Micro Motion Micro Motion High Pressure Coriolis Flow Meters Installation Manual

Page 1
Installation Manual
MMI- 20032352, Rev AD
March 2020
Micro Motion™ High Pressure Coriolis Flow Meters
Page 2
Safety messages
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. and Ireland 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 704 136
Mexico +52 55 5809 5300 France +33 (0) 800 917
Argentina +54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy +39 8008 77334 China +86 21 2892 9000
Chile +56 2 2928 4800 Central & Eastern +41 (0) 41 7686
Peru +51 15190130 Russia/CIS +7 495 995 9559 South Korea +82 2 3438 4600
Europe and Middle East Asia Pacific
New Zealand 099 128 804
666
India 800 440 1468
901
Japan +81 3 5769 6803
111
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
2
Page 3
Installation Manual Contents
MMI- 20032352 March 2020

Contents

Chapter 1 Before you begin............................................................................................................ 5
1.1 About this document........................................................................................................................5
1.2 Hazard messages..............................................................................................................................5
1.3 Related documentation....................................................................................................................5
Chapter 2 Planning........................................................................................................................ 7
2.1 Installation checklist.........................................................................................................................7
2.2 Best practices................................................................................................................................... 8
2.3 HPC010 vibration limits — vibration broadband random...................................................................8
2.4 HPC015 vibration limits....................................................................................................................8
2.5 Temperature limits...........................................................................................................................9
Chapter 3 Mounting.....................................................................................................................11
3.1 Mount the HPC010 sensor..............................................................................................................11
3.2 Mount the HPC015 sensor..............................................................................................................12
3.3 Mount the enhanced core processor ..............................................................................................13
3.4 Mount the I.S. barrier .....................................................................................................................14
3.5 Attach extended electronics...........................................................................................................15
Chapter 4 Transmitter power and I/O wiring................................................................................ 17
4.1 Options for wiring...........................................................................................................................17
4.2 Connect 4-wire cable......................................................................................................................17
4.3 Connect 9-wire cable......................................................................................................................22
Chapter 5 Grounding....................................................................................................................25
Chapter 6 Purge the sensor case .................................................................................................. 27
Chapter 7 Pressure relief.............................................................................................................. 29
Installation Manual iii
Page 4
Contents Installation Manual
March 2020 MMI- 20032352
iv Micro Motion HPC
Page 5
Installation Manual Before you begin
MMI- 20032352 March 2020

1 Before you begin

1.1 About this document

This document provides information on planning, mounting, wiring, and grounding the HPC sensor.
The information in this document assumes that users understand basic transmitter and sensor installation, configuration, and maintenance concepts and procedures.

1.2 Hazard messages

This document uses the following criteria for hazard messages based on ANSI standards Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access to protect users' assets. This is true for all systems used within the facility.

1.3 Related documentation

You can find all product documentation on the product documentation DVD shipped with the product or at www.emerson.com.
See any of the following documents for more information:
The hazardous area approvals documentation shipped with the sensor or available at
www.emerson.com/flowmeasurement.
Micro Motion High Pressure Coriolis Flow Meters Product Data Sheet
Installation Manual 5
Page 6
Before you begin Installation Manual
March 2020 MMI- 20032352
Micro Motion 9-Wire Flowmeter Cable Preparation and Installation Guide
The transmitter installation and configuration and use guides
6 Micro Motion HPC
Page 7
Installation Manual Planning
MMI- 20032352 March 2020

2 Planning

2.1 Installation checklist

If you plan to mount the meter in a hazardous area:
WARNING
Make sure that the hazardous area specified on the approval tag is suitable for the environment in which the meter will be installed.
Verify that the local ambient and process temperatures are within the limits of the
meter.
If the sensor has an integral transmitter, no wiring is required between the sensor and
transmitter. Follow the wiring instructions in the transmitter installation manual for signal and power wiring.
If the transmitter has remote-mounted electronics, follow the instructions in this
manual for wiring between the sensor and the transmitter, and then follow the instructions in the transmitter installation manual for power and signal wiring.
For optimal performance, install the sensor in the preferred orientation. The sensor will
work in any orientation as long as the flow tubes remain full of process fluid.
Table 2-1: Preferred sensor orientation
Process content HPC010 HPC015
Liquids
Self-draining applications
Gases
Installation Manual 7
Page 8
Planning Installation Manual
March 2020 MMI- 20032352
Orient the sensor so that personnel and equipment will not be exposed to escaping
pressurized discharge from the rupture disk. The sensor has a rupture disk to evacuate the case in the unlikely event of a loss of primary containment.
Install the meter so that the flow direction arrow on the sensor case matches the actual
forward flow of the process. (Flow direction is also software-selectable.)

2.2 Best practices

The following information can help you get the most from your sensor.
There are no pipe run requirements for Micro Motion sensors. Straight runs of pipe
upstream or downstream are unnecessary.
If the sensor is installed in a vertical pipeline, liquids and slurries should flow upward
through the sensor. Gases should flow downward.
Keep the sensor full of process fluid.
For halting flow through the sensor with a single valve, install the valve downstream
from the sensor.
Minimize bending and torsional piping loads on the meter. Do not use the meter to
align misaligned piping.
The sensor does not require external supports. The flanges will support the sensor in
any orientation.

2.3 HPC010 vibration limits — vibration broadband random

5 to 1,000 Hz; 1.25E-4 g2/Hz per IEC 60068-2-64
Total: 0.35g RMS
Vibration isolation should be used in installations above 0.35 g RMS or for applications requiring Lloyd’s approval.
Vibration isolation clamps are available as a spare part. For more information about mounting a sensor in high vibration environments, contact customer support.

2.4 HPC015 vibration limits

Meets IEC 60068-2-6, endurance sweep, 5 to 2000 Hz up to 1.0 g.
8 Micro Motion HPC
Page 9
Installation Manual Planning
MMI- 20032352 March 2020

2.5 Temperature limits

Model Component Limit
HPC010 Process fluid temperature -58 °F (-50 °C) to 257 °F
(125.0 °C)
Ambient temperature -40 °F (-40.0 °C) to 140 °F
(60.0 °C)
HPC015 Process fluid temperature -50.8 °F (-46 °C) to 392 °F
(200 °C)
Ambient temperature -40 °F (-40.0 °C) to 140 °F
(60 °C)
Notes
In all cases, the electronics cannot be operated where the ambient temperature is
below -40 °F (-40.0 °C) or above 140 °F (60.0 °C). If a sensor is to be used where the ambient temperature is outside of the range permissible for the electronics, the electronics must be remotely located where the ambient temperature is within the permissible range, as indicated by the shaded area of the temperature limit graphs.
Temperature limits may be further restricted by hazardous area approvals. Refer to the
hazardous area approvals documentation shipped with the sensor or available from
www.emerson.com/flowmeasurement.
Installation Manual 9
Page 10
Planning Installation Manual
March 2020 MMI- 20032352
10 Micro Motion HPC
Page 11
Installation Manual Mounting
MMI- 20032352 March 2020

3 Mounting

3.1 Mount the HPC010 sensor

Use your common practices to minimize torque and bending load on process connections.
Tip
To reduce the risk of condensation problems, do not orient transmitters or sensor junction boxes with their conduit openings pointing upward.
NOTICE
Lifting the sensor by the electronics or rupture disk can damage the device.
Figure 3-1: Mounting the HPC010 sensor
A. Optional: Use the sensor grooves for mounting the sensor.
Notes
Do not use the sensor to support the piping.
The sensor does not require external supports. The flanges will support the sensor in
any orientation.
Installation Manual 11
Page 12
Mounting Installation Manual
March 2020 MMI- 20032352

3.2 Mount the HPC015 sensor

Procedure
1. Mount the sensor.
2. Optional: Use a bracket to mount the HPC015 sensor to a wall.
12 Micro Motion HPC
Page 13
Installation Manual Mounting
MMI- 20032352 March 2020

3.3 Mount the enhanced core processor

Procedure
1. If desired, reorient the core processor housing on the bracket. a) Loosen each of the four cap screws.
b) Rotate the bracket so that the core processor is oriented as desired.
c) Tighten the cap screws, torquing to 2.2 ft lbf (3 N m) to 3 ft lbf (4 N m).
2. Attach the mounting bracket to an instrument pole or wall. For pipe mount, two
user-supplied U-bolts are required.
Figure 3-2: Pipe mount
Installation Manual 13
Page 14
Mounting Installation Manual
March 2020 MMI- 20032352
Figure 3-3: Wall mount

3.4 Mount the I.S. barrier

Use this procedure if you are mounting an MVD™ Direct Connect™ I.S. barrier.
Procedure
1. Snap the barrier onto a 1.38 in (35 mm) DIN rail. You can mount it in either
direction. To remove the barrier from the rail, lift the bottom lock.
2. Hook one end of the end clamp over the DIN rail.
3. Position the end clamp snugly against the barrier.
4. Tighten the screw until the end clamp is securely fastened to the DIN rail.
5. Close the cover and fasten the clamps.
Figure 3-4: Barrier mount on DIN rail
14 Micro Motion HPC
Page 15
E
D
C
A
B
F
Installation Manual
Mounting
MMI- 20032352 March 2020

3.5 Attach extended electronics

If your installation has a sensor with extended electronics, you will need to install the extender onto the sensor case.
Extended core processors are matched at the factory to specific sensors. Keep each core processor together with the sensor with which it was shipped.
NOTICE
Keep the extender and feedthrough clean and dry. Moisture or debris in the extender or feedthrough can damage electronics and result in measurement error or flowmeter failure.
Procedure
1. Remove and recycle the plastic cap from the feedthrough on the sensor.
A. Transmitter or core processor B. Extender C. O-ring
D. Feedthrough
E. Clamping ring F. Clamping screw
2. Loosen the clamping screw and remove the clamping ring. Leave the O-ring in place
on the feedthrough.
3. Remove and recycle the plastic plug from the extender.
4. Fit the extender onto the feedthrough by carefully aligning the notches on the
Installation Manual 15
bottom of the extender with the notches on the feedthrough.
5. Close the clamping ring and tighten the clamping screw to 13 in lbf (1.47 N m) to
18 in lbf (2.03 N m).
Page 16
Mounting Installation Manual
March 2020 MMI- 20032352
16 Micro Motion HPC
Page 17
Installation Manual Transmitter power and I/O wiring
MMI- 20032352 March 2020

4 Transmitter power and I/O wiring

4.1 Options for wiring

The wiring procedure you follow depends on which electronics option you have.
Table 4-1: Wiring procedures by electronics option
Electronics option Wiring procedure
Integral transmitter The transmitter is already connected to the sensor. No wiring is
required between sensor and transmitter. See the transmitter installation manual for wiring the power and signal cable to the transmitter.
Extended electronics The electronics are separated from the sensor by an extender and
must be attached as described in Attach extended electronics. There is no wiring required because the physical connection includes the electrical connection.
MVD™ Direct Connect
There is no transmitter to wire. See the Micro Motion MVD Direct Connect Meters manual for wiring the power and signal cable between the sensor and the direct host. Refer to Connect power
to the I.S. barrier.
Integral core processor with remote transmitter
WARNING
Make sure the hazardous area specified on the sensor approval tag is suitable for the environment in which the sensor will be installed. Failure to comply with the requirements for intrinsic safety in a hazardous area could result in an explosion resulting in injury or death.
NOTICE
Fully close and tighten all housing covers and conduit openings. Improperly sealed housings can expose electronics to moisture, which can cause measurement error or flowmeter failure. Inspect and grease all gaskets and O-rings.
The core processor is already connected to the sensor. Connect a 4-wire cable between the core processor and transmitter. Refer to Connect the wires to the core processor terminals.

4.2 Connect 4-wire cable

4.2.1 4-wire cable types and usage

Micro Motion offers two types of 4-wire cable: shielded and armored. Both types contain shield drain wires.
The cable supplied by Micro Motion consists of one pair of red and black 18 AWG (0.823 mm²) wires for the VDC connection, and one pair of white and green 22 AWG (0.326 mm²) wires for the RS-485 connection.
Installation Manual 17
Page 18
Transmitter power and I/O wiring Installation Manual
March 2020 MMI- 20032352
User-supplied cable must meet the following requirements:
Twisted pair construction.
Applicable hazardous area requirements, if the core processor is installed in a
hazardous area.
Wire gauge appropriate for the cable length between the core processor and the
transmitter, or the host.
Wire gauge Maximum cable length
VDC 22 AWG (0.326 mm²) 300 ft (91 m)
VDC 20 AWG (0.518 mm²) 500 ft (152 m)
VDC 18 AWG (0.823 mm²) 1,000 ft (305 m)
RS-485 22 AWG (0.326 mm²) or larger 1,000 ft (305 m)

4.2.2 Maximum cable lengths

Table 4-2: Maximum lengths for Micro Motion cable
Cable type To transmitter Maximum length
Micro Motion 9-wire All other MVD transmitters 60 ft (18 m)
Micro Motion 4-wire All 4-wire MVD transmitters 1,000 ft (305 m) without
Table 4-3: Maximum lengths for user-supplied 4-wire cable
Wire function Wire size Maximum length
Power (VDC) 22 AWG (0.326 mm²) 300 ft (91 m)
20 AWG (0.518 mm²) 500 ft (152 m)
18 AWG (0.823 mm²) 1,000 ft (305 m)
Signal (RS-485) 22 AWG (0.326 mm²) or larger 1,000 ft (305 m)

4.2.3 Prepare a cable with a metal conduit

Procedure
Ex-approval
500 ft (152 m) with IIC
rated sensors
1,000 ft (305 m) with IIB
rated sensors
1. Remove the core processor cover using a flat-blade screw driver.
2. Run the conduit to the sensor.
3. Pull the cable through the conduit.
4. Cut the drain wires and let them float at both ends of the conduit.
18 Micro Motion HPC
Page 19
Installation Manual Transmitter power and I/O wiring
MMI- 20032352 March 2020

4.2.4 Prepare a cable with user-supplied cable glands

Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Pass the wires through the gland.
3. Terminate the shield and drain wires inside the gland.
4. Assemble the gland according to vendor instructions.

4.2.5 Prepare a cable with Micro Motion-supplied cable glands

Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Pass the wires through the gland nut and clamping insert.
A. Gland nut B. Clamping insert
3. Strip the cable jacket.
Option
NPT gland type Strip 4.5 in (114 mm)
M20 gland type Strip 4.25 in (108 mm)
4. Remove the clear wrap and filler material.
5. Strip most of the shielding.
Option
NPT gland type Strip all but 0.75 in (19 mm)
M20 gland type Strip all but 0.5 in (13 mm)
6. Wrap the drain wires twice around the shield and cut off the excess drain wires.
Description
Description
A. Drain wires wrapped around shield
Installation Manual 19
Page 20
Transmitter power and I/O wiring Installation Manual
March 2020 MMI- 20032352
7. For foil (shielded cable) only:
Note
For braided (armored cable) skip this step and contine to the next step.
Option Description
NPT gland type
M20 gland type
a. Slide the shielded heat shrink over the drain wires. Ensure that the
wires are completely covered.
b. Apply 250 °F (121.1 °C) heat to shrink the tubing. Do not burn the
cable.
c. Position the clamping insert so the interior end is flush with the
braid of the heat shrink.
A. Shielded heat shrink B. After heat is applied
Trim 0.3 in (8 mm).
A. Trim
8. Assemble the gland by folding the shield or braid back over the clamping insert and
0.125 in (3 mm) past the O-ring.
A. Shield folded back
9. Install the gland body into the conduit opening on the core processor housing.
20 Micro Motion HPC
Page 21
Installation Manual Transmitter power and I/O wiring
MMI- 20032352 March 2020
10. Insert the wires through the gland body and tighten the gland nut onto the gland body.
A. Shield folded back B. Gland body

4.2.6 Connect the wires to the core processor terminals

After the 4-wire cable has been prepared and shielded (if required), connect the individual wires of the 4-wire cable to the terminals on the core processor.
Procedure
1. Connect the wires to the core processor terminals.
2. Reinstall the core processor cover.
3. Torque the cover screws to:
For aluminum housing: 10 in lbf (1.13 N m) to 13 in lbf (1.47 N m)
For stainless steel housing: minimum 19 in lbf (2.15 N m)
If properly seated, there will be no gap between cover and base.
4. Connect the wires to the transmitter terminals using the transmitter installation manual.
Installation Manual 21
Page 22
Transmitter power and I/O wiring Installation Manual
March 2020 MMI- 20032352

4.3 Connect 9-wire cable

4.3.1 Connect the 9-wire cable

Procedure
1. Prepare and install the cable according to the instructions in the Micro Motion 9-Wire Flowmeter Cable Preparation and Installation Guide.
2. Insert the stripped ends of the individual wires into the terminal blocks of the junction box. Ensure that no bare wires remain exposed.
3. Match the wires color for color. For wiring at the transmitter or remote core processor, refer to the transmitter documentation.
4. Tighten the screws to hold the wires in place.
5. Ensure integrity of gaskets, then tightly close and seal the junction box cover and all housing covers.
6. Refer to the transmitter installation manual for signal and power wiring instructions.
4.3.2
4.3.3

Connect the 9-wire cable on a remote enhanced core processor

Procedure
1. Insert the stripped ends of the individual wires into the terminal blocks. Ensure that no bare wires remain exposed.
2. Match the wires color for color.
3. Tighten the screws to hold the wires in place.
4. Ensure integrity of gaskets, then tightly close and seal all housing covers.

Wire the MVD Direct Connect I.S. barrier

Procedure
Connect the core processor to the barrier:
a) Connect the RS-485 wires from the core processor to the I.S. RS-485 terminals at
the barrier (terminals 43 and 44), matching A and B. See the following table and figure.
b) Connect the power supply wires from the core processor to the I.S. VDC terminals
at the barrier (terminals 42 and 41), matching positive and negative (+ and –). Do not terminate the shields at the barrier. See the following table and figure.
Function
RS-485 A 3 43
RS-485 B 4 44
22 Micro Motion HPC
Core processor terminals Barrier I.S. terminals
Page 23
Installation Manual Transmitter power and I/O wiring
MMI- 20032352 March 2020
Function Core processor terminals Barrier I.S. terminals
VDC + 1 42
VDC – 2 41
c) Connect the RS-485 wires to the non-I.S. RS-485 terminals at the barrier (terminals
13 and 14). These wires will be used in the next step to connect the barrier to the remote host. Do not terminate the shields at the barrier.
d) Connect the power supply wires to the non-I.S. VDC terminals at the barrier
(terminals 11 and 12). These wires will be used in the next step to connect the barrier to the power supply.
Figure 4-1: Barrier terminals
4.3.4
A. I. S. terminals for connection to the core processor B. Non I.S. terminals for connection to remote host and power supply

Connect power to the I.S. barrier

You can connect multiple MVD Direct Connect installations to a single power supply, as
long as each installation receives sufficient power.
For power supply to I.S. barrier connections, the power supply can be used to power
other equipment.
Procedure
Connect the power supply wires between the enhanced core processor and the barrier, matching positive and negative (+ and –).
Installation Manual 23
Page 24
Transmitter power and I/O wiring Installation Manual
March 2020 MMI- 20032352
Figure 4-2: Barrier terminals
A. I.S. terminals for connection to enhanced core processor
B. Non I.S. terminals for connection to remote host and power supply
24 Micro Motion HPC
Page 25
Installation Manual
MMI- 20032352 March 2020
Grounding

5 Grounding

The meter must be grounded according to the standards that are applicable at the site. The customer is responsible for knowing and complying with all applicable standards.
Prerequisites
Use the following guides for grounding practices:
In Europe, IEC 60079-14 is applicable to most installations, in particular sections
16.2.2.3 and 16.2.2.4.
In the U.S.A. and Canada, ISA 12.06.01 Part 1 provides examples with associated
applications and requirements.
If no external standards are applicable, follow these guidelines to ground the sensor:
Use copper wire, 14 AWG (2.08 mm²) or larger wire size.
Keep all ground leads as short as possible, less than 1 Ω impedance.
Connect ground leads directly to earth, or follow plant standards.
NOTICE
Ground the flowmeter to earth, or follow ground network requirements for the facility. Improper grounding can cause measurement error.
Procedure
Check the joints in the pipeline.
If the joints in the pipeline are ground-bonded, the sensor is automatically
grounded and no further action is necessary (unless required by local code).
If the joints in the pipeline are not grounded, connect a ground wire to the
grounding screw located on the sensor electronics.
Tip
The sensor electronics may be a transmitter, core processor, or junction box. The grounding screw may be internal or external.
A. Grounding screw
Installation Manual 25
Page 26
Grounding Installation Manual
March 2020 MMI- 20032352
26 Micro Motion HPC
Page 27
Installation Manual Purge the sensor case
MMI- 20032352 March 2020

6 Purge the sensor case

Prerequisites
Make sure the following are available before beginning the purge procedure:
Teflon™ tape
Argon or nitrogen gas sufficient to purge the sensor case
Whenever a purge plug is removed from the sensor case, you must purge the case again.
Procedure
1. Shut down the process, or set control devices for manual operation.
NOTICE
Before performing the case purging procedure, shut down the process or set the control devices for manual operation. Performing the purge procedure while the flowmeter is operating could affect measurement accuracy, resulting in inaccurate flow signals.
2. Remove both purge plugs from the sensor case. If purge lines are being used, open
the valve in the purge lines.
WARNING
If a rupture disk has been installed on the purge fitting, stay clear of the
rupture disk pressure relief area. High-pressure fluid escaping from the sensor can cause severe injury or death. Orient the sensor so that personnel and equipment will not be exposed to any discharge along the pressure relief path.
Take all necessary precautions when removing purge plugs. Removing a purge
plug compromises the secondary containment of the sensor and could expose the user to process fluid.
Improper pressurization of the sensor case could result in injury.
NOTICE
If a rupture disk has been installed on the purge fitting, use thread protectors when removing the purge fitting so as not to damage the disk membrane surrounding the rupture disk.
3. Prepare the purge plugs for reinstallation by wrapping them with 2–3 turns of Teflon tape.
4. Connect the supply of nitrogen or argon gas to the inlet purge connection or open inlet purge line. Leave the outlet connection open.
NOTICE
Exercise caution to avoid introducing dirt, moisture, rust, or other contaminants
into the sensor case.
If the purge gas is heavier than air (such as argon), locate the inlet lower than the
outlet, so that the purge gas will displace air from bottom to top.
Installation Manual 27
Page 28
Purge the sensor case Installation Manual
March 2020 MMI- 20032352
If the purge gas is lighter than air (such as nitrogen), locate the inlet higher than
the outlet, so that the purge gas will displace air from top to bottom.
5. Make sure that there is a tight seal between the inlet connection and sensor case, so that air cannot be drawn by suction into the case or purge line during the purging process.
6. Run purge gas through the sensor.
The purge time is the amount of time required for full exchange of atmosphere to inert gas. The larger the line size, the greater amount of time is required to purge the case. If purge lines are being used, increase the purge time to fill the additional volume of the purge line.
Important
Keep the purge gas pressure below 7.25 psi (0.5 bar).
7. At the appropriate time, shut off the gas supply, then immediately seal the purge outlet and inlet connections with the purge plugs.
Avoid pressurizing the sensor case. If pressure inside the case elevates above atmospheric pressure during operation, the flowmeter density calibration will be inaccurate.
8. Make sure that the purge fitting seals are tight so that air cannot be drawn by suction into the sensor case.
28 Micro Motion HPC
Page 29
Installation Manual Pressure relief
MMI- 20032352 March 2020

7 Pressure relief

HPC sensors are available with a rupture disk installed on the case. Rupture disks vent process fluid from the sensor case in the unlikely event of a flow tube breach. Some users connect a pipeline to the rupture disk to help contain escaping process fluid. For more information about rupture disks, contact customer service.
If the sensor has a rupture disk, keep it installed at all times as it would otherwise be necessary to re-purge the case. If the rupture disk is activated by a tube breach, the seal in the rupture disk will be broken, and the Coriolis meter should be removed from service.
Figure 7-1: Rupture disk on the HPC010
A. Rupture disk
Figure 7-2: Rupture disk on the HPC015
A. Rupture disk
Installation Manual 29
Page 30
Pressure relief Installation Manual
March 2020 MMI- 20032352
WARNING
Orient the sensor so that personnel and equipment will not be exposed to any
discharge along the pressure relief path.
Stay clear of the rupture disk pressure relief area. High-pressure fluid escaping from
the sensor can cause severe injury or death.
Important
If using a rupture disk, the housing can no longer assume a secondary containment function.
NOTICE
Removing the purge fitting, blind plug, or rupture disks compromises the Ex-i Safety Certification, the Ex-tc Safety Certification, and the IP-rating of the Coriolis meter. Any modification to the purge fitting, blind plug, or rupture disks must maintain a minimum of IP66/IP67 Ratings.
30 Micro Motion HPC
Page 31
Installation Manual
MMI- 20032352 March 2020
Installation Manual 31
Page 32
*MMI- 20032352*
MMI- 20032352
Rev. AD
2020
Micro Motion Inc. USA
Worldwide Headquarters 7070 Winchester Circle Boulder, Colorado USA 80301 T +1 303-527-5200 T +1 800-522-6277 F +1 303-530-8459
www.emerson.com
Micro Motion Asia
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 Republic of Singapore T +65 6363-7766 F +65 6770-8003
©
2020 Micro Motion, Inc. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Automation Solutions family of companies. All other marks are property of their respective owners.
Micro Motion Europe
Emerson Automation Solutions Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495 555 T +31 (0) 70 413 6666 F +31 (0) 318 495 556
www.emerson.com/nl-nl
Micro Motion United Kingdom
Emerson Automation Solutions Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U.K. T +44 0870 240 1978 F +44 0800 966 181
Loading...