Micro Motion Micro Motion 5700 Transmitters with PROFIBUS-PA Manuals & Guides

Page 1
Configuration and Use Manual
MMI- 20070546, Rev AB
Micro Motion™ 5700 Transmitters with PROFIBUS®-PA
Configuration and Use Manual
June 2021
Page 2
Safety messages
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are available: the EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions. In addition the IECEx Installation Instructions for installations outside of the European Union and the CSA Installation Instructions for installations in North America are available on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com. For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. and Ireland 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 70 413
Mexico +52 55 5809 5010 France +33 (0) 800 917
Argentina +54 11 4809 2700 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy +39 8008 77334 China +86 21 2892 9000
Chile +56 2 2928 4800 Central & Eastern +41 (0) 41 7686
Peru +51 15190130 Russia/CIS +7 495 995 9559 South Korea +82 2 3438 4600
Europe and Middle East Asia Pacific
New Zealand 099 128 804
6666
India 800 440 1468
901
Japan +81 3 5769 6803
111
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
2
Page 3
Configuration and Use Manual Contents
MMI- 20070546 June 2021

Contents

Chapter 1 Before you begin........................................................................................................7
1.1 About this manual....................................................................................................................... 7
1.2 Hazard messages.........................................................................................................................7
1.3 Related documents......................................................................................................................8
1.4 Communication methods............................................................................................................8
Chapter 2 Quick start................................................................................................................. 9
2.1 Power up the transmitter.............................................................................................................9
2.2 Check meter status......................................................................................................................9
2.3 Determine PROFIBUS PA device address and Ident Selection using the display...........................10
2.4 Commissioning wizards............................................................................................................. 10
2.5 Make a startup connection to the transmitter............................................................................11
2.6 Set the transmitter clock............................................................................................................11
2.7 View the licensed features......................................................................................................... 11
2.8 Set informational parameters.................................................................................................... 12
2.9 Characterize the meter (if required)...........................................................................................13
2.10 Verify mass flow measurement................................................................................................16
2.11 Verify the zero......................................................................................................................... 16
Chapter 3 Introduction to configuration and commissioning....................................................19
3.1 Security and write protection.....................................................................................................19
3.2 Work with configuration files.....................................................................................................23
Chapter 4 Configure process measurement..............................................................................29
4.1 Configure Sensor Flow Direction Arrow .....................................................................................29
4.2 Configure mass flow measurement........................................................................................... 30
4.3 Configure volume flow measurement for liquid applications..................................................... 35
4.4 Configure Gas Standard Volume (GSV) flow measurement........................................................39
4.5 Configure density measurement................................................................................................44
4.6 Configure temperature measurement....................................................................................... 47
4.7 Configure Pressure Measurement Unit ......................................................................................49
4.8 Configure Velocity Measurement Unit ...................................................................................... 50
4.9 Energy flow................................................................................................................................50
4.10 Piecewise linearization (PWL) for calibrating gas meters.......................................................... 52
Chapter 5 Configure process measurement applications.......................................................... 53
5.1 Set up the API Referral application ............................................................................................ 53
5.2 Set up concentration measurement...........................................................................................65
Chapter 6 Configure advanced options for process measurement............................................ 81
6.1 Configure Response Time ......................................................................................................... 81
Configuration and Use Manual 3
Page 4
Contents Configuration and Use Manual
June 2021 MMI- 20070546
6.2 Detect and report two-phase flow............................................................................................. 81
6.3 Configure Flow Rate Switch .......................................................................................................83
6.4 Configure events....................................................................................................................... 84
6.5 Configure totalizers and inventories.......................................................................................... 86
6.6 Configure logging for totalizers and inventories.........................................................................90
6.7 Configure Process Variable Fault Action .................................................................................... 90
Chapter 7 Configure device options and preferences................................................................ 95
7.1 Configure the transmitter display.............................................................................................. 95
7.2 Configure the transmitter's response to alerts......................................................................... 101
7.3 Control button sensitivity on the display..................................................................................109
Chapter 8 Integrate the meter with the control system.......................................................... 111
8.1 Configure PROFIBUS-PA Channel A.......................................................................................... 111
8.2 Configure mA Output Channel B..............................................................................................111
8.3 Configure FO/DO Channel C.................................................................................................... 120
Chapter 9 Complete the configuration................................................................................... 131
9.1 Test or tune the system using sensor simulation......................................................................131
9.2 Enable or disable software write-protection.............................................................................132
Chapter 10 Transmitter operation............................................................................................ 135
10.1 View process and diagnostic variables................................................................................... 135
10.2 View and acknowledge status alerts...................................................................................... 136
10.3 Read totalizer and inventory values........................................................................................137
10.4 Start, stop, and reset totalizers and inventories..................................................................... 137
Chapter 11 Measurement support............................................................................................141
11.1 Use Smart Meter Verification................................................................................................. 141
11.2 Zero the meter...................................................................................................................... 148
11.3 Set up pressure compensation...............................................................................................151
11.4 Validate the meter.................................................................................................................154
11.5 Perform a (standard) D1 and D2 density calibration...............................................................156
11.6 Adjust concentration measurement with Trim Slope and Trim Offset ................................... 159
Chapter 12 Maintenance.......................................................................................................... 161
12.1 Install a new transmitter license.............................................................................................161
12.2 Upgrade the transmitter firmware......................................................................................... 162
12.3 Reboot the transmitter.......................................................................................................... 163
12.4 Battery replacement..............................................................................................................164
Chapter 13 Log files, history files, and service files....................................................................165
13.1 Generate history files.............................................................................................................165
13.2 Generate service files.............................................................................................................171
Chapter 14 Troubleshooting.................................................................................................... 179
14.1 Status LED and device status..................................................................................................179
4 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 5
Configuration and Use Manual Contents
MMI- 20070546 June 2021
14.2 API Referral troubleshooting..................................................................................................179
14.3 Concentration measurement troubleshooting...................................................................... 180
14.4 Alert when connecting a core processor to a remote 5700 transmitter..................................181
14.5 Density measurement troubleshooting................................................................................. 182
14.6 Discrete Output troubleshooting...........................................................................................184
14.7 Flow measurement troubleshooting......................................................................................185
14.8 Frequency Output troubleshooting....................................................................................... 187
14.9 mA Output troubleshooting.................................................................................................. 189
14.10 Status alerts, causes, and recommendations....................................................................... 192
14.11 Perform a core processor resistance test..............................................................................211
14.12 Check the cutoffs.................................................................................................................213
14.13 Check the direction parameters...........................................................................................213
14.14 Check the drive gain............................................................................................................ 213
14.15 Check for internal electrical problems..................................................................................214
14.16 Check Frequency Output Fault Action .................................................................................215
14.17 Check the scaling of the Frequency Output..........................................................................215
14.18 Check grounding................................................................................................................. 215
14.19 Perform loop tests............................................................................................................... 216
14.20 Check Lower Range Value and Upper Range Value ..............................................................220
14.21 Check mA Output Fault Action ............................................................................................220
14.22 Trim mA Output.................................................................................................................. 220
14.23 Check the pickoff voltage.................................................................................................... 221
14.24 Check power supply wiring.................................................................................................. 222
14.25 Check for radio frequency interference (RFI)........................................................................ 222
14.26 Check sensor-to-transmitter wiring..................................................................................... 223
14.27 Check the sensor coils..........................................................................................................223
14.28 Using sensor simulation for troubleshooting....................................................................... 225
14.29 Check for two-phase flow (slug flow)................................................................................... 225
14.30 Simulation problems........................................................................................................... 226
14.31 Temperature measurement troubleshooting...................................................................... 228
14.32 Velocity measurement troubleshooting.............................................................................. 229
Appendix A 5700 PROFIBUS-PA transducer blocks.....................................................................231
A.1 Transducer block overview...................................................................................................... 231
A.2 Slot identification.................................................................................................................... 232
A.3 PROFIBUS-PA parameters 0 through 7..................................................................................... 233
A.4 I & M functions.........................................................................................................................234
A.5 Physical block.......................................................................................................................... 237
A.6 Totalizer block parameters (slots 4, 6, 7, and 8)....................................................................... 242
A.7 Analog Output block parameters (slots 9 and 10)....................................................................246
A.8 Analog Input block parameters (slots 1, 2, 3, and 5)................................................................ 251
A.9 Discrete Output block parameters (slot 11)............................................................................. 255
Configuration and Use Manual 5
Page 6
Contents Configuration and Use Manual
June 2021 MMI- 20070546
A.10 Discrete Input block parameters (slot 12).............................................................................. 260
A.11 PROFIBUS-PA channels.......................................................................................................... 263
A.12 Measurement parameters (slot 13)....................................................................................... 269
A.13 Device slot parameters (slot 14)............................................................................................ 292
A.14 Configurable totalizer and inventory block parameters (slot 15)............................................317
A.15 Smart Meter Verification block parameters (slot 16)..............................................................332
A.16 API process variables block parameters (slot 17)....................................................................342
A.17 Concentration measurement block parameters (slot 18).......................................................344
A.18 Advanced Phase Measurement block parameters (slot 19).................................................... 349
Appendix B PROFIBUS PA function blocks..................................................................................359
B.1 Function block overview.......................................................................................................... 359
B.2 Analog Input function block.....................................................................................................363
B.3 Totalizer function block........................................................................................................... 365
B.4 Analog Output function block..................................................................................................368
B.5 Discrete Output function block................................................................................................371
B.6 Discrete Input function block...................................................................................................372
B.7 Slave diagnostic response........................................................................................................374
B.8 Alerts.......................................................................................................................................378
Appendix C Using the transmitter display................................................................................. 381
C.1 Components of the transmitter display................................................................................... 381
C.2 Access and use the display menus........................................................................................... 383
Appendix D Using ProLink III with the transmitter..................................................................... 387
D.1 Connect with ProLink III .......................................................................................................... 387
Appendix E Concentration measurement matrices, derived variables, and process variables.... 389
E.1 Standard matrices for the concentration measurement application.........................................389
E.2 Derived variables and calculated process variables...................................................................390
Appendix F Environmental compliance.....................................................................................393
F.1 RoHS and WEEE........................................................................................................................393
6 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 7
Configuration and Use Manual Before you begin
MMI- 20070546 June 2021

1 Before you begin

1.1 About this manual

This manual helps you configure, commission, use, maintain, and troubleshoot Micro Motion 5700 transmitters with PROFIBUS-PA.
Important
This manual assumes that:
The transmitter has been installed correctly and completely according to the instructions in the
transmitter installation manual
Users understand basic transmitter and sensor installation, configuration, and maintenance concepts and
procedures

1.2 Hazard messages

This document uses the following criteria for hazard messages based on ANSI standards Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access to protect users' assets. This is true for all systems used within the facility.
Configuration and Use Manual 7
Page 8
Before you begin Configuration and Use Manual
June 2021 MMI- 20070546

1.3 Related documents

You can find all product documentation on the product documentation DVD shipped with the product or at
www.emerson.com.
See any of the following documents for more information:
Micro Motion 5700 Product Data Sheet
Micro Motion 5700 Transmitters for PROFIBUS-PA: Installation Manual
Replacing the Junction Box for the 4200 Transmitter and the 5700 Transmitter
Replacing the Sensor Cable for the 4200 Transmitter and the 5700 Transmitter
Sensor installation manual

1.4 Communication methods

You can use several different communications methods to interface with the transmitter. You may use different methods in different locations or for different tasks.
Interface Tool
Display Infrared-sensitive buttons
Universal Service Port ProLink™ III
PROFIBUS PA channel PROFIBUS-PA host
On a PROFIBUS-PA host, the transmitter parameters are displayed in UIRD form (for example, the AMS intelligent Device Manager with DeltaV™ or Siemens PDM)
For information about how to use the communication tools, see the appendices in this manual.
®
8 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 9
Configuration and Use Manual Quick start
MMI- 20070546 June 2021

2 Quick start

2.1 Power up the transmitter

The transmitter must be powered up for all configuration and commissioning tasks, or for process measurement.
Procedure
1. Verify that all transmitter and sensor covers and seals are closed.
WARNING
To prevent ignition of flammable or combustible atmospheres, ensure that all covers and seals are tightly closed. For hazardous area installations, applying power while housing covers are removed or loose can cause an explosion resulting in injury or death.
2. Turn on the electrical power at the power supply.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the initial startup, or if power has been off long enough to allow components to reach ambient temperature, allow the electronics to warm up for approximately 10 minutes before relying on process measurements. During this warm-up period, you may observe minor measurement instability or inaccuracy.

2.2 Check meter status

Check the meter for any error conditions that require user action or that affect measurement accuracy.
Procedure
1. Wait approximately 10 seconds for the power-up sequence to complete.
Immediately after power-up, the transmitter runs through diagnostic routines and checks for error conditions. During the power-up sequence, the Transmitter Initializing alert is active. This
alert should clear automatically when the power-up sequence is complete.
2. Check the status LED on the transmitter.
Table 2-1: Status LED and device status
Status LED condition Device status
Solid green No alerts are active.
Solid yellow One or more alerts are active with Alert Severity = Out of Specification,
Maintenance Required, or Function Check.
Solid red One or more alerts are active with Alert Severity = Failure.
Flashing yellow (1 Hz) The Function Check in Progress alert is active.
Configuration and Use Manual 9
Page 10
Quick start Configuration and Use Manual
June 2021 MMI- 20070546
Table 2-2: Network status LED connection status
Network status LED condition Network status
Solid green Connection made with primary protocol host.
Solid red Configuration error or other error during the PROFIBUS start up sequence.
Off No connection with primary protocol host.
2.3 Determine PROFIBUS PA device address and Ident
Selection using the display
You can configure the 5700 address using either of the following methods:
Hardware addressing
Software addressing
For more information, see Addressing.
Procedure
1. To determine the PROFIBUS-PA device address, choose MenuConfigurationProfibus-PA Setting
Profibus PA Address.
The 5700 address is configurable if the BCD switches at the back of the printed circuit assembly
(PCA) on the display are set > 125.
If you change the 5700 address from the display, power cycle the 5700 so that the new address gets
used for PROFIBUS-PA communication.
2. To determine the PROFIBUS-PA Ident Selection, choose Menu Configuration Profibus-PA Setting Ident Selection.

2.4 Commissioning wizards

The transmitter menu includes a Guided Setup to help you move quickly through the most common configuration parameters. ProLink III also provides a commissioning wizard.
By default, when the transmitter starts up, the Guided Setup menu is offered. You can choose to use it or not. You can also choose whether or not Guided Setup is displayed automatically.
To enter Guided Setup upon transmitter startup, choose Yes at the prompt.
To enter Guided Setup after transmitter startup, choose Menu Startup Tasks.
To control the automatic display of Guided Setup, choose Menu Configuration Guided Setup.
For information on the ProLink III commissioning wizard, see the Micro Motion ProLink III with ProcessViz Software User Manual.
As the commissioning wizards are self guided, they are not documented in detail.
10 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 11
Configuration and Use Manual Quick start
MMI- 20070546 June 2021

2.5 Make a startup connection to the transmitter

For all configuration tools except the display, you must have an active connection to the transmitter to configure the transmitter.
Procedure
Identify the connection type to use, and follow the instructions for that connection type in the appropriate appendix.

2.6 Set the transmitter clock

Display Menu Configuration Time/Date/Tag
ProLink III Device Tools Configuration Transmitter Clock
The transmitter clock provides timestamp data for alerts, service logs, history logs, and all other timers and dates in the system. You can set the clock for your local time or for any standard time you want to use.
Tip
You may find it convenient to set all of your transmitter clocks to the same time, even if the transmitters are in different time zones.
Procedure
1. Select the time zone that you want to use.
2. If you need a custom time zone, select Special Time Zone and enter your time zone as a difference from UTC (Coordinated Universal Time).
3. Set the time appropriately for the selected time zone.
Tip
The transmitter does not adjust for Daylight Savings Time. If you observe Daylight Savings Time, you must reset the transmitter clock manually.
4. Set the month, day, and year.
The transmitter tracks the year and automatically adds a day for leap years.

2.7 View the licensed features

Display
ProLink III Device Tools Device Information Licensed Features
DeltaV AMS Overview Device Information Licenses
Siemens PDM view Overview Device Information Licenses
You can view the licensed features to ensure that the transmitter was ordered with the required features.
Menu About Licenses Licensed Features
Licensed features are purchased and available for permanent use. The options model code represents the licensed features.
Configuration and Use Manual 11
Page 12
Quick start Configuration and Use Manual
June 2021 MMI- 20070546
A trial license allows you to explore features before purchasing. The trial license enables the specified features for a limited number of days. This number is displayed for reference. At the end of this period, the feature will no longer be available.
To purchase additional features or request a trial license, document the Unique ID Number and current license key from your transmitter and contact customer service. To enable the additional features or trial license, you will need to install the new license on the transmitter.

2.8 Set informational parameters

Display Menu Configuration Device Information
ProLink III Device Tools Configuration Informational Parameters
DeltaV AMS Configure Manual Setup Device
Siemens PDM Device Manual Setup Device
You can set several parameters that identify or describe the transmitter and sensor. These parameters are not used in processing and are not required.
Procedure
1. Set informational parameters for the transmitter.
a) Set Transmitter Serial Number to the serial number of your transmitter.
The transmitter serial number is provided on the metal tag that is attached to the transmitter housing.
b) Set Descriptor to any desired description of this transmitter or measurement point.
c) Set Message to any desired message.
d) Verify that Model Code (Base) is set to the base model code of the transmitter.
The base model code completely describes your transmitter, except for the features that can be licensed independently. The base model code is set at the factory.
e) Set Model Code (Options) to the options model code of the transmitter.
The options model code describes the independent features that have been licensed for this transmitter. The original options model code is set at the factory. If you license additional options for this transmitter, Micro Motion will supply an updated options model code.
2. Set informational parameters for the sensor.
a) Set Sensor Serial Number to the serial number of the sensor connected to this transmitter.
The sensor serial number is provided on the metal tag that is attached to the sensor case.
b) Set Sensor Material to the material used for the sensor.
c) Set Sensor Liner to the material used for the sensor liner, if any.
d) Set Flange Type to the type of flange that was used to install the sensor.
12 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 13
Configuration and Use Manual Quick start
MMI- 20070546 June 2021
Do not set Sensor Type. Sensor Type is set or derived during characterization.

2.9 Characterize the meter (if required)

Display Menu Configuration Sensor Parameters
ProLink III Device Tools Calibration Data
DeltaV AMS Configure Manual Setup Characterization
Siemens PDM Device Manual Setup Characterization
Characterizing the meter adjusts your transmitter to match the unique traits of the sensor it is paired with. The characterization parameters (also called calibration parameters) describe the sensor’s sensitivity to flow, density, and temperature. Depending on your sensor type, different parameters are required.
Values for your sensor are provided on the sensor tag or the calibration certificate.
If your transmitter was ordered with a sensor, it was characterized at the factory. However, you should still
verify the characterization parameters.
Perform a characterization whenever you replace a core processor.
Procedure
1. Optional: Specify Sensor Type.
Straight Tube (T-Series sensors)
Curved Tube (all sensors except T-Series)
Note
Unlike earlier transmitters, the 5700 derives Sensor Type from the user-specified values for FCF and K1 in combination with an internal ID.
2. Set the flow calibration factor: FCF (also called Flow Cal or Flow Calibration Factor). Be sure to include
all decimal points.
3. Set the density characterization parameters: D1, D2, TC, K1, K2, and FD. (TC is sometimes shown as
DT.)
4. Apply the changes as required by the tool you are using.
The transmitter identifies your sensor type, and characterization parameters are adjusted as required:
If Sensor Type changed from Curved Tube to Straight Tube, five characterization parameters are
added to the list.
If Sensor Type changed from Straight Tube to Curved Tube, five characterization parameters are
removed from the list.
If Sensor Type did not change, the list of characterization parameters does not change.
5. T-Series sensors only: Set the additional characterization parameters listed below.
Characterization parameter type
Flow FTG, FFQ
Configuration and Use Manual 13
Parameters
Page 14
Quick start Configuration and Use Manual
June 2021 MMI- 20070546
Characterization parameter type Parameters
Density DTG, DFQ1, DFQ2

2.9.1 Sample sensor tags

Figure 2-1: Tag on newer curved-tube sensors (all sensors except T-Series)
Figure 2-2: Tag on older straight-tube sensor (T-Series)
Figure 2-3: Tag on newer straight-tube sensor (T-Series)
14 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 15
Configuration and Use Manual Quick start
MMI- 20070546 June 2021

2.9.2 Flow calibration parameters (FCF, FT)

Two separate values are used to describe flow calibration: a 6-character FCF value and a 4-character FT value. They are provided on the sensor tag.
Both values contain decimal points. During characterization, these are entered as a single 10-character string. The 10-character string is called either Flowcal or FCF.
If your sensor tag shows the FCF and the FT values separately and you need to enter a single value, concatenate the two values to form the single parameter value, retaining both decimal points.
Concatenating FCF and FT
FCF = x.xxxx FT = y.yy Flow calibration parameter: x.xxxxy.yy

2.9.3 Density calibration parameters (D1, D2, K1, K2, FD, DT, TC)

Density calibration parameters are typically on the sensor tag and the calibration certificate.
If your sensor tag does not show a D1 or D2 value:
For D1, enter the Dens A or D1 value from the calibration certificate. This value is the line-condition
density of the low-density calibration fluid. Micro Motion uses air. If you cannot find a Dens A or D1 value, enter 0.001 g/cm3.
For D2, enter the Dens B or D2 value from the calibration certificate. This value is the line-condition density
of the high-density calibration fluid. Micro Motion uses water. If you cannot find a Dens B or D2 value, enter 0.998 g/cm3 .
If your sensor tag does not show a K1 or K2 value:
For K1, enter the first five digits of the density calibration factor. In this sample tag, this value is shown as
12500.
For K2, enter the second five digits of the density calibration factor. In this sample tag, this value is shown
as 14286.
Figure 2-4: K1, K2, and TC values in the density calibration factor
If your sensor does not show an FD value, contact customer service.
Configuration and Use Manual 15
Page 16
Quick start Configuration and Use Manual
June 2021 MMI- 20070546
If your sensor tag does not show a DT or TC value, enter the last four characters of the density calibration factor. In the sample tag shown above, the value is shown as 4.44.
Do not confuse the Meter Factor line on the pictured sensor tag with any meter factor settings discussed in this manual.

2.10 Verify mass flow measurement

Check to see that the mass flow rate reported by the transmitter is accurate. You can use any available method.
Procedure
Read the value for Mass Flow Rate on the transmitter display.
Connect to the transmitter with ProLink III and read the value for Mass Flow Rate in the Process Variables
panel.
Postrequisites
If the reported mass flow rate is not accurate:
Check the characterization parameters.
Review the troubleshooting suggestions for flow measurement issues.

2.11 Verify the zero

Display
ProLink III Device Tools Calibration Smart Zero Verification and Calibration Verify Zero
DeltaV AMS Service Tools Maintenance Calibration Zero Calibration Perform Zero Verify
Siemens PDM Diagnostics Maintenance Calibration Zero Calibration Perform Zero Verify
Verifying the zero helps you determine if the stored zero value is appropriate to your installation, or if a field zero can improve measurement accuracy.
Important
In most cases, the factory zero is more accurate than the field zero. Do not zero the meter unless one of the following is true:
The zero is required by site procedures.
The stored zero value fails the zero verification procedure.
Do not verify the zero or zero the meter if a high-severity alert is active. Correct the problem, then verify the zero or zero the meter. You may verify the zero or zero the meter if a low-severity alert is active.
Menu Service Tools Verification & Calibration Meter Zero Zero Verification
Procedure
1. Prepare the meter:
a) Allow the meter to warm up for at least 20 minutes after applying power.
b) Run the process fluid through the sensor until the sensor temperature reaches the normal
process operating temperature.
16 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 17
Configuration and Use Manual Quick start
MMI- 20070546 June 2021
c) Stop flow through the sensor by shutting the downstream valve, and then the upstream valve if
available.
d) Verify that the sensor is blocked in, that flow has stopped, and that the sensor is completely full
of process fluid.
2. Start the zero verification procedure, and wait until it completes.
3. If the zero verification procedure fails:
a) Confirm that the sensor is completely blocked in, that flow has stopped, and that the sensor is
completely full of process fluid.
b) Verify that the process fluid is not flashing or condensing, and that it does not contain particles
that can settle out.
c) Repeat the zero verification procedure.
d) If it fails again, zero the meter.
Postrequisites
Restore normal flow through the sensor by opening the valves.
Related information
Zero the meter
Configuration and Use Manual 17
Page 18
Quick start Configuration and Use Manual
June 2021 MMI- 20070546
18 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 19
Configuration and Use Manual Introduction to configuration and commissioning
MMI- 20070546 June 2021

3 Introduction to configuration and commissioning

3.1 Security and write protection

The transmitter has several features that can help to protect it against intentional or unintentional access and configuration changes.
When locked, the mechanical lock switch on the front of the display prevents any configuration changes
to the transmitter from any local or remote configuration tool. A transmitter without a display does not have a lock switch.
When enabled, the software setting Write Protection prevents any configuration changes. The setting
can only be enabled if the transmitter does not have a display.
If the Universal Service Port (USP) is disabled, the port cannot be used by any service tool to communicate
with or make changes to the transmitter.
When enabled, Security prevents any configuration changes being made from the display unless the
appropriate password is entered.
When enabled, the PROFIBUS PA write lock prevents any configuration changes being written from the
PROFIBUS PA segment.

3.1.1 Universal Service Port security

This transmitter is equipped with a Universal Service Port that works with USB type A connections, including compatible flash drives. There are multiple levels of security built into the transmitter's service port that you can configure according to your needs and security standards.
The service port offers the following features that enhance interface security:
The service port is inaccessible without physical access to the transmitter and requires removal of the
terminal cover
The service port can be disabled from the transmitter through software
The transmitter has a non-traditional operating system that is not designed to execute programs or run
scripts
The display can be password protected to limit access to the USB file menu
Overall transmitter security switches such as the lock switch or write-protection disallows configuration
changes from all interfaces including the Universal Service Port
This transmitter:
Was designed to be implemented in an industrial automation control system (Level 1 and Level 2 of the
Purdue Reference Architecture Model), with defense in depth security controls
Is not intended to be directly connected to an enterprise or to an internet-facing network without a
compensating control in place
Configuration and Use Manual 19
Page 20
Introduction to configuration and commissioning Configuration and Use Manual
June 2021 MMI- 20070546

3.1.2 Lock or unlock the transmitter

If the transmitter has a display, a mechanical switch on the display can be used to lock or unlock the transmitter. When locked, no configuration changes can be made using any configuration tool.
Figure 3-1: Lock switch on transmitter display
You can determine whether you need to lock or unlock the transmitter by looking at the switch.
If the switch is in the right position, the transmitter is locked.
If the switch is in the left position, the transmitter is unlocked.
Note
The top switch is reserved for future use.
Procedure
1.
2. Remove the transmitter housing cover.
Figure 3-2: Removing the transmitter housing cover
WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is powered up. Failure to follow these instructions can cause an explosion resulting in injury or death.
If you are in a hazardous area, power down the transmitter.
20 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 21
Configuration and Use Manual Introduction to configuration and commissioning
MMI- 20070546 June 2021
3. Using a fine-pointed tool, move the switch to the desired position.
4. Replace the transmitter housing cover.
5. If necessary, power up the transmitter.

3.1.3 Enable or disable the service port

Display Menu Configuration Security Service Port
ProLink III Not available
DeltaV AMS Configure Manual Setup Security and Simulation Enable/Disable Service Port
Siemens PDM Device Manual Setup Security and Simulation Enable/Disable Service Port
The service port is enabled by default, so you can use it for transferring files or connect to it with ProLink III. If you want to completely prevent it from being used, you can disable it.
Note
Enabling or disabling the service port will not take effect until power has been cycled to the transmitter.
WARNING
Do not use the service port if the transmitter is in a hazardous area because using the service port means that you must open the transmitter wiring compartment. Opening the wiring compartment in a hazardous area while the transmitter is powered up can cause an explosion resulting in injury or death.

3.1.4 Enable or disable software write-protection

Display
ProLink III Device Tools Configuration Write-Protection
DeltaV AMS Configure Manual Setup Security and Simulation Profibus PA Write Lock
Siemens PDM Device Manual Setup Security and Simulation Profibus PA Write Lock
When enabled, Write-Protection prevents changes to the transmitter configuration. You can perform all other functions, and you can view the transmitter configuration parameters.
Note
The write protection setting via software methods (such as ProLink III) is available only on transmitters without a display. For transmitters with a display, write protection is available only using the lock switch on the display. See Lock
or unlock the transmitter.
Write-protecting the transmitter primarily prevents accidental changes to configuration, not intentional changes. Any user who can make changes to the configuration can disable write protection.
Use the mechanical switch on the display.

3.1.5 Configure security for the display

Display
ProLink III Device Tools Configuration Transmitter Display Display Security
Menu Configuration Security Display Security
Configuration and Use Manual 21
Page 22
Introduction to configuration and commissioning Configuration and Use Manual
June 2021 MMI- 20070546
DeltaV AMS Configure Manual Setup Display Display Menus
Siemens PDM Device Manual Setup Display Display Menus
When using the display, you can require users to enter a password to do any of the following tasks:
Enter the main menu
Change a parameter
Access alert data through the display
Start, stop, or reset totalizers or inventories via the context menu
The display password can be the same or different from the totalizer/inventory context menu control password. If different, the display password is used to reset, start, and stop totalizers or inventories using Menu Operations Totalizers.
Procedure
1. Configure Password Required as desired.
Option Description
At Write When an user chooses an action that leads to a configuration change, they are
prompted to enter the display password.
Enter Menu When the menu is selected from the process variable screen, the display password
will be immediately required if Password Required is set.
Never (default) When a user chooses an action that leads to a configuration change, they are
prompted to activate ⇦⇧⇩⇨. This is designed to protect against accidental changes to configuration. It is not a security measure.
2. If the At Write or Enter Menu option was selected, enable or disable alert security as desired.
Option
Description
Enabled If an alert is active, the alert symbol is shown in the upper right corner of the display but
the alert banner is not displayed. If the operator attempts to enter the alert menu, they are prompted to enter the display password.
Disabled If an alert is active, the alert symbol is shown in the upper right corner of the display and
the alert banner is displayed automatically. No password or confirmation is required to enter the alert menu.
Restriction
You cannot set Password Required to Never and enable alert security.
If you did not enable Password Required, alert security is disabled and cannot be enabled.
Alert security is disabled automatically if you set Password Required to Never after:Password Required is initially set to either At Write or Enter Menu
Alert security is enabled
22 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 23
Configuration and Use Manual Introduction to configuration and commissioning
MMI- 20070546 June 2021
3. If Password Required has been set to At Write or Enter Menu, you will be prompted to enter the desired password.
Default: AAAA
Range: Any four alphanumeric characters
Password Required must be set to At Write or Enter Menu to enable the totalizer/inventory control
context menu password option.
Important
If you enable Password Required but you do not change the display password, the transmitter will post a configuration alert.
4. Configure Main Menu Available as desired.
Option Description
Enabled The local display Menu option from the process variable screen will be accessible.
Disabled The local display Menu option from the process variable screen will not be accessible.
Important
Once Main Menu Available has been disabled, you cannot enable it from the local display. Use another configuration tool, such as ProLink III, to re-enable main menu access from the local display.

3.1.6 Enable or disable PROFIBUS write lock

When locked, the PROFIBUS write lock prevents any configuration changes being written from the PROFIBUS segment.
Procedure
Set the Write Lock parameter (OD index 34) of the physical block to Locked (0) or Unlocked (2457).

3.2 Work with configuration files

You can save the current transmitter configuration in two forms: a backup file and a replication file. You can save the configuration to the SD card on your transmitter or to a USB drive.
Tip
You can use a saved configuration file to change the nature of the transmitter quickly. This might be convenient if the transmitter is used for different applications or different process fluids.
You can load a configuration file to the transmitter's working memory or to the transmitter's SD card. You can load either a backup file or a replication file.
Backup files
Replication files
Configuration and Use Manual 23
Contain all parameters. They are used to restore the current device if required. The .spare extension is used to identify backup files.
Contain all parameters except the device-specific parameters, e.g., calibration factors or meter factors. They are used to replicate the transmitter configuration to other devices. The .xfer extension is used to identify replication files.
Page 24
Introduction to configuration and commissioning Configuration and Use Manual
June 2021 MMI- 20070546

3.2.1 Save a configuration file using the display

Prerequisites
If you are planning to use the USB drive, the service port must be enabled. It is enabled by default. However, if you need to enable it, choose Menu Configuration Security and set Service Port to On.
Procedure
To save the current configuration to the transmitter's SD card as a backup file:
a) Choose Menu Configuration Save/Restore Config Save Config to Memory.
b) Enter the name for this configuration file.
The configuration file is saved to the transmitter's SD card as yourname.spare.
To save the current configuration to a USB drive, as either a backup file or a replication file:
a)
b) Choose Menu USB Options Transmitter --> USB Drive Save Active Config to USB Drive.
c) Choose Backup or Replicate.
d) Enter the name for this configuration file.
The configuration file is saved to the USB drive as yourname.spare or yourname.xfer.
To copy a configuration file from the transmitter's SD card to the USB drive:
a)
b) Choose Menu USB Options Transmitter --> USB Drive Transfer Config File to USB Drive.
c) Choose Backup or Replicate.
WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is powered up. Failure to follow these instructions can cause an explosion resulting in injury or death.
Open the wiring compartment on the transmitter and insert a USB drive into the service port.
WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is powered up. Failure to follow these instructions can cause an explosion resulting in injury or death.
Open the wiring compartment on the transmitter and insert a USB drive into the service port.
d) Select the file that you want to transfer.
The configuration file is copied to the USB drive, using its existing name.

3.2.2 Save a configuration file using ProLink III

Note
When you use ProLink III format for configuration files, you can specify configuration parameters individually or by groups. Therefore, you can use this format for both backup and replication.
24 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 25
Configuration and Use Manual Introduction to configuration and commissioning
MMI- 20070546 June 2021
Procedure
To save the current configuration to the transmitter's SD card:
a) Choose Device Tools Configuration Transfer Save Configuration.
b) Select On my 5700 Device Internal Memory and select Next.
c) Select Save.
d) Enter the name for this configuration file.
e) Set the file type.
To save a backup file, set the file type to Backup.
To save a replication file, set the file type to Transfer.
f) Select Save.
The configuration file is saved to the transmitter's SD card as yourname.spare or yourname.xfer.
To save the current configuration to your PC, in 5700 format:
a) Choose Device Tools Configuration Transfer Save Configuration.
b) Select On my computer in 5700 device file format and select Next.
c) Select Save.
d) Browse to the desired location, then enter the name for this configuration file.
e) Set the file type.
To save a backup file, set the file type to Backup.
To save a replication file, set the file type to Transfer.
f) Select Save.
The configuration file is saved to the specified location as yourname.spare or yourname.xfer.
To save the current configuration to your PC, in ProLink III format:
a) Choose Device Tools Configuration Transfer Save Configuration.
b) Select On my computer in ProLink III file format and click Next.
c) Select Save.
d) Select the configuration parameters to be included in this file.
To save a backup file, select all parameters.
To save a replication file, select all parameters except device-specific parameters.
e) Select Save.
f) Browse to the desired location, then enter the name for this configuration file.
g) Set the file type to ProLink configuration file.
h) Select Start Save.
The configuration file is saved to the specified location as yourname.pcfg.
Configuration and Use Manual 25
Page 26
Introduction to configuration and commissioning Configuration and Use Manual
June 2021 MMI- 20070546

3.2.3 Load a configuration file using the display

Prerequisites
You must have a backup file or a replication file available for use.
If you are planning to use the USB drive, the service port must be enabled. It is enabled by default. However, if you need to enable it, choose Menu Configuration Security and set Service Port to On.
Procedure
To load either a backup file or a replication file from the transmitter's SD card:
a) Choose Menu Configuration Save/Restore Config Restore Config from Memory.
b) Select Backup or Replicate.
c) Select the file that you want to load.
The file is loaded to working memory and becomes active immediately.
To load a either a backup file or a replication file from a USB drive:
a) WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is powered up. Failure to follow these instructions can cause an explosion resulting in injury or death.
Open the wiring compartment on the transmitter and insert the USB drive containing the backup file or replication file into the service port.
b) Choose Menu USB Options USB Drive --> Transmitter Upload Configuration File.
c) Select Backup or Replicate.
d) Select the file that you want to load.
e) Choose Yes or No when prompted to apply the settings.
Yes: The file is loaded to working memory and becomes active immediately.
No: The file is loaded to the transmitter's SD card but not to working memory. You can load it
from the SD card to working memory at a later time.

3.2.4 Load a configuration file using ProLink III

You can load a configuration file to the transmitter's working memory. You can load a backup file or a replication file. Two PC file formats are supported: the 5700 format and the ProLink III format.
Note
When you use ProLink III format for configuration files, you can specify configuration parameters individually or by groups. Therefore, you can use this format for both backup and replication.
Procedure
To load a backup file or replication file from the transmitter's SD card:
a) Choose Device Tools Configuration Transfer Load Configuration.
26 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 27
Configuration and Use Manual Introduction to configuration and commissioning
MMI- 20070546 June 2021
b) Select On my 5700 Device Internal Memory and select Next.
c) Select Restore.
d) Set the file type.
To load a backup file, set the file type to Backup.
To load a replication file, set the file type to Transfer.
e) Select the file that you want to load and select Load.
The parameters are written to working memory, and the new settings become effectively immediately.
To load a backup file or replication file in 5700 format from the PC:
a) Choose Device Tools Configuration Transfer Load Configuration.
b) Select On my computer in 5700 device file format and select Next.
c) Select Restore.
d) Set the file type.
To load a backup file, set the file type to Backup.
To load a replication file, set the file type to Transfer.
e) Navigate to the file you want to load, and select it.
The parameters are written to working memory, and the new settings become effectively immediately.
To load a file in ProLink III format from the PC:
a) Choose Device Tools Configuration Transfer Load Configuration.
b) Select On my computer in ProLink III file format and select Next.
c) Select the parameters that you want to load.
d) Select Load.
e) Set the file type to Configuration file.
f) Navigate to the file you want to load, and select it.
g) Select Start Load.
The parameters are written to working memory, and the new settings become effectively immediately.

3.2.5 Restore the factory configuration

Display
ProLink III Device Tools Configuration Transfer Restore Factory Configuration
DeltaV AMS Service Tools Maintenance Reset/Restore Restore Factory Configuration
Siemens PDM Diagnostics Maintenance Reset/Restore Restore Factory Configuration
Menu Configuration Save/Restore Configuration Restore Config from Memory
Configuration and Use Manual 27
Page 28
Introduction to configuration and commissioning Configuration and Use Manual
June 2021 MMI- 20070546
A file containing the factory configuration is always saved in the transmitter's internal memory, and is available for use.
This action is typically used for error recovery or for repurposing a transmitter.
If you restore the factory configuration, the real-time clock, the audit trail, the historian, and other logs are not reset.
Note
Using a web browser, you can download the factory (.cfg) configuration file and view it with a text editor, but you must use ProLink III or the display to restore the factory configuration.

3.2.6 Replicate a transmitter configuration

Replicating a transmitter configuration is a fast method to set up similar or identical measurement points.
Procedure
1. Configure a transmitter and verify its operation and performance.
2. Use any available method to save a replication file from that transmitter.
3. Use any available method to load the replication file to another transmitter.
4. At the replicated transmitter, set device-specific parameters and perform device-specific procedures: a) Set the clock.
b) Set the tag and related parameters.
c) Characterize the transmitter.
d) Perform zero validation and take any recommended actions.
e) Perform loop tests and take any recommended actions, including mA Output trim.
f) Use sensor simulation to verify transmitter response.
g) Set Node Address for PROFIBUS PA communication.
5. At the replicated transmitter, set device-specific parameters and perform device-specific procedures: a) Set the clock.
b) Set the tag, long tag, Modbus address, and related parameters.
c) Characterize the transmitter.
d) Perform zero validation and take any recommended actions.
e) Perform loop tests and take any recommended actions, including mA Output trim.
f) Use sensor simulation to verify transmitter response.
g) Set Node Address for PROFIBUS PA communication.
6. At the replicated transmitter, make any other configuration changes.
7. Follow your standard procedures to ensure that the replicated transmitter is performing as desired.
28 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 29
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021

4 Configure process measurement

4.1 Configure Sensor Flow Direction Arrow

Display Menu Configuration Process Measurement Flow Variables Flow Direction
ProLink III Device Tools Configuration Process Measurement Flow Sensor Direction
DeltaV AMS Configure Manual Setup Measurements Flow Sensor Direction
Siemens PDM Device Manual Setup Measurements Flow Sensor Direction
Sensor Flow Direction Arrow is used to accommodate installations in which the Flow arrow on the sensor does not match the majority of the process flow. This typically happens when the sensor is accidentally installed backwards.
Sensor Flow Direction Arrow interacts with mA Output Direction, Frequency Output Direction, and Totalizer Direction to control how flow is reported by the outputs and accumulated by the totalizers and
inventories.
The Sensor Flow Direction Arrow also affects how flow is reported on the transmitter display and via digital communications. This includes ProLink III, the PROFIBUS PA host, and all other user interfaces.
Figure 4-1: Flow arrow on sensor
A. Flow arrow
B. Actual flow direction
Procedure
Set Sensor Flow Direction Arrow as appropriate.
Option
Description
With Arrow The majority of flow through the sensor matches the Flow arrow on the sensor. Actual
forward flow is processed as forward flow.
Against Arrow The majority of flow through the sensor is opposite to the Flow arrow on the sensor. Actual
forward flow is processed as reverse flow.
Configuration and Use Manual 29
Page 30
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
Tip
Micro Motion sensors are bidirectional. Measurement accuracy is not affected by actual flow direction or the setting of Sensor Flow Direction Arrow. Sensor Flow Direction Arrow controls only whether actual flow is processed as forward flow or reverse flow.
Related information
Configure mA Output Direction Configure Frequency Output Direction Configure Discrete Output Source Configure totalizers and inventories Effect of Sensor Flow Direction Arrow on digital communications

4.2 Configure mass flow measurement

The mass flow measurement parameters control how mass flow is measured and reported. The mass total and mass inventory are derived from the mass flow data.

4.2.1 Configure Mass Flow Measurement Unit

Display Menu Configuration Process Measurement Flow Variables Mass Flow Settings Units
ProLink III Device Tools Configuration Process Measurement Flow Mass Flow Rate Unit
DeltaV AMS Configure Manual Setup Measurements Mass Flow Unit
Siemens PDM Device Manual Setup Measurements Mass Flow Unit
Mass Flow Measurement Unit specifies the unit of measure that will be used for the mass flow rate. The default unit used for mass total and mass inventory is derived from this unit.
Procedure
Set Mass Flow Measurement Unit to the unit you want to use.
Default: g/sec (grams per second)
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Mass Flow Measurement Unit
The transmitter provides a standard set of measurement units for Mass Flow Measurement Unit, plus one user-defined special measurement unit. Different communications tools may use different labels for the units.
Unit description
Display ProLink III PROFIBUS PA host Host code
Grams per second gram/s g/sec g/s 1318
Grams per minute gram/min g/min g/min 1319
Grams per hour gram/h g/hr g/h 1320
30 Micro Motion 5700 Transmitters with PROFIBUS-PA
Label
Page 31
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021
Unit description
Kilograms per second kg/s kg/sec kg/s 1322
Kilograms per minute kg/min kg/min kg/min 1323
Kilograms per hour kg/h kg/hr kg/h 1324
Kilograms per day kg/d kg/day kg/d 1325
Metric tons per minute MetTon/min mTon/min t/min 1327
Metric tons per hour MetTon/h mTon/hr t/h 1328
Metric tons per day MetTon/d mTon/day t/d 1329
Pounds per second lb/s lbs/sec lb/s 1330
Pounds per minute lb/min lbs/min lb/min 1331
Pounds per hour lb/h lbs/hr lb/h 1332
Pounds per day lb/d lbs/day lb/d 1333
Short tons (2000 pounds) per minute
Short tons (2000 pounds) per hour
Short tons (2000 pounds) per day
Display ProLink III PROFIBUS PA host Host code
STon/min sTon/min STon/min 1335
STon/h sTon/hr STon/h 1336
STon/d sTon/day STon/d 1337
Label
Long tons (2240 pounds) per hour
Long tons (2240 pounds) per day
Special unit SPECIAL Special Special 1999
LTon/h lTon/hr LTon/h 1340
LTon/d lTon/day LTon/d 1341
Define a special measurement unit for mass flow
Display
ProLink III Device Tools Configuration Process Measurement Flow Mass Flow Rate Unit Special
DeltaV AMS Configure Manual Setup Measurements Optional Setup Special Units Mass Special Units
Siemens PDM Device Manual Setup Measurements Optional Setup Special Units Mass Special Units
Procedure
1. Specify Base Mass Unit.
Base Mass Unit is the existing mass unit that the special unit will be based on.
2. Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
Menu Configuration Process Measurement Flow Variables Mass Flow Settings Units SPECIAL
Configuration and Use Manual 31
Page 32
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
3. Calculate Mass Flow Conversion Factor as follows:
a) x base units = y special units
b) Mass Flow Conversion Factor = x ÷ y
4. Enter Mass Flow Conversion Factor.
The original mass flow rate value is divided by this value.
5. Set Mass Flow Label to the name you want to use for the mass flow unit.
6. Set Mass Total Label to the name you want to use for the mass total and mass inventory unit.
The special measurement unit is stored in the transmitter. You can configure the transmitter to use the special measurement unit at any time.
Example: Defining a special measurement unit for mass flow
If you want to measure mass flow in ounces per second (oz/sec):
1. Set Base Mass Unit to Pounds (lb).
2. Set Base Time Unit to Seconds (sec).
3. Calculate Mass Flow Conversion Factor:
a. 1 lb/sec = 16 oz/sec
b. Mass Flow Conversion Factor = 1 ÷ 16 = 0.0625
4. Set Mass Flow Conversion Factor to 0.0625.
5. Set Mass Flow Label to oz/sec.
6. Set Mass Total Label to oz.

4.2.2 Configure Flow Damping

Display
ProLink III Device Tools Configuration Process Measurement Flow Flow Rate Damping
DeltaV AMS Configure Manual Setup Measurements Flow Damping
Siemens PDM Device Manual Setup Measurements Flow Damping
Flow Damping controls the amount of damping that will be applied to the measured mass flow rate. It affects flow rate process variables that are based on the measured mass flow rate. This includes volume flow rate and gas standard volume flow rate.
Flow Damping also affects specialized flow rate variables such as temperature-corrected volume flow rate (API Referral) and net mass flow rate (concentration measurement).
Menu Configuration Process Measurement Flow Variables Flow Damping
Damping is used to smooth out small, rapid fluctuations in process measurement. The damping value specifies the time period, in seconds, over which the transmitter will spread changes in the process variable. At the end of the interval, the internal value of the process variable (the damped value) will reflect 63% of the change in the actual measured value.
32 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 33
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021
Procedure
Set Flow Damping to the value you want to use.
Default: 0.64 seconds
Range: 0 seconds to 60 seconds
Note
If a number greater than 60 is entered, it is automatically changed to 60.
Tip
A high damping value makes the process variable appear smoother because the reported value changes
slowly.
A low damping value makes the process variable appear more erratic because the reported value changes
more quickly.
The combination of a high damping value and rapid, large changes in flow rate can result in increased
measurement error.
Whenever the damping value is non-zero, the reported measurement will lag the actual measurement
because the reported value is being averaged over time.
In general, lower damping values are preferable because there is less chance of data loss, and less lag time
between the actual measurement and the reported value.
The transmitter automatically rounds off any entered damping value to the nearest valid value. Therefore,
the recommended damping value for gas applications should be 3.2 seconds. If you enter 2.56, the transmitter will round it off to 3.2.
For filling applications, Micro Motion recommends using the default value of 0.04 seconds.
Effect of flow damping on volume measurement
Flow damping affects volume measurement for liquid volume data. Flow damping also affects volume measurement for gas standard volume data. The transmitter calculates volume data from the damped mass flow data.
Interaction between Flow Damping and mA Output Damping
In some circumstances, both Flow Damping and mA Output Damping are applied to the reported mass flow value.
Flow Damping controls the rate of change in flow process variables. mA Output Damping controls the rate of change reported via the mA Output. If mA Output Process Variable is set to Mass Flow Rate, and both Flow Damping and mA Output Damping are set to non-zero values, flow damping is applied first, and the added damping calculation is applied to the result of the first calculation.

4.2.3 Configure Mass Flow Cutoff

Display
ProLink III Device Tools Configuration Process Measurement Flow Mass Flow Cutoff
Configuration and Use Manual 33
Menu Configuration Process Measurement Flow Variables Mass Flow Settings Low Flow Cutoff
Page 34
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
DeltaV AMS Configure Manual Setup Measurements Flow Cutoff
Siemens PDM Device Manual Setup Measurements Flow Cutoff
Mass Flow Cutoff specifies the lowest mass flow rate that will be reported as measured. All mass flow rates below this cutoff will be reported as 0.
Procedure
Set Mass Flow Cutoff to the value you want to use.
Default: A sensor-specific value set at the factory. If your transmitter was ordered without a sensor, the
default may be 0.0.
Recommendation: 0.5% of maximum flow rate of the attached sensor. See the sensor specifications.
Important
Do not use your meter for measurement with Mass Flow Cutoff set to 0.0 g/sec. Ensure that Mass Flow Cutoff is set to the value that is appropriate for your sensor.
Effect of Mass Flow Cutoff on volume measurement
Mass Flow Cutoff does not affect volume measurement. Volume data is calculated from the actual mass data rather than the reported value.
Volume flow has a separate Volume Flow Cutoff that is not affected by the Mass Flow Cutoff value.
Interaction between Mass Flow Cutoff and mA Output Cutoff
Mass Flow Cutoff defines the lowest mass flow value that the transmitter will report as measured. mA Output Cutoff defines the lowest flow rate that will be reported via the mA Output. If mA Output Process Variable is set to Mass Flow Rate, the mass flow rate reported via the mA Output is controlled by the higher of
the two cutoff values.
Mass Flow Cutoff affects all reported values and values used in other transmitter behavior (e.g., events defined on mass flow).
mA Output Cutoff affects only mass flow values reported via the mA Output.
Example: Cutoff interaction with mA Output Cutoff lower than Mass Flow Cutoff
Configuration:
mA Output Process Variable: Mass Flow Rate
Frequency Output Process Variable: Mass Flow Rate
mA Output Cutoff: 10 g/sec
Mass Flow Cutoff: 15 g/sec
Result: If the mass flow rate drops below 15 g/sec, mass flow will be reported as 0, and 0 will be used in all internal processing.
34 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 35
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021
Example: Cutoff interaction with mA Output Cutoff higher than Mass Flow Cutoff
Configuration:
mA Output Process Variable: Mass Flow Rate
Frequency Output Process Variable: Mass Flow Rate
mA Output Cutoff: 15 g/sec
Mass Flow Cutoff: 10 g/sec
Result:
If the mass flow rate drops below 15 g/sec but not below 10 g/sec:The mA Output will report zero flow.
The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all
internal processing.
If the mass flow rate drops below 10 g/sec, both outputs will report zero flow, and 0 will be used in all
internal processing.
4.3 Configure volume flow measurement for liquid
applications
The volume flow measurement parameters control how liquid volume flow is measured and reported. The volume total and volume inventory are derived from volume flow data.
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time. Choose one or the other.

4.3.1 Configure Volume Flow Type for liquid applications

Display
ProLink III
DeltaV AMS
Siemens PDM
Volume Flow Type controls whether liquid or gas standard volume flow measurement will be used.
Restriction
Gas standard volume measurement is incompatible with the following applications:
API Referral
Menu Configuration Process Measurement Flow Variables Volume Flow Settings Flow Type Liquid
Device Tools Configuration Process Measurement Flow Volume Flow Type Liquid Volume
Overview Device Information Licenses Enable/Disable Applications Volume Flow Type
View Overview Device Information Licenses Enable/Disable Applications Volume Flow Type
Concentration measurement
For these applications, set Volume Flow Type to Liquid.
Configuration and Use Manual 35
Page 36
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
Procedure
Set Volume Flow Type to Liquid.
4.3.2 Configure Volume Flow Measurement Unit for liquid
applications
Display Menu Configuration Process Measurement Flow Variables Volume Flow Settings Units
ProLink III Device Tools Configuration Process Measurement Flow Volume Flow Rate Unit
DeltaV AMS Configure Manual Setup Measurements Volume Flow Unit
Siemens PDM Device Manual Setup Measurements Volume Flow Unit
Volume Flow Measurement Unit specifies the unit of measurement that will be displayed for the volume flow rate. The unit used for the volume total and volume inventory is based on this unit.
Prerequisites
Before you configure Volume Flow Measurement Unit, be sure that Volume Flow Type is set to Liquid.
Procedure
Set Volume Flow Measurement Unit to the unit you want to use.
Default: l/sec (liters per second)
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Volume Flow Measurement Unit for liquid applications
Unit description
Display ProLink III PROFIBUS PA host Host code
Cubic feet per second ft3/s ft3/sec ft³/min 1356
Cubic feet per minute ft3/min ft3/min ft³/min 1357
Cubic feet per hour ft3/h ft3/hr ft³/h 1358
Cubic feet per day ft3/d ft3/day ft³/d 1359
Cubic meters per second m3/s m3/sec m³/s 1347
Cubic meters per minute m3/min m3/min m³/min 1348
Cubic meters per hour m3/h m3/hr m³/h 1349
Cubic meters per day m3/d m3/day m³/d 1350
Label
U.S. gallons per second gal/s US gal/sec gal/s 1362
U.S. gallons per minute gal/m US gal/min gal/min 1363
U.S. gallons per hour gal/h US gal/hr gal/h 1364
U.S. gallons per day gal/d US gal/day gal/d 1365
Million U.S. gallons per day MMgal/d mil US gal/day Mgal/d 1366
36 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 37
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021
Unit description
Display ProLink III PROFIBUS PA host Host code
Liters per second L/s l/sec L/s 1351
Liters per minute L/min l/min L/min 1352
Liters per hour L/h l/hr L/h 1353
Million liters per day MML/d mil l/day ML/d 1355
Imperial gallons per second Impgal/s Imp gal/sec ImpGal/s 1367
Imperial gallons per minute Impgal/m Imp gal/min ImpGal/min 1368
Imperial gallons per hour Impgal/h Imp gal/hr ImpGal/h 1369
Imperial gallons per day Impgal/d Imp gal/day ImpGal/d 1370
Special unit SPECIAL Special Special 1999
Label
Define a special measurement unit for volume flow
Display Menu Configuration Process Measurement Flow Variables Volume Flow Settings Units
ProLink III Device Tools Configuration Process Measurement Flow Volume Flow Rate Unit Special
DeltaV AMS Configure Manual Setup Measurements Optional Setup Special Units Volume Special Units
Siemens PDM Device Manual Setup Measurements Optional Setup Special Units Volume Special Units
SPECIAL
Procedure
1. Specify Base Volume Unit.
Base Volume Unit is the existing volume unit that the special unit will be based on.
2. Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
3. Calculate Volume Flow Conversion Factor as follows:
a) x base units = y special units
b) Volume Flow Conversion Factor = x ÷ y
4. Enter Volume Flow Conversion Factor.
The original volume flow rate value is divided by this conversion factor.
5. Set Volume Flow Label to the name you want to use for the volume flow unit.
6. Set Volume Total Label to the name you want to use for the volume total and volume inventory unit.
The special measurement unit is stored in the transmitter. You can configure the transmitter to use the special measurement unit at any time.
Example: Defining a special measurement unit for volume flow
You want to measure volume flow in pints per second (pints/sec).
1. Set Base Volume Unit to Gallons (gal).
Configuration and Use Manual 37
Page 38
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
2. Set Base Time Unit to Seconds (sec).
3. Calculate the conversion factor:
a. 1 gal/sec = 8 pints/sec
b. Volume Flow Conversion Factor = 1 ÷ 8 = 0.1250
4. Set Volume Flow Conversion Factor to 0.1250.
5. Set Volume Flow Label to pints/sec.
6. Set Volume Total Label to pints.

4.3.3 Configure Volume Flow Cutoff

Display Menu Configuration Process Measurement Flow Variables Volume Flow Settings Low Flow
ProLink III Device Tools Configuration Process Measurement Flow Volume Flow Cutoff
DeltaV AMS Configure Manual Setup Measurements Volume Flow Cutoff
Siemens PDM Device Manual Setup Measurements Volume Flow Cutoff
Cutoff
Volume Flow Cutoff specifies the lowest volume flow rate that will be reported as measured. All volume flow
rates below this cutoff are reported as 0.
Procedure
Set Volume Flow Cutoff to the value you want to use.
Default: 0.0 l/sec (liters per second)
Range: 0 l/sec to x l/sec, where x is the sensor’s flow calibration factor, multiplied by 0.0002.
Interaction between Volume Flow Cutoff and mAO Cutoff
Volume Flow Cutoff defines the lowest liquid volume flow value that the transmitter will report as measured. mAO Cutoff defines the lowest flow rate that will be reported via the mA Output. If mA Output Process Variable is set to Volume Flow Rate, the volume flow rate reported via the mA Output is controlled by the
higher of the two cutoff values.
Volume Flow Cutoff affects both the volume flow values reported via the outputs and the volume flow values used in other transmitter behavior (e.g., events defined on the volume flow).
mAO Cutoff affects only flow values reported via the mA Output.
Example: Cutoff interaction with mAO Cutoff lower than Volume Flow Cutoff
Configuration:
mA Output Process Variable: Volume Flow Rate
Frequency Output Process Variable: Volume Flow Rate
AO Cutoff: 10 l/sec
Volume Flow Cutoff: 15 l/sec
38 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 39
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021
Result: If the volume flow rate drops below 15 l/sec, volume flow will be reported as 0, and 0 will be used in all internal processing.
Example: Cutoff interaction with mAO Cutoff higher than Volume Flow Cutoff
Configuration:
mA Output Process Variable: Volume Flow Rate
Frequency Output Process Variable: Volume Flow Rate
AO Cutoff: 15 l/sec
Volume Flow Cutoff: 10 l/sec
Result:
If the volume flow rate drops below 15 l/sec but not below 10 l/sec:The mA Output will report zero flow.
The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all
internal processing.
If the volume flow rate drops below 10 l/sec, both outputs will report zero flow, and 0 will be used in all
internal processing.
4.4 Configure Gas Standard Volume (GSV) flow
measurement
The gas standard volume (GSV) flow measurement parameters control how gas standard volume flow is measured and reported.
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time. Choose one or the other.

4.4.1 Configure Volume Flow Type for gas applications

Display
ProLink III
DeltaV AMS
Siemens PDM
Volume Flow Type controls whether liquid or gas standard volume flow measurement will be used.
Restriction
Gas standard volume measurement is incompatible with the following applications:
API Referral
Menu Configuration Process Measurement Flow Variables Volume Flow Settings Flow Type Gas
Device Tools Configuration Process Measurement Flow Volume Flow Type Gas Standard Volume
Overview Device Information Licenses Enable/Disable Applications Volume Flow Type
view Overview Device Information Licenses Enable/Disable Applications Volume Flow Type
Concentration measurement
Configuration and Use Manual 39
Page 40
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
For these applications, set Volume Flow Type to Liquid.
Procedure
Set Volume Flow Type to Gas.

4.4.2 Configure Standard Gas Density

Display Menu Configuration Process Measurement Flow Variables Volume Flow Settings Standard
ProLink III Device Tools Configuration Process Measurement Flow Standard Density of Gas
DeltaV AMS Configure Manual Setup Measurements Optional Setup Gas Standard Volume Density
Siemens PDM Device Manual Setup Measurements Optional Setup Gas Standard Volume Density Gas
Gas Density
Gas Reference Density
Reference Density
Standard Gas Density is the density of your gas at reference temperature and reference pressure. This is
often called standard density or base density. It is used to calculate the GSV flow rate from the mass flow rate.
Procedure
Set Standard Gas Density to the density of your gas at reference temperature and reference pressure.
You can use any reference temperature and reference pressure that you choose. It is not necessary to configure these values in the transmitter.
Tip
ProLink III provides a guided method that you can use to calculate the standard density of your gas if you do not know it.

4.4.3 Configure Gas Standard Volume Flow Measurement Unit

Display
ProLink III Device Tools Configuration Process Measurement Flow Gas Standard Volume Flow Unit
DeltaV AMS Configure Manual Setup Measurement Gas Standard Volume Flow Unit
Siemens PDM Device Manual Setup Measurement Gas Standard Volume Flow Unit
Menu Configuration Process Measurement Flow Variables Volume Flow Settings Units
Gas Standard Volume Flow Measurement Unit specifies the unit of measure that will be used for the gas
standard volume (GSV) flow rate. The unit used for gas standard volume total and gas standard volume inventory is derived from this unit.
Prerequisites
Before you configure Gas Standard Volume Flow Measurement Unit, be sure that Volume Flow Type is set to Gas Standard Volume.
Procedure
Set Gas Standard Volume Flow Measurement Unit to the unit you want to use.
Default: SCFM (Standard Cubic Feet per Minute)
40 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 41
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Gas Standard Volume Flow Measurement Unit
The transmitter provides a standard set of measurement units for Gas Standard Volume Flow Measurement Unit, plus one user-defined special measurement unit. Different communications tools may use different
labels for the units.
Unit description
Normal cubic meters per second
Normal cubic meters per minute
Normal cubic meters per hour NCMH Nm3/hr m³/h normal 1590
Normal cubic meters per day NCMD Nm3/day m³/d normal 1591
Normal liter per second NLPS NLPS L/s normal 1592
Normal liter per minute NLPM NLPM L/min normal 1593
Normal liter per hour NLPH NLPH L/h normal 1594
Normal liter per day NLPD NLPD NL/d normal 1595
Standard cubic feet per second SCFS SCFS ft3/min std. 1360
Standard cubic feet per minute SCFM SCFM ft3/s std. 1604
Standard cubic feet per hour SCFH SCFH ft3/h std. 1361
Standard cubic feet per day SCFD SCFD ft3/d std. 1605
Standard cubic meters per second
Display ProLink III PROFIBUS PA host Host code
NCMS Nm3/sec m³/s normal 1588
NCMM Nm3/min m³/min normal 1589
SCMS Sm3/sec m³/s std. 1596
Label
Standard cubic meters per minute
Standard cubic meters per hour
Standard cubic meters per day SCMD Sm3/day Sm³/d std. 1599
Standard liter per second SLPS SLPS L/s std. 1600
Standard liter per minute SLPM SLPM L/min std. 1601
Standard liter per hour SLPH SLPH L/h std. 1602
Standard liter per day SLPD SLPD L/d std. 1603
Special measurement unit SPECIAL Special Special 1999
Configuration and Use Manual 41
SCMM Sm3/min m³/min std. 1597
SCMH Sm3/hr m³/h std. 1598
Page 42
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
Define a special measurement unit for gas standard volume flow
Display
ProLink III
DeltaV AMS
Siemens PDM
Menu Configuration Process Measurement Flow Variables Volume Flow Settings Units SPECIAL
Device Tools Configuration Process Measurement Flow Gas Standard Volume Flow Unit Special
Configure Manual Setup Measurements Optional Setup Special Units Special Gas Standard Volume Units
Device Manual Setup Measurements Optional Setup Special Units Special Gas Standard Volume Units
A special measurement unit is a user-defined unit of measure that allows you to report process data, totalizer data, and inventory data in a unit that is not available in the transmitter. A special measurement unit is calculated from an existing measurement unit using a conversion factor.
Procedure
1. Specify Base Gas Standard Volume Unit.
Base Gas Standard Volume Unit is the existing gas standard volume unit that the special unit will be
based on.
2. Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
3. Calculate Gas Standard Volume Flow Conversion Factor as follows:
a) x base units = y special units
b) Gas Standard Volume Flow Conversion Factor = x ÷ y
4. Enter the Gas Standard Volume Flow Conversion Factor.
The original gas standard volume flow value is divided by this conversion factor.
5. Set Gas Standard Volume Flow Label to the name you want to use for the gas standard volume flow
unit.
6. Set Gas Standard Volume Total Label to the name you want to use for the gas standard volume total
and gas standard volume inventory unit.
The special measurement unit is stored in the transmitter. You can configure the transmitter to use the special measurement unit at any time.
Example: Defining a special measurement unit for gas standard volume flow
You want to measure gas standard volume flow in thousands of standard cubic feet per minute.
1. Set Base Gas Standard Volume Unit to SCFM.
2. Set Base Time Unit to minutes (min).
3. Calculate the conversion factor:
a. One thousands of standard cubic feet per minute = 1000 cubic feet per minute
b. Gas Standard Volume Flow Conversion Factor = 1 ÷ 1000 = 0.001
4. Set Gas Standard Volume Flow Conversion Factor to 0.001.
42 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 43
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021
5. Set Gas Standard Volume Flow Label to KSCFM.
6. Set Gas Standard Volume Total Label to KSCF.

4.4.4 Configure Gas Standard Volume Flow Cutoff

Display
ProLink III
DeltaV AMS
Siemens PDM
Menu Configuration Process Measurement Flow Variables Volume Flow Settings Low Flow Cutoff
Device Tools Configuration Process Measurement Flow Gas Standard Volume Flow Cutoff
Configure Manual Setup Measurements Gas Standard Volume Flow Cutoff
Device Manual Setup Measurements Gas Standard Volume Flow Cutoff
Gas Standard Volume Flow Cutoff specifies the lowest gas standard volume flow rate that will reported as
measured. All gas standard volume flow rates below this cutoff will be reported as 0.
Procedure
Set Gas Standard Volume Flow Cutoff to the value you want to use.
Default: 0.0
Range: 0.0 to any positive value
Interaction between Gas Standard Volume Flow Cutoff and mA Output Cutoff
Gas Standard Volume Flow Cutoff defines the lowest Gas Standard Volume flow value that the transmitter will report as measured. mA Output Cutoff defines the lowest flow rate that will be reported via the mA Output. If mA Output Process Variable is set to Gas Standard Volume Flow Rate, the volume flow rate reported via the mA Output is controlled by the higher of the two cutoff values.
Gas Standard Volume Flow Cutoff affects both the gas standard volume flow values reported through outputs and the gas standard volume flow values used in other transmitter behavior (for example, events defined on gas standard volume flow).
mA Output Cutoff affects only flow values reported via the mA Output.
Example: Cutoff interaction with mA Output Cutoff lower than Gas Standard Volume Flow Cutoff
Configuration:
mA Output Process Variable for the primary mA Output: Gas Standard Volume Flow Rate
Frequency Output Process Variable: Gas Standard Volume Flow Rate
mA Output Cutoff for the primary mA Output: 10 SLPM (standard liters per minute)
Gas Standard Volume Flow Cutoff: 15 SLPM
Result: If the gas standard volume flow rate drops below 15 SLPM, the volume flow will be reported as 0, and 0 will be used in all internal processing.
Configuration and Use Manual 43
Page 44
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
Example: Cutoff interaction with mA Output Cutoff higher than Gas Standard Volume Flow Cutoff
Configuration:
mA Output Process Variable for the primary mA Output: Gas Standard Volume Flow Rate
Frequency Output Process Variable: Gas Standard Volume Flow Rate
mA Output Cutoff for the primary mA Output: 15 SLPM (standard liters per minute)
Gas Standard Volume Flow Cutoff: 10 SLPM
Result:
If the gas standard volume flow rate drops below 15 SLPM but not below 10 SLPM:The primary mA Output will report zero flow.
The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all
internal processing.
If the gas standard volume flow rate drops below 10 SLPM, both outputs will report zero flow, and 0 will be
used in all internal processing.

4.5 Configure density measurement

The density measurement parameters control how density is measured and reported. Density measurement is used with mass flow rate measurement to determine liquid volume flow rate.

4.5.1 Configure Density Measurement Unit

Display
ProLink III Device Tools Configuration Process Measurement Density Density Unit
DeltaV AMS Configure Manual Setup Measurements Density Density Unit
Siemens PDM Device Manual Setup Measurements Density Density Unit
Density Measurement Unit controls the measurement units that will be used in density calculations and reporting.
Restriction
If the API Referral application is enabled, you cannot change the density measurement unit here. The density measurement unit is controlled by the API table selection.
Procedure
Set Density Measurement Unit to the option you want to use.
Default: g/cm3 (grams per cubic centimeter)
Menu Configuration Process Measurement Density Units
44 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 45
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021
Options for Density Measurement Unit
The transmitter provides a standard set of measurement units for Density Measurement Unit. Different communications tools may use different labels.
Unit description
Specific gravity
Grams per cubic centimeter g/cm3 g/cm3 g/cm³ 1100
Grams per liter g/L g/l g/L 1105
Grams per milliliter g/mL g/ml g/ml 1104
Kilograms per liter kg/L kg/l kg/L 1103
Kilograms per cubic meter kg/m3 kg/m3 kg/m³ 1097
Pounds per U.S. gallon lb/gal lbs/USgal lb/gal 1108
Pounds per cubic foot lb/ft3 lbs/ft3 lb/ft³ 1107
Pounds per cubic inch lb/in3 lbs/in3 lb/in³ 1106
Degrees API API API °API 1113
Short ton per cubic yard STon/yd3 sT/yd3 STon/yd³ 1109
(1) Non-standard calculation. This value represents line density divided by the density of water at 60 °F (15.6 °C).
(1)
Display ProLink III PROFIBUS PA host Host code
SGU SGU SGU 1114
Label

4.5.2 Configure Density Damping

Display
ProLink III Device Tools Configuration Process Measurement Density Density Damping
DeltaV AMS Configure Manual Setup Measurements Density Damping
Siemens PDM Device Manual Setup Measurements Density Damping
Menu Configuration Process Measurement Density Damping
Density Damping controls the amount of damping that will be applied to density data.
Damping is used to smooth out small, rapid fluctuations in process measurement. The damping value specifies the time period, in seconds, over which the transmitter will spread changes in the process variable. At the end of the interval, the internal value of the process variable (the damped value) will reflect 63% of the change in the actual measured value.
Procedure
Set Density Damping to the desired value.
Default: 1.28 seconds
Range: 0.0 to 60 seconds
Tip
A high damping value makes the process variable appear smoother because the reported value changes
slowly.
Configuration and Use Manual 45
Page 46
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
A low damping value makes the process variable appear more erratic because the reported value changes
more quickly.
The combination of a high damping value and rapid, large changes in density can result in increased
measurement error.
Whenever the damping value is non-zero, the damped value will lag the actual measurement because the
damped value is being averaged over time.
In general, lower damping values are preferable because there is less chance of data loss, and less lag time
between the actual measurement and the damped value.
If a number greater than 60 is entered, it is automatically changed to 60.
Effect of Density Damping on volume measurement
Density Damping affects liquid volume measurement. Liquid volume values are calculated from the damped density value rather than the measured density value. Density Damping does not affect gas standard volume measurement.
Interaction between Density Damping and mA Output Damping
When the mA Output is configured to report density, both Density Damping and mA Output Damping are applied to the reported density value.
Density Damping controls the rate of change in the value of the process variable in transmitter memory. mA Output Damping controls the rate of change reported via the mA Output.
If mA Output Source is set to Density, and both Density Damping and mA Output Damping are set to non­zero values, density damping is applied first, and the mA Output damping calculation is applied to the result of the first calculation. This value is reported over the mA Output.

4.5.3 Configure Density Cutoff

Display
ProLink III Device Tools Configuration Process Measurement Density Density Cutoff
DeltaV AMS Configure Manual Setup Measurements Density Cutoff
Siemens PDM Device Manual Setup Measurements Density Cutoff
Density Cutoff specifies the lowest density value that will be reported as measured. All density values below this cutoff will be reported as 0.
Procedure
Set Density Cutoff to the value you want to use.
Default: 0.2 g/cm
Range: 0.0 g/cm3 to 0.5 g/cm
Menu Configuration Process Measurement Density Cutoff
3
3
46 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 47
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021
Effect of Density Cutoff on volume measurement
Density Cutoff affects liquid volume measurement. If the density value goes below Density Cutoff, the volume flow rate is reported as 0.

4.6 Configure temperature measurement

The temperature measurement parameters control how temperature data is processed. Temperature data is used in several different ways, including temperature compensation, API Referral, and concentration measurement.

4.6.1 Configure Temperature Measurement Unit

Display Menu Configuration Process Measurement Temperature Units
ProLink III Device Tools Configuration Process Measurement Temperature Temperature Unit
DeltaV AMS Configure Manual Setup Measurements Temperature Unit
Siemens PDM Device Manual Setup Measurements Temperature Unit
Temperature Measurement Unit specifies the unit that will be used for temperature measurement.
Procedure
Set Temperature Measurement Unit to the option you want to use.
Default: °C (Celsius)
Options for Temperature Measurement Unit
The transmitter provides a standard set of units for Temperature Measurement Unit. Different communications tools may use different labels for the units.
Unit description
Display ProLink III PROFIBUS-PA Host code
Degrees Celsius °C °C °C 1001
Degrees Fahrenheit °F °F °F 1002
Degrees Rankine °R °R °R 1003
Kelvin °K °K K 1000
Label

4.6.2 Configure Temperature Damping

Display
ProLink III Device Tools Configuration Process Measurement Temperature Temperature Damping
DeltaV AMS Configure Manual Setup Measurements Temperature Damping
Siemens PDM Device Manual Setup Measurements Temperature Damping
Menu Configuration Process Measurement Temperature Damping
Configuration and Use Manual 47
Page 48
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
Temperature Damping controls the amount of damping that will be applied to temperature data from the sensor. Temperature Damping is not applied to external temperature data.
Damping is used to smooth out small, rapid fluctuations in process measurement. The damping value specifies the time period, in seconds, over which the transmitter will spread changes in the process variable. At the end of the interval, the internal value of the process variable (the damped value) will reflect 63% of the change in the actual measured value.
Procedure
Set Temperature Damping to the desired value.
Default: 4.8 seconds
Range: 0.0 to 80 seconds
Note
If a number greater than 80 is entered, it is automatically changed to 80.
Tip
A high damping value makes the process variable appear smoother because the reported value changes
slowly.
A low damping value makes the process variable appear more erratic because the reported value changes
more quickly.
The combination of a high damping value and rapid, large changes in temperature can result in increased
measurement error.
Whenever the damping value is non-zero, the damped value will lag the actual measurement because the
damped value is being averaged over time.
In general, lower damping values are preferable because there is less chance of data loss, and less lag time
between the actual measurement and the damped value.
Effect of Temperature Damping on process measurement
Temperature Damping affects all processes and algorithms that use temperature data from the internal sensor RTD.
Temperature compensation
Temperature compensation adjusts process measurement to compensate for the effect of temperature on the sensor tubes.
API Referral
Temperature Damping affects API Referral process variables only if the transmitter is configured to use temperature data from the sensor. If an external temperature value is used for API Referral, Temperature Damping does not affect API Referral process variables.
Concentration measurement
Temperature Damping affects concentration measurement process variables only if the transmitter is configured to use temperature data from the sensor. If an external temperature value is used for concentration measurement, Temperature Damping does not affect concentration measurement process variables.
48 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 49
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021

4.7 Configure Pressure Measurement Unit

Display
ProLink III
DeltaV AMS
Siemens PDM
Menu Configuration Process Measurement Pressure Units
Device Tools Configuration Process Measurement Pressure Compensation Pressure Unit
Configure Manual Setup Measurements Optional Setup External Variables Pressure Unit
Device Manual Setup Measurements Optional Setup External Variables Pressure Unit
Pressure Measurement Unit controls the measurement unit used for pressure. This unit must match the unit
used by the external pressure device.
Pressure data is used for pressure compensation and for API Referral. The device does not measure pressure directly. You must set up a pressure input.
Procedure
Set Pressure Measurement Unit to the desired unit.
Default: psi

4.7.1 Options for Pressure Measurement Unit

The transmitter provides a standard set of measurement units for Pressure Measurement Unit. Different communications tools may use different labels for the units. In most applications, set Pressure Measurement Unit to match the pressure measurement unit used by the remote device.
Unit description
Display ProLink III PROFIBUS PA host Host code
Label
Feet water @ 68 °F ftH2O @68°F Ft Water @ 68°F ftH2O (68°F) 1154
Inches water @ 4 °C inH2O @4°C In Water @ 4°C inH2O (4°C) 1147
Inches water @ 60 °F inH2O @60°F In Water @ 60°F inH2O (60°F) 33003
Inches water @ 68 °F inH2O @68°F In Water @ 68°F inH2O (68°F) 1148
Millimeters water @ 4 °C mmH2O @4°C mm Water @ 4°C mmH2O (4°C) 1150
Millimeters water @ 68 °F mmH2O @68°F mm Water @ 68°F mmH2O (68°F) 1151
Millimeters mercury @ 0 °C mmHg @0°C mm Mercury @ 0°C mmHg (0°C) 1158
Inches mercury @ 0 °C inHg @0°C In Mercury @ 0°C inHg (0°C) 1156
Pounds per square inch psi PSI psi 1141
Bar bar bar bar 1137
Millibar mbar millibar mbar 1138
Grams per square centimeter g/cm2 g/cm2 gf/cm² 1144
Kilograms per square centimeter
Pascals Pa pascals Pa 1130
Kilopascals kPA Kilopascals kPa 1133
kg/cm2 kg/cm2 Kgf/cm² 1145
Configuration and Use Manual 49
Page 50
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
Unit description
Display ProLink III PROFIBUS PA host Host code
Megapascals mPA Megapascals MPa 1132
Torr @ 0 °C torr Torr @ 0°C torr 1139
Atmospheres atm atms atm 1140
Label

4.8 Configure Velocity Measurement Unit

Display Menu Configuration Process Measurement Velocity Units
ProLink III Device Tools Configuration Process Measurement Velocity Unit
DeltaV AMS Configure Manual Setup Measurements 2 Approximate Velocity Velocity Unit
Siemens PDM Device Manual Setup Measurements 2 Approximate Velocity Velocity Unit
Velocity Measurement Unit controls the measurement unit used to report velocity.
Procedure
Set Velocity Measurement Unit to the desired unit.
Default: m/sec

4.8.1 Options for Velocity Measurement Unit

The transmitter provides a standard set of measurement units for Velocity Measurement Unit. Different communications tools may use different labels.
Unit description
Display ProLink III PROFIBUS PA host Host code
Feet per minute ft/min ft/min ft/min 1070
Feet per second ft/s ft/sec ft/s 1067
Inches per minute in/min in/min in/min 1069
Inches per second in/s in/sec in/s 1066
Meters per hour m/h m/hr m/h 1063
Meters per second m/s m/sec m/s 1061
Label

4.9 Energy flow

Energy flow is the energy content of the process gas flowing through the pipe per units of time. The 5700 can compute the energy flow by taking the Analog Output function block input using the PROFIBUS-PA connection. The calculated energy flow is available on the Energy Flow process variable.
50 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 51
Configuration and Use Manual Configure process measurement
MMI- 20070546 June 2021

4.9.1 Set up energy flow

Prerequisites
If you plan to poll an external device, assign either of the Analog Output function block channels as Calorific Value.
Procedure
1. From the display, go to Menu Configuration Process Measurement Energy Flow.
2. Select Units for Calorific Value and Energy Flow.
3. To poll an external device, set up either Analog Output function block for Calorific Value.
4. Set up energy flow on an mA Output or Frequency Output.
Option Description
mAO a. Configure an mA Output
b. Select Energy Flow as a source.
FO a. Configure a Frequency Output
b. Select Energy Flow as a source.

4.9.2 Options for Energy Flow Unit

Unit description
PROFIBUS PA host Unit code for PROFIBUS PA
Megajoule per minute MJ/min 1443
Megajoule per hour MJ/h 1196
British thermal unit per minute Btu/min 1446
British thermal unit per hour Btu/h 1197
British thermal unit per day Btu/day 1447
Label

4.9.3 Options for Calorific Value Unit

Unit description
Megajoule per kilogram MJ/kg 1207
Megajoule per meter cube MJ/m
PROFIBUS PA host Unit code for PROFIBUS PA
3
Label
33006
British thermal unit per pound Btu/lb 1516
British thermal unit per standard cubic feet Btu/scf 33005
Configuration and Use Manual 51
Page 52
Configure process measurement Configuration and Use Manual
June 2021 MMI- 20070546
4.10 Piecewise linearization (PWL) for calibrating gas
meters
Piecewise linearization (PWL) can linearize the measurements of flow meters for greater accuracy in order to measure gas over a wide range of flow rates. PWL does not apply when measuring liquid flow. When better accuracy is required over the published gas measurement specifications, an Emerson-approved independent gas laboratory can calibrate gas up to 10 PWL adjustment points.
For more information, see the white paper, The Practical Application of Multi-Point Piecewise Linear Interpolation (PWL) and Other Developing Trends with Coriolis Meters for Natural Gas Custody Transfer Applications, available at
www.emerson.com.
The PWL feature is available in ProLink III, so you can view the points that are stored and capture them in the uploaded and downloaded configuration files.

4.10.1 Configure PWL

Display Not available
ProLink III Device Tools Configuration Process Measurement Piecewise Linearization for Gas (PWL)
DeltaV AMS Configure Manual Setup Measurements Optional Setup Gas Linearization
Siemens PDM Device Manual Setup Measurements Optional Setup Gas Linearization
The PROFIBUS PA host shows only the 10 point linearization table values.
52 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 53
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021

5 Configure process measurement applications

5.1 Set up the API Referral application

The API Referral application corrects line density to reference temperature and reference pressure according to American Petroleum Institute (API) standards. The resulting process variable is referred density.
Restriction
The API Referral application is not compatible with the following applications:
Gas Standard Volume Measurement (GSV)
Piecewise linearization (PWL)
Advanced Phase Measurement
Concentration measurement

5.1.1 Set up the API Referral application using the display

Enable the API Referral application using the display
The API Referral application must be enabled before you can perform any setup. If the API Referral application was enabled at the factory, you do not need to enable it now.
Prerequisites
The API Referral application must be licensed on your transmitter.
Procedure
1. Choose Menu Configuration Process Measurement.
2. Choose Flow Variables Volume Flow Settings and ensure that Flow Type is set to Liquid.
3. Return to the Process Measurement menu.
4. If the concentration measurement application is displayed in the list, choose Concentration
Measurement and ensure that Enabled/Disabled is set to Disabled.
The concentration measurement application and the API Referral application cannot be enabled simultaneously.
5. If the gas linearization application displays in the list, choose Gas Linearization and verify that Enable/
Disable is set to Disabled.
The gas linearization application and the API Referral application cannot be enabled simultaneously.
6. If the Adv Phase Measurement application displays in the list, choose Adv Phase Measurement and
verify that Application Setup is set to Disabled.
The Advance Phase Measurement application and the API Referral application cannot be enabled simultaneously.
Configuration and Use Manual 53
Page 54
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Configure API Referral using the display
The API Referral parameters specify the API table, measurement units, and reference values to be used in referred density calculations.
Prerequisites
You will need API documentation for the API table that you select.
Depending on your API table, you may need to know the thermal expansion coefficient (TEC) for your process fluid.
You must know the reference temperature and reference pressure that you want to use.
Procedure
1. Choose Menu Configure Process Measurement API Referral.
2. Set API Table to the API table that you want to use to calculate referred density.
Each API table is associated with a specific set of equations. Choose your API table based on your process fluid and the measurement unit that you want to use for referred density.
Your choice also determines the API table that will be used to calculate the correction factor for volume (CTPL or CTL).
3. Refer to the API documentation and confirm your table selection.
a) Verify that your process fluid falls within range for line density, line temperature, and line
pressure.
b) Verify that the referred density range of the selected table is adequate for your application.
4. If you chose a C table, enter Thermal Expansion Coefficient (TEC) for your process fluid.
Acceptable limits:
230.0 x 10-6 to 930.0 x 10-6 per °F
414.0 x 10-6 to 1674.0 x 10-6 per °C
5. If required, set Reference Temperature to the temperature to which density will be corrected in
referred density calculations.
The default reference temperature is determined by the selected API table.
6. If required, set Reference Pressure to the pressure to which density will be corrected in referred
density calculations.
The default reference pressure is determined by the selected API table.
Set up temperature and pressure data for API Referral using the display
The API Referral application uses temperature and, optionally, pressure data in its calculations. You must decide how to provide this data, then perform the required configuration and setup.
Note
Fixed values for temperature or pressure are not recommended. Using a fixed temperature or pressure value may produce inaccurate process data.
54 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 55
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
Prerequisites
The pressure measurement must be gauge pressure, not atmospheric pressure.
The pressure device must use the pressure unit that is configured in the transmitter.
If you are using an external temperature device, it must use the temperature unit that is configured in the transmitter.
Procedure
1. Choose the method to be used to supply temperature data, and perform the required setup.
Method Description Setup
Internal temperature
Digital communications
Temperature data from the on­board temperature sensor (RTD) will be used for all measurements and calculations. No external temperature data will be available.
A host writes temperature data to the meter at appropriate intervals. This data will be available in addition to the internal temperature data.
a. Choose Menu Configuration Process Measurement
Temperature.
b. Set External Temperature to Off.
a. Choose Menu Configuration Process Measurement
Temperature.
b. Set External Temperature to On.
c. Perform the necessary host programming and
communications setup to write temperature data to the transmitter at appropriate intervals.
2. Choose the method to be used to supply pressure data, and perform the required setup.
Method
Digital communications
Description Setup
A host writes pressure data to the meter at appropriate intervals.
a. Choose Menu Configuration Process Measurement
b. Set External Pressure to On.
c. Perform the necessary host programming and
PressureExternal Pressure.
communications setup to write pressure data to the transmitter at appropriate intervals.
Postrequisites
Choose Menu Service Tools Service Data View Process Variables and verify the values for External Temperature and External Pressure.
Need help?
If the value is not correct:
Ensure that the external device and the meter are using the same measurement unit.
For digital communications:Verify that the host has access to the required data.
Configuration and Use Manual 55
Page 56
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Verify that the output variable is being correctly received and processed by the transmitter.

5.1.2 Set up the API Referral application using ProLink III

Enable the API referral application using ProLink III
The API referral application must be enabled before you can perform any setup. If the API referral application was enabled at the factory, you do not need to enable it now.
Prerequisites
The API referral application must be licensed on your transmitter.
Procedure
1. Choose Device Tools Configuration Process Measurement Flow and ensure that Volume
Flow Type is set to Liquid Volume.
2. Choose Device Tools Configuration Process Measurement Advance Phase Measurement
APM Status and ensure that Application Status is set to Disable.
The Advance Phase Measurement application and the API referral application cannot be enabled simultaneously.
3. Choose Device Tools Configuration Transmitter Options.
4. If the concentration measurement application is enabled, disable it and select Apply.
The concentration measurement application and the API referral application cannot be enabled simultaneously.
5. If the gas linearization application is enabled, disable it and select Apply.
The gas linearization application and the API referral application cannot be enabled simultaneously.
Configure API Referral using ProLink III
The API Referral parameters specify the API table, measurement units, and reference values to be used in referred density calculations.
Prerequisites
You will need API documentation for the API table that you select.
Depending on your API table, you may need to know the thermal expansion coefficient (TEC) for your process fluid.
You must know the reference temperature and reference pressure that you want to use.
Procedure
1. Choose Device Tools Configuration Process Measurement API Referral.
2. Specify the API table to use to calculate referred density.
Each API table is associated with a specific set of equations.
a) Set Process Fluid to the API table group that your process fluid belongs to.
56 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 57
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
API table group Process fluids
A tables Generalized crude and JP4
B tables Generalized products: Gasoline, jet fuel, aviation fuel, kerosene, heating oils,
fuel oils, diesel, gas oil
C tables Liquids with a constant base density or known thermal expansion coefficient
(TEC). You will be required to enter the TEC for your process fluid.
D tables Lubricating oils
E tables NGL (Natural Gas Liquids) and LPG (Liquid Petroleum Gas)
b) Set Referred Density Measurement Unit to the measurement units that you want to use for
referred density.
c) Select Apply.
These parameters uniquely identify the API table to be used to calculate referred density. The selected API table is displayed, and the meter automatically changes the density unit, temperature unit, pressure unit, and reference pressure to match the API table.
Your choice also determines the API table that will be used to calculate the correction factor for volume (CTPL or CTL).
Restriction
Not all combinations are supported by the API Referral application. See the list of API tables in this manual.
3. Refer to the API documentation and confirm your table selection.
a) Verify that your process fluid falls within range for line density, line temperature, and line
pressure.
b) Verify that the referred density range of the selected table is adequate for your application.
4. If you chose a C table, enter Thermal Expansion Coefficient (TEC) for your process fluid.
Acceptable limits:
230.0 x 10-6 to 930.0 x 10-6 per °F
414.0 x 10-6 to 1674.0 x 10-6 per °C
5. Set Reference Temperature to the temperature to which density will be corrected in referred density
calculations. If you choose Other, select the temperature measurement unit and enter the reference temperature.
6. Set Reference Pressure to the pressure to which density will be corrected in referred density
calculations.
Configuration and Use Manual 57
Page 58
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Set up temperature and pressure data for API Referral using ProLink III
The API Referral application uses temperature and, optionally, pressure data in its calculations. You must decide how to provide this data, then perform the required configuration and setup.
Note
Fixed values for temperature or pressure are not recommended. Using a fixed temperature or pressure value may produce inaccurate process data.
Prerequisites
The pressure measurement must be gauge pressure, not atmospheric pressure.
The pressure device must use the pressure unit that is configured in the transmitter.
If you are using an external temperature device, it must use the temperature unit that is configured in the transmitter.
Procedure
1. Choose Device Tools Configuration Process Measurement API Referral.
2. Choose the method to be used to supply temperature data, and perform the required setup.
Option Description Setup
Digital communications
A host writes temperature data to the meter at appropriate intervals. This data will be available in addition to the internal RTD temperature data.
a. Set Line Temperature Source to Fixed Value or Digital
Communications.
b. Select Apply.
c. Perform the necessary host programming and
communications setup to write temperature data to the meter at appropriate intervals.
3. Choose the method you will use to supply pressure data, and perform the required setup.
Option
Digital communications
Description Setup
A host writes pressure data to the meter at appropriate intervals.
a. Set Pressure Source to Fixed Value or Digital
b. Perform the necessary host programming and
Communications.
communications setup to write pressure data to the meter at appropriate intervals.
Postrequisites
If you are using external temperature data, verify the external temperature value displayed in the Inputs group on the ProLink III main window.
The current pressure value is displayed in the External Pressure field. Verify that the value is correct.
Need help?
If the value is not correct:
Ensure that the external device and the meter are using the same measurement unit.
58 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 59
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
For digital communications:Verify that the host has access to the required data.
Verify that the output variable is being correctly received and processed by the transmitter.

5.1.3 Set up the API referral application using a PROFIBUS-PA host

This section guides you through the tasks required to set up and implement the API referral application using a PROFIBUS-PA host.
Enable the API referral application using a PROFIBUS-PA host
DeltaV AMS Overview Device Information Licenses Enable/Disable Application Volume Flow
Siemens PDM Overview Device Information Licenses Enable/Disable Application Volume Flow Type
The API referral application must be enabled before you can perform any setup. If the API referral application was enabled at the factory, you do not need to enable it now.
Prerequisites
The API referral application must be licensed on your transmitter.
Volume Flow Type must be set to Liquid.
Procedure
1. Ensure that the volume flow is set to Liquid.
2. If the concentration measurement application is enabled, disable it.
The concentration measurement application and the API referral application cannot be enabled simultaneously.
3. If the gas linearization application is enabled, disable it.
The gas linearization application and the API referral application cannot be enabled simultaneously.
4. If Advance Phase Measurement Output Type is other than Disabled, disable it.
The Advance Phase Measurement application and the API referral application cannot be enabled simultaneously.
Configure the API referral application using a PROFIBUS PA host
DeltaV AMS
Siemens PDM Device Manual Setup Measurements Optional Setup API Referral
The API Referral parameters specify the API table, measurement units, and reference values to be used in referred density calculations.
Configure Manual Setup Measurements Optional Setup API Referral
Prerequisites
Prerequisites
You will need API documentation for the API table that you select.
Configuration and Use Manual 59
Page 60
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Depending on your API table, you may need to know the thermal expansion coefficient (TEC) for your process fluid.
You must know the reference temperature and reference pressure that you want to use.
Procedure
1. Choose API Referral Setup.
2. Specify the API table that you want to use to calculate referred density.
Each API table is associated with a specific set of equations.
a) Set API Table Number to the number that matches the API table units that you want to use for
referred density.
Your choice also determines the measurement unit to be used for temperature and pressure, and the default values for reference temperature and reference pressure.
API table number
Measurement unit for referred density
Temperature measurement unit
Pressure measurement unit
Default reference temperature
Default reference pressure
5 °API °F psi (g) 60 °F 0 psi (g)
(1)
6
°API °F psi (g) 60 °F 0 psi (g)
23 SGU °F psi (g) 60 °F 0 psi (g)
(1)
24
SGU °F psi (g) 60 °F 0 psi (g)
53 kg/m³ °C kPa (g) 15 °C 0 kPa (g)
(1)
54
kg/m³ °C kPa (g) 15 °C 0 kPa (g)
59 kg/m³ °C kPa (g) 20 °C 0 kPa (g)
60 kg/m³ °C kPa (g) 20 °C 0 kPa (g)
(1) Used only with API Table Letter = C.
b) Set API Table Letter to the letter of the API table group that is appropriate for your process fluid.
API table letter Process fluids
(1)
A
(1)
B
(2)
C
(1)
D
(3)
E
Generalized crude and JP4
Generalized products: Gasoline, jet fuel, aviation fuel, kerosene, heating oils, fuel oils, diesel, gas oil
Liquids with a constant base density or known thermal expansion coefficient (TEC). You will be required to enter the TEC for your process fluid.
Lubricating oils
NGL (Natural Gas Liquids) and LPG (Liquid Petroleum Gas)
(1) Used only with API Table Number= 5, 23, 53, 59, or 60. (2) Used only with API Table Number= 6, 24, or 54. (3) Used only with API Table Number = 23, 24, 53, 54, 59, or 60.
60 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 61
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
API Table Number and API Table Letter uniquely identify the API table. The selected API table is displayed, and the meter automatically changes the density unit, temperature unit, pressure unit, reference temperature, and reference pressure to match the API table.
Your choice also determines the API table that will be used to calculate the correction factor for volume (CTPL or CTL).
Restriction
Not all combinations are supported by the API Referral application. See the list of API tables in this manual.
3. If you chose a C table, enter Thermal Expansion Coefficient (TEC) for your process fluid.
Acceptable limits:
230.0 x 10-6 to 930.0 x 10-6 per °F
414.0 x 10-6 to 1674.0 x 10-6 per °C
4. Refer to the API documentation and confirm your table selection.
a) Verify that your process fluid falls within range for line density, line temperature, and line
pressure.
b) Verify that the referred density range of the selected table is adequate for your application.
5. If required, set Reference Temperature to the temperature to which density will be corrected in
referred density calculations.
The default reference temperature is determined by the selected API table.
6. If required, set Reference Pressure to the pressure to which density will be corrected in referred
density calculations.
The default reference pressure is determined by the selected API table. API referral requires gauge pressure.
Set up temperature and pressure data for API referral using a PROFIBUS PA host
DeltaV AMS
Siemens PDM Device Manual Setup Measurements Optional Setup External Variables External
The API Referral application uses temperature and, optionally, pressure data in its calculations. You must decide how to provide this data, then perform the required configuration and setup.
Note
Fixed values for temperature or pressure are not recommended. Using a fixed temperature or pressure value may produce inaccurate process data.
Configure Manual Setup Measurements Optional Setup External Variables External Temperature
Temperature
Procedure
1. Choose the method to be used to supply temperature data, and perform the required setup.
Configuration and Use Manual 61
Page 62
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Method Description Setup
Internal RTD temperature data
Digital communications
Temperature data from the on­board temperature sensor (RTD) is used.
A host writes temperature data to the meter at appropriate intervals. This data will be available in addition to the internal RTD temperature data.
Set Temperature Compensation to Disable.
a. Set Temperature Compensation to Enable.
b. Choose one of the following options:
For DeltaV AMS, Configure Manual Setup Classic
View Function Block Analog Output Block
For Siemens PDM, Device Manual Setup Classic
View Function Block Analog Output Block
c. Select either AO Block 1 or AO Block 2.
d. Set IN Channel as Temperature.
e. Set PV Scale Unit Index to the matching host
Temperature Unit.
f. Set Out Scale Unit Index to the matching device
Temperature Unit.
g. Ensure that the corresponding AO block is assigned to the
slot.
2. Perform the required setup for digital communications so that the host writes pressure data to the meter at appropriate intervals.
a) Choose one of the following options:
For DeltaV AMS, Configure Manual Setup Measurements Optional Setup
External Variables External Pressure
For Siemens PDM, Device Manual Setup Measurements Optional Setup External
Variables External Pressure
b) Set Pressure Compensation to Enable.
c) Choose Configure Manual Setup Classic View AI/AO Block Channel Mapping
Analog Output Block.
d) Select either AO Block 1 or AO Block 2.
e) Set IN Channel as Pressure.
f) Set PV Scale Unit Index to the matching host Pressure Unit.
g) Set Out Scale Unit Index to the matching device Pressure Unit.
h) Ensure that the corresponding AO block is assigned to the slot.
Postrequisites
Need help?
If the value is not correct:
62 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 63
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
Ensure that the external device and the meter are using the same measurement unit.
For digital communications:Verify that the host has access to the required data.
Verify that the output variable is being correctly received and processed by the transmitter.

5.1.4 API tables supported by the API Referral application

The API tables listed here are supported by the API Referral application.
Table 5-1: API tables, process fluids, measurement units, and default reference values
Process fluid
Generalized crude and JP4
Generalized products (gasoline, jet fuel, aviation fuel, kerosene, heating oils, fuel oils, diesel, gas oil)
Liquids with a constant density base or known thermal expansion coefficient
(5)
API tables
(calculations)
Referred density
5A 6A Unit: °API
23A 24A Unit: SGU
53A 54A Unit: kg/m
5B 6B Unit: °API
23B 24B Unit: SGU
53B 54B Unit: kg/m
N/A 6C Unit: °API 60 °F 0 psi (g) API MPMS 11.1
N/A 24C Unit: SGU 60 °F 0 psi (g)
N/A 54C Unit: kg/m³ 15 °C 0 kPa (g)
(2)
(1)
CTL or CTPL
Referred density (API): unit and range
(3) (4)
Range: 0 to 100 °API
Range: 0.6110 to
1.0760 SGU
Range: 610 to 1075 kg/m³
Range: 0 to 85 °API
Range: 0.6535 to
1.0760 SGU
Range: 653 to 1075 kg/m³
Default reference temp
60 °F 0 psi (g) API MPMS 11.1
60 °F 0 psi (g)
3
3
15 °C 0 kPa (g)
60 °F 0 psi (g) API MPMS 11.1
60 °F 0 psi (g)
15 °C 0 kPa (g)
Default reference pressure
API standard
5D 6D Unit: °API
Range: 10 to +40 °API
23D 24D Unit: SGU
Lubricating oils
53D 54D Unit: kg/m³
Configuration and Use Manual 63
Range: 0.8520 to
1.1640 SGU
Range: 825 to 1164 kg/m³
60 °F 0 psi (g) API MPMS 11.1
60 °F 0 psi (g)
15 °C 0 kPa (g)
Page 64
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Table 5-1: API tables, process fluids, measurement units, and default reference values (continued)
API tables
Process fluid
NGL (natural gas liquids) and LPG (liquid petroleum gas)
(1) Each API table represents a specialized equation defined by the American Petroleum Institute for a specific combination
of process fluid, line conditions, and output.
(2) Referred density is calculated from line density. You must specify this table, either directly or by selecting the process
fluid and base density measurement unit.
(3) You do not need to specify this table. It is invoked automatically as a result of the previous table selection. (4) CTL is a correction factor based on online temperature. CTPL is a correction factor based on both line pressure and line
temperature. Calculation of CTL and CTPL for A, B, C, and D table products is in accordance with API MPMS Chapter
11.1. Calculation of CTL and CTPL for E table products is in accordance with API MPMS Chapters 11.2.2, 11.2.4, and
11.2.5.
(5) The Thermal Expansion Coefficient (TEC) replaces the referred density calculation. Use the CTL/CTPL table instead.
(calculations)
Referred density
23E 24E Unit: SGU 60 °F 0 psi (g) API MPMS 11.2.4
53E 54E Unit: kg/m³ 15 °C 0 psi (g)
59A 60A Unit: kg/m³ 20 °C 0 psi (g)
59B 60B Unit: kg/m³ 20 °C 0 psi (g)
59D 60D Unit: kg/m³ 20 °C 0 psi (g)
59E 60E Unit: kg/m³ 20 °C 0 psi (g)
(2)
(1)
CTL or CTPL
Referred density (API): unit and range
(3) (4)
Default reference temp
Default reference pressure
API standard

5.1.5 Process variables from the API Referral application

The API Referral application calculates several different process variables according to API standards.
CTPL
CTL
Referred density
API volume flow
Batch-weighted average density
Batch-weighted average temperature
API volume total
Correction factor based on line temperature and line pressure.
Correction factor based on line temperature at saturation conditions.
The measured density after CTL or CTPL has been applied.
The measured volume flow rate after CTL or CTPL has been applied. Also called corrected volume flow.
One density value is recorded for each unit of flow (e.g., barrel, liter). The average is calculated from these values. The average is reset when the API totalizer is reset. Not available unless a totalizer has been configured with Source set to Corrected Volume Flow.
One temperature value is recorded for each unit of flow (e.g., barrel, liter). The average is calculated from these values. The average is reset when the API totalizer is reset. Not available unless a totalizer has been configured with Source set to Temperature-Corrected Volume Flow.
The total API volume measured by the transmitter since the last API totalizer reset. Also called corrected volume total. Not available unless a totalizer has been configured with Source set to Corrected Volume Flow.
64 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 65
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
API volume inventory
The total API volume measured by the transmitter since the last API inventory reset. Also called corrected volume inventory. Not available unless an inventory has been configured with Source set to Corrected Volume Flow.

5.2 Set up concentration measurement

The concentration measurement application calculates concentration from line density and line temperature.

5.2.1 Preparing to set up concentration measurement

The procedure for setting up concentration measurement application depends on how your device was ordered and how you want to use the application. Review this information before you begin.
Requirements for concentration measurement
To use the concentration measurement application, the following conditions must be met:
The concentration measurement application must be enabled.
The API Referral application must be disabled.
The gas piecewise linearization (PWL) application must be disabled.
The Advanced Phase Measurement application must be disabled .
A concentration matrix must be loaded into one of the six slots on the transmitter.
Tip
In most cases, the concentration matrix that you ordered was loaded at the factory. If it was not, you have several options for loading a matrix. You can also build a matrix.
Temperature Source must be configured and set up.
One matrix must be selected as the active matrix (the matrix used for measurement).
Requirements for matrices
A matrix is the set of coefficients used to convert process data to concentration, plus related parameters. The matrix can be saved as a file.
The transmitter requires all matrices to be in .matrix format. You can use ProLink III to load matrices in other formats:
.edf (used by ProLink II)
.xml (used by ProLink III)
The transmitter can store matrices in two locations:
One of the six slots in memory
The transmitter's SD card
Any matrix in a slot is available for use. In other words, it can be selected as the active matrix and used for measurement. Matrices on the SD card are not available for use. Matrices must be loaded into a slot before they can be used for measurement.
All matrices in slots must use the same derived variable. Matrices on the SD card have no requirement for their derived variables to match.
Configuration and Use Manual 65
Page 66
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Requirements for derived variables
A derived variable is the process variable that a concentration matrix measures. All other process variables are calculated from the derived variable. There are eight possible derived variables. Each matrix is designed for one specific derived variable.
The transmitter can store up to six matrices in six slots. There are additional matrices on the transmitter's SD card. All matrices in the six slots must use the same derived variable. If you change the setting of Derived Variable, all matrices are deleted from the six slots. Any matrices on the transmitter's SD card are not affected.
Tip
Always ensure that Derived Variable is set correctly before loading matrices into slots.
Derived variables and net flow rate
If you want the transmitter to calculate Net Mass Flow Rate, the derived variable must be set to Mass Concentration (Density). If your matrix is not designed for Mass Concentration (Density), contact customer support for assistance.
If you want the transmitter to calculate Net Volume Flow Rate, the derived variable must be set to Volume Concentration (Density). If your matrix is not designed for Volume Concentration (Density), contact customer support for assistance.
Derived variables based on specific gravity
The following derived variables are based on specific gravity:
Specific Gravity
Concentration (Specific Gravity)
Mass Concentration (Specific Gravity)
Volume Concentration (Specific Gravity)
If you are using one of these derived variables, two additional parameters can be configured:
Reference Temperature of Water (default setting: 4 °C)
Water Density at Reference Temperature (default setting: 999.99988 kg/m³)
These two parameters are used to calculate specific gravity.
You cannot set these parameters from the display. If the default values are not appropriate, you must use another method to set them.
Optional tasks in setting up concentration measurement
The following tasks are optional:
Modifying names and labels
Configuring extrapolation alerts
66 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 67
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021

5.2.2 Set up concentration measurement using the display

This section guides you through most of the tasks related to setting up and implementing the concentration measurement application.
Restriction
This section does not cover building a concentration matrix. For detailed information on building a matrix, see the Micro Motion Enhanced Density Application Manual.
Enable concentration measurement using the display
The concentration measurement application must be enabled before you can perform any setup. If the concentration measurement application was enabled at the factory, you do not need to enable it now.
Prerequisites
The concentration measurement application must be licensed on your transmitter.
Disable the following applications before enabling concentration measurement as concentration measurement cannot be enabled at the same time:
API Referral
Piecewise linearization (PWL)
Gas Standard Volume
Procedure
1. Choose Menu Configuration Process Measurement.
2. Choose Flow Variables Volume Flow Settings and ensure that Flow Type is set to Liquid.
3. Return to the Process Measurement menu.
4. If the API Referral application is displayed in the menu, choose API Referral and ensure that Enabled/ Disabled is set to Disabled.
The concentration measurement application and the API Referral application cannot be enabled simultaneously.
5. If the Advanced Phase Measurement application is displayed in the menu, choose Advanced Phase Measurement Application Setup and ensure that Enabled/Disabled is set to Disabled.
6. Enable concentration measurement.
a) Choose Menu Configuration Process Measurement Concentration Measurement.
b) Set Enabled/Disabled to Enabled.
Load a concentration matrix from a USB drive using the display
At least one concentration matrix must be loaded into one of the six slots on your transmitter. You can load up to six matrices into slots. You can also copy matrices to the transmitter's SD card, and load them into slots at a later time.
Tip
In many cases, concentration matrices were ordered with the device and loaded at the factory. You may not need to load any matrices.
Configuration and Use Manual 67
Page 68
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is powered up. Failure to follow these instructions can cause an explosion resulting in injury or death.
Prerequisites
The concentration measurement application must be enabled on your device.
For each concentration matrix that you want to load, you need a file containing the matrix data. The transmitter's SD card and the ProLink III installation include a set of standard concentration matrices. Other matrices are available from Micro Motion.
Each concentration matrix file must be in .matrix format.
Tip
If you have a custom matrix on another device, you can save it to a file, then load it to the current device.
If you have a matrix file in a different format, you can load it using ProLink III.
The .matrix files must be copied to the root directory of a USB drive.
You must know the derived variable that the matrix is designed to calculate.
Important
All concentration matrices on your transmitter must use the same derived variable.
If you change the setting of Derived Variable, all existing concentration matrices will be deleted from the
six slots on the transmitter, but not from the SD card. Set Derived Variable before loading concentration matrices.
Procedure
1. Choose Menu Configuration Process Measurement Concentration Measurement
Configure Application and ensure that the setting of Derived Variable matches the derived variable used by your matrix. If it does not, change it as required and click Apply.
Important
If you change the setting of Derived Variable, all existing concentration matrices will be deleted from the six slots, but not from the transmitter's SD card. Verify the setting of Derived Variable before continuing.
2. Load the matrix.
a) Remove the cover from the transmitter's wiring compartment, open the snap flap to access the
service port, and insert the USB drive into the service port.
b) Choose Menu USB Options USB Drive --> Transmitter Upload Configuration File.
c) Set Config File Type to Concentration Measurement Matrix.
d) Select the .matrix file that you want to load, and wait for the transfer to complete.
3. Choose Yes or No when you are asked if you want to apply the settings.
68 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 69
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
The transmitter has six slots that are used to store concentration matrices. Any one of these can be used for measurement. The transmitter also has the capability to store multiple concentration matrices on its SD card. These cannot be used for measurement until they are moved to a slot.
Option Description
Yes The matrix is saved to the SD card, and the loading process continues with loading the
matrix into one of the slots.
No The matrix is saved to the SD card, and the loading process ends. You must load a matrix into
a slot before you can use it for measurement.
4. If you chose Yes, select the slot to load this matrix into, and wait until the load is complete.
You can load the matrix into any empty slot, or you can overwrite an existing matrix.
Postrequisites
If you loaded the matrix into a slot, choose Menu Configuration Process Measurement Concentration Measurement Configure Application Active Matrix and ensure that the matrix is listed.
If you loaded the matrix onto the SD card only, choose Menu Configuration Process Measurement Concentration Measurement Load Matrix and ensure that the matrix is listed.
Load a concentration matrix from the SD card using the display
If you have a concentration matrix on the transmitter's SD card, you can load it into one of the six slots on your transmitter. You cannot use the matrix for measurement until it has been loaded into a slot. You can load up to six matrices into slots.
Prerequisites
You must have one or more concentration matrices stored on the transmitter's SD card. The standard matrices are loaded to the SD card at the factory.
You must know the derived variable that the matrix is designed to calculate.
Procedure
1. Choose Menu Configuration Process Measurement Concentration Measurement and ensure
that the setting of Derived Variable matches the derived variable used by your matrix. If it does not, change it as required and click Apply.
Important
If you change the setting of Derived Variable, all existing concentration matrices will be deleted from the six slots, but not from the transmitter's SD card. Verify the setting of Derived Variable before continuing.
2. Choose Menu Configuration Process Measurement Concentration Measurement Load
Matrix. The transmitter displays a list of all matrices that are on the SD card.
3. Select the matrix that you want to load.
Configuration and Use Manual 69
Page 70
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
4. Select the slot that you want to load it into.
You can load the matrix into any empty slot, or you can overwrite an existing matrix.
Postrequisites
Choose Menu Configuration Process Measurement Concentration Measurement Configure Application Active Matrix and ensure that the matrix is listed.
Set up temperature data using the display
The concentration measurement application uses line temperature data in its calculations. You must decide how to provide this data, then perform the required configuration and setup. Temperature data from the on­board temperature sensor (RTD) is always available. Optionally, you can set up an external temperature device and use external temperature data.
The temperature setup that you establish here will be used for all concentration measurement matrices on this meter.
Important
Line temperature data is used in several different measurements and calculations. It is possible to use the internal RTD temperature in some areas and an external temperature in others. The transmitter stores the internal RTD temperature and the external temperature separately. However, the transmitter stores only one alternate temperature value, which may be either the external temperature or the configured fixed value. Accordingly, if you choose a fixed temperature for some uses, and an external temperature for others, the external temperature will overwrite the fixed value.
Procedure
Choose the method to be used to supply temperature data, and perform the required setup.
Method
Internal temperature
Digital communications
Description Setup
Temperature data from the on­board temperature sensor (RTD) will be used for all measurements and calculations. No external temperature data will be available.
A host writes temperature data to the meter at appropriate intervals. This data will be available in addition to the internal temperature data.
a. Choose Menu Configuration Process Measurement
b. Set External Temperature to Off.
a. Choose Menu Configuration Process Measurement
b. Set External Temperature to On.
c. Perform the necessary host programming and
Temperature.
Temperature.
communications setup to write temperature data to the transmitter at appropriate intervals.
Postrequisites
Choose Menu Service Tools Service Data View Process Variables and verify the value for External Temperature.
70 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 71
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
Need help?
If the value is not correct:
Ensure that the external device and the meter are using the same measurement unit.
For digital communications:Verify that the host has access to the required data.
Verify that the output variable is being correctly received and processed by the transmitter.
Modify matrix names and labels using the display
For convenience, you can change the name of a concentration matrix and the label used for its measurement unit. This does not affect measurement.
Procedure
1. Choose Menu Configuration Process Measurement Concentration Measurement
Configure Matrix.
2. Select the matrix that you want to modify.
3. Set Matrix Name to the name that will be used for this matrix.
4. Set Concentration Unit to the label that will be used for the concentration unit.
If you want to use a custom label, you can use the display to select Special. However, you cannot use the display to configure the custom label. You must use another tool to change the label from Special to a user-defined string.
Modify extrapolation alerts using the display
You can enable and disable extrapolation alerts, and set extrapolation alert limits. These parameters control the behavior of the concentration measurement application but do not affect measurement directly.
Each concentration matrix is built for a specific density range and a specific temperature range. If line density or line temperature goes outside the range, the transmitter will extrapolate concentration values. However, extrapolation may affect accuracy. Extrapolation alerts are used to notify the operator that extrapolation is occurring.
Each concentration matrix has its own extrapolation alert limits.
Procedure
1. Choose Menu Configuration Process Measurement Concentration Measurement
Configure Matrix.
2. Select the matrix that you want to modify.
3. Set Extrapolation Limit to the point, in percent, at which an extrapolation alert will be posted.
4. Choose Menu Configuration Process Measurement Concentration Measurement
Configure Application Extrapolation Alerts.
5. Enable or disable the high and low limit alerts for temperature and density as desired.
Configuration and Use Manual 71
Page 72
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Example: Extrapolation alerts in action
If Extrapolation Limit is set to 5%, High Limit (Temp) is enabled, and the active matrix is built for a temperature range of 40 °F (4.4 °C) to 80 °F (26.7 °C), a high-temperature extrapolation alert will be posted if line temperature goes above 82 °F (27.8 °C).
Select the active concentration matrix using the display
You must select the concentration matrix to be used for measurement. Although the transmitter can store up to six concentration matrices, only one matrix can be used for measurement at any one time.
Procedure
1. Choose Menu Configuration Process Measurement Concentration Measurement
Configure Application.
2. Set Active Matrix to the matrix you want to use.

5.2.3 Set up concentration measurement using ProLink III

This section guides you through the tasks required to set up, configure, and implement concentration measurement.
Enable concentration measurement using ProLink III
The concentration measurement application must be enabled before you can perform any setup. If the concentration measurement application was enabled at the factory, you do not need to enable it now.
Prerequisites
The concentration measurement application must be licensed on your transmitter.
Disable the following applications before enabling concentration measurement as concentration measurement cannot be enabled at the same time:
API Referral
Piecewise linearization (PWL)
Gas Standard Volume
Procedure
1. Choose Device Tools Configuration Process Measurement Flow and ensure that Volume
Flow Type is set to Liquid Volume.
2. Choose Device Tools Configuration Process Measurement Advance Phase Measurement
APM Status and ensure that Application Status is set to Disable.
3. Choose Device Tools Configuration Transmitter Options.
4. Disable API Referral and set the Advance Phase Measurement application to Disabled or Single Liquid.
5. Disable gas Piecewise Linearization (PWL), and set the Advance Phase Measurement application to
Disabled or Single Liquid.
6. Set Concentration Measurement to Enabled and select Apply.
72 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 73
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
Load a concentration matrix using ProLink III
At least one concentration matrix must be loaded onto your transmitter. You can load up to six.
Prerequisites
The concentration measurement application must be enabled on your device.
For each concentration matrix that you want to load, you need a file containing the matrix data. The ProLink III installation includes a set of standard concentration matrices. Other matrices are available from Micro Motion. The file can be on your computer or in the transmitter's internal memory.
The file must be in one of the formats that ProLink III supports. This includes:
.xml (ProLink III)
.matrix (5700)
If you are loading an .xml file, you must know the following information for your matrix:
The derived variable that the matrix is designed to calculate
The density unit that the matrix was built with
The temperature unit that the matrix was built with
If you are loading a .matrix file, you must know the derived variable that the matrix is designed to calculate.
Important
All concentration matrices on your transmitter must use the same derived variable.
If you change the setting of Derived Variable, all existing concentration matrices will be deleted from the
six slots on the transmitter, but not from the transmitter's SD card. Set Derived Variable before loading concentration matrices.
ProLink III loads matrices directly to one of the transmitter's six slots.
Tip
In many cases, concentration matrices were ordered with the device and loaded at the factory. You may not need to load any matrices.
Restriction
You cannot use ProLink III to load a matrix to the transmitter's SD card.
Procedure
1. If you are loading an .xml file, choose Device Tools Configuration Process Measurement Line
Density and set Density Unit to the density unit used by your matrix.
Important
When you load a matrix in one of these formats, if the density unit is not correct, concentration data will be incorrect. The density units must match at the time of loading. You can change the density unit after the matrix is loaded.
Configuration and Use Manual 73
Page 74
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
2. If you are loading an .xml file, choose Device Tools Configuration Process Measurement Line
Temperatureand set Temperature Unit to the temperature unit used by your matrix.
Important
When you load a matrix in one of these formats, if the temperature unit is not correct, concentration data will be incorrect. The temperature units must match at the time of loading. You can change the temperature unit after the matrix is loaded.
3. Choose Device Tools Configuration Process Measurement Concentration Measurement.
The Concentration Measurement window is displayed. It is organized into steps that allow you to perform several different setup and configuration tasks. For this task, you will not use all the steps.
4. In Step 1, ensure that the setting of Derived Variable matches the derived variable used by your
matrix. If it does not, change it as required and select Apply.
Important
If you change the setting of Derived Variable, all existing concentration matrices will be deleted from the six slots. Verify the setting of Derived Variable before continuing.
5. Load one or more matrices.
a) In Step 2, set Matrix Being Configured to the location (slot) to which the matrix will be loaded.
b) To load a .xml file from your computer, select Load Matrix from File, navigate to the file, and
load it.
c) To load a .matrix file from your computer, select Load Matrix from My Computer, navigate to
the file, and load it.
d) To load a .matrix file from the transmitter's internal memory, select Load Matrix from 5700
Device Memory, navigate to the file on the transmitter, and load it.
e) Repeat until all required matrices are loaded.
Set reference temperature values for specific gravity using ProLink III
When Derived Variable is set to any option based on specific gravity, you must set the reference temperature for water, then verify the density of water at the configured reference temperature. These values affect specific gravity measurement.
This requirement applies to the following derived variables:
Specific Gravity
Concentration (Specific Gravity)
Mass Concentration (Specific Gravity)
Volume Concentration (Specific Gravity)
Procedure
1. Choose Device Tools Configuration Process Measurement Concentration Measurement.
The Concentration Measurement window is displayed. It is organized into steps that allow you to perform several different setup and configuration tasks. For this task, you will not use all the steps.
2. Scroll to Step 2, set Matrix Being Configured to the matrix you want to modify, and select Change
Matrix.
74 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 75
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
3. Scroll to Step 3, then perform the following actions:
a) Set Reference Temperature for Referred Density to the temperature to which line density will
be corrected for use in the specific gravity calculation.
b) Set Reference Temperature for Water to the water temperature that will be used in the specific
gravity calculation.
c) Set Water Density at Reference Temperature to the density of water at the specified reference
temperature.
The transmitter automatically calculates the density of water at the specified temperature. The new value will be displayed the next time that transmitter memory is read. You can enter a different value if you prefer.
4. Select Apply at the bottom of Step 3.
Set up temperature data using ProLink III
The concentration measurement application uses line temperature data in its calculations. You must decide how to provide this data, then perform the required configuration and setup. Temperature data from the on­board temperature sensor (RTD) is always available. Optionally, you can set up an external temperature device and use external temperature data.
The temperature setup that you establish here will be used for all concentration measurement matrices on this meter.
Important
Line temperature data is used in several different measurements and calculations. It is possible to use the internal RTD temperature in some areas and an external temperature in others. The transmitter stores the internal RTD temperature and the external temperature separately. However, the transmitter stores only one alternate temperature value, which may be either the external temperature or the configured fixed value. Accordingly, if you choose a fixed temperature for some uses, and an external temperature for others, the external temperature will overwrite the fixed value.
Procedure
1. Choose Device Tools Configuration Process Measurement Concentration Measurement.
The Concentration Measurement window is displayed. It is organized into steps that allow you to perform several different setup and configuration tasks. For this task, you will not use all the steps.
2. Scroll to Step 4.
3. Choose the method to be used to supply temperature data, and perform the required setup.
Option
Internal temperature
Description Setup
Temperature data from the on­board temperature sensor (RTD) will be used for all measurements and calculations. No external temperature data will be available.
a. Set Line Temperature Source to Internal.
b. Click Apply.
Configuration and Use Manual 75
Page 76
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Option Description Setup
Digital communications
A host writes temperature data to the meter at appropriate intervals. This data will be available in addition to the internal RTD temperature data.
a. Set Line Temperature Source to Fixed Value or Digital
Communications.
b. Click Apply.
c. Perform the necessary host programming and
communications setup to write temperature data to the meter at appropriate intervals.
Postrequisites
If you are using external temperature data, verify the external temperature value displayed in the Inputs group on the ProLink III main window.
Need help?
If the value is not correct:
Ensure that the external device and the meter are using the same measurement unit.
For digital communications:Verify that the host has access to the required data.
Verify that the output variable is being correctly received and processed by the transmitter.
Modify matrix names and labels using ProLink III
For convenience, you can change the name of a concentration matrix and the label used for its measurement unit. This does not affect measurement.
Procedure
1. Choose Device Tools Configuration Process Measurement Concentration Measurement.
The Concentration Measurement window is displayed. It is organized into steps that allow you to perform several different setup and configuration tasks. For this task, you will not use all the steps.
2. Scroll to Step 2, set Matrix Being Configured to the matrix you want to modify, and click Change
Matrix.
3. Scroll to Step 3, then perform the following actions:
a) Set Concentration Units Label to the label that will be used for the concentration unit.
b) If you set Concentration Units Label to Special, enter the custom label in User-Defined Label.
c) In Matrix Name, enter the name to be used for the matrix.
4. Select Apply at the bottom of Step 3.
Modify extrapolation alerts using ProLink III
You can enable and disable extrapolation alerts, and set extrapolation alert limits. These parameters control the behavior of the concentration measurement application but do not affect measurement directly.
Each concentration matrix is built for a specific density range and a specific temperature range. If line density or line temperature goes outside the range, the transmitter will extrapolate concentration values. However,
76 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 77
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
extrapolation may affect accuracy. Extrapolation alerts are used to notify the operator that extrapolation is occurring.
Each concentration matrix has its own extrapolation alert limits.
Procedure
1. Choose Device Tools Configuration Process Measurement Concentration Measurement.
The Concentration Measurement window is displayed. It is organized into steps that allow you to perform several different setup and configuration tasks. For this task, you will not use all the steps.
2. Scroll to Step 2, set Matrix Being Configured to the matrix you want to modify, and click Change
Matrix.
3. Scroll to Step 4.
4. Set Extrapolation Alert Limit to the point, in percent, at which an extrapolation alert will be posted.
5. Enable or disable the high and low limit alerts for temperature and density, as desired, and click Apply.
Example: Extrapolation alerts in action
If Extrapolation Limit is set to 5%, High Limit (Temp) is enabled, and the active matrix is built for a temperature range of 40 °F (4.4 °C) to 80 °F (26.7 °C), a high-temperature extrapolation alert will be posted if line temperature goes above 82 °F (27.8 °C).
Select the active concentration matrix using ProLink III
You must select the concentration matrix to be used for measurement. Although the transmitter can store up to six concentration matrices, only one matrix can be used for measurement at any one time.
Procedure
1. Choose Device Tools Configuration Process Measurement Concentration Measurement.
2. Scroll to Step 2, set Active Matrix to the matrix you want to use and select Change Matrix.

5.2.4 Set up concentration measurement using a PROFIBUS PA host

This section guides you through most of the tasks related to setting up and implementing the concentration measurement application.
Enable concentration measurement using a PROFIBUS PA host
DeltaV AMS
Siemens PDM view Overview Device Information Licenses Enable/Disable Applications
The concentration measurement application must be enabled before you can perform any setup. If the concentration measurement application was enabled at the factory, you do not need to enable it now.
Prerequisites
Overview Device Information Licenses Enable/Disable Applications
The concentration measurement application must be licensed on your transmitter.
Disable the following applications before enabling concentration measurement as concentration measurement cannot be enabled at the same time:
API Referral
Configuration and Use Manual 77
Page 78
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Piecewise linearization (PWL)
Gas Standard Volume
Procedure
1. Ensure that Flow Type is set to Liquid Volume Flow.
2. Ensure that the API Referral and piecewise linearization (PWL) are disabled.
3. Ensure that the Advance Phase Measurement Output Type is either disabled or set to liquid with gas
continuous flow or liquid with gas variable flow.
4. Execute the concentration measurement method. This method sets the device application for
concentration measurement.
Set reference temperature values for specific gravity using a PROFIBUS PA host
DeltaV AMS Configure Manual Setup Measurements Optional Setup Concentration Measurement
Siemens PDM Device Manual Setup Measurements Optional Setup Concentration Measurement
When Derived Variable is set to any option based on specific gravity, you must set the reference temperature for water, then verify the density of water at the configured reference temperature. These values affect specific gravity measurement.
The PROFIBUS PA host shows only the 10 point linearization table values.
Check the setting of Configure Concentration Measurement Derived Variable.
Important
Do not change the setting of Derived Variable. If you change the setting of Derived Variable, all existing concentration matrices will be deleted from transmitter memory.
Procedure
1. Set Configure Matrix Matrix Being Configured to the matrix you want to modify.
2. Choose Reference Conditions, then perform the following actions:
a) Set Reference Temperature to the temperature to which line density will be corrected for use in
the specific gravity calculation.
b) Set Water Reference Temperature to the water temperature that will be used in the specific
gravity calculation.
c) Set Water Reference Density to the density of water at the specified reference temperature.
The transmitter automatically calculates the density of water at the specified temperature. The new value will be displayed the next time that transmitter memory is read. Optionally, you can enter a different value.
Provide temperature data using a PROFIBUS PA host
DeltaV AMS
Siemens PDM Device Manual Setup Measurements Optional Setup External Variables
78 Micro Motion 5700 Transmitters with PROFIBUS-PA
Configure Manual Setup Measurements Optional Setup External Variables
Page 79
Configuration and Use Manual Configure process measurement applications
MMI- 20070546 June 2021
The concentration measurement application uses line temperature data in its calculations. You must decide how to provide this data, then perform the required configuration and setup. Temperature data from the on­board temperature sensor (RTD) is always available. You can set up an external temperature device and use external temperature data if you want to.
The temperature setup that you establish here will be used for all concentration measurement matrices on this meter.
Procedure
Choose the method to be used to supply temperature data, and perform the required setup.
Method Description Setup
Internal RTD temperature data
Digital communications
Temperature data from the on­board temperature sensor (RTD) is used.
A host writes temperature data to the meter at appropriate intervals. This data will be available in addition to the internal RTD temperature data.
Set Temperature Compensation to Disable.
a. Set Temperature Compensation to Enable.
b. Perform the necessary host programming and
communications setup to write temperature data to the meter at appropriate intervals.
Postrequisites
Choose Service Tools Variables External Variables and verify the value for External Temperature.
Need help?
If the value is not correct:
Ensure that the external device and the meter are using the same measurement unit.
For digital communications:Verify that the host has access to the required data.
Verify that the output variable is being correctly received and processed by the transmitter.
Modify matrix names and labels using a PROFIBUS PA host
DeltaV AMS
Siemens PDM Device Manual Setup Measurements Optional Setup Concentration Measurement
Configure Manual Setup Measurements Optional Setup Concentration Measurement Configure Matrix Matrix Selection
Configure Matrix Matrix Selection
For convenience, you can change the name of a concentration matrix and the label used for its measurement unit. This does not affect measurement.
Procedure
1. Set Matrix Being Configured to the matrix you want to modify.
2. Set Matrix Name to the name to be used for the matrix.
3. Set Concentration Unit to the label that will be used for the concentration unit.
4. If you set Concentration Unit to Special, choose Label and enter the custom label.
Configuration and Use Manual 79
Page 80
Configure process measurement applications Configuration and Use Manual
June 2021 MMI- 20070546
Modify extrapolation alerts for concentration measurement using a PROFIBUS PA host
DeltaV AMS Configure Manual Setup Measurements Optional Setup Concentration Measurement
Siemens PDM Device Manual Setup Measurements Optional Setup Concentration Measurement
Configure Matrix
Configure Matrix
You can enable and disable extrapolation alerts, and set extrapolation alert limits. These parameters control the behavior of the concentration measurement application but do not affect measurement directly.
Each concentration matrix is built for a specific density range and a specific temperature range. If line density or line temperature goes outside the range, the transmitter will extrapolate concentration values. However, extrapolation may affect accuracy. Extrapolation alerts are used to notify the operator that extrapolation is occurring.
Each concentration matrix has its own extrapolation alert limits.
Procedure
1. Set Matrix Selection Matrix Being Configured to the matrix you want to modify.
2. Set Extrapolation Alert Limit to the point, in percent, at which an extrapolation alert will be posted.
3. Choose one of the following options based on the tool you are using:
For DeltaV AMS, Configure Alert Setup Concentration Measurement Alerts
For Siemens PDM, Device Alert Setup Concentration Measurement Alerts
4. Enable or disable the high and low alerts for temperature and density, as desired.
Example: Extrapolation alerts in action
If Extrapolation Limit is set to 5%, High Limit (Temp) is enabled, and the active matrix is built for a temperature range of 40 °F (4.4 °C) to 80 °F (26.7 °C), a high-temperature extrapolation alert will be posted if line temperature goes above 82 °F (27.8 °C).
Select the active concentration matrix using a PROFIBUS PA host
DeltaV AMS
Siemens PDM Device Manual Setup Measurements Optional Setup Concentration Measurement
You must select the concentration matrix to be used for measurement. Although the transmitter can store up to six concentration matrices, only one matrix can be used for measurement at any one time.
Procedure
Set Active Matrix to the matrix you want to use.
Configure Manual Setup Measurements Optional Setup Concentration Measurement
80 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 81
Configuration and Use Manual Configure advanced options for process measurement
MMI- 20070546 June 2021

6 Configure advanced options for process measurement

6.1 Configure Response Time

Display Menu Configuration Process Measurement Response Time
ProLink III Device Tools Configuration Process Measurement Response Time
DeltaV AMS Configure Manual Setup Measurements 2 Response Time
Siemens PDM Device Manual Setup Measurements 2 Response Time
Response Time controls the speed of various internal processes that are involved in retrieving electronic data from the sensor and converting it to process data.
Response Time affects all process and diagnostic variables.
Restriction
Response Time is configurable only if you are using the enhanced core processor. If you are using the standard core processor, Response Time is set to Low Filtering and cannot be changed.
Procedure
Set Response Time as desired.
Option
Normal Appropriate for typical applications.
High Filtering Slower response. Appropriate for applications with significant amount of entrained gas or
Low Filtering Fastest response. Appropriate for proving or filling applications.
Description
process noise.

6.2 Detect and report two-phase flow

Two-phase flow (gas in a liquid process or liquid in a gas process) can cause a variety of process control issues. The transmitter provides two methods to detect and report or respond to two-phase flow.

6.2.1 Detect two-phase flow using density

Display
ProLink III
DeltaV AMS
Menu Configuration Process Measurement Density
Device Tools Configuration Process Measurement Density
Configure Manual Setup Measurements Two-Phase Flow Low Limit
Configure Manual Setup Measurements Two-Phase Flow High Limit
Configure Manual Setup Measurements Two-Phase Flow Duration
Configuration and Use Manual 81
Page 82
Configure advanced options for process measurement Configuration and Use Manual
June 2021 MMI- 20070546
Device Manual Setup Measurements Two-Phase Flow Low Limit
Siemens PDM
Device Manual Setup Measurements Two-Phase Flow High Limit
Device Manual Setup Measurements Two-Phase Flow Duration
The transmitter can use line density data to detect two-phase flow (gas in a liquid process or liquid in a gas process). The density limits are user-specified. When two-phase flow is detected, an alert is posted.
Procedure
1. Set Two-Phase Flow Low Limit to the lowest density value that is considered normal in your process.
Values below this will cause the transmitter to post a Process Aberration alert.
Tip
Gas entrainment can cause your process density to drop temporarily. To reduce the occurrence of two­phase flow alerts that are not significant to your process, set Two-Phase Flow Low Limit slightly below your expected lowest process density.
You must enter Two-Phase Flow Low Limit in g/cm³, even if you configured another unit for density measurement.
Default: 0 g/cm³
Range: 0 g/cm³ to the sensor limit
2. Set Two-Phase Flow High Limit to the highest density value that is considered normal in your process.
Values above this will cause the transmitter to post a Process Aberration alert.
Tip
To reduce the occurrence of two-phase flow alerts that are not significant to your process, set Two­Phase Flow High Limit slightly above your expected highest process density.
You must enter Two-Phase Flow High Limit in g/cm³, even if you configured another unit for density measurement.
Default: 5 g/cm³
Range: 5 g/cm³ to the sensor limit
3. Set Two-Phase Flow Timeout to the number of seconds that the transmitter will wait for a two-phase
flow condition to clear before posting the alert.
Default: 0 seconds, meaning that the alert will be posted immediately
Range: 0 to 60 seconds

6.2.2 Detect two-phase flow using sensor diagnostics

Display
ProLink III
DeltaV AMS
Siemens PDM
82 Micro Motion 5700 Transmitters with PROFIBUS-PA
Menu Configuration Inputs/Outputs Channel B I/O Settings Source
Device Tools Configuration I/O Outputs mA Output
Configure Manual Setup Mapping/Source Output Source Milliamp Output Source
Device Manual Setup Mapping/Source Output Source Milliamp Output Source
Page 83
Configuration and Use Manual Configure advanced options for process measurement
MMI- 20070546 June 2021
The transmitter always monitors sensor diagnostics and applies a two-phase flow algorithm. You can assign an mA Output to report the results of this calculation: single-phase flow, moderate two-phase flow, or severe two-phase flow. Severe two-phase flow can cause the meter to stop functioning.
Prerequisites
Channel B must be configured as mA Output.
Procedure
Set mA Output Source to Two-Phase Flow Detection.
The signal from the mA Output indicates the current state of the process:
12 mA: Single-phase flow
16 mA: Moderate two-phase flow
20 mA: Severe two-phase flow

6.3 Configure Flow Rate Switch

Display Menu Configuration Alert Setup Enhanced Events Flow Rate Switch
ProLink III Device Tools Configuration I/O Outputs Discrete Output Source Flow Switch Indication
DeltaV AMS Configure Manual Setup Mapping/Source Output Source Discrete Output Source
Siemens PDM Device Manual Setup Mapping/Source Output Source Discrete Output Source
Flow Rate Switch is used to indicate that the flow rate has moved past a user-specified setpoint, in either direction. The flow rate switch is implemented with a user-configurable hysteresis.
Typically, a Discrete Output is assigned as the flow rate switch indicator. The Discrete Output can be wired to an external device such as a light or a horn.
Prerequisites
Channel C must be configured as a Discrete Output.
Procedure
1. Set Discrete Output Source to Flow Switch, if you have not already done so.
2. Set Flow Switch Variable to the flow variable that you want to use to control the flow rate switch.
3. Set Flow Switch Setpoint to the value at which the flow switch will be triggered (after Hysteresis is
applied).
Depending on the polarity of the Discrete Output:
If the flow rate is below this value, the Discrete Output is ON.
If the flow rate is above this value, the Discrete Output is OFF.
4. Set Hysteresis to the percentage of variation above and below the setpoint that will operate as a
deadband.
Configuration and Use Manual 83
Page 84
Configure advanced options for process measurement Configuration and Use Manual
June 2021 MMI- 20070546
Hysteresis defines a range around the setpoint within which the flow rate switch will not change.
Default: 5%
Range: 0.1% to 10%
Example
If Flow Switch Setpoint = 100 g/sec and Hysteresis = 5%, and the first measured flow rate is above 100 g/sec, the discrete output is OFF. It will remain OFF unless the flow rate drops below 95 g/sec. If
this happens, the discrete output will turn ON, and remain ON until the flow rate rises above 105 g/sec. At this point it turns OFF and will remain OFF until the flow rate drops below 95 g/sec.
Related information
Configure a Discrete Output

6.4 Configure events

An event occurs when the real-time value of a user-specified process variable moves past a user-defined setpoint. Events are used to provide notification of process changes or to perform specific transmitter actions if a process change occurs.
Related information
Configure an enhanced event

6.4.1 Configure an enhanced event

Display
ProLink III Device Tools Configuration Events Enhanced Events
DeltaV AMS Configure Manual Setup Events Configure Events
Siemens PDM Device Manual Setup Events Configure Events
An enhanced event is used to provide notification of process changes and, optionally, to perform specific transmitter actions if the event occurs. An enhanced event occurs (is ON) if the real-time value of a user­specified process variable moves above (HI) or below (LO) a user-defined setpoint, or in range (IN) or out of range (OUT) with respect to two user-defined setpoints.
You can define up to five enhanced events. For each enhanced event, you can assign one or more actions that the transmitter will perform if the enhanced event occurs.
Procedure
1. Select the event that you want to configure.
2. Assign a process variable to the event.
3. Specify Event Type.
Menu Configuration Alert Setup Enhanced Events
Option
HI x > A
84 Micro Motion 5700 Transmitters with PROFIBUS-PA
Description
Page 85
Configuration and Use Manual Configure advanced options for process measurement
MMI- 20070546 June 2021
Option Description
The event occurs when the value of the assigned process variable (x) is greater than the setpoint (Setpoint A), endpoint not included.
LO x < A
The event occurs when the value of the assigned process variable (x) is less than the setpoint (Setpoint A), endpoint not included.
IN A ≤ x ≤ B
The event occurs when the value of the assigned process variable (x) is in range, that is, between Setpoint A and Setpoint B, endpoints included.
OUT x ≤ A or x ≥ B
The event occurs when the value of the assigned process variable (x) is out of range, that is, less than Setpoint A or greater than Setpoint B, endpoints included.
4. Set values for the required setpoints.
For HI and LO events, set Setpoint A.
For IN and OUT events, set Setpoint A and Setpoint B.
5. Optional: Configure a Discrete Output to switch states in response to the event status.
6. Optional: Specify the action or actions that the transmitter will perform when the event occurs.
Option
Description
Display Menu Configuration Alert Setup
Enhanced Events, select any enhanced event,
and choose Assign Actions
ProLink III Device Tools Configuration I/O Inputs
Action Assignment
Related information
Configure Discrete Output Source
Options for Enhanced Event Action
Action
Display ProLink III PROFIBUS-PA
Standard
Label
Start sensor zero Start Zero Calibration Start Sensor Zero Start Sensor Zero
Totalizers
Start/stop all totalizers and inventories
Reset totalizer X Reset Total X Totalizer X Reset Total X
Configuration and Use Manual 85
Start/stop all totalizers Start or Stop All Totalizers Start/Stop All Totals
Page 86
Configure advanced options for process measurement Configuration and Use Manual
June 2021 MMI- 20070546
Action Label
Display ProLink III PROFIBUS-PA
Reset all totalizers and inventories
Start\stop inventory X Start\stop Inventory X Start or stop Inventory X Start\Stop Inventory X
Concentration measurement
Increment CM matrix Increment Matrix Increment ED Curve Increment Curve
Meter verification
Start meter verification test Start SMV Start Meter Verification Start Smart Meter
Reset All Totals Reset All Totals Reset All Totals
Verification

6.5 Configure totalizers and inventories

Display Menu Configuration Process Measurement Totalizers & Inventories
ProLink III Device Tools Totalizer Control Totalizers
DeltaV AMS Configure Manual Setup Measurements Optional Setup Configure Totalizers/Inventories
Siemens PDM Device Manual Setup Measurements Optional Setup Configure Totalizers/Inventories
The transmitter provides seven configurable totalizers and seven configurable inventories. Each totalizer and each inventory can be configured independently.
Totalizers track the process since the last totalizer reset. Inventories track the process since the last inventory reset. Inventories are typically used to track the process across totalizer resets.
Tip
The default configurations cover the most typical uses of totalizers and inventories. You may not need to change any configurations.
Prerequisites
Before configuring the totalizers and inventories, ensure that the process variables you plan to track are available on the transmitter.
Procedure
1. Select the totalizer or inventory that you want to configure.
2. Set Totalizer Source or Inventory Source to the process variable that the totalizer or inventory will
track.
Option
Description
Mass flow The totalizer or inventory will track Mass Flow Rate and calculate total
mass since the last reset.
Volume flow The totalizer or inventory will track Volume Flow Rate and calculate total
volume since the last reset.
86 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 87
Configuration and Use Manual Configure advanced options for process measurement
MMI- 20070546 June 2021
Option Description
Gas standard volume flow
Temperature-corrected volume flow
The totalizer or inventory will track Gas Standard Volume Flow Rate and calculate total volume since the last reset.
The totalizer or inventory will track Temperature-Corrected Volume Flow Rate and calculate total volume since the last reset.
Standard volume flow The totalizer or inventory will track Standard Volume Flow Rate and
calculate total volume since the last reset.
Net mass flow The totalizer or inventory will track Net Mass Flow Rate and calculate total
mass since the last reset.
Net volume flow The totalizer or inventory will track Net Volume Flow Rate and calculate
total volume since the last reset.
For totalizer source codes, see Totalizer source Advanced Phase Measurement codes.
Note
The totalizer/inventory value will not automatically be reset when the source is changed. The user must manually reset the totalizer/inventory.
Tip
If you are using the API Referral application and you want to measure batch-weighted average density or batch-weighted average temperature, you must have a totalizer configured to measure temperature-corrected volume flow.
3. Set Totalizer Direction to specify how the totalizer or inventory will respond to forward or reverse flow.
Option
Forward Only Forward Totals increment
Reverse Only Forward Totals do not change
Bidirectional Forward Totals increment
Absolute Value Forward Totals increment
Flow direction Totalizer and inventory behavior
Reverse Totals do not change
Reverse Totals increment
Reverse Totals decrement
Reverse Totals increment
Important
Actual flow direction interacts with Sensor Flow Direction Arrow to determine the flow direction that the transmitter uses in processing. See the following table.
Configuration and Use Manual 87
Page 88
Configure advanced options for process measurement Configuration and Use Manual
June 2021 MMI- 20070546
Table 6-1: Interaction between actual flow direction and Sensor Flow Direction Arrow
Actual flow direction
Forward (same direction as Flow arrow on sensor)
Reverse (opposite from Flow arrow on sensor)
Setting of Sensor Flow Direction Arrow
With Arrow Forward
Against Arrow Reverse
With Arrow Reverse
Against Arrow Forward
Flow direction sent to outputs and totalizers
4. Optional: Set User Name to the name you want to use for the inventory or totalizer.
User Name can have a maximum of 16 characters.
The transmitter automatically generates a name for each totalizer and inventory, based on its source, direction, and type.
Example
Totalizer Source=Mass Flow
Totalizer Direction=Forward Only
Totalizer name=Mass Fwd Total
Example
Inventory Source=Gas Standard Volume Flow
Inventory Direction=Bidirectional
Inventory name = GSV Bidir Inv
The specified name is used on the transmitter display and on all interfaces that support it. If User Name contains only spaces, the transmitter-generated name is used. Not all interfaces support totalizer and inventory names.
Example: Checking for backflow
You suspect that there is a significant amount of backflow through the sensor. To collect data, configure two totalizers as follows:
Source=Mass Flow, Direction=Forward Only
Source=Mass Flow, Direction=Reverse Only
Reset both totalizers, allow them to run for an appropriate period, then look at the amount of reverse flow as a percentage of forward flow.
Example: Tracking three different process fluids
Three tanks are connected to a loading dock through a single meter. Each tank contains a different process fluid. You want to track each process fluid separately.
1. Set up three totalizers, one for each tank.
2. Name the totalizers Tank 1, Tank 2, and Tank 3.
88 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 89
Configuration and Use Manual Configure advanced options for process measurement
MMI- 20070546 June 2021
3. Configure each totalizer as required for the corresponding process fluid.
4. Stop and reset all three totalizers to ensure that the beginning values are 0.
5. When loading from a tank, start the corresponding totalizer, and stop it when the load is finished.

6.5.1 Totalizer source Advanced Phase Measurement codes

Code Description
73 APM: Net Flow Oil at Line
75 APM: Net Flow Water at Line
78 APM: Net Flow Oil At Reference
81 APM: Net Flow Water At Reference
188 APM: SF Net Oil Flow at Line
189 APM: SF Net Oil Flow at Reference
190 APM: SF Volume Flow at Reference
210 APM: Unremediated Mass Flow
212 APM: Unremediated Vol Flow
230 APM: TMR Liquid Flow

6.5.2 Default settings for totalizers and inventories

Totalizer or inventory
1 Mass flow Forward Only Mass Fwd Total
2 Volume flow Forward Only Volume Fwd Total
3 Temperature-corrected volume
4 Gas standard volume flow Forward Only GSV Fwd Total
5 Standard volume flow Forward Only Standard Vol Fwd Total
6 Net mass flow Forward Only Net Mass Fwd Total
7 Net volume flow Forward Only Net Vol Fwd Total
Source (process variable assignment
flow
Direction Name of totalizer
Name of inventory
Mass Fwd Inv
Volume Fwd Inv
Forward Only API Volume Fwd Total
API Volume Fwd Inv
GSV Fwd Inv
Standard Vol Fwd Inv
Net Mass Fwd Inv
Net Vol Fwd Inv
Configuration and Use Manual 89
Page 90
Configure advanced options for process measurement Configuration and Use Manual
June 2021 MMI- 20070546

6.6 Configure logging for totalizers and inventories

Display Menu Configuration Totalizer Log
ProLink III Device Tools Configuration Totalizer Log
DeltaV AMS Not available
Siemens PDM Not available
The transmitter can write the current value of four totalizers or inventories to a log, at user-specified intervals. You can generate a log file from this data for viewing and analysis.
Procedure
1. Specify the date on which totalizer logging will begin.
You must specify a future date. If you try to specify the current date, the transmitter will reject the setting.
2. Specify the time at which totalizer logging will begin.
3. Specify the number of hours between records.
4. Select up to four totalizers or inventories to be logged.

6.7 Configure Process Variable Fault Action

Display
ProLink III Device Tools Configuration Fault Processing
DeltaV AMS Configure Alert Setup Output Fault Actions Fault Setting
Siemens PDM Device Alert Setup Output Fault Actions Fault Setting
Process Variable Fault Action specifies the values that will be reported via the display and digital communications if the device encounters a fault condition. The values are also sent to the outputs for processing against their configured fault actions.
Procedure
Set Process Variable Fault Action as desired.
Default: None
Restriction
If you set Process Variable Fault Action to NAN, you cannot set mA Output Fault Action or Frequency Output Fault Action to None. If you try to do this, the transmitter will not accept the configuration.
Important
If you want the mA Output to continue reporting process data during fault conditions, you must set both
Process Variable Fault Action and mA Output Fault Action to None. If mA Output Fault Action is set to None and Process Variable Fault Action is set to any other option, the mA Output will produce the signal
associated with the selection.
Menu Configuration Alert Setup Output Fault Actions
If you want the Frequency Output to continue reporting process data during fault conditions, you must set
both Process Variable Fault Action and Frequency Output Fault Action to None. If Frequency Output
90 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 91
Configuration and Use Manual Configure advanced options for process measurement
MMI- 20070546 June 2021
Fault Action is set to None and Process Variable Fault Action is set to any other option, the Frequency Output will produce the signal associated with the selection.

6.7.1 Options for Process Variable Fault Action

Label
Display ProLink III PROFIBUS-PA
Upscale Upscale Upscale Process variable values indicate that the
Downscale Downscale Downscale Process variable values indicate that the
Zero Zero Zero Flow rate variables go to the value that
Description
value is greater than the upper sensor limit.
Totalizers stop incrementing.
value is lower than the lower sensor limit.
Totalizers stop incrementing.
represents a flow rate of 0 (zero).
Density is reported as 0.
Temperature is reported as 0 °C , or the
equivalent if other units are used (e.g.,
32 °F .
Drive gain is reported as measured.
Totalizers stop incrementing.
Not-a-Number (NAN) Not a Number NAN Process variables are reported as IEEE
NAN.
Drive gain is reported as measured.
Modbus scaled integers are reported as
Max Int.
Totalizers stop incrementing.
Flow to Zero Flow to Zero Flow goes to zero Flow rates are reported as 0.
Other process variables are reported as
measured.
Totalizers stop incrementing.
None (default) None None All process variables are reported as
measured.
Totalizers increment if they are running.
Configuration and Use Manual 91
Page 92
Configure advanced options for process measurement Configuration and Use Manual
June 2021 MMI- 20070546

6.7.2 Interaction between Process Variable Fault Action and other fault actions

The setting of Process Variable Fault Action affects the operation of the mA Outputs, Frequency Outputs, and Discrete Outputs if the corresponding output fault actions are set to None.
Interaction between Process Variable Fault Action and mA Output Fault Action
If mA Output Fault Action is set to None, the mA Output signal depends on the setting of Process Variable Fault Action.
If the device detects a fault condition:
1. Process Variable Fault Action is evaluated and applied.
2. mA Output Fault Action is evaluated.
If it is set to None, the output reports the value associated with the setting of Process Variable
Fault Action.
If it is set to any other option, the output performs the specified fault action.
If you want the mA Output to continue to report process data during fault conditions, you must set both mA Output Fault Action and Process Variable Fault Action to None.
Interaction between Process Variable Fault Action and Frequency Output Fault Action
If Frequency Output Fault Action is set to None, the Frequency Output signal depends on the setting of Process Variable Fault Action.
If the device detects a fault condition:
1. Process Variable Fault Action is evaluated and applied.
2. Frequency Output Fault Action is evaluated.
If it is set to None, the output reports the value associated with the setting of Process Variable
Fault Action.
If it is set to any other option, the output performs the specified fault action.
If you want the Frequency Output to continue to report process data during fault conditions, you must set both Frequency Output Fault Action and Process Variable Fault Action to None.
Interaction between Process Variable Fault Action and Discrete Output Fault Action
If Discrete Output Fault Action is set to None and Discrete Output Source is set to Flow Rate Switch, the Discrete Output state during a fault depends on the setting of Process Variable Fault Action.
If the device detects a fault condition:
1. Process Variable Fault Action is evaluated and applied.
2. Discrete Output Fault Action is evaluated.
If it is set to None, and Discrete Output Source is set to Flow Rate Switch, the Discrete Output will
use the value determined by the current setting of Process Variable Fault Action to determine if a flow rate switch has occurred.
92 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 93
Configuration and Use Manual Configure advanced options for process measurement
MMI- 20070546 June 2021
If Discrete Output Source is set to any other option, the setting of Process Variable Fault Action is
irrelevant to the behavior of the Discrete Output during fault conditions. The Discrete Output is set to the specified fault action.
If you want the Discrete Output to report a flow rate switch appropriately during fault conditions, you must set both Discrete Output Fault Action and Process Variable Fault Action to None.
Related information
Configure mA Output Fault Action Configure Frequency Output Fault Action Configure Discrete Output Fault Action
Configuration and Use Manual 93
Page 94
Configure advanced options for process measurement Configuration and Use Manual
June 2021 MMI- 20070546
94 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 95
Configuration and Use Manual Configure device options and preferences
MMI- 20070546 June 2021

7 Configure device options and preferences

7.1 Configure the transmitter display

You can control the language used on the display, the process variables shown on the display, and a variety of display behaviors.

7.1.1 Configure the language used on the display

Display Menu Configuration Display Settings Language
ProLink III Device Tools Configuration Local Display Settings Transmitter Display General Language
DeltaV AMS Configure Manual Setup Display Display Language Language
Siemens PDM Device Manual Setup Display Display Language Language
Language controls the language that the display uses for process data, menus, and information.
The languages available depend on your transmitter model and version.
Procedure
Set Language to the desired language.

7.1.2 Configure the process variables shown on the display

Display
ProLink III Device Tools Configuration Transmitter Display Display Variables
DeltaV AMS Configure Manual Setup Display Display Variables
Siemens PDM Device Manual Setup Display Display Variables
You can control the process variables shown on the display and the order in which they appear. The display can scroll through up to 15 process variables in any order you choose. This configuration applies to both auto­scroll and manual scrolling.
By default, one process variable is shown at a time. You can configure a custom display screen that shows two process variables at a time.
Restriction
You cannot remove all display variables. At least one display variable must be configured.
Notes
If you have a display variable configured to show a volume process variable, and you change Volume Flow
Type to Gas Standard Volume, the display variable is automatically changed to the equivalent GSV
variable, and vice versa.
Menu Configuration Display Settings Display Variables
For all other display variables, if the process variable becomes unavailable due to changes in configuration,
the transmitter will not display that variable.
Configuration and Use Manual 95
Page 96
Configure device options and preferences Configuration and Use Manual
June 2021 MMI- 20070546
Procedure
For each display variable, select the process variable to be shown in that position in the rotation.
You can skip positions and you can repeat process variables.
Table 7-1: Default configuration for display variables
Display variable Process variable assignment
Display Variable 1 Mass flow rate
Display Variable 2 Mass total
Display Variable 3 Volume flow rate
Display Variable 4 Volume total
Display Variable 5 Density
Display Variable 6 Temperature
Display Variable 7 Drive gain
Display Variable 8 None
Display Variable 9 None
Display Variable 10 None
Display Variable 11 None
Display Variable 12 None
Display Variable 13 None
Display Variable 14 None
Display Variable 15 None

7.1.3 Configure a two-line display screen

Display
ProLink III Device Tools Configuration Transmitter Display Display Variables 2 PV Screen Slot #X
DeltaV AMS Configure Manual Setup Display Display Variables Two Variable Screen
Siemens PDM Device Manual Setup Display Display Variables Two Variable Screen
You can configure one display screen to show two process variables at a time. For each of these process variables, the current value and the measurement is shown.
The two-line display screen operates like one of the basic 15 screens. You can use and to scroll to it. If Auto Scroll is enabled, the two-line screen will be the last screen in the cycle.
Menu Configuration Display Settings Display Variables 2-Value View
96 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 97
Configuration and Use Manual Configure device options and preferences
MMI- 20070546 June 2021
7.1.4 Configure the number of decimal places (precision) shown on
the display
Display Menu Configuration Display Settings Decimals on Display
ProLink III Device Tools Configuration Transmitter Display Display Variables Decimal Places for x
DeltaV AMS Configure Manual Setup Display Decimal Places
Siemens PDM Display Manual Setup Display Decimal Places
You can specify the precision (the number of decimal places) that the display uses for each display variable. You can set the precision independently for each display variable.
The display precision does not affect the actual value of the variable, the value used in calculations, or the value reported via outputs or digital communications.
Procedure
1. Select a process variable or a diagnostic variable.
You can configure the precision for all variables, whether or not they are assigned as display variables. The configured precision will be stored and used when applicable.
2. Set Number of Decimal Places to the number of decimal places to be used when this variable is shown
on the display.
Default:Temperature variables: 2
All other variables: 4
Range: 0 to 5
Tip
The lower the precision, the greater the change must be for it to be reflected on the display. Do not set Number of Decimal Places too low to be useful.

7.1.5 Turn on and turn off automatic scrolling through the display variables

Display
ProLink III Device Tools Configuration Transmitter Display General Auto Scroll
DeltaV AMS Configure Manual Setup Display General Setting Auto Scroll
Siemens PDM Device Manual Setup Display General Setting Auto Scroll
You can configure the display to automatically scroll through the list of display variables or to show a single display variable until the operator activates Scroll. If Auto Scroll is turned on, you can configure the number of seconds that each display variable will be shown.
Menu Configuration Display Settings Auto Scroll
Procedure
1. Turn on or turn off Auto Scroll as desired.
Configuration and Use Manual 97
Page 98
Configure device options and preferences Configuration and Use Manual
June 2021 MMI- 20070546
Option Description
On The display automatically shows each display variable for the number of seconds specified
by Scroll Rate, then shows the next display variable. The operator can move to the next display variable at any time by activating Scroll.
Off The display shows Display Variable 1 and does not scroll automatically. The operator can
move to the next display variable at any time by activating Scroll.
Default: Off
2. If you turned on Auto Scroll, set Scroll Rate as desired.
Default: 10
Range: 1 to 30 seconds
Tip
Scroll Rate may not be available until you apply Auto Scroll.

7.1.6 Configure the display backlight

Display Menu Configuration Display Settings
ProLink III Device Tools Configuration Transmitter Display General Backlight
DeltaV AMS Configuration Manual Setup Display Backlight Control
Siemens PDM Device Manual Setup Display Backlight Control
You can control the intensity and contrast of the backlight on the display's LCD panel.
Procedure
1. Set Intensity as desired.
Default: 50
Range: 0 to 100
2. Set Contrast as desired.
Default: 50
Range: 0 to 100

7.1.7 Configure security for the display

Display
ProLink III Device Tools Configuration Transmitter Display Display Security
DeltaV AMS Configure Manual Setup Display Display Menus
Siemens PDM Device Manual Setup Display Display Menus
Menu Configuration Security Display Security
98 Micro Motion 5700 Transmitters with PROFIBUS-PA
Page 99
Configuration and Use Manual Configure device options and preferences
MMI- 20070546 June 2021
When using the display, you can require users to enter a password to do any of the following tasks:
Enter the main menu
Change a parameter
Access alert data through the display
Start, stop, or reset totalizers or inventories via the context menu
The display password can be the same or different from the totalizer/inventory context menu control password. If different, the display password is used to reset, start, and stop totalizers or inventories using Menu Operations Totalizers.
Procedure
1. Configure Password Required as desired.
Option Description
At Write When an user chooses an action that leads to a configuration change, they are
prompted to enter the display password.
Enter Menu When the menu is selected from the process variable screen, the display password
will be immediately required if Password Required is set.
Never (default) When a user chooses an action that leads to a configuration change, they are
prompted to activate ⇦⇧⇩⇨. This is designed to protect against accidental changes to configuration. It is not a security measure.
2. If the At Write or Enter Menu option was selected, enable or disable alert security as desired.
Option
Description
Enabled If an alert is active, the alert symbol is shown in the upper right corner of the display but
the alert banner is not displayed. If the operator attempts to enter the alert menu, they are prompted to enter the display password.
Disabled If an alert is active, the alert symbol is shown in the upper right corner of the display and
the alert banner is displayed automatically. No password or confirmation is required to enter the alert menu.
Restriction
You cannot set Password Required to Never and enable alert security.
If you did not enable Password Required, alert security is disabled and cannot be enabled.
Alert security is disabled automatically if you set Password Required to Never after:Password Required is initially set to either At Write or Enter Menu
Alert security is enabled
Configuration and Use Manual 99
Page 100
Configure device options and preferences Configuration and Use Manual
June 2021 MMI- 20070546
3. If Password Required has been set to At Write or Enter Menu, you will be prompted to enter the desired password.
Default: AAAA
Range: Any four alphanumeric characters
Password Required must be set to At Write or Enter Menu to enable the totalizer/inventory control
context menu password option.
Important
If you enable Password Required but you do not change the display password, the transmitter will post a configuration alert.
4. Configure Main Menu Available as desired.
Option Description
Enabled The local display Menu option from the process variable screen will be accessible.
Disabled The local display Menu option from the process variable screen will not be accessible.
Important
Once Main Menu Available has been disabled, you cannot enable it from the local display. Use another configuration tool, such as ProLink III, to re-enable main menu access from the local display.

7.1.8 Configure totalizer and inventory control

Display
ProLink III Device Tools Configuration Totalizer Control Methods
DeltaV AMS Configure Manual Setup Display Totalizer Options
Siemens PDM Device Manual Setup Display Totalizer Options
You can enable or disable the operator's ability to start, stop, or reset totalizers or inventories. The totalizer/ inventory control context menus password can also be configured. The context menu is accessed by selecting the options menu from the process variable screen when a total or inventory is displayed.
These parameters do not affect the operator's ability to start, stop, or reset totalizers or inventories using another tool.
Procedure
1. Enable or disable Reset Totalizers, as desired.
Default = Enable
Menu Configuration Security Display Security Totalizers & Inventories
Configure Manual Setup Display Inventory Options
Device Manual Setup Display Inventory Options
2. Enable or disable Start/Stop Totalizers, as desired.
Default = Enable
3. Enable or disable Reset Inventory, as desired.
100 Micro Motion 5700 Transmitters with PROFIBUS-PA
Loading...