Micro Motion™ Model 1700 Transmitters with
Analog Outputs
Configuration and Use Manual
Safety messages
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are
available: the EU Declaration of Conformity, with all applicable European directives, and the complete ATEX installation drawings
and instructions. In addition, the IECEx installation instructions for installations outside of the European Union and the CSA
installation instructions for installations in North America are available at Emerson.com or through your local Micro Motion
support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found at Emerson.com. For
hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Troubleshooting information can be found in the Configuration Manual. Product data sheets and manuals are available from the
Micro Motion web site at Emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at Emerson.com, or by calling the Micro Motion Customer
Service department.
2
Configuration and Use ManualContents
MMI-20019028June 2022
Contents
Chapter 1Before you begin........................................................................................................7
1.1 About this manual....................................................................................................................... 7
1.2 Transmitter model code.............................................................................................................. 7
1.3 Communications tools and protocols.......................................................................................... 7
1.4 Related documentation............................................................................................................... 8
F.1 NE 53 history............................................................................................................................213
Configuration and Use Manual5
ContentsConfiguration and Use Manual
June 2022MMI-20019028
6Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualBefore you begin
MMI-20019028June 2022
1 Before you begin
1.1 About this manual
This manual helps you configure, commission, use, maintain, and troubleshoot Micro Motion 1700
transmitters with analog outputs.
Important
This manual assumes that:
• The transmitter has been installed correctly and completely according to the instructions in the
transmitter installation manual.
• Users understand basic transmitter and sensor installation, configuration, and maintenance concepts and
procedures.
1.2 Transmitter model code
You can verify that this manual pertains to your transmitter by ensuring the model code on the transmitter
tag matches the format.
Example:
The transmitter has a model number of the following form: 1700(R/I/E/B/C/M/P)**A******
R
4-wire remote-mount with aluminum housing
I
Integral mount
E
4-wire remote mount transmitter with 9-wire remote enhanced core processor
B
4-wire remote mount transmitter with 9-wire remote core processor
C
9-wire remote-mount with integral core processor and aluminum housing
M
4-wire remote mount with stainless steel housing
P
9-wire remote mount transmitter with integral core processor and stainless steel housing
A
Analog outputs option board
1.3 Communications tools and protocols
You can use several different communications tools and protocols to interface with the transmitter, use
different tools in different locations, or use different tools for different tasks.
Tool
Supported protocols
ProLink III• HART®/RS-485
• HART®/Bell 202
• Modbus®/RS-485
• Service port
Configuration and Use Manual7
Before you beginConfiguration and Use Manual
June 2022MMI-20019028
ToolSupported protocols
Field CommunicatorHART/Bell 202
For information about how to use the communication tools, see the appendices in this manual.
Tip
You may be able to use other communications tools, such as AMS™ Suite: Intelligent Device Manager, or the
Smart Wireless THUM™ Adapter. Use of AMS or the Smart Wireless THUM Adapter is not discussed in this
manual. For more information on the Smart Wireless THUM Adapter, refer to the documentation available at
Emerson.com.
1.4 Related documentation
You can find all product documentation on the product documentation DVD shipped with the product or at
Emerson.com.
See any of the following documents for more information:
• Micro Motion Series 1000 and Series 2000 Transmitters with MVD Technology Product Data Sheet
• Micro Motion 1700 and 2700 Installation Manual
• Micro Motion Enhanced Density Application Manual
• Modbus Interface Tool
• Sensor installation manual
8Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualQuick start
MMI-20019028June 2022
2 Quick start
2.1 Power up the transmitter
The transmitter must be powered up for all configuration and commissioning tasks or for process
measurement.
Procedure
1.WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is
powered up. Failure to follow these instructions can cause an explosion resulting in injury or death.
Ensure that all transmitter and sensor covers and seals are closed.
2. Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. The transmitter is self-switching and
will automatically detect the supply voltage. When using DC power, a minimum of 1.5 amps of startup
current is required. During this period, Alert 009 is active. The diagnostic routines should complete in
approximately 30 seconds. The status LED will turn green and begin to flash when the startup
diagnostics are complete. If the status LED exhibits different behavior, an alert is active.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics can take up to
ten minutes to reach thermal equilibrium. Therefore, if this is the initial startup, or if power has been off long
enough to allow components to reach ambient temperature, allow the electronics to warm up for
approximately ten minutes before relying on process measurements. During this warm-up period, you may
observe minor measurement instability or inaccuracy.
2.2 Check meter status
Check the meter for any error conditions that require user action or that affect measurement accuracy.
Procedure
1. Wait approximately 10 seconds for the power-up sequence to complete.
Immediately after power-up, the transmitter runs through diagnostic routines and checks for error
conditions. During the power-up sequence, Alert A009 is active. This alert should clear automatically
when the power-up sequence is complete.
2. Check the status LED on the transmitter.
Related information
View and acknowledge status alerts
Status alerts, causes, and recommendations
Configuration and Use Manual9
Quick startConfiguration and Use Manual
June 2022MMI-20019028
2.2.1 Transmitter status reported by LED
LED stateDescriptionRecommendation
Solid greenNo alerts are active.Continue with configuration or process
measurement.
Flashing green (if
enabled)
Solid yellowOne or more low-severity alerts are active.
Flashing yellow (if
enabled)
Solid redOne or more high-severity alerts are active.A high-severity alert condition affects
Flashing red (if
enabled)
Unacknowledged corrected condition (no
alert)
A low severity alarm can mean one or more
process variables is at a set output level (i.e.
simulation or two phase timeout).
Calibration in progress, or Known Density
Verification in progress.
One or more low-severity alerts are active and
have not been acknowledged.
One or more high-severity alerts are active
and have not been acknowledged.
Continue with configuration or process
measurement. Acknowledge the alert if you
choose.
A low-severity alert condition does not affect
measurement accuracy or output behavior.
You can continue with configuration or
process measurement, but Micro Motion still
recommends identifying and resolving the
alert condition.
A low-severity alert condition does not affect
measurement accuracy or output behavior.
You can continue with configuration or
process measurement, but Micro Motion still
recommends identifying and resolving the
alert condition.
measurement accuracy and output behavior.
Resolve the alert condition before continuing.
A high-severity alert condition affects
measurement accuracy and output behavior.
Resolve the alert condition before continuing.
Acknowledge the alert if you choose.
If Status LED Blinking is disabled, all LEDs will show a solid color rather than flashing.
2.3 Make a startup connection to the transmitter
For all configuration tools except the display, you must have an active connection to the transmitter to
configure the transmitter. Follow this procedure to make your first connection to the transmitter.
Procedure
Identify the connection type to use, and follow the instructions for that connection type in the appropriate
appendix. Use the default communications parameters shown in the appendix.
Communications tool
ProLink IIIHART/RS-485
Field CommunicatorHART/Bell 202Using a field communicator with the
10Micro Motion 1700 Transmitters with Analog Outputs
Connection type to useInstructions
Using ProLink III with the transmitter
Modbus/RS-485
Service port
transmitter
Configuration and Use ManualQuick start
MMI-20019028June 2022
2.4 (Optional) Adjust digital communications settings
Change the communications parameters to site-specific values.
Important
If you are changing communications parameters for the connection type that you are using, you will lose the
connection when you write the parameters to the transmitter. Reconnect using the new parameters.
Procedure
1. To change the communications parameters using ProLink III, choose Device Tools → Configuration →
Communications.
2. To change the communications parameters using the Field Communicator, choose On-Line Menu →
Configure → Manual Setup → Inputs/Outputs → Communications.
2.5 Verify mass flow measurement
Check to see that the mass flow rate reported by the transmitter is accurate. You can use any available
method.
Procedure
• Read the value for Mass Flow Rate on the transmitter display.
Menu → Operations → Process Variable Values
• Connect to the transmitter with ProLink III and read the value for Mass Flow Rate in the Process Variables
panel.
• Connect to the transmitter with a field communicator and read the value for Mass Flow Rate.
Online → Overview → Mass Flow Rate
Postrequisites
If the reported mass flow rate is not accurate:
• Check the characterization parameters.
• Review the troubleshooting suggestions for flow measurement issues.
For information about modifying these values, refer to Configure mass flow measurement.
2.6 Verify the zero
Verifying the zero helps you determine if the stored zero value is appropriate to your installation, or if a field
zero can improve measurement accuracy.
The zero verification procedure analyzes the Live Zero value under conditions of zero flow, and compares it to
the Zero Stability range for the sensor. If the average Live Zero value is within a reasonable range, the zero
value stored in the transmitter is valid. Performing a field calibration will not improve measurement accuracy.
Important
In most cases, the factory zero is more accurate than the field zero. Do not zero the meter unless one of the
following is true:
Configuration and Use Manual11
Quick startConfiguration and Use Manual
June 2022MMI-20019028
• The zero is required by site procedures.
• The stored zero value fails the zero verification procedure.
Do not verify the zero or zero the meter if a high-severity alert is active. Correct the problem, then verify the
zero or zero the meter. You may verify the zero or zero the meter if a low-severity alert is active.
Procedure
1. Allow the flowmeter to warm up for at least 20 minutes after applying power.
2. Run the process fluid through the sensor until the sensor temperature reaches the normal process
operating temperature.
3. Stop flow through the sensor by shutting the downstream valve, and then the upstream valve if
available.
4. Verify that the sensor is blocked in, that flow has stopped, and that the sensor is completely full of
process fluid.
5. From ProLink III, choose Device Tools→Calibration→Zero Verification and Calibration→Verify
Zero and wait until the procedure completes.
6. Observe the drive gain, temperature, and density readings. If they are stable, check the Live Zero or
Field Verification Zero value. If the average value is close to 0, you should not need to zero the meter.
7. If the zero verification procedure fails:
a) Confirm that the sensor is completely blocked in, that flow has stopped, and that the sensor is
completely full of process fluid.
b) Verify that the process fluid is not flashing or condensing, and that it does not contain particles
that can settle out.
c) Remove or reduce sources of electromechanical noise if appropriate.
d) Repeat the zero verification procedure.
e) If it fails again, zero the meter.
Postrequisites
Restore normal flow through the sensor by opening the valves.
Related information
Zero the meter
2.6.1 Terminology used with zero verification and zero calibration
Term
ZeroIn general, the offset required to synchronize the left pickoff and the right pickoff under
Factory ZeroThe zero value obtained at the factory, under laboratory conditions.
Field ZeroThe zero value obtained by performing a zero calibration outside the factory.
Prior ZeroThe zero value stored in the transmitter at the time a field zero calibration is begun. May
Definition
conditions of zero flow. Unit = microseconds.
be the factory zero or a previous field zero.
12Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualQuick start
MMI-20019028June 2022
TermDefinition
Manual ZeroThe zero value stored in the transmitter, typically obtained from a zero calibration
procedure. It may also be configured manually. Also called “mechanical zero” or “stored
zero”.
Live ZeroThe real-time bidirectional mass flow rate with no flow damping or mass flow cutoff
applied. An adaptive damping value is applied only when the mass flow rate changes
dramatically over a very short interval. Unit = configured mass flow measurement unit.
Zero StabilityA laboratory-derived value used to calculate the expected accuracy for a sensor. Under
laboratory conditions at zero flow, the average flow rate is expected to fall within the
range defined by the Zero Stability value (0 ± Zero Stability). Each sensor size and model
has a unique Zero Stability value.
Zero CalibrationThe procedure used to determine the zero value.
Zero TimeThe time period over which the Zero Calibration procedure is performed. Unit = seconds.
Field Verification ZeroA 3-minute running average of the Live Zero value, calculated by the transmitter. Unit =
configured mass flow measurement unit.
Zero VerificationA procedure used to evaluate the stored zero and determine whether or not a field zero
can improve measurement accuracy.
Configuration and Use Manual13
Quick startConfiguration and Use Manual
June 2022MMI-20019028
14Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualIntroduction to configuration and commissioning
MMI-20019028June 2022
3 Introduction to configuration and
commissioning
3.1 Configuration flowchart
Use the following flowchart as a general guide to the configuration and commissioning process.
Some options may not apply to your installation. Detailed information is provided in the remainder of this
manual. If you are using the Weights & Measures application, additional configuration and setup are required.
Configure process measurement
Configure mass flow
measurement
Configure volume flow
meaurement
Configure device options and
preferences
Configure display
parameters
Configure fault handling
parameters
Test and move to production
Test or tune transmitter
using sensor simulation
Back up transmitter
configuration
Volume flow type
Liquid
Configure flow direction
Configure density
measurement
Configure temperature
measurement
Configure pressure
compensation (optional)
Configure PVR, TMR,
or TBR (if available)
Gas
Define gas properties
Configure sensor
parameters
Configure device
parameters
Integrate device with control system
Configure the channel(s)
Configure the mA
output(s)
Configure the frequency
output(s)
Configure the discrete
output(s)
Configure events
Enable write-protection on
transmitter configuration
Done
Configure digital
communications
Configuration and Use Manual15
Introduction to configuration and commissioningConfiguration and Use Manual
June 2022MMI-20019028
3.2 Default values and ranges
See Default values and ranges to view the default values and ranges for the most commonly used parameters.
3.3 Enable access to the off-line menu of the display
Field CommunicatorConfigure→Manual Setup→Display→Offline Variable Menu Features
By default, access to the off-line menu of the display is enabled. If it is disabled, you must enable it if you want
to use the display to configure the transmitter.
Restriction
You cannot use the display to enable access to the off-line menu. You must make a connection from another
tool.
If the transmitter is write-protected, the configuration is locked and you must unlock it before you can change
any configuration parameters. By default, the transmitter is not write-protected.
Tip
Write-protecting the transmitter prevents accidental changes to configuration. It does not prevent normal
operational use. You can always disable write-protection, perform any required configuration changes, then
re-enable write-protection.
Field communicatorService Tools→Maintenance→Reset/Restore→Restore Factory Configuration
Restoring the factory configuration returns the transmitter to the same configuration it had when it left the
factory. This may be useful if you experience problems during configuration.
Not available
Important
You cannot restore factory configurations with a 700 core.
Tip
Restoring the factory configuration is not a common action. You may want to contact customer support to
see if there is a preferred method to resolve any issues.
16Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
4 Configure process measurement
4.1 Configure mass flow measurement
The mass flow measurement parameters control how mass flow is measured and reported.
Field CommunicatorConfigure→Manual Setup→Measurements→Flow→Mass Flow Unit
Mass Flow Measurement Unit specifies the unit of measure that will be used for the mass flow rate. The unit
used for mass total and mass inventory is derived from this unit.
Any selected measurement unit, (mass, volume or gas standard volume), is automatically applied to both the
mA and Frequency Outputs.
Procedure
Set Mass Flow Measurement Unit to the unit you want to use.
The default setting for Mass Flow Measurement Unit is g/sec (grams per second).
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Mass Flow Measurement Unit
The transmitter provides a standard set of measurement units for Mass Flow Measurement Unit, plus one
user-defined special measurement unit. Different communications tools may use different labels for the
units.
Label
Unit description
Grams per secondG/Sg/secg/s
Grams per minuteG/MINg/ming/min
Grams per hourG/Hg/hrg/h
Kilograms per secondKG/Skg/seckg/s
Kilograms per minuteKG/MINkg/minkg/min
Kilograms per hourKG/Hkg/hrkg/h
DisplayProLink IIIField Communicator
Kilograms per dayKG/Dkg/daykg/d
Metric tons per minuteT/MINmTon/minMetTon/min
Metric tons per hourT/HmTon/hrMetTon/h
Metric tons per dayT/DmTon/dayMetTon/d
Configuration and Use Manual17
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
Label
Unit description
Pounds per secondLB/Slbs/seclb/s
Pounds per minuteLB/MINlbs/minlb/min
Pounds per hourLB/Hlbs/hrlb/h
Pounds per dayLB/Dlbs/daylb/d
Short tons (2000 pounds) per minuteST/MINsTon/minSTon/min
Short tons (2000 pounds) per hourST/HsTon/hrSTon/h
Short tons (2000 pounds) per dayST/DsTon/daySTon/d
Long tons (2240 pounds) per hourLT/HlTon/hrLTon/h
Long tons (2240 pounds) per dayLT/DlTon/dayLTon/d
Special unitSPECLspecialSpcl
DisplayProLink IIIField Communicator
Define a special measurement unit for mass flow
DisplayNot available
ProLink IIIDevice Tools→Configuration→Process Measurement→Flow→Special Units
Field CommunicatorConfigure→Manual Setup→Measurements→Special Units→Mass Special Units
A special measurement unit is a user-defined unit of measure that allows you to report process data, totalizer
data, and inventory data in a unit that is not available in the transmitter. A special measurement unit is
calculated from an existing measurement unit using a conversion factor.
Note
Although you cannot define a special measurement unit using the display, you can use the display to select an
existing special measurement unit, and to view process data using the special measurement unit.
Procedure
1. Specify Base Mass Unit.
Base Mass Unit is the existing mass unit that the special unit will be based on.
2. Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
3. Calculate Mass Flow Conversion Factor as follows:
a) x base units = y special units
b) Mass Flow Conversion Factor = x ÷ y
The original mass flow rate value is divided by this value.
4. Enter Mass Flow Conversion Factor.
5. Set Mass Flow Label to the name you want to use for the mass flow unit.
6. Set Mass Total Label to the name you want to use for the mass total and mass inventory unit.
18Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
The special measurement unit is stored in the transmitter. You can configure the transmitter to use the
special measurement unit at any time.
Example: Defining a special measurement unit for mass flow
You want to measure mass flow in ounces per second (oz/sec).
Field CommunicatorConfigure→Manual Setup→Measurements→Flow→Flow Damping
Damping is used to smooth out small, rapid fluctuations in process measurement. Damping Value specifies
the time period (in seconds) over which the transmitter will spread changes in the process variable. At the end
of the interval, the internal value will reflect 63% of the change in the actual measured value.
Procedure
Set Flow Damping to the value you want to use.
The default value is 0.8 seconds. The range depends on the core processor type and the setting of UpdateRate, as shown in the following table.
Update Rate setting
Normal0 to 51.2 seconds
Special0 to 40.96 seconds
The value you enter is automatically rounded off to the nearest valid value. For example, if the damping is
currently set to 0.8 seconds, any value entered up to 1.2 seconds will be rounded down to 0.8 seconds, and
any value entered from 1.21 to 1.59 seconds will be rounded up to 1.6 seconds.
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
Effect of flow damping on volume measurement
Flow damping affects volume measurement for liquid volume data. Flow damping also affects volume
measurement for gas standard volume data. The transmitter calculates volume data from the damped mass
flow data.
Interaction between Flow Damping and mA Output Damping
In some circumstances, both Flow Damping and mA Output Damping are applied to the reported mass flow
value.
Flow Damping controls the rate of change in flow process variables. mA Output Damping controls the rate
of change reported through mA Output. If mA Output Process Variable is set to Mass Flow Rate, and both
Flow Damping and mA Output Damping are set to non-zero values, flow damping is applied first, and the
added damping calculation is applied to the result of the first calculation.
Field CommunicatorConfigure→Manual Setup→Measurements→Flow→Mass Flow Cutoff
Mass Flow Cutoff specifies the lowest mass flow rate that will be reported as measured. All mass flow rates
below this cutoff will be reported as 0.
Procedure
Set Mass Flow Cutoff to the value you want to use.
The default value for Mass Flow Cutoff is 0.0 g/sec or a sensor-specific value set at the factory. The
recommended value is 0.5% of the nominal flow rate of the attached sensor. See the sensor specifications. Do
not leave Mass Flow Cutoff at 0.0 g/sec.
Effect of Mass Flow Cutoff on volume measurement
Mass Flow Cutoff does not affect volume measurement. Volume data is calculated from the actual mass data
rather than the reported value.
Volume flow has a separate Volume Flow Cutoff that is not affected by the Mass Flow Cutoff value.
Interaction between Mass Flow Cutoff and mA Output Cutoff
Mass Flow Cutoff defines the lowest mass flow value that the transmitter will report as measured. mA
Output Cutoff defines the lowest flow rate that will be reported through mA Output. If mA Output Process
Variable is set to Mass Flow Rate, the mass flow rate reported through mA Output is controlled by the higher
of the two cutoff values.
Mass Flow Cutoff affects all reported values and values used in other transmitter behavior (e.g., events
defined on mass flow).
mA Output Cutoff affects only mass flow values reported through mA Output.
20Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
Example: Cutoff interaction with mA Output Cutoff lower than Mass Flow Cutoff
Configuration:
• mA Output Process Variable: Mass Flow Rate
• Frequency Output Process Variable: Mass Flow Rate
• mA Output Cutoff: 10 g/sec
• Mass Flow Cutoff: 15 g/sec
Result: If the mass flow rate drops below 15 g/sec, mass flow will be reported as 0, and 0 will be used in all
internal processing.
Example: Cutoff interaction with mA Output Cutoff higher than Mass Flow Cutoff
Configuration:
• mA Output Process Variable: Mass Flow Rate
• Frequency Output Process Variable: Mass Flow Rate
• mA Output Cutoff: 15 g/sec
• Mass Flow Cutoff: 10 g/sec
Result:
• If the mass flow rate drops below 15 g/sec but not below 10 g/sec:
— The mA Output will report zero flow.
— The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all
internal processing.
• If the mass flow rate drops below 10 g/sec, both outputs will report zero flow, and 0 will be used in all
internal processing.
4.2 Configure volume flow measurement for liquid
applications
The volume flow measurement parameters control how liquid volume flow is measured and reported.
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time. Choose one
or the other.
Note
If you need to switch from gas standard volume to liquid volume, polling for base density will automatically be
disabled.
4.2.1 Configure Volume Flow Type for liquid applications
Field CommunicatorConfigure→Manual Setup→Measurements→GSV→Volume Flow Type→Liquid
Configuration and Use Manual21
Not available
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
Volume Flow Type controls whether liquid or gas standard volume flow measurement will be used.
Restriction
Gas standard volume measurement is incompatible with some applications. Set Volume Flow Type to Liquid
if you are using any of the following applications:
• Production Volume Reconciliation (PVR)
Procedure
Set Volume Flow Type to Liquid.
4.2.2 Configure Volume Flow Measurement Unit for liquid
Field CommunicatorConfigure→Manual Setup→Measurements→Flow→Volume Flow Unit
Volume Flow Measurement Unit specifies the unit of measurement that will be displayed for the volume
flow rate. The unit used for the volume total and volume inventory is based on this unit.
Prerequisites
Before you configure Volume Flow Measurement Unit, be sure that Volume Flow Type is set to Liquid.
Procedure
Set Volume Flow Measurement Unit to the unit you want to use.
To read US gallons, select that unit from this menu. G/MIN stands for grams per minute (USGPM), not gallons
per minute. The default setting for Volume Flow Measurement Unit is l/sec (liters per second).
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Volume Flow Measurement Unit for liquid applications
The transmitter provides a standard set of measurement units for Volume Flow Measurement Unit, plus one
user-defined measurement unit. Different communications tools may use different labels for the units.
Label
Unit description
Cubic feet per secondCUFT/Sft3/secCuft/s
Cubic feet per minuteCUF/MNft3/minCuft/min
DisplayProLink IIIField Communicator
Cubic feet per hourCUFT/Hft3/hrCuft/h
Cubic feet per dayCUFT/Dft3/dayCuft/d
Cubic meters per secondM3/Sm3/secCum/s
Cubic meters per minuteM3/MINm3/minCum/min
22Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
Label
Unit description
DisplayProLink IIIField Communicator
Cubic meters per hourM3/Hm3/hrCum/h
Cubic meters per dayM3/Dm3/dayCum/d
U.S. gallons per secondUSGPSUS gal/secgal/s
U.S. gallons per minuteUSGPMUS gal/mingal/min
U.S. gallons per hourUSGPHUS gal/hrgal/h
U.S. gallons per dayUSGPDUS gal/daygal/d
Million U.S. gallons per dayMILG/Dmil US gal/dayMMgal/d
Liters per secondL/Sl/secL/s
Liters per minuteL/MINl/minL/min
Liters per hourL/Hl/hrL/h
Million liters per dayMILL/Dmil l/dayML/d
Imperial gallons per secondUKGPSImp gal/secImpgal/s
Imperial gallons per minuteUKGPMImp gal/minImpgal/min
Imperial gallons per hourUKGPHImp gal/hrImpgal/h
Imperial gallons per dayUKGPDImp gal/dayImpgal/d
(1)
(1)
(1)
(1)
(2)
(2)
(2)
(2)
BBL/Sbarrels/secbbl/s
BBL/MNbarrels/minbbl/min
BBL/Hbarrels/hrbbl/h
BBL/Dbarrels/daybbl/d
BBBL/SBeer barrels/secbbbl/s
BBBL/MNBeer barrels/minbbbl/min
BBBL/HBeer barrels/hrbbbl/h
BBBL/DBeer barrels/daybbbl/d
Barrels per second
Barrels per minute
Barrels per hour
Barrels per day
Beer barrels per second
Beer barrels per minute
Beer barrels per hour
Beer barrels per day
Special unitSPECLspecialSpcl
(1) Unit based on oil barrels (42 U.S. gallons).
(2) Unit based on U.S. beer barrels (31 U.S. gallons).
Define a special measurement unit for volume flow
Display
ProLink IIIDevice Tools→Configuration→Process Measurement→Flow→Special Units
Field CommunicatorConfigure→Manual Setup→Measurements→Special Units→Volume Special Units
Configuration and Use Manual23
Not available
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
A special measurement unit is a user-defined unit of measure that allows you to report process data, totalizer
data, and inventory data in a unit that is not available in the transmitter. A special measurement unit is
calculated from an existing measurement unit using a conversion factor.
Note
Although you cannot define a special measurement unit using the display, you can use the display to select an
existing special measurement unit, and to view process data using the special measurement unit.
Procedure
1. Specify Base Volume Unit.
Base Volume Unit is the existing volume unit that the special unit will be based on.
2. Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
3. Calculate Volume Flow Conversion Factor as follows:
a) x base units = y special units
b) Volume Flow Conversion Factor = x ÷ y
4. Enter Volume Flow Conversion Factor.
The original volume flow rate value is divided by this conversion factor.
5. Set Volume Flow Label to the name you want to use for the volume flow unit.
6. Set Volume Total Label to the name you want to use for the volume total and volume inventory unit.
The special measurement unit is stored in the transmitter. You can configure the transmitter to use the
special measurement unit at any time.
Defining a special measurement unit for volume flow
You want to measure volume flow in pints per second (pints/sec).
Field CommunicatorConfigure→Manual Setup→Measurements→Flow→Volume Flow Cutoff
24Micro Motion 1700 Transmitters with Analog Outputs
Not available
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
Volume Flow Cutoff specifies the lowest volume flow rate that will be reported as measured. All volume flow
rates below this cutoff are reported as 0.
Procedure
Set Volume Flow Cutoff to the value you want to use.
The default value for Volume Flow Cutoff is 0.0 l/sec (liters per second). The lower limit is 0. Leaving the
volume flow cutoff at 0 is not recommended.
Interaction between Volume Flow Cutoff and mAO Cutoff
Volume Flow Cutoff defines the lowest liquid volume flow value that the transmitter will report as measured.
mAO Cutoff defines the lowest flow rate that will be reported through mA Output. If mA Output Process
Variable is set to Volume Flow Rate, the volume flow rate reported through mA Output is controlled by the
higher of the two cutoff values.
Volume Flow Cutoff affects both the volume flow values reported via the outputs and the volume flow values
used in other transmitter behavior (e.g., events defined on the volume flow).
mAO Cutoff affects only flow values reported through mA Output.
Example: Cutoff interaction with mAO Cutoff lower than Volume Flow Cutoff
Configuration:
• mA Output Process Variable: Volume Flow Rate
• Frequency Output Process Variable: Volume Flow Rate
• AO Cutoff: 10 l/sec
• Volume Flow Cutoff: 15 l/sec
Result: If the volume flow rate drops below 15 l/sec, volume flow will be reported as 0, and 0 will be used in all
internal processing.
Example: Cutoff interaction with mAO Cutoff higher than Volume Flow Cutoff
Configuration:
• mA Output Process Variable: Volume Flow Rate
• Frequency Output Process Variable: Volume Flow Rate
• AO Cutoff: 15 l/sec
• Volume Flow Cutoff: 10 l/sec
Result:
• If the volume flow rate drops below 15 l/sec but not below 10 l/sec:
— The mA Output will report zero flow.
— The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all
internal processing.
• If the volume flow rate drops below 10 l/sec, both outputs will report zero flow, and 0 will be used in all
internal processing.
Configuration and Use Manual25
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
4.3 Configure GSV flow measurement
The gas standard volume (GSV) flow measurement parameters control how volume flow is measured and
reported in a gas application.
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time. Choose one
or the other.
4.3.1 Configure Volume Flow Type for gas applications
Field CommunicatorConfigure→Manual Setup→Measurements→GSV→Volume Flow Type→Standard Gas Volume
Volume Flow Type controls whether liquid or gas standard volume flow measurement is used.
Restriction
Gas standard volume measurement is incompatible with some applications. Set Volume Flow Type to Liquid
if you are using any of the following applications:
Field CommunicatorConfigure→Manual Setup→Measurements→GSV→Gas Ref Density
The Standard Density of Gas value is the gas density at standard reference conditions. Use it to convert the
measured mass flow data to volume flow at reference conditions.
Prerequisites
Ensure that Density Measurement Unit is set to the measurement unit you want to use for Standard Density
of Gas.
Procedure
From the Source field, choose the method to supply gas base density data and perform the required setup.
Option
Fixed Value or Digital
Communications
Not available
Description
A host writes gas base density data to the meter at appropriate intervals.
Continue to Configure fixed value or digital communications.
26Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
OptionDescription
Poll for external valueThe meter polls an external HART® device for gas base density data in order
to then compute gas standard volume from the mass flow and gas base
density.
Continue to Poll for external value.
Configure fixed value or digital communications
Prerequisites
Configure Standard Density of Gas
Procedure
1. Set Standard Density of Gas to the standard reference density of the gas you are measuring.
Note
ProLink III provides a guided method that you can use to calculate your gas base density, if you do not
know it.
2. Continue to Configure Gas Standard Volume Flow Unit .
Poll for external value
Prerequisites
Configure Standard Density of Gas
Procedure
1. Set Polling Slot to an available slot.
2. Set Polling Control n as one of the following options:
The n is the value you selected in the Polling Slot field.
If there is another master, and if that master is primary, then set this field to secondary. If the other
master is secondary, then set this field to primary.
Option
Poll as PrimaryNo other HART® masters will be on the network.
Poll as SecondaryOther HART® masters will be on the network.
3. Set External Device Tag n to the HART tag of the device being polled.
The n is the value you selected in the Polling Slot field.
Description
• The device being polled (slave) cannot have special units set for density. Otherwise, the master will
reject the base density and report the following alarm:
A115: No External Input or Polled Data Alert
• On the slave side, setup the HART Primary Variable for Base Density. The master will reject anything
other than Base Density for the HART Primary Variable and trigger an A115 alarm.
Configuration and Use Manual27
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
• The density units on the transmitter and the polled device can be different as long as they can be
classified as density units; for example, kg/m3 and g/cm3. The transmitter converts the polled units
into compatible specified units.
For wiring and setup instructions for a polled device, refer to the Micro Motion Gas Density Meters (GDM)Installation Manual or the Micro Motion Specific Gravity Meters (SGM) Installation Manual.
4. Continue to Configure Gas Standard Volume Flow Unit .
Field CommunicatorConfigure→Manual Setup→Measurements→GSV→GSV Flow Unit
Gas Standard Volume Flow Unit specifies the unit of measure that will be displayed for the gas standard
volume flow. The measurement unit used for the gas volume total and the gas volume inventory is derived
from this unit.
Prerequisites
Before you configure Gas Standard Volume Flow Unit, be sure that Volume Flow Type is set to Gas Standard
Volume.
For polling, the first transmitter (master) requests density from a second transmitter (slave) via HART
®
communications. Special units for GSV are allowed on the master side, but the device being polled (slave)
cannot have special units set for density, otherwise the master will reject the base density and report an A115:
No External Input or Polled Data Alert.
Procedure
Set Gas Standard Volume Flow Unit to the unit you want to use.
The default setting for Gas Standard Volume Flow Unit is SCFM (Standard Cubic Feet per Minute).
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Gas Standard Volume Flow Unit
The transmitter provides a standard set of measurement units for Gas Standard Volume Flow Unit, plus one
user-defined special measurement unit. Different communications tools may use different labels for the
units.
Label
Unit description
DisplayProLink IIIField Communicator
Normal cubic meters per secondNM3/SNm3/secNm3/sec
Normal cubic meters per minuteNM3/MNNm3/secNm3/min
Normal cubic meters per hourNM3/HNm3/hrNm3/hr
Normal cubic meters per dayNM3/DNm3/dayNm3/day
Normal liters per secondNLPSNLPSNLPS
28Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
Label
Unit description
Normal liters per minuteNLPMNLPMNLPM
Normal liters per hourNLPHNLPHNLPH
Normal liters per dayNLPDNLPDNLPD
Standard cubic feet per secondSCFSSCFSSCFS
Standard cubic feet per minuteSCFMSCFMSCFM
Standard cubic feet per hourSCFHSCFHSCFH
Standard cubic feet per daySCFDSCFDSCFD
Standard cubic meters per secondSM3/SSm3/secSm3/sec
Standard cubic meters per minuteSM3/MNSm3/minSm3/min
Standard cubic meters per hourSM3/HSm3/hrSm3/hr
Standard cubic meters per daySM3/DSm3/daySm3/day
Standard liters per secondSLPSSLPSSLPS
Standard liters per minuteSLPMSLPMSLPM
Standard liters per hourSLPHSLPHSLPH
Standard liters per daySLPDSLPDSLPD
Special measurement unitSPECLspecialSpecial
DisplayProLink IIIField Communicator
Define a special measurement unit for gas standard volume flow
Display
ProLink IIIDevice Tools→Configuration→Process Measurement→Flow→Special Units
Field CommunicatorConfigure→Manual Setup→Measurements→Special Units→Special GSV Units
A special measurement unit is a user-defined unit of measure that allows you to report process data, totalizer
data, and inventory data in a unit that is not available in the transmitter. A special measurement unit is
calculated from an existing measurement unit using a conversion factor.
Note
Although you cannot define a special measurement unit using the display, you can use the display to select an
existing special measurement unit, and to view process data using the special measurement unit.
Procedure
1. Specify Base Gas Standard Volume Unit.
Base Gas Standard Volume Unit is the existing gas standard volume unit that the special unit will be
based on.
2. Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
3. Calculate Gas Standard Volume Flow Conversion Factor as follows:
Not available
Configuration and Use Manual29
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
a) x base units = y special units
b) Gas Standard Volume Flow Conversion Factor = x ÷ y
4. Enter the Gas Standard Volume Flow Conversion Factor.
The original gas standard volume flow value is divided by this conversion factor.
5. Set Gas Standard Volume Flow Label to the name you want to use for the gas standard volume flow
unit.
6. Set Gas Standard Volume Total Label to the name you want to use for the gas standard volume total
and gas standard volume inventory unit.
The special measurement unit is stored in the transmitter. You can configure the transmitter to use the
special measurement unit at any time.
Example: Defining a special measurement unit for gas standard volume flow
You want to measure gas standard volume flow in thousands of standard cubic feet per minute.
1. Set Base Gas Standard Volume Unit to SCF.
2. Set Base Time Unit to minutes (min).
3. Calculate the conversion factor:
a. 1 thousands of standard cubic feet per minute = 1000 cubic feet per minute
b. Gas Standard Volume Flow Conversion Factor = 1 ÷ 1000 = 0.001 standard
4. Set Gas Standard Volume Flow Conversion Factor to 0.001.
Field CommunicatorConfigure→Manual Setup→Measurements→GSV→GSV Cutoff
Gas Standard Volume Flow Cutoff specifies the lowest gas standard volume flow rate that will reported as
measured. All gas standard volume flow rates below this cutoff will be reported as 0.
Procedure
Set Gas Standard Volume Flow Cutoff to the value you want to use.
The default value for Gas Standard Volume Flow Cutoff is 0.0. The lower limit is 0.0. There is no upper limit.
The recommended value is 0.5% of the nominal flow rate of the attached sensor. See the sensor
specifications.
Not available
30Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
Interaction between Gas Standard Volume Flow Cutoff and mA Output
Cutoff
Gas Standard Volume Flow Cutoff defines the lowest Gas Standard Volume flow value that the transmitter
will report as measured. mA Output Cutoff defines the lowest flow rate that will be reported through mA
Output. If mA Output Process Variable is set to Gas Standard Volume Flow Rate, the volume flow rate
reported through mA Output is controlled by the higher of the two cutoff values.
Gas Standard Volume Flow Cutoff affects both the gas standard volume flow values reported through
outputs and the gas standard volume flow values used in other transmitter behavior (for example, events
defined on gas standard volume flow).
mA Output Cutoff affects only flow values reported through mA Output.
Example: Cutoff interaction with mA Output Cutoff lower than Gas Standard Volume Flow Cutoff
Configuration:
• mA Output Process Variable for the primary mA Output: Gas Standard Volume Flow Rate
• Frequency Output Process Variable: Gas Standard Volume Flow Rate
• mA Output Cutoff for the primary mA Output: 10 SLPM (standard liters per minute)
• Gas Standard Volume Flow Cutoff: 15 SLPM
Result: If the gas standard volume flow rate drops below 15 SLPM, the volume flow will be reported as 0, and 0
will be used in all internal processing.
Example: Cutoff interaction with mA Output Cutoff higher than Gas Standard Volume Flow Cutoff
Configuration:
• mA Output Process Variable for the primary mA Output: Gas Standard Volume Flow Rate
• Frequency Output Process Variable: Gas Standard Volume Flow Rate
• mA Output Cutoff for the primary mA Output: 15 SLPM (standard liters per minute)
• Gas Standard Volume Flow Cutoff: 10 SLPM
Result:
• If the gas standard volume flow rate drops below 15 SLPM but not below 10 SLPM:
— The primary mA Output will report zero flow.
— The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all
internal processing.
• If the gas standard volume flow rate drops below 10 SLPM, both outputs will report zero flow, and 0 will be
Field CommunicatorConfigure→Manual Setup→Measurements→Flow→Flow Direction
Configuration and Use Manual31
Not available
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
Flow Direction controls how forward flow and reverse flow affect flow measurement and reporting.
Flow Direction is defined with respect to the flow arrow on the sensor:
• Forward flow (positive flow) moves in the direction of the flow arrow on the sensor.
• Reverse flow (negative flow) moves in the direction opposite to the flow arrow on the sensor.
Tip
Micro Motion sensors are bidirectional. Measurement accuracy is not affected by actual flow direction or the
setting of the Flow Direction parameter.
Procedure
Set Flow Direction to the value you want to use.
The default setting is Forward.
4.4.1 Options for Flow Direction
Flow Direction setting
Relationship to Flow Direction arrow on sensorProLink IIIField Communicator
ForwardForwardAppropriate when the Flow Direction arrow is in
the same direction as the majority of flow.
ReverseReverseAppropriate when the Flow Direction arrow is in
the opposite direction from the majority of flow.
Absolute ValueAbsolute ValueFlow Direction arrow is not relevant.
BidirectionalBi directionalAppropriate when both forward and reverse flow
are expected, and forward flow will dominate, but
the amount of reverse flow will be significant.
Negate ForwardNegate/Forward OnlyAppropriate when the Flow Direction arrow is in
the opposite direction from the majority of flow.
Negate BidirectionalNegate/Bi-directionalAppropriate when both forward and reverse flow
are expected, and reverse flow will dominate, but
the amount of forward flow will be significant.
Effect of Flow Direction on mA Outputs
Flow Direction affects how the transmitter reports flow values via the mA Outputs. The mA Outputs are
affected by Flow Direction only if mA Output Process Variable is set to a flow variable.
Flow Direction and mA Outputs
The effect of Flow Direction on the mA Outputs depends on Lower Range Value configured for the mA
Output:
• If Lower Range Value is set to 0, see Figure 4-1.
• If Lower Range Value is set to a negative value, see Figure 4-2.
32Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
Figure 4-1: Effect of Flow Direction on the mA Output: Lower Range Value = 0
Flow Direction = Forward
20
12
mA output
4
-x0x
Reverse flowForward flow
Flow Direction = Reverse, Negate Forward
20
12
mA output
4
-x0x
Reverse flowForward flow
Flow Direction = Absolute Value, Bidirectional,
Negate Bidirectional
20
12
mA output
4
• Lower Range Value = 0
• Upper Range Value = x
Figure 4-2: Effect of Flow Direction on the mA Output: Lower Range Value < 0
Flow Direction = Forward
20
Flow Direction = Reverse, Negate Forward
20
Flow Direction = Absolute Value, Bidirectional,
Negate Bidirectional
20
-x0x
Reverse flowForward flow
12
mA output
4
-x0x
Reverse flowForward flow
12
mA output
4
-x0x
Reverse flowForward flow
12
mA output
4
-x0x
Reverse flowForward flow
• Lower Range Value = −x
• Upper Range Value = x
Flow Direction = Forward and Lower Range Value = 0
Configuration:
• Flow Direction = Forward
• Lower Range Value = 0 g/sec
• Upper Range Value = 100 g/sec
Configuration and Use Manual33
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
Result:
• Under conditions of zero flow, the mA Output is 4 mA.
• Under conditions of forward flow, up to a flow rate of 100 g/sec, the mA Output varies between 4 mA and
20 mA in proportion to the flow rate.
• Under conditions of forward flow, if the flow rate equals or exceeds 100 g/sec, the mA Output will be
proportional to the flow rate up to 20.5 mA, and will be level at 20.5 mA at higher flow rates.
Flow Direction = Forward and Lower Range Value < 0
Configuration:
• Flow Direction = Forward
• Lower Range Value = −100 g/sec
• Upper Range Value = +100 g/sec
Result:
• Under conditions of zero flow, the mA Output is 12 mA.
• Under conditions of forward flow, for flow rates between 0 and +100 g/sec, the mA Output varies between
12 mA and 20 mA in proportion to (the absolute value of) the flow rate.
• Under conditions of forward flow, if (the absolute value of) the flow rate equals or exceeds 100 g/sec, the
mA Output is proportional to the flow rate up to 20.5 mA, and will be level at 20.5 mA at higher flow rates.
• Under conditions of reverse flow, for flow rates between 0 and −100 g/sec, the mA Output varies between
4 mA and 12 mA in inverse proportion to the absolute value of the flow rate.
• Under conditions of reverse flow, if the absolute value of the flow rate equals or exceeds 100 g/sec, the mA
Output is inversely proportional to the flow rate down to 3.8 mA, and will be level at 3.8 mA at higher
absolute values.
Flow Direction = Reverse
Configuration:
• Flow Direction = Reverse
• Lower Range Value = 0 g/sec
• Upper Range Value = 100 g/sec
Result:
• Under conditions of zero flow, the mA Output is 4 mA.
• Under conditions of reverse flow, for flow rates between 0 and +100 g/sec, the mA Output level varies
between 4 mA and 20 mA in proportion to the absolute value of the flow rate.
• Under conditions of reverse flow, if the absolute value of the flow rate equals or exceeds 100 g/sec, the mA
Output will be proportional to the absolute value of the flow rate up to 20.5 mA, and will be level at
20.5 mA at higher absolute values.
34Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
Effect of flow direction on Frequency Outputs
Flow direction affects how the transmitter reports flow values via the Frequency Outputs. The Frequency
Outputs are affected by flow direction only if Frequency Output Process Variable is set to a flow variable.
Table 4-1: Effect of the flow direction parameter and actual flow direction on Frequency Outputs
Actual flow direction
Flow Direction setting
ForwardHz > 00 Hz0 Hz
Reverse0 Hz0 HzHz > 0
BidirectionalHz > 00 HzHz > 0
Absolute ValueHz > 00 HzHz > 0
Negate Forward0 Hz0 HzHz > 0
Negate BidirectionalHz > 00 HzHz > 0
ForwardZero flowReverse
Effect of flow direction on Discrete Outputs
The flow direction parameter affects the Discrete Output behavior only if Discrete Output Source is set to
Flow Direction.
Table 4-2: Effect of the flow direction parameter and actual flow direction on Discrete Outputs
Actual flow direction
Flow Direction setting
ForwardOFFOFFON
ReverseOFFOFFON
BidirectionalOFFOFFON
Absolute ValueOFFOFFON
Negate ForwardONOFFOFF
Negate BidirectionalONOFFOFF
ForwardZero flowReverse
Effect of flow direction on digital communications
Flow direction affects how flow values are reported via digital communications. The following table describes
the effect of the flow direction parameter and actual flow direction on flow values reported via digital
communications.
Table 4-3: Effect of the flow direction on flow values
Actual flow direction
Flow Direction setting
ForwardPositive0Negative
ReversePositive0Negative
BidirectionalPositive0Negative
Configuration and Use Manual35
ForwardZero flowReverse
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
Table 4-3: Effect of the flow direction on flow values (continued)
Actual flow direction
Flow Direction setting
Absolute ValuePositive
Negate ForwardNegative0Positive
Negate BidirectionalNegative0Positive
(1) Refer to the digital communications status bits for an indication of whether flow is positive or negative.
ForwardZero flowReverse
(1)
0Positive
(1)
Effect of flow direction on flow totals
Flow direction affects how flow totals and inventories are calculated.
Actual flow direction
Flow Direction setting
ForwardTotals increaseTotals do not changeTotals do not change
ReverseTotals do not changeTotals do not changeTotals increase
BidirectionalTotals increaseTotals do not changeTotals decrease
Absolute ValueTotals increaseTotals do not changeTotals increase
Negate ForwardTotals do not changeTotals do not changeTotals increase
Negate BidirectionalTotals decreaseTotals do not changeTotals increase
ForwardZero flowReverse
4.5 Configure density measurement
The density measurement parameters control how density is measured and reported.
The two-phase flow parameters control how the transmitter detects and reports two-phase flow (gas in a
liquid process or liquid in a gas process).
Note
Two-phase flow is also referred to as slug flow.
Procedure
1. Set Two-Phase Flow Low Limit to the lowest density value that is considered normal in your process.
Values below this will cause the transmitter to post Alert A105 (Two-Phase Flow).
Tip
Gas entrainment can cause your process density to drop temporarily. To reduce the occurrence of twophase flow alerts that are not significant to your process, set Two-Phase Flow Low Limit slightly below
your expected lowest process density.
Configuration and Use Manual37
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
You must enter Two-Phase Flow Low Limit in g/cm³, even if you configured another unit for density
measurement.
The default value for Two-Phase Flow Low Limit is 0.0 g/cm³. The range is 0.0 to 10.0 g/cm³.
2. Set Two-Phase Flow High Limit to the highest density value that is considered normal in your process.
Micro Motion recommends leaving Two-Phase Flow High Limit at the default value.
Values above this will cause the transmitter to post Alert A105 (Two-Phase Flow).
You must enter Two-Phase Flow High Limit in g/cm³, even if you configured another unit for density
measurement.
The default value for Two-Phase Flow High Limit is 5.0 g/cm³. The range is 0.0 to 10.0 g/cm³.
3. Set Two-Phase Flow Timeout to the number of seconds that the transmitter will wait for a two-phase
flow condition to clear before posting the alert.
The default value for Two-Phase Flow Timeout is 0.0 seconds, meaning that the alert will be posted
immediately. The range is 0.0 to 60.0 seconds.
The Two-Phase Flow alert is set immediately. The flow rate will hold the last measured value for the
Timeout time. Then the flow rate will report zero flow. If the density goes back in range, the error clears
immediately.
Detecting and reporting two-phase flow
Two-phase flow (gas in a liquid process or liquid in a gas process) can cause a variety of process control issues.
By configuring the two-phase flow parameters appropriately for your application, you can detect process
conditions that require correction.
Micro Motion recommends leaving Two-Phase Flow High Limit at the default value.
A two-phase flow condition occurs whenever the measured density goes below Two-Phase Flow Low Limit or
above Two-Phase Flow High Limit. If this occurs:
• A two-phase flow alert is posted to the active alert log.
• All outputs that are configured to represent flow rate hold their last pre-alert value for the number of
seconds configured in Two-Phase Flow Timeout.
If the two-phase flow condition clears before Two-Phase Flow Timeout expires:
• Outputs that represent flow rate revert to reporting actual flow.
• The two-phase flow alert is deactivated, but remains in the active alert log until it is acknowledged.
If the two-phase flow condition does not clear before Two-Phase Flow Timeout expires, the outputs that
represent flow rate report a flow rate of 0.
If Two-Phase Flow Timeout is set to 0.0 seconds, the outputs that represent flow rate will report a flow rate of
0 as soon as two-phase flow is detected.
4.5.3 Configure Density Damping
Display
38Micro Motion 1700 Transmitters with Analog Outputs
Not available
Configuration and Use ManualConfigure process measurement
Field CommunicatorConfigure→Manual Setup→Measurements→Density→Density Damping
Density Damping controls the amount of damping that will be applied to the line density value.
Damping is used to smooth out small, rapid fluctuations in process measurement. Damping Value specifies
the time period (in seconds) over which the transmitter will spread changes in the process variable. At the end
of the interval, the internal value will reflect 63% of the change in the actual measured value.
Tip
Density damping affects all process variables that are calculated from line density.
Procedure
Set Density Damping to the value you want to use.
The default value is 1.6 seconds. For most applications, the default density damping setting is sufficient. The
range depends on the core processor type and the setting of Update Rate, as shown in the following table:
Update Rate settingDamping range
Normal0 to 51.2 seconds
Special0 to 40.96 seconds
Tip
• A high damping value makes the process variable appear smoother because the reported value changes
slowly.
• A low damping value makes the process variable appear more erratic because the reported value changes
more quickly.
• Whenever the damping value is non-zero, the reported measurement will lag the actual measurement
because the reported value is being averaged over time.
• In general, lower damping values are preferable because there is less chance of data loss, and less lag time
between the actual measurement and the reported value.
The value you enter is automatically rounded off to the nearest valid value. The valid values for DensityDamping depend on the setting of Update Rate.
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
Effect of Density Damping on volume measurement
Density Damping affects liquid volume measurement. Liquid volume values are calculated from the damped
density value rather than the measured density value. Density Damping does not affect gas standard volume
measurement.
Field CommunicatorConfigure→Manual Setup→Measurements→Density→Density Cutoff
Density Cutoff specifies the lowest density value that will be reported as measured. All density values below
this cutoff will be reported as 0.
Procedure
Set Density Cutoff to the value you want to use.
For most applications, the default setting (0.2 g/cm³) is sufficient. The range is 0.0 g/cm³ to 0.5 g/cm³.
Effect of Density Cutoff on volume measurement
Density Cutoff affects liquid volume measurement. If the density value goes below Density Cutoff, the
volume flow rate is reported as 0. Density Cutoff does not affect gas standard volume measurement. Gas
standard volume values are always calculated from the value configured for Standard Gas Density or polled
value if configured for polled base density.
4.6 Configure temperature measurement
The temperature measurement parameters control how temperature data from the sensor is reported.
Field CommunicatorConfigure→Manual Setup→Measurements→Temperature→Temperature Unit
Temperature Measurement Unit specifies the unit that will be used for temperature measurement.
Procedure
Set Temperature Measurement Unit to the option you want to use.
The default setting is Degrees Celsius.
OFF-LINE MAINT → OFF-LINE CONFG → UNITS → TEMP
40Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
Options for Temperature Measurement Unit
The transmitter provides a standard set of units for Temperature Measurement Unit. Different
communications tools may use different labels for the units.
Field CommunicatorConfigure→Manual Setup→Measurements→Temperature→Temp Damping
Temperature Damping controls the amount of damping that will be applied to the line temperature value,
when the on-board temperature data is used (RTD).
Damping is used to smooth out small, rapid fluctuations in process measurement. Damping Value specifies
the time period (in seconds) over which the transmitter will spread changes in the process variable. At the end
of the interval, the internal value will reflect 63% of the change in the actual measured value.
Tip
Temperature Damping affects all process variables, compensations, and corrections that use temperature
data from the sensor.
Procedure
Enter the value you want to use for Temperature Damping.
The default value is 4.8 seconds. For most applications, the default temperature damping setting is sufficient.
The range is 0.0 to 38.4 seconds.
Tip
• A high damping value makes the process variable appear smoother because the reported value changes
slowly.
• A low damping value makes the process variable appear more erratic because the reported value changes
more quickly.
• Whenever the damping value is non-zero, the reported measurement will lag the actual measurement
because the reported value is being averaged over time.
• In general, lower damping values are preferable because there is less chance of data loss, and less lag time
between the actual measurement and the reported value.
The value you enter is automatically rounded off to the nearest valid value. Valid values for TemperatureDamping are 0, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, and 38.4.
Configuration and Use Manual41
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
4.6.3 Effect of Temperature Damping on process measurement
Temperature Damping affects all processes and algorithms that use temperature data from the internal
sensor RTD.
Temperature compensation
Temperature compensation adjusts process measurement to compensate for the effect of temperature on
the sensor tubes.
4.6.4 Configure Temperature Input
Temperature data from the on-board temperature sensor (RTD) is always available. Optionally, you can set up
an external temperature device and use external temperature data.
Pressure compensation adjusts process measurement to compensate for the pressure effect on the sensor.
The pressure effect is the change in the sensor’s sensitivity to flow and density caused by the difference
between the calibration pressure and the process pressure.
Tip
Not all sensors or applications require pressure compensation. The pressure effect for a specific sensor model
can be found in the product data sheet located at Emerson.com. If you are uncertain about implementing
pressure compensation, contact customer service.
Prerequisites
You will need the flow factor, density factor, and calibration pressure values for your sensor.
• For the flow factor and density factor, see the product data sheet for your sensor.
• For the calibration pressure, see the calibration sheet for your sensor. If the data is unavailable, use 20 PSI.
4.7.1 Configure pressure compensation using ProLink III
If you will use an external pressure value, set Pressure Unit to match the pressure unit used by the
external pressure device.
4. Enter Flow Calibration Pressure for your sensor.
The calibration pressure is the pressure at which your sensor was calibrated, and defines the pressure at
which there is no pressure effect. If the data is unavailable, enter 20 PSI.
42Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
5. Enter Flow Factor for your sensor.
The flow factor is the percent change in the flow rate per PSI. When entering the value, reverse the
sign.
Example
If the flow factor is 0.000004 % per PSI, enter −0.000004 % per PSI.
6. Enter Density Factor for your sensor.
The density factor is the change in fluid density, in g/cm3/PSI. When entering the value, reverse the
sign.
Example
If the density factor is −0.000006 g/cm3/PSI, enter +0.000006 g/cm3/PSI.
7. Set Pressure Source to the method that the transmitter will use to obtain pressure data.
OptionDescription
Poll for external valueThe transmitter will poll an external pressure device, using HART
®
protocol over the primary mA Output.
Fixed Value or Digital
Communications
The transmitter will use the pressure value that it reads from
memory.
• Fixed Value: The configured value is used.
• Digital Communications: A host writes transmitter data to
transmitter memory.
Note
If the Weights & Measures application is implemented and the
transmitter is secured, digital communications cannot be used to
write temperature or pressure data to the transmitter.
8. If you chose to poll for pressure data:
a) Select the Polling Slot to use.
b) Set Polling Control to Poll as Primary or Poll as Secondary, and click Apply.
Tip
• Poll as Primary: No other HART masters will be on the network.
• Poll as Secondary: Other HART masters will be on the network. The Field Communicator is
not a HART master.
c) Set External Device Tag to the HART tag of the external pressure device, and click Apply.
d) Ensure that the primary mA Output is wired to support HART communications with the external
pressure device.
9. If you chose to use a fixed pressure value:
Configuration and Use Manual43
Configure process measurementConfiguration and Use Manual
June 2022MMI-20019028
a) Set Fixed Value to the value to use, and click Apply
10. If you want to use digital communications, click Apply, then perform the necessary host programming
and communications setup to write pressure data to the transmitter at appropriate intervals.
Postrequisites
If you are using an external pressure value, verify the setup by checking the External Pressure value displayed
in the Inputs area of the main window.
4.7.2 Configure pressure compensation using the Field
Communicator
The calibration pressure is the pressure at which your sensor was calibrated, and defines the pressure at
which there is no pressure effect. If the data is unavailable, enter 20 PSI.
4. Enter Flow Press Factor for your sensor.
The flow factor is the percent change in the flow rate per PSI. When entering the value, reverse the
sign.
Example
If the flow factor is −0.0002 % per PSI, enter +0.0002 % per PSI.
5. Enter Dens Press Factor for your sensor.
The density factor is the change in fluid density, in g/cm3/PSI. When entering the value, reverse the
sign.
Example
If the density factor is −0.000006 g/cm3/PSI, enter +0.000006 g/cm3/PSI.
6. Determine how the transmitter will obtain pressure data, and perform the required setup.
Option
A user-configured static
pressure value
Setup
a. Set Pressure Unit to the desired unit.
b. Set Compensation Pressure to the desired value.
Polling for pressurea. Ensure that the primary mA Output has been wired to support HART
polling.
b. Choose Online→Configure→Manual Setup→Measurements→
External Pressure/Temperature→External Polling.
44Micro Motion 1700 Transmitters with Analog Outputs
®
Configuration and Use ManualConfigure process measurement
MMI-20019028June 2022
OptionSetup
c. Set Poll Control to Poll As Primary Host or Poll as Secondary Host.
d. Choose an unused polling slot.
e. Set External Tag to the HART tag of the external pressure device.
f. Set Polled Variable to Pressure.
Tip
• Poll as Primary: No other HART masters will be on the network.
• Poll as Secondary: Other HART masters will be on the network. The Field
Communicator is not a HART master.
A value written by
digital communications
a. Set Pressure Unit to the desired unit.
b. Perform the necessary host programming and communications setup
to write pressure data to the transmitter at appropriate intervals.
Note
If the Weights & Measures application is implemented and the transmitter
is secured, digital communications cannot be used to write temperature or
pressure data to the transmitter.
Postrequisites
If you are using an external pressure value, verify the setup by choosing Service Tools → Variables → External
Variables and checking the value displayed for External Pressure.
4.7.3 Options for Pressure Measurement Unit
The transmitter provides a standard set of measurement units for Pressure Measurement Unit. Different
communications tools may use different labels for the units. In most applications, Pressure MeasurementUnit should be set to match the pressure measurement unit used by the remote device.
Label
Unit description
DisplayProLink IIIField Communicator
Feet water @ 68 °FFTH2OFt Water @ 68 °FftH2O
Inches water @ 4 °CINW4CIn Water @ 4 °CinH2O @4DegC
Inches water @ 60 °FINW60In Water @ 60 °FinH2O @60DegF
Inches water @ 68 °FINH2OIn Water @ 68 °FinH2O
Millimeters water @ 4 °CmmW4Cmm Water @ 4 °CmmH2O @4DegC
Millimeters water @ 68 °FmmH2Omm Water @ 68 °FmmH2O
Field CommunicatorConfigure→Manual Setup→Display→Display Variables
You can control the process variables and diagnostic variables shown on the display, and the order in which
they appear. The display can scroll through up to 15 variables in any order you choose. In addition, you can
repeat variables or leave slots unassigned.
Restriction
• You cannot set Display Variable 1 to None or to a diagnostic variable. Display Variable 1 must be set to a
process variable.
• If you have configured Display Variable 1 to track the primary mA Output, you cannot change the setting
of Display Variable 1 using this procedure. To change the setting of Display Variable 1, you must change
the configuration of mA Output Process Variable for the primary mA Output.
Note
If you configure a display variable as a volume process variable and then change Volume Flow Type, the
display variable is automatically changed to the equivalent process variable. For example, Volume Flow Rate
would be changed to Gas Standard Volume Flow Rate.
Not available
Procedure
For each display variable you want to change, assign the process variable you want to use.
Configuration and Use Manual47
Configure device options and preferencesConfiguration and Use Manual
June 2022MMI-20019028
Default display variable configuration
Display variableProcess variable assignment
Display Variable 1
Display Variable 2
Display Variable 3
Display Variable 4
Display Variable 5
Display Variable 6
Display Variable 7
Display Variable 8
Display Variable 9
Display Variable 10
Display Variable 11
Display Variable 12
Display Variable 13
Display Variable 14
Display Variable 15
Mass flow
Mass total
Volume flow
Volume total
Density
Temperature
External pressure
Mass flow
None
None
None
None
None
None
None
Configure Display Variable 1 to track the primary mA Output
Field CommunicatorConfigure→Manual Setup→Display→Display Variables
You can configure Display Variable 1 to track mA Output Process Variable for the primary mA Output. When
tracking is enabled, you can control Display Variable 1 from the display menu.
Tip
This feature is the only way to configure a display variable from the display menus, and it applies only to
Display Variable 1.
Procedure
Configure Display Variable 1 to track the primary mA Output.
Display Variable 1 will automatically be set to match mA Output Process Variable for the primary mA
Output. If you change the configuration of mA Output Process Variable, Display Variable 1 will be updated
automatically.
OFF-LINE MAINT → OFF-LINE CONFG → DISPLY → VAR 1
48Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure device options and preferences
MMI-20019028June 2022
5.1.3 Configure the number of decimal places (precision) shown on
Field CommunicatorConfigure→Manual Setup→Display→Decimal Places
You can specify the number of decimal places (precision) that are shown on the display for each process
variable or diagnostic variable. You can set the precision independently for each variable.
The display precision does not affect the actual value of the variable or the value used in calculations.
Procedure
1. Select a variable.
2. Set Number of Decimal Places to the number of decimal places you want shown when the process
variable or diagnostic variable appears on the display.
For temperature and density process variables, the default value is 2 decimal places. For all other
variables, the default value is 4 decimal places. The range is 0 to 5.
Tip
The lower the precision, the greater the change must be for it to be reflected on the display. Do not set
the precision too low or too high to be useful.
5.1.4 Configure the refresh rate of data shown on the display
Field CommunicatorConfigure→Manual Setup→Display→Display Variable Menu Features→Auto Scroll
OFF-LINE MAINT → OFF-LINE CONFG → DISPLAY → AUTO SCRLL
Configuration and Use Manual49
Configure device options and preferencesConfiguration and Use Manual
June 2022MMI-20019028
You can configure the display to automatically scroll through the configured display variables or to show a
single display variable until the operator activates Scroll. When you set automatic scrolling, you can also
configure the length of time each display variable is displayed.
Procedure
1. Enable or disable Auto Scroll as desired.
OptionDescription
EnabledThe display automatically scrolls through each display variable as specified by Scroll
Rate. The operator can move to the next display variable at any time using Scroll.
Disabled
(default)
The display shows Display Variable 1 and does not scroll automatically. The
operator can move to the next display variable at any time using Scroll.
2. If you enabled Auto Scroll, set Scroll Rate as desired.
The default value is 10 seconds.
Tip
Scroll Rate may not be available until you apply Auto Scroll.
Field CommunicatorConfigure→Manual Setup→Display→Display Variable Menu Features→Status LED Blinking
By default, the status LED blinks (flashes) to indicate unacknowledged alerts. If you disable Status LEDBlinking, the status LED does not blink, whether alerts are acknowledged or not. It still changes color to
indicate active alerts.
Procedure
Enable or disable Status LED Blinking.
The default setting is Enabled.
50Micro Motion 1700 Transmitters with Analog Outputs
Not available
Configuration and Use ManualConfigure device options and preferences
MMI-20019028June 2022
5.2 Enable or disable operator actions from the display
You can configure the transmitter to let the operator perform specific actions using the display.
5.2.1 Enable or disable Totalizer Start/Stop from the display
Field CommunicatorConfigure→Manual Setup→Display→Offline Variable Menu Features
52Micro Motion 1700 Transmitters with Analog Outputs
OFF-LINE MAINT → OFF-LINE CONFG → DISPLAY
Configuration and Use ManualConfigure device options and preferences
MMI-20019028June 2022
You can control operator access to different sections of the display off-line menu. You can also configure a
password to control access.
Procedure
1. To control operator access to the maintenance section of the off-line menu, enable or disable Off-Line
Menu.
OptionDescription
Enabled (default) Operator can access the maintenance section of the off-line menu. This access is
required for configuration and calibration, but is not required to view alerts or to
access Smart Meter Verification (if applicable).
DisabledOperator cannot access the maintenance section of the off-line menu.
2. To control operator access to the alert menu, enable or disable Alert Menu.
OptionDescription
Enabled (default) Operator can access the alert menu. This access is required to view and
acknowledge alerts, but is not required for Smart Meter Verification (if applicable),
configuration, or calibration.
DisabledOperator cannot access the alert menu.
Note
The transmitter status LED changes color to indicate that there are active alerts, but does not show
specific alerts.
3. To require a password for access to the maintenance section of the off-line menu and the Smart Meter
Verification menu, enable or disable Off-Line Password.
Option
Description
EnabledOperator is prompted for the off-line password at entry to the Smart Meter
Verification menu (if applicable), or entry to the maintenance section of the
off-line menu.
Disabled (default)No password is required for entry to the Smart Meter Verification menu (if
applicable) or entry to the maintenance section of the off-line menu.
4. To require a password to access the alert menu, enable or disable Alert Password.
Option
Description
EnabledOperator is prompted for the off-line password at entry to the alert menu.
Disabled (default)No password is required for entry to the alert menu.
If both Off-Line Password and Alert Password are enabled, the operator is prompted for the off-line
password to access the off-line menu, but is not prompted thereafter.
5. Set Off-Line Password to the desired value.
Configuration and Use Manual53
Configure device options and preferencesConfiguration and Use Manual
June 2022MMI-20019028
The default value is 1234. The range is 0000 to 9999.
The same value is used for both the off-line password and the alert password.
Tip
Record your password for future reference.
5.4 Configure response time parameters
You can configure the rate at which process data is polled and process variables are calculated.
Field CommunicatorConfigure→Manual Setup→Measurements→Update Rate
Update Rate controls the rate at which process data is polled and process variables are calculated. Update
Rate = Special produces faster and “noisier” response to changes in the process. Do not use Special mode
unless required by your application.
Prerequisites
Before setting Update Rate to Special:
• Check the effects of Special mode on specific process variables.
• Contact customer support.
Tip
For systems with a standard core processor, Special mode can improve performance for applications with
entrained air or Empty-Full-Empty conditions. This does not apply to systems with an enhanced core
processor.
Procedure
1. Set Update Rate as desired.
Option
Normal All process data is polled at the rate of 20 times per second (20 Hz).
Special A single, user-specified process variable is polled at the rate of 100 times per second
Description
All process variables are calculated at 20 Hz.
This option is appropriate for most applications.
(100 Hz). Other process data is polled at 6.25 Hz. Some process, diagnostic, and calibration
data is not polled.
All available process variables are calculated at 100 Hz.
Use this option only if required by your application.
If you change Update Rate, the settings for Flow Damping, and Density Damping are automatically
adjusted.
54Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure device options and preferences
MMI-20019028June 2022
2. If you set Update Rate to Special, select the process variable to be polled at 100 Hz.
Effects of Update Rate = Special
Incompatible features and functions
Special mode is not compatible with the following features and functions:
• Enhanced events. Use basic events instead.
• All calibration procedures.
• Zero verification.
• Restoring the factory zero or the prior zero.
If required, you can switch to Normal mode, perform the desired procedures, and then return to Special
mode.
Process variable updates
Some process variables are not updated when Special mode is enabled.
Table 5-1: Special mode and process variable updates
Always polled and updatedUpdated only when the petroleum
measurement application is
disabled
• Mass flow
• Volume flow
• Gas standard volume flow
• Density
• Temperature
• Drive gain
• LPO amplitude
• Status [contains Event 1 and Event
2 (basic events)]
• Mass total
• Volume total
• Live zero
• Gas standard volume total
• RPO amplitude
• Core input voltage
• Mass inventory
• Volume inventory
• Gas standard volume inventory
5.4.2 Configure Response Time
Never updated
All other process variables and
calibration data. They retain the values
held at the time you enabled Special
mode.
Display
ProLink IIIDevice Tools→Configuration→Process Measurement→Response→Response Time
Field CommunicatorNot available
Configuration and Use Manual55
Not available
Configure device options and preferencesConfiguration and Use Manual
June 2022MMI-20019028
Response Time is used to apply a different algorithm to the calculation of process variables from the raw
process data.
Restriction
Response Time is available only on systems with the enhanced core processor.
Procedure
Set Response Time as desired.
OptionDescription
Normal (Legacy)Transmitter calculates process variables at the standard speed. This option is
selected if this parameter was configured on an earlier version of ProLink III
software.
Special (Legacy)Transmitter calculates process variables at a faster speed. This option is
selected if this parameter was configured on an earlier version of ProLink III
software.
Normal - Optimal FilteringTransmitter calculates process variables at standard filtering and speed.
Low Filtering - Fastest
Response
High Filtering - Smoothest
Output
ServiceFor factory use only.
Transmitter calculates process variables at the fastest speed.
Transmitter calculates process variables at the smoothest (least noisy)
response to changes in the process.
5.5 Configure alert handling
The alert handling parameters control the transmitter’s response to process and device conditions.
Field CommunicatorConfigure→Alert Setup→Alert Severity→Fault Timeout
Fault Timeout controls the delay before fault actions are performed.
Restriction
Fault Timeout is applied only to the following alerts (listed by Status Alert Code): A003, A004, A005, A008,
A016, A017, A033. For all other alerts, fault actions are performed as soon as the alert is detected.
Not available
Procedure
Set Fault Timeout as desired.
The default value is 0 seconds. The range is 0 to 60 seconds.
If you set Fault Timeout to 0, fault actions are performed as soon as the alert condition is detected.
56Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure device options and preferences
MMI-20019028June 2022
The fault timeout period begins when the transmitter detects an alert condition. During the fault timeout
period, the transmitter continues to report its last valid measurements.
If the fault timeout period expires while the alert is still active, the fault actions are performed. If the alert
condition clears before the fault timeout expires, no fault actions are performed.
Field CommunicatorConfigure→Manual Setup→Info Parameters→Sensor Information→Sensor Serial Number
Sensor Serial Number lets you store the serial number of the sensor component of your flowmeter in
transmitter memory. This parameter is not used in processing and is not required.
Procedure
1. Obtain the sensor serial number from your sensor tag.
2. Enter the serial number in the Sensor Serial Number field.
Field CommunicatorConfigure→Manual Setup→Info Parameters→Sensor Information→Tube Wetted Material
Sensor Material lets you store the type of material used for your sensor’s wetted parts in transmitter
memory. This parameter is not used in processing and is not required.
Procedure
1. Obtain the material used for your sensor’s wetted parts from the documents shipped with your sensor,
or from a code in the sensor model number.
To interpret the model number, refer to the product data sheet for your sensor.
Field CommunicatorConfigure→Manual Setup→Info Parameters→Sensor Information→Tube Lining
Sensor Liner Material lets you store the type of material used for your sensor liner in transmitter memory.
This parameter is not used in processing and is not required.
Procedure
1. Obtain your sensor’s liner material from the documents shipped with your sensor, or from a code in the
sensor model number.
To interpret the model number, refer to the product data sheet for your sensor.
2. Set Sensor Liner Material to the appropriate option.
Field CommunicatorConfigure→Manual Setup→Info Parameters→Transmitter Info→Date
Not available
62Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualConfigure device options and preferences
MMI-20019028June 2022
Date lets you store a static date (not updated by the transmitter) in transmitter memory. This parameter is
not used in processing and is not required.
Procedure
Enter the date you want to use, in the form mm/dd/yyyy.
Tip
ProLink III provides a calendar tool to help you select the date.
Configuration and Use Manual63
Configure device options and preferencesConfiguration and Use Manual
June 2022MMI-20019028
64Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualIntegrate the meter with the control system
MMI-20019028June 2022
6 Integrate the meter with the control
system
6.1 Configure the transmitter channels
DisplayOFF-LINE MAINT→OFF-LINE CONFG→IO→CH B
ProLink IIIDevice Tools→Configuration→I/O→Outputs
Field communicatorConfigure→Manual Setup→Inputs/Outputs→Channels→Channel B
You can configure Channel B on your transmitter to operate as a Frequency Output or a Discrete Output. The
channel configuration must match the wiring at the transmitter terminals.
Prerequisites
To avoid causing process errors:
• Configure the channels before configuring the outputs.
• Before changing the channel configuration, ensure that all control loops affected by the channel are under
manual control.
Procedure
Set Channel B as desired.
Option
Frequency OutputChannel B will operate as a Frequency Output.
Discrete OutputChannel B will operate as a Discrete Output.
Postrequisites
For each channel that you configured, perform or verify the corresponding input or output configuration.
When the configuration of a channel is changed, the channel’s behavior will be controlled by the
configuration that is stored for the selected input or output type, and the stored configuration may not be
appropriate for your process.
After verifying channel and output configuration, return the control loop to automatic control.
Description
6.2 Configure the mA Output
The mA Output is used to report the configured process variable. The mA Output parameters control how the
process variable is reported.
Your transmitter has one mA Output: Channel A.
Restriction
The process variable assigned to the primary mA Output is automatically assigned to the Frequency Output.
You cannot assign a different process variable.
Configuration and Use Manual65
Integrate the meter with the control systemConfiguration and Use Manual
June 2022MMI-20019028
Important
Whenever you change an mA Output parameter, verify all other mA Output parameters before returning the
meter to service. In some situations, the transmitter automatically loads a set of stored values, and these
values may not be appropriate for your application.
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→mA Output
Use mA Output Process Variable to select the variable that is reported over the mA Output. This variable is
applied automatically to the Frequency Output.
Prerequisites
• If you plan to configure the output to report volume flow, ensure that you have set Volume Flow Type as
desired: Liquid or Gas Standard Volume.
• If you are using the HART® variables, be aware that changing the configuration of mA Output Process
Variable will change the configuration of the HART Primary Variable (PV) and the HART Tertiary Variable
(TV).
• If you have configured Display Variable 1 to track mA Output Process Variable, be aware that changing
the configuration of mA Output Process Variable will change the contents of Display Variable 1.
Procedure
Set mA Output Process Variable as desired.
The default setting is Mass Flow Rate.
Postrequisites
If you changed the setting of mA Output Process Variable, verify the settings of Lower Range Value (LRV)
and Upper Range Value (URV).
Options for mA Output Process Variable
The transmitter provides a basic set of options for mA Output Process Variable, plus several applicationspecific options. Different communications tools may use different labels for the options.
Table 6-1: Standard mA Output process variables
Process variableLabel
DisplayProLink IIIField Communicator
Gas standard volume flow
rate
Mass flow rateMFLOWMass Flow RateMass flo
Volume flow rateVFLOWVolume Flow RateVol flo
66Micro Motion 1700 Transmitters with Analog Outputs
GSV FGas Standard Volume Flow
Rate
Gas vol flo
Configuration and Use ManualIntegrate the meter with the control system
MMI-20019028June 2022
Table 6-2: PVR mA Output process variables
Process variableLabel
DisplayProLink IIIField Communicator
Uncorrected oil flowOILOil Flow Rate At LineOil Flow Rate at Line
Uncorrected water cutWATER%Water Cut At LineWater Cut at Line
Uncorrected water flowWATERWater Flow Rate At LineWater Flow Rate at Line
Corrected oil flowOIL60Oil Flow Rate At ReferenceOil Flow Rate at Reference
Corrected water cutWCT60%Water Cut At ReferenceWater Cut at Reference
Corrected water flowWTR60Water Flow Rate At
Reference
Shrinkage factor corrected
net oil at line
Shrinkage factor corrected
net oil at 60F
Shrinkage factor corrected
volume of mix at 60F
SFOILSF Oil Flow Rate At LineShrinkage Factor Oil Flow
SFO60SF Oil Flow Rate At
Reference
SFM60SF Volume Flow Rate At
Reference
Water Flow Rate at
Reference
Rate at Line
Shrinkage Factor Oil Flow
Rate at Reference
Shrinkage Factor Volume
Flow Rate at Reference
6.2.2 Configure Lower Range Value (LRV) and Upper Range Value
Field Communicator• Configure→Manual Setup→Inputs/Outputs→mA Output→mA Output Settings→PV LRV
The Lower Range Value (LRV) and Upper Range Value (URV) are used to scale the mA Output, that is, to
define the relationship between mA Output Process Variable and the mA Output level.
• OFF-LINE MAINT → OFF-LINE CONFG → IO → CH A → 4 mA
• OFF-LINE MAINT → OFF-LINE CONFG → IO → CH A → 20 mA
• Configure → Manual Setup → Inputs/Outputs → mA Output → mA Output Settings → PV URV
Prerequisites
Ensure that mA Output Process Variable is set to the desired process variable. Each process variable has its
own set of LRV and URV values. When you change the values of LRV and URV, you are configuring values for
the currently assigned mA Output process variable.
Ensure that the measurement unit for the configured process variable has been set as desired.
Note
For transmitter software v5.0 and later, if you change LRV and URV from the factory default values, and you
later change mA Output Process Variable, LRV and URV will not reset to the default values.
Procedure
Set LRV and URV as desired.
Configuration and Use Manual67
Integrate the meter with the control systemConfiguration and Use Manual
June 2022MMI-20019028
• LRVis the value of mA Output Process Variable represented by an output of 4 mA. The default value for
LRV depends on the setting of mA Output Process Variable. Enter LRV in the measurement units that are
configured for mA Output Process Variable.
• URV is the value of mA Output Process Variable represented by an output of 20 mA. The default value for
URV depends on the setting of mA Output Process Variable. Enter URV in the measurement units that are
configured for mA Output Process Variable.
The mA Output uses a range of 4–20 mA to represent mA Output Process Variable. Between LRV and URV,
the mA Output is linear with the process variable. If the process variable drops below LRV or rises above URV,
the transmitter posts an output saturation alert.
Default values for Lower Range Value (LRV) and Upper Range Value (URV)
Each option for mA Output Process Variable has its own LRV and URV. If you change the configuration of mA
Output Process Variable, the corresponding LRV and URV are loaded and used.
Table 6-3: Default values for Lower Range Value (LRV) and Upper Range Value (URV)
Process variableLRVURV
All mass flow variables–200.000 g/sec200.000 g/sec
All liquid volume flow variables–0.200 l/sec0.200 l/sec
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→mA Output→mA Output Settings→PV MAO Cutoff
AO Cutoff (Analog Output Cutoff) specifies the lowest mass flow rate, volume flow rate, or gas standard
volume flow rate that will be reported through the mA Output. Any flow rates below AO Cutoff will be
reported as 0.
Restriction
AO Cutoff is applied only if mA Output Process Variable is set to Mass Flow Rate, Volume Flow Rate, or Gas
Standard Volume Flow Rate. If mA Output Process Variable is set to a different process variable, AO Cutoff is
not configurable, and the transmitter does not implement the AO cutoff function.
Procedure
Set AO Cutoff as desired.
Not available
The default value for AO Cutoff is 0.0 g/sec.
Tip
For most applications, the default value of AO Cutoff should be used. Contact customer service before
changing AO Cutoff.
68Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualIntegrate the meter with the control system
MMI-20019028June 2022
Interaction between AO Cutoff and process variable cutoffs
When mA Output Process Variable is set to a flow variable (for example, mass flow rate or volume flow rate),
AO Cutoff interacts with Mass Flow Cutoff or Volume Flow Cutoff. The transmitter puts the cutoff into effect
at the highest flow rate at which a cutoff is applicable.
Example: Cutoff interaction
Configuration:
• mA Output Process Variable = Mass Flow Rate
• Frequency Output Process Variable = Mass Flow Rate
• AO Cutoff = 10 g/sec
• Mass Flow Cutoff = 15 g/sec
Result: If the mass flow rate drops below 15 g/sec, all outputs representing mass flow will report zero flow.
Example: Cutoff interaction
Configuration:
• mA Output Process Variable = Mass Flow Rate
• Frequency Output Process Variable = Mass Flow Rate
• AO Cutoff = 15 g/sec
• Mass Flow Cutoff = 10 g/sec
Result:
• If the mass flow rate drops below 15 g/sec but not below 10 g/sec:
— The mA Output will report zero flow.
— The Frequency Output will report the actual flow rate.
• If the mass flow rate drops below 10 g/sec, both outputs will report zero flow.
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→mA Output→mA Output Settings→PV Added
Added Damping controls the amount of damping that will be applied to the mA Output.
Damping is used to smooth out small, rapid fluctuations in process measurement. Damping Value specifies
the time period (in seconds) over which the transmitter will spread changes in the process variable. At the end
of the interval, the internal value will reflect 63% of the change in the actual measured value.
Not available
Damping
Added Damping affects the reporting of mA Output Process Variable through the mA Output only. It does
not affect the reporting of that process variable via any other method (e.g., a Frequency Output or digital
communications), or the value of the process variable used in calculations.
Configuration and Use Manual69
Integrate the meter with the control systemConfiguration and Use Manual
June 2022MMI-20019028
Note
Added Damping is not applied if the mA Output is fixed (for example, during loop testing) or if the mA
Output is reporting a fault. Added Damping is applied while sensor simulation is active.
Procedure
Set Added Damping to the desired value.
The default value is 0.0 seconds. The range is 0.0 to 440 seconds.
When you specify a value for Added Damping, the transmitter automatically rounds the value down to the
nearest valid value.
Note
Added Damping values are affected by the setting of Update Rate and 100 Hz Variable.
Interaction between mA Output Damping and process variable damping
When mA Output Source is set to a flow rate variable, mA Output Damping interacts with Flow Damping. If
multiple damping parameters are applicable, the effect of damping the process variable is calculated first,
and the mA output damping calculation is applied to the result of that calculation.
Example: Damping interaction
Configuration:
• Flow Damping = 1 second
• mA Output Source = Mass Flow Rate
• mA Output Damping = 2 seconds
Result: A change in the mass flow rate will be reflected in the mA Output over a time period that is greater
than 3 seconds. The exact time period is calculated by the transmitter according to internal algorithms which
are not configurable.
6.2.5 Configure mA Output Fault Action and mA Output Fault Level
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→mA Output→MA0 Fault Settings
70Micro Motion 1700 Transmitters with Analog Outputs
Not available
Configuration and Use ManualIntegrate the meter with the control system
MMI-20019028June 2022
mA Output Fault Action controls the behavior of the mA Output if the transmitter encounters an internal
fault condition.
Note
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement the fault
action until the timeout has elapsed.
Procedure
1. Set mA Output Fault Action to the desired value.
The default setting is Downscale.
Restriction
If Digital Communications Fault Action is set to NAN (not a number), you cannot set mA Output Fault
Action or Frequency Output Fault Action to None. If you try to do this, the transmitter will not accept
the configuration.
2. If you set mA Output Fault Action to Upscale or Downscale, set mA Output Fault Level as desired.
Postrequisites
NOTICE
If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set Digital
Communications Fault Action to None. If you do not, the output will not report actual process data, and this
may result in measurement errors or unintended consequences for your process.
Options for mA Output Fault Action and mA Output Fault Level
Option
UpscaleGoes to the configured fault levelDefault: 22.0 mA
Downscale (default)Goes to the configured fault levelDefault: 2.0 mA
Internal ZeroGoes to the mA Output level associated with a
NoneTracks data for the assigned process variable; no
mA Output behavior
process variable value of 0 (zero), as determined
by Lower Range Value and Upper Range Value
settings
fault action
mA Output Fault Level
Range: 21.0 to 24.0 mA
Range: 1.0 to 3.6 mA
Not applicable
Not applicable
6.3 Configure the Frequency Output
The Frequency Output is used to report a process variable. The Frequency Output parameters control how the
process variable is reported. Your transmitter may have zero or one Frequency Output: Channel B can be
configured as a Frequency Output or a Discrete Output. The default assignment for Channel B is Frequency
Output.
Restriction
The process variable assigned to the primary mA Output is automatically assigned to the Frequency Output.
You cannot assign a different process variable.
Configuration and Use Manual71
Integrate the meter with the control systemConfiguration and Use Manual
June 2022MMI-20019028
Important
Whenever you change a Frequency Output parameter, verify all other Frequency Output parameters before
returning the flowmeter to service. In some situations, the transmitter automatically loads a set of stored
values, and these values may not be appropriate for your application.
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→Frequency Output→FO Settings→FO Polarity
Frequency Output Polarity controls how the output indicates the ON (active) state. The default value, Active
High, is appropriate for most applications. Your receiving device might require an Active Low setting.
Procedure
Set Frequency Output Polarity as desired.
The default setting is Active High.
Options for Frequency Output Polarity
Polarity optionReference voltage (OFF)Pulse voltage (ON)
Active High0As determined by power supply,
pull-up resistor, and load. See
the installation manual for your
transmitter.
Active LowAs determined by power supply,
pull-up resistor, and load. See
the installation manual for your
transmitter.
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→Frequency Output→FO Scaling
Frequency Output Scaling Method defines the relationship between output pulse and flow units. Set
Frequency Output Scaling Method as required by your frequency receiving device.
Procedure
1. Set Frequency Output Scaling Method.
OFF-LINE MAINT → OFF-LINE CONFG → IO → CH B → SET FO → FO SCALE
Option
Description
Frequency=Flow (default)Frequency calculated from flow rate
Pulses/UnitA user-specified number of pulses represents one flow unit
72Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualIntegrate the meter with the control system
MMI-20019028June 2022
OptionDescription
Units/PulseA pulse represents a user-specified number of flow units
2. Set additional required parameters.
• If you set Frequency Output Scaling Method to Frequency=Flow, set Rate Factor and Frequency
Factor.
• If you set Frequency Output Scaling Method to Pulses/Unit, define the number of pulses that will
represent one flow unit.
• If you set Frequency Output Scaling Method to Units/Pulse, define the number of units that each
pulse will indicate.
For all scaling methods, the transmitter puts out a fixed number of pulses per unit, and at the same
time, the Frequency Output signal varies in proportion to flowrate.
Calculate frequency from flow rate
The Frequency=Flow option is used to customize the Frequency Output for your application when you do not
know appropriate values for Units/Pulse or Pulses/Unit.
If you specify Frequency=Flow, you must provide values for Rate Factor and Frequency Factor:
Rate Factor
Frequency Factor
The resulting Frequency Factor must be within the range of the Frequency Output 0 to 10,000 Hz:
• If Frequency Factor is less than 1 Hz, reconfigure the receiving device for a higher pulses/unit setting.
• If Frequency Factor is greater than 10,000 Hz, reconfigure the receiving device for a lower pulses/unit
setting.
The maximum flow rate that you want the Frequency Output to report.
A value calculated as follows:
FrequencyFactor
where:
T
Factor to convert selected time base to seconds
N
Number of pulses per flow unit, as configured in the receiving device
RateFactor
T
× N
6.3.3 Configure Frequency Output Fault Action and Frequency
Frequency Output Fault Action controls the behavior of the Frequency Output if the transmitter encounters
an internal fault condition.
Note
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement the fault
action until the timeout has elapsed.
Procedure
1. Set Frequency Output Fault Action as desired.
The default value is Downscale (0 Hz).
2. If you set Frequency Output Fault Action to Upscale, set Frequency Fault Level to the desired value.
The default value is 15000 Hz. The range is 10 to 15000 Hz.
Options for Frequency Output Fault Action
Table 6-5: Options for Frequency Output Fault Action
LabelFrequency Output behavior
UpscaleGoes to configured Upscale value:
• Range: 10 Hz to 15000 Hz
• Default: 15000 Hz
Downscale0 Hz
Internal Zero0 Hz
None (default)Tracks data for the assigned process variable; no fault action
NOTICE
If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set Digital
Communications Fault Action to None. If you do not, the output will not report actual process data, and this
may result in measurement errors or unintended consequences for your process.
Restriction
If Digital Communications Fault Action is set to NAN (not a number), you cannot set mA Output Fault
Action or Frequency Output Fault Action to None. If you try to do this, the transmitter will not accept the
configuration.
74Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualIntegrate the meter with the control system
MMI-20019028June 2022
6.4 Configure the Discrete Output
The Discrete Output is used to report specific meter or process conditions. The Discrete Output parameters
control which condition is reported and how it is reported. Your transmitter may have zero or one Discrete
Output: Channel B can be configured as a Frequency Output or a Discrete Output.
Restriction
Before you can configure the Discrete Output, you must configure a channel to operate as a Discrete Output.
Important
Whenever you change a Discrete Output parameter, verify all other Discrete Output parameters before
returning the meter to service. In some situations, the transmitter automatically loads a set of stored values,
and these values may not be appropriate for your application.
Flow Switch is used to indicate that the flow rate (measured by the configured flow variable) has moved past
the configured setpoint, in either direction. The flow switch is implemented with a user-configurable
hysteresis.
Procedure
1. Set Discrete Output Source to Flow Switch, if you have not already done so.
2. Set Flow Switch Variable to the flow variable that you want to use to control the flow switch.
3. Set Flow Switch Setpoint to the value at which the flow switch will be triggered (after Hysteresis is
applied).
• If the flow rate is below this value, the Discrete Output is ON.
• If the flow rate is above this value, the Discrete Output is OFF.
4. Set Hysteresis to the percentage of variation above and below the setpoint that will operate as a
deadband.
Hysteresis defines a range around the setpoint within which the flow switch will not change. The
default is 5%. The valid range is 0.1% to 10%.
Example
If Flow Switch Setpoint = 100 g/sec and Hysteresis = 5%, and the first measured flow rate is above
100 g/sec, the Discrete Output is OFF. It will remain OFF unless the flow rate drops below 95 g/sec. If
this happens, the Discrete Output will turn ON, and remain ON until the flow rate rises above
105 g/sec. At this point it turns OFF and will remain OFF until the flow rate drops below 95 g/sec.
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→Discrete Output→DO Polarity
Discrete Outputs have two states: ON (active) and OFF (inactive). Two different voltage levels are used to
represent these states. Discrete Output Polarity controls which voltage level represents which state.
OFF-LINE MAINT → OFF-LINE CONFG → IO → CH B → DO → POLAR
Procedure
Set Discrete Output Polarity as desired.
The default setting is Active High.
76Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualIntegrate the meter with the control system
MMI-20019028June 2022
Options for Discrete Output Polarity
Polarity optionDescription
Active High• When asserted (condition tied to DO is
true), the circuit provides a pull-up to 24 V.
• When not asserted (condition tied to DO is
false), the circuit provides 0 V.
Active Low• When asserted (condition tied to DO is
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→Discrete Output→DO Fault Action
Discrete Output Fault Action controls the behavior of the Discrete Output if the transmitter encounters an
internal fault condition.
Note
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement the fault
action until the timeout has elapsed.
NOTICE
Do not use Discrete Output Fault Action as a fault indicator. If you do, you may not be able to distinguish a
fault condition from a normal operating condition. If you want to use the Discrete Output as a fault indicator,
set Discrete Output Source to Fault and set Discrete Output Fault Action to None.
Procedure
Set Discrete Output Fault Action as desired.
The default setting is None.
Related information
Fault indication with a Discrete Output
Options for Discrete Output Fault Action
Label
Upscale• Fault: Discrete Output is ON (site-specific voltage)
• No fault: Discrete Output is controlled by its assignment
Discrete Output behavior
Downscale• Fault: Discrete Output is OFF (0 V)
• No fault: Discrete Output is controlled by its assignment
Configuration and Use Manual77
Integrate the meter with the control systemConfiguration and Use Manual
June 2022MMI-20019028
LabelDiscrete Output behavior
None (default)Discrete Output is controlled by its assignment
Fault indication with a Discrete Output
To indicate faults via a Discrete Output, set Discrete Output Source to Fault. Then, if a fault occurs, the
Discrete Output is always ON and the setting of Discrete Output Fault Action is ignored.
6.5 Configure events
An event occurs when the real-time value of a user-specified process variable moves past a user-defined
setpoint. Events are used to provide notification of process changes or to perform specific transmitter actions
if a process change occurs.
A basic event is used to provide notification of process changes. A basic event occurs (is ON) if the real-time
value of a user-specified process variable moves above (HI) or below (LO) a user-defined setpoint. You can
define up to two basic events. Event status can be queried via digital communications, and a Discrete Output
can be configured to report event status.
Procedure
1. Select the event that you want to configure.
2. Specify Event Type.
Option
HIx > A
LOx < A
Description
The event occurs when the value of the assigned process variable (x) is greater
than the setpoint (Setpoint A), endpoint not included.
The event occurs when the value of the assigned process variable (x) is less than
the setpoint (Setpoint A), endpoint not included.
3. Assign a process variable to the event.
4. Set a value for Setpoint A.
5. Optional: Configure a Discrete Output to switch states in response to the event status.
78Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualIntegrate the meter with the control system
Field CommunicatorConfigure→Alert Setup→Discrete Events
An enhanced event is used to provide notification of process changes and, optionally, to perform specific
transmitter actions if the event occurs. An enhanced event occurs (is ON) if the real-time value of a userspecified process variable moves above (HI) or below (LO) a user-defined setpoint, or in range (IN) or out of
range (OUT) with respect to two user-defined setpoints. You can define up to five enhanced events.
Procedure
1. Select the event that you want to configure.
2. Specify Event Type.
OptionDescription
HIx > A
The event occurs when the value of the assigned process variable (x) is greater
than the setpoint (Setpoint A), endpoint not included.
LOx < A
The event occurs when the value of the assigned process variable (x) is less than
the setpoint (Setpoint A), endpoint not included.
INA ≤ x ≤ B
The event occurs when the value of the assigned process variable (x) is in range,
that is, between Setpoint A and Setpoint B, endpoints included.
OUTx ≤ A or x ≥ B
The event occurs when the value of the assigned process variable (x) is out ofrange, that is, less than Setpoint A or greater than Setpoint B, endpoints
included.
3. Assign a process variable to the event.
4. Set values for the required setpoints.
• For HI and LO events, set Setpoint A.
• For IN and OUT events, set Setpoint A and Setpoint B.
5. Optional: Configure a Discrete Output to switch states in response to the event status.
6. Optional: Specify the action or actions that the transmitter will perform when the event occurs.
• With the display: OFF-LINE MAINT→OFF-LINE CONFG→IO→CH C→SET DI→DI ACT
• With ProLink III: Device Tools→Configuration→I/O→Action Assignment
• With a field communicator: Configure→Alert Setup→Discrete Events→Assign Discrete Action
Configuration and Use Manual79
Integrate the meter with the control systemConfiguration and Use Manual
June 2022MMI-20019028
Options for Enhanced Event Action
ActionLabel
DisplayProLink IIIField Communicator
Standard
None (default)NONENoneNone
Start sensor zeroSTART ZEROStart Sensor ZeroPerform auto zero
Start/stop all totalizersSTART STOPStart/Stop All TotalizationStart/stop totals
Reset mass totalRESET MASSReset Mass TotalReset mass total
Reset volume totalRESET VOLReset Volume TotalReset volume total
Reset gas standard volume
total
Reset all totalsRESET ALLReset All TotalsReset totals
Meter verification
Start meter verification testSTART VERFYStart Meter VerificationNot available
Note
Before assigning actions to an enhanced event, check the status of the event. If it is ON, all assigned actions
will be performed when the new configuration is implemented. If this is not acceptable, wait until an
appropriate time to assign actions to the event.
RESET GSVTReset Gas Std Volume TotalReset gas standard volume
total
6.6 Configure digital communications
The digital communications parameters control how the transmitter will communicate using digital
communications.
Your transmitter supports the following types of digital communications:
• HART®/Bell 202 over the primary mA terminals
• HART®/RS-485 over the RS-485 terminals
• Modbus®/RS-485 over the RS-485 terminals
• Modbus® RTU via the service port
Note
The service port responds automatically to a wide range of connection requests. It is not configurable.
6.6.1 Configure HART®/Bell 202 communications
HART®/Bell 202 communications parameters support HART® communications with the transmitter's primary
mA terminals over a HART®/Bell 202 network.
Configure basic HART parameters
Display
80Micro Motion 1700 Transmitters with Analog Outputs
OFF-LINE MAINT → OFF-LINE CONFG → COMM
Configuration and Use ManualIntegrate the meter with the control system
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→Communications→HART Communications
Basic HART parameters include the HART address, HART tags, and the operation of the primary mA Output.
HART/Bell 202 communications parameters support HART communication with the transmitter's primary mA
terminals over a HART/Bell 202 network. The HART/Bell 202 communications parameters include:
• HART Address (Polling Address)
• mA Output Action
• Burst Parameters (optional)
• HART Variables (optional)
Procedure
1. Set HART Address to a value that is unique on your network.
• Default: 0
• Range: 0 to 15
Tip
• The default address is typically used unless you are in a multidrop environment.
• Devices using HART protocol to communicate with the transmitter may use either HART Address or
HART Tag (Software Tag) to identify the transmitter. Configure either or both, as required by your
other HART devices.
2. Ensure that mA Output Action is configured appropriately.
Option
Description
Enabled (Live)The primary mA Output reports process data as configured.
Disabled (Fixed)The primary mA Output is fixed at 4 mA and does not report process data.
Important
If you use ProLink III to set HART Address to 0, the program automatically enables mA Output Action.
If you use ProLink III to set HART Address to any other value, the program automatically disables mAOutput Action. This is designed to make it easier to configure the transmitter for legacy behavior.
Always verify mA Output Action after setting HART Address.
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→Communications→Set Up Burst Mode
Not available
Configuration and Use Manual81
Integrate the meter with the control systemConfiguration and Use Manual
June 2022MMI-20019028
Burst mode is a mode of communication during which the transmitter regularly broadcasts HART digital
information over the mA Output. The burst parameters control the information that is broadcast when burst
mode is enabled.
Tip
In typical installations, burst mode is disabled. Enable burst mode only if you are using a HART Triloop.
Procedure
1. Enable Burst Mode.
2. Set Burst Mode Output as desired.
LabelDescription
ProLink IIIField Communicator
Source (Primary Variable)PVThe transmitter sends the primary variable (PV) in the
configured measurement units in each burst (e.g.,
14.0 g/sec, 13.5 g/sec, 12.0 g/sec.
Primary Variable (Percent
Range/Current)
Process Variables/CurrentProcess variables/currentThe transmitter sends PV, SV, TV, and QV values in
Transmitter variablesFld dev varThe transmitter sends four user-specified process variables
% range/currentThe transmitter sends the PV’s percent of range and the
PV’s actual mA level in each burst (e.g., 25%, 11.0 mA.
measurement units and the PV’s actual milliamp reading in
each burst (e.g., 50 g/sec, 23 °C, 50 g/sec, 0.0023 g/cm3,
11.8 mA.
in each burst.
3. Ensure that the burst output variables are set appropriately.
• If you set Burst Mode Output to send four user-specified variables, set the four process variables to
be sent in each burst.
• If you set Burst Mode Output to any other option, ensure that the HART variables are set as desired.
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→Variable Mapping
The HART variables are a set of four variables predefined for HART use. The HART variables include the
Primary Variable (PV), Secondary Variable (SV), Tertiary Variable (TV), and Quaternary Variable (QV). You can
assign specific process variables to the HART variables, and then use standard HART methods to read or
broadcast the assigned process data.
Not available
Restriction
The TV is automatically set to match the PV and cannot be configured independently.
Tip
The Tertiary Variable and Quaternary Variable are also called the Third Variable (TV) and Fourth Variable (FV).
82Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualIntegrate the meter with the control system
MMI-20019028June 2022
Options for HART variables
Table 6-6: Standard HART process variables
Process variablePrimary
Variable (PV)
Gas Standard Volume Flow Rate✓✓✓✓
Gas Standard Volume Inventory✓
Gas Standard Volume Total✓
Line (Gross) Volume Flow Rate✓✓✓✓
Line (Gross) Volume Inventory✓
Line (Gross) Volume Total✓
Mass Flow Rate✓✓✓✓
Mass Inventory✓
Mass Total✓
Secondary
Variable (SV)
Third Variable
(TV)
Table 6-7: PVR-only HART process variables
Process variablePrimary
Variable (PV)
Corrected Oil Flow✓✓✓
Corrected Oil Total✓
Corrected Water Cut✓
Secondary
Variable (SV)
Third Variable
(TV)
Fourth
Variable (QV )
Fourth
Variable (QV )
Corrected Water Flow✓✓✓
Corrected Water Total✓
Density of Oil @ Line Fixd degAPI✓
Density of Oil @ Line Fixd SGU✓
Oil Total @ Line✓
Shrinkage Factor Corrected Oil Flow @ 60 °F✓✓✓
Shrinkage Factor Corrected Oil Flow @ Line✓✓✓
Shrinkage Factor Corrected Oil Total @ 60 °F✓
Shrinkage Factor Corrected Oil Total @ Line✓
Shrinkage Factor Corrected Total of Mix @ 60 °F✓
Shrinkage Factor Corrected Volume Of Mix @ 60 °F ✓✓✓
Uncorrected Oil Flow✓✓✓
Uncorrected Water Cut✓
Uncorrected Water Flow✓✓✓
Volume Flow of Mix at Line✓✓✓
Volume Total Of Mix @ Line✓
Configuration and Use Manual83
Integrate the meter with the control systemConfiguration and Use Manual
June 2022MMI-20019028
Table 6-7: PVR-only HART process variables (continued)
Process variablePrimary
Variable (PV)
Water Total @ Line✓
Secondary
Variable (SV)
Third Variable
(TV)
Table 6-8: TMR-only HART process variables
Process variablePrimary
Variable (PV)
Remediated Mass Flow✓✓✓
Remediated Mass Total✓
Remediated Mass Inventory✓
Secondary
Variable (SV)
Third Variable
(TV)
Table 6-9: PVR- and TBR-only HART process variables
Process variablePrimary
Variable (PV)
Unremediated Density✓
Secondary
Variable (SV)
Third Variable
(TV)
Table 6-10: PVR, TBR, and TMR HART process variables
Process variablePrimary
Variable (PV)
Total Remediated Time✓
Secondary
Variable (SV)
Third Variable
(TV)
Fourth
Variable (QV )
Fourth
Variable (QV )
Fourth
Variable (QV )
Fourth
Variable (QV )
Interaction of HART variables and transmitter outputs
The HART variables are automatically reported through specific transmitter outputs. They may also be
reported through HART burst mode, if enabled on your transmitter.
Table 6-11: HART variables and transmitter outputs
HART variableReported viaComments
Primary Variable (PV)Primary mA outputIf one assignment is changed, the other is changed
automatically, and vice versa.
Secondary Variable (SV)Not associated with an
output
Tertiary Variable (TV)Frequency Output (if
present on your transmitter)
Quaternary Variable (QV)Not associated with an
output
The SV must be configured directly, and the value of the SV
is available only via digital communications.
If one assignment is changed, the other is changed
automatically, and vice versa. If your transmitter does not
have a Frequency Output, the TV must be configured
directly, and the value of the TV is available only via digital
communications.
The QV must be configured directly, and the value of the
QV is available only via digital communications.
6.6.2 Configure HART®/RS-485 communications
Display
OFF-LINE MAINT → OFF-LINE CONFG → COMM
84Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualIntegrate the meter with the control system
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→Communications→HART Communications
HART/RS-485 communications parameters support HART communication with the transmitter's RS-485
terminals.
HART/RS-485 communication parameters include:
• Protocol
• HART Address (Polling Address)
• Parity, Stop Bits, and Baud Rate
Restriction
The transmitter uses the same RS-485 terminals for HART/RS-485, Modbus® RTU, and Modbus ASCII
communications. All RS-485 connection requests must use the same protocol and connection parameters
that are configured in the transmitter.
Procedure
1. Set Protocol to HART RS-485.
2. Set Baud Rate to match the baud rate that will be used by your HART master.
3. Set Parity to match the parity that will be used by your HART master.
4. Set Stop Bits to match the stop bits setting that will be used by your HART master.
5. Set HART Address to a unique value on your network.
Valid address values are between 0 and 15. The default address (0) is typically used unless you are in a
multidrop environment.
Tip
Devices using HART protocol to communicate with the transmitter may use either HART Address or
HART Tag (Software Tag) to identify the transmitter. Configure either or both, as required by your
Field CommunicatorConfigure→Manual Setup→Inputs/Outputs→Communications→Set Up RS-485 Port
Modbus/RS-485 communications parameters control Modbus communication with the transmitter's RS-485
terminals.
OFF-LINE MAINT → OFF-LINE CONFG → COMM
Procedure
1. Set Disable Modbus ASCII as desired.
Support for Modbus ASCII limits the set of addresses that are available for the transmitter's Modbus
address.
Configuration and Use Manual85
Integrate the meter with the control systemConfiguration and Use Manual
June 2022MMI-20019028
Modbus ASCII supportAvailable Modbus addresses
Disabled1–127, excluding 111 (111 is reserved to the service port)
Enabled1–15, 32–47, 64–79, and 96–110
2. Set Protocol to match the protocol used by your Modbus/RS-485 host.
OptionDescription
Modbus RTU (default)8–bit communications
Modbus ASCII7–bit communications
If support for Modbus ASCII is disabled, you must use Modbus RTU.
3. Set Modbus Address to a unique value on the network.
4. Set Parity, Stop Bits, and Baud Rate as appropriate for your network.
5. Set Floating-Point Byte Order to match the byte order used by your Modbus host.
CodeByte order
01–2 3–4
13–4 1–2
22–1 4–3
34–3 2–1
See the following table for the bit structure of bytes 1 through 4.
Table 6-12: Bit structure of floating-point bytes
ByteBitsDefinition
1SEEEEEEES=Sign
E=Exponent
2EMMMMMMME=Exponent
M=Mantissa
3MMMMMMMMM=Mantissa
4MMMMMMMMM=Mantissa
6. (Optional) Set Additional Communications Response Delay in delay units.
A delay unit is 2/3 of the time required to transmit one character, as calculated for the port currently in
use and the character transmission parameters. Valid values range from 1 to 255.
Additional Communications Response Delay is used to synchronize Modbus communications with
hosts that operate at a slower speed than the transmitter. The value specified here will be added to
each response the transmitter sends to the host.
86Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualIntegrate the meter with the control system
MMI-20019028June 2022
Tip
Do not set Additional Communications Response Delay unless required by your Modbus host.
6.6.4 Configure Digital Communications Fault Action
Field CommunicatorConfigure→Alert Setup→I/O Fault Actions→Comm Fault Action
Digital Communications Fault Action specifies the values that will be reported via digital communications if
the device encounters an internal fault condition.
Procedure
Set Digital Communications Fault Action as desired.
The default setting is None.
Restriction
• If mA Output Fault Action or Frequency Output Fault Action is set to None, Digital Communications
Fault Action should also be set to None. If you do not, the output will not report actual process data, and
this may result in measurement errors or unintended consequences for your process.
• If you set Digital Communications Fault Action to NAN, you cannot set mA Output Fault Action or
Frequency Output Fault Action to None. If you try to do this, the transmitter will not accept the
configuration.
Options for Digital Communications Fault Action
Label
ProLink IIIField Communicator
UpscaleUpscale• Process variable values indicate that the value is greater
DownscaleDownscale• Process variable values indicate that the value is lower
ZeroIntZero-All 0• Flow rate variables go to the value that represents a
Description
than the upper sensor limit.
• Totalizers stop incrementing.
than the lower sensor limit.
• Totalizers stop incrementing.
flow rate of 0 (zero).
• Density is reported as 0.
• Temperature is reported as 0 °C , or the equivalent if
other units are used (e.g., 32 °F .
• Drive gain is reported as measured.
• Totalizers stop incrementing.
Configuration and Use Manual87
Integrate the meter with the control systemConfiguration and Use Manual
June 2022MMI-20019028
LabelDescription
ProLink IIIField Communicator
Not a NumberNot-a-Number• Process variables are reported as IEEE NAN.
• Drive gain is reported as measured.
• Modbus® scaled integers are reported as Max Int.
• Totalizers stop incrementing.
Flow to ZeroIntZero-Flow 0• Flow rates are reported as 0.
• Other process variables are reported as measured.
• Totalizers stop incrementing.
NoneNone (default)• All process variables are reported as measured.
• Totalizers increment if they are running.
NOTICE
If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set Digital
Communications Fault Action to None. If you do not, the output will not report actual process data, and this
may result in measurement errors or unintended consequences for your process.
Restriction
If Digital Communications Fault Action is set to NAN (not a number), you cannot set mA Output Fault
Action or Frequency Output Fault Action to None. If you try to do this, the transmitter will not accept the
configuration.
88Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualComplete the configuration
MMI-20019028June 2022
7 Complete the configuration
7.1 Test or tune the system using sensor simulation
Use sensor simulation to test the system's response to a variety of process conditions, including boundary
conditions, problem conditions, or alert conditions, or to tune the loop.
Prerequisites
Before enabling sensor simulation, ensure that your process can tolerate the effects of the simulated process
values.
Restriction
Sensor simulation is available only on flow meters with the enhanced core processor.
Field CommunicatorService Tools→Simulate→Simulate Sensor
2. Enable sensor simulation.
3. For mass flow, set Wave Form as desired and enter the required values.
Option
FixedFixed Value
SawtoothPeriod
SinePeriod
4. For density, set Wave Form as desired and enter the required values.
Required values
Minimum
Maximum
Minimum
Maximum
Option
FixedFixed Value
SawtoothPeriod
Configuration and Use Manual89
Required values
Minimum
Maximum
Complete the configurationConfiguration and Use Manual
June 2022MMI-20019028
OptionRequired values
SinePeriod
Minimum
Maximum
5. For temperature, set Wave Form as desired and enter the required values.
OptionRequired values
FixedFixed Value
SawtoothPeriod
Minimum
Maximum
SinePeriod
Minimum
Maximum
6. Observe the system response to the simulated values and make any appropriate changes to the
transmitter configuration or to the system.
7. Modify the simulated values and repeat.
8. When you have finished testing or tuning, disable sensor simulation.
7.1.1 Sensor simulation
Sensor simulation allows you to test the system or tune the loop without having to create the test conditions
in your process. When sensor simulation is enabled, the transmitter reports the simulated values for mass
flow, density, and temperature, and takes all appropriate actions. For example, the transmitter might apply a
cutoff, activate an event, or post an alert.
When sensor simulation is enabled, the simulated values are stored in the same memory locations used for
process data from the sensor. The simulated values are then used throughout transmitter functioning. For
example, sensor simulation will affect:
• All mass flow rate, temperature, and density values displayed or reported via outputs or digital
communications
• The mass total and mass inventory values
• All volume calculations and data, including reported values, volume totals, and volume inventories
• All mass, temperature, density, or volume values logged to Data Logger
Sensor simulation does not affect any diagnostic values.
Unlike actual mass flow rate and density values, the simulated values are not temperature-compensated
(adjusted for the effect of temperature on the sensor’s flow tubes).
90Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualComplete the configuration
MMI-20019028June 2022
7.2 Back up transmitter configuration
ProLink III provides a configuration upload/download function which allows you to save configuration sets to
your PC. This allows you to back up and restore your transmitter configuration. This is also a convenient way
to replicate a configuration across multiple devices.
Restriction
This function is not available with any other communications tools.
Procedure
To back up the transmitter configuration using ProLink III:
a) Choose Device Tools→Configuration Transfer→Save or Load Configuration Data.
b) In the Configuration group box, select the configuration data you want to save.
c) Click Save, then specify a file name and location on your computer.
d) Click Start Save.
The backup file is saved to the specified name and location. It is saved as a text file and can be read using any
text editor.
Field CommunicatorConfigure→Manual Setup→Info Parameters→Transmitter Info→Write Protect
If the transmitter is write-protected, the configuration is locked and nobody can change it until it is unlocked.
This prevents accidental or unauthorized changes to the transmitter configuration parameters.
OFF-LINE MAINT → CONFIG → LOCK
Configuration and Use Manual91
Complete the configurationConfiguration and Use Manual
June 2022MMI-20019028
92Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualTransmitter operation
MMI-20019028June 2022
8 Transmitter operation
8.1 Record the process variables
Micro Motion suggests that you make a record of specific process variable measurements, including the
acceptable range of measurements, under normal operating conditions. This data will help you recognize
when the process or diagnostic variables are unusually high or low, and may help you diagnose and
troubleshoot application issues.
Procedure
Record the following process and diagnostic variables, under normal operating conditions.
Measurement
Variable
Flow rate
Density
Temperature
Tube frequency
Pickoff voltage
Drive gain
Typical averageTypical highTypical low
8.2 View process variables
Display
ProLink IIIView the desired variable on the main screen under Process Variables. See View process variables and other
Field CommunicatorOverview→Shortcuts→Variables→Process Variables
Process variables provide information about the state of the process fluid, such as flow rate, density, and
temperature, as well as running totals. Process variables can also provide data about flowmeter operation,
such as drive gain and pickoff voltage. This information can be used to understand and troubleshoot your
process.
Scroll to the desired process variable. If AutoScroll is enabled, you can wait until the process variable is
displayed. See View process variables using the display for more information.
data using ProLink III for more information.
8.2.1 View process variables using the display
Procedure
View the desired process variables.
The display shows the configured display variables. For each display variable, the display reports the
abbreviated name of the process variable (for example, DENS for density), the current value of that process
variable, and the associated unit of measure (for example, G/CM3).
Configuration and Use Manual93
A
B
C
D
E
F
G
H
Transmitter operationConfiguration and Use Manual
June 2022MMI-20019028
If Auto Scroll is enabled, the display cycles through the display variables, showing each display variable for a
user-specified number of seconds. Whether or not Auto Scroll is enabled, you can activate Select to move to
the next display variable.
Figure 8-1: Transmitter display features
A. Status LED
B. Display (LCD panel)
C. Process variable
D. Scroll optical switch
E. Optical switch indicator: turns red when either Scroll or Select is activated
F. Select optical switch
G. Unit of measure for process variable
H. Current value of process variable
8.2.2 View process variables and other data using ProLink III
Monitor process variables, diagnostic variables, and other data to maintain process quality.
ProLink III automatically displays process variables, diagnostic variables, and other data on the main screen.
Tip
ProLink III allows you to choose the process variables that appear on the main screen. You can also choose
whether to view data in Analog Gauge view or digital view, and you can customize the gauge settings. For
more information, see the Prolink III user manual.
94Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualTransmitter operation
MMI-20019028June 2022
8.2.3 View process variables using the Field Communicator
Monitor process variables to maintain process quality.
Procedure
• To view current values of basic process variables, choose Overview.
• To view a more complete set of process variables, plus the current state of the outputs, choose Service
Tools→Variables.
8.3 View transmitter status using the status LED
The status LED shows the current alert condition of the transmitter. The status LED is located on the face of
the transmitter.
Procedure
Observe the status LED.
• If your transmitter has a display, you can view the status LED with the transmitter housing cover in place.
• If your transmitter does not have a display, it does not have a status LED. This option is not available.
To interpret the status LED, see the following table.
Restriction
If LED Blinking is disabled, the status LED will flash only during calibration. It will not flash to indicate an
unacknowledged alarm.
LED state
Solid greenNo alerts are active.Continue with configuration or process
Flashing green (if
enabled)
Solid yellowOne or more low-severity alerts are active.
Flashing yellow (if
enabled)
DescriptionRecommendation
measurement.
Unacknowledged corrected condition (no
alert)
A low severity alarm can mean one or more
process variables is at a set output level (i.e.
simulation or two phase timeout).
Calibration in progress, or Known Density
Verification in progress.
One or more low-severity alerts are active and
have not been acknowledged.
Continue with configuration or process
measurement. Acknowledge the alert if you
choose.
A low-severity alert condition does not affect
measurement accuracy or output behavior.
You can continue with configuration or
process measurement, but Micro Motion still
recommends identifying and resolving the
alert condition.
A low-severity alert condition does not affect
measurement accuracy or output behavior.
You can continue with configuration or
process measurement, but Micro Motion still
recommends identifying and resolving the
alert condition.
Solid redOne or more high-severity alerts are active.A high-severity alert condition affects
measurement accuracy and output behavior.
Resolve the alert condition before continuing.
Configuration and Use Manual95
Transmitter operationConfiguration and Use Manual
June 2022MMI-20019028
LED stateDescriptionRecommendation
Flashing red (if
enabled)
One or more high-severity alerts are active
and have not been acknowledged.
A high-severity alert condition affects
measurement accuracy and output behavior.
Resolve the alert condition before continuing.
Acknowledge the alert if you choose.
8.4 View and acknowledge status alerts
The transmitter posts status alerts whenever a process variable exceeds its defined limits or the transmitter
detects a fault condition. You can view active alerts, and you can acknowledge alerts. Acknowledging alerts is
not required.
8.4.1 View and acknowledge alerts using the display
You can view a list containing all alerts that are active, or inactive but unacknowledged. From this list, you can
acknowledge individual alerts.
Prerequisites
Operator access to the alert menu must be enabled (default setting). If operator access to the alert menu is
disabled, you must use another method to view or acknowledge status alerts.
Note
Only Fault and Informational alerts are listed. The transmitter automatically filters out alerts with Status Alert
Severity set to Ignore.
Procedure
See Figure 8-2.
96Micro Motion 1700 Transmitters with Analog Outputs
SEE ALERT
Select
Is ACK ALL enabled?
Scroll and Select
simultaneously for 4 seconds
Yes
ACK ALL
NoNoYes
SelectScroll
EXIT
SelectScroll
Active/
unacknowledged
alarms?
YesNo
Alert codeNO ALERT
ScrollScrollSelect
ACKEXIT
YesNo
SelectScroll
Configuration and Use ManualTransmitter operation
MMI-20019028June 2022
Figure 8-2: Using the display to view and acknowledge the status alerts (alarms)
Configuration and Use Manual97
Transmitter operationConfiguration and Use Manual
June 2022MMI-20019028
Postrequisites
• To clear the following alerts, you must correct the problem, acknowledge the alert, then power-cycle the
• For all other alerts:
— If the alert is inactive when it is acknowledged, it will be removed from the list.
— If the alert is active when it is acknowledged, it will be removed from the list when the alert condition
clears.
Related information
Alert data in transmitter memory
8.4.2 View and acknowledge alerts using ProLink III
You can view a list containing all alerts that are active, or inactive but unacknowledged. From this list, you can
acknowledge individual alerts or choose to acknowledge all alerts at once.
Procedure
1. View alerts on the ProLink III Device Tools→Alerts tab.
All active or unacknowledged alerts are listed, and displayed according to the following categories:
CategoryDescription
Failed: Fix NowA meter failure has occurred and must be addressed immediately.
Maintenance: Fix SoonA condition has occurred that can be fixed at a later time.
Advisory: InformationalA condition has occurred, but requires no maintenance from you.
Notes
• All fault alerts are displayed in the Failed: Fix Now category.
• All information alerts are displayed in either the Maintenance: Fix Soon category or the Advisory:
Informational category. The category assignment is hard-coded.
• The transmitter automatically filters out alerts with Alert Severity set to Ignore.
2. To acknowledge a single alert, check the Ack checkbox for that alert. To acknowledge all alerts at once,
click Ack All.
Postrequisites
• To clear the following alerts, you must correct the problem, acknowledge the alert, then power-cycle the
• For all other alerts:
— If the alert is inactive when it is acknowledged, it will be removed from the list.
— If the alert is active when it is acknowledged, it will be removed from the list when the alert condition
clears.
98Micro Motion 1700 Transmitters with Analog Outputs
Configuration and Use ManualTransmitter operation
MMI-20019028June 2022
Related information
Alert data in transmitter memory
8.4.3 View alerts using the Field Communicator
You can view a list containing all alerts that are active, or inactive but unacknowledged.
Procedure
• To view active or unacknowledged alerts, choose Service Tools→Alerts.
All active alerts and unacknowledged alerts are listed.
Note
Only Fault and Informational alerts are listed. The transmitter automatically filters out alerts with Status
Alert Severity set to Ignore.
• To refresh the list, choose Service Tools → Alerts → Refresh Alerts.
Related information
Alert data in transmitter memory
8.5 Read totalizer and inventory values
Display
ProLink IIIView the desired variable on the main screen under Process Variables.
Field CommunicatorService Tools→Variables→Totalizer Control
Totalizers keep track of the total amount of mass or volume measured by the transmitter since the last
totalizer reset. Inventories keep track of the total amount of mass or volume measured by the transmitter
since the last inventory reset.
Tip
You can use the inventories to keep a running total of mass or volume across multiple totalizer resets.
To read a totalizer or inventory value from the display, it must be configured as a display variable.
8.6 Start and stop totalizers and inventories
Display
ProLink IIIDevice Tools→Totalizer Control→Totalizer and Inventories→Start All Totals
Field CommunicatorService Tools→Variables→Totalizer Control→All Totalizers→Start Totalizers
See Start and stop totalizers and inventories using the display .
Device Tools → Totalizer Control → Totalizer and Inventories → Stop All Totals
Service Tools → Variables → Totalizer Control → All Totalizers → Stop Totalizers
Configuration and Use Manual99
Transmitter operationConfiguration and Use Manual
June 2022MMI-20019028
When you start a totalizer, it tracks process measurement. In a typical application, its value increases with
flow. When you stop a totalizer, it stops tracking process measurement and its value does not change with
flow. Inventories are started and stopped automatically, when totalizers are started and stopped.
Important
Totalizers and inventories are started or stopped as a group. When you start any totalizer, all other totalizers
and all inventories are started simultaneously. When you stop any totalizer, all other totalizers and all
inventories are stopped simultaneously. You cannot start or stop inventories directly.
8.6.1 Start and stop totalizers and inventories using the display
Prerequisites
• The Totalizer Start/Stop display function must be enabled.
• At least one totalizer must be configured as a display variable.
Procedure
• To start all totalizers and inventories using the display:
Note
If the PLC is connected and communicating, the start/stop and reset totalizers commands might be
overriding any totalizer commands from the local display or from ProLink III.
a) Scroll until the word TOTAL appears in the lower left corner of the display.
Important
Because all totalizers are started or stopped together, it does not matter which total you use.
b) Select.
c) Scroll until START appears beneath the current totalizer value.
Exit displays beneath the current totalizer value.
d) Select.
e) Select again to confirm.
f) Scroll to EXIT.
• To stop all totalizers and inventories using the display:
a) Scroll until the word TOTAL appears in the lower left corner of the display.
Important
Because all totalizers are started or stopped together, it does not matter which total you use.
b) Select.
c) Scroll until STOP appears beneath the current totalizer value.
d) Select.
e) Select again to confirm.
f) Scroll to EXIT.
100Micro Motion 1700 Transmitters with Analog Outputs
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.