Micro Motion™ 5700 Transmitters with
Configurable Inputs and Outputs
All Installation Types (Integral, four-Wire, and nine-Wire)
April 2022
Safety messages
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are
available: the EU Declaration of Conformity, with all applicable European directives, and the complete ATEX installation drawings
and instructions. In addition, the IECEx installation instructions for installations outside of the European Union and the CSA
installation instructions for installations in North America are available at Emerson.com or through your local Micro Motion
support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found at Emerson.com. For
hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Troubleshooting information can be found in the Configuration Manual. Product data sheets and manuals are available from the
Micro Motion web site at Emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at Emerson.com, or by calling the Micro Motion Customer
Service department.
2
Installation ManualContents
MMI-20027478April 2022
Contents
Chapter 1Before you begin........................................................................................................5
1.1 About this document...................................................................................................................5
3.3 Wire a remote-mount transmitter to the sensor........................................................................ 16
3.4 Ground the meter components................................................................................................. 18
3.5 Rotate the transmitter on the sensor (optional)......................................................................... 20
3.6 Rotate the user interface on the transmitter (optional)..............................................................22
3.7 Rotate the sensor wiring junction box on a remote-mount transmitter (optional)......................23
Chapter 4Wiring the channels................................................................................................. 25
4.1 Available channels..................................................................................................................... 25
4.2 Access the wiring channels........................................................................................................ 26
4.3 Wire the mA output...................................................................................................................27
4.4 Wire the mA/HART® output....................................................................................................... 28
4.5 Wire the frequency output.........................................................................................................31
4.6 Wire the discrete output............................................................................................................34
4.7 Wire the RS-485 output............................................................................................................. 37
4.8 Wire the mA input..................................................................................................................... 37
4.9 Wire the discrete input.............................................................................................................. 38
4.10 Wire the frequency input......................................................................................................... 39
4.11 Wire Channels A and D for Safety Instrumented Systems (SIS) applications............................. 40
Chapter 5Wiring the power supply..........................................................................................45
Chapter 6Wire the printer....................................................................................................... 47
Chapter 7Power up the transmitter.........................................................................................49
Chapter 8Configuring the transmitter with Guided Setup........................................................51
Chapter 9Using the display controls........................................................................................ 53
Chapter 10Available service port connection.............................................................................55
Appendix AWire the Micro Motion 5700 to the Micro Motion 3100 transmitter..........................57
Installation Manual3
ContentsInstallation Manual
April 2022MMI-20027478
4Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualBefore you begin
MMI-20027478April 2022
1Before you begin
1.1About this document
This manual provides information on planning, mounting, wiring, and initial setup of the
Micro Motion 5700 transmitter. For information on full configuration, maintenance,
troubleshooting, or service of the transmitter, see the Configuration and Use Manual.
The information in this document assumes that users understand basic transmitter and
sensor installation, configuration, and maintenance concepts and procedures.
1.2Hazard messages
This document uses the following criteria for hazard messages based on ANSI standards
Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a
situation is not avoided. There is no credible risk of physical injury.
Physical access
WARNING
Unauthorized personnel can potentially cause significant damage and/or
misconfiguration of end users' equipment. Protect against all intentional or
unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access to protect users' assets. This is true for
all systems used within the facility.
1.3Related documentation
You can find all product documentation on the product documentation DVD shipped with
the product or at Emerson.com.
See any of the following documents for more information:
• Micro Motion 5700 Product Data Sheet
Installation Manual5
Before you beginInstallation Manual
April 2022MMI-20027478
• Micro Motion 5700 Transmitters with Configurable Inputs and Outputs: Configuration and
Use Manual
• Coriolis Flow Meter with Micro Motion 5700 Transmitters Safety Manual for Safety
Instrumented Systems (SIS)
• Micro Motion 5700 Transmitters with a Marine Bunker Transfer Package: Application
Manual
• Replacing the Junction Box for the 4200 Transmitter and the 5700 Transmitter
• Replacing the Sensor Cable for the 4200 Transmitter and the 5700 Transmitter
• Sensor installation manual
6Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation Manual
MMI-20027478April 2022
Planning
2Planning
2.1Installation checklist
□ If possible, install the transmitter in a location that will prevent direct exposure to
sunlight. The environmental limits for the transmitter may be further restricted by
hazardous area approvals.
□ If you plan to mount the transmitter in a hazardous area:
WARNING
— Verify that the transmitter has the appropriate hazardous area approval. Each
transmitter has a hazardous area approval tag attached to the transmitter
housing.
— Ensure that any cable used between the transmitter and the sensor meets the
hazardous area requirements.
— For ATEX/IECEx installations, strictly adhere to the safety instructions
documented in the ATEX/IECEx approvals documentation available on the
product documentation DVD shipped with the product or at Emerson.com.
□ Verify that you have the appropriate cable and required cable installation parts for your
installation. For wiring between the transmitter and sensor, verify the maximum cable
length does not exceed 1,000 ft (305 m).
□ Ensure that you use the following cables for the different connections:
— A shielded, twisted-pair instrument cable with drain for all in and out connections
— A twisted-pair shielded cable for the RS-485 (Channel E) connection
□ You can mount the transmitter in any orientation as long as the conduit openings or
transmitter display do not point upward.
Installing the transmitter with the conduit openings or transmitter display facing
upward risks condensation moisture entering the transmitter housing, which could
damage the transmitter.
Following are examples of possible orientations for the transmitter.
Preferred orientation
Alternate orientations
□ To prevent conduit connectors from seizing in the threads of the conduit openings,
apply a conductive anti-galling compound to the threads, or wrap threads with PTFE
Installation Manual7
PlanningInstallation Manual
April 2022MMI-20027478
tape two to three layers deep. Wrap the tape in the opposite direction that the male
threads will turn when inserted into the female conduit opening.
□ Mount the meter in a location and orientation that satisfies the following conditions:
— Allows sufficient clearance to open the transmitter housing cover. Install with 8 in
(203 mm) to 10 in (254 mm) clearance at the wiring access points.
— Provides clear access for installing cabling to the transmitter.
— Provides clear access to all wiring terminals for troubleshooting.
2.2Additional considerations for retrofitting
existing installations
□ The transmitter installation may require 3 in (76 mm) to 6 in (152 mm) of additional
wiring for the input/output and power connections. This length would be in addition to
the currently installed wiring. Confirm you have the additional wiring necessary for the
new installation.
□ Before removing the existing transmitter, be sure to record the configuration data for
the currently installed transmitter. At initial startup of the newly installed transmitter,
you will be prompted to configure the meter via a guided setup.
Record the following information (if applicable):
Variable
Tag
Mass flow units
Volume flow units
Density units
Temperature units
Channel configuration
mA Outputs 1— Power (internal or external):
mA Outputs 2 (optional)— Power (internal or external):
Setting
— Source:
— Scaling (LRV, URV):
— Fault action:
— Source:
— Scaling (LRV, URV):
— Fault action:
8Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation Manual
Planning
MMI-20027478April 2022
VariableSetting
Frequency outputs (optional)— Power (nternal or external):
— Source:
— Scaling (LRV, URV):
— Fault action:
— Dual output:
Discrete outputs (optional)— Power (internal or external):
— Source:
— Scaling (LRV, URV):
— Fault action:
Discrete input (optional)— Power (internal or external):
• 85 to 240 VAC, 50/60 Hz, 6 watts typical, 11 watts maximum
• 18 to 100 VDC, 6 watts typical, 11 watts maximum
Note
For DC power:
• Power requirements assume a single transmitter per cable.
• At start-up, the power source must provide a minimum of 1.5 amps of short-term
current per transmitter and not pull voltage below 18 VDC.
• Length and conductor diameter of the power cable must be sized to provide 18 VDC
minimum at the power terminals, at a load current of 0.7 amps.
Installation Manual9
PlanningInstallation Manual
April 2022MMI-20027478
Cable sizing formula
M = 18V + (R x L x 0.7A)
• M: minimum supply voltage
• R: cable resistance
• L: cable length (in Ω/ft)
Typical power cable resistance at 68 °F (20.0 °C)
Wire gaugeResistance
14 AWG0.0050 Ω/ft
16 AWG0.0080 Ω/ft
18 AWG0.0128 Ω/ft
20 AWG0.0204 Ω/ft
2.5 mm
1.5 mm
1.0 mm
0.75 mm
0.50 mm
2
2
2
2
2
0.0136 Ω/m
0.0228 Ω/m
0.0340 Ω/m
0.0460 Ω/m
0.0680 Ω/m
2.3.1Maximum cable lengths between sensor and transmitter
The maximum cable length between the sensor and transmitter, which are installed
separately, is determined by cable type.
Cable type
Micro Motion 4-wire remote
mount
Micro Motion 9-wire remote
mount
User-supplied 4-wireVDC 22 AWG (0.326 mm²)300 ft (91 m)
Wire gaugeMaximum length
Not applicable• 1,000 ft (305 m) without
Ex-approval
• 500 ft (152 m) with IIC
rated sensors
• 1,000 ft (305 m) with IIB
rated sensors
Not applicable60 ft (18 m)
VDC 20 AWG (0.518 mm²)500 ft (152 m)
VDC 18 AWG (0.823 mm²)1,000 ft (305 m)
RS-485 22 AWG (0.326 mm²)
or larger
1,000 ft (305 m)
10Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualMounting and sensor wiring
MMI-20027478April 2022
3Mounting and sensor wiring
3.1Mounting and sensor wiring for integralmount transmitters
There are no separate mounting requirements for integral transmitters, and there is no
need to connect wiring between the transmitter and the sensor.
3.2Mounting transmitters
There are two options available for mounting transmitters:
• Mount the transmitter to a wall or flat surface.
• Mount the transmitter to an instrument pole.
3.2.1
Mount the transmitter to a wall or flat surface
Prerequisites
• Emerson recommends 5/16-18 (8 mm–1.25) fasteners that can withstand the process
environment. Emerson does not supply bolts or nuts as part of the standard offering
(general purpose bolts and nuts are available as an option).
• Ensure that the surface is flat and rigid and that it does not vibrate or move excessively.
• Confirm that you have the necessary tools and the mounting kit shipped with the
transmitter.
Procedure
1. Attach the mounting bracket to the transmitter and tighten the screws to 80 in lbf
(9.04 N m) to 90 in lbf (10.17 N m).
Installation Manual11
Mounting and sensor wiringInstallation Manual
April 2022MMI-20027478
Figure 3-1: Mounting bracket to an aluminum transmitter
Figure 3-2: Mounting bracket to a stainless steel transmitter
2. For wall-mount installations, secure the mounting bracket to the prepared surface.
12Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualMounting and sensor wiring
MMI-20027478April 2022
Figure 3-3: Wall-mounting bracket and dimensions for an aluminum
transmitter
A. 2.8 in (71 mm)
B. 2.8 in (71 mm)
Figure 3-4: Wall-mounting bracket and dimensions for a stainless steel
transmitter
A. 7.51 in (190.8 mm)
B. 3.67 in (93.2 mm)
Installation Manual13
Mounting and sensor wiringInstallation Manual
April 2022MMI-20027478
3. For aluminum transmitters, place and attach the transmitter-mounting bracket to
the mounting bracket secured to the wall or instrument pole.
Figure 3-5: Attaching and securing an aluminum transmitter to the mounting
bracket
3.2.2
Tip
To ensure the mounting bracket holes are aligned, insert all attachment bolts into
place before tightening.
Mount the transmitter to a pole
Prerequisites
• Ensure that the instrument pole extends at least 12 in (305 mm) from a rigid base and
is no more than 2 in (51 mm) in diameter.
• Confirm that you have the necessary tools, and the instrument-pole mounting kit
shipped with the transmitter.
Procedure
For pole-mount installations, attach the U-bolt mounting piece to the instrument pole.
14Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualMounting and sensor wiring
MMI-20027478April 2022
Figure 3-6: Pole-mounting bracket attachment for an aluminum transmitter
Installation Manual15
Mounting and sensor wiringInstallation Manual
April 2022MMI-20027478
Figure 3-7: Pole-mounting bracket attachment for a stainless steel transmitter
3.3Wire a remote-mount transmitter to the
sensor
Use this procedure to wire a four-wire or nine-wire remote-mount transmitter to the
sensor.
Prerequisites
• Prepare the four-wire cable as described in the sensor documentation.
• Prepare the nine-wire cable as described in the Micro Motion 9-Wire Flow Meter Cable
Preparation and Installation Guide.
• Connect the cable to the sensor-mounted core processor or junction box as described
in the sensor documentation. You can access all product documentation on the
documentation DVD shipped with the product or at Emerson.com.
16Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualMounting and sensor wiring
MMI-20027478April 2022
Procedure
1. Remove the transmitter-to-sensor wiring compartment cover to reveal the terminal
connections.
Figure 3-8: Removal of the transmitter-to-sensor wiring compartment cover
2. Feed the sensor wiring cable into the transmitter wiring compartment.
Figure 3-9: Sensor wiring feedthrough
3. Connect the sensor wires to the appropriate terminals.
Important
Terminate the four-wire cable drain wires only at the sensor/core processor end of
the cable. See the sensor installation manual for more detail. Do not connect the
four-wire cable drain wires to the ground screw located inside the junction box.
• See Figure 3-10 for four-wire terminal connections.
• See Figure 3-11 for nine-wire terminal connections.
Connect the four drain wires in the nine-wire cable to the ground screw located
inside the junction box.
4. Replace the transmitter-to-sensor wiring compartment cover and tighten the
screws to 14 in lbf (1.58 N m) to 15 in lbf (1.69 N m).
3.4Ground the meter components
In 4-wire or 9-wire remote installations, the transmitter and sensor are grounded
separately.
18Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualMounting and sensor wiring
MMI-20027478April 2022
Prerequisites
NOTICE
Improper grounding could cause inaccurate measurements or meter failure.
WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result
in an explosion causing death or serious injury.
Note
For hazardous area installations in Europe, refer to standard EN 60079-14 or national
standards.
If national standards are not in effect, adhere to the following guidelines for grounding:
• Use copper wire, 14 AWG (2.08 mm2) or larger wire size.
• Keep all ground leads as short as possible, less than 1 Ω impedance.
• Connect ground leads directly to earth, or follow plant standards.
Procedure
1. Ground the Coriolis sensor according to the instructions in the sensor installation
manual for your Coriolis sensor.
2. Ground the transmitter according to applicable local standards, using the
transmitter’s internal or external ground screw.
• The earth ground terminal is located inside the power wiring compartment.
• The external ground screw is located on the outside of the transmitter housing
below the transmitter tag.
Installation Manual19
Mounting and sensor wiringInstallation Manual
April 2022MMI-20027478
3.5Rotate the transmitter on the sensor (optional)
In integral installations, you can rotate the transmitter on the sensor up to 360° in 45°
increments.
Procedure
1. Using a 4 mm hex key, loosen and remove the clamp securing the transmitter head
in place.
Figure 3-12: Removal of the sensor clamp
2. Gently lift the transmitter straight up, and rotate the transmitter to the desired
position.
You can rotate the transmitter to any of the eight positions, but a stop exists that
will not allow a full 360° rotation.
Figure 3-13: Rotate transmitter head
3. Gently lower the transmitter onto the base, confirming that the transmitter is in a
locked position.
20Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualMounting and sensor wiring
MMI-20027478April 2022
4. Replace the clamp in its original position and tighten the cap screw. Torque to 28 in
lbf (3.16 N m) to 30 in lbf (3.39 N m).
Figure 3-14: Re-attachment of the sensor clamp
Installation Manual21
Mounting and sensor wiringInstallation Manual
April 2022MMI-20027478
3.6Rotate the user interface on the transmitter
(optional)
The user interface on the transmitter electronics module can be rotated 90°, 180°, or 270°
from the original position.
Figure 3-15: Display components
A. Transmitter housing
B. Sub-bezel
C. Display module
D. Display screws
E. End-cap clamp
F. Cap screw
G. Display cover
Procedure
1. Shut off power to the unit.
WARNING
If the transmitter is in a hazardous area, wait five minutes after disconnecting the
power. Failure to do so could result in an explosion causing death or injury.
2. Loosen and rotate the end cap clamp so that it does not interfere with the cover.
3. Turn the display cover counterclockwise to remove it from the main enclosure.
4. Carefully loosen the captive display screws while holding the display module in
place.
5. Carefully pull the display module out of the main enclosure.
6. Rotate the display module to the desired position.
22Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualMounting and sensor wiring
MMI-20027478April 2022
7. Gently press the display module back onto the connector.
8. Tighten display screws.
9. Place the display cover onto the main enclosure.
10. Turn the display cover clockwise until it is fully seated.
11. Replace the end-cap clamp by tightening the cap screw.
12. Restore power to the transmitter.
3.7Rotate the sensor wiring junction box on a
remote-mount transmitter (optional)
In remote-mount installations, you can rotate the sensor wiring junction box on the
transmitter plus or minus 180º.
Procedure
1. Using a 4 mm hex key, loosen and remove the clamp securing the sensor wiring
junction box in place.
Figure 3-16: Removal of the clamp
2. Gently rotate the junction box to the desired position.
You can rotate the junction box plus or minus 180° to any position.
Installation Manual23
Mounting and sensor wiringInstallation Manual
April 2022MMI-20027478
Figure 3-17: Rotate the transmitter on the junction box
3. Gently set the junction box into its new position, confirming that the position is
locked.
4. Replace the clamp in its original position and tighten the cap screw. Torque to 28 in
lbf (3.16 N m) to 30 in lbf (3.39 N m).
Figure 3-18: Re-attach the clamp
24Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualWiring the channels
MMI-20027478April 2022
4Wiring the channels
Note
To prevent conduit connectors from seizing in the threads of the conduit openings, apply
a conductive anti-galling compound to the threads, or wrap threads with PTFE tape two to
three layers deep.
Wrap the tape in the opposite direction that the male threads will turn when inserted into
the female conduit opening.
4.1Available channels
SignalChannel AChannel BChannel CChannel DChannel E
Wiring
terminals
mA inputs
and outputs
Frequency
outputs
Discrete
outputs
Discrete
inputs
Frequency
inputs
(1) Frequency output 2 can be mapped to Channel B or D. For multiple frequency outputs, use Frequency 1 on Channel C
1. Remove the wiring access cover to reveal the inputs and outputs wiring terminal
block connectors.
2. Confirm which transmitter channels are activated, or ON, and identify the type of
configuration you will be wiring to based on the options available.
Figure 4-1: Activated channel identification
A. Key to identify the activated input/outputs
3. Record the channel and wiring configuration on the label provided inside the
transmitter housing cover.
26Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
A
D
C
B
Installation ManualWiring the channels
MMI-20027478April 2022
Figure 4-2: Channel and wiring configurations label
4.3Wire the mA output
Wire the mA output in explosion-proof, nonincendive, or nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel.
4.3.1
Wire the mA output (internally powered)
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-3: mA output wiring (internally powered)
A. mA output
B. Channel A, B, or C
C. 820 Ω maximum loop resistance
D. Signal device
Installation Manual27
A
E
D
C
B
0
100
200
300
400
500
600
700
800
900
1000
1100
07.515.022.530.0
B
A
Wiring the channelsInstallation Manual
April 2022MMI-20027478
4.3.2Wire the mA output (externally powered)
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-4: mA output wiring (externally powered)
A. mA output
B. Channel A, B, or C
C. 5–30 VDC (maximum)
D. See Figure 4-5 for maximum loop resistance
E. Signal device
Figure 4-5: Externally-powered mA output: maximum loop resistance
A. Maximum resistance (Ω)
B. External supply voltage (V)
4.4Wire the mA/HART® output
Wire the mA/HART output in explosion-proof, nonincendive, or nonhazardous
installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel.
28Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
A
1
2
C
B
A
1
2
D
C
B
Installation ManualWiring the channels
MMI-20027478April 2022
4.4.1Wire the mA/HART® output (internally powered)
B. 5–30 VDC (maximum)
C. 250–600 Ω resistance (see Figure 4-8 for maximum loop resistance)
D. HART device
Installation Manual29
0
100
200
300
400
500
600
700
800
900
1000
1100
07.515.022.530.0
B
A
B
A
C
E
D
F
I give up
Wiring the channelsInstallation Manual
April 2022MMI-20027478
Figure 4-8: Externally-powered mA/HART output: maximum loop resistance
A. Maximum resistance (Ω)
B. External supply voltage (V)
4.4.3
Wire the mA/HART® multidrop installation (internally or
externally powered)
Procedure
See the Figure 4-9 for information on wiring a mA/HART multidrop installation.
Figure 4-9: mA/HART multidrop wiring
30Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
A. 250–600 Ω resistance
B. HART-compatible host or controller
C. HART-compatible transmitter (internally powered)
D. Micro Motion 5700 transmitter (internally powered) mA/HART connections
E. SMART FAMILY™ transmitters
F. 24 VDC loop power supply required for external transmitter
A
D
C
B
0
2
4
6
8
10
12
14
16
18
20
22
24
02505007501000
A
B
Installation ManualWiring the channels
MMI-20027478April 2022
4.5Wire the frequency output
Use this section to wire the frequency output in explosion-proof, nonincendive, or
nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel.
4.5.1Wire the frequency output (internally powered)
Use this procedure to wire the internally-powered frequency output for Channel B or C.
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-10: Frequency output wiring (internally powered)
Figure 4-11: Internally powered frequency output: output amplitude versus load
resistance [24 VDC (Nom) open circuit]
Installation Manual31
A. Frequency output
B. Channel B or C
C. See Figure 4-11for output amplitude versus load resistance
D. Counter
A. Output amplitude (V)
B. Load resistor (Ω)
A
B
E
D
C
A
7
8
C
B
Wiring the channelsInstallation Manual
April 2022MMI-20027478
4.5.2Wire the frequency output (externally powered)
Use this procedure to wire the externally-powered frequency output for Channel B or C.
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-12: Frequency output wiring (externally powered)
A. Frequency output
B. Channel B or C
C. 5–30 VDC (maximum)
D. Current limiting resistor. Close resistor to limit current below 500mA (maximum).
Current= C (VDC)/ D (ohms).
E. Counter
4.5.3
Wire the frequency output (internally powered)
(Channel D)
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-13: Frequency output wiring (internally powered)
A. Frequency output
B. See Figure 4-14 for output amplitude versus load resistance
C. Counter
32Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
0
2
4
6
8
10
12
14
16
18
20
22
24
025005000750010000
A
B
A
7
8
D
C
B
Installation ManualWiring the channels
MMI-20027478April 2022
Figure 4-14: Internally powered frequency output: output amplitude versus load
resistance [24 VDC (Nom) open circuit]
A. Output amplitude (V)
B. Load resistor (Ω)
4.5.4
Wire the frequency output (externally powered Channel
D)
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-15: Frequency output wiring (externally powered)
A. Frequency output
B. 3–30 VDC (maximum)
C. 500 mA current (maximum)
Installation Manual33
D. Signal device
A
D
C
B
0
2
4
6
8
10
12
14
16
18
20
22
24
0750150022503000
A
B
Wiring the channelsInstallation Manual
April 2022MMI-20027478
4.6Wire the discrete output
Use this section to wire the discrete output in explosion-proof, nonincendive, or
nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel.
4.6.1Wire the discrete output (internally powered)
Use this procedure to wire the internally-powered discrete output for Channel B or C.
Use this section to wire the frequency input in explosion-proof, nonincendive, or
nonhazardous installations.
Important
Meter installation and wiring should be performed only by suitably-trained personnel.
4.10.1
Wire the frequency input (internally powered)
Procedure
Wire to the appropriate input terminal and pins.
Figure 4-27: Frequency input wiring (internally powered)
A. Frequency input
B. Frequency input device
C. (Optional) 1–10 KΩ resistor/open collector
D. (Optional) 3–30 VDC
Installation Manual39
A
D
B
C
7
8
Wiring the channelsInstallation Manual
April 2022MMI-20027478
4.10.2Wire the frequency input (externally powered)
Procedure
Wire to the appropriate input terminal and pins.
Figure 4-28: Frequency input wiring (externally powered)
A. Frequency input
B. Frequency input device
C. 1–10 KΩ resistance
D. 3–30 VDC
4.11Wire Channels A and D for Safety Instrumented
Systems (SIS) applications
Use this procedure to wire Channels A and D for SIS applications.
Procedure
Use one of the following power options:
• Channel A active (internal) power and Channel D passive (external) power
• Channel A passive (external) power and Channel D passive (external) power
40Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualWiring the channels
MMI-20027478April 2022
Figure 4-29: Channel A active (internal) and Channel D passive (external) power
A. Channel A mA output
B. Channel D mA input
C. Terminals
D. 820 ohm maximum loop resistance including 100 ohms (H) for mA input (250–600 ohm
for HART communications)
E. Signal device
F. Terminal compartment
G. External to the 5700
H. 100 ohm input resistance
Installation Manual41
0
100
200
300
400
500
600
700
800
900
1000
1100
07.515.022.530.0
B
A
Wiring the channelsInstallation Manual
April 2022MMI-20027478
Figure 4-30: Channel A passive (external) and Channel D passive (external) power
A. Channel A mA output
B. Channel D mA input
C. Terminals
D. Maximum loop resistance including 100 ohms (I) for mA input — see Figure 4-31.
E. Signal device
F. 5–30 VDC (maximum)
G. Terminal compartment
H. External to the 5700
I. 100 ohm input resistance
Figure 4-31: Externally-powered mA/HART output: maximum loop resistance
42Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
A. Maximum resistance (Ω)
B. External supply voltage (V)
Installation ManualWiring the channels
MMI-20027478April 2022
Note
The calculation for loop resistance must include 100 ohms for the mA Input.
Postrequisites
To configure your system for SIS applications, see the Coriolis Flow Meter with Micro Motion
5700 Transmitters Safety Manual for Safety Instrumented Systems (SIS) and the Micro Motion
5700 Transmitters with Configurable Inputs and Outputs: Configuration and Use Manual.
Installation Manual43
Wiring the channelsInstallation Manual
April 2022MMI-20027478
44Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
A
B
C
Installation ManualWiring the power supply
MMI-20027478April 2022
5Wiring the power supply
You can install a user-supplied switch in the power supply line.
Important
For compliance with the Low Voltage Directive 2014/35/EU (European installations), verify
that the transmitter is located in close proximity to a switch.
Procedure
1. Remove the wiring access cover.
2. Open the Power warning flap to locate the power terminals.
Figure 5-1: Location of power supply wiring terminals and equipment ground
A. Power supply wiring terminals (+ and -)
B. Conduit connection for power supply wiring
C. Equipment ground
3. Connect the power supply wires.
• For DC power: connect to terminals + and –.
• For AC power: connect to terminals L/L1 (line) and N/L2 (neutral).
NOTICE
Do not use the conduit specified for power supply wires for input/output wiring (see
Figure 5-1) to avoid pinched wires when the cover is closed.
4. Tighten the two screws holding the power connector in place.
5. Ground the power supply using the equipment ground, also under the Power
warning flap.
Installation Manual45
Wiring the power supplyInstallation Manual
April 2022MMI-20027478
46Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualWire the printer
MMI-20027478April 2022
6Wire the printer
Procedure
Wire the RS-232-RS-485 adapter terminals to the transmitter terminals.
ConverterTerminals
K2 ADE• Wire the K2 ADE terminal 1 to Channel E, RS-485B, terminal
10
• Wire the K2 ADE terminal 2 to Channel E, RS-485A, terminal 9
K2• Wire the K2 terminal 3 to Channel E, RS-485B, terminal 10
• Wire the K2 terminal 4 to Channel E, RS-485A, terminal 9
Figure 6-1: Wiring between the K2 terminals to the transmitter terminals
A. Transmitter with end-cap removed
Important
For a K2 ADE converter, use terminals 1 and 2 on the converter.
For more information, see RS-485/RS-232 adapter instructions supplied by the
manufacturer.
Installation Manual47
Wire the printerInstallation Manual
April 2022MMI-20027478
48Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualPower up the transmitter
MMI-20027478April 2022
7Power up the transmitter
The transmitter must be powered up for all configuration and commissioning tasks or for
process measurement.
Procedure
1.WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while
the transmitter is powered up. Failure to follow these instructions can cause an
explosion resulting in injury or death.
Ensure that all transmitter and sensor covers and seals are closed.
2. Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. The transmitter is
self-switching and will automatically detect the supply voltage. When using DC
power, a minimum of 1.5 amps of startup current is required. During this period,
Alert 009 is active. The diagnostic routines should complete in approximately
30 seconds. The status LED will turn green and begin to flash when the startup
diagnostics are complete. If the status LED exhibits different behavior, an alert is
active.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the
electronics can take up to ten minutes to reach thermal equilibrium. Therefore, if this is
the initial startup, or if power has been off long enough to allow components to reach
ambient temperature, allow the electronics to warm up for approximately ten minutes
before relying on process measurements. During this warm-up period, you may observe
minor measurement instability or inaccuracy.
Installation Manual49
Power up the transmitterInstallation Manual
April 2022MMI-20027478
50Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualConfiguring the transmitter with Guided Setup
MMI-20027478April 2022
8Configuring the transmitter with
Guided Setup
At initial start-up of the transmitter, the guided configuration screen appears on the
transmitter display. This tool guides you through basic configuration of the transmitter.
The guided setup allows you to upload configuration files, set the transmitter display
options, configure channels, and review sensor calibration data.
Procedure
To access the guided setup screen from the display main menu, go to: Startup Tasks →
Guided Setup.
Installation Manual51
Configuring the transmitter with Guided SetupInstallation Manual
April 2022MMI-20027478
52Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualUsing the display controls
MMI-20027478April 2022
9Using the display controls
The transmitter display interface includes a display (LCD panel) and four optical switches –
left, up, down, and right arrow keys – used to access the display menus and navigate the
display screens.
Procedure
1. To activate an optical switch, block the light by holding your thumb or finger in
front of the opening.
You can activate the optical switch through the lens. Do not remove the transmitter
housing cover.
Important
The transmitter only detects one switch selection at a time. Be sure to place your
thumb or finger directly over a single optical switch, and ensure no other switches
are being obstructed.
Figure 9-1: Proper finger positioning for activating an optical switch
2. Use the arrow indicators on the display screen to identify which optical switch to
use to navigate the screen (see examples 1 and 2).
Important
When using the arrow keys, you must first activate the optical switch then release
the same switch by removing your finger from the glass to move up, down, right,
left or to make a selection. To enable auto-scroll when navigating up or down,
activate the appropriate switch and continue to hold for one second. Release the
switch when the desired selection is highlighted.
Installation Manual53
Using the display controlsInstallation Manual
April 2022MMI-20027478
Figure 9-2: Example 1: Active arrow indicators on the transmitter display
Figure 9-3: Example 2: Active arrow indicators on the transmitter display
54Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
Installation ManualAvailable service port connection
MMI-20027478April 2022
10Available service port connection
Use the service port connection to download or upload data from/to the transmitter.
To access the service port, you can use commonly-available USB hardware, such as a USB
drive, or USB cable.
WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the
transmitter is powered up. Failure to follow these instructions can cause an explosion
resulting in injury or death.
The service port connection is located under the Service Port warning flap at the wiring
access points.
Installation Manual55
Available service port connectionInstallation Manual
April 2022MMI-20027478
56Micro Motion 5700 Transmitters with Configurable Inputs and Outputs
F3
C A
IEC 127-2
J3
DISC
OUT 3
T5A 250V
C A
F1
C A
IEC 127-2
J1
J4
MODEL 3300/350 0
TERMINAL
CONNECTION
DS1
T5A 250V
K3K2K1
ABC
'
(
)
DISC
OUT 2
IEC 127-2
F2 T5A 250V
J2
DS2
DISC
OUT 1
DS3
1 2 3 4 5 6 7 8 9 10
A14
C18
C16
C14
Installation ManualWire the Micro Motion 5700 to the Micro Motion 3100 transmitter
MMI-20027478April 2022
AWire the Micro Motion 5700 to the
Micro Motion 3100 transmitter
Prerequisites
• Set up the transmitter channel configuration to DO before wiring.
• Use active high and internal power.
• Use wire size 24 AWG (0,25 mm2) to 16 AWG (1,5 mm2).
Procedure
Tie the three ground pins of the 5700 together and then land on A14 of the 3100. The
ground pins are even numbers: 4, 6, and 8.
Example (see the following figure): Use relay 1 (C) and 2 (B) with Channels B and C, then
connect terminal 2 and 4 together from 5700 and land on A14.
Figure A-1: 5700 to 3100 - screw-type or solder-tail connector
This graphic sets Channel B, configured as digital output (DO)1, to relay 1. If a different
channel is assigned to DO, wire any DO to any relay.
A. Relay 3, DO 3 pins 6 and 7, C18
B. Relay 2, DO 2 pins 5 and 6, C16
C. Relay 1, DO 1 pins 3 and 4, C14
D. Channel D
The Emerson logo is a trademark and service mark of Emerson
Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct
Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of
their respective owners.
www.emerson.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.