Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration
of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available
on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion
Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States800-522-6277U.K. and Ireland0870 240 1978Australia800 158 727
Chapter 9Using the display controls........................................................................................ 51
Chapter 10Available service port connection............................................................................. 53
Appendix AWire the 5700 to the 3100 relays..............................................................................55
Installation Manual3
ContentsInstallation Manual
August 2020MMI-20029768
4 Micro Motion 5700 Ethernet Transmitters
Installation ManualBefore you begin
MMI-20029768August 2020
1 Before you begin
1.1 About this document
This manual provides information on planning, mounting, wiring, and initial setup of the 5700 transmitter.
For information on full configuration, maintenance, troubleshooting, or service of the transmitter, see the
configuration and use manual.
The information in this document assumes that users understand basic transmitter and sensor installation,
configuration, and maintenance concepts and procedures.
1.2 Hazard messages
This document uses the following criteria for hazard messages based on ANSI standards Z535.6-2011
(R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided.
There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users'
equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to protecting your system.
Restrict physical access to protect users' assets. This is true for all systems used within the facility.
1.3 Related documentation
You can find all product documentation on the product documentation DVD shipped with the product or at
www.emerson.com.
See any of the following documents for more information:
• Micro Motion 5700 Product Data Sheet
• Micro Motion 5700 with Ethernet Transmitters: Configuration and Use Manual
□ If possible, install the transmitter in a location that will prevent direct exposure to sunlight. The
environmental limits for the transmitter may be further restricted by hazardous area approvals.
□ If you plan to mount the transmitter in a hazardous area:
WARNING
— Verify that the transmitter has the appropriate hazardous area approval. Each transmitter has a
hazardous area approval tag attached to the transmitter housing.
— Ensure that any cable used between the transmitter and the sensor meets the hazardous area
requirements.
— For ATEX/IECEx installations, strictly adhere to the safety instructions documented in the ATEX/IECEx
approvals documentation available on the product documentation DVD shipped with the product or
at www.emerson.com.
□ Verify that you have the appropriate cable and required cable installation parts for your installation. For
wiring between the transmitter and sensor, verify the maximum cable length does not exceed 1,000 ft
(305 m).
□ Ensure that you use the following cables for the different connections:
— A twisted-pair instrument cable for the Channel C I/O connection
— A shielded Cat5e or higher rated instrumentation cable for the Ethernet connections
□ You can mount the transmitter in any orientation as long as the conduit openings or transmitter display do
not point upward.
Installing the transmitter with the conduit openings or transmitter display facing upward risks
condensation moisture entering the transmitter housing, which could damage the transmitter.
Following are examples of possible orientations for the transmitter.
Preferred orientation
Alternate orientations
□ Mount the meter in a location and orientation that satisfies the following conditions:
— Allows sufficient clearance to open the transmitter housing cover. Install with 8 in (203 mm) to 10 in
(254 mm) clearance at the wiring access points.
— Provides clear access for installing cabling to the transmitter.
— Provides clear access to all wiring terminals for troubleshooting.
Installation Manual7
PlanningInstallation Manual
August 2020MMI-20029768
2.2 Additional considerations for retrofitting existing
installations
□ The transmitter installation may require 3 in (76 mm) to 6 in (152 mm) of additional wiring for the input/
output and power connections. This length would be in addition to the currently installed wiring. Confirm
you have the additional wiring necessary for the new installation.
□ Before removing the existing transmitter, be sure to record the configuration data for the currently
installed transmitter. At initial startup of the newly installed transmitter, you will be prompted to
configure the meter via a guided setup.
Record the following information (if applicable):
VariableSetting
Tag
Mass flow units
Volume flow units
Density units
Temperature units
Channel configuration
mA Output 1— Power (Internal or External):
— Source:
— Scaling (LRV, URV):
— Fault Action:
mA Output 2 (optional)— Power (Internal or External):
— Source:
— Scaling (LRV, URV):
— Fault Action:
Frequency Output (optional)— Power (Internal or External):
— Source:
— Scaling (LRV, URV):
— Fault Action:
— Dual output:
Discrete Output (optional)— Power (Internal or External):
— Source:
— Scaling (LRV, URV):
— Fault Action:
8 Micro Motion 5700 Ethernet Transmitters
Installation ManualPlanning
MMI-20029768August 2020
VariableSetting
Discrete Input (optional)— Power (Internal or External):
• 85 to 240 VAC, 6.5 watts typical, 9 watts maximum
• 18 to 100 VDC, 6.5 watts typical, 9 watts maximum
Note
For DC power:
• Power requirements assume a single transmitter per cable.
• At startup, the power source must provide a minimum of 1.5 amps of short-term current per transmitter
and not pull voltage below 18 VDC.
• Length and conductor diameter of the power cable must be sized to provide 18 VDC minimum at the
power terminals, at a load current of 0.7 amps.
Cable sizing formula
M = 18V + (R x L x 0.7A)
• M: minimum supply voltage
• R: cable resistance
• L: cable length (in Ω/ft)
Typical power cable resistance at 68 °F (20.0 °C)
Wire gauge
14 AWG0.0050 Ω/ft
16 AWG0.0080 Ω/ft
Installation Manual9
Resistance
PlanningInstallation Manual
August 2020MMI-20029768
Wire gaugeResistance
18 AWG0.0128 Ω/ft
20 AWG0.0204 Ω/ft
2.5 mm
1.5 mm
1.0 mm
0.75 mm
0.50 mm
2
2
2
2
2
0.0136 Ω/m
0.0228 Ω/m
0.0340 Ω/m
0.0460 Ω/m
0.0680 Ω/m
2.3.1 Maximum cable lengths between sensor and transmitter
The maximum cable length between the sensor and transmitter that are separately installed is determined by
cable type.
Cable typeWire gaugeMaximum length
Micro Motion 4-wire remote mountNot applicable• 1,000 ft (305 m) without Ex-
approval
• 500 ft (152 m) with IIC rated
sensors
• 1,000 ft (305 m) with IIB rated
sensors
Micro Motion 9-wire remote mountNot applicable60 ft (18 m)
User-supplied 4-wireVDC 22 AWG (0.326 mm²)300 ft (91 m)
VDC 20 AWG (0.518 mm²)500 ft (152 m)
VDC 18 AWG (0.823 mm²)1,000 ft (305 m)
RS-485 22 AWG (0.326 mm²) or larger 1,000 ft (305 m)
2.4 5700 transmitters in Ethernet networks
You can install the 5700 Ethernet transmitter in star, ring, or daisy-chain networks using industrial-rated
shielded Ethernet cables.
• Make sure that each cable is no longer than 328 ft (99.97 m).
• Connect the 5700 Ethernet transmitter to the host system via a LAN (Local Area Network) and not a WAN
(Wide Area Network).
• Follow all network security best practices.
10 Micro Motion 5700 Ethernet Transmitters
Installation ManualPlanning
MMI-20029768August 2020
2.4.1 Star topology
5700 Ethernet transmitters can be installed in a star network.
Figure 2-1: 5700 star network
A. Programmable Logic Controller (PLC)
B. 5700 with Ethernet output
C. External Ethernet switch
Installation Manual11
PlanningInstallation Manual
August 2020MMI-20029768
2.4.2 Ring topology
5700 Ethernet transmitters can be installed in a ring network.
Figure 2-2: 5700 ring network
A. Programmable Logic Controller (PLC)
B. 5700 with Ethernet output
12 Micro Motion 5700 Ethernet Transmitters
Installation ManualPlanning
MMI-20029768August 2020
2.4.3 Daisy-chain topology
5700 Ethernet transmitters can be installed in a daisy-chain network.
Figure 2-3: 5700 daisy-chain network
A. Programmable Logic Controller (PLC)
B. 5700 with Ethernet output
Installation Manual13
PlanningInstallation Manual
August 2020MMI-20029768
14 Micro Motion 5700 Ethernet Transmitters
Installation ManualMounting and sensor wiring
MMI-20029768August 2020
3 Mounting and sensor wiring
3.1 Mounting and sensor wiring for integral-mount
transmitters
There are no separate mounting requirements for integral transmitters, and no need to connect wiring
between the transmitter and the sensor.
3.2 Mounting transmitters
There are two options available for mounting transmitters:
• Mount the transmitter to a wall or flat surface.
• Mount the transmitter to an instrument pole.
3.2.1 Mounting the transmitter to a wall or flat surface
Prerequisites
• Micro Motion recommends 5/16-18 (M8X1.25) fasteners that can withstand the process environment.
Micro Motion does not supply bolts or nuts as part of the standard offering (general purpose bolts and
nuts are available as an option).
• Ensure that the surface is flat and rigid, does not vibrate, or move excessively.
• Confirm that you have the necessary tools, and the mounting kit shipped with the transmitter.
Procedure
1. Attach the mounting bracket to the transmitter and tighten the screws to 80 in lbf (9.04 N m) to 90 in
lbf (10.17 N m).
Figure 3-1: Mounting bracket to an aluminum transmitter
Installation Manual15
Mounting and sensor wiringInstallation Manual
August 2020MMI-20029768
Figure 3-2: Mounting bracket to a stainless steel transmitter
2. For wall-mount installations, secure the mounting bracket to the prepared surface.
Figure 3-3: Wall-mounting bracket and dimensions for an aluminum transmitter
A. 2.8 in (71 mm)
B. 2.8 in (71 mm)
16 Micro Motion 5700 Ethernet Transmitters
Installation ManualMounting and sensor wiring
MMI-20029768August 2020
Figure 3-4: Wall-mounting bracket and dimensions for a stainless steel transmitter
A. 7.51 in (190.8 mm)
B. 3.67 in (93.2 mm)
3. For aluminum transmitters, place and attach the transmitter-mounting bracket to the mounting
bracket secured to the wall or instrument pole.
Figure 3-5: Attaching and securing an aluminum transmitter to the mounting bracket
Tip
To ensure the mounting bracket holes are aligned, insert all attachment bolts into place before tightening.
Installation Manual17
Mounting and sensor wiringInstallation Manual
August 2020MMI-20029768
3.2.2 Mount the transmitter to a pole
Prerequisites
• Ensure that the instrument pole extends at least 12 in (305 mm) from a rigid base and is no more than 2 in
(51 mm) in diameter.
• Confirm that you have the necessary tools, and the instrument-pole mounting kit shipped with the
transmitter.
Procedure
For pole-mount installations, attach the U-bolt mounting piece to the instrument pole.
Figure 3-6: Pole-mounting bracket attachment for an aluminum transmitter
18 Micro Motion 5700 Ethernet Transmitters
Installation ManualMounting and sensor wiring
MMI-20029768August 2020
Figure 3-7: Pole-mounting bracket attachment for a stainless steel transmitter
3.3 Wire a remote-mount transmitter to the sensor
Use this procedure to wire a 4-wire or 9-wire remote-mount transmitter to the sensor.
Prerequisites
• Prepare the 4-wire cable as described in the sensor documentation.
• Prepare the 9-wire cable as described in the Micro Motion 9-Wire Flow Meter Cable Preparation and
Installation Guide.
• Connect the cable to the sensor-mounted core processor or junction box as described in the sensor
documentation. You can access all product documentation on the documentation DVD shipped with the
product or at www.emerson.com.
Installation Manual19
Mounting and sensor wiringInstallation Manual
August 2020MMI-20029768
Procedure
1. Remove the transmitter-to-sensor wiring compartment cover to reveal the terminal connections.
Figure 3-8: Removal of the transmitter-to-sensor wiring compartment cover
2. Feed the sensor wiring cable into the transmitter wiring compartment.
Figure 3-9: Sensor wiring feedthrough
3. Connect the sensor wires to the appropriate terminals.
Important
Terminate the 4-wire cable drain wires only at the sensor/core processor end of the cable. See the
sensor installation manual for more detail. Do not connect the 4-wire cable drain wires to the ground
screw located inside the 5700 junction box.
• See Figure 3-10 for 4-wire terminal connections.
• See Figure 3-11 for 9-wire terminal connections.
Connect the 4 drain wires in the 9-wire cable to the ground screw located inside the junction box.
4. Replace the transmitter-to-sensor wiring compartment cover and tighten the screws to 14 in lbf
(1.58 N m) to 15 in lbf (1.69 N m).
3.4 Ground the meter components
In 4-wire or 9-wire remote installations, the transmitter and sensor are grounded separately.
Prerequisites
NOTICE
Improper grounding could cause inaccurate measurements or meter failure.
Installation Manual21
Mounting and sensor wiringInstallation Manual
August 2020MMI-20029768
WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion
causing death or serious injury.
Note
For hazardous area installations in Europe, refer to standard EN 60079-14 or national standards.
If national standards are not in effect, adhere to the following guidelines for grounding:
• Use copper wire, 14 AWG (2.08 mm2) or larger wire size.
• Keep all ground leads as short as possible, less than 1 Ω impedance.
• Connect ground leads directly to earth, or follow plant standards.
Procedure
1. Ground the sensor according to the instructions in the sensor documentation.
2. Ground the transmitter according to applicable local standards, using the transmitter’s internal or
external ground screw.
• The internal ground screw is located inside the transmitter-to-sensor wiring compartment.
Figure 3-12: Internal ground screw
• The earth ground terminal is located inside the power wiring compartment.
• The external ground screw is located on the side of the transmitter located below the transmitter
tag.
22 Micro Motion 5700 Ethernet Transmitters
Installation ManualMounting and sensor wiring
MMI-20029768August 2020
Figure 3-13: External ground screw
3.5 Rotate the transmitter on the sensor (optional)
In integral installations, you can rotate the transmitter on the sensor up to 360º in 45º increments.
Procedure
1. Using a 4 mm hex key, loosen and remove the clamp securing the transmitter head in place.
Figure 3-14: Removal of the sensor clamp
Installation Manual23
Mounting and sensor wiringInstallation Manual
August 2020MMI-20029768
2. Gently lift the transmitter straight up, and rotate the transmitter to the desired position.
You can rotate the transmitter to any of the eight positions, but a stop exists that will not allow a full
360° rotation.
Figure 3-15: Rotation of the transmitter head
3. Gently lower the transmitter onto the base, confirming that the transmitter is in a locked position.
4. Replace the clamp in its original position and tighten the cap screw. Torque to 28 in lbf (3.16 N m) to
30 in lbf (3.39 N m).
Figure 3-16: Re-attachment of the sensor clamp
24 Micro Motion 5700 Ethernet Transmitters
Installation ManualMounting and sensor wiring
MMI-20029768August 2020
3.6 Rotate the user interface on the transmitter
(optional)
The user interface on the transmitter electronics module can be rotated 90°, 180°, or 270° from the original
position.
Figure 3-17: Display components
A. Transmitter housing
B. Sub-bezel
C. Display module
D. Display screws
E. End-cap clamp
F. Cap screw
G. Display cover
Procedure
1. Shut off power to the unit.
WARNING
If the transmitter is in a hazardous area, wait five minutes after disconnecting the power. Failure to
do so could result in an explosion causing death or injury.
2. Loosen and rotate the end cap clamp so that it does not interfere with the cover.
3. Turn the display cover counterclockwise to remove it from the main enclosure.
4. Carefully loosen the captive display screws while holding the display module in place.
5. Carefully pull the display module out of the main enclosure.
6. Rotate the display module to the desired position.
7. Gently press the display module back onto the connector.
8. Tighten display screws.
9. Place the display cover onto the main enclosure.
Installation Manual25
Mounting and sensor wiringInstallation Manual
August 2020MMI-20029768
10. Turn the display cover clockwise until it is fully seated.
11. Replace the end-cap clamp by tightening the cap screw.
12. Restore power to the transmitter.
3.7 Rotate the sensor wiring junction box on a remotemount transmitter (optional)
In remote-mount installations, you can rotate the sensor wiring junction box on the transmitter plus or minus
180º.
Procedure
1. Using a 4 mm hex key, loosen and remove the clamp securing the sensor wiring junction box in place.
Figure 3-18: Removal of the clamp
2. Gently rotate the junction box to the desired position.
You can rotate the junction box plus or minus 180º to any position.
Figure 3-19: Rotation of the sensor wiring junction box
3. Gently set the junction box into its new position, confirming that the position is locked.
4. Replace the clamp in its original position and tighten the cap screw. Torque to 28 in lbf (3.16 N m) to
30 in lbf (3.39 N m).
26 Micro Motion 5700 Ethernet Transmitters
Installation ManualMounting and sensor wiring
MMI-20029768August 2020
Figure 3-20: Re-attachment of the clamp
Installation Manual27
Mounting and sensor wiringInstallation Manual
August 2020MMI-20029768
28 Micro Motion 5700 Ethernet Transmitters
Installation ManualWiring the channels
MMI-20029768August 2020
4 Wiring the channels
4.1 Available channels
SignalChannel AChannel BChannel C
Channel
options
EtherNet/IP
The same protocol must be
ordered on both Channel A and
B. ProLink™ III and the Integrated
Webserver can always be
connected to either Channel A or
B.
Modbus TCPModbus TCPFrequency Output
PROFINETPROFINETDiscrete Output
EtherNet/IPmA Output
4.2 Wire the I/O channel
The Channel C I/O can be configured as:
• mA Output
• Frequency Output
• Discrete Output
• Discrete Input
4.2.1 Access the wiring channels
Discrete Input
Procedure
Remove the wiring access cover to reveal the I/O wiring terminal block connectors.
Installation Manual29
A
D
C
B
A
E
D
C
B
Wiring the channelsInstallation Manual
August 2020MMI-20029768
4.2.2 Wire the mA Output
Wire the mA Output for explosion-proof, nonincendive, or nonhazardous installations.
Prerequisites
WARNING
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate
government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-1: Internally-powered mA Output wiring
A. mA Output
B. Channel C
C. 820 Ω maximum loop resistance
D. Signal device
Figure 4-2: Externally-powered mA Output wiring
A. mA Output
B. Channel C
C. 5–30 VDC (maximum)
D. See Figure 4-3
E. Signal device
30 Micro Motion 5700 Ethernet Transmitters
0
100
200
300
400
500
600
700
800
900
1000
1100
07.515.022.530.0
B
A
A
D
C
B
Installation ManualWiring the channels
MMI-20029768August 2020
Figure 4-3: Externally-powered mA Output: maximum loop resistance
A. Maximum resistance (Ω)
B. External supply voltage (V)
4.2.3 Wire the Frequency Output
Wire the Frequency Output in explosion-proof, nonincendive, or nonhazardous installations.
Prerequisites
WARNING
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate
government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-4: Internally-powered FO wiring
A. Frequency Output
B. Channel C
C. See Figure 4-5
D. Counter
Installation Manual31
0
2
4
6
8
10
12
14
16
18
20
22
24
02505007501000
A
B
A
B
E
D
C
Wiring the channelsInstallation Manual
August 2020MMI-20029768
Figure 4-5: Internally-powered FO: output amplitude versus load resistance [24 VDC (Nom) open
circuit]
A. Output amplitude (V)
B. Load resistor (Ω)
Figure 4-6: Externally-powered FO wiring
A. Frequency Output
B. Channel C
C. 5–30 VDC (maximum)
D. 500 mA current (maximum)
E. Counter
4.2.4 Wire the Discrete Output
Wire the Discrete Output in explosion-proof, nonincendive, or nonhazardous installations.
Prerequisites
WARNING
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate
government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
32 Micro Motion 5700 Ethernet Transmitters
A
D
C
B
0
2
4
6
8
10
12
14
16
18
20
22
24
0750150022503000
A
B
Installation ManualWiring the channels
MMI-20029768August 2020
Figure 4-7: Internally-powered DO wiring
A. Discrete Output
B. Channel C
C. See Figure 4-8
D. Counter
Figure 4-8: Internally-powered DO: output amplitude versus load resistance [24 VDC (Nom) open
circuit]
A. Output amplitude (V)
B. Load resistor (Ω)
Installation Manual33
A
B
E
D
C
A
C
B
Wiring the channelsInstallation Manual
August 2020MMI-20029768
Figure 4-9: Externally-powered DO wiring
A. Discrete Output
B. Channel C
C. 3–30 VDC (maximum)
D. 500 mA current (maximum)
E. Counter
4.2.5 Wire the Discrete Input
Prerequisites
WARNING
Wire the Discrete Input in explosion-proof, nonincendive, or nonhazardous installations.
WARNING
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate
government and corporate safety standards.
Procedure
Wire to the appropriate input terminal and pins.
Figure 4-10: Internally-powered DI wiring
A. Discrete Input
B. Channel C
C. Switch
34 Micro Motion 5700 Ethernet Transmitters
A
C
B
Installation ManualWiring the channels
MMI-20029768August 2020
Figure 4-11: Externally-powered DI wiring
A. Discrete Input
B. Channel C
C. 30 VDC (maximum)
Note
• Maximum positive threshold is 3 VDC.
• Minimum negative threshold is 0.6 VDC.
4.2.6 Wire the I/O channel using an M12-terminated cable
(optional)
Use this procedure if you are using an M12-terminated cable to wire the I/O channel.
Prerequisites
Obtain an A-coded M12-terminated cable.
Procedure
1. Attach the M12-terminated cable to the configuration I/O connector on the 5700 transmitter. See
Figure 4-12.
2. Attach the other cable end using the pinouts described in Table 4-1.
Figure 4-12: M12-terminated cables to the configuration I/O
Installation Manual35
Wiring the channelsInstallation Manual
August 2020MMI-20029768
Table 4-1: M12 configuration I/O pinouts
Pin identificationWire colorOutputs
Pin 1Not usedNot used
Pin 2WhitePositive terminal
Pin 3Not usedNot used
Pin 4BlackNeutral terminal
4.3 Wire the Ethernet channels
To meet the EC Directive for Electromagnetic Compatibility (EMC), use a suitable shielded Cat5e, or higherrated instrumentation cable to connect the meter. The instrumentation cable should have an overall screen
to cover all cores. Where permissible, connect the overall screen to earth at the host end (360° bonded).
4.3.1 Wire an Ethernet network using the RJ45 ports
Prerequisites
When using a pre-terminated RJ45 cable, ensure there is no protective boot on the connector, as a protective
boot will not fit through the conduit. Alternatively, you can use the RJ45 connector using a shielded-field
termination connector.
4.3.1 Direct connection and star topology
Procedure
1. Feed the RJ45 cable through the conduit on the 5700 transmitter.
2. Connect the RJ45 cable into either Channel A or Channel B.
Functionality is identical for both Channel A and Channel B as the 5700 transmitter contains an internal
Ethernet switch.
3. Anchor the cable to the module backplate using a cable tie.
36 Micro Motion 5700 Ethernet Transmitters
Installation ManualWiring the channels
MMI-20029768August 2020
Example
4.3.1 Daisy chain and ring topologies
Procedure
1. Feed two RJ45 cables through the conduits on the 5700 transmitter.
Since two cables will not fit into one conduit, you will need to use separate conduits for each cable.
2. Connect the external switch or previous transmitter to Channel A or Channel B.
Functionality is identical for both Channel A and Channel B as the 5700 transmitter contains an internal
Ethernet switch.
3. Connect the next transmitter in the network to the unused channel.
4. Anchor the cables to the module backplate using cable ties.
Example
4.3.2 Wire the Ethernet I/O using M12-terminated cables (optional)
Prerequisites
Obtain two D-coded M12-terminated Ethernet cables.
Procedure
1. Attach both M12-terminated Ethernet cables to the Ethernet I/O connectors on the 5700 transmitter.
See Figure 4-13.
Installation Manual37
Wiring the channelsInstallation Manual
August 2020MMI-20029768
2. Attach the other cable end using the pinouts described in Table 4-2.
Figure 4-13: M12 cables to the Ethernet I/O
Note
Depending on what type of M12 Ethernet option you have, your transmitter may have only the two Ethernet
I/O connectors.
Table 4-2: M12 Ethernet I/O pinouts
Pin
identification
Pin 1Orange/WhitePin 1TDP1/RDP2
Pin 2Green/WhitePin 3RDP1/TDP2
Pin 3OrangePin 2TDN1/RDN2
Pin 4GreenPin 6RDN1/RDN2
Wire colorOutputs on RJ45Signal name
38 Micro Motion 5700 Ethernet Transmitters
Installation ManualPower supply wiring
MMI-20029768August 2020
5 Power supply wiring
5.1 Wiring the power supply
You can install a user-supplied switch in the power supply line.
Important
For compliance with the Low Voltage Directive 2014/35/EU (European installations), verify that the
transmitter is located in close proximity to a switch.
Procedure
1. Remove the wiring access cover.
2. Open the Power warning flap to locate the power terminals.
Figure 5-1: Location of power supply wiring terminals and equipment ground
A. Power supply wiring terminals (+ and -)
B. Equipment ground
3. Connect the power supply wires:
• For DC power: connect to terminals + and –.
• For AC power: connect to terminals L/L1 (line) and N/L2 (neutral).
4. Tighten the two screws holding the power connector in place.
5. Ground the power supply using the equipment ground, also under the Power warning flap.
5.2 Wire the power supply using an M12-terminated
cable (optional)
Use this procedure if you are using an M12-terminated cable to wire the power supply.
Prerequisites
Obtain an S-coded M12-terminated cable.
Installation Manual39
Power supply wiringInstallation Manual
August 2020MMI-20029768
Procedure
1. Attach the M12-terminated cable to the power connector on the 5700 transmitter. See Figure 5-2.
2. Attach the other cable end using the pinouts described in Table 5-1.
Figure 5-2: M12-terminated cable to power supply
Table 5-1: M12 power supply pinouts
Pin identificationOutputs
Pin 1+ / L / L1
Pin 2- / N / L2
Pin 3Not used
GroundRing terminal (C)
40 Micro Motion 5700 Ethernet Transmitters
Installation ManualSet up the printer
MMI-20029768August 2020
6 Set up the printer
Use this section to set up printing with a 5700 Ethernet transmitter and an Epson TM-T88VI printer. For
information on configuring the printer, see Micro Motion 5700 with Ethernet Transmitters: Configuration andUse Manual.
There are two ways to set up printing:
• Use the printer's default IP address
• Change the printer's default IP address
6.1 Set up the printer by changing the printer default IP
address
Use this procedure to set up printing with a 5700 Ethernet transmitter and an Epson TM-T88VI printer by
changing the printer's default IP address.
Procedure
1. Connect one end of an Ethernet cable and power supply to the printer.
2. Connect the other end of the Ethernet cable to the PC.
3. Power on the printer.
The printer IP address prints after a few minutes.
4. Temporarily change the Ethernet address for the PC so that the Ethernet is on the same subnet as the
printer:
Default IP address = 192.168.192.168
a) From Windows 10, right-click the Start button and select Network Connections.
b) Right-click the Ethernet connection and select Properties.
Select Yes on any user account pop-up windows.
c) Select Internet Protocol Version 4(TCP/IPv4), then select properties.
d) Select Use the following IP address and configure the IP address and subnet mask as follows:
• IP address: 192.168.192.x, where x is something other than 0, 1, or 168
• Subnet mask: 255.255.255.0
e) Select OK.
5. Change the printer firmware options.
a) Open your web browser and type http://192.168.192.168 (default printer IP).
The browser displays, Your connection is not private. Ignore the warning and proceed
to the website.
b) Select ADVANCED.
c) Select Proceed to 192.168.192.168.
d) At the login screen, enter:
Installation Manual41
Set up the printerInstallation Manual
August 2020MMI-20029768
Default username: epson
Default password: epson
The EpsonNet Config utility screen displays.
e) Select TCP/IP under the configuration settings (not the basic settings), listed on the left side of
the screen.
f) Change the IP Address (i.e., 192.168.1.55), Subnet Mask, and Default Gateway based on your
network. Select an IP address that is unique to the local network.
The printer must be on the same subnet as the 5700.
g) Required: Set Acquiring the IP Address to Manual.
h) Select Send to save your settings.
i) Select Reset, or power cycle the printer when prompted to apply the changes.
6. Change the PC network settings back to the original settings.
Use the windows you used in Step 4.
7. Configure the 5700 Ethernet transmitter for the printer.
a) Remove the Ethernet cable from the PC and connect it to the 5700 Ethernet transmitter.
b) If you have not already done so, configure the transmitter IP address, subnet mask, and default
Menu → Configuration → Ethernet Settings → Network Settings
For instructions on how to configure the transmitter and PC Ethernet settings, see the MicroMotion 5700 with Ethernet Transmitters: Configuration and Use Manual.
c) Enter the printer IP address you configured in the previous step into the 5700 Ethernet
transmitter.
Display
ProLink IIIDevice Tools →Configuration →Printer and Tickets
Web browserConfiguration→Printer and Tickets
Menu → Configuration → Printer → Printer IP address
8. Perform a test print to verify the settings are correct.
Display
Menu → Operations → Printer → Print Ticket → Print Test Page
ProLink IIIDevice Tools →Configuration →Printer and Tickets
Web browserConfiguration→Printer and Tickets
For instructions on how to configure print ticket options, see the Micro Motion 5700 with Ethernet
Transmitters: Configuration and Use Manual.
42 Micro Motion 5700 Ethernet Transmitters
Installation ManualSet up the printer
MMI-20029768August 2020
If needed, see Function Check Failed in the Status alerts, causes, and recommendations section of the MicroMotion 5700 with Ethernet Transmitters: Configuration and Use Manual.
6.2 Set up the printer using the printer default IP address
Use this procedure to set up printing with a 5700 Ethernet transmitter and an Epson TM-T88VI printer using
the printer's default IP address.
Procedure
1. Connect one end of an Ethernet cable and power supply to the printer.
2. Connect the other end of the Ethernet cable to the PC.
3. Power on the printer.
It can take 1-2 minutes for the printer to finish configuring network settings. When complete, the
following ticket prints.
*********************************
IP Address : 192.168.192.168
SubnetMask : 255.255.255.0
Gateway : 0.0.0.0 DHCP : No server - > Static
*********************************
4. Turn off DHCP if it is enabled.
From the display
a. Go to Menu → Configuration → Ethernet
Settings → Network Settings → Auto obtain
IP()DHCP.
b. Select Disabled and Save.
c. Back out to the Ethernet Settings page to apply the
DHCP off setting.
From ProLink III
a. Go to Device Tools → Configuration → Network
Settings.
b. Uncheck Obtain an IP address automatically
(DHCP).
c. Select Apply.
5. Configure the IP address.
a) Navigate to one of the following screens:
From the display
Go to Menu → Configuration → Ethernet Settings
→ Network Settings → IP address.
From ProLink III
Go to Device Tools → Configuration → Network
Settings.
b) Set the IP address to 192.168.192.x, where x is something other than 0, 1, or 168.
6. Configure the subnet mask.
Installation Manual43
Set up the printerInstallation Manual
August 2020MMI-20029768
a) Navigate to one of the following screens:
From the displayFrom ProLink III
Go to Menu → Configuration → Ethernet Settings
→ Network Settings → Subnet Mask.
b) Set the subnet mask to 255.255.255.0.
7. Configure the printer type.
a) Navigate to one of the following screens:
From the displayFrom ProLink III
Go to Menu → Configuration → Printer → Printer
Type.
b) Verify that the IP address is 192.168.192.168.
Go to Device Tools→Configuration→NetworkSettings.
Go to Device Tools→Configuration→Printer andTickets.
6.3 Reset the interface settings
Use this procedure if you forgot the IP address of your printer and need to reset the default
(192.168.192.168).
Procedure
1. Turn off the printer and close the roll paper cover.
2. If the connector cover is attached, remove the cover.
3. Hold down the status sheet button on the back of the printer while turning on the printer.
A message displays indicating that resetting is being performed.
4. Release the status sheet button to reset the printer settings to default.
Important
Do not turn off power until the process is complete.
When complete, a Resetting to Factory Default Finished message displays.
6.4 Function Check Failed
A functional check alert is commonly triggered due to the following conditions:
• Incorrect network settings configuration
• Out of paper
• Paper tray is open
• Printer already has six open connections
• Another transmitter tries to start a print while another transmitter is printing
Configuration items and audit log tickets can take more than 15 minutes to print and use up paper. If
during this time another transmitter starts a print, the new print may either be rejected, causing a
44 Micro Motion 5700 Ethernet Transmitters
Installation ManualSet up the printer
MMI-20029768August 2020
functional check alert (printer offline), or the print will be inserted in the middle of the configuration/audit
log print.
The functional check alert is cleared after a successful print.
Installation Manual45
Set up the printerInstallation Manual
August 2020MMI-20029768
46 Micro Motion 5700 Ethernet Transmitters
Installation ManualPower up the transmitter
MMI-20029768August 2020
7 Power up the transmitter
The transmitter must be powered up for all configuration and commissioning tasks, or for process
measurement.
Procedure
1.WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is
powered up. Failure to follow these instructions can cause an explosion resulting in injury or death.
Ensure that all transmitter and sensor covers and seals are closed.
2. Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. The transmitter is self-switching and
will automatically detect the supply voltage. When using DC power, a minimum of 1.5 amps of startup
current is required. During this period, Alert 009 is active. The diagnostic routines should complete in
approximately 30 seconds. The status LED will turn green and begin to flash when the startup
diagnostics are complete. If the status LED exhibits different behavior, an alert is active.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics can take up to
10 minutes to reach thermal equilibrium. Therefore, if this is the initial startup, or if power has been off long
enough to allow components to reach ambient temperature, allow the electronics to warm up for
approximately 10 minutes before relying on process measurements. During this warm-up period, you may
observe minor measurement instability or inaccuracy.
Installation Manual47
Power up the transmitterInstallation Manual
August 2020MMI-20029768
48 Micro Motion 5700 Ethernet Transmitters
Installation ManualGuided setup
MMI-20029768August 2020
8 Guided setup
At initial startup of the transmitter, the guided configuration screen appears on the transmitter display. This
tool guides you through basic configuration of the transmitter. The guided setup allows you to upload
configuration files, set the transmitter display options, configure channels, and review sensor calibration data.
Installation Manual49
Guided setupInstallation Manual
August 2020MMI-20029768
50 Micro Motion 5700 Ethernet Transmitters
Installation ManualUsing the display controls
MMI-20029768August 2020
9 Using the display controls
The transmitter display interface includes a display (LCD panel) and four optical switches – left, up, down, and
right arrow keys – used to access the display menus and navigate the display screens.
Procedure
1. To activate an optical switch, block the light by holding your thumb or finger in front of the opening.
You can activate the optical switch through the lens. Do not remove the transmitter housing cover.
Important
The transmitter only detects one switch selection at a time. Be sure to place your thumb or finger
directly over a single optical switch, and ensure no other switches are being obstructed.
Figure 9-1: Proper finger positioning for activating an optical switch
2. Use the arrow indicators on the display screen to identify which optical switch to use to navigate the
screen (see examples 1 and 2).
Important
When using the arrow keys, you must first activate the optical switch then release the same switch by
removing your finger from the glass to move up, down, right, left or to make a selection. To enable
auto-scroll when navigating up or down, activate the appropriate switch and continue to hold for one
second. Release the switch when the desired selection is highlighted.
Installation Manual51
Using the display controlsInstallation Manual
August 2020MMI-20029768
Figure 9-2: Example 1: Active arrow indicators on the transmitter display
Figure 9-3: Example 2: Active arrow indicators on the transmitter display
52 Micro Motion 5700 Ethernet Transmitters
Installation ManualAvailable service port connection
MMI-20029768August 2020
10 Available service port connection
Use the service port connection to download or upload data from/to the transmitter.
To access the service port, you can use commonly-available USB hardware, such as a USB drive, or USB cable.
WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is powered
up. Failure to follow these instructions can cause an explosion resulting in injury or death.
The service port connection is located under the transmitter cap.
Installation Manual53
Available service port connectionInstallation Manual
August 2020MMI-20029768
54 Micro Motion 5700 Ethernet Transmitters
F3
C A
IEC 127 -2
J3
DISC
OUT 3
T5A 250V
C A
F1
C A
IEC 127 -2
J1
J4
DS1
T5A 250V
K3K2K1
ABC
DISC
OUT 2
IEC 127 -2
F2 T5A 250V
J2
DS2
DISC
OUT 1
DS3
C18
C16
C14
A14
Installation ManualWire the 5700 to the 3100 relays
MMI-20029768August 2020
A Wire the 5700 to the 3100 relays
Use this procedure to wire the Discrete Output on the 5700 Ethernet transmitter to the 3100 transmitter
relays for single-stage batch control.
Prerequisites
• Set up the Channel C configuration to DO before wiring
• Use active high and internal power.
• Use wire size 24 AWG (0,25 mm2) to 16 AWG (1,5 mm2).
Procedure
1. Wire the negative terminal on Channel C from the 5700 Ethernet transmitter to A14.
2. Wire the positive terminal on Channel C from the 5700 Ethernet transmitter to either C14, C16, or C18.
Figure A-1: Wiring for 5700 Ethernet Channel C DO to 3100 relays
Installation Manual55
*MMI-20029768*
MMI-20029768
Rev. AD
2020
Micro Motion Inc. USA
7070 Winchester Circle
Boulder, Colorado USA 80301
T +1 303-527-5200
T +1 800-522-6277
F +1 303-530-8459
www.emerson.com
Micro Motion Asia
Emerson Automation Solutions
1 Pandan Crescent
Singapore 128461
Republic of Singapore
T +65 6363-7766
F +65 6770-8003
The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE,
ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of their respective owners.
Micro Motion Europe
Emerson Automation Solutions
Neonstraat 1
6718 WX Ede
The Netherlands
T +31 (0) 318 495 555
T +31 (0) 70 413 6666
F +31 (0) 318 495 556
www.emerson.com/nl-nl
Micro Motion United Kingdom
Emerson Automation Solutions
Emerson Process Management Limited
Horsfield Way
Bredbury Industrial Estate
Stockport SK6 2SU U.K.
T +44 0870 240 1978
F +44 0800 966 181
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.