Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are
available: the EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings
and Instructions. In addition the IECEx Installation Instructions for installations outside of the European Union and the CSA
Installation Instructions for installations in North America are available on the internet at www.emerson.com or through your local
Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com. For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion
Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States800-522-6277U.K. and Ireland0870 240 1978Australia800 158 727
Chapter 9Components of the transmitter display.................................................................... 39
9.1 Access and use the display menus..............................................................................................40
Chapter 10Available service port connection............................................................................. 45
Appendix AWire the 1600 to the 3100 relays..............................................................................47
Installation Manual3
ContentsInstallation Manual
March 202200825-0100-1600
4 Micro Motion 1600 Ethernet Transmitters
Installation ManualBefore you begin
00825-0100-1600March 2022
1Before you begin
1.1About this document
This manual provides information on planning, mounting, wiring, and initial setup of the
1600 Ethernet transmitter. For information on full configuration, maintenance,
troubleshooting, or service of the transmitter, see the configuration and use manual.
The information in this document assumes that users understand basic transmitter and
sensor installation, configuration, and maintenance concepts and procedures.
1.2Hazard messages
This document uses the following criteria for hazard messages based on ANSI standards
Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a
situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration
of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access to protect users' assets. This is true for all
systems used within the facility.
Installation Manual5
Before you beginInstallation Manual
March 202200825-0100-1600
1.3Related documentation
You can find all product documentation on the product documentation DVD shipped with
the product or at www.emerson.com.
See any of the following documents for more information:
• Micro Motion 1600 Product Data Sheet
• Micro Motion 1600 with Ethernet Transmitters: Configuration and Use Manual
□ If possible, install the transmitter in a location that will prevent direct exposure to
sunlight. The environmental limits for the transmitter may be further restricted by
hazardous area approvals.
□ If you plan to mount the transmitter in a hazardous area:
WARNING
— Verify that the transmitter has the appropriate hazardous area approval. Each
transmitter has a hazardous area approval tag attached to the transmitter
housing.
— Ensure that any cable used between the transmitter and the sensor meets the
hazardous area requirements.
— For ATEX/IECEx installations, strictly adhere to the safety instructions
documented in the ATEX/IECEx approvals documentation available on the
product documentation DVD shipped with the product or at www.emerson.com.
□ Verify that you have the appropriate cable and required cable installation parts for your
installation. For wiring between the transmitter and sensor, verify the maximum cable
length does not exceed 60 ft (18 m).
□ Ensure that you use the following cables for the different connections:
— A twisted-pair instrument cable for the Channel B I/O connection
— A suitable shielded or unshielded Cat5e or a higher-rated instrumentation cable for
the Ethernet connections to connect the meter
Note
If the transmitter is powered by the PoE connection, use shielded Cat5e cables to
meet the requirements of NAMUR NE-21.
Note
The instrumentation cable should have an overall screen to cover all cores. Where
permissible, connect the overall screen to earth at the host end (360° bonded).
(1)
□ You can mount the transmitter in any orientation as long as the conduit openings or
transmitter display do not point upward.
Installing the transmitter with the conduit openings or transmitter display facing
upward risks condensation moisture entering the transmitter housing, which could
damage the transmitter.
Following are examples of possible orientations for the transmitter.
Connections must meet the EC Directive for Electromagnetic Compatibility (EMC).
(1)
Installation Manual7
PlanningInstallation Manual
March 202200825-0100-1600
Preferred orientationAlternate orientations
□ Mount the meter in a location and orientation that satisfies the following conditions:
— Allows sufficient clearance to open the transmitter housing cover. Install with 8 in
(203 mm) to 10 in (254 mm) clearance at the wiring access points.
— Provides clear access for installing cabling to the transmitter.
— Provides clear access to all wiring terminals for troubleshooting.
2.2Additional considerations for retrofitting
existing installations
□ The transmitter installation may require 3 in (76 mm) to 6 in (152 mm) of additional
wiring for the input/output and power connections. This length would be in addition to
the currently installed wiring. Confirm you have the additional wiring necessary for the
new installation.
□ Before removing the existing transmitter, be sure to record the configuration data for
the currently installed transmitter. At initial startup of the newly installed transmitter,
you will be prompted to configure the meter via a guided setup.
Record the following information (if applicable):
Variable
Tag
Mass flow units
Volume flow units
Density units
Temperature units
Channel configuration
mA Output (if licensed)— Power (Internal or External):
Setting
— Source:
— Scaling (LRV, URV):
— Fault Action:
8 Micro Motion 1600 Ethernet Transmitters
Installation Manual
Planning
00825-0100-1600March 2022
VariableSetting
Frequency Output (if licensed) — Power (Internal or External):
— Source:
— Scaling (Frequency Factor or Flow Rate Factor):
— Fault Action:
— Fault Frequency:
Discrete Output (if licensed)— Power (Internal or External):
ProLink III and the Integrated Web server can always be
connected to Channel A
Modbus TCPFrequency Output
(1) ProLink III and the integrated web server can always be connected to Channel A.
(1)
4.2Wire the I/O channel
The Channel 1600 I/O can be configured as:
• mA Output
• Frequency Output
• Discrete Output
4.2.1
Access the wiring channels
Procedure
Remove the wiring access cover to reveal the I/O wiring terminal block connectors.
Channel B
mA Output
Discrete Output
Installation Manual17
A
D
C
B
A
E
D
C
B
Wiring the channelsInstallation Manual
March 202200825-0100-1600
4.2.2Wire the mA Output
Wire the mA Output for nonhazardous installations.
Prerequisites
WARNING
Meter installation and wiring should be performed only by suitably-trained personnel
using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-1: Internally-powered mA Output wiring
A. mA Output
B. Channel B
C. 820 Ω maximum loop resistance
Note
This resistor is normally built into the signal device (d). This resistor is not used for HART
communications.
D. Signal device
Figure 4-2: Externally-powered mA Output wiring
A. mA Output
B. Channel B
C. 5–30 VDC (maximum)
D. See Figure 4-3
E. Signal device
18 Micro Motion 1600 Ethernet Transmitters
0
100
200
300
400
500
600
700
800
900
1000
1100
07.515.022.530.0
B
A
A
D
C
B
Installation ManualWiring the channels
00825-0100-1600March 2022
Figure 4-3: Externally-powered mA Output: maximum loop resistance
A. Maximum resistance (Ω)
B. External supply voltage (V)
4.2.3
Wire the Frequency Output
Wire the Frequency Output in nonhazardous installations.
Prerequisites
WARNING
Meter installation and wiring should be performed only by suitably-trained personnel
using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Figure 4-4: Internally-powered FO wiring
Installation Manual19
A. Frequency Output
B. Channel B
C. See Figure 4-5
D. Counter
0
2
4
6
8
10
12
14
16
18
20
22
24
02505007501000
A
B
A
B
E
D
C
Wiring the channelsInstallation Manual
March 202200825-0100-1600
Figure 4-5: Internally-powered FO: output amplitude versus load resistance [24 VDC
(Nom) open circuit]
A. Output amplitude (V)
B. Load resistor (Ω)
Figure 4-6: Externally-powered FO wiring
4.2.4
Wire the Discrete Output
Wire the Discrete Output in nonhazardous installations.
20 Micro Motion 1600 Ethernet Transmitters
Prerequisites
Meter installation and wiring should be performed only by suitably-trained personnel
using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
A. Frequency Output
B. Channel B
C. 5–30 VDC (maximum)
D. 500 mA current (maximum)
E. Counter
WARNING
A
D
C
B
0
2
4
6
8
10
12
14
16
18
20
22
24
0750150022503000
A
B
Installation ManualWiring the channels
00825-0100-1600March 2022
Figure 4-7: Internally-powered DO wiring
A. Discrete Output
B. Channel B
C. See Figure 4-8
D. Counter
Figure 4-8: Internally-powered DO: output amplitude versus load resistance [24 VDC
(Nom) open circuit]
A. Output amplitude (V)
B. Load resistor (Ω)
Installation Manual21
A
B
E
D
C
Wiring the channelsInstallation Manual
March 202200825-0100-1600
Figure 4-9: Externally-powered DO wiring
A. Discrete Output
B. Channel B
C. 3–30 VDC (maximum)
D. 500 mA current (maximum)
E. Counter
4.2.5
Wire the I/O channel using an M12-terminated cable
(optional)
Use this procedure if you are using an M12-terminated cable to wire the I/O channel.
Prerequisites
Obtain an A-coded M12-terminated cable.
Procedure
1. Attach the M12-terminated cable to the configuration I/O connector on the 1600
transmitter.
2. Attach the other cable end using the pinouts described in the following table.
Figure 4-10: M12-terminated cables to the configuration I/O
Table 4-1: Cable end I/O pinouts
Pin
identification
Pin 1BrownPin3VDC +
22 Micro Motion 1600 Ethernet Transmitters
Wire colorOutputs on terminalSignal name
Installation ManualWiring the channels
00825-0100-1600March 2022
Table 4-1: Cable end I/O pinouts (continued)
Pin
identification
Pin 2WhitePin 1Channel B +
Pin 3BluePin 4VDC -
Pin 4BlackPin 2Channel B -
Wire colorOutputs on terminalSignal name
4.3Wire the Ethernet channels
To meet the EC Directive for Electromagnetic Compatibility (EMC), use a suitable shielded
or unshielded Cat5e, or higher-rated instrumentation cable to connect the meter. If your
1600 is powered by the PoE connection, in order to meet the requirements of NAMUR
NE-21, use shielded Cat5e cable.
The instrumentation cable should have an overall screen to cover all cores. Where
permissible, connect the overall screen to earth at the host end (360° bonded).
4.3.1
Wire an Ethernet network using the RJ45 ports
Prerequisites
When using a pre-terminated RJ45 cable, ensure there is no protective boot on the
connector, as a protective boot will not fit through the conduit. Alternatively, you can use
the RJ45 connector using a shielded-field termination connector.
4.3.1 Direct connection and star topology
Procedure
1. Feed the RJ45 cable through the conduit on the 1600 transmitter.
2. Connect the RJ45 cable into Channel A.
3. Anchor the cable to the module backplate using a cable tie.
Installation Manual23
Wiring the channelsInstallation Manual
March 202200825-0100-1600
4.3.2Wire the Ethernet I/O using M12-terminated cables
(optional)
Prerequisites
Obtain one D-coded M12-terminated Ethernet cable.
Procedure
1. Attach the M12-terminated Ethernet cable to the Ethernet I/O connector on the
1600 transmitter.
Figure 4-11: M12-terminated cables to the Ethernet I/O
2. Attach the other cable end using the pinouts described in the following table.
Table 4-2: M12 Ethernet I/O pinouts
Pin
identification
Pin 1Orange/WhitePin1TDP1/RDP2
Pin 2Green/WhitePin 3RDP1/TDP2
Pin 3OrangePin 2TDN1/RDN2
Pin 4GreenPin 6RDN1/RDN2
Wire colorOutputs on RJ45Signal name
24 Micro Motion 1600 Ethernet Transmitters
Installation ManualPower supply wiring
00825-0100-1600March 2022
5Power supply wiring
Depending on the power supply you plan to install, perform only one of the following
tasks:
• Wiring the VDC power supply
• Wiring the Power over Ethernet (PoE) power
5.1Wiring the VDC power supply
You can install a user-supplied switch in the power supply line.
Important
For compliance with the Low Voltage Directive 2014/35/EU (European installations), verify
that the transmitter is located in close proximity to a switch.
Figure 5-1: Location of power supply wiring terminals and equipment ground
Procedure
1. Remove the housing cover and the display, where applicable.
2. Connect the power supply wires.
For DC power, connect to terminals VDC (+) and VDC (-).
3. Tighten the two screws of the power connector to hold the wire.
Installation Manual25
Power supply wiringInstallation Manual
March 202200825-0100-1600
5.2Wiring the Power over Ethernet (PoE) power
The transmitter supports both IEEE 802.3af and IEEE 802.3 standards for PoE. Use this
procedure if you are using PoE from Power Sourcing Equipment (PSE) through the
Ethernet cable.
Prerequisites
The PSE connecting to the 1600 transmitter must be labeled as compliant with either the
IEEE 802.3af standard or the IEEE 802.3at standard. Check the specific manufacturer's
specifications of any device to make sure it references IEEE 802.3 or it may not work with
the 1600 transmitter.
NOTICE
If the installation requires NAMUR NE-21 certification on the customer side, you should
use shielded Cat5e or shielded high-rated cables.
Note
The1600 transmitter belongs to PD (Power Device) Classification 3 in the IEEE 802.3af and
802.3at standards. If the installation uses Cat5e or Cat6 Ethernet cables, the transmitter
supports both Mode A and Mode B power delivery. If the installation uses D code M12
cables, the transmitter only supports Mode A power delivery.
WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the
transmitter is powered up. Failure to follow these instructions can cause an explosion
resulting in injury or death.
NOTICE
If both PoE and an external supply power is wired to VDC+, VDC-, the transmitter
automatically switches the power to the DC power input.
Procedure
1. Remove the housing cover and the display, where applicable.
2. Connect the PoE on Channel A (refer to Figure 5-2) using either a Cat5e cable or a
higher rated cable such as Cat6.
26 Micro Motion 1600 Ethernet Transmitters
Installation ManualPower supply wiring
00825-0100-1600March 2022
Figure 5-2: Connecting the PoE on Channel A of the Transmitter
3. Because the Cat5e and higher-rated Ethernet cables are 360° bonded these cables
need to be grounded at the host end.
4. Replace the display where applicable, and the housing cover.
5.3Wire the power supply using an M12terminated cable (optional)
Use this procedure if you are using an M12-terminated cable to wire the power supply.
Prerequisites
Obtain an A-coded M12-terminated cable.
Procedure
1. Attach the M12-terminated cable to the power connector on the 1600 transmitter.
Installation Manual27
Power supply wiringInstallation Manual
March 202200825-0100-1600
Figure 5-3: M12-terminated cables to the configuration I/O
Table 5-1: Cable end I/O pinouts
Pin
identification
Pin 1BrownPin3VDC +
Pin 2WhitePin 1Channel B +
Pin 3BluePin 4VDC -
Pin 4BlackPin 2Channel B -
Wire colorOutputs on terminalSignal name
2. Attach the other cable end using the pinouts described in Table 5-2.
Note
For M12 power supply pinouts, only pins 1 and 3 are used.
Table 5-2: M12 power supply pinouts
Pin
identification
Pin 1BrownPin3VDC +
Pin 2WhitePin 1Channel B +
Pin 3BluePin 4VDC -
Pin 4BlackPin 2Channel B -
Wire colorOutputs on terminalSignal name
28 Micro Motion 1600 Ethernet Transmitters
Installation ManualSet up the printer
00825-0100-1600March 2022
6Set up the printer
Use this section to set up printing with a 1600 Ethernet transmitter and an
Epson TM-T88VI Ethernet printer. For information on configuring the printer, see Micro
Motion 1600 Transmitters with Configurable Inputs and Outputs: Configuration and Use
Manual.
There are two ways to set up printing:
• Use the printer's default IP address
• Change the printer's default IP address
6.1Set up the printer by changing the printer
default IP address
Use this procedure to set up printing with a 1600 Ethernet transmitter and an Epson TMT88VI printer by changing the printer's default IP address.
Procedure
1. Connect one end of an Ethernet cable and power supply to the printer.
2. Connect the other end of the Ethernet cable to the PC.
3. Power on the printer.
The printer IP address prints after a few minutes.
4. Temporarily change the Ethernet address for the PC so that the Ethernet is on the
same subnet as the printer:
Default IP address = 192.168.192.168
a) From Windows 10, right-click the Start button and select Network
Connections.
b) Right-click the Ethernet connection and select Properties.
Select Yes on any user account pop-up windows.
c) Select Internet Protocol Version 4(TCP/IPv4), then select properties.
d) Select Use the following IP address and configure the IP address and subnet
mask as follows:
• IP address: 192.168.192.x, where x is something other than 0, 1, or 168
• Subnet mask: 255.255.255.0
e) Select OK.
5. Change the printer firmware options.
a) Open your web browser and type http://192.168.192.168 (default
printer IP).
The browser displays, Your connection is not private. Ignore the
warning and proceed to the website.
Installation Manual29
Set up the printerInstallation Manual
March 202200825-0100-1600
b) Select ADVANCED.
c) Select Proceed to 192.168.192.168.
d) At the login screen, enter:
Default username: epson
Default password: epson
The EpsonNet Config utility screen displays.
e) Select TCP/IP under the configuration settings (not the basic settings), listed
on the left side of the screen.
f) Change the IP Address (i.e., 192.168.1.55), Subnet Mask, and Default
Gateway based on your network. Select an IP address that is unique to the
local network.
The printer must be on the same subnet as the 1600.
g) Required: Set Acquiring the IP Address to Manual.
h) Select Send to save your settings.
i) Select Reset, or power cycle the printer when prompted to apply the
changes.
6. Change the PC network settings back to the original settings.
Use the windows you used in Step 4.
7. Configure the 1600 Ethernet transmitter for the printer.
a) Remove the Ethernet cable from the PC and connect it to the 1600 Ethernet
transmitter.
b) If you have not already done so, configure the transmitter IP address, subnet
Menu → Configuration → Ethernet Settings →
Network Settings
For instructions on how to configure the transmitter and PC Ethernet
settings, see the Micro Motion 1600 with Ethernet Transmitters: Configurationand Use Manual.
c) Enter the printer IP address you configured in the previous step into the 1600
Ethernet transmitter.
Display
Menu → Configuration → Printer → Printer IP
address
ProLink IIIDevice Tools →Configuration →Printer and Tickets
Web browserConfiguration→Printer and Tickets
30 Micro Motion 1600 Ethernet Transmitters
Installation ManualSet up the printer
00825-0100-1600March 2022
8. Perform a test print to verify the settings are correct.
DisplayMenu→Operations→Printer→Print Ticket→Print Test
Page
ProLink IIIDevice Tools →Configuration →Printer and Tickets
Web browserConfiguration→Printer and Tickets
For instructions on how to configure print ticket options, see the Micro Motion 1600with Ethernet Transmitters: Configuration and Use Manual.
If needed, see Function Check Failed in the Status alerts, causes, and recommendations
section of the Micro Motion 1600 with Ethernet Transmitters: Configuration and Use Manual.
6.2Set up the printer using the printer default IP
address
Use this procedure to set up printing with a 1600 Ethernet transmitter and an Epson TMT88VI printer using the printer's default IP address.
Procedure
1. Connect one end of an Ethernet cable and power supply to the printer.
2. Connect the other end of the Ethernet cable to the PC.
3. Power on the printer.
It can take 1-2 minutes for the printer to finish configuring network settings. When
complete, the following ticket prints.
*********************************
IP Address : 192.168.192.168
SubnetMask : 255.255.255.0
Gateway : 0.0.0.0 DHCP : No server - > Static
*********************************
4. Turn off DHCP if it is enabled.
From the display
a. Go to Menu → Configuration →
Ethernet Settings → Network Settings
→Auto obtain IP()DHCP.
b. Select Disabled and Save.
c. Back out to the Ethernet Settings page
to apply the DHCP off setting.
From ProLink III
a. Go to Device Tools → Configuration →
Network Settings.
b. Uncheck Obtain an IP address
automatically (DHCP).
c. Select Apply.
Installation Manual31
Set up the printerInstallation Manual
March 202200825-0100-1600
5. Configure the IP address.
a) Navigate to one of the following screens:
From the displayFrom ProLink III
Go to Menu → Configuration →
Ethernet Settings → Network Settings
→IP address.
Go to Device Tools→Configuration→Network Settings.
b) Set the IP address to 192.168.192.x, where x is something other than 0, 1,
or 168.
6. Configure the subnet mask.
a) Navigate to one of the following screens:
From the displayFrom ProLink III
Go to Menu → Configuration →
Ethernet Settings → Network Settings
→Subnet Mask.
Go to Device Tools→Configuration→Network Settings.
b) Set the subnet mask to 255.255.255.0.
7. Configure the printer type.
a) Navigate to one of the following screens:
From the display
Go to Menu → Configuration → Printer
→ Printer Type.
From ProLink III
Go to Device Tools → Configuration →
Printer and Tickets.
b) Verify that the IP address is 192.168.192.168.
6.3Reset the interface settings
Use this procedure if you forgot the IP address of your printer and need to reset the default
(192.168.192.168).
Procedure
1. Turn off the printer and close the roll paper cover.
2. If the connector cover is attached, remove the cover.
3. Hold down the status sheet button on the back of the printer while turning on the
printer.
A message displays indicating that resetting is being performed.
4. Release the status sheet button to reset the printer settings to default.
Important
Do not turn off power until the process is complete.
32 Micro Motion 1600 Ethernet Transmitters
Installation ManualSet up the printer
00825-0100-1600March 2022
When complete, a Resetting to Factory Default Finished message
displays.
6.4Function Check Failed
A functional check alert is commonly triggered due to the following conditions:
• Incorrect network settings configuration
• Out of paper
• Paper tray is open
• Printer already has six open connections
• Another transmitter tries to start a print while another transmitter is printing
Configuration items and audit log tickets can take more than 15 minutes to print and
use up paper. If during this time another transmitter starts a print, the new print may
either be rejected, causing a functional check alert (printer offline), or the print will be
inserted in the middle of the configuration/audit log print.
The functional check alert is cleared after a successful print.
Installation Manual33
Set up the printerInstallation Manual
March 202200825-0100-1600
34 Micro Motion 1600 Ethernet Transmitters
Installation ManualPower up the transmitter
00825-0100-1600March 2022
7Power up the transmitter
The transmitter must be powered up for all configuration and commissioning tasks, or for
process measurement.
Procedure
1.WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while
the transmitter is powered up. Failure to follow these instructions can cause an
explosion resulting in injury or death.
Ensure that all transmitter and sensor covers and seals are closed.
2. Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. When using DC
power, a minimum of 1.5 amps of startup current is required. During this period,
Alert 009 is active. The diagnostic routines should complete in approximately
30 seconds. The status LED will turn green and begin to flash when the startup
diagnostics are complete. If the status LED exhibits different behavior, an alert is
active.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the
electronics can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the
initial startup, or if power has been off long enough to allow components to reach ambient
temperature, allow the electronics to warm up for approximately 10 minutes before
relying on process measurements. During this warm-up period, you may observe minor
measurement instability or inaccuracy.
Installation Manual35
Power up the transmitterInstallation Manual
March 202200825-0100-1600
36 Micro Motion 1600 Ethernet Transmitters
Installation ManualGuided setup
00825-0100-1600March 2022
8Guided setup
At initial startup of the transmitter, the guided configuration screen appears on the
transmitter display. This tool guides you through basic configuration of the transmitter.
The guided setup allows you to upload configuration files, set the transmitter display
options, configure channels, and review sensor calibration data.
Installation Manual37
Guided setupInstallation Manual
March 202200825-0100-1600
38 Micro Motion 1600 Ethernet Transmitters
Installation ManualComponents of the transmitter display
00825-0100-1600March 2022
9Components of the transmitter
display
The transmitter display includes two status LEDs, a multi-line LCD panel, and four
membrane arrow keys — left, up, down, and right — used to access the display menus and
navigate the display screens.
Figure 9-1: 1600 transmitter display
A. Status LED
B. LCD Display
Status LEDs
The status LEDs indicate the current state of the transmitter (STATUS) and the current
state of the Ethernet network (NET). From the display, the symbol “√” on the right side is
the transmitter status LED. The symbol “NET” on the left side is the network status LED.
The 1600 status LED supports NE107 mode. For configuration information, see the Micro
Motion 1600 with Ethernet Transmitters: Configuration and Use Manual.
Installation Manual39
Components of the transmitter displayInstallation Manual
March 202200825-0100-1600
Table 9-1: Status LED and device status (MMI mode)
Status LED conditionDevice status
Solid greenNo alerts are active.
Solid yellowOne or more alerts are active with Alert Severity = Out of
Specification, Maintenance Required, or Function Check.
Solid redOne or more alerts are active with Alert Severity = Failure.
Flashing yellow (1 Hz)The Function Check in Progress alert is active.
Table 9-2: Network status LED and Ethernet network connection status
Network status LED condition Network status
Flashing greenNo connections made with primary protocol host.
Solid greenConnection made with primary protocol host.
Flashing redConnection from primary protocol host has timed out.
Solid redAddress Conflict Detection (ACD) algorithm has detected a
duplicate IP address.
LCD panel
In normal operation, the LCD panel shows the current value of the display variables, and
their measurement units.
The LCD panel also provides access to the display menus and alert information. From the
display menus, you can:
• View the current configuration and make configuration changes.
• Perform procedures such as loop testing and zero verification.
• Run batches.
The alert information allows you to see which alerts are active, acknowledge the alerts
individually or as a group, and to see more detailed information for individual alerts.
9.1Access and use the display menus
The display menus allow you to perform most configuration, administration, and
maintenance tasks.
The four switches, ⇦⇧⇩⇨, are used to navigate the menus, make selections, and enter
data.
Procedure
1. Observe the action bar at the bottom of the LCD panel.
The action bar displays Menu⇨.
2. Press your thumb or finger over the ⇨ membrane switch to activate it.
The top-level menu is displayed.
40 Micro Motion 1600 Ethernet Transmitters
Installation ManualComponents of the transmitter display
00825-0100-1600March 2022
3. Navigate the menus using the four membrane switches:
• Activate ⇧ or ⇩ to scroll to the previous or next item in the menu.
• Activate and hold ⇧ or ⇩ (approximately 1 second) to scroll rapidly through
numbers or menu options.
• Activate ⇨ to drill down to a lower menu or to select an option.
• Activate and hold ⇨ to save and apply your action.
• Activate ⇦ to return to the previous menu.
• Activate and hold ⇦ to cancel your action.
The action bar is updated with context-sensitive information. The ⇨ and ⇦ symbols
indicate the associated membrane switch.
If the menu or the topic is too large for a single display screen, the ⇩ and ⇧ symbols
at the bottom and top of the LCD panel are used to indicate that you must scroll
down or up to see more information.
Figure 9-2: Navigation arrows
4. If you make a menu choice that leads back to the main menu, or changes to certain
procedures such as zero calibration:
• If display security is not enabled, the display prompts you to activate ⇦⇩⇨, in
that order. This feature protects against accidental changes to configuration,
but does not provide any security.
Installation Manual41
Components of the transmitter displayInstallation Manual
March 202200825-0100-1600
Figure 9-3: Security prompts
• If display security is enabled, the display prompts you to enter the display
password.
5. If you make a menu choice that requires entering a numeric value or character
string, the display provides a screen similar to the following:
42 Micro Motion 1600 Ethernet Transmitters
Installation ManualComponents of the transmitter display
00825-0100-1600March 2022
Figure 9-4: Numeric values and character strings
• Activate ⇦ or ⇨ to position the cursor.
• Activate ⇧ and ⇩ to scroll through the values that are valid for that position.
• Repeat until all characters are set.
• Activate and hold ⇨ to save the value.
6. To exit the display menu system, use either of the following methods:
• Wait until the menu times out and returns to the display variables.
• Exit each menu separately, working your way back to the top of the menu
system.
Installation Manual43
Components of the transmitter displayInstallation Manual
March 202200825-0100-1600
44 Micro Motion 1600 Ethernet Transmitters
Installation ManualAvailable service port connection
00825-0100-1600March 2022
10Available service port connection
Use the service port connection to download or upload data from/to the transmitter.
To access the service port, you can use the following signal converter to connect to the
service port terminals:
• USB to USB Type C
WARNING
If the transmitter is in a hazardous area, do not remove the housing cover while the
transmitter is powered up. Failure to follow these instructions can cause an explosion
resulting in injury or death.
Installation Manual45
Available service port connectionInstallation Manual
March 202200825-0100-1600
46 Micro Motion 1600 Ethernet Transmitters
F3
C A
IEC 127-2
J3
DISC
OUT 3
T5A 250V
C A
F1
C A
IEC 127-2
J1
J4
DS1
T5A 250V
K3K2K1
ABC
DISC
OUT 2
IEC 127-2
F2 T5A 250V
J2
DS2
DISC
OUT 1
DS3
C18
C16
C14
A14
Installation ManualWire the 1600 to the 3100 relays
00825-0100-1600March 2022
AWire the 1600 to the 3100 relays
Use this procedure to wire the Discrete Output on the 1600 Ethernet transmitter to the
3100 transmitter relays for single-stage batch control.
Prerequisites
• Set up the Channel B configuration to DO before wiring
• Use active high and internal power.
• Use wire size 24 AWG (0,25 mm2) to 16 AWG (1,5 mm2).
Procedure
1. Wire the negative terminal on Channel B from the 1600 Ethernet transmitter to
A14.
2. Wire the positive terminal on Channel B from the 1600 Ethernet transmitter to
either C14, C16, or C18.
Figure A-1: Wiring for 1600 Ethernet Channel B DO to 3100 relays
The Emerson logo is a trademark and service mark of Emerson
Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct
Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of
their respective owners.
www.emerson.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.