ivMicro Motion® Model D and DT Sensors Instruction Manual
Page 5
Before You Begin
Your new sensor
Your new Micro Motion® Model D or DT sensor, or D600 sensor and
booster amplifier, is one part of a Coriolis flowmetering system. The
other part is a transmitter.
Transmitter connections
Model D sensors are available with a factory-supplied 9-wire junction
box for connecting to a remotely mounted transmitter, or to a remotely
mounted core processor.
Model DT sensors are available with a 3-foot (1-meter) pigtail of cable
that connects to a user-supplied junction box. The junction box connects
to a remotely mounted transmitter, or to a remotely mounted core
processor.
The D600 has a booster amplifier. The booster amplifier is available with
a factory-supplied 9-wire junction box for connecting to a remotely
mounted transmitter, or with a factory-supplied core processor for
connecting to a 4-wire remotely mounted transmitter or to a usersupplied remote host.
All Model D and DT sensors may be connected to the Micro Motion
transmitters listed in Table 1. The D600 sensor may be connected to the
transmitters listed in Table 2.
Table 1.Transmitter and sensor compatibility guide
Transmitter
Model 1700/2700 (9-wire)XX
Model 3500/3700 (9-wire)XX
RFT9739 (7- or 9-wire)XX
IFT9701 (9-wire)X
RFT9712 (7- or 9-wire)XX
(1)Except D600.
(factory-supplied junction box)
Model D sensor
(1)
Model DT sensor
(user-supplied junction box)
Micro Motion® Model D and DT Sensors Instruction Manual1
Page 6
Before You Begin continued
The D600 sensor and booster amplifier are available in any of the
configurations described in Table 2. Table 2 also lists the transmitters
that can be used with each configuration.
Table 2.D600 configurations and compatible transmitters
D600 sensor configuration
Booster amplifier location
Integral to sensorJunction box9-wire• Model 1700/2700 (with integral core
Remote from sensorJunction box9-wire• Model 1700/2700 (with integral core
(1)A direct host is a user-supplied remote controller, PLC, or other device.
Booster amplifier wiring
component
Core processor4-wire• Model 1700/2700
Core processor4-wire• Model 1700/2700
Connection to
transmitterCompatible transmitters
processor)
• Model 3500/3700 (9-wire)
• RFT9739
• RFT9712
• Remote core processor
• Model 3500/3700 (MVD)
• Model 2500
• Direct host
processor)
• Model 3500/3700 (9-wire)
• RFT9739
• RFT9712
• Remote core processor
• Model 3500/3700 (MVD)
• Model 2500
• Direct host
(1)
(1)
European installations
This Micro Motion product complies with all applicable European
directives when properly installed in accordance with the instructions in
this quick reference guide. Refer to the EC declaration of conformity for
directives that apply to this product.
The EC declaration of conformity, with all applicable European
directives, and the complete ATEX Installation Drawings and Instructions
are available on the internet at www.micromotion.com/atex or through
your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure
Equipment Directive can be found on the internet at
www.micromotion.com/library.
Sensor components
Components of the sensor are illustrated on pages 3-6.
2Micro Motion® Model D and DT Sensors Instruction Manual
Page 7
Before You Begin continued
Ground screw
Purge connections
(optional)
Junction box
Sensor housing
Flow direction
arrow
Process
connection
Calibration tag
Approvals tag
Flow direction
arrow
Purge connection
(optional)
Calibration tag
Sensor
housing
Junction box
Process
connection
Approvals
tag
Ground screw
Purge connection
(optional)
DS025, DH025, DH038, and DS040 sensors
DS065, DS100, DH100, DS150, DH150, DS300, and DH300 sensors
Micro Motion® Model D and DT Sensors Instruction Manual3
Page 8
Before You Begin continued
Sensor housing
Booster
amplifier
Process connection
Customer tag
(if requested)
Snub-mount
connector
Junction box
Flow direction
arrow
Calibration tag
Approval tag
Approval tag
Sensor housing
Calibration tag
Flow direction
arrow
Booster amplifier
Core processor
Process connection
Customer tag (if
requested)
Snub mount connector
D600 sensor with integral booster amplifier and junction box
D600 sensor with integral booster amplifier and core processor
4Micro Motion® Model D and DT Sensors Instruction Manual
Page 9
Before You Begin continued
Approval tag
Sensor housing
Remote booster
amplifier
Process connection
Customer tag
(if requested)
Snub-mount
connector
Junction box
Flow direction
arrow
Calibration tag
Explosion-proof wiring
Intrinsically
safe wiring
Approval tag
Factory-supplied wiring
Approval
tag
Explosion-proof wiring
Intrinsically safe
wiring
Flow
direction
arrow
Core
processor
Sensor housing
Approval tag
Calibration tag
Remote booster
amplifier
Customer tag
(if requested)
Process connection
Snub mount
connector
Factory-supplied wiring
D600 sensor with remote booster amplifier and junction box
D600 sensor with remote booster amplifier and core processor
Micro Motion® Model D and DT Sensors Instruction Manual5
Page 10
Before You Begin continued
Flow direction arrow
Calibration tag
Sensor cable with flexible conduit
Process
connection
Approvals tag
Ground screw
Lifting handle
Sensor housing
DT065, DT100, and DT150 sensors
The installation process
Installing your new sensor involves five steps:
Step 1. Location
Determining the proper location for the sensor, taking into account
hazardous areas, process piping, transmitter location, and valves. See
page 9.
Step 2. Orientation
Determining the desired orientation for the sensor in the process
pipeline. See page 13.
Step 3. Mounting
Installing the sensor in the pipeline. See page 17.
Step 4. Wiring
Connecting the flowmeter cable to the sensor and transmitter. See
page 19.
Step 5. Startup
Requirements for flowmeter startup. See page 39.
6Micro Motion® Model D and DT Sensors Instruction Manual
Page 11
Before You Begin continued
Additional information
In addition to installation instructions, the following subjects are also
covered in this manual:
• Troubleshooting for problems that might be attributable to the sensor
begins on page 41.
• Purge fittings are described in Appendix A, page 55.
• Rupture disks are discussed in Appendix B, page 59.
• Maintenance of labels is covered in Appendix C, page 61.
• Return policy for Micro Motion equipment is described in Appendix D,
page 65.
Micro Motion® Model D and DT Sensors Instruction Manual7
Page 12
8Micro Motion® Model D and DT Sensors Instruction Manual
Page 13
Keys for sensor location
The sensor may be located anywhere in the process line, as long as
the following conditions are met:
• Before operation, you must be able to stop flow through the sensor.
(During the zeroing procedure, flow must be stopped completely, and
the sensor must be full of process fluid.)
• The sensor must be installed in an area that is compatible with the
classification specified on the sensor approvals tag. (See
illustrations, pages 3-6.)
Installation
Step 1
Location
Pipe run
Maximum wiring distances
Micro Motion sensors do not require a straight run of pipe upstream or
downstream.
Use these guidelines for calculating maximum wiring distances.
Maximum distance between sensor and transmitter depends on cable
type. See Table 1.
.
Table 1.Maximum cable lengths
Cable typeWire gaugeMaximum length
Micro Motion 9-wire to an MVD
transmitter or core processor
Micro Motion 9-wire to all other
transmitters
Micro Motion 4-wireNot applicable1000 feet (300
User-supplied 4-wire
• Power wires (VDC)22 AWG
• Signal wires (RS-485)22 AWG (0,35 mm
(1)Micro Motion recommends using Micro Motion cable.
(1)
Not applicable60 feet (20 meters)
Not applicable1000 feet (300
meters)
meters)
(0,35 mm
20 AWG (0,5 mm
18 AWG (0,8 mm
larger
2
)300 feet (90 meters)
2
)500 feet (150 meters)
2
)1000 feet (300
2
) or
meters)
1000 feet (300
meters)
Micro Motion® Model D and DT Sensors Instruction Manual9
Page 14
Location continued
DT sensor junction box
Environmental limits
Model DT sensors come with a 3-foot (1 meter) pigtail of cable
pre-installed. A junction box can be installed at the end of this pigtail.
Sensor temperature limits
Temperature limits vary by sensor; refer to Table 2.
Table 2.Temperature specifications
Sensor type°F°C
DS025
DS040
DS065
DS100
DS150
DS150Z
DS300
DS300Z
DH025
DH038
DH100
DH150
DH300
DT065
DT100
DT150
D600 with integral booster amplifier
D600 with remote booster amplifier
–400 to +350–240 to +177
–400 to +350–240 to + 177
–400 to +350–240 to + 177
–400 to +400–240 to + 204
–400 to +400–240 to + 204
+32 to +2500 to + 121
–400 to +400–240 to + 204
+32 to +2500 to + 121
–400 to +350–240 to + 177
–400 to +350–240 to + 177
–400 to +400–240 to + 204
–400 to +400–240 to + 204
–400 to +400–240 to + 204
+32 to +8000 to + 426
+32 to +8000 to + 426
+32 to +8000 to + 426
–58 to +140–50 to +60
–400 to +400–240 to +200
Valves
For ATEX approvals, process fluid temperature can be further restricted
by ambient temperatures. For guidelines, go to www.micromotion.com/
atex.
D600 booster amplifier ambient temperature limits
Install the booster amplifier in a location that falls within the following
limits:
Ambient temperature limits between –58 to +140°F (–50 to +60 °C).
For ATEX approvals, process fluid temperature can be further restricted
by ambient temperatures. For guidelines, go to www.micromotion.com/
atex.
After the sensor and transmitter have been fully installed, you must
perform the zeroing procedure. During the zeroing procedure, flow
through the sensor must be halted and the sensor tubes must be
completely full of process fluid. A shutoff valve, downstream from the
sensor, is required to halt flow during the zeroing procedure. For more
information about zeroing, see page 39.
10Micro Motion® Model D and DT Sensors Instruction Manual
Page 15
Location continued
Hazardous area installations
Make sure the hazardous area specified on the sensor approvals tag is
suitable for the environment in which the sensor is installed. (See
illustrations on pages 3-6.) For installation in an area that requires
intrinsic safety, refer to Micro Motion hazardous approval
documentation, shipped with the sensor or available from the Micro
Motion web site.
For hazardous installations in Europe, refer to standard EN 60079-14 if
national standards do not apply.
If you don’t have access to the World Wide Web, you can obtain an I.S.
manual by contacting the Micro Motion Customer Service Department:
• In the U.S.A., phone 1-800-522-MASS (1-800-522-6277), 24 hours
• In Canada and Latin America, phone +1 303-527-5200 (U.S.A.)
• In Asia, phone +65 6777-8211 (Singapore)
• In the U.K., phone 0870 240 1978 (toll-free)
• Outside the U.K., phone +31 (0) 318 495 555 (The Netherlands)
Micro Motion® Model D and DT Sensors Instruction Manual11
Page 16
12Micro Motion® Model D and DT Sensors Instruction Manual
Page 17
Installation
Keys for sensor orientation
The sensor will function properly in any orientation if the sensor flow
tubes remain filled with process fluid.
Step 2 Orientation
Flow direction
Process fluid
Micro Motion sensors measure accurately regardless of flow direction as
long as the sensor flow tubes remain filled with process fluid.
Flow direction arrow
The sensor has a flow direction arrow (see illustrations, pages 3-6) to
help you configure the transmitter for flow direction. Process fluid flowing
in the direction opposite to the flow direction arrow may cause
unexpected transmitter output unless the transmitter is configured
appropriately. For instructions on configuring the transmitter’s flow
direction parameter, refer to the transmitter instruction manual.
Vertical pipeline
If the sensor is installed in a vertical pipeline, liquids and slurries should
flow upward through the sensor. Gases may flow upward or downward.
Typical sensor orientations are shown in the tables on the following
pages:
• For measuring liquids, see page 14.
• For measuring gases, see page 15.
• For measuring slurries, see page 16.
Micro Motion® Model D and DT Sensors Instruction Manual13
Page 18
Orientation continued
Flow
Flow
Flow
Orientations for measuring liquids
Sensor
model
DS025
DH025
DH038
DS040
DS065
DS100
DH100
DS150
DH150
DS300
DH300
D600
DT65
DT065
DT100
DT150
Preferred orientation for
measuring liquids
Tubes down
Horizontal pipeline
Tubes down
Horizontal pipeline
Tubes down
Horizontal pipeline
Alternative orientation for
measuring liquids
Tubes up
Horizontal pipeline
Self-draining
Tubes up
Horizontal pipeline
Self-draining
Tubes up
Horizontal pipeline
Self-draining
Flag mount
Vertical pipeline
Flag mount
Vertical pipeline
Flag mount
Vertical pipeline
14Micro Motion® Model D and DT Sensors Instruction Manual
Page 19
Orientation continued
Flow
Flow
Flow
Orientations for measuring gases
Sensor
model
DS025
DH025
DH038
DS040
DS065
DS100
DH100
DS150
DH150
DS300
DH300
D600
DT65
DT065
DT100
DT150
Preferred orientation for
measuring gases
Tubes up
Horizontal pipeline
Self-draining
Tubes up
Horizontal pipeline
Self-draining
Tubes up
Horizontal pipeline
Self-draining
Alternative orientation for
Flag mount
Vertical pipeline
Flag mount
Vertical pipeline
Flag mount
Vertical pipeline
measuring gases
Dry gases only
Tubes down
Horizontal pipeline
Dry gases only
Tubes down
Horizontal pipeline
Dry gases only
Tubes down
Horizontal pipeline
Micro Motion® Model D and DT Sensors Instruction Manual15
Page 20
Orientation continued
Flow
Flow
Flow
Orientations for measuring slurries
Sensor
model
DS025
DH025
DH038
DS040
DS065
DS100
DH100
DS150
DH150
DS300
DH300
D600
DT65
DT065
DT100
DT150
Preferred orientation for
measuring slurries
Flag mount
Vertical pipeline
Flag mount
Vertical pipeline
Flag mount
Vertical pipeline
Alternative orientation for
measuring slurries
Tub e s u p
Horizontal pipeline
Self-draining
Tub e s u p
Horizontal pipeline
Self-draining
Tub e s u p
Horizontal pipeline
Self-draining
16Micro Motion® Model D and DT Sensors Instruction Manual
Page 21
Installation
CAUTION
Keys for sensor mounting
Use your common piping practices to minimize:
• Torque on process connections
• Bending load on process connections
• For proper orientation, see pages 14-16
• For optional D600 mounting, see page 18
Step 3Mounting
Mounting any D or DT sensor
Using the sensor to support piping
can damage the sensor or
cause measurement error.
Do not use sensor to support pipe.
Micro Motion® Model D and DT Sensors Instruction Manual17
Page 22
Mounting continued
Snub-mount connector
• Connect support only to the factory-supplied
rubber snub-mount connector
• Attach with 1/2"-13 UNC bolt
• Bolt may penetrate isolator to 1 1/2" (40 mm)
D600 in flag-mount orientation can use
snub connector for added support in
high-vibration installations
Conduit openingsIf possible, install wiring with the conduit openings pointed downward to
reduce the risk of condensation or excessive moisture in the housing.
Otherwise, install drip legs on the cable or conduit.
Optional Model D600 mounting
When installing a Model D600 in a high-vibration area, additional
support may be added if desired. Use the D600 snub-mount connector
with vibration isolator to help support the sensor. See illustration, below.
Typically, the snub-mount connector is used when the D600 is installed
in the flag-mount orientation (in a vertical pipeline), as shown below.
Model D600 mounting with snub-mount connector
DT sensors
Model DT sensors come with a 3-foot (1-meter) pigtail of cable
pre-installed. A junction box can be connected at the end of this pigtail.
The junction box is used for connecting the cable from the transmitter.
18Micro Motion® Model D and DT Sensors Instruction Manual
Page 23
Installation
WARNING
Step 4Wiring
Hazardous area installations
Model D sensor junction box
The following warning applies to hazardous area installations
Failure to comply with requirements for intrinsic
safety in a hazardous area could result in an
explosion.
• Make sure the hazardous area specified on the sensor
approvals tag is suitable for the environment in which the
sensor is installed. See illustrations, pages 3-6.
• For installation in an area that requires intrinsic safety,
refer to Micro Motion hazardous approval installation
instructions.
• For hazardous area installations in Europe, refer to
standard EN 60079-14 if national standards do not apply.
Most Model D sensors are shipped with a junction box for wiring. There
are two types of junction boxes: one for the D600 sensor, one for all the
other D sensors.
• The D600 junction box is different than the junction box for other D
sensors. D600 sensors are also available with a core processor. For
more information on the D600 sensor, see page 24.
• Model DT sensors can use a junction box. For more information on the
DT sensor junction box, see page 20.
For Model D sensors (except the DT series and D600):
• If it if not already installed, install the junction box on the sensor,
following the wiring instructions on the junction box.
• If possible, install wiring with the junction-box opening pointed
downward, or with a drip leg in the conduit or cable, to reduce the risk
of condensation or excessive moisture in the junction box. See
illustration on page 20.
• Next, follow the guidelines in Connecting and shielding 9-wire cable to
wire the sensor to the transmitter.
Micro Motion® Model D and DT Sensors Instruction Manual19
Page 24
Wiring continued
3/4" NPT female
conduit opening
Drip leg in
conduit or cable
Model D sensor junction box
Model DT sensor cable and
junction box
Model DT sensors can use a junction box. Model DT sensors come with
a 3-foot (1 meter) pigtail of pre-installed cable and a 3-foot (1 meter)
piece of conduit that needs to be fitted over the pre-installed cable. See
illustration on page 21.
• Slide the conduit over the pre-installed cable.
• Screw the conduit fitting end into the sensor.
The other end of the conduit can be connected to a user-supplied
junction box or directly to a transmitter.
• If the conduit is connected to a user-supplied junction box, connect the
wires to the terminals on the junction box. If possible, install wiring with
junction-box openings pointed downward, or with drip legs in the
conduits or cables, to reduce the risk of condensation or excessive
moisture in the junction box. Next, connect the 9-wire cable from the
junction box to the transmitter by following the instructions in
Connecting and shielding 9-wire cable.
• If the conduit is connected directly to a transmitter, refer to the wiring
instructions in the transmitter Quick Reference Guide.
20Micro Motion® Model D and DT Sensors Instruction Manual
Page 25
Wiring continued
Drip leg
1/2" NPT
conduit fitting
3 ft. (1 m) factory-supplied flex conduit
• Liquid tight to meet CE requirements
for European installations
• Permanently attached to sensor
Grounding screw
1/2" NPT conduit fitting
• Factory-supplied fitting
• Ensure 360
° contact
CAUTION
Model DT sensor cable
Connecting and shielding 9-wire
cable
A 9-wire connection is required between the junction box and the core
processor or transmitter. Micro Motion offers two types of 9-wire cable:
• Shielded
•Armored
Both cable types contain shield drain wires. You may also use jacketed
cable with conduit.
Cable connections to sensor and transmitter
The wiring procedure is the same for the sensor and transmitter. Refer to
the wiring diagrams on the following pages, and follow these steps:
Failure to seal the sensor and transmitter housings
could cause a short circuit, which would result in
measurement error or flowmeter failure.
• Ensure integrity of gaskets and O-rings.
• Grease all O-rings before sealing.
• Install drip legs in cable or conduit.
• Seal all conduit openings.
Micro Motion® Model D and DT Sensors Instruction Manual21
Page 26
Wiring continued
CAUTION
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Model D or DT
sensor terminals
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Ye l l ow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the instructions
that are shipped with the cable
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
Brown
Red
Orange
Ye l l ow
Green
Blue
Violet
Gray
White
Black (drains)
Connect outer
braid of shielded or
armored cable
For DT sensor junction box
information, see page 20.
Model 3500
with I/O cable
Not approved for intrinsic safety
in Europe
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Model D or DT
sensor terminals
Flowmeter
cable
Model 3500
with screw-type or
solder-tail terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Ye l l ow
Black
(Drains from all
wire sets)
Yellow
Violet
Green
Blue
Brown
Black (Drains)
Orange
White
Gray
Red
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the instructions
that are shipped with the cable
c4
c6
c8
c10
c12
a4
a6
a8
a10
a12
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
For DT sensor junction box
information, see page 20.
1. Locate the wires by color and terminal number.
2. Insert the stripped ends of the individual wires into the terminal
blocks. No bare wires should remain exposed.
• At the sensor, connect wiring inside the junction box.
• At the transmitter, connect wiring to the transmitter’s intrinsically
safe terminals for sensor wiring.
3. Tighten the screws to hold the wires in place.
4. Ensure integrity of gaskets, then tightly close and seal the
junction-box cover and all housing covers on the transmitter.
Drain wires from a 9-wire cable must be clipped at the
sensor end and insulated with heat-shrink wrapping.
Failure to properly terminate drain wires will cause
sensor error.
Model D or DT sensor (except D600) wiring to Model 3500 with I/O cable
Model D or DT sensor (except D600) wiring to Model 3500 with screw or solder terminals
22Micro Motion® Model D and DT Sensors Instruction Manual
Page 27
Wiring continued
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Model D or DT
sensor terminals
Flowmeter
cable
Model 3700
terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Ye l l ow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the instructions
that are shipped with the cable
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
Red
Brown
Yellow
Black (drains)
Violet
Orange
Green
White
Blue
Gray
For DT sensor junction box
information, see page 20.
9 7531
86420
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Model D or DT
sensor terminals
Flowmeter
cable
Field-mount
RFT9739 terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Brown
Orange
Green
Violet
White
Gray
Blue
Yellow
Red
Black (Drains)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the instructions
that are shipped with the cable
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
For DT sensor junction-box
information, see page 20.
CN1
BZ
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Model D or DT
sensor terminals
Flowmeter
cable
Rack-mount
RFT9739 terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Ye l l ow
Black
(Drains from all
wire sets)
Red
Yellow
Orange
White
Gray
Brown
Black (Drains)
Violet
Green
Blue
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the instructions
that are shipped with the cable
B2
B4
B6
B8
B10
Z2
Z4
Z6
Z8
Z10
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
For DT sensor junction box
information, see page 20.
Model D or DT sensor (except D600) wiring to Model 3700
Model D or DT sensor (except D600) wiring to RFT9739 field-mount transmitter
Model D or DT sensor (except D600) wiring to RFT9739 rack-mount transmitter
Micro Motion® Model D and DT Sensors Instruction Manual23
Page 28
Wiring continued
9 7531
86420
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Model D or DT
sensor terminals
Flowmeter
cable
RFT9712
terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Brown
Orange
Green
Violet
White
Gray
Blue
Yellow
Red
Black (Drains)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the instructions
that are shipped with the cable
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
For DT sensor junction box
information, see page 20.
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Model D or DT
sensor junction box
terminals
Flowmeter
cable
Field-mount Model
2700 terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Brown
Violet
Ye l l ow
Maximum cable length 60 ft. (20 m)
Prepare cable in accordance with the
instructions that are shipped with the cable.
Do not allow shields to contact sensor
junction box.
Blue
Gray
Orange
Red
Green
White
Ground screw
Black
Brown
Red
Orange
Ye l l ow
Green
Blue
Violet
Gray
White
10
11
12
GND
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Ye l l ow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the instructions
that are shipped with the cable
Black (Drains,
remote-mount only)
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
Model D sensor
terminals
* Model D600 and DT sensors cannot be used with IFT9701 transmitters
IFT9701 or
Model 5300 terminals
Model D or DT sensor (except D600) wiring to RFT9712 transmitter
Model D sensor or DT (except D600) wiring to Model 1700 or 2700 transmitter
Model D sensor wiring (except the D600) to IFT9701* and Model 5300 transmitters
24Micro Motion® Model D and DT Sensors Instruction Manual
Page 29
Wiring continued
CAUTION
WARNING
D600 sensor
For wiring between the sensor and transmitter, there are two options:
junction box or core processor.
• For wiring instructions from junction box to transmitter, see page 29.
• For wiring from core processor to transmitter or for direct host, see
page 32.
The D600 also requires wiring to an AC power supply for the integral and
remote version of the booster amplifier. Between 85-250 VAC of power
must be provided. See pages 26-27.
The remote version of the booster amplifier requires wiring to the sensor
and wiring of the drive wires. See page 28.
The sensor is shipped with 16 feet (5 meters) of 9-wire cable for
connecting from the remote booster amplifier to the intrinsically safe
junction box located on the sensor. For longer cable lengths, up to 60
feet (20 meters), contact Micro Motion.
Improper installation of wiring could cause
measurement error or sensor failure.
• Shut off power before installing power-supply wiring.
• Follow all instructions to ensure sensor will operate
correctly.
• Install drip legs in conduit or cable.
• Seal all conduit openings.
• Ensure integrity of gaskets, and fully tighten sensor
junction-box cover, core processor cover, and all
transmitter housing covers.
Explosion Hazard
In a hazardous area:
• Do not open booster amplifier housing cover while
booster amplifier is energized.
• Wait at least 30 minutes after power is shut off before
opening.
Micro Motion® Model D and DT Sensors Instruction Manual25
Page 30
Wiring continued
Screw and terminal cover
Chassis ground
L/L
1
N/L
2
85-250 VAC
50/60 Hz
Supplementary bonding connection
Power supply wiring to the
remote booster amplifier
• Remove screw and terminal cover before installing wiring. Re-install
cover before operating.
• Provide 85-250 VAC power to terminals L2 and L1 as shown in the
diagram below.
• This unit is provided with an external terminal for supplementary
bonding connections. This terminal is for use where local codes or
authorities permit or require such connections.
Remote booster amplifier power-supply wiring
26Micro Motion® Model D and DT Sensors Instruction Manual
Page 31
Wiring continued
85-250 VAC
50/60 Hz
N/L2L/L1
Power supply
ground
Wiring
compartment
Supplementary bonding connection
Power supply wiring to the
integral booster amplifier
Provide 85-250 VAC power to terminals L2 and L1 as shown in the
diagram below.
This unit is provided with an external terminal for supplementary
bonding connections. This terminal is for use where local codes or
authorities permit or require such connections.
Integral booster amplifier power-supply wiring
Micro Motion® Model D and DT Sensors Instruction Manual27
Page 32
Wiring continued
User-supplied drive wiring,
18 AWG (0,75 mm
2
). See
page 29 for connections at
remote booster amplifier.
White
Blue
Violet
Ye l l o w
Orange
Red (factory wired)
Brown (factory wired)
Factory-supplied drive
wiring
Gray
Factory-supplied 9-wire
cable for intrinsically safe
wiring (RTD and pickoffs)
Remote booster amplifier
Green
Explosion-proof wiringIntrinsically safe wiring
12
Wiring from the remote booster
For intrinsically safe junction box wiring (see left side of figure below):
amplifier to the sensor
• Terminate factory-supplied 9-wire cable. Match wire colors to the
corresponding terminal wire colors from the remote booster amplifier.
• Orange wire in cable does not have corresponding orange wire from
sensor. Note: Terminate the orange wire in cable to the terminal shown
in diagram below.
• Clip remaining wires (brown and red) of cable (intrinsically safe side only) and insulate.
For explosion-proof junction box wiring (see right side of figure below):
Install user-supplied drive wiring, shielded 18 AWG (0,75 mm
cable, from remote booster amplifier terminals 1 and 2 to sensor
terminals 1 and 2. (See figure on page 29 for wiring at booster amplifier.)
Remote booster amplifier wiring to sensor
2
) 2-wire
28Micro Motion® Model D and DT Sensors Instruction Manual
Page 33
Wiring continued
Factory-supplied 9-wire
cable for intrinsically
safe wiring
(RTD and pickoffs)
Wiring to
transmitter
Remove screw and terminal cover
before installing wiring. Re-install
cover before operating
Connection diagram
From remote
booster amp
terminal
To sensor
explosion-proof
J-box terminal
11
22
CAUTION
Remote booster amplifier drive wiring
Wiring to a transmitter (D600
sensor with junction box)
The instructions in this section explain how to connect a fully prepared
9-wire Micro Motion flowmeter cable to the sensor and transmitter.
• The procedure for preparing Micro Motion cable and cable glands is
described in the instructions that are shipped with the cable.
• Install cable and wiring to meet local code requirements.
Cable connections to sensor and transmitter
The wiring procedure is the same for the sensor and transmitter. Refer to
the wiring diagrams on the following pages, and follow these steps:
Failure to seal the sensor and transmitter housings
could cause a short circuit, which would result in
measurement error or flowmeter failure.
• Ensure integrity of gaskets and O-rings.
• Grease all O-rings before sealing.
• Install drip legs in cable or conduit.
• Seal all conduit openings.
Micro Motion® Model D and DT Sensors Instruction Manual29
Page 34
Wiring continued
CAUTION
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
Black (drains)
Connect outer
braid of shielded
or armored cable
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Ye l l ow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Green
White
Brown
Violet
Ye l l ow
Orange
Blue
Gray
Red
Model D600 sensor
junction box
terminals
Model 3500
with I/O cable
Not approved for intrinsic safety
in Europe
Prepare cable in accordance with the
instructions that are shipped with the cable.
Do not allow shields to contact sensor
junction box.
Model 3500
with screw-type or
solder-tail terminals
Ye l l ow
Violet
Green
Blue
Brown
Black (Drains)
Orange
White
Gray
Red
c4
c6
c8
c10
c12
a4
a6
a8
a10
a12
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Ye l l ow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Green
White
Brown
Violet
Ye l l ow
Orange
Blue
Gray
Red
Model D600 sensor
junction box
terminals
Prepare cable in accordance with the
instructions that are shipped with the cable.
Do not allow shields to contact sensor
junction box.
1. Locate the wires by color and terminal number.
2. Insert the stripped ends of the individual wires into the terminal
blocks. No bare wires should remain exposed.
• At the sensor, connect wiring inside the junction box.
• At the transmitter, connect wiring to the transmitter’s intrinsically
safe terminals for sensor wiring.
3. Tighten the screws to hold the wires in place.
4. Ensure integrity of gaskets, then tightly close and seal the
junction-box cover and all housing covers on the transmitter.
Drain wires from a 9-wire cable must be clipped at the
sensor end and insulated with heat-shrink wrapping.
Failure to properly terminate drain wires will cause
sensor error.
Model D600 wiring to Model 3500 with I/O cable
Model D600 wiring to Model 3500 with screw or solder terminals
30Micro Motion® Model D and DT Sensors Instruction Manual
Page 35
Wiring continued
Model 3700
terminals
Red
Brown
Ye l l ow
Black (drains)
Violet
Orange
Green
White
Blue
Gray
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Ye l l ow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Green
White
Brown
Violet
Yellow
Orange
Blue
Gray
Red
Model D600 sensor
junction box
terminals
Prepare cable in accordance with the
instructions that are shipped with the cable.
Do not allow shields to contact sensor
junction box.
Green
White
Brown
Violet
Ye l l ow
Orange
Blue
Gray
Red
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Ye l l ow
Clip drain wire back
Model D600 sensor
junction box
terminals
Flowmeter
cable
Field-mount
RFT9739 terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Brown
Orange
Green
Violet
White
Gray
Blue
Yellow
Red
Black (Drains)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the
instructions that are shipped with the cable.
Do not allow shields to contact sensor
junction box.
Rack-mount
RFT9739 terminals
Red
Ye l l ow
Orange
White
Gray
Brown
Black (Drains)
Violet
Green
Blue
B2
B4
B6
B8
B10
Z2
Z4
Z6
Z8
Z10
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Ye l l ow
Clip drain wire back
Flowmeter
cable
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Maximum cable length 1000 ft. (300 m)
Green
White
Brown
Violet
Ye l l ow
Orange
Blue
Gray
Red
Model D600 sensor
junction box
terminals
Prepare cable in accordance with the
instructions that are shipped with the cable.
Do not allow shields to contact sensor
junction box.
Model D600 wiring to Model 3700
Model D600 wiring to RFT9739 field-mount transmitter
Model D600 wiring to RFT9739 rack-mount transmitter
Micro Motion® Model D and DT Sensors Instruction Manual31
Page 36
Wiring continued
97531
86420
97531
86420
9 753 1
8 6420
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Yellow
Clip drain wire back
Model D600 sensor
terminals
Flowmeter
cable
RFT9712
terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Brown
Orange
Green
Violet
White
Gray
Blue
Yellow
Red
Black (Drains)
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the instructions
that are shipped with the cable
Green
White
Brown
Violet
Ye l l ow
Orange
Blue
Gray
Red
Green
White
Brown
Violet
Ye l l ow
Orange
Blue
Gray
Red
Brown
Red
Clip drain wire back
Green
White
Clip drain wire back
Blue
Gray
Clip drain wire back
Orange
Violet
Ye l l ow
Clip drain wire back
Model D600 sensor
junction box
terminals
Flowmeter
cable
Field-mount Model
2700 terminals
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Black
(Drains from all
wire sets)
Brown
Violet
Ye l l ow
Maximum cable length 60 ft. (20 m)
Prepare cable in accordance with the
instructions that are shipped with the cable.
Do not allow shields to contact sensor
junction box.
Blue
Gray
Orange
Red
Green
White
Ground screw
Black
Model D600 wiring to RFT9712 transmitter
Model D600 sensor wiring to the 9-wire Model 1700 or 2700 transmitter
Core processor to a 4-wire
remote transmitter or remote
host
32Micro Motion® Model D and DT Sensors Instruction Manual
To connect wiring at the core processor:
1. Use one of the following methods to shield the wiring from the core
processor to the remote transmitter:
• If you are installing unshielded wiring in continuous metallic conduit
that provides 360° termination shielding for the enclosed wiring, go
to Step 6, page 35.
• If you are installing user-supplied cable gland with shielded cable or
armored cable, terminate the shields in the cable gland. Terminate
both the armored braid and the shield drain wires in the cable gland.
• If you are installing a Micro Motion-supplied cable gland at the core
processor housing:
- Prepare the cable and apply shielded heat shrink as described
below. The shielded heat shrink provides a shield termination
suitable for use in the gland when using cable whose shield
consists of foil and not a braid. Proceed to Step 2.
Page 37
Wiring continued
4 1/2 in
(114 mm)
3/4 in
(19 mm)
7/8 in
(22 mm)
7/8 in
(22 mm)
Shielded heat shrink
Gland body
Gland nut
Gland clamping
insert
Shield drain wire(s) wrapped twice around exposed shield foil
- With armored cable, where the shield consists of braid, prepare the
cable as described below, but do not apply heat shrink. Proceed to
Step 2.
2. Remove the cover from the core processor.
3. Slide the gland nut and the clamping insert over the cable.
4. For connection at the core processor housing, prepare shielded cable
as follows (for armored cable, omit steps d, e, f, and g):
a. Strip 4 1/2 inches (114 mm) of cable jacket.
b. Remove the clear wrap that is inside the cable jacket, and remove
the filler material between the wires.
c. Remove the foil shield that is around the insulated wires, leaving
3/4 inch (19 mm) of foil or braid and drain wires exposed, and
separate the wires.
d. Wrap the shield drain wire(s) around the exposed foil twice. Cut off
the excess wire.
e. Place the EMI-shielded heat shrink over the exposed shield drain
wire(s). The tubing should completely cover the drain wires.
Micro Motion® Model D and DT Sensors Instruction Manual33
f. Without burning the cable, apply heat (250 °F or 120 °C) to shrink
g. Position gland clamping insert so the interior end is flush with the
heat shrink.
h. Fold the cloth shield or braid and drain wires over the clamping
insert and approximately 1/8 inch (3 mm) past the O-ring.
i. Install the gland body into the core processor housing conduit
opening.
5. Insert the wires through the gland body and assemble the gland by
tightening the gland nut.
6. Identify the wires in the 4-wire cable. The 4-wire cable supplied by
Micro Motion consists of one pair of 18 AWG (0,75 mm
2
) wires (red
and black), which should be used for the VDC connection, and one
pair of 22 AWG (0,35 mm
2
) wire (green and white), which should be
used for the RS-485 connection. Connect the four wires to the
numbered slots on the core processor, matching corresponding
numbered terminals on the transmitter.
34Micro Motion® Model D and DT Sensors Instruction Manual
Page 39
Wiring continued
WARNING
Power supply +
(Red wire)
Power su pply –
(Black wire)
RS-485A
(White wire)
RS-485B
(Green wire)
Core processor housing internal ground screw
• For connections to earth ground when sensor cannot be grounded via
piping and local codes require ground connections to be made internally
• Do not connect shield drain wires to this terminal
7. Reattach the core processor housing.
Twisting the core processor will damage the sensor.
Do not twist the core processor.
8. Shield and shield drain wire(s) should not be grounded at the
transmitter.
• For wiring at the transmitter, see the transmitter Quick Reference
Guide (QRG).
• If you are connecting to an MVDSolo with MVD Direct Connect
barrier supplied by Micro Motion, the barrier supplies power to the
core processor. Refer to the barrier documentation to identify the
terminals at the barrier.
• If you are connecting to an MVDSolo without I.S. barrier:
- Connect the VDC wires from the core processor (see figure on
page 36) to an independent power supply. This power supply must
connect only to the core processor. A recommended power supply
is the SDN series of 24-VDC power supplies manufactured by
Sola/Hevi-Duty.
- Do not ground either connection of the power supply.
™
I.S.
- Connect the RS-485 wires from the core processor (see figure
below) to the RS-485 terminals at the remote host. Refer to the
vendor documentation to identify the terminals.
Micro Motion® Model D and DT Sensors Instruction Manual35
Page 40
Wiring continued
Power supply +
Power supply –
RS-485B
RS-485A
CAUTION
Core processor terminals
Sensor grounding
Ground the sensor and transmitter independently.
Improper grounding could cause measurement error.
To reduce the risk of measurement error:
• Ground the flowmeter to earth, or follow ground network
requirements for the facility.
• For installation in an area that requires intrinsic safety,
refer to Micro Motion hazardous approval documentation,
shipped with the sensor or available from the Micro
Motion web site.
• For hazardous area installations in Europe, refer to
standard EN 60079-14 if national standards do not apply.
The sensor can be grounded via the piping if the joints in the pipeline are
ground-bonded. If the sensor is not grounded via the piping, connect a
ground wire to the internal or external grounding screw, which is located
on the core processor or junction box.
If national standards are not in effect, follow these guidelines:
• Use copper wire, 14 AWG (2,5 mm
2
) or larger wire size for grounding.
• Keep all ground leads as short as possible, less than 1 ohm
impedance.
• Connect ground leads directly to earth, or follow plant standards.
36Micro Motion® Model D and DT Sensors Instruction Manual
Refer to the transmitter documentation for instructions on grounding the
transmitter.
Page 41
Wiring continued
Other Model D
sensors
Model DT
sensors
Model D600
sensors
Sensor grounding screw
Micro Motion® Model D and DT Sensors Instruction Manual37
Page 42
38Micro Motion® Model D and DT Sensors Instruction Manual
Page 43
Installation
Step 5Startup
Zeroing
Configuration, calibration, and
characterization
After the flowmeter has been fully installed, you must perform the
zeroing procedure. Flowmeter zeroing establishes flowmeter response
to zero flow and sets a baseline for flow measurement. Refer to the
transmitter instruction manual for information on performing the zeroing
procedure.
You can use the transmitter to configure, calibrate, and characterize the
meter. For more information, refer to the transmitter instruction manuals.
The following information explains the difference between configuration,
calibration, and characterization. Certain parameters might require
configuration even when calibration is not necessary.
Configuration parameters include such items as flowmeter tag,
measurement units, flow direction, damping values, and slug flow
parameters. If requested at time of order, the meter is configured at the
factory according to customer specifications.
Calibration accounts for the flowmeter’s sensitivity to flow, density, and
temperature. Calibration is done at the factory.
Characterization is the process of entering calibration factors for flow,
density, and temperature directly into transmitter memory, instead of
performing field calibration procedures. Calibration factors can be found
on the sensor serial number tag and on the certificate that is shipped
with the sensor.
For instructions about flowmeter configuration, calibration, and
characterization, see the manual that was shipped with the transmitter.
If the sensor and transmitter are ordered together as a Coriolis
flowmeter, the factory has characterized the meter — no additional
characterization is necessary. If either the sensor or transmitter is
replaced, characterization is required.
Micro Motion® Model D and DT Sensors Instruction Manual39
Page 44
Startup continued
Customer Service
The Micro Motion Customer Service Department is available for
assistance with flowmeter startup if you experience problems you
cannot solve on your own.
If possible, provide us with the model numbers and/or serial numbers of
your Micro Motion equipment, which will assist us in answering your
questions.
• In the U.S.A., phone 1-800-522-MASS (1-800-522-6277), 24 hours
• In Canada and Latin America, phone +1 303-527-5200 (U.S.A.)
• In Asia, phone +65 6777-8211 (Singapore)
• In the U.K., phone 0870 240 1978 (toll-free)
• Outside the U.K., phone +31 (0) 318 495 555 (The Netherlands)
• Or visit our website at www.micromotion.com.
40Micro Motion® Model D and DT Sensors Instruction Manual
Page 45
Troubleshooting
General information
Most troubleshooting is performed at the transmitter. However, the
following troubleshooting topics are described in this manual:
• Zero drift, page 42
• Erratic flow rate, page 43
• Inaccurate flow rate or batch total, page 44
• Inaccurate density reading, page 45
• Inaccurate temperature reading, page 46
If you cannot find the problem you are looking for, check the transmitter
instruction manual.
To troubleshoot the flowmeter, you might need a digital multimeter
(DMM) or similar device, the transmitter display, if it has one, and one of
the following:
• HART Communicator
• ProLink or ProLink II software
• AMS software
• Modbus master controller (RFT9739, Series 1000, or Series 2000)
• Fieldbus host controller (Series 1000 or Series 2000)
• Profibus-PA host controller (Series 1000 or Series 2000)
If you cannot find the problem you are looking for, or if troubleshooting
fails to reveal the problem, contact the Micro Motion Customer Service
Department.
If possible, provide us with the model numbers and/or serial numbers of
your Micro Motion equipment, which will assist us in answering your
questions.
• In the U.S.A., phone 1-800-522-MASS (1-800-522-6277), 24 hours
• In Canada and Latin America, phone +1 303-527-5200 (U.S.A.)
• In Asia, phone +65 6777-8211 (Singapore)
• In the U.K., phone 0870 240 1978 (toll-free)
• Outside the U.K., phone +31 (0) 318 495 555 (The Netherlands)
Micro Motion® Model D and DT Sensors Instruction Manual41
Page 46
Troubleshooting continued
Zero drift
Symptom
The flowmeter indicates the process fluid is flowing while flow is
stopped; or indicates a flow rate that does not agree with a reference
rate at low flow, but does agree at higher flow rates.
Troubleshooting instructions
To troubleshoot zero drift, you will need one of the communications
devices listed on page 46 or a transmitter with a display. Refer to the
table below for the necessary steps to troubleshoot zero drift.
Table 1.Troubleshooting zero drift
ProcedureInstructionsWhat to do next
1. Check for leaking valves and seals• If no leaks are found, go to step 2
2. Check the flow unitsSee page 46• If the flow units are OK, go to step 3
3. Make sure the flowmeter was
zeroed properly
4. Check for the proper flow
calibration factor
5. Check the damping valueSee page 50• If the damping value is OK, go to step 6
6. Check for two-phase flowSee page 53• If there is no two-phase flow, go to step 7
7. Check for moisture in the sensor
junction box
8. Check for faulty or improperly
installed flowmeter wiring
9. Check for faulty or improperly
installed grounding
10. Check for mounting stress on the
sensor
11. Check for vibration or crosstalkSee page 53• If there is no vibration or crosstalk, go to step 12
12. Make sure the sensor is oriented
properly
13. Check for plugging or build-up on
the sensor flow tubes
14. Check for RF interferenceSee page 51• If there is no interference, or the source cannot be detected,
15. Check again for zero drift• If there is no longer any zero drift, you’ve solved the problem
16. Contact Micro MotionPhone numbers are
See page 39• If the flowmeter was zeroed properly, go to step 4
See page 49• If the flow cal factor is correct, go to step 5
See page 52• If there is no moisture present, go to step 8
See page 47• If the wiring is OK, go to step 9
See page 51• If the grounding is OK, go to step 10
See page 53• If the sensor mount is OK, go to step 11
See page 13• If the sensor is oriented properly, go to step 13
See page 54• If the tubes are not plugged, go to step 14
listed on page 41
• If leaks are found, eliminate them, then go to step 15
• If the flow units are wrong, change them, then go to step 15
• If the flowmeter was not zeroed properly, zero it, then go
to step 15
• If the flow cal factor is incorrect, change it, then go to step 15
• If the damping value is too low, change it, then go to step 15
• If there is two-phase flow, fix the problem, then go to step 15
• If there is moisture in the junction box, dry out and seal the
junction box, then go to step 15
• If the wiring is faulty, fix or replace it, then go to step 15
• If the grounding is incorrect or faulty, fix it, then go to step 15
• If there are mounting stresses, fix it, then go to step 15
• If there is vibration or crosstalk, eliminate it, then go to
step 15
• If the sensor is not oriented properly, change the orientation,
then go to step 15
• If there is plugging or build-up, clear the tubes, then go to
step 15
go to step 16
• If there is interference, eliminate it, then go to step 15
• If the zero drifts again, start over at step 3 or go to step 16
42Micro Motion® Model D and DT Sensors Instruction Manual
Page 47
Troubleshooting continued
Erratic flow rate
Symptom
The flowmeter indicates the flow rate is varying, even though it is steady.
Troubleshooting instructions
To troubleshoot an erratic flow rate, you will need one of the
communications devices listed on page 46 or a transmitter with a
display. Refer to the table below for the necessary steps to troubleshoot
an erratic flow rate.
Table 2.Troubleshooting erratic flow rate
ProcedureInstructionsWhat to do next
1. Check for erratic flow rate at the
transmitter
2. Check for faulty output wiringSee page 47• If the output wiring is OK, go to step 3
3. Check the receiving device for
malfunctions
4. Check the flow unitsSee page 46• If the flow units are OK, go to step 5
5. Check the damping valueSee page 50• If the damping value is OK, go to step 6
6. Check for stable drive gainSee page 50• If the drive gain is stable, go to step 7
7. Check for a stable density reading See page 50• If the density reading is stable, go to step 8
8. Check for faulty or improperly
installed flowmeter wiring
9. Check for faulty or improperly
installed grounding
10. Check for vibration or crosstalkSee page 53• If there is no vibration or crosstalk, go to step 11
11. Check for two-phase flowSee page 53• If there is no two-phase flow, go to step 12
12. Check for plugging or build-up on
the sensor flow tubes
13. Check again for erratic flow rateSee page 47• If the signal is no longer erratic, you’ve solved the problem
14. Contact Micro MotionPhone numbers are
See page 47• If the signal is stable at the transmitter, go to step 2
See instruction
manual for the device
See page 47• If the flowmeter wiring is OK, go to step 9
See page 51• If the grounding is OK, go to step 10
See page 54• If the tubes are not plugged, go to step 14
listed on page 41
• If the signal is erratic at the transmitter, go to step 4
• If the output wiring is faulty, repair or replace it, then go to
step 13
• If the receiving device is OK, go to step 4
• If the receiving device is faulty, contact the manufacturer
• If the flow units are wrong, change them, then go to step 13
• If the damping value is too low, change it, then go to step 13
• If the drive gain is not stable, go to step 11
• If the density reading is not stable, go to step 11
• If the flowmeter wiring is incorrect or faulty, fix or replace it,
then go to step 13
• If the grounding is incorrect or faulty, fix it, then go to step 13
• If there is vibration or crosstalk, eliminate it, then go to
step 13
• If there is two-phase flow, fix the problem, then go to step 13
• If there is plugging or build-up, clear the tubes, then go to
step 13
• If the signal is still erratic, start over at step 1 or go to step 14
Micro Motion® Model D and DT Sensors Instruction Manual43
Page 48
Troubleshooting continued
Inaccurate flow rate or batch total
Symptom
The flowmeter indicates a flow rate or batch total that does not agree
with a reference rate or total.
Troubleshooting instructions
To troubleshoot an inaccurate flow rate or batch total, you will need one
of the communications devices listed on page 46 or a transmitter with a
display. Refer to the table below for the necessary steps to troubleshoot
an inaccurate rate or total.
Table 3.Troubleshooting inaccurate flow rate or batch total
ProcedureInstructionsWhat to do next
1. Check for the proper flow
calibration factor
2. Check the flow unitsSee page 46• If the flow units are OK, go to step 3
3. Make sure the flowmeter was
zeroed properly
4. Is the flow measurement
configured for mass or volume?
5. Check for the proper density
calibration factor
6. Make sure the density reading is
accurate for the fluid
7. Make sure the temperature
reading is accurate for the fluid
8. Is the flow measurement
configured for mass or volume?
9. Is the reference total based on a
fixed density value?
10. Change flow units to mass flow
units
11. Check for faulty or improperly
installed grounding
12. Check for two-phase flowSee page 53• If there is no two-phase flow, go to step 13
13. Check the scale (or reference
measurement) for accuracy
14. Check for faulty or improperly
installed flowmeter wiring
15. Run a new batch and check again
for an inaccurate rate or total
16. Contact Micro MotionPhone numbers are
See page 49• If the flow cal factor is correct, go to step 2
See page 39• If the flowmeter was zeroed properly, go to step 4
See page 46• If the configuration is for mass, go to step 6
See page 49• If the dens cal factor is correct, go to step 6
See page 50• If the density reading is correct, go to step 7
See page 50• If the temperature reading is correct, go to step 8
See page 46• If the configuration is for mass, go to step 11
See page 46• Go to step 15
See page 51• If the grounding is OK, go to step 12
Use your plant
procedures
See page 47• If the flowmeter wiring is OK, go to step 16
listed on page 41
• If the flow cal factor is incorrect, change it, then go to step 15
• If the flow units are wrong, change them, then go to step 15
• If the flowmeter was not zeroed properly, zero it, then go
to step 15
• If the configuration is for volume, go to step 5
• If the dens cal factor is incorrect, change it, then go to
step 15
• If the density reading is wrong, go to step 11
• If the temperature reading is wrong, go to step 14
• If the configuration is for volume, go to step 9
• If the total is based on a fixed value, go to step 10
• If the total is not based on a fixed value, go to step 11
• If the grounding is incorrect or faulty, fix it, then go to step 15
• If there is two-phase flow, fix the problem, then go to step 15
• If the scale is accurate, go to step 14
• If the scale is not accurate, fix it, then go to step 15
• If the flowmeter wiring is incorrect or faulty, fix or replace it,
then go to step 15
• If the rate or total is correct, you’ve solved the problem
• If the rate or total is wrong, start over at step 2 or go to
step 16
44Micro Motion® Model D and DT Sensors Instruction Manual
Page 49
Troubleshooting continued
Inaccurate density reading
Symptom
The flowmeter density measurement is erratic, or is lower or higher than
the density of the fluid.
Troubleshooting instructions
To troubleshoot an inaccurate density reading, you will need one of the
communications devices listed on page 46 or a transmitter with a
display. Refer to the table below for the necessary steps to troubleshoot
an inaccurate density reading.
Table 4.Troubleshooting inaccurate density reading
ProcedureInstructionsWhat to do next
1. Check for stable density reading
at the transmitter
2. Check for the proper density
calibration factor
3. Check for faulty or improperly
installed flowmeter wiring
4. Check for faulty or improperly
installed grounding
5. Check to see if the density reading
is low or high
6. Run a quality check on the
process fluid
7. If you checked the wiring in step 3,
go to step 8, otherwise, check for
faulty or improperly installed
flowmeter wiring
8. Check for two-phase flowSee page 53• If there is no two-phase flow, go to step 9
9. Check for vibration or crosstalkSee page 53• If there is no vibration or crosstalk, go to step 12
10. Check for plugging or build-up on
the sensor flow tubes
11. Check again for inaccurate density
reading at the transmitter
12. Contact Micro MotionPhone numbers are
See page 50• If the density reading is stable, go to step 2
See page 49• If the dens cal factor is correct, go to step 4
See page 47• If the flowmeter wiring is OK, go to step 4
See page 51• If the grounding is OK, go to step 5
See page 50• If the density reading is low, go to step 6
Use your plant
procedures
See page 47• If the flowmeter wiring is OK, go to step 8
See page 54• If the tubes are not plugged, go to step 12
See page 50• If the reading is correct, you’ve solved the problem
listed on page 41
• If the density reading is not stable, go to step 3
• If the dens cal factor is incorrect, change it, then go to
step 11
• If the flowmeter wiring is incorrect or faulty, fix or replace it,
then go to step 11
• If the grounding is incorrect or faulty, fix it, then go to step 11
• If the density reading is high, go to step 10
• If the product quality is OK, go to step 7
• If the product quality is not OK, fix it, then go to step 11
• If the flowmeter wiring is incorrect or faulty, fix or replace it,
then go to step 11
• If there is two-phase flow, fix the problem, then go to step 11
• If there is vibration or crosstalk, eliminate it, then go to
step 11
• If there is plugging or build-up, clear the tubes, then go to
step 11
• If the reading is still wrong, start over at step 1 or go to
step 12
Micro Motion® Model D and DT Sensors Instruction Manual45
Page 50
Troubleshooting continued
Inaccurate temperature reading
Symptom
The flowmeter temperature reading is different than expected.
Troubleshooting instructions
To troubleshoot an inaccurate temperature reading, you will need one of
the communications devices listed on page 46 or a transmitter with a
display. Refer to the table below for the necessary steps to troubleshoot
an inaccurate temperature reading.
Table 5.Troubleshooting inaccurate temperature reading
ProcedureInstructionsWhat to do next
1. Check for faulty or improperly
installed flowmeter wiring
2. Check for the proper temperature
calibration factor
3. Check again for inaccurate
temperature reading at the
transmitter
4. Contact Micro MotionPhone numbers are
Troubleshooting at the
transmitter
See page 47• If the flowmeter wiring is OK, go to step 2
• If the flowmeter wiring is faulty, fix or replace it, then go to
step 3
See page 49• If the temp cal factor is correct, go to step 4
• If the temp cal factor is incorrect, change it, then go to step 3
See page 50• If the reading is correct, you’ve solved the problem
• If the reading is still wrong, start over at step 1 or go to step 4
listed on page 41
The tables in the preceding sections refer you to this section for
instructions on troubleshooting at the transmitter. To troubleshoot at the
transmitter, you might need a digital multimeter (DMM) or similar device,
the transmitter display, if it has one, and one of the following:
• HART Communicator
• ProLink or ProLink II software
• AMS software
• Modbus master controller (RFT9739 only, Series 1000, or Series 2000)
• Fieldbus host controller (Series 1000, or Series 2000)
• Profibus host controller (Series 1000 or 2000)
Checking or changing the flow units
Check or change the flow units (units of measure) configuration at the
transmitter. If necessary, refer to the instruction manual (or on-line help
for software) for the method you choose.
• Use the transmitter display, if it has one
• Use a HART Communicator, ProLink software, or AMS software
• Use a Modbus, fieldbus, or Profibus-PA host controller
Make sure the configured units of measure are the ones you want. Also,
make sure you know what the abbreviations mean. For example, g/sec is
grams per second, not gallons per second.
46Micro Motion® Model D and DT Sensors Instruction Manual
Page 51
Troubleshooting continued
Checking for erratic flow rate at the transmitter
Before troubleshooting erratic flow rate, you must first determine
whether it is a result of the transmitter or a connected output device.
Check for an erratic flow signal at the transmitter using any of the
following methods. If necessary, refer to the instruction manual (or
on-line help for software) for the method you choose.
• Use the transmitter display, if it has one
• Use a HART Communicator, ProLink software, or AMS software
• Use a Modbus, fieldbus, or Profibus-PA host controller
• Use a DMM on the transmitter’s 4-20 mA or frequency output terminals
If the flow rate or output signal is not erratic at the transmitter outputs,
the problem is not with the transmitter.
Checking for faulty output wiring
Having already checked the output at the transmitter end (above), use a
DMM to check the signal at the other end (the receiving end) of the
output wiring. If the signal is not erratic, the problem is not with the
output wiring.
Checking for faulty flowmeter wiring
Wiring problems are often incorrectly diagnosed as a faulty sensor.
Examine wiring between the sensor and transmitter as follows:
1. Check the cable preparation. The flowmeter cable must be
prepared correctly. The most common problem is improperly
prepared drain wires. See illustration, below. The drains are clipped at
the sensor end. They should not be connected to any terminals in the
sensor junction box. See wiring diagrams, pages 22-32.
2. Check wire terminations. Check to be sure wires are secured tightly
in the terminal blocks, and making good connections. Make sure no
wires remain exposed at either end of the flowmeter cable.
3. Check ohm levels. If the cable was properly prepared and terminal
connections are good, check resistance across wire pairs to
determine whether the flowmeter cable is faulty. The procedure is
performed first at the transmitter, then at the sensor. Follow these
steps:
a. Disconnect the transmitter’s power supply.
b. Disconnect sensor wiring from the transmitter’s flowmeter
terminals.
Micro Motion® Model D and DT Sensors Instruction Manual47
Page 52
Troubleshooting continued
Cable jacket
Wire sets
Wire sets
Drain wire
(one for each wire set)
c. Use a DMM to measure resistance across wire pairs at the
transmitter end of the cable. See table on page 48.
• If the measured value is within the range listed in the table,
reconnect wiring and restore power to the transmitter.
• If the measured resistance is outside the range listed in the table,
repeat the measurements at the sensor junction box.
- If the sensor is a not a D600, refer to the “Nominal resistance
ranges” table below.
- If the sensor is a D600, refer to the table and illustration on
page 49.
- If resistance values measured at the sensor are also outside the
range listed in the table, the sensor might be faulty.
Cross-section of cable with drain wires
Table 6. Nominal resistance ranges for flowmeter circuits (for all D and DT sensors except the D600)
Notes
• Disconnect wires from terminals before checking resistance values.
• Temperature-sensor value increases 0.38675 ohms per °C increase in temperature.
• Nominal resistance values will vary 40% per 100°C. However, confirming an open coil or shorted coil is more important than
any slight deviation from the resistance values presented below.
• Resistance across blue and gray wires (right pickoff circuit) should be within 10% of resistance across green and white wires
(left pickoff circuit).
• Actual resistance values depend on the sensor model and date of manufacture.
• Reading across wire pairs should be steady.
CircuitWire colorsSensor terminals*Nominal resistance range
Drive coilBrown to red1 to 28 to 2650 Ω
Left pickoffGreen to white5 to 916 to 300 Ω
Right pickoffBlue to gray6 to 816 to 300 Ω
Temperature sensorOrange to violet3 to 7100 Ω at 0°C + 0.38675 Ω / °C
Lead length compensatorYellow to violet4 to 7100 Ω at 0°C + 0.38675 Ω / °C
* For transmitter terminal designations, refer to the table below. For D600 sensors, see the illustration and table on page 49.
48Micro Motion® Model D and DT Sensors Instruction Manual
Page 53
Troubleshooting continued
Check drive coil circuit, brown to red here
Check all circuits except
drive coil circuit (brown to
red wires) here
D600 sensor with integral booster amplifier
D600 sensor with remote mounted booster amplifier
(booster amplifier not shown)
Check all circuits except drive coil circuit (brown to red wires) here
Checking ohm levels at a D600 sensor (applicable only to sensors with a junction box)
Table 7.Nominal resistance values for D600 circuits
Notes
• Disconnect wires from terminals before checking resistance values.
• Temperature-sensor value increases 0.38675 ohms per °C increase in temperature.
• Nominal resistance values will vary 40% per 100°C. However, confirming an open coil or shorted coil is more important than
any slight deviation from the resistance values presented below.
• Resistance across blue and gray wires (right pickoff circuit) should be within 10% of resistance across green and white wires
(left pickoff circuit).
• Actual resistance values depend on the sensor model and date of manufacture.
• Reading across wire pairs should be steady.
• See previous illustration for terminal locations.
CircuitWire colorsApproximate nominal resistance
Drive coilBrown to red16 Ω
Primary left pickoffGreen to white140 Ω
Primary right pickoffBlue to gray140 Ω
Secondary left pickoffBrown to white140 Ω
Secondary right pickoffRed to gray140 Ω
Temperature sensorYellow to violet100 Ω at 0°C + 0.38675 Ω / °C
Micro Motion® Model D and DT Sensors Instruction Manual49
Page 54
Troubleshooting continued
Checking the calibration factors
Check or change the flow, density, or temperature calibration factors at
the transmitter. The temperature cal factor is for the RFT9739, Model
1700, Model 2700, Model 3500, and 3700 only. If necessary, refer to the
instruction manual (or on-line help for software) for the method you
choose.
• Use the Model 3500 or 3700 display
• Use a HART Communicator, ProLink or ProLink II software, or AMS
software
• Use the host controller
Enter the calibration factors that are listed on the flowmeter calibration
tag. (Calibration factors are also listed on the certificate that was
shipped with the meter.) If the calibration factors at the flowmeter are
already correct, the problem is not with the calibration factors.
Checking the damping value
Check or change the damping value at the transmitter. If necessary,
refer to the instruction manual (or on-line help for software) for the
method you choose.
• Use the Model 3500 or 3700 display
• Use a HART Communicator, ProLink software, or AMS software
• Use the host controller
In almost all applications, the damping value should be greater than or
equal to 0.8 seconds. If the damping value is already greater than or
equal to 0.8 seconds, the problem is probably not with the damping
value.
Damping values less than 0.8 seconds are used in very few applications.
After troubleshooting is complete, if you have a question about whether
your application might require a lower damping value, contact the Micro
Motion Customer Service Department. Phone numbers are listed on
page 41. The two most common applications affected by a damping
value that is too high are:
• Very short batching applications
• Very short-pass proving applications
Checking the drive gain
Contact Micro Motion to check the drive gain. Phone numbers are listed
on page 41.
If the transmitter is a Model 1700, 2700, 3500, or 3700, you can use the
display to view drive gain. For more information, refer to the manual that
is shipped with the transmitter.
Checking the density or temperature reading
View the flowmeter density or temperature measurement in any of
several ways:
• Use the transmitter display, if it has one
• Use a HART Communicator, ProLink or ProLink II software, or AMS
software
• Use the connected output device, if there is one
50Micro Motion® Model D and DT Sensors Instruction Manual
Page 55
Troubleshooting continued
External shield
(braided wire)
Cable jacket
Individual wire sets
with drain wires
• Use the host controller
If necessary, test the process fluid to confirm the flowmeter
measurement is correct.
Checking for RF or transient-voltage interference
Radio-frequency (RF) or transient-voltage interference can affect the
input or output signals at the transmitter. If you suspect interference, and
can eliminate the source, do so before checking the alternatives
described below.
Output wiring. Output wiring can be affected by interference. Make
sure output wiring from the transmitter is properly grounded in
accordance with the instructions in the transmitter manual. Also make
sure no wires remain exposed at either end of output wiring.
Flowmeter cable. If the flowmeter cable does not have an external
shield (see illustration, below), and is not installed in conduit, it could be
affected by interference. Also make sure no wires remain exposed at
either end of the flowmeter cable.
Troubleshooting at the sensor
Cross-section of externally shielded cable
The tables in the preceding sections refer you to this section for
instructions on troubleshooting at the sensor. To troubleshoot at the
sensor, you might need a digital multimeter (DMM) or similar device. For
some procedures, you might also need the transmitter manual.
Checking flowmeter grounding
The sensor can be grounded via the piping, as long as joints in the
pipeline are ground-bonded, or by means of a ground screw on the
sensor case. See illustration, below. Transmitter grounding is described
in the transmitter instruction manual.
If the sensor is not grounded via the piping, and if national standards are
not in effect, adhere to these guidelines to ground the sensor via the
junction box:
Micro Motion® Model D and DT Sensors Instruction Manual51
• Use copper wire, 14 AWG (2,5 mm
• Keep all ground leads as short as possible, less than 1 ohm
impedance.
• Connect ground leads directly to earth, or follow plant standards.
2
) or larger wire size for grounding.
Page 56
Troubleshooting continued
Other Model D
sensors
Model DT
sensors
Model D600
sensors
WARNING
Sensor grounding screw
For hazardous area installation in Europe, use standard EN 60079-14 as
a guideline if national standards are not in effect.
Checking for moisture in the core processor or sensor junction box
Note that the following will help reduce the risk of getting moisture in the
core processor or sensor junction box: If possible, install wiring with the
conduit openings pointed down to reduce the risk of condensation or
moisture in the housing. Otherwise, install drip legs on the cable or
conduit.
All wiring compartments must be sealed to prevent a short circuit. A
short would result in measurement error or flowmeter failure.
• The D600 has a junction box and a booster amplifier housing.
• Do not open the D600 booster amplifier housing while the booster
amplifier is energized. See the warning statement below.
• Replace all covers and seal all openings before applying power to a
D600 sensor.
Explosion Hazard
In a hazardous area:
• Do not open booster amplifier housing cover while
booster amplifier is energized.
• Wait at least 30 minutes after power is shut off before
opening.
52Micro Motion® Model D and DT Sensors Instruction Manual
Page 57
Troubleshooting continued
Open the junction box (and, for a D600, the booster amplifier housing) to
check for moisture. If moisture is present, dry out the junction box. Do
not use contact cleaner. Follow these guidelines to avoid risk of
condensation or excessive moisture from accumulating:
• Seal all conduit openings.
• Install drip legs in conduit or cable.
• If possible, install wiring with junction-box openings pointed down.
• Check integrity of gaskets.
• Close and fully seal all housing covers.
Checking for mounting stress on the sensor
Because each installation is unique, it is not possible to offer a definitive
solution for mounting problems. However, mounting stresses can be
caused by one or more of the following conditions:
• The pipeline is being supported by (hung from) the sensor.
• Misaligned piping was drawn together by the sensor.
• An unsupported pipeline is not sturdy enough to support the sensor.
If you are unable to determine whether the process connections are
being subjected to mounting stress, contact Micro Motion for additional
assistance. Phone numbers are listed on page 41.
Checking for vibration and crosstalk
Micro Motion sensors have been designed to minimize the effect of
vibration. In very rare cases, however, vibration or crosstalk can affect
flowmeter operation. Crosstalk is the transfer of resonant vibration from
one sensor to another, and sometimes occurs when two like-size
sensors are installed in close proximity to each other and are operating
on the same fluid for short periods of time.
Micro Motion meters are rarely affected by vibration, so vibration or
crosstalk is probably not the problem. If you are not sure whether
vibration or crosstalk is affecting the sensor, contact Micro Motion for
additional assistance. Phone numbers are listed on page 41.
Checking for 2-phase flow
Two-phase flow occurs when air or gas is present in a liquid process
stream, or when liquid is present in a gas process stream. Two-phase
flow has several causes, as described below.
Leaks. Leaks can occur at process connections, valve seals, and pump
seals, resulting in air being introduced into a liquid stream. Air might also
be drawn in at the system inlet. Check the system for leaks, and repair
any leaks that are found.
Cavitation and flashing. Cavitation and flashing are caused by
operating the system at or near the process fluid vapor pressure,
resulting in pockets of air or gas being introduced into the process fluid.
If the sensor is near a device that causes pressure drop, such as a
control valve, locating the sensor upstream from the device can
decrease the risk of flashing. Alternatively, increasing back pressure
downstream from the sensor can also reduce the risk of cavitation and
flashing.
Cascading. Cascading of the fluid can occur when the flow rate
diminishes to the point where the sensor tube is only partially filled.
Micro Motion® Model D and DT Sensors Instruction Manual53
Page 58
Troubleshooting continued
Often, this occurs because fluid is flowing downward through a sensor
installed in a vertical pipeline. (When a sensor is mounted this way, it is
called the flag-mount orientation).
To help eliminate cascading, fluids should flow upward through a flagmounted sensor. Mounting the sensor in the preferred orientation often
reduces cascading. (See Orientation, page 13.) Increasing back
pressure downstream from the sensor can also reduce or eliminate
cascading.
High points in the system. When measuring liquids, entrained air
(pockets of non-condensable gas) can collect in high points of a fluid
system. If the fluid velocity is low, and/or the high points are very high
relative to the system, entrained air pockets can grow and persist. If the
air pocket releases and passes through the sensor, measurement error
could occur. One possible solution is to install vent valves or air
eliminators at a high point in the system, upstream from the sensor. Use
your common plant practices if you choose to install vent valves or air
eliminators.
Low points in the system. When measuring gases, liquid condensate
can collect in low points of a fluid system. If the fluid velocity is low,
and/or the low points are very low relative to the system, condensates
can accumulate and persist. If the liquid passes through the sensor,
measurement error could occur. One possible solution is to install
condensate valves at a low point in the system, upstream from the
sensor. Use your common plant practices if you choose to install
condensate valves.
Checking for plugging or build-up
If the process fluid tends to build up in the piping, the sensor can
become plugged or partially plugged due to build-up of material inside
the sensor flow tubes. To determine whether plugging or build-up has
occurred, check at the transmitter for a high drive gain and high density
reading (see page 50).
• If the drive gain and the density reading are both high, flush or clean
the sensor, then check for an accurate density reading on water (or
some other fluid with a known density). If the density is still wrong,
plugging of the tube is probably not the problem.
• If either the drive gain or the density reading is not high, plugging of the
tube is probably not the problem.
54Micro Motion® Model D and DT Sensors Instruction Manual
Page 59
Appendix
1/2" NPT female
purge fitting
Purge plug
Sensor case
Front
view
Side
view
APurge Fittings
Keeping purge fittings sealed
If the sensor has purge fittings, they should remain sealed at all times.
After a purge plug is removed, the sensor case should be purged with a
dry, inert gas (such as argon or nitrogen), and resealed. See Case purging procedure, page 56.
Purging the case protects internal components. Before Micro Motion
ships a sensor from the factory, it purges the sensor case. If you never
loosen or remove the fittings, you do not have to be concerned about
them.
For more information, contact the Micro Motion Customer Service
Department:
• In the U.S.A., phone 1-800-522-MASS (1-800-522-6277), 24 hours
• In Canada and Latin America, phone +1 303-527-5200 (U.S.A.)
• In Asia, phone +65 6777-8211 (Singapore)
• In the U.K., phone 0870 240 1978 (toll-free)
• Outside the U.K., phone +31 (0) 318 495 555 (The Netherlands)
• Or visit our website at www.micromotion.com.
Purge fittings
Micro Motion® Model D and DT Sensors Instruction Manual55
Page 60
Purge Fittings continued
WARNING
CAUTION
Using purge fittings
Removing a purge plug
Case purging procedure
The primary reason for having purge fittings is to monitor pressure inside
the sensor case. Some users, such as those measuring highly volatile
fluids, install a pressure transmitter across the sensor purge fittings. A
control device, connected to the pressure transmitter, shuts down the
process if a change in pressure is detected. This provides additional
protection should a rupture occur inside the sensor.
If you remove a purge plug from the sensor case, it is necessary to
re-purge the case.
Removing a purge plug will require the sensor case to
be re-purged with a dry inert gas. Improper
pressurization could result in serious personal injury.
Follow all instructions for re-purging the sensor case. See
Case purging procedure, below.
Read all instructions before performing the case purging procedure. It is
not necessary to perform this procedure unless a purge plug has been
removed.
1. Shut down the process, or set control devices for manual operation.
Performing the purge procedure while the flowmeter is
operating could affect measurement accuracy,
resulting in inaccurate flow signals.
Before performing the case purging procedure, shut down
the process, or set control devices for manual operation.
2. Remove both purge plugs from the sensor case. If purge lines are
being used, open the valve in the purge lines.
56Micro Motion® Model D and DT Sensors Instruction Manual
Page 61
Purge Fittings continued
3. Connect the supply of dry, inert gas to the inlet purge connection or
open inlet purge line. Leave the outlet connection open.
• Exercise caution to avoid introducing dirt, moisture, rust, or other
contaminants into the sensor case.
• If the purge gas is heavier than air (such as argon), locate the inlet
lower than the outlet, so the purge gas will displace air from bottom
to top.
• If the purge gas is lighter than air (such as nitrogen), locate the inlet
higher than the outlet, so the purge gas will displace air from top to
bottom.
4. Make sure there is a tight seal between the inlet connection and
sensor case, so air cannot be drawn by suction into the case or purge
line.
5. The purge time is the amount of time required for full exchange of
atmosphere to inert gas. For each sensor size, the purge time is
different. Refer to the table below. If purge lines are being used,
increase the purge time to fill the additional volume of the purge line.
6. Avoid pressurizing the sensor case. At the appropriate time, shut off
the gas supply, then immediately seal the purge outlet and inlet
connections. If pressure inside the case elevates above atmospheric
pressure during operation, the flowmeter density calibration will be
inaccurate.
* If purge lines are being used, increase purge time to fill the additional volume.
Purge rate
cubic ft/hr (l/hr)
Time*
minutes
Micro Motion® Model D and DT Sensors Instruction Manual57
Page 62
58Micro Motion® Model D and DT Sensors Instruction Manual
Page 63
Appendix
WARNING
Rupture disk
assembly
Sensor
case
BRupture Disk
Using the rupture disk
The primary reason for having a rupture disk is to vent process fluid from
inside the sensor case, should the sensor flow tube rupture in a highpressure application. Some users, such as those measuring highpressure gases, install a pipeline at the rupture disk fitting, to help
contain escaping process fluid. This provides additional protection
should a rupture occur.
Pressure Relief Zone.
Escaping high-pressure fluid can cause severe injury
or death.
Stay clear of rupture disk pressure-relief area.
For more information, contact the Micro Motion Customer Service
Department:
• In the U.S.A., phone 1-800-522-MASS (1-800-522-6277), 24 hours
• In Canada and Latin America, phone +1 303-527-5200 (U.S.A.)
• In Asia, phone +65 6777-8211 (Singapore)
• In the U.K., phone 0870 240 1978 (toll-free)
• Outside the U.K., phone +31 (0) 318 495 555 (The Netherlands)
• Or visit our website at www.micromotion.com.
Rupture disk
Micro Motion® Model D and DT Sensors Instruction Manual59
Page 64
60Micro Motion® Model D and DT Sensors Instruction Manual
Page 65
Appendix
CAUTION: Removal of plugs will require sensor case to
be repurged with a dry inert gas.
!
WARNING: Improper pressurization may result in
injury. Refer to sensor manual for repurging instructions.
Part No. 1003972, Rev. B
D sensor with
purge fittings
Part No. 1004570
CAUTION
Do not step
or place weight on case.
Precision instrument
enclosed.
CLabel Maintenance and
Replacement
Maintaining and replacing labels
Label number 1003972
Micro Motion product safety labels have been designed in accordance
with the voluntary standard, ANSI Z535.4. If any of the labels illustrated
below is illegible, damaged, or missing, promptly have a new one
installed. The sensor includes the safety labels illustrated below.
Contact Micro Motion for replacement labels:
• In the U.S.A., phone 1-800-522-MASS (1-800-522-6277), 24 hours
• In Canada and Latin America, phone +1 303-527-5200 (U.S.A.)
• In Asia, phone +65 6777-8211 (Singapore)
• In the U.K., phone 0870 240 1978 (toll-free)
• Outside the U.K., phone +31 (0) 318 495 555 (The Netherlands)
• Or visit our website at www.micromotion.com.
For additional information, see Removing a purge plug and Case purging procedure, page 56.
Label number 1004570
Micro Motion® Model D and DT Sensors Instruction Manual61
Page 66
Label Maintenance and Replacement continued
P/N 1004134 Rev. A
WARNING
Pressure Relief Zone.
Escaping pressure
can cause
severe injury or death.
Stay clear of vent.
D sensor with
rupture disk
(label inside core processor housing)
Label number 1004134
For additional information, see Appendix B, page 59.
Label number 3600460
Label number 3005784
62Micro Motion® Model D and DT Sensors Instruction Manual
Page 67
Label Maintenance and Replacement continued
Label number 3100436
Micro Motion® Model D and DT Sensors Instruction Manual63
Page 68
64Micro Motion® Model D and DT Sensors Instruction Manual
Page 69
Appendix
DReturn Policy
General guidelines
New and unused equipment
Used equipment
Micro Motion procedures must be followed when returning equipment.
These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for
Micro Motion employees. Failure to follow Micro Motion procedures will
result in your equipment being refused delivery.
Information on return procedures and forms is available on our web
support system at www.micromotion.com, or by phoning the Micro
Motion Customer Service department.
Only equipment that has not been removed from the original shipping
package will be considered new and unused. New and unused
equipment requires a completed Return Materials Authorization form.
All equipment that is not classified as new and unused is considered
used. This equipment must be completely decontaminated and cleaned
before being returned.
Used equipment must be accompanied by a completed Return Materials
Authorization form and a Decontamination Statement for all process
fluids that have been in contact with the equipment. If a
Decontamination Statement cannot be completed (e.g., for food-grade
process fluids), you must include a statement certifying decontamination
and documenting all foreign substances that have come in contact with
the equipment.
Micro Motion® Model D and DT Sensors Instruction Manual65
Page 70
66Micro Motion® Model D and DT Sensors Instruction Manual
Page 71
Index
A
Air eliminators 54
AMS software 41, 46
Approvals tag
keys for sensor location
B
Batch total
inaccurate batch total
9
44
Before you begin 1–7
additional information 7
installation process 6
your new sensor 1
Booster amplifier
sensor location
C
Cable
10
. See also Flowmeter cable; Wiring
DT sensor 10
glands 29
configuration, calibration, and characterization 39
customer service 40
zeroing 39
T
Temperature
checking
50
inaccurate temperature reading 46
Transmitter
compatible models
1
Troubleshooting 41
air eliminators 54
AMS software 41, 46
at the sensor 51
at the transmitter 46–51
cascading 53
cavitation 53
checking
calibration factors
49
crosstalk 53
damping value 50
density reading 50
drive gain 50
faulty flowmeter wiring 47–49
faulty output wiring 47
grounding 51
junction box 52
mounting stress 53
plugging 54
RF interference 51
temperature reading 50
2-phase flow 53
vibration 53
condensate valves 54
customer service 41
DMM 41, 46
Fieldbus host 46
flashing 53
general information 41
HART Communicator 46
high points in system 54
low points in system 54
procedures