Micro Motion Model 5700 Transmitters with Intrinsically Safe Outputs Installation Manual

Installation Manual
MMI-20039473, Rev AD
Micro Motion™ 5700 Transmitters with Intrinsically Safe Outputs
All Installation Types (Integral, 4-Wire, and 9-Wire)
February 2020
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. and Ireland 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 704 136
Mexico +52 55 5809 5300 France +33 (0) 800 917
Argentina +54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy +39 8008 77334 China +86 21 2892 9000
Chile +56 2 2928 4800 Central & Eastern +41 (0) 41 7686
Peru +51 15190130 Russia/CIS +7 495 995 9559 South Korea +82 2 3438 4600
Europe and Middle East Asia Pacific
New Zealand 099 128 804
666
India 800 440 1468
901
Japan +81 3 5769 6803
111
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
2
Installation Manual Contents
MMI-20039473 February 2020

Contents

Chapter 1 Before you begin............................................................................................................ 5
1.1 About this document........................................................................................................................5
1.2 Hazard messages..............................................................................................................................5
1.3 Related documents.......................................................................................................................... 6
Chapter 2 Planning........................................................................................................................ 7
2.1 Installation checklist.........................................................................................................................7
2.2 Power requirements......................................................................................................................... 8
Chapter 3 Mounting and sensor wiring........................................................................................ 11
3.1 Mounting and sensor wiring for integral-mount transmitters......................................................... 11
3.2 Mounting transmitters................................................................................................................... 11
3.3 Wire a remote-mount transmitter to the sensor............................................................................. 15
3.4 Ground the meter components...................................................................................................... 17
3.5 Rotate the transmitter on the sensor (optional)..............................................................................19
3.6 Rotate the user interface on the transmitter (optional)...................................................................20
3.7 Rotate the sensor wiring junction box on a remote-mount transmitter (optional).......................... 21
Chapter 4 Wiring the channels..................................................................................................... 23
4.1 Installation types for the 5700 transmitter......................................................................................23
4.2 Available channels.......................................................................................................................... 23
4.3 Barriers verified by Micro Motion.................................................................................................... 24
4.4 mA power requirements ................................................................................................................24
4.5 FO and DO power requirements .....................................................................................................26
4.6 Access the wiring channels............................................................................................................. 27
4.7 Wire the Channel A mA/HART Output............................................................................................ 28
4.8 Wire the Channel B and C mA Output............................................................................................. 29
4.9 Wire the mA/SIL output..................................................................................................................30
4.10 Wire the mA/HART multidrop installation.................................................................................... 30
4.11 Wire the Frequency Output or the Discrete Output...................................................................... 31
Chapter 5 Wiring the power supply..............................................................................................33
Chapter 6 Power up the transmitter............................................................................................. 35
Chapter 7 Configuring the transmitter with Guided Setup............................................................ 37
Chapter 8 Using the display controls............................................................................................ 39
Chapter 9 Available service port connection................................................................................. 41
Appendix A 5700 to 3100 transmitter connections..........................................................................43
Installation Manual iii
Contents Installation Manual
February 2020 MMI-20039473
iv Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Before you begin
MMI-20039473 February 2020

1 Before you begin

1.1 About this document

This manual provides information on planning, mounting, wiring, and initial setup of the 5700 transmitter. For information on full configuration, maintenance, troubleshooting, or service of the transmitter, see the configuration and use manual.
The information in this document assumes that users understand basic transmitter and sensor installation, configuration, and maintenance concepts and procedures.

1.2 Hazard messages

This document uses the following criteria for hazard messages based on ANSI standards Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access to protect users' assets. This is true for all systems used within the facility.
Installation Manual 5
Before you begin Installation Manual
February 2020 MMI-20039473

1.3 Related documents

You can find all product documentation on the product documentation DVD shipped with the product or at www.emerson.com.
See any of the following documents for more information:
Micro Motion 5700 Product Data Sheet
Micro Motion 5700 Transmitters with Intrinsically Safe Outputs: Configuration and Use
Manual
Coriolis Flowmeter with Micro Motion Model 5700 Transmitters Safety Manual for Safety
Instrumented Systems (SIS)
Modbus Interface Tool
Sensor installation manual
6 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual
MMI-20039473 February 2020
Planning

2 Planning

2.1 Installation checklist

If possible, install the transmitter in a location that will prevent direct exposure to
sunlight. The environmental limits for the transmitter may be further restricted by hazardous area approvals.
If you plan to mount the transmitter in a hazardous area:
WARNING
Verify that the transmitter has the appropriate hazardous area approval. Each
transmitter has a hazardous area approval tag attached to the transmitter housing.
Ensure that any cable used between the transmitter and the sensor meets the
hazardous area requirements.
For ATEX/IECEx installations, strictly adhere to the safety instructions
documented in the ATEX/IECEx approvals documentation available on the product documentation DVD shipped with the product or at www.emerson.com.
Verify that you have the appropriate cable and required cable installation parts for your
installation. For wiring between the transmitter and sensor, verify the maximum cable length does not exceed 1,000 ft (305 m).
Ensure that you use a twisted-pair instrument cable for all output connections.
You can mount the transmitter in any orientation as long as the conduit openings or
transmitter display do not point upward. Installing the transmitter with the conduit openings or transmitter display facing
upward risks condensation moisture entering the transmitter housing, which could damage the transmitter.
Following are examples of possible orientations for the transmitter.
Preferred orientation
Alternate orientations
Mount the meter in a location and orientation that satisfies the following conditions:
Allows sufficient clearance to open the transmitter housing cover. Install with 8 in
(203 mm) to 10 in (254 mm) clearance at the wiring access points.
Provides clear access for installing cabling to the transmitter.
Provides clear access to all wiring terminals for troubleshooting.
Installation Manual 7
Planning Installation Manual
February 2020 MMI-20039473

2.2 Power requirements

Self-switching AC/DC input, automatically recognizes supply voltage:
85 to 240 VAC, 50/60 Hz, 6 watts typical, 11 watts maximum
18 to 100 VDC, 6 watts typical, 11 watts maximum
Note
For DC power:
Power requirements assume a single transmitter per cable.
At startup, the power source must provide a minimum of 1.5 amps of short-term
current per transmitter and not pull voltage below 18 VDC.
Length and conductor diameter of the power cable must be sized to provide 18 VDC
minimum at the power terminals, at a load current of 0.7 amps.
Cable sizing formula
M = 18V + (R x L x 0.5A)
M: minimum supply voltage
R: cable resistance
L: cable length (in Ω/ft)
Typical power cable resistance at 68 °F (20.0 °C)
Wire gauge
14 AWG 0.0050 Ω/ft
16 AWG 0.0080 Ω/ft
18 AWG 0.0128 Ω/ft
20 AWG 0.0204 Ω/ft
2.5 mm
1.5 mm
1.0 mm
0.75 mm
0.50 mm
2
2
2
2
2
Resistance
0.0136 Ω/m
0.0228 Ω/m
0.0340 Ω/m
0.0460 Ω/m
0.0680 Ω/m
8 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Planning
MMI-20039473 February 2020

2.2.1 Maximum cable lengths between sensor and transmitter

The maximum cable length between the sensor and transmitter that are separately installed is determined by cable type.
Cable type Wire gauge Maximum length
Micro Motion 4-wire remote mount
Micro Motion 9-wire remote mount
User-supplied 4-wire VDC 22 AWG (0.326 mm²) 300 ft (91 m)
Not applicable 1,000 ft (305 m) without
Ex-approval
500 ft (152 m) with IIC
rated sensors
1,000 ft (305 m) with IIB
rated sensors
Not applicable 60 ft (18 m)
VDC 20 AWG (0.518 mm²) 500 ft (152 m)
VDC 18 AWG (0.823 mm²) 1,000 ft (305 m)
RS-485 22 AWG (0.326 mm²) or larger
1,000 ft (305 m)
Installation Manual 9
Planning Installation Manual
February 2020 MMI-20039473
10 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Mounting and sensor wiring
MMI-20039473 February 2020

3 Mounting and sensor wiring

3.1 Mounting and sensor wiring for integral­mount transmitters
There are no separate mounting requirements for integral transmitters, and no need to connect wiring between the transmitter and the sensor.

3.2 Mounting transmitters

There are two options available for mounting transmitters:
Mount the transmitter to a wall or flat surface.
Mount the transmitter to an instrument pole.
3.2.1

Mounting the transmitter to a wall or flat surface

Prerequisites
Ensure that the surface is flat and rigid, does not vibrate, or move excessively.
Confirm that you have the necessary tools, and the mounting kit shipped with the
transmitter.
Procedure
1. Attach the mounting bracket to the transmitter and tighten the screws to 80 in lbf (9.04 N m) to 90 in lbf (10.17 N m).
Figure 3-1: Mounting bracket to an aluminum transmitter
Installation Manual 11
Mounting and sensor wiring Installation Manual
February 2020 MMI-20039473
Figure 3-2: Mounting bracket to a stainless steel transmitter
2. For wall-mount installations, secure the mounting bracket to the prepared surface.
Figure 3-3: Wall-mounting bracket and dimensions for an aluminum transmitter
A. 2.8 in (71 mm) B. 2.8 in (71 mm)
12 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Mounting and sensor wiring
MMI-20039473 February 2020
Figure 3-4: Wall-mounting bracket and dimensions for a stainless steel transmitter
A. 7.51 in (190.8 mm) B. 3.67 in (93.2 mm)
3. For aluminum transmitters, place and attach the transmitter-mounting bracket to the mounting bracket secured to the wall or instrument pole.
Figure 3-5: Attaching and securing an aluminum transmitter to the mounting bracket
Tip
To ensure the mounting bracket holes are aligned, insert all attachment bolts into place before tightening.
Installation Manual 13
Mounting and sensor wiring Installation Manual
February 2020 MMI-20039473

3.2.2 Mount the transmitter to a pole

Prerequisites
Ensure that the instrument pole extends at least 12 in (305 mm) from a rigid base and
is no more than 2 in (51 mm) in diameter.
Confirm that you have the necessary tools, and the instrument-pole mounting kit
shipped with the transmitter.
Procedure
For pole-mount installations, attach the U-bolt mounting piece to the instrument pole.
Figure 3-6: Pole-mounting bracket attachment for an aluminum transmitter
14 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Mounting and sensor wiring
MMI-20039473 February 2020
Figure 3-7: Pole-mounting bracket attachment for a stainless steel transmitter

3.3 Wire a remote-mount transmitter to the sensor

Use this procedure to wire a 4-wire or 9-wire remote-mount transmitter to the sensor.
Prerequisites
Prepare the 4-wire cable as described in the sensor documentation.
Prepare the 9-wire cable as described in the Micro Motion 9-Wire Flowmeter Cable
Preparation and Installation Guide.
Connect the cable to the sensor-mounted core processor or junction box as described
in the sensor documentation. You can access all product documentation on the documentation DVD shipped with the product or at www.emerson.com.
Installation Manual 15
Mounting and sensor wiring Installation Manual
February 2020 MMI-20039473
Procedure
1. Remove the transmitter-to-sensor wiring compartment cover to reveal the terminal connections.
Figure 3-8: Removal of the transmitter-to-sensor wiring compartment cover
2. Feed the sensor wiring cable into the transmitter wiring compartment.
Figure 3-9: Sensor wiring feedthrough
3. Connect the sensor wires to the appropriate terminals.
Important
Terminate the 4-wire cable drain wires only at the sensor/core processor end of the cable. See the sensor installation manual for more detail. Do not connect the 4-wire cable drain wires to the ground screw located inside the 5700 junction box.
See Figure 3-10 for 4-wire terminal connections.
See Figure 3-11 for 9-wire terminal connections.
16 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Mounting and sensor wiring
MMI-20039473 February 2020
Figure 3-10: 4-wire transmitter-to-sensor wiring connections
Figure 3-11: 9-wire transmitter-to-sensor wiring connections
Note
Connect the 4 drain wires in the 9-wire cable to the ground screw located inside the junction box.
4. Replace the transmitter-to-sensor wiring compartment cover and tighten the screws to 14 in lbf (1.58 N m) to 15 in lbf (1.69 N m).

3.4 Ground the meter components

In 4-wire or 9-wire remote installations, the transmitter and sensor are grounded separately.
Installation Manual 17
Mounting and sensor wiring Installation Manual
February 2020 MMI-20039473
Prerequisites
NOTICE
Improper grounding could cause inaccurate measurements or meter failure.
WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion causing death or serious injury.
Note
For hazardous area installations in Europe, refer to standard EN 60079-14 or national standards.
If national standards are not in effect, adhere to the following guidelines for grounding:
Use copper wire, 14 AWG (2.08 mm²) or larger wire size.
Keep all ground leads as short as possible, less than 1 Ω impedance.
Connect ground leads directly to earth, or follow plant standards.
Procedure
1. Ground the sensor according to the instructions in the sensor documentation.
2. Ground the transmitter according to applicable local standards, using the transmitter’s internal or external ground screw.
The earth ground terminal is located inside the power wiring compartment.
The external ground screw is located on the side of the transmitter located
below the transmitter tag.
18 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Mounting and sensor wiring
MMI-20039473 February 2020

3.5 Rotate the transmitter on the sensor (optional)

In integral installations, you can rotate the transmitter on the sensor up to 360º in 45º increments.
Procedure
1. Using a 4 mm hex key, loosen and remove the clamp securing the transmitter head in place.
Figure 3-12: Removal of the sensor clamp
2. Gently lift the transmitter straight up, and rotate the transmitter to the desired position.
You can rotate the transmitter to any of the eight positions, but a stop exists that will not allow a full 360° rotation.
Figure 3-13: Rotation of the transmitter head
3. Gently lower the transmitter onto the base, confirming that the transmitter is in a locked position.
Installation Manual 19
Mounting and sensor wiring Installation Manual
February 2020 MMI-20039473
4. Replace the clamp in its original position and tighten the cap screw. Torque to 28 in lbf (3.16 N m) to 30 in lbf (3.39 N m).
Figure 3-14: Re-attachment of the sensor clamp

3.6 Rotate the user interface on the transmitter (optional)

The user interface on the transmitter electronics module can be rotated 90°, 180°, or 270° from the original position.
Figure 3-15: Display components
A. Transmitter housing
B. Sub-bezel C. Display module D. Display screws
E. End-cap clamp
F. Cap screw
G. Display cover
20 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Mounting and sensor wiring
MMI-20039473 February 2020
Procedure
1. Shut off power to the unit.
WARNING
If the transmitter is in a hazardous area, wait five minutes after disconnecting the power. Failure to do so could result in an explosion causing death or injury.
2. Loosen and rotate the end cap clamp so that it does not interfere with the cover.
3. Turn the display cover counterclockwise to remove it from the main enclosure.
4. Carefully loosen the captive display screws while holding the display module in
place.
5. Carefully pull the display module out of the main enclosure.
6. Rotate the display module to the desired position.
7. Gently press the display module back onto the connector.
8. Tighten display screws.
9. Place the display cover onto the main enclosure.
10. Turn the display cover clockwise until it is fully seated.
11. Replace the end-cap clamp by tightening the cap screw.
12. Restore power to the transmitter.

3.7 Rotate the sensor wiring junction box on a remote-mount transmitter (optional)

In remote-mount installations, you can rotate the sensor wiring junction box on the transmitter plus or minus 180º.
Procedure
1. Using a 4 mm hex key, loosen and remove the clamp securing the sensor wiring junction box in place.
Figure 3-16: Removal of the clamp
2. Gently rotate the junction box to the desired position.
Installation Manual 21
Mounting and sensor wiring Installation Manual
February 2020 MMI-20039473
You can rotate the junction box plus or minus 180º to any position.
Figure 3-17: Rotation of the sensor wiring junction box
3. Gently set the junction box into its new position, confirming that the position is locked.
4. Replace the clamp in its original position and tighten the cap screw. Torque to 28 in lbf (3.16 N m) to 30 in lbf (3.39 N m).
Figure 3-18: Re-attachment of the clamp
22 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Wiring the channels
MMI-20039473 February 2020

4 Wiring the channels

4.1 Installation types for the 5700 transmitter

WARNING
If you are installing the transmitter in a hazardous area, refer to Micro Motion approval instructions shipped with the product or available from the Emerson website. Improper installation in a hazardous area can cause an explosion resulting in injury or death.
A. Hazardous area
B. Safe area C. 2-wire signal cable D. Barrier
E. 4-20 mA, FO, or DO
F. Signal input device G. HART variables H. DCS
I. Emerson AMS Trex communicator

4.2 Available channels

Signal Channel A Channel B Channel C Channel D
Wiring terminals
mA Outputs mA Output (1) (HART) mA Output (2) mA Output (3)
Frequency Outputs
Discrete Outputs
Ui 30 V 30 V 30 V 30 V
1 2 3 4 5 6 7 8
Frequency Output (1) Frequency Output (2)
Discrete Output (1) Discrete Output (2)
Ii 484 mA 484 mA 484 mA 484 mA
Installation Manual 23
Wiring the channels Installation Manual
February 2020 MMI-20039473
Signal Channel A Channel B Channel C Channel D
Pi 2.05 W 2.05 W 2.05 W 2.05 W
Ci 150 pF 150 pF 150 pF 150 pF
Li 0 μH 0 μH 0 μH 0 μH

4.3 Barriers verified by Micro Motion

The following table lists the barriers that Micro Motion has verified with the 5700 transmitter. For other barriers, refer to the manufacturer's data sheet.
Table 4-1: Barriers verified by Micro Motion
Vendor Barrier
Micro Motion 505
Pepperl & Fuchs KFD2-STC1-EX1
Pepperl & Fuchs KFD2-STC4-EX1
MTL 787S+
MTL 7707P+
MTL 7787+
MTL 5042
MTL 3046B
MTL 7728P+
MTL 4541
STAHL 9002/13-280-110-00
PR Electronics 5106

4.4 mA power requirements

The supply voltage required by the 5700 transmitter depends on the total resistance in the mA loop. This includes all sensor resistance and wire resistance.
Channel A mA HART terminal requirements
Use the following chart to determine the required supply voltage for Channel A based on loop resistance.
24 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Wiring the channels
MMI-20039473 February 2020
Figure 4-1: Channel A mA/HART supply voltage and loop resistance
A. Total loop resistance R
(including barrier)
max
B. Supply voltage VDC (volts) C. Operating region with HART D. Operating region without HART (includes the C range)
Channel B or C terminal requirements
Use the following chart to determine the required supply voltage for Channel B or C based on loop resistance.
Figure 4-2: Channel B and C mA output supply voltage and loop resistance
A. Total loop resistance R
B. R
load
(including barrier)
max
C. Supply voltage VDC (volts) D. Operating region
Note
Rmax = (Vsupply - 8) / 0.024 mA Output is linear with process from 3.8 to 20.5 mA, per NAMUR NE-43 (February 2003).
Installation Manual 25
Wiring the channels Installation Manual
February 2020 MMI-20039473

4.5 FO and DO power requirements

The supply voltage required by the 5700 transmitter depends on the total resistance in the mA loop. This includes all sensor resistance and wire resistance.
Channel C or D terminal requirements
Use the following chart to determine the required supply voltage for Channel C or D based on loop resistance.
Figure 4-3: Channel C or D DO/FO supply voltage and loop resistance
Blue line = Maximum Red line = Minimum
A. External resistor R
B. Supply voltage VDC (volts) C. Operating region
Note
Rmax = (Vsupply - 6) / 0.0025 Rmin = 100Ω
load
26 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Wiring the channels
MMI-20039473 February 2020
Figure 4-4: Output high and low voltages
A. Output voltage (V)
B. Load resistance (ohm) C. High voltage ≈ (Vsupply ﹣1.8V) * RL / (1200 + RL) D. Low voltage ≈ 0.0008*RL
Minimum resistance = 100Ω Maximum resistance = 9.6kΩ

4.6 Access the wiring channels

Procedure
1. Remove the wiring access cover to reveal the I/O wiring terminal block connectors.
2. Confirm which transmitter channels are activated, or ON, and identify the type of
configuration you will be wiring to based on the options available.
Installation Manual 27
Wiring the channels Installation Manual
February 2020 MMI-20039473
Figure 4-5: Activated channel identification
3. (Recommended) Record the channel and wiring configuration on the label provided
inside the transmitter housing cover.
Figure 4-6: Channel and wiring configurations label
Related information
Available channels

4.7 Wire the Channel A mA/HART Output

Wire the mA/HART Output in explosion-proof, intrinsically safe, or nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
28 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Wiring the channels
MMI-20039473 February 2020
Figure 4-7: Channel A mA/HART output wiring
A. Hazardous area
B. Non-hazardous area C. mA/HART output D. 250–600 Ω resistance
E. 24V nominal
F. HART device

4.8 Wire the Channel B and C mA Output

Wire the mA Output in explosion-proof, intrinsically safe, or nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Installation Manual 29
Wiring the channels Installation Manual
February 2020 MMI-20039473
Figure 4-8: Channel B and C mA Output wiring
A. Hazardous area
B. Non-hazardous area C. mA Output D. 250–600 Ω resistance
E. 24V nominal
F. Input device

4.9 Wire the mA/SIL output

Refer to the Coriolis Flowmeter with Micro Motion Model 5700 Transmitters Safety Manual for Safety Instrumented Systems (SIS) for additional information regarding installation and
commissioning that complies with SIS requirements.

4.10 Wire the mA/HART multidrop installation

Wire the mA/HART multidrop output in explosion-proof, intrinsically safe, or nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate government and corporate safety standards.
Procedure
See the following figure for information on wiring an mA/HART multidrop installation.
30 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Wiring the channels
MMI-20039473 February 2020
Figure 4-9: mA/HART multidrop wiring
A. Input Device 1
B. Input Device 2 C. Input Device 3 D. Meter (mA+/HART output)
E. Hazardous area
F. Non-hazardous area G. DIN rail H. 250 Ω resistance
I. 24VDC J. HART/Field Communicator

4.11 Wire the Frequency Output or the Discrete Output

Use this procedure to wire Channel C or D as the Frequency Output or the Discrete Output. Wire the FO or DO in explosion-proof, intrinsically safe, or nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Installation Manual 31
Wiring the channels Installation Manual
February 2020 MMI-20039473
Figure 4-10: Frequency Output or Discrete Output wiring
A. Hazardous area
B. Non-hazardous area C. Frequency Output D. 250–600 Ω resistance
E. 24V nominal
F. Input device
32 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Wiring the power supply
MMI-20039473 February 2020

5 Wiring the power supply

You can install a user-supplied switch in the power supply line.
Important
For compliance with the Low Voltage Directive 2014/35/EU (European installations), a switch in close proximity to the transmitter is required.
Procedure
1. Remove the wiring access cover.
2. Open the Power warning flap to locate the power terminals.
Figure 5-1: Location of power supply wiring terminals and equipment ground
A. Power supply wiring terminals (+ and -) B. Equipment ground
3. Connect the power supply wires:
For DC power: connect to terminals + and –.
For AC power: connect to terminals L/L1 (line) and N/L2 (neutral).
4. Tighten the two screws holding the power connector in place.
5. Ground the power supply using the equipment ground, also under the Power
warning flap.
Installation Manual 33
Wiring the power supply Installation Manual
February 2020 MMI-20039473
34 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Power up the transmitter
MMI-20039473 February 2020

6 Power up the transmitter

The transmitter must be powered up for all configuration and commissioning tasks, or for process measurement.
Procedure
1. WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is powered up. Failure to follow these instructions can cause an explosion resulting in injury or death.
Ensure that all transmitter and sensor covers and seals are closed.
2. Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. The transmitter is self-switching and will automatically detect the supply voltage. When using DC power, a minimum of 1.5 amps of startup current is required. During this period, Alert 009 is active. The diagnostic routines should complete in approximately 30 seconds. The status LED will turn green and begin to flash when the startup diagnostics are complete. If the status LED exhibits different behavior, an alert is active.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the initial startup, or if power has been off long enough to allow components to reach ambient temperature, allow the electronics to warm up for approximately 10 minutes before relying on process measurements. During this warm-up period, you may observe minor measurement instability or inaccuracy.
Installation Manual 35
Power up the transmitter Installation Manual
February 2020 MMI-20039473
36 Micro Motion 5700 transmitters with Intrinsically Safe Outputs

Installation Manual Configuring the transmitter with Guided Setup

MMI-20039473 February 2020
7 Configuring the transmitter with
Guided Setup
At initial startup of the transmitter, the guided configuration screen appears on the transmitter display. This tool guides you through basic configuration of the transmitter. The guided setup allows you to upload configuration files, set the transmitter display options, configure channels, and review sensor calibration data.
Procedure
To access the guided setup screen from the display main menu, go to: Startup Tasks Guided Setup.
Installation Manual 37
Configuring the transmitter with Guided Setup Installation Manual
February 2020 MMI-20039473
38 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Using the display controls
MMI-20039473 February 2020

8 Using the display controls

The transmitter display interface includes a display (LCD panel) and four optical switches – left, up, down, and right arrow keys – used to access the display menus and navigate the display screens.
Procedure
1. To activate an optical switch, block the light by holding your thumb or finger in
front of the opening. You can activate the optical switch through the lens. Do not remove the transmitter
housing cover.
Important
The transmitter only detects one switch selection at a time. Be sure to place your thumb or finger directly over a single optical switch, and ensure no other switches are being obstructed.
Figure 8-1: Proper finger positioning for activating an optical switch
2. Use the arrow indicators on the display screen to identify which optical switch to
use to navigate the screen (see examples 1 and 2).
Important
When using the arrow keys, you must first activate the optical switch then release the same switch by removing your finger from the glass to move up, down, right, left or to make a selection. To enable auto-scroll when navigating up or down, activate the appropriate switch and continue to hold for one second. Release the switch when the desired selection is highlighted.
Installation Manual 39
Using the display controls Installation Manual
February 2020 MMI-20039473
Figure 8-2: Example 1: Active arrow indicators on the transmitter display
Figure 8-3: Example 2: Active arrow indicators on the transmitter display
40 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
Installation Manual Available service port connection
MMI-20039473 February 2020

9 Available service port connection

Use the service port connection to download or upload data from/to the transmitter.
To access the service port, you can use commonly-available USB hardware, such as a USB drive, or USB cable.
WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is powered up. Failure to follow these instructions can cause an explosion resulting in injury or death.
The service port connection is located under the Service Port warning flap at the wiring access points.
Installation Manual 41
Available service port connection Installation Manual
February 2020 MMI-20039473
42 Micro Motion 5700 transmitters with Intrinsically Safe Outputs
F3
C A
IEC 127-2
J3
DISC
OUT 3
T5A 250V
C A
F1
C A
IEC 127-2
J1
J4
MODEL 3300/350 0 TERMINAL CONNECTION
DS1
T5A 250V
K3 K2 K1
A B C
'
(
)
DISC
OUT 2
IEC 127-2
F2 T5A 250V
J2
DS2
DISC
OUT 1
DS3
1 2 3 4 5 6 7 8 9 10
A14
C18
C16
C14
Installation Manual 5700 to 3100 transmitter connections
MMI-20039473 February 2020
A 5700 to 3100 transmitter
connections
Use this section as a reference when wiring a 5700 transmitter to a 3100 transmitter.
The following graphic sets Channel B, configured as DO1, to relay 1. If a different channel is assigned to DO, wire any DO to any relay.
Set up the transmitter channel configuration to DO before wiring.
Use active high and internal power.
Tie the three ground pins of the 5700 together and then land on A14 of the 3100. The
ground pins are even numbers: 4, 6, and 8. Example (see the following figure): Use relay 1 (C) and 2 (B) with Channels B and C,
then connect terminal 2 and 4 together from 5700 and land on A14.
Land each positive power terminal on C14, C16, and C18.
Example: Using the same example as above, land 1 (Channel B) on C14 for relay 1, and 3 (Channel C) on C16 for relay 2.
Use wire size 24 AWG (0,25 mm2) to 16 AWG (1,5 mm2).
Figure A-1: 5700 to 3100 - screw-type or solder-tail connector
A. Relay 3, DO 3 pins 6 and 7, C18
B. Relay 2, DO 2 pins 5 and 6, C16 C. Relay 1, DO 1 pins 3 and 4, C14 D. Channel D
E. Channel C
F. Channel B
Installation Manual 43
*MMI-20039473*
MMI-20039473
Rev. AD
2020
Micro Motion Inc. USA
Worldwide Headquarters 7070 Winchester Circle Boulder, Colorado USA 80301 T +1 303-527-5200 T +1 800-522-6277 F +1 303-530-8459
www.emerson.com
Micro Motion Asia
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 Republic of Singapore T +65 6363-7766 F +65 6770-8003
©
2020 Micro Motion, Inc. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Automation Solutions family of companies. All other marks are property of their respective owners.
Micro Motion Europe
Emerson Automation Solutions Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495 555 T +31 (0) 70 413 6666 F +31 (0) 318 495 556
www.emerson.com/nl-nl
Micro Motion United Kingdom
Emerson Automation Solutions Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U.K. T +44 0870 240 1978 F +44 0800 966 181
Loading...