Micro Motion™ 5700 Transmitters with
Intrinsically Safe Outputs
All Installation Types (Integral, 4-Wire, and 9-Wire)
February 2020
Safety messages
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration
of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available
on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion
Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States800-522-6277U.K. and Ireland0870 240 1978Australia800 158 727
3.3 Wire a remote-mount transmitter to the sensor............................................................................. 15
3.4 Ground the meter components...................................................................................................... 17
3.5 Rotate the transmitter on the sensor (optional)..............................................................................19
3.6 Rotate the user interface on the transmitter (optional)...................................................................20
3.7 Rotate the sensor wiring junction box on a remote-mount transmitter (optional).......................... 21
Chapter 4Wiring the channels..................................................................................................... 23
4.1 Installation types for the 5700 transmitter......................................................................................23
4.2 Available channels.......................................................................................................................... 23
4.3 Barriers verified by Micro Motion.................................................................................................... 24
4.4 mA power requirements ................................................................................................................24
4.5 FO and DO power requirements .....................................................................................................26
4.6 Access the wiring channels............................................................................................................. 27
4.7 Wire the Channel A mA/HART Output............................................................................................ 28
4.8 Wire the Channel B and C mA Output............................................................................................. 29
4.9 Wire the mA/SIL output..................................................................................................................30
4.10 Wire the mA/HART multidrop installation.................................................................................... 30
4.11 Wire the Frequency Output or the Discrete Output...................................................................... 31
Chapter 5Wiring the power supply..............................................................................................33
Chapter 6Power up the transmitter............................................................................................. 35
Chapter 7Configuring the transmitter with Guided Setup............................................................ 37
Chapter 8Using the display controls............................................................................................ 39
Chapter 9Available service port connection................................................................................. 41
Appendix A5700 to 3100 transmitter connections..........................................................................43
Installation Manualiii
ContentsInstallation Manual
February 2020MMI-20039473
ivMicro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualBefore you begin
MMI-20039473February 2020
1Before you begin
1.1About this document
This manual provides information on planning, mounting, wiring, and initial setup of the
5700 transmitter. For information on full configuration, maintenance, troubleshooting, or
service of the transmitter, see the configuration and use manual.
The information in this document assumes that users understand basic transmitter and
sensor installation, configuration, and maintenance concepts and procedures.
1.2Hazard messages
This document uses the following criteria for hazard messages based on ANSI standards
Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a
situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration
of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access to protect users' assets. This is true for all
systems used within the facility.
Installation Manual5
Before you beginInstallation Manual
February 2020MMI-20039473
1.3Related documents
You can find all product documentation on the product documentation DVD shipped with
the product or at www.emerson.com.
See any of the following documents for more information:
• Micro Motion 5700 Product Data Sheet
• Micro Motion 5700 Transmitters with Intrinsically Safe Outputs: Configuration and Use
Manual
• Coriolis Flowmeter with Micro Motion Model 5700 Transmitters Safety Manual for Safety
Instrumented Systems (SIS)
• Modbus Interface Tool
• Sensor installation manual
6Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual
MMI-20039473February 2020
Planning
2Planning
2.1Installation checklist
□ If possible, install the transmitter in a location that will prevent direct exposure to
sunlight. The environmental limits for the transmitter may be further restricted by
hazardous area approvals.
□ If you plan to mount the transmitter in a hazardous area:
WARNING
— Verify that the transmitter has the appropriate hazardous area approval. Each
transmitter has a hazardous area approval tag attached to the transmitter
housing.
— Ensure that any cable used between the transmitter and the sensor meets the
hazardous area requirements.
— For ATEX/IECEx installations, strictly adhere to the safety instructions
documented in the ATEX/IECEx approvals documentation available on the
product documentation DVD shipped with the product or at www.emerson.com.
□ Verify that you have the appropriate cable and required cable installation parts for your
installation. For wiring between the transmitter and sensor, verify the maximum cable
length does not exceed 1,000 ft (305 m).
□ Ensure that you use a twisted-pair instrument cable for all output connections.
□ You can mount the transmitter in any orientation as long as the conduit openings or
transmitter display do not point upward.
Installing the transmitter with the conduit openings or transmitter display facing
upward risks condensation moisture entering the transmitter housing, which could
damage the transmitter.
Following are examples of possible orientations for the transmitter.
Preferred orientation
Alternate orientations
□ Mount the meter in a location and orientation that satisfies the following conditions:
— Allows sufficient clearance to open the transmitter housing cover. Install with 8 in
(203 mm) to 10 in (254 mm) clearance at the wiring access points.
— Provides clear access for installing cabling to the transmitter.
— Provides clear access to all wiring terminals for troubleshooting.
• 85 to 240 VAC, 50/60 Hz, 6 watts typical, 11 watts maximum
• 18 to 100 VDC, 6 watts typical, 11 watts maximum
Note
For DC power:
• Power requirements assume a single transmitter per cable.
• At startup, the power source must provide a minimum of 1.5 amps of short-term
current per transmitter and not pull voltage below 18 VDC.
• Length and conductor diameter of the power cable must be sized to provide 18 VDC
minimum at the power terminals, at a load current of 0.7 amps.
Cable sizing formula
M = 18V + (R x L x 0.5A)
• M: minimum supply voltage
• R: cable resistance
• L: cable length (in Ω/ft)
Typical power cable resistance at 68 °F (20.0 °C)
Wire gauge
14 AWG0.0050 Ω/ft
16 AWG0.0080 Ω/ft
18 AWG0.0128 Ω/ft
20 AWG0.0204 Ω/ft
2.5 mm
1.5 mm
1.0 mm
0.75 mm
0.50 mm
2
2
2
2
2
Resistance
0.0136 Ω/m
0.0228 Ω/m
0.0340 Ω/m
0.0460 Ω/m
0.0680 Ω/m
8Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualPlanning
MMI-20039473February 2020
2.2.1Maximum cable lengths between sensor and transmitter
The maximum cable length between the sensor and transmitter that are separately
installed is determined by cable type.
Cable typeWire gaugeMaximum length
Micro Motion 4-wire remote
mount
Micro Motion 9-wire remote
mount
User-supplied 4-wireVDC 22 AWG (0.326 mm²)300 ft (91 m)
Not applicable• 1,000 ft (305 m) without
Ex-approval
• 500 ft (152 m) with IIC
rated sensors
• 1,000 ft (305 m) with IIB
rated sensors
Not applicable60 ft (18 m)
VDC 20 AWG (0.518 mm²)500 ft (152 m)
VDC 18 AWG (0.823 mm²)1,000 ft (305 m)
RS-485 22 AWG (0.326 mm²)
or larger
1,000 ft (305 m)
Installation Manual9
PlanningInstallation Manual
February 2020MMI-20039473
10Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualMounting and sensor wiring
MMI-20039473February 2020
3Mounting and sensor wiring
3.1Mounting and sensor wiring for integralmount transmitters
There are no separate mounting requirements for integral transmitters, and no need to
connect wiring between the transmitter and the sensor.
3.2Mounting transmitters
There are two options available for mounting transmitters:
• Mount the transmitter to a wall or flat surface.
• Mount the transmitter to an instrument pole.
3.2.1
Mounting the transmitter to a wall or flat surface
Prerequisites
• Ensure that the surface is flat and rigid, does not vibrate, or move excessively.
• Confirm that you have the necessary tools, and the mounting kit shipped with the
transmitter.
Procedure
1. Attach the mounting bracket to the transmitter and tighten the screws to 80 in lbf
(9.04 N m) to 90 in lbf (10.17 N m).
Figure 3-1: Mounting bracket to an aluminum transmitter
Installation Manual11
Mounting and sensor wiringInstallation Manual
February 2020MMI-20039473
Figure 3-2: Mounting bracket to a stainless steel transmitter
2. For wall-mount installations, secure the mounting bracket to the prepared surface.
Figure 3-3: Wall-mounting bracket and dimensions for an aluminum
transmitter
A. 2.8 in (71 mm)
B. 2.8 in (71 mm)
12Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualMounting and sensor wiring
MMI-20039473February 2020
Figure 3-4: Wall-mounting bracket and dimensions for a stainless steel
transmitter
A. 7.51 in (190.8 mm)
B. 3.67 in (93.2 mm)
3. For aluminum transmitters, place and attach the transmitter-mounting bracket to
the mounting bracket secured to the wall or instrument pole.
Figure 3-5: Attaching and securing an aluminum transmitter to the mounting
bracket
Tip
To ensure the mounting bracket holes are aligned, insert all attachment bolts into
place before tightening.
Installation Manual13
Mounting and sensor wiringInstallation Manual
February 2020MMI-20039473
3.2.2Mount the transmitter to a pole
Prerequisites
• Ensure that the instrument pole extends at least 12 in (305 mm) from a rigid base and
is no more than 2 in (51 mm) in diameter.
• Confirm that you have the necessary tools, and the instrument-pole mounting kit
shipped with the transmitter.
Procedure
For pole-mount installations, attach the U-bolt mounting piece to the instrument pole.
Figure 3-6: Pole-mounting bracket attachment for an aluminum transmitter
14Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualMounting and sensor wiring
MMI-20039473February 2020
Figure 3-7: Pole-mounting bracket attachment for a stainless steel transmitter
3.3Wire a remote-mount transmitter to the
sensor
Use this procedure to wire a 4-wire or 9-wire remote-mount transmitter to the sensor.
Prerequisites
• Prepare the 4-wire cable as described in the sensor documentation.
• Prepare the 9-wire cable as described in the Micro Motion 9-Wire Flowmeter Cable
Preparation and Installation Guide.
• Connect the cable to the sensor-mounted core processor or junction box as described
in the sensor documentation. You can access all product documentation on the
documentation DVD shipped with the product or at www.emerson.com.
Installation Manual15
Mounting and sensor wiringInstallation Manual
February 2020MMI-20039473
Procedure
1. Remove the transmitter-to-sensor wiring compartment cover to reveal the terminal
connections.
Figure 3-8: Removal of the transmitter-to-sensor wiring compartment cover
2. Feed the sensor wiring cable into the transmitter wiring compartment.
Figure 3-9: Sensor wiring feedthrough
3. Connect the sensor wires to the appropriate terminals.
Important
Terminate the 4-wire cable drain wires only at the sensor/core processor end of the
cable. See the sensor installation manual for more detail. Do not connect the 4-wire
cable drain wires to the ground screw located inside the 5700 junction box.
• See Figure 3-10 for 4-wire terminal connections.
• See Figure 3-11 for 9-wire terminal connections.
16Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Connect the 4 drain wires in the 9-wire cable to the ground screw located inside the
junction box.
4. Replace the transmitter-to-sensor wiring compartment cover and tighten the
screws to 14 in lbf (1.58 N m) to 15 in lbf (1.69 N m).
3.4Ground the meter components
In 4-wire or 9-wire remote installations, the transmitter and sensor are grounded
separately.
Installation Manual17
Mounting and sensor wiringInstallation Manual
February 2020MMI-20039473
Prerequisites
NOTICE
Improper grounding could cause inaccurate measurements or meter failure.
WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result
in an explosion causing death or serious injury.
Note
For hazardous area installations in Europe, refer to standard EN 60079-14 or national
standards.
If national standards are not in effect, adhere to the following guidelines for grounding:
• Use copper wire, 14 AWG (2.08 mm²) or larger wire size.
• Keep all ground leads as short as possible, less than 1 Ω impedance.
• Connect ground leads directly to earth, or follow plant standards.
Procedure
1. Ground the sensor according to the instructions in the sensor documentation.
2. Ground the transmitter according to applicable local standards, using the
transmitter’s internal or external ground screw.
• The earth ground terminal is located inside the power wiring compartment.
• The external ground screw is located on the side of the transmitter located
below the transmitter tag.
18Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualMounting and sensor wiring
MMI-20039473February 2020
3.5Rotate the transmitter on the sensor (optional)
In integral installations, you can rotate the transmitter on the sensor up to 360º in 45º
increments.
Procedure
1. Using a 4 mm hex key, loosen and remove the clamp securing the transmitter head
in place.
Figure 3-12: Removal of the sensor clamp
2. Gently lift the transmitter straight up, and rotate the transmitter to the desired
position.
You can rotate the transmitter to any of the eight positions, but a stop exists that
will not allow a full 360° rotation.
Figure 3-13: Rotation of the transmitter head
3. Gently lower the transmitter onto the base, confirming that the transmitter is in a
locked position.
Installation Manual19
Mounting and sensor wiringInstallation Manual
February 2020MMI-20039473
4. Replace the clamp in its original position and tighten the cap screw. Torque to 28 in
lbf (3.16 N m) to 30 in lbf (3.39 N m).
Figure 3-14: Re-attachment of the sensor clamp
3.6Rotate the user interface on the transmitter
(optional)
The user interface on the transmitter electronics module can be rotated 90°, 180°, or 270°
from the original position.
Figure 3-15: Display components
A. Transmitter housing
B. Sub-bezel
C. Display module
D. Display screws
E. End-cap clamp
F. Cap screw
G. Display cover
20Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualMounting and sensor wiring
MMI-20039473February 2020
Procedure
1. Shut off power to the unit.
WARNING
If the transmitter is in a hazardous area, wait five minutes after disconnecting the
power. Failure to do so could result in an explosion causing death or injury.
2. Loosen and rotate the end cap clamp so that it does not interfere with the cover.
3. Turn the display cover counterclockwise to remove it from the main enclosure.
4. Carefully loosen the captive display screws while holding the display module in
place.
5. Carefully pull the display module out of the main enclosure.
6. Rotate the display module to the desired position.
7. Gently press the display module back onto the connector.
8. Tighten display screws.
9. Place the display cover onto the main enclosure.
10. Turn the display cover clockwise until it is fully seated.
11. Replace the end-cap clamp by tightening the cap screw.
12. Restore power to the transmitter.
3.7Rotate the sensor wiring junction box on a
remote-mount transmitter (optional)
In remote-mount installations, you can rotate the sensor wiring junction box on the
transmitter plus or minus 180º.
Procedure
1. Using a 4 mm hex key, loosen and remove the clamp securing the sensor wiring
junction box in place.
Figure 3-16: Removal of the clamp
2. Gently rotate the junction box to the desired position.
Installation Manual21
Mounting and sensor wiringInstallation Manual
February 2020MMI-20039473
You can rotate the junction box plus or minus 180º to any position.
Figure 3-17: Rotation of the sensor wiring junction box
3. Gently set the junction box into its new position, confirming that the position is
locked.
4. Replace the clamp in its original position and tighten the cap screw. Torque to 28 in
lbf (3.16 N m) to 30 in lbf (3.39 N m).
Figure 3-18: Re-attachment of the clamp
22Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualWiring the channels
MMI-20039473February 2020
4Wiring the channels
4.1Installation types for the 5700 transmitter
WARNING
If you are installing the transmitter in a hazardous area, refer to Micro Motion approval
instructions shipped with the product or available from the Emerson website. Improper
installation in a hazardous area can cause an explosion resulting in injury or death.
A. Hazardous area
B. Safe area
C. 2-wire signal cable
D. Barrier
E. 4-20 mA, FO, or DO
F. Signal input device
G. HART variables
H. DCS
I. Emerson AMS Trex communicator
4.2Available channels
SignalChannel AChannel BChannel CChannel D
Wiring
terminals
mA OutputsmA Output (1) (HART)mA Output (2)mA Output (3)
Frequency
Outputs
Discrete
Outputs
Ui30 V30 V30 V30 V
12345678
Frequency Output (1)Frequency Output (2)
Discrete Output (1)Discrete Output (2)
Ii484 mA484 mA484 mA484 mA
Installation Manual23
Wiring the channelsInstallation Manual
February 2020MMI-20039473
SignalChannel AChannel BChannel CChannel D
Pi2.05 W2.05 W2.05 W2.05 W
Ci150 pF150 pF150 pF150 pF
Li0 μH0 μH0 μH0 μH
4.3Barriers verified by Micro Motion
The following table lists the barriers that Micro Motion has verified with the 5700
transmitter. For other barriers, refer to the manufacturer's data sheet.
Table 4-1: Barriers verified by Micro Motion
VendorBarrier
Micro Motion505
Pepperl & FuchsKFD2-STC1-EX1
Pepperl & FuchsKFD2-STC4-EX1
MTL787S+
MTL7707P+
MTL7787+
MTL5042
MTL3046B
MTL7728P+
MTL4541
STAHL9002/13-280-110-00
PR Electronics5106
4.4mA power requirements
The supply voltage required by the 5700 transmitter depends on the total resistance in the
mA loop. This includes all sensor resistance and wire resistance.
Channel A mA HART terminal requirements
Use the following chart to determine the required supply voltage for Channel A based on
loop resistance.
24Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualWiring the channels
MMI-20039473February 2020
Figure 4-1: Channel A mA/HART supply voltage and loop resistance
A. Total loop resistance R
(including barrier)
max
B. Supply voltage VDC (volts)
C. Operating region with HART
D. Operating region without HART (includes the C range)
Channel B or C terminal requirements
Use the following chart to determine the required supply voltage for Channel B or C based
on loop resistance.
Figure 4-2: Channel B and C mA output supply voltage and loop resistance
A. Total loop resistance R
B. R
load
(including barrier)
max
C. Supply voltage VDC (volts)
D. Operating region
Note
Rmax = (Vsupply - 8) / 0.024
mA Output is linear with process from 3.8 to 20.5 mA, per NAMUR NE-43 (February 2003).
Installation Manual25
Wiring the channelsInstallation Manual
February 2020MMI-20039473
4.5FO and DO power requirements
The supply voltage required by the 5700 transmitter depends on the total resistance in the
mA loop. This includes all sensor resistance and wire resistance.
Channel C or D terminal requirements
Use the following chart to determine the required supply voltage for Channel C or D based
on loop resistance.
Figure 4-3: Channel C or D DO/FO supply voltage and loop resistance
Blue line = Maximum
Red line = Minimum
A. External resistor R
B. Supply voltage VDC (volts)
C. Operating region
Note
Rmax = (Vsupply - 6) / 0.0025
Rmin = 100Ω
load
26Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualWiring the channels
MMI-20039473February 2020
Figure 4-4: Output high and low voltages
A. Output voltage (V)
B. Load resistance (ohm)
C. High voltage ≈ (Vsupply ﹣1.8V) * RL / (1200 + RL)
D. Low voltage ≈ 0.0008*RL
Minimum resistance = 100Ω
Maximum resistance = 9.6kΩ
4.6Access the wiring channels
Procedure
1. Remove the wiring access cover to reveal the I/O wiring terminal block connectors.
2. Confirm which transmitter channels are activated, or ON, and identify the type of
configuration you will be wiring to based on the options available.
Installation Manual27
Wiring the channelsInstallation Manual
February 2020MMI-20039473
Figure 4-5: Activated channel identification
3. (Recommended) Record the channel and wiring configuration on the label provided
inside the transmitter housing cover.
Figure 4-6: Channel and wiring configurations label
Related information
Available channels
4.7Wire the Channel A mA/HART Output
Wire the mA/HART Output in explosion-proof, intrinsically safe, or nonhazardous
installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel
using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
28Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualWiring the channels
MMI-20039473February 2020
Figure 4-7: Channel A mA/HART output wiring
A. Hazardous area
B. Non-hazardous area
C. mA/HART output
D. 250–600 Ω resistance
E. 24V nominal
F. HART device
4.8Wire the Channel B and C mA Output
Wire the mA Output in explosion-proof, intrinsically safe, or nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel
using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Installation Manual29
Wiring the channelsInstallation Manual
February 2020MMI-20039473
Figure 4-8: Channel B and C mA Output wiring
A. Hazardous area
B. Non-hazardous area
C. mA Output
D. 250–600 Ω resistance
E. 24V nominal
F. Input device
4.9Wire the mA/SIL output
Refer to the Coriolis Flowmeter with Micro Motion Model 5700 Transmitters Safety Manual for
Safety Instrumented Systems (SIS) for additional information regarding installation and
commissioning that complies with SIS requirements.
4.10Wire the mA/HART multidrop installation
Wire the mA/HART multidrop output in explosion-proof, intrinsically safe, or
nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel
using the appropriate government and corporate safety standards.
Procedure
See the following figure for information on wiring an mA/HART multidrop installation.
30Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualWiring the channels
MMI-20039473February 2020
Figure 4-9: mA/HART multidrop wiring
A. Input Device 1
B. Input Device 2
C. Input Device 3
D. Meter (mA+/HART output)
E. Hazardous area
F. Non-hazardous area
G. DIN rail
H. 250 Ω resistance
I. 24VDC
J. HART/Field Communicator
4.11Wire the Frequency Output or the Discrete
Output
Use this procedure to wire Channel C or D as the Frequency Output or the Discrete Output.
Wire the FO or DO in explosion-proof, intrinsically safe, or nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel
using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Installation Manual31
Wiring the channelsInstallation Manual
February 2020MMI-20039473
Figure 4-10: Frequency Output or Discrete Output wiring
A. Hazardous area
B. Non-hazardous area
C. Frequency Output
D. 250–600 Ω resistance
E. 24V nominal
F. Input device
32Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualWiring the power supply
MMI-20039473February 2020
5Wiring the power supply
You can install a user-supplied switch in the power supply line.
Important
For compliance with the Low Voltage Directive 2014/35/EU (European installations), a
switch in close proximity to the transmitter is required.
Procedure
1. Remove the wiring access cover.
2. Open the Power warning flap to locate the power terminals.
Figure 5-1: Location of power supply wiring terminals and equipment ground
A. Power supply wiring terminals (+ and -)
B. Equipment ground
3. Connect the power supply wires:
• For DC power: connect to terminals + and –.
• For AC power: connect to terminals L/L1 (line) and N/L2 (neutral).
4. Tighten the two screws holding the power connector in place.
5. Ground the power supply using the equipment ground, also under the Power
warning flap.
Installation Manual33
Wiring the power supplyInstallation Manual
February 2020MMI-20039473
34Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualPower up the transmitter
MMI-20039473February 2020
6Power up the transmitter
The transmitter must be powered up for all configuration and commissioning tasks, or for
process measurement.
Procedure
1.WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while
the transmitter is powered up. Failure to follow these instructions can cause an
explosion resulting in injury or death.
Ensure that all transmitter and sensor covers and seals are closed.
2. Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. The transmitter is
self-switching and will automatically detect the supply voltage. When using DC
power, a minimum of 1.5 amps of startup current is required. During this period,
Alert 009 is active. The diagnostic routines should complete in approximately
30 seconds. The status LED will turn green and begin to flash when the startup
diagnostics are complete. If the status LED exhibits different behavior, an alert is
active.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the
electronics can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the
initial startup, or if power has been off long enough to allow components to reach ambient
temperature, allow the electronics to warm up for approximately 10 minutes before
relying on process measurements. During this warm-up period, you may observe minor
measurement instability or inaccuracy.
Installation Manual35
Power up the transmitterInstallation Manual
February 2020MMI-20039473
36Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualConfiguring the transmitter with Guided Setup
MMI-20039473February 2020
7Configuring the transmitter with
Guided Setup
At initial startup of the transmitter, the guided configuration screen appears on the
transmitter display. This tool guides you through basic configuration of the transmitter.
The guided setup allows you to upload configuration files, set the transmitter display
options, configure channels, and review sensor calibration data.
Procedure
To access the guided setup screen from the display main menu, go to: Startup Tasks →
Guided Setup.
Installation Manual37
Configuring the transmitter with Guided SetupInstallation Manual
February 2020MMI-20039473
38Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualUsing the display controls
MMI-20039473February 2020
8Using the display controls
The transmitter display interface includes a display (LCD panel) and four optical switches –
left, up, down, and right arrow keys – used to access the display menus and navigate the
display screens.
Procedure
1. To activate an optical switch, block the light by holding your thumb or finger in
front of the opening.
You can activate the optical switch through the lens. Do not remove the transmitter
housing cover.
Important
The transmitter only detects one switch selection at a time. Be sure to place your
thumb or finger directly over a single optical switch, and ensure no other switches
are being obstructed.
Figure 8-1: Proper finger positioning for activating an optical switch
2. Use the arrow indicators on the display screen to identify which optical switch to
use to navigate the screen (see examples 1 and 2).
Important
When using the arrow keys, you must first activate the optical switch then release
the same switch by removing your finger from the glass to move up, down, right,
left or to make a selection. To enable auto-scroll when navigating up or down,
activate the appropriate switch and continue to hold for one second. Release the
switch when the desired selection is highlighted.
Installation Manual39
Using the display controlsInstallation Manual
February 2020MMI-20039473
Figure 8-2: Example 1: Active arrow indicators on the transmitter display
Figure 8-3: Example 2: Active arrow indicators on the transmitter display
40Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation ManualAvailable service port connection
MMI-20039473February 2020
9Available service port connection
Use the service port connection to download or upload data from/to the transmitter.
To access the service port, you can use commonly-available USB hardware, such as a USB
drive, or USB cable.
WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the
transmitter is powered up. Failure to follow these instructions can cause an explosion
resulting in injury or death.
The service port connection is located under the Service Port warning flap at the wiring
access points.
Installation Manual41
Available service port connectionInstallation Manual
February 2020MMI-20039473
42Micro Motion 5700 transmitters with Intrinsically Safe Outputs
F3
C A
IEC 127-2
J3
DISC
OUT 3
T5A 250V
C A
F1
C A
IEC 127-2
J1
J4
MODEL 3300/350 0
TERMINAL
CONNECTION
DS1
T5A 250V
K3K2K1
ABC
'
(
)
DISC
OUT 2
IEC 127-2
F2 T5A 250V
J2
DS2
DISC
OUT 1
DS3
1 2 3 4 5 6 7 8 9 10
A14
C18
C16
C14
Installation Manual5700 to 3100 transmitter connections
MMI-20039473February 2020
A5700 to 3100 transmitter
connections
Use this section as a reference when wiring a 5700 transmitter to a 3100 transmitter.
The following graphic sets Channel B, configured as DO1, to relay 1. If a different channel
is assigned to DO, wire any DO to any relay.
• Set up the transmitter channel configuration to DO before wiring.
• Use active high and internal power.
• Tie the three ground pins of the 5700 together and then land on A14 of the 3100. The
ground pins are even numbers: 4, 6, and 8.
Example (see the following figure): Use relay 1 (C) and 2 (B) with Channels B and C,
then connect terminal 2 and 4 together from 5700 and land on A14.
• Land each positive power terminal on C14, C16, and C18.
Example: Using the same example as above, land 1 (Channel B) on C14 for relay 1, and
3 (Channel C) on C16 for relay 2.
• Use wire size 24 AWG (0,25 mm2) to 16 AWG (1,5 mm2).
Figure A-1: 5700 to 3100 - screw-type or solder-tail connector
A. Relay 3, DO 3 pins 6 and 7, C18
B. Relay 2, DO 2 pins 5 and 6, C16
C. Relay 1, DO 1 pins 3 and 4, C14
D. Channel D
E. Channel C
F. Channel B
Installation Manual43
*MMI-20039473*
MMI-20039473
Rev. AD
2020
Micro Motion Inc. USA
Worldwide Headquarters
7070 Winchester Circle
Boulder, Colorado USA 80301
T +1 303-527-5200
T +1 800-522-6277
F +1 303-530-8459
www.emerson.com
Micro Motion Asia
Emerson Automation Solutions
1 Pandan Crescent
Singapore 128461
Republic of Singapore
T +65 6363-7766
F +65 6770-8003
The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE,
ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of their respective owners.
Micro Motion Europe
Emerson Automation Solutions
Neonstraat 1
6718 WX Ede
The Netherlands
T +31 (0) 318 495 555
T +31 (0) 70 413 6666
F +31 (0) 318 495 556
www.emerson.com/nl-nl
Micro Motion United Kingdom
Emerson Automation Solutions
Emerson Process Management Limited
Horsfield Way
Bredbury Industrial Estate
Stockport SK6 2SU U.K.
T +44 0870 240 1978
F +44 0800 966 181
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.