Micro Motion Micro Motion 1600 with Ethernet Transmitter Configuration and Use Manual Manuals & Guides

Configuration and Use Manual
Micro Motion™ 1600 with Ethernet Transmitter
Configuration and Use Manual
00809-0100-1600, Rev AA
July 2022
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are available: the EU Declaration of Conformity, with all applicable European directives, and the complete ATEX installation drawings and instructions. In addition, the IECEx installation instructions for installations outside of the European Union and the CSA installation instructions for installations in North America are available at Emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found at Emerson.com. For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Troubleshooting information can be found in the Configuration Manual. Product data sheets and manuals are available from the Micro Motion web site at Emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at Emerson.com, or by calling the Micro Motion Customer Service department.
2
Configuration and Use Manual Contents
00809-0100-1600 July 2022

Contents

Chapter 1 Before you begin........................................................................................................7
1.1 About this manual....................................................................................................................... 7
1.2 Hazard messages.........................................................................................................................7
1.3 Related documents......................................................................................................................8
1.4 Communication methods............................................................................................................8
Chapter 2 Quick start................................................................................................................. 9
2.1 Power up the transmitter.............................................................................................................9
2.2 Check meter status......................................................................................................................9
2.3 Commissioning wizards............................................................................................................. 10
2.4 Make a startup connection to the transmitter............................................................................10
2.5 Set the transmitter clock............................................................................................................11
2.6 View the licensed features (optional)......................................................................................... 11
2.7 Set informational parameters.................................................................................................... 12
2.8 Characterize the meter (if required)...........................................................................................12
2.9 Verify mass flow measurement..................................................................................................15
2.10 Verify the zero......................................................................................................................... 15
Chapter 3 Introduction to configuration and commissioning....................................................17
3.1 Security and write protection.....................................................................................................17
3.2 Work with configuration files.....................................................................................................21
Chapter 4 Configure process measurement..............................................................................25
4.1 Configure Sensor Flow Direction Arrow .....................................................................................25
4.2 Configure mass flow measurement........................................................................................... 26
4.3 Configure volume flow measurement for liquid applications..................................................... 31
4.4 Configure Gas Standard Volume (GSV) flow measurement........................................................35
4.5 Configure density measurement................................................................................................40
4.6 Configure temperature measurement....................................................................................... 42
4.7 Configure Pressure Measurement Unit ......................................................................................44
4.8 Configure Velocity Measurement Unit ...................................................................................... 45
Chapter 5 Configure process measurement applications.......................................................... 47
5.1 Set up the API Referral application ............................................................................................ 47
5.2 Set up concentration measurement...........................................................................................57
Chapter 6 Configure advanced options for process measurement............................................ 71
6.1 Configure Response Time ......................................................................................................... 71
6.2 Detect and report two-phase flow............................................................................................. 71
6.3 Configure Flow Rate Switch .......................................................................................................73
6.4 Configure events....................................................................................................................... 73
Configuration and Use Manual 3
Contents Configuration and Use Manual
July 2022 00809-0100-1600
6.5 Configure totalizers and inventories.......................................................................................... 76
6.6 Configure logging for totalizers and inventories.........................................................................79
6.7 Configure Process Variable Fault Action .................................................................................... 80
Chapter 7 Configure device options and preferences................................................................ 83
7.1 Configure the transmitter display.............................................................................................. 83
7.2 Configure the transmitter response to alerts..............................................................................89
Chapter 8 Integrate the meter with the control system............................................................ 97
8.1 Channel configuration............................................................................................................... 97
8.2 Configure Ethernet Channel A....................................................................................................97
8.3 Configure I/O Channel B.............................................................................................................97
8.4 Configure an mA Output............................................................................................................98
8.5 Configure a Frequency Output.................................................................................................106
8.6 Configure a Discrete Output.................................................................................................... 111
Chapter 9 Set the Ethernet protocol....................................................................................... 115
Chapter 10 Configure, setup, and use a printer for tickets.........................................................117
10.1 TM-T88VI printer limitations..................................................................................................117
10.2 Set up the printer...................................................................................................................117
10.3 Reset the interface settings................................................................................................... 120
10.4 Configure the printer and print tickets...................................................................................121
10.5 Configure a discrete event..................................................................................................... 122
10.6 Ticket types........................................................................................................................... 122
Chapter 11 Complete the configuration................................................................................... 125
11.1 Test or tune the system using sensor simulation....................................................................125
11.2 Enable or disable write-protection......................................................................................... 126
Chapter 12 Transmitter operation............................................................................................129
12.1 View process and diagnostic variables................................................................................... 129
12.2 View and acknowledge status alerts...................................................................................... 130
12.3 Read totalizer and inventory values........................................................................................131
12.4 Start, stop, and reset totalizers and inventories..................................................................... 132
Chapter 13 Operation using the batcher...................................................................................135
13.1 Run a batch............................................................................................................................135
13.2 Perform AOC calibration........................................................................................................ 138
Chapter 14 Measurement support............................................................................................141
14.1 Use Smart Meter Verification................................................................................................. 141
14.2 Zero the meter...................................................................................................................... 147
14.3 Validate the meter.................................................................................................................149
14.4 Perform a (standard) D1 and D2 density calibration...............................................................151
14.5 Adjust concentration measurement with Trim Offset ............................................................154
14.6 Adjust concentration measurement with Trim Slope and Trim Offset ................................... 154
4 Micro Motion 1600 with Ethernet Transmitters
Configuration and Use Manual Contents
00809-0100-1600 July 2022
Chapter 15 Maintenance.......................................................................................................... 157
15.1 Install a new transmitter license.............................................................................................157
15.2 Upgrade the transmitter firmware......................................................................................... 158
15.3 Reboot the transmitter.......................................................................................................... 158
15.4 Battery replacement..............................................................................................................159
Chapter 16 Log files, history files, and service files....................................................................161
16.1 Generate history files.............................................................................................................161
16.2 Generate service files.............................................................................................................167
Chapter 17 Troubleshooting.................................................................................................... 173
17.1 Status LED and device status..................................................................................................173
17.2 Network status LED................................................................................................................173
17.3 API Referral troubleshooting..................................................................................................174
17.4 Batch troubleshooting...........................................................................................................174
17.5 Concentration measurement troubleshooting...................................................................... 176
17.6 Density measurement troubleshooting................................................................................. 177
17.7 Discrete Output troubleshooting...........................................................................................179
17.8 Flow measurement troubleshooting......................................................................................180
17.9 Frequency Output troubleshooting....................................................................................... 182
17.10 mA Output troubleshooting................................................................................................ 184
17.11 Status alerts, causes, and recommendations....................................................................... 187
17.12 Check the cutoffs.................................................................................................................205
17.13 Check the direction parameters...........................................................................................205
17.14 Check the drive gain............................................................................................................ 206
17.15 Check for internal electrical problems..................................................................................207
17.16 Check Frequency Output Fault Action .................................................................................207
17.17 Check the scaling of the Frequency Output..........................................................................207
17.18 Check grounding................................................................................................................. 208
17.19 Perform loop tests............................................................................................................... 208
17.20 Check Lower Range Value and Upper Range Value ..............................................................213
17.21 Check mA Output Fault Action ............................................................................................213
17.22 Trim mA Output.................................................................................................................. 213
17.23 Check the pickoff voltage.................................................................................................... 214
17.24 Check power supply wiring.................................................................................................. 215
17.25 Check for radio frequency interference (RFI)........................................................................ 216
17.26 Check sensor-to-transmitter wiring..................................................................................... 216
17.27 Using sensor simulation for troubleshooting....................................................................... 217
17.28 Check the printing............................................................................................................... 217
17.29 Check for two-phase flow (slug flow)................................................................................... 217
17.30 Check the sensor coils..........................................................................................................218
Appendix A Using the transmitter display................................................................................. 221
Configuration and Use Manual 5
Contents Configuration and Use Manual
July 2022 00809-0100-1600
A.1 Components of the transmitter display................................................................................... 221
A.2 Access and use the display menus........................................................................................... 222
Appendix B Using ProLink III with the transmitter..................................................................... 227
B.1 Basic information about ProLink III .......................................................................................... 227
B.2 Connect with ProLink III ...........................................................................................................228
Appendix C Using a web browser to configure the transmitter..................................................231
C.1 Recommended web browsers................................................................................................. 231
C.2 Configuring transmitter and PC Ethernet settings....................................................................231
C.3 Log in with a web browser using a secure connection.............................................................. 232
C.4 Log in with a web browser using an unsecure connection........................................................ 234
C.5 Change Ethernet login passwords............................................................................................235
C.6 Loading an SSL Certificate from a PC to a 1600 transmitter through ProLink III........................ 236
C.7 Import the SSL Certificate into Microsoft® Windows®.............................................................. 237
C.8 Private key file......................................................................................................................... 238
C.9 Import from a Certificate Authority......................................................................................... 238
Appendix D Concentration measurement matrices................................................................... 241
D.1 Standard matrices for the concentration measurement application........................................ 241
D.2 Derived variables and calculated process variables.................................................................. 242
Appendix E Environmental compliance.....................................................................................245
E.1 RoHS and WEEE........................................................................................................................245
Appendix F Example tickets......................................................................................................246
F.1 Print examples......................................................................................................................... 246
6 Micro Motion 1600 with Ethernet Transmitters
Configuration and Use Manual Before you begin
00809-0100-1600 July 2022

1 Before you begin

1.1 About this manual

This manual helps you configure, commission, use, maintain, and troubleshoot a Micro Motion 1600 transmitter with Ethernet.
Important
This manual assumes that:
The transmitter has been installed correctly and completely according to the instructions in the
transmitter installation manual.
Users understand basic transmitter and sensor installation, configuration, and maintenance concepts and
procedures.

1.2 Hazard messages

This document uses the following criteria for hazard messages based on ANSI standards Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided. There is no credible risk of physical injury.
Physical access
WARNING
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access to protect users' assets. This is true for all systems used within the facility.
Configuration and Use Manual 7
Before you begin Configuration and Use Manual
July 2022 00809-0100-1600

1.3 Related documents

You can find all product documentation on the product documentation DVD shipped with the product or at
Emerson.com.
See any of the following documents for more information:
Micro Motion 1600 Transmitters Product Data Sheet
Micro Motion 1600 Transmitters EtherNet/IP Rockwell RSLogix Integration Guide
Micro Motion 1600 Ethernet Transmitters Installation Guide
Sensor installation manual
Replacing the Electronics Assembly Module for the 1600 Transmitter

1.4 Communication methods

You can use several different communications methods to interface with the transmitter. You may use different methods in different locations or for different tasks.
Interface Tool
Display Tactile buttons
Universal Service Port ProLink™ III
Ethernet ports Web browser (http)
EtherNet/IP
Modbus® TCP
For information about how to use the communication tools, see the appendices in this manual.
8 Micro Motion 1600 with Ethernet Transmitters
Configuration and Use Manual Quick start
00809-0100-1600 July 2022

2 Quick start

2.1 Power up the transmitter

The transmitter must be powered up for all configuration and commissioning tasks, or for process measurement.
Procedure
1. Follow appropriate procedures to ensure that a new device on the network does not interfere with
existing measurement and control loops.
2. Verify that the cables are connected to the transmitter as described in the installation manual.
3. Verify that all transmitter and sensor covers and seals are closed.
WARNING
To prevent ignition of flammable or combustible atmospheres, ensure that all covers and seals are tightly closed. For hazardous area installations, applying power while housing covers are removed or loose can cause an explosion resulting in injury or death.
4. Turn on the electrical power at the power supply.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the initial startup, or if power has been off long enough to allow components to reach ambient temperature, allow the electronics to warm up for approximately 10 minutes before relying on process measurements. During this warm-up period, you may observe minor measurement instability or inaccuracy.

2.2 Check meter status

Check the meter for any error conditions that require user action or that affect measurement accuracy.
Procedure
1. Wait approximately 10 seconds for the power-up sequence to complete.
Immediately after power-up, the transmitter runs through diagnostic routines and checks for error conditions. During the power-up sequence, the Transmitter Initializing alert is active. This
alert should clear automatically when the power-up sequence is complete.
2. Check the status LED on the transmitter.
Table 2-1: Status LED and device status (MMI mode)
Status LED condition Device status
Solid green No alerts are active.
Solid yellow One or more alerts are active with Alert Severity = Out of Specification,
Maintenance Required, or Function Check.
Configuration and Use Manual 9
Quick start Configuration and Use Manual
July 2022 00809-0100-1600
Table 2-1: Status LED and device status (MMI mode) (continued)
Status LED condition Device status
Solid red One or more alerts are active with Alert Severity = Failure.
Flashing yellow (1 Hz) The Function Check in Progress alert is active.
Table 2-2: Network status LED and Ethernet network connection status
Network status LED condition Network status
Flashing green No connections made with primary protocol host.
Solid green Connection made with primary protocol host.
Flashing red Connection from primary protocol host has timed out.
Solid red Address Conflict Detection (ACD) algorithm has detected a duplicate IP
address (All 1600 transmitter Ethernet communications are stopped.)

2.3 Commissioning wizards

The transmitter menu includes a Guided Setup to help you move quickly through the most common configuration parameters. ProLink III also provides a commissioning wizard.
By default, when the transmitter starts up, the Guided Setup menu is offered. You can choose to use it or not. You can also choose whether or not Guided Setup is displayed automatically.
To enter Guided Setup upon transmitter startup, choose Yes at the prompt.
To enter Guided Setup after transmitter startup, choose Menu Startup Tasks.
To control the automatic display of Guided Setup, choose Menu Configuration Guided Setup.
For information on the ProLink III commissioning wizard, see the Micro Motion ProLink III with ProcessViz Software User Manual.
As the commissioning wizards are self guided, they are not documented in detail.

2.4 Make a startup connection to the transmitter

For all configuration tools except the display, you must have an active connection to the transmitter to configure the transmitter.
Procedure
Identify the connection type to use, and follow the instructions for that connection type in the appropriate appendix.
Communications tool
ProLink III Service port Using ProLink III with the transmitter
Web browser Ethernet Using a web browser to configure the
10 Micro Motion 1600 with Ethernet Transmitters
Connection type to use Instructions
transmitter
Configuration and Use Manual Quick start
00809-0100-1600 July 2022

2.5 Set the transmitter clock

Display Menu Configuration Time/Date/Tag
ProLink III Device Tools Configuration Transmitter Clock
Web browser Configuration Time/Date/Tag
The transmitter clock provides timestamp data for alerts, service logs, history logs, and all other timers and dates in the system. You can set the clock for your local time or for any standard time you want to use.
Tip
You may find it convenient to set all of your transmitter clocks to the same time, even if the transmitters are in different time zones.
Procedure
1. Select the time zone that you want to use.
2. If you need a custom time zone, select Special Time Zone and enter your time zone as a difference
from UTC (Coordinated Universal Time).
3. Set the time appropriately for the selected time zone.
Tip
The transmitter does not adjust for Daylight Savings Time. If you observe Daylight Savings Time, you must reset the transmitter clock manually.
4. Set the month, day, and year.
The transmitter tracks the year and automatically adds a day for leap years.

2.6 View the licensed features (optional)

Display
ProLink III Device Tools Device Information Licensed Features
Web browser Configuration Device Information Licensed Features
The transmitter license controls the features (applications) that are enabled on the transmitter. You can view the licensed features to ensure that the transmitter was ordered with the required features.
Licensed features are purchased and available for permanent use. The options model code represents the licensed features.
A trial license allows you to explore features before purchasing. The trial license enables the specified features for a limited number of days. This number is displayed for reference. At the end of this period, the feature will no longer be available.
Menu About Licenses Licensed Features
To purchase additional features or request a trial license, either write down or record the Unique ID Number and current license key from your transmitter and then contact customer service. To enable the additional features or trial license, you will need to install the new license on the transmitter.
Configuration and Use Manual 11
Quick start Configuration and Use Manual
July 2022 00809-0100-1600

2.7 Set informational parameters

Display Menu Configuration Device Information
ProLink III Device Tools Configuration Informational Parameters
Web browser Configuration Time/Date/Tag
You can set several parameters that identify or describe the transmitter and sensor. These parameters are not used in processing and are not required.
Procedure
1. Set informational parameters for the transmitter.
a) Set Transmitter Serial Number to the serial number of your transmitter.
The transmitter serial number is provided on the metal tag that is attached to the transmitter housing.
b) Set Descriptor to any desired description of this transmitter or measurement point.
c) Set Message to any desired message.
d) Verify that Model Code (Base) is set to the base model code of the transmitter.
The base model code completely describes your transmitter, except for the features that can be licensed independently. The base model code is set at the factory.
e) Set Model Code (Options) to the options model code of the transmitter.
The options model code describes the independent features that have been licensed for this transmitter. The original options model code is set at the factory. If you license additional options for this transmitter, Emerson will supply an updated options model code.
2. Set informational parameters for the sensor.
a) Set Sensor Serial Number to the serial number of the sensor connected to this transmitter.
The sensor serial number is provided on the metal tag that is attached to the sensor case.
b) Set Sensor Material to the material used for the sensor.
c) Set Sensor Liner to the material used for the sensor liner, if any.
d) Set Flange Type to the type of flange that was used to install the sensor.
Sensor Type is set or derived during characterization.

2.8 Characterize the meter (if required)

Display
ProLink III Device Tools Calibration Data
Web browser Configuration Sensor Parameters
12 Micro Motion 1600 with Ethernet Transmitters
Menu Configuration Sensor Parameters
Configuration and Use Manual Quick start
00809-0100-1600 July 2022
Characterizing the meter adjusts your transmitter to match the unique traits of the sensor it is paired with. The characterization parameters (also called calibration parameters) describe the sensor’s sensitivity to flow, density, and temperature. Depending on your sensor type, different parameters are required.
Values for your sensor are provided on the sensor tag or the calibration certificate.
If your transmitter was ordered with a sensor, it was characterized at the factory. However, you should still
verify the characterization parameters.
Perform a characterization whenever you replace a core processor.
Note
If the transmitter and sensor are purchased together, you do not need to characterize the meter because this step was performed at the factory prior to shipping.
Note
The 1600 derives Sensor Type from the user-specified values for FCF and K1.
Procedure
1. Set the flow calibration factor: FCF (also called Flow Cal or Flow Calibration Factor). Be sure to include
both decimal points and all zeros.
2. Set the density characterization parameters: D1, D2, TC, K1, K2, and FD. (TC is sometimes shown as
DT.)
3. Apply the changes as required by the tool you are using.
The transmitter identifies your sensor type, and characterization parameters are adjusted as required:
If Sensor Type changed from Curved Tube to Straight Tube, five characterization parameters are
added to the list.
If Sensor Type changed from Straight Tube to Curved Tube, five characterization parameters are
removed from the list.
If Sensor Type did not change, the list of characterization parameters does not change.
4. T-Series sensors only: Set the additional characterization parameters listed below.
Characterization parameter type
Flow FTG, FFQ
Density DTG, DFQ1, DFQ2
Parameters
Configuration and Use Manual 13
Quick start Configuration and Use Manual
July 2022 00809-0100-1600

2.8.1 Sample sensor tags

Figure 2-1: Tag on newer curved-tube sensors (all sensors except T-Series)

2.8.2 Flow calibration parameters (FCF, FT)

Two separate values are used to describe flow calibration: a 6-character FCF value and a 4-character FT value. They are provided on the sensor tag.
Both values contain decimal points. During characterization, these are entered as a single 10-character string. The 10-character string is called either Flowcal or FCF.
If your sensor tag shows the FCF and the FT values separately and you need to enter a single value, concatenate the two values to form the single parameter value, retaining both decimal points.
Concatenating FCF and FT
FCF = x.xxxx FT = y.yy Flow calibration parameter: x.xxxxy.yy

2.8.3 Density calibration parameters (D1, D2, K1, K2, FD, DT, TC)

Density calibration parameters are typically on the sensor tag and the calibration certificate. If your sensor tag does not show a D1 or D2 value:
For D1, enter the Dens A or D1 value from the calibration certificate. This value is the line-condition
density of the low-density calibration fluid. Micro Motion uses air. If you cannot find a Dens A or D1 value, enter 0.001 g/cm3.
For D2, enter the Dens B or D2 value from the calibration certificate. This value is the line-condition density
of the high-density calibration fluid. Micro Motion uses water. If you cannot find a Dens B or D2 value, enter 0.998 g/cm3 .
If your sensor tag does not show a K1 or K2 value:
For K1, enter the first five digits of the density calibration factor. In this sample tag, this value is shown as
12500.
For K2, enter the second five digits of the density calibration factor. In this sample tag, this value is shown
as 14286.
14 Micro Motion 1600 with Ethernet Transmitters
Configuration and Use Manual Quick start
00809-0100-1600 July 2022
Figure 2-2: K1, K2, and TC values in the density calibration factor
If your sensor does not show an FD value, contact customer service.
If your sensor tag does not show a DT or TC value, enter the last four characters of the density calibration factor. In the sample tag shown above, the value is shown as 4.44.
Do not confuse the Meter Factor line on the pictured sensor tag with any meter factor settings discussed in this manual.

2.9 Verify mass flow measurement

Check to see that the mass flow rate reported by the transmitter is accurate. You can use any available method.
Procedure
Read the value for Mass Flow Rate on the transmitter display.
Connect to the transmitter with ProLink III and read the value for Mass Flow Rate in the Process Variables
panel.
Postrequisites
If the reported mass flow rate is not accurate:
Check the characterization parameters.
Review the troubleshooting suggestions for flow measurement issues.
For information about modifying these values, refer to Configure mass flow measurement.

2.10 Verify the zero

Display
ProLink III Device Tools Calibration Smart Zero Verification and Calibration Verify Zero
Web browser Service Tools Verification and Calibration Meter Zero Zero Verification
Configuration and Use Manual 15
Menu Service Tools Verification & Calibration Meter Zero Zero Verification
Quick start Configuration and Use Manual
July 2022 00809-0100-1600
Verifying the zero helps you determine if the stored zero value is appropriate to your installation, or if a field zero can improve measurement accuracy.
Important
In most cases, the factory zero is more accurate than the field zero. Do not zero the meter unless one of the following is true:
The zero is required by site procedures.
The stored zero value fails the zero verification procedure.
Do not verify the zero or zero the meter if a high-severity alert is active. Correct the problem, then verify the zero or zero the meter. You may verify the zero or zero the meter if a low-severity alert is active.
Procedure
1. Prepare the meter:
a) Allow the meter to warm up for at least 20 minutes after applying power.
b) Run the process fluid through the sensor until the sensor temperature reaches the normal
process operating temperature.
c) Stop flow through the sensor by shutting the downstream valve, and then the upstream valve if
available.
d) Verify that the sensor is blocked in, that flow has stopped, and that the sensor is completely full
of process fluid.
2. Start the zero verification procedure, and wait until it completes.
3. If the zero verification procedure fails:
a) Confirm that the sensor is completely blocked in, that flow has stopped, and that the sensor is
completely full of process fluid.
b) Verify that the process fluid is not flashing or condensing, and that it does not contain particles
that can settle out.
c) Repeat the zero verification procedure.
d) If it fails again, zero the meter.
Postrequisites
Restore normal flow through the sensor by opening the valves.
Related information
Zero the meter
16 Micro Motion 1600 with Ethernet Transmitters
Configuration and Use Manual Introduction to configuration and commissioning
00809-0100-1600 July 2022

3 Introduction to configuration and commissioning

3.1 Security and write protection

The transmitter has several features that can help to protect it against intentional or unintentional access and configuration changes.
When locked, the mechanical lock switch on the front of the upper puck prevents any configuration
changes to the transmitter from any local or remote configuration tool.
When enabled, the software setting Write Protection prevents any configuration changes. The setting
can only be enabled if the transmitter does not have a display.
If the Universal Service Port (USP) is disabled, the port cannot be used by any service tool to communicate
with or make changes to the transmitter.
When enabled, Security prevents any configuration changes being made from the display unless the
appropriate password is entered.

3.1.1 Web server security

You can configure this transmitter using web services. There are multiple levels of security built into the transmitter that you can configure according to your needs and security standards, including:
Disabling the web servers
Allowing downloads of configuration and historian files, but disallowing file uploads to the transmitter
through the Ethernet interface
Configuring Transport Layer Security (TLS) on the web server to encrypt all data transmitted between the
web server and the transmitter
Requiring user authentication and strong passwords to access the web server and the transmitter
Notifying users through alerts if the default password has not been changed
Disallowing configuration changes from all interfaces including the Ethernet port using transmitter
security switches, such as the lock switch or write protection
This transmitter:
Was designed to be implemented in an industrial automation control system (Level 1 and Level 2 of the
Purdue Reference Architecture Model), with defense in depth security controls.
Is not intended to be directly connected to an enterprise or to an internet-facing network without a
compensating control in place.

3.1.2 Enable or disable the service port

Display
ProLink III Not available
Web browser Not available
Configuration and Use Manual 17
Menu Configuration Security Service Port
Introduction to configuration and commissioning Configuration and Use Manual
July 2022 00809-0100-1600
The service port is enabled by default. You can use the service port for connecting to ProLink III and for transferring files. If you want to completely prevent it from being used, you can disable it.
Note
Enabling or disabling the service port will not take effect until power has been cycled to the transmitter.
WARNING
Do not use the service port if the transmitter is in a hazardous area because using the service port means that you must open the transmitter wiring compartment. Opening the wiring compartment in a hazardous area while the transmitter is powered up can cause an explosion resulting in injury or death.

3.1.3 Enable or disable write-protection

Upper puck Use the mechanical switch on the upper puck.
ProLink III Not available
Web browser Not available
When enabled, Write-Protection prevents changes to the transmitter configuration. You can perform all other functions, and you can view the transmitter configuration parameters.
Note
Write protection is available only by removing the display in order to access the upper puck component and using the lock switch to set the switch ON.
Figure 3-1: Removing the transmitter housing cover
A. Display Component
B. Upper Puck Component
18 Micro Motion 1600 with Ethernet Transmitters
Configuration and Use Manual Introduction to configuration and commissioning
00809-0100-1600 July 2022
Figure 3-2: Setting Switch 1 ON (to the left) to Set Write-Protection
A. Switch 1
Write-protecting the transmitter primarily prevents accidental changes to configuration, not intentional changes. Any user who can make changes to the configuration can disable write protection.

3.1.4 Configure security for the display

Display
ProLink III Device Tools Configuration Transmitter Display Display Security
Web browser Not available
When using the display, you can require users to enter a password to do any of the following tasks:
Enter the main menu
Change a parameter
Access alert data through the display
Start, stop, or reset totalizers or inventories via the context menu
The display password can be the same or different from the totalizer/inventory context menu control password. If different, the display password is used to reset, start, and stop totalizers or inventories using
Menu Operations Totalizers.
Menu Configuration Security Display Security
Configuration and Use Manual 19
Introduction to configuration and commissioning Configuration and Use Manual
July 2022 00809-0100-1600
Procedure
1. Configure Password Required as desired.
Option Description
At Write When an user chooses an action that leads to a configuration change, they are
prompted to enter the display password.
Enter Menu When the menu is selected from the process variable screen, the display password
will be immediately required if Password Required is set.
Never (default) When a user chooses an action that leads to a configuration change, they are
prompted to activate ⇦⇧⇩⇨. This is designed to protect against accidental changes to configuration. It is not a security measure.
2. If the At Write or Enter Menu option was selected, enable or disable alert security as desired.
Option Description
Enabled If an alert is active, the alert symbol is shown in the lower right corner of the display but
the alert banner is not displayed. If the operator attempts to enter the alert menu, they are prompted to enter the display password.
Disabled If an alert is active, the alert symbol is shown in the lower right corner of the display and
the alert banner is displayed automatically. No password or confirmation is required to enter the alert menu.
Restriction
You cannot set Password Required to Never and enable alert security.
If you did not enable Password Required, alert security is disabled and cannot be enabled.
Alert security is disabled automatically if you set Password Required to Never after:Password Required is initially set to either At Write or Enter Menu
Alert security is enabled
3. If Password Required has been set to At Write or Enter Menu, you will be prompted to enter the desired password.
Default: AAAA
Range: Any four alphanumeric characters
Password Required must be set to At Write or Enter Menu to enable the totalizer/inventory control
context menu password option.
Important
If you enable Password Required but you do not change the display password, the transmitter will post a configuration alert.
20 Micro Motion 1600 with Ethernet Transmitters
Configuration and Use Manual Introduction to configuration and commissioning
00809-0100-1600 July 2022
4. Configure Main Menu Available as desired.
Option Description
Enabled The local display Menu option from the process variable screen will be accessible.
Disabled The local display Menu option from the process variable screen will not be accessible.
Important
Once Main Menu Available has been disabled, you cannot enable it from the local display. Use another configuration tool, such as ProLink III, to re-enable main menu access from the local display.

3.2 Work with configuration files

You can save the current transmitter configuration in two forms: a backup file and a replication file.
Tip
You can use a saved configuration file to change the nature of the transmitter quickly. This might be convenient if the transmitter is used for different applications or different process fluids.
Backup files
Replication files
Contain all parameters. They are used to restore the current device if required. The .spare extension is used to identify backup files.
Contain all parameters except the device-specific parameters, e.g., calibration factors or meter factors. They are used to replicate the transmitter configuration to other devices. The .xfer extension is used to identify replication files.

3.2.1 Save a configuration file using the display

Procedure
To save the current configuration to the transmitter's internal memory:
a) Choose Menu Configuration Save/Restore Config Save Config to Memory.
b) When prompted to load 1600 device configuration data from a file, click the on my 1600 device
internal memory radio button.
c) Enter the name for this configuration file.
The configuration file is saved to internal memory as yourname.spare.

3.2.2 Save a configuration file using ProLink III

Note
When you use ProLink III format for configuration files, you can specify configuration parameters individually or by groups. Therefore, you can use this format for both backup and replication.
Configuration and Use Manual 21
Introduction to configuration and commissioning Configuration and Use Manual
July 2022 00809-0100-1600
Prerequisites
If you are planning to use the USP (Universal Service Port)), the port must be enabled. It is enabled by default. However, if you need to enable or disable it using the display, choose Menu Configuration Security and set Service Port to On.
Procedure
To save the current configuration to your PC, in 1600 format:
a) Choose Device Tools Configuration Transfer Save Configuration.
b) Select On my computer in 1600 device file format and click Next.
c) Select Save.
d) Browse to the desired location, then enter the name for this configuration file.
e) Set the file type.
To save a backup file, set the file type to Backup.To save a replication file, set the file type to Transfer.
f) Select Save.
The configuration file is saved to the specified location as yourname.spare or yourname.xfer.
To save the current configuration to your PC, in ProLink III format:
a) Choose Device Tools Configuration Transfer Save Configuration.
b) Select On my computer in ProLink III file format and click Next.
c) Select Save.
d) Select the configuration parameters to be included in this file.
To save a backup file, select all parameters.To save a replication file, select all parameters except device-specific parameters.
e) Select Save.
f) Browse to the desired location, then enter the name for this configuration file.
g) Set the file type to ProLink configuration file.
h) Select Start Save.
The configuration file is saved to the specified location as yourname.pcfg.

3.2.3 Load a configuration file using the display

Prerequisites
You must have a backup file or a replication file available for use in internal memory.
22 Micro Motion 1600 with Ethernet Transmitters
Configuration and Use Manual Introduction to configuration and commissioning
00809-0100-1600 July 2022
Procedure
To load a configuration file to the transmitter's internal memory:
a) Make sure the configuration file is in the Config folder.
b) Upload the configuration file through the USP file by specifying Device Tools Configuration
Transfer Load Configuration.
c) When prompted to load 1600 device configuration data from a file, click the on my 1600 device
internal memory radio button.
d) Choose Backup and click Restore.
The configuration file is loaded to internal memory as yourname.spare.

3.2.4 Load a configuration file using ProLink III

You can load a configuration file to a transmitter's internal memory, as well as loading a backup file or a replication file. Two PC file formats are supported: the 1600 format and the ProLink III format.
Note
When you use ProLink III format for configuration files, you can specify configuration parameters individually or by groups. Therefore, you can use this format for both backup and replication.
Procedure
To load a backup file or replication file in 1600 format from the PC:
a) Choose Device Tools Configuration Transfer Load Configuration.
b) Select On my computer in 1600 device file format and select Next.
c) Select Restore.
d) Set the file type.
To load a backup file, set the file type to Backup.To load a replication file, set the file type to Transfer.
e) Navigate to the file you want to load, and select it.
The parameters are written to the internal memory, and the new settings become effectively immediately.
To load a file in ProLink III format from the PC:
a) Choose Device Tools Configuration Transfer Load Configuration.
b) Select On my computer in ProLink III file format and select Next.
c) Select the parameters that you want to load.
d) Select Load.
e) Set the file type to Configuration file.
f) Navigate to the file you want to load, and select it.
g) Select Start Load.
Configuration and Use Manual 23
Introduction to configuration and commissioning Configuration and Use Manual
July 2022 00809-0100-1600
The parameters are written to the internal memory, and the new settings become effectively immediately.

3.2.5 Replicate a transmitter configuration

Replicating a transmitter configuration is a fast method to set up similar or identical measurement points.
Procedure
1. Configure a transmitter and verify its operation and performance.
2. Use any available method to save a replication file from that transmitter.
3. Use any available method to load the replication file to another transmitter.
4. At the replicated transmitter, set device-specific parameters and perform device-specific procedures: a) Set the clock.
b) Set the tag, long tag, IP address, and related parameters.
c) Characterize the transmitter.
d) Perform zero validation and take any recommended actions.
e) Perform loop tests and take any recommended actions, including mA Output trim.
f) Use sensor simulation to verify transmitter response.
5. At the replicated transmitter, make any other configuration changes.
6. Follow your standard procedures to ensure that the replicated transmitter is performing as desired.
24 Micro Motion 1600 with Ethernet Transmitters
Configuration and Use Manual Configure process measurement
00809-0100-1600 July 2022

4 Configure process measurement

4.1 Configure Sensor Flow Direction Arrow

Display Menu Configuration Process Measurement Flow Variables Flow Direction
ProLink III Device Tools Configuration Process Measurement Flow Sensor Direction
Web browser Configuration Process Measurement Flow Variables Sensor Direction
Sensor Flow Direction Arrow is used to accommodate installations in which the Flow arrow on the sensor does not match the majority of the process flow. This typically happens when the sensor is either accidentally installed backwards or conditions require that it be installed backwards.
Sensor Flow Direction Arrow interacts with mA Output Direction, Frequency Output Direction, and Totalizer Direction to control how flow is reported by the outputs and accumulated by the totalizers and
inventories. The Sensor Flow Direction Arrow also affects how flow is reported on the transmitter display and via digital
communications. This includes ProLink III, the web browser, and all other user interfaces.
Figure 4-1: Flow arrow on sensor
A. Flow arrow
B. Actual flow direction
Procedure
Set Sensor Flow Direction Arrow as appropriate.
Option
With Arrow The majority of flow through the sensor matches the Flow arrow on the sensor. Actual
Description
forward flow is processed as forward flow.
Against Arrow The majority of flow through the sensor is opposite to the Flow arrow on the sensor. Actual
forward flow is processed as reverse flow.
Configuration and Use Manual 25
Configure process measurement Configuration and Use Manual
July 2022 00809-0100-1600
Tip
Micro Motion sensors are bidirectional. Measurement accuracy is not affected by actual flow direction or the setting of Sensor Flow Direction Arrow. Sensor Flow Direction Arrow controls only whether actual flow is processed as forward flow or reverse flow.
Related information
Configure mA Output Direction Configure Frequency Output Direction Configure Discrete Output Source Configure totalizers and inventories Effect of Sensor Flow Direction Arrow on digital communications

4.2 Configure mass flow measurement

The mass flow measurement parameters control how mass flow is measured and reported. The mass total and mass inventory are derived from the mass flow data.

4.2.1 Configure Mass Flow Measurement Unit

Display Menu Configuration Process Measurement Flow Variables Mass Flow Settings Units
ProLink III Device Tools Configuration Process Measurement Flow Mass Flow Rate Unit
Web browser Configuration Process Measurement Flow Variables Mass Flow Rate Unit
Mass Flow Measurement Unit specifies the unit of measure that will be used for the mass flow rate. The default unit used for mass total and mass inventory is derived from this unit.
Procedure
Set Mass Flow Measurement Unit to the unit you want to use.
Default: g/sec (grams per second)
Tip
If the measurement unit you want to use is not available, you can define a special measurement unit.
Options for Mass Flow Measurement Unit
The transmitter provides a standard set of measurement units for Mass Flow Measurement Unit, plus one user-defined special measurement unit. Different communications tools may use different labels for the units.
Label
Unit description
Grams per second gram/s g/sec g/sec
Grams per minute gram/min g/min g/min
Grams per hour gram/h g/hr g/hr
Kilograms per second kg/s kg/sec kg/sec
26 Micro Motion 1600 with Ethernet Transmitters
Display ProLink III Web browser
Configuration and Use Manual Configure process measurement
00809-0100-1600 July 2022
Label
Unit description
Kilograms per minute kg/min kg/min kg/min
Kilograms per hour kg/h kg/hr kg/hr
Kilograms per day kg/d kg/day kg/day
Metric tons per minute MetTon/min mTon/min mTon/min
Metric tons per hour MetTon/h mTon/hr mTon/hr
Metric tons per day MetTon/d mTon/day mTon/day
Pounds per second lb/s lbs/sec lbs/sec
Pounds per minute lb/min lbs/min lbs/min
Pounds per hour lb/h lbs/hr lbs/hr
Pounds per day lb/d lbs/day lbs/day
Short tons (2000 pounds) per minute STon/min sTon/min sTon/min
Short tons (2000 pounds) per hour STon/h sTon/hr sTon/hr
Short tons (2000 pounds) per day STon/d sTon/day sTon/day
Long tons (2240 pounds) per hour LTon/h lTon/hr lTon/hr
Long tons (2240 pounds) per day LTon/d lTon/day lTon/day
Special unit SPECIAL Special Special
Display ProLink III Web browser
Define a special measurement unit for mass flow
Display
ProLink III Device Tools Configuration Process Measurement Flow Mass Flow Rate Unit Special
Web browser Configuration Process Measurement Flow Variables Mass Flow Rate Unit Special
Procedure
1. Specify Base Mass Unit.
Base Mass Unit is the existing mass unit that the special unit will be based on.
2. Specify Base Time Unit.
Base Time Unit is the existing time unit that the special unit will be based on.
3. Calculate Mass Flow Conversion Factor as follows: a) x base units = y special units
b) Mass Flow Conversion Factor = x ÷ y
4. Enter Mass Flow Conversion Factor.
The original mass flow rate value is divided by this value.
Menu Configuration Process Measurement Flow Variables Mass Flow Settings Units SPECIAL
Configuration and Use Manual 27
Configure process measurement Configuration and Use Manual
July 2022 00809-0100-1600
5. Set Mass Flow Label to the name you want to use for the mass flow unit.
6. Set Mass Total Label to the name you want to use for the mass total and mass inventory unit.
The special measurement unit is stored in the transmitter. You can configure the transmitter to use the special measurement unit at any time.
Example: Defining a special measurement unit for mass flow
If you want to measure mass flow in ounces per second (oz/sec):
1. Set Base Mass Unit to Pounds (lb).
2. Set Base Time Unit to Seconds (sec).
3. Calculate Mass Flow Conversion Factor: a. 1 lb/sec = 16 oz/sec
b. Mass Flow Conversion Factor = 1 ÷ 16 = 0.0625
4. Set Mass Flow Conversion Factor to 0.0625.
5. Set Mass Flow Label to oz/sec.
6. Set Mass Total Label to oz.

4.2.2 Configure Flow Damping

Display
ProLink III Device Tools Configuration Process Measurement Flow Flow Rate Damping
Web browser Configuration Process Measurement Flow Variables Flow Rate Damping
Flow Damping controls the amount of damping that will be applied to the measured mass flow rate. It affects flow rate process variables that are based on the measured mass flow rate. This includes volume flow rate and gas standard volume flow rate.
Flow Damping also affects specialized flow rate variables such as temperature-corrected volume flow rate (API Referral) and net mass flow rate (concentration measurement).
Damping is used to smooth out small, rapid fluctuations in process measurement. The damping value specifies the time period, in seconds, over which the transmitter will spread changes in the process variable. At the end of the interval, the internal value of the process variable (the damped value) will reflect 63% of the change in the actual measured value.
Procedure
Set Flow Damping to the value you want to use.
Default: 0.64 seconds
Menu Configuration Process Measurement Flow Variables Flow Damping
Range: 0 seconds to 60 seconds
Note
If a number greater than 60 is entered, it is automatically changed to 60.
28 Micro Motion 1600 with Ethernet Transmitters
Configuration and Use Manual Configure process measurement
00809-0100-1600 July 2022
Tip
A high damping value makes the process variable appear smoother because the reported value changes
slowly.
A low damping value makes the process variable appear more erratic because the reported value changes
more quickly.
The combination of a high damping value and rapid, large changes in flow rate can result in increased
measurement error.
Whenever the damping value is non-zero, the reported measurement will lag the actual measurement
because the reported value is being averaged over time.
In general, lower damping values are preferable because there is less chance of data loss, and less lag time
between the actual measurement and the reported value.
The transmitter automatically rounds off any entered damping value to the nearest valid value. Therefore,
the recommended damping value for gas applications should be 3.2 seconds. If you enter 2.56, the transmitter will round it off to 3.2.
For filling applications, Emerson recommends using the default value of 0.04 seconds.
Effect of flow damping on volume measurement
Flow damping affects volume measurement for liquid volume data. Flow damping also affects volume measurement for gas standard volume data. The transmitter calculates volume data from the damped mass flow data.
Interaction between Flow Damping and mA Output Damping
In some circumstances, both Flow Damping and mA Output Damping are applied to the reported mass flow value.
Flow Damping controls the rate of change in flow process variables. mA Output Damping controls the rate of change reported through mA Output. If mA Output Process Variable is set to Mass Flow Rate, and both Flow Damping and mA Output Damping are set to non-zero values, flow damping is applied first, and the added damping calculation is applied to the result of the first calculation.

4.2.3 Configure Mass Flow Cutoff

Display
ProLink III Device Tools Configuration Process Measurement Flow Mass Flow Cutoff
Web browser Configuration Process Measurement Flow Variables Mass Flow Cutoff
Mass Flow Cutoff specifies the lowest mass flow rate that will be reported as measured. All mass flow rates below this cutoff will be reported as 0.
Menu Configuration Process Measurement Flow Variables Mass Flow Settings Low Flow Cutoff
Procedure
Set Mass Flow Cutoff to the value you want to use.
Default: A sensor-specific value set at the factory. If your transmitter was ordered without a sensor, the
default may be 0.0.
Configuration and Use Manual 29
Configure process measurement Configuration and Use Manual
July 2022 00809-0100-1600
Recommendation: 0.5% of maximum flow rate of the attached sensor. See the sensor specifications.
Important
Do not use your meter for measurement with Mass Flow Cutoff set to 0.0 g/sec. Ensure that Mass Flow Cutoff is set to the value that is appropriate for your sensor.
Effect of Mass Flow Cutoff on volume measurement
Mass Flow Cutoff does not affect volume measurement. Volume data is calculated from the actual mass data rather than the reported value.
Volume flow has a separate Volume Flow Cutoff that is not affected by the Mass Flow Cutoff value.
Interaction between Mass Flow Cutoff and mA Output Cutoff
Mass Flow Cutoff defines the lowest mass flow value that the transmitter will report as measured. mA Output Cutoff defines the lowest flow rate that will be reported through mA Output. If mA Output Process Variable is set to Mass Flow Rate, the mass flow rate reported through mA Output is controlled by the higher
of the two cutoff values. Mass Flow Cutoff affects all reported values and values used in other transmitter behavior (e.g., events
defined on mass flow). mA Output Cutoff affects only mass flow values reported through mA Output.
Example: Cutoff interaction with mA Output Cutoff lower than Mass Flow Cutoff
Configuration:
mA Output Process Variable: Mass Flow Rate
Frequency Output Process Variable: Mass Flow Rate
mA Output Cutoff: 10 g/sec
Mass Flow Cutoff: 15 g/sec
Result: If the mass flow rate drops below 15 g/sec, mass flow will be reported as 0, and 0 will be used in all internal processing.
Example: Cutoff interaction with mA Output Cutoff higher than Mass Flow Cutoff
Configuration:
mA Output Process Variable: Mass Flow Rate
Frequency Output Process Variable: Mass Flow Rate
mA Output Cutoff: 15 g/sec
Mass Flow Cutoff: 10 g/sec
Result:
If the mass flow rate drops below 15 g/sec but not below 10 g/sec:The mA Output will report zero flow.
The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all
internal processing.
30 Micro Motion 1600 with Ethernet Transmitters
Loading...
+ 218 hidden pages