
1-Alert
Coil 376
1689-1960, Float
3992-3993, Float
Sales Density Enables comparison of
produced density to sales density to determine the shrinkage factor.
Table A-2: PVR application status
Modbus location and data type
52–55, 8–byte ASCII
Value Description
DENSHI The calculated uncorrected water cut is greater than 100%. Water
DENSLO The calculated uncorrected water cut is less than 0%. Water cut is
GVF_HI The GVF is high; drive gain is higher than PVR Drive Gain Threshold
GVF_LO The GVF is low; drive gain is between PVR Drive Gain Threshold and
(eight space characters)
4465-4466, Float
cut is reported as 100%.
reported as 0%.
High.
PVR Drive Gain Threshold High.
No condition is active.
32 Micro Motion Multiphase Applications
Page 33
Supplement Application parameters and data
MMI-20026578 January 2022
Table A-3: PVR process variables
Process variable Value Modbus location
No entrained gas detected
Entrained gas detected
and data type
Water Cut At Line Calculated water cut at line
conditions
Water Cut At Reference
Water Flow Rate At Line
(1)
Calculated water cut at 60 °F Core Processor ETO < v4.13:01557–1558, Float
(1)
Net volume flow rate of the water at line conditions
Core Processor ETO < v4.13:01555–1556, Float
Core Processor ETO ≥ v4.13:
PVR Action=0 or 1:
Calculated water cut at line conditions
PVR Action=2: 0
Core Processor ETO ≥ v4.13:
PVR Action=0 or 1:
Calculated water cut at 60 °F
PVR Action=2: 0
Core Processor ETO < v4.13:01561–1562, Float
Core Processor ETO ≥ v4.13:
PVR Action=0 or 1: Net
volume flow rate at line conditions
PVR Action=2: 0
Water Total At Reference
(1)
Net volume flow rate of the
0 1549–1550, Float
water at 60 °F
Water Total At Line Net volume total of the
water at line conditions, incrementing
Core Processor ETO < v4.13: Net volume total of the water at line conditions held
1667–1668, Float
at previous value; total does not increment
Core Processor ETO ≥ v4.13:
PVR Action=0 or 1: Net
volume flow rate at line conditions, incrementing
PVR Action=2: Net
volume total of the water at line conditions held at previous value; total does not increment
Supplement 33
Page 34
Application parameters and data Supplement
January 2022 MMI-20026578
Table A-3: PVR process variables (continued)
Process variable Value Modbus location
and data type
1663–1664, Float
Water Total At Reference
No entrained gas detected
(1)
Net volume total of the water at 60 °F, incrementing
Entrained gas detected
Core Processor ETO < v4.13: Net volume total of the water at 60 °F held at previous value; total does not increment
Core Processor ETO ≥ v4.13:
PVR Action=0 or 1: Net
volume flow rate at 60 °F, incrementing
PVR Action=2: Net
volume total of the water at 60 °F held at previous value; total does not increment
Oil Density At Line (Fixed SGU Units)
(1)
Density of the oil at 60 °F (user-specified), converted to line conditions using line temperature and API Even Table Correction for “A Tables” (Temp DensityOil
@60F
,
@Line
), then
reported in SGU units
Oil Density At Line (Fixed API
(1)
Units)
Density of the oil at 60 °F (user-specified), converted to line conditions using line temperature and API Even Table Correction for “A Tables” (Temp DensityOil
@60F
,
@Line
), reported in
°API
Oil Flow Rate At Line
(1)
Volume flow rate of oil at line conditions
Oil Flow Rate At Reference
(1)
Volume flow rate of oil at 60 °F
Oil Total Rate At Line Net volume total of the oil at
line conditions
Oil Total At Reference
(1)
Net volume total of the oil at 60 °F
Density of the oil at 60 °F (user-specified), converted to line conditions using line temperature and API Even Table Correction for “A Tables” (Temp DensityOil
@60F
,
@Line
), then
reported in SGU units
Density of the oil at 60 °F (user-specified), converted to line conditions using line temperature and API Even Table Correction for “A Tables” (Temp DensityOil
@60F
,
@Line
), reported in
°API
Volume flow rate of oil at line conditions
Volume flow rate of oil at 60 °F
Net volume total of the oil at line conditions
Net volume total of the oil at 60 °F
345–346, Float
347–348, Float
1553–1554, Float
1547–1548, Float
1665–1666, Float
1661–1662, Float
Density Density of the oil and water
mixture, at line conditions
Core Processor ETO < v4.13: Remediated density of the
249–250, Float
mixture at line conditions, with the configured TBR action applied
34 Micro Motion Multiphase Applications
Page 35
Supplement Application parameters and data
MMI-20026578 January 2022
Table A-3: PVR process variables (continued)
Process variable Value Modbus location
No entrained gas detected
Entrained gas detected
Core Processor ETO ≥ v4.13:
PVR Action=0 or 1:
Remediated density of the mixture at line conditions, with the configured TBR action applied
PVR Action=2: User-
specified density of oil at 60 °F, converted to line conditions
and data type
Mass Flow Rate Mass flow rate of the liquid
mixture, unremediated for PVR
Mass Total Mass total of the liquid
mixture, unremediated for PVR
Mass Inventory Mass inventory of the
mixture, unremediated for PVR
Volume Flow Rate Volume flow rate of the
mixture, remediated for PVR
Volume Total Total volume of the mixture
at line conditions, remediated
Volume Inventory Volume inventory of the
mixture, remediated for PVR
Unremediated Volume Flow Rate At Line
(1)
Volume flow rate of the mixture at line conditions, with TBR correction (unremediated)
Volume Total At Line
(1)
Total volume of the mixture at line conditions, without TBR correction (unremediated)
Accumulated TBR Time
(2)
Total number of seconds that TBR correction has been active, since the last master reset
Mass flow rate of the liquid mixture, unremediated for PVR
Mass total of the liquid mixture, unremediated for PVR
Mass inventory of the mixture, unremediated for PVR
Volume flow rate of the mixture, remediated for PVR
Total volume of the mixture at line conditions, remediated
Volume inventory of the mixture, remediated for PVR
Volume flow rate of the mixture at line conditions, with TBR correction (unremediated).
Total volume of the mixture at line conditions, without TBR correction (unremediated)
Total number of seconds that TBR correction has been active, since the last master reset
247–248, Float
259–260, Float
263–264, Float
253–254, Float
261–262, Float
265–266, Float
2265–2266, Float
349-350, Float
2267–2268, INT32
Shrinkage Factor Oil Flow Rate At Line
(3)
Volume flow of oil at line conditions, adjusted by shrinkage factor and shrinkage meter factor
Volume flow of oil at line conditions, adjusted by shrinkage factor and shrinkage meter factor
1733–1734, Float
Supplement 35
Page 36
Application parameters and data Supplement
January 2022 MMI-20026578
Table A-3: PVR process variables (continued)
Process variable Value Modbus location
No entrained gas detected
Entrained gas detected
and data type
Shrinkage Factor Oil Flow Rate At Reference
(3)
Shrinkage Factor Volume Flow Rate At Reference
Shrinkage Factor Oil Total at
(3)
Line
Shrinkage Factor Oil Total at Reference
Shrinkage Factor Volume Total At Reference
(3)
(3)
Measured Oil Density At Reference (Fixed SGU
(3)
Units)
Measured Oil Density At Reference (Fixed API
(3)
Units)
Unremediated Density
Volume flow of oil at reference conditions, adjusted by shrinkage factor and shrinkage meter factor
Volume flow of the mix at
(3)
reference conditions
Volume Total of the mix at line conditions
Oil Total of the mix at reference conditions
Volume Total of the mix at reference conditions
Density of the mixture at 60 °F, assuming the mixture is all oil. reported in SGU Units
Density of the mixture at 60 °F, assuming the mixture is all oil. reported in °API.
(4)
Density of the mixture at
Volume flow of oil at reference conditions, adjusted by shrinkage factor and shrinkage meter factor
Volume flow of the mix at reference conditions
Volume Total of the mix at line conditions
Oil Total of the mix at reference conditions
Volume Total of the mix at reference conditions
1735–1736, Float
1737–1738, Float
4616–4617, Float
4618–4619, Float
4796–4797, Float
1655–1666, Float
4465–4466, Float
1539–1540, Float line conditions (unremediated for PVR)
(1) Not available when connected to a transmitter. (2) Requires the enhanced core processor v4.11 or later with ETO 22166 or ETO 22701. (3) Requires the enhanced core processor v4.31 or later with ETO 22166 or ETO 22701. (4) Requires the enhanced core processor v4.40 or later with ETO 22166 or ETO 22701. If for direct connect, use ETO
13386 or the standard 800 v4.42 or greater if connected to a Model 2700 Transmitter.
36 Micro Motion Multiphase Applications
Page 37
Supplement Application parameters and data
MMI-20026578 January 2022

A.2 TBR parameters and data

Table A-4: TBR configuration parameters
Parameter Description Modbus location and data type
Drive Gain Threshold The drive gain, in %, that triggers TBR 617–618, Float
TBR Action The remediation action to be implemented 624, U16
Bit #0: Initial Action0=Hold Last Value
1=Alert Only
Bit #2: Drive Gain Averaging0=1 second
1=4 seconds
Bit #3: Apply to Mass Flow (affects volume
flow)
0=Yes
1=No
Bit #4: Apply to Density (affects volume
flow)
0=Yes
1=No
Bit #5: Timeout Alert Type0=Two-Phase Flow
1=Density Out of Range
TBR Lookback Period
TBR Timeout Enable or disable a timeout on the TBR
TBR Timeout Value The number of seconds that TBR remediation
TBR Timeout Action The action to be performed if TBR remediation
The time period (seconds) that the application goes back in time to determine the substitute density to use in calculations
remediation action
will be performed before timing out
times out
620, U16
624 Bit #6, U16
0=Disabled
1=Enabled
619, U16
624 Bit #1, U16
0=Normal Measurement
1=Alert
Table A-5: TBR application status parameters
Application status Description Modbus location and data type
TBR Active Indicates whether TBR is active or inactive 433 Bit #10, U16
TBR Total Time The duration of the TBR interval, in seconds 989, U32
Supplement 37
Page 38
Application parameters and data Supplement
January 2022 MMI-20026578
Table A-6: TBR process variables
Process variable Description Modbus location and
data type
Mixture Mass Flow Rate (unremediated) Mass flow rate of the mixture, unremediated 247–248, Float
Mixture Mass Total (unremediated) Mass total of the mixture, unremediated 259–260, Float
Mixture Mass Inventory (unremediated) Mass inventory of the mixture, unremediated 263–264, Float
Mixture Uncorrected Volume Flow Rate (remediated)
Mixture Uncorrected Volume Total (remediated)
Mixture Uncorrected Volume Inventory (remediated)
Unremediated Density
(1) Requires the enhanced core processor v4.40 or later with ETO 13386 for direct connect, or the standard 800 v4.42 or
greater if connected to a Model 2700 Transmitter.
(1)
Volume flow rate of the mixture, remediated 253–254, Float
Total volume of the mixture at line conditions, remediated
Volume inventory of the mixture at line conditions, remediated
Volume inventory of the mixture at line conditions, remediated
261–262, Float
265–266, Float
1539-1540, Float

A.3 TMR parameters and data

Table A-7: TMR configuration parameters
Parameter Description Modbus location and data type
Application Status Enabled/disabled Coil 75 (Core processor version less than
v4.40) Coil 473 (Core processor version 4.40 or
greater.)
0=Disabled
1=Enabled
Drive Gain Threshold The drive gain, in %, that triggers TMR 617–618, Float
Pre–Mist Averaging Period
Post–Mist Adjustment Delay
TMR Action The remediation action to be implemented 624, U16
The time period (seconds) that the application goes back in time to determine the density to use in TMR remediation
The time period (seconds) that the transmitter waits before beginning density adjustment
619, U16
620, U16
Bit #5: Timeout Alert Type0=Two–Phase Flow
1=Density Out of Range
Table A-8: TMR application status parameters
Application status Description Modbus location and data type
TMR Active Indicates whether TMR is active or inactive 433 Bit #12, U16
38 Micro Motion Multiphase Applications
Page 39
Supplement Application parameters and data
MMI-20026578 January 2022
Table A-8: TMR application status parameters (continued)
Application status Description Modbus location and data type
TMR Total Time The duration of the TMR interval, in seconds 989, U32
Table A-9: TMR process variables
Process variable Description Modbus location and
data type
Mass Flow Rate (remediated) Mass flow rate of the process fluid, remediated 973–974, Float
Mass Total (remediated) Mass total of the process fluid, remediated 975–976, Float
Mass Inventory (remediated) Mass inventory of the process fluid,
977–978, Float
remediated
Mass Flow Rate (unremediated) Mass flow rate of the process fluid,
247–248, Float
unremediated
Mass Total (unremediated) Mass total of the process fluid, unremediated 259–260, Float
Mass Inventory (unremediated) Mass inventory of the process fluid,
263–264, Float
unremediated
Uncorrected Liquid Volume Flow Rate (remediated)
Uncorrected Liquid Volume Total (remediated)
Uncorrected Liquid Volume Inventory (remediated)
(1)
(1)
(1)
Corrected GSV Flow Rate (remediated)
(2)
Volume flow rate of the process fluid, remediated
Total volume of the process fluid at line conditions, remediated
Volume inventory of the process fluid at line conditions, remediated
Corrected GSV flow rate of the process fluid,
253–254, Float
261–262, Float
265–266, Float
455–456, Float
remediated
Corrected GSV Total (remediated)
(2)
Corrected GSV total of the process fluid,
457–458, Float
remediated
Corrected GSV Inventory (remediated)
(2)
Corrected GSV inventory of the process fluid,
459–460, Float
remediated
(1) Applicable if Volume Flow Type = Liquid. (2) Applicable if Volume Flow Type = Gas Standard Volume. GSV is available with TMR for transmitters v6.62 and later.
Supplement 39
Page 40
Application parameters and data Supplement
January 2022 MMI-20026578
40 Micro Motion Multiphase Applications
Page 41
Supplement Best practices for two-phase measurement performance
MMI-20026578 January 2022
B Best practices for two-phase
measurement performance

B.1 Entrained gas performance

Measurement accuracy for liquids with entrained gas is a complex function of GVF, viscosity, velocity, sensor geometry, drive frequency, and orientation. The best measurement performance will always be achieved if fluid can be measured in single­phase. Add a free-gas knockout upstream if possible. The following guidelines apply regardless if APM options are licensed or not. When gas entrainment is inevitable, APM will improve the measurement performance.
Common sources for unintentional gas entrainment
Long drops from fill point to liquid level in tanks
Agitators and mixers
Leaks in seals or pumps
Pumping out of nearly empty tanks
Pressure loss (flashing) for volatile liquids
Pumping through nearly empty piping
Ways to minimize flow errors
Use ELITE® (low frequency) sensors whenever possible. F-Series and H-Series sensors
are also acceptable, but less accurate.
Do not use T-Series sensors or Models F300/H300 compact because they have a high
operating frequency.
Use the enhanced core processor (Model 800) either as direct connect or with the
1000-2000 Transmitter family: they perform best in applications with entrained gas.
Orient the meter properly:
Table B-1: Preferred sensor orientation for liquids with entrained gas
Process Preferred orientation
Delta-shaped sensors (CMF010, CMF025, CMF050, CMF100)
Supplement 41
Page 42
Best practices for two-phase measurement performance Supplement
January 2022 MMI-20026578
Table B-1: Preferred sensor orientation for liquids with entrained gas (continued)
Process Preferred orientation
Any F-Series or CMFS sensor, and CMF200 or larger (flow should go up)
Ensure sensor is filled as quickly as possible, and stays full during measurement:For horizontal pipes, maintain a minimum flow velocity of 1 m/s to purge air from
an empty pipe and keep it full.
For vertical pipes, flow upward and maintain minimum velocity of 1 m/s to prevent
solids from settling out of the fluid.
Add back pressure, or increase line pressure, to minimize size of bubbles in flow
stream.
Size the meter appropriately to operate normally as close to the sensor nominal flow
rate as is practical. Higher velocity leads to better performance, as long as pressure drop does not cause liquids flash.
Ensure fluid is well mixed. If needed, you can install a blind “T” and/or static mixer just
upstream of the sensor to evenly distribute bubbles through both sensor tubes. If using a blind “T”, install it in the same plane as the sensor tubes.
If re-zeroing in the field is necessary, zeroing must be done on a pure liquid without
bubbles in order to avoid error. If this cannot be done, use the factory zero.
Minimize damping on outputs to minimize processing delay from electronics.
Do not stop the totalizer immediately after batch; allow the totalizer to stabilize for
approximately 1 second.
Set Flow Cutoff as high as is practical to avoid totalizing at no flow condition if bubbles
remain in the sensor.

B.2 Entrained liquid (mist) performance

Measurement accuracy for gases with entrained liquids (mist) is mostly related to the amount of mass contained in liquid droplets compared to an equivalent volume of gas containing the same mass. It is important to choose the correct sensor. Otherwise, sensor geometry, drive frequency, and orientation can cause errors that reduce performance. The best measurement performance will always be achieved if fluid can be measured in single­phase. Add a liquid trap upstream if possible. The following guidelines apply regardless if APM options are licensed or not. When liquid entrainment is inevitable, APM will improve the measurement performance.
42 Micro Motion Multiphase Applications
Page 43
Supplement Best practices for two-phase measurement performance
MMI-20026578 January 2022
Common sources for unintentional liquid entrainment
Temperature loss (condensation)
Pressure increase
Poorly managed level control in separators or GLCCs
Malfunctioning or over-filled liquid traps
Ways to minimize measurement errors
Use ELITE® (low frequency) sensors whenever possible. F-Series and H-Series sensors
are also acceptable, but less accurate.
Size the meter appropriately for gas flow. Avoid high turndowns where sensor
sensitivity may be reduced.
Do not use T-Series sensors or compact Models F300/H300 because they have a high
operating frequency.
Use the enhanced core processor (Model 800) or the 1000-2000 transmitter family:
they perform best in applications with entrained liquid.
Use the enhanced core processor (Model 800) either as direct connect or with the
1000-2000 transmitter family: they perform best in applications with entrained liquid.
Orient the meter properly:
Table B-2: Preferred sensor orientation when there could be entrained liquid
Process Preferred orientation
Delta-shaped sensors (CMF010, CMF025, CMF050, CMF100)
Any F-Series or CMFS sensor, and CMF200 or larger (flow should go down)
Ensure sensor is dried (blown-out) as quickly as possible, and stays dry during
measurement.
Avoid temperature losses; insulation is highly recommended if condensate is caused by
cooling temperatures.
Avoid pressure increases in the system; Ensure that pressure regulators are functioning
properly.
Supplement 43
Page 44
Best practices for two-phase measurement performance Supplement
January 2022 MMI-20026578
If entrained liquid is unavoidable, try to ensure that the process is well mixed.
Avoid elbows, valves, or other components that may introduce a flow profile affecting
one tube (for example, a swirling motion entering the flow tubes)
If re-zeroing in the field is necessary, zeroing must be done on a pure gas without liquid
in order to avoid error. If this cannot be done, use the factory zero.
Minimize damping on outputs to minimize processing delay from electronics.
Do not stop the totalizer immediately after batch; allow the totalizer to stabilize for
approximately 1 second.
Set Flow Cutoff as high as is practical to avoid totalizing at no flow condition if droplets
remain in the sensor.

B.3 Density determination

If you are using either the PVR application or the , you must know the density of water from the well, corrected to reference temperature, and the density of dry oil from the well, corrected to reference temperature.
B.3.1
Important
Micro Motion recommends working with a laboratory to obtain the most accurate values. The accuracy of the PVR data depends upon the accuracy of these two density values.
Density determination using a petroleum laboratory
To configure PVR for net oil measurement, you must know the density of oil at reference temperature, and the density of produced water at reference temperature. You can obtain these values from a petroleum laboratory.
Note
Even after separation, oil typically contains some amount of interstitial water. The water cut may be as high as 1% to 3%.
Important
If you are using a three-phase separator, you can collect the oil sample and the water sample separately, after separation, or you can collect one sample before separation and have the laboratory perform the separation.
If you are using a two-phase separator, you should collect one sample before separation and have the laboratory perform the separation.
Prerequisites
Sample collection must meet these requirements:
You must be able to collect a sample that is representative of your process.
The sample must be collected by a qualified person, using industry-accepted safety
standards.
You must know the minimum required sample size. This varies depending on the water
cut and the volume of the sample cylinder. Consult the petroleum laboratory for specific values.
44 Micro Motion Multiphase Applications
Page 45
Supplement Best practices for two-phase measurement performance
MMI-20026578 January 2022
If the sample contains oil, you must be able to collect and maintain the sample at line
pressure, so that the oil will not lose pressure and outgas. This will change the laboratory-measured density.
If you collect the water sample separately, you must be able to protect it from
contamination and evaporation.
You must know the reference temperature that you plan to use.
The petroleum laboratory must be able to meet these requirements:
The laboratory density meter must be able to keep the oil sample pressurized at line
pressure during the density measurement.
The sample cylinder must be a constant-pressure type, and must be properly rated for
the oil–water composition and for sample pressure.
The oil and water density measurement units must be entered into the PVR software in
g/cm³ at reference temperature (always 60 °F with an enhanced core processor direct connect or with the 1000-2000 transmitter family).
The laboratory report must include the oil density, water density, and the reference
temperature.
Procedure
1. Communicate the handling and measurement requirements and the reference
temperature to the petroleum laboratory.
2. If you are collecting one sample that contains both oil and water, identify the point
in the line where the sample will be taken.
Recommendations:
Collect the sample at a point where the fluid is well mixed.
The line pressure at the sample point should be close to the line pressure at the
sensor.
The line temperature at the sample point should be close to the line
temperature at the sensor.
3. If you are using a three-phase separator and collecting the oil and water samples separately:
a) Identify the points where the samples will be taken.
Recommendations:
The sample point for oil must be on the oil leg, as close to the sensor as
possible.
The line pressure at the oil sample point should be similar to the line
pressure at the sensor.
The sample point for water must be on the water leg, as close to the
sensor as possible.
The line temperature at the water sample point should be similar to the
line temperature at the sensor.
Supplement 45
Page 46
Best practices for two-phase measurement performance Supplement
January 2022 MMI-20026578
b) Wait until separation has occurred.
4. Collect the sample or samples, meeting all requirements for pressure and protection from contamination or evaporation.
5. Mark and tag the sample or samples with the well name or number, time and date, sample type, line pressure, and line temperature.
6. Transport the samples to the laboratory safely, as soon as is practical.
Postrequisites
If the laboratory measurements were not corrected to your reference temperature, use the Oil & Water Density Calculator to calculate density at reference temperature. This is a spreadsheet tool developed by Micro Motion. You can obtain a copy by visiting https://
www.emersonflowsolutions.com/oildensityref or from your Micro Motion representative.
B.3.2
Density determination using a three-phase separator
To configure net oil measurement, you must know the density of dry oil at reference temperature, and the density of produced water at reference temperature. If you have a three-phase separator, you can use density data and the Oil & Water Density Calculator to obtain these values.
Note
Even after separation, oil typically contains some amount of interstitial water. The water cut may be as high as 1% to 3%. For purposes of this application, this is considered dry oil.
Prerequisites
You must have a three-phase separator in the process. You can use a mobile three-phase test separator.
You must have a sensor and transmitter installed on the oil leg, and a sensor and transmitter installed on the water leg or determine the water density separately by manual sampling.
You must know the reference temperature that you plan to use (always 60 °F (15.6 °C) with an enhanced core processor direct connect or with the 1000-2000 transmitter family).
You must have the Oil & Water Density Calculator. This is a spreadsheet tool developed by Micro Motion. You can obtain a copy from your Micro Motion representative or by visiting
https://www.emersonflowsolutions.com/oildensityref.
Important
The accuracy of net oil data depends on the accuracy of the density data. Never use an unstable density value, or any density value that has an elevated drive gain.
Procedure
1. Wait until separation has occurred.
2. At the transmitter on the oil leg, do one of the following options:
Read and record the density value and the temperature value
46 Micro Motion Multiphase Applications
Page 47
Supplement Best practices for two-phase measurement performance
MMI-20026578 January 2022
If logging the live variable data, monitor the live density at line conditions, or the
corrected density at 60 °F (15.6 °C) (modbus register 1655)
3. At the transmitter on the water leg, read and record the density value and the temperature value. Alternatively, enter the density of the water obtained by another method, such as sampling.
4. Use the Oil & Water Density Calculator to calculate the density of dry oil at reference temperature and the density of produced water at reference temperature. You can obtain a copy from your Micro Motion representative or by visiting https://
www.emersonflowsolutions.com/oildensityref.
Tip
Unless the oil is light hot condensate, the oil will almost always contain some interstitial water. This is generally acceptable for allocation measurements. However, if further accuracy is desired, you can determine the water cut and use it in the calculation. To determine or estimate the water cut, take a shakeout sample from one of the following:
The current flow/dump cycle, at the time of minimum density
Similar oils produced from the same reservoir
The tank or tanks that the separator flows into
Enter this water cut into the Oil & Water Density Calculator to calculate the density of dry oil at reference temperature.
Supplement 47
Page 48
MMI-20026578
Rev. AD
2022
For more information:
©
2022 Micro Motion, Inc. All rights reserved.
www.emerson.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Automation Solutions family of companies. All other marks are property of their respective owners.
Loading...