Micro Motion Manual: Transmitter with Foundation Fieldbus - Model 5300 | Micro Motion Manuals & Guides

Product Manual
http://www.micromotion.com
Model 5300 Transmitter withF
OUNDATION
NOTICE
Read this manual before working with the product. For optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
The products described in this document are NOT designed for nuclear­qualified applications.
Using non-nuclear qualified products in applications that require nuclear­qualified hardware or products may cause inaccurate readings.
For information on Fisher-Rosemount nuclear-qualified products, contact your local Fisher-Rosemount Sales Representative.
Micro Motion Model 5300 Transmitter with FOUNDATION fieldbus may be protected by one or more U.S. Patents Pending. Other foreign patents pending.
Micro Motion, the Micro Motion logotype, ELITE, and BASIS are registered trademarks of Micro Motion Inc. Rosemount is a registered trademark of Rosemount Inc. DeltaV, the DeltaV logotype, PlantWeb, and the PlantWeb logotype are trademarks of Fisher-Rosemount
OUNDATION is a trademark of the Fieldbus Foundation
F Hastelloy is a registered trademark of Haynes International Inc. Teflon is a registered trademark of E. I. Du Pont de Nemours Co. Inc.
fieldbus
Micro Motion Inc. USA Worldwide Headquarters
7070 Winchester Circle Boulder, Colorado 80301 Tel (303) 530-8400
(800) 522-6277
Fax (303) 530-8459
P/N 3100869, Rev. A © Micro Motion, Inc. 1999
Model 5300 transmitters satisfy all obligations coming from legislation to harmonize product requirements in the European Union.
The Model 5300 transmitter has passed a series of tests conducted by the Fieldbus Foundation at its independent laboratory, and is interoperable with otherregistered instruments regardless of manufacturer.
Model 5300 transmitters support PlantWeb field-based architecture, ascalable way to use open and interoperable devices and systems to build process solutions of the future.

Table of Contents

IMPORTANT
Procedures and instructions in this manual may require special precautions to ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol (). Refer to
the safety messages, listed throughout this manual, before performing an operation preceded by this symbol.
SECTION 1 Introduction
SECTION 2 Installation
SECTION 3 Operation
Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Model 5300. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
OUNDATION fieldbus Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
F
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Safety, Reliability, and Accessibility . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Remotely Mounting the Model 5300. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Mounting Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Sensor Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Power-Supply And Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
General Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Power-Supply Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Output Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Software Functionality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Resource Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
OUNDATION fieldbus Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
F
Diagnostics and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Flowmeter Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Configuring and Calibrating the Model5300 . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Calibration and Characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Process Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Viewing Process Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
SECTION 4 Troubleshooting
General Guidelines For Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Customer Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Alarm Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Troubleshooting Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Error Messages Displayed By the fieldbus Host or Controller . . . . . . . 4-5
i
APPENDIX A Specifications
Functional Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Hazardous Area Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
APPENDIX B Transducer Blocks
Transducer Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
ii

Introduction

Section
1 Introduction
USING THIS MANUAL
This manual is intended to assist in installing, operating, and maintaining the MicroMotion Micro Motion Coriolis flow sensors. For more information about the sensor, see the sensor instruction manual.
This manual does not explain how to use F fieldbus host. Users should have at least a basic knowledge of F fieldbus before using this or any fieldbus product.
Section 2: Installation
provides mechanical, electrical, and environmental considerations and installation instructions (see page2-1).
Section 3: Operation
summarizes basic operation, software functionality, and configuration (see page3-1).
Section 4: Troubleshooting
provides troubleshooting instructions for diagnosing messages (see page4-1).
Appendix A: Specifications
provides functional, performance, and physical specification data (see pageA-1).
Appendix B: Transducer Block Data
provides transducer blocks data for the Model 5300 (see pageB-1).
®
Model 5300 Transmitter with FOUNDATION™ fieldbus, for use with
OUNDATION fieldbus or any specific
OUNDATION
SAFETY MESSAGES
DEFINITIONS
Procedures and instructions in this manual may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol (). Refer to safety messages before performing an operation preceded by this symbol.
The term sensor refers to a Micro Motion sensor only. The term flowmeter refers to the Model 5300 transmitter and the sensor installed as a flowmetering system.
1-1
Micro Motion Model 5300 Transmitter with FOUNDATION fieldbus
Introduction
GETTING ACQUAINTED WITH THE TRANSMITTER
Model 5300
FOUNDATION fieldbus Technology
The Model 5300 transmitter has passed a series of tests conducted by the Fieldbus Foundation at its independent laboratory. The Model 5300 is registered with the Fieldbus Foundation, and is interoperable with otherregistered instruments regardless of manufacturer.
The Model 5300 transmitter can be integrally mounted to a Micro Motion BASIS sensor, or remotely mounted from an ELITE
FOUNDATION fieldbus is an all digital, serial, two-way communication system that interconnects field equipment such as sensors, actuators, and controllers. Fieldbus is a Local Area Network (LAN) for instruments used in both process and manufacturing automation with built-in capability to distribute the control application across the network. The fieldbus environment is the base level group of digital networks in the hierarchy of plant networks.
The fieldbus retains the desirable features of the 4–20mA analog system, including a standardized physical interface to the wire, bus powered devices on a single wire, and intrinsic safety options, and enables additional capabilities, such as:
• Increased capabilities due to full digital communications
• Reduced wiring and wire terminations due to multiple devices on one set of wires
• Increased selection of suppliers due to interoperability
• Reduced loading on control room equipment with the distribution of some control and input/output functions to field devices
®
, BASIS, D, DT, or DL sensor.
®
1-2
Section

Installation

2 Installation
OVERVIEW
GENERAL CONSIDERATIONS
Safety, Reliability, and Accessibility
This section contains transmitter-specific installation information. For fieldbus­related installation information, refer to Fisher-Rosemount’s Site Planning Guide
for Fieldbus PlantWeb
Builder if you are using the DeltaV™ Fieldbus
Configuration Tool.
Before getting started, read the following general information regarding transmitter installation.
Explosion hazard Improper installation in a hazardous area could cause an explosion.
Install the transmitter in an environment that is compatible with the hazardous area specified on the approvals label, “Label 2,” below.
Do not remove EExe (field wiring) or EEx d (circuit board) compartment covers in an explosive atmosphere within 2 minutes after power is disconnected. Read labels that point to compartment covers before accessing wiring or circuit board compartments.
Field Wiring
Compartment
Rated EExe
and EEx i
Circuit Board Compartment
Rated EExd
Label 2
Label 1
Lockout Device
• ”Label 1” indicates the sensor wiring compartment is rated EExi (intrinsically safe), and may be opened at any time.
• ”Label 2” indicates the field wiring compartment is rated EExe (increased safety), and should remain closed when power is on.
• The circuit board compartment is rated EExd (flameproof), and should remain closed at all times after the transmitter has been installed. Normally, there is no reason for the user to access this compartment. If the transmitter is approved by CENELEC as flameproof, the compartment has a lockout device, shown above. The lockout device must be loosened and rotated before the compartment cover can be unscrewed.
Sensor Wiring Compartment
Rated EExi
2-1
Installation
Micro Motion Model 5300 Transmitter with FOUNDATION fieldbus
Orientation and Mounting Orient the Model 5300 so wiring compartments and conduit openings are easily
accessible.
• If the Model 5300 will be integrally mounted to a BASIS sensor, see the sensor instruction manual for information about flowmeter mounting and location.
• If the Model 5300 will be remotely mounted, use the supplied bolt assemblies to attach the Model 5300 to the mounting bracket. Attach the bracket to a rigid, stable surface or instrument pole that will not transfer excessive vibration into the transmitter. See page2-3 for more information about remote mounting.
• To rotate the Model 5300 on the sensor manifold or the mounting bracket, use the four supplied mounting bolt assemblies. Each bolt assembly includes one M8 bolt, one lock washer, and one flat washer. Remove the bolt assemblies, rotate the Model 5300, then reinstall the bolt assemblies to 12 ft-lb (16 Nm) of torque.
Temperature Limits Install the Model 5300 in an area where ambient temperature will remain between
Visibility of Tags To ensure personal and system safety, all tags attached to the Model 5300 housing
–22 and 131°F (–30 and 55°C).
must remain visible. Clean or replace them as often as necessary.
2-2
Installation
Installation
Tables2-1, 2-2, and 2-3, pages 2-5 and 2-6
REMOTELY MOUNTING THE MODEL 5300
Mounting Procedure
FIGURE 2-1. Installation Dimensions for Remote Mounting.
Dimensions in
2X3/14-14 NPT
or M20 x 1.5
conduit opening
inches
(mm)
5 3/4 (147)
The instructions in this section apply only if the Model 5300 will be remotely mounted from the sensor. If the Model 5300 is integrally mounted to a BASIS sensor, proceed to page2-10.
To install the Model 5300 remotely from the sensor, follow these steps:
1. Choose the proper location. Install the Model 5300 according to the conditions stated in “General Considerations” on page 2-1.
• For mounting dimensions, see Figure2-1, below.
• Total length of cable from sensor to Model 5300 must not exceed 1000 feet (300 meters).
• For bend radii of cables, see Tables 2-1, 2-2, and 2-3, on pages 2-5 and 2-6.
2. If the Model 5300 was ordered for remote-mounting from the sensor, the transmitter is shipped with an L-shaped mounting bracket. Attach the bracket to a rigid, stable surface or instrument pole that will not transfer excessive vibration into the transmitter. Mount the Model 5300 to the bracket.
• For flat-surface mounting, see Figure 2-2a on page 2-4.
• For pole mounting, see Figure 2-2b on page 2-4.
1 3/8
(35)
4 15/64
(108)
19/32
(15)
3/4-14 NPT gland
for sensor wiring
25/64
Ø
(10)
2 13/16
(71)
2 13/16
(71)
61/64
(24)
7 1/64
(178)
5 57/64
2X
(150)
4 1/4 (108)
9 43/64
(245)
For minimum bend radius ofcable, see
4 53/64
(122)
6 17/64
(159)
2-3
Installation
Micro Motion Model 5300 Transmitter with FOUNDATION fieldbus
FIGURE 2-2a. Mounting the Model5300 to a Wall or Other Surface.
Circuit Board Compartment
User access not normally required
Area Approval Tag
Field Wiring Compartment
Sensor Wiring Compartment
4X M8 Bolt
4X lock washer
To rotate transmitter, remove, then
re-install to 12 ft-lb (16Nm) torque
4X flat washer
Suitable for installation environment
4X 5/16 (M8) Bolt
User-supplied
Use washers to shim bracket if
mounting surface is not flat
Do not secure bolts to separate beams, girders, wall studs, etc.
FIGURE 2-2b. Mounting the Model5300 to an Instrument Pole.
Area Approval Tag
Field Wiring Compartment
Sensor Wiring Compartment
Circuit Board Compartment
User access not normally required
4X 5/16 (M8) Bolt
User-supplied
Suitable for installation environment
To rotate transmitter, remove, then
re-install to 12 ft-lb (16Nm) torque
2-4
4X M8 Bolt
4X lock washer
4X flat washer
2X 5/16-Inch U-Bolt for 2-InchPipe
User -supplied Suitable for installation environment
Installation
Installation
TABLE 2-1. Jacketed Cable.
TABLE 2-2. Shielded Cable.
Jacket
Material
PVC 0.415 inch
®
Teflon
FEP
Jacket
Material
PVC 0.560 inch
®
Teflon
FEP
Outside
Diameter
(10 mm)
0.340 inch (9 mm)
Outside
Diameter
(14 mm)
0.425 inch
(11 mm)
Minimum Bend Radii
Static (No Load) Condition Under Dynamic Load
3 1/8 inch
(80 mm)
2 5/8 inch
(67 mm)
6 1/4 inch (159 mm)
5 1/8 inch (131 mm)
Jacket
Drain Wire (4)
Filler (5)
Minimum Bend Radii
Static (No Load) Condition Under Dynamic Load
4 1/4 inch (108 mm)
3 1/4 inch
(83 mm)
8 1/2 inch (216 mm)
6 3/8 inch (162 mm)
Outer Jacket
Tin-Plated Copper Braided Shield
Foil Shield
Inner Jacket
Drain Wire (4)
Filler (5)
2-5
Installation
Micro Motion Model 5300 Transmitter with FOUNDATION fieldbus
TABLE 2-3. Armored Cable.
Jacket
Material
PVC 0.560 inch
®
Teflon
FEP
Outside
Diameter
(14 mm)
0.425 inch (11 mm)
Static (No Load) Condition Under Dynamic Load
4 1/4 inch (108 mm)
3 1/4 inch
Minimum Bend Radii
(83 mm)
8 1/2 inch (216 mm)
6 3/8 inch (162 mm)
Outer Jacket
Stainless Steel Braided Shield
Foil Shield
Inner Jacket
Drain Wire (4)
Filler (5)
TABLE 2-4. Temperature Ranges for Jacket Material.
Cable Jacket Material
PVC –40°F
®
Teflon
FEP –76°F
Low Operating
Temperature Limit
(–40°C)
(–60°C)
High Operating
Temperature Limit
221°F
(105°C)
302°F
(150°C)
TABLE 2-5. Cable Installation Guidelines.
Installation Conditions
Conduit is used Conduit is not used Conduit is not used and
mechanicalprotection is required
Jacketed
Cable
ü
Shielded
Cable
ü
Armored
Cable
ü
2-6
Installation
Installation
Sensor Wiring
Connect the Model 5300 to the sensor using Micro Motion-supplied 9-wire jacketed, shielded, or armored cable. Refer to the instructions below and on page2-8.
General Cable Information
• The remote-mount Model 5300 may be ordered with a length of cable attached to the transmitter by the factory, or with cable not yet attached.
• Jacketed cable is CE-compliant when it is installed inside user- supplied sealed metallic conduit that provides 360° termination shielding for the enclosed cable.
• Shielded and armored cable are CE-compliant when the cable is installed with the factory-supplied cable glands.
®
• Each cable type is available with a PVC or Teflon
FEP jacket. For
temperature ranges of cable jacket materials, see Table 2-4on page 2-6.
• All cable types are acceptable for cable tray installation.
Guidelines for Cable Glands
• Prepare cable ends and assemble the supplied cable gland according to the instructions that are enclosed with the cable preparation kit.
• Connect the ¾-inch NPT male cable gland to the ¾-inch NPT female conduit opening on the sensor junction box.
Improper installation of cable, cable gland, or conduit could cause inaccurate measurements or flowmeter failure.
Ensure 360° termination shielding for flowmeter wiring. Install the factory-supplied cable gland or user-supplied sealed metallic conduit to the conduit opening on the sensor junction box.
Guidelines for Conduit
• If sealed metallic conduit is installed, it must provide 360° termination shielding for the enclosed flowmeter cable.
• Install a drip leg in conduit to prevent liquids from entering the junction box.
• Connect the sealed end of the conduit to the ¾-inch NPT female conduit opening on the sensor junction box.
2-7
Installation
Micro Motion Model 5300 Transmitter with FOUNDATION fieldbus
Wiring Connections to Sensor
• Insert the ends of the individual wires into the terminals inside the sensor junction box. No bare wires should remain exposed.
• Match the wire colors of the cable with the wire colors at the sensor wiring terminal as described in Table 2-6, below, and Figure2-3, page2-9.
• If possible, position the junction box so the conduit entrance points downward to prevent moisture from entering.
Failure to seal sensor junction box or transmitter housing could cause a short circuit, which would result in measurement error or flowmeter failure.
To avoid risk of condensation or excessive moisture entering the junction box or transmitter housing:
• Seal all conduit openings.
• Install drip legs in cable or conduit.
• Ensure integrity of gaskets and O-rings, and fully tighten sensor junction box and transmitter housing covers.
TABLE 2-6. Sensor Terminal Designations.
Terminal
Number
1 Brown Drive + 2 Red Drive – 3 Orange Temperature – 4 Yellow Temperature Lead Length Compensator 5 Green Left Pickoff + 6 Blue Right Pickoff + 7 Violet Temperature + 8 Gray Right Pickoff – 9 White Left Pickoff –
Wire
Color
Function
2-8
Installation
FIGURE 2-3. Cable Connections to
Black (Drains,
remote-mount only)
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
Black (Drains,
remote-mount only)
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
Sensor wire number
Black (Drains,
remote-mount only)
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
Sensor and Model 5300 Transmitter
Installation
.
ELITE® Sensor
Terminals
Green
White
Brown
Violet
Yellow
Orange
BASIS®, D, and DL
Sensor Terminals
Brown Red Orange Yellow Green Blue Violet Gray White
Blue Gray Red
Brown
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Flowmeter
Cable
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the instructions
that are shipped with the cable
Flowmeter
Cable
Maximum cable length 1000 ft. (300 m)
Black (Drains from all wire sets)
Brown Red
Green White
Blue Gray
Orange Violet Yellow
Black (Drains from all wire sets)
Brown Red
Green White
Blue Gray
Orange Violet Yellow
GND
10 11 12
GND
10 11 12
Model 5300
Terminals
Model 5300
Terminals
Prepare cable in accordance with the instructions
that are shipped with the cable
Model DT
sensorterminals
User-supplied metal
junctionbox with
terminalblock
Brown Red Orange Yellow Green Blue Violet Gray White
Earth ground
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Prepare cable in accordance with the instructions
Flowmeter
cable
Maximum cable length 1000 ft. (300 m)
that are shipped with the cable
Black (Drains from all wire sets)
Brown Red
Green White
Blue Gray
Orange Violet Yellow
Model 5300
Terminals
2-9
Installation
Micro Motion Model 5300 Transmitter with FOUNDATION fieldbus
POWER-SUPPLY AND OUTPUT WIRING
The information in this section applies to power-supply and output wiring. For specific output wiring information — suitable types of wire, maximum lengths, and other concerns specific to the electrical specifications of a fieldbus loop —
refer to the Site Planning Guide for the Fieldbus PlantWeb
Builder if you are
using the DeltaV™ Fieldbus Configuration Tool.
General Guidelines
The transmitter has a sensor wiring compartment for intrinsically safe sensor wiring, and a field wiring compartment for non-intrinsically safe power-supply wiring and intrinsically safe output wiring. See Figure2-4.
• Access to the sensor wiring and circuit board compartments is not required during installation of power-supply and output wiring.
• To access power-supply and output wiring, loosen the four captive screws that secure the cover of the field wiring compartment.
• Install cable and wiring so they meet local code requirements.
• The transmitter has two separate ¾-inch NPT or M20 female conduit openings, which must remain sealed to keep the transmitter watertight. See Figure2-4.
Failure to seal transmitter housing could cause a short circuit, which would result in measurement error or flowmeter failure.
To avoid risk of condensation or excessive moisture entering the transmitter housing:
• Seal all conduit openings.
• Install drip legs in cable or conduit.
• Ensure integrity of gaskets, and fully tighten transmitter housing covers.
FIGURE 2-4. Power-Supply Wiring and Output Terminals.
Power-supply Terminals
and Voltage Label
Match power supply to
voltage specified on label
Conduit Opening for
Power-Supply Wiring
Seal all conduit openings
Ground Screw for Power Supply
If national standards are not in effect, adhere to this standard:
• For grounding, use copper wire, 14AWG (2.5mm²) or larger wire size.
• Keep all ground leads as short as possible.
• Transmitter must be grounded with less than 1ohm impedance.
• Connect power-supply ground directly to earth.
Circuit Board Compartment
User access not normally required
Output Wiring Terminals
Conduit Opening for Output Wiring
• Terminate output cable shielding at gland or conduit fitting.
• 360° termination of shielding is not necessary.
• Do not terminate shield inside wiring compartment.
• Seal all conduit openings.
Field Wiring Compartment
Fully tighten cover to keep sealed.
Sensor Wiring Compartment
2-10
Installation
Installation
Power-Supply Wiring
Connect power-supply wiring to the power-supply terminals, indicated in Figure2-4.
• Wiring terminals accommodate 20 AWG (0.5 mm²) to 16 AWG (1.5mm²) wire.
• If the transmitter has a DC power supply, maximum wire lengths are as follows:
Power-Supply
Wire Size
16 AWG (1.5 mm²) 1500 feet (450 meters)
18 AWG (0.75 mm²) 1000 feet (300 meters)
20 AWG (0.5 mm²) 600 feet (200 meters)
Maximum Length
• A switch may be installed in the power-supply line. For compliance with low-voltage directive 73/23/EEC, a switch in close proximity to the transmitter is required.
• Do not install power cable in the same conduit or cable tray as flowmeter cable or output wiring.
• The transmitter must be grounded with a maximum impedance of 1 ohm. Either the internal ground screw or external case ground screw may be used as required by local policy or code.
Output Wiring
Incorrect voltage, or installation with power supply on, could cause transmitter damage or failure.
• Shut off power before installing transmitter.
• Match power supply voltage with voltage indicated on label in field wiring compartment.
Power-Supply VoltageLabel
Connect output wiring to the Model 5300 output terminals, indicated in Figure2-4. Wiring terminals accommodate 20 AWG (0.5 mm²) to 16 AWG (1.5mm²) wire.
For information about suitable types of wire, maximum lengths, and other concerns specific to the electrical specifications of a Fieldbus loop, refer to the Site
Planning Guide for the Fieldbus PlantWeb
Builder.
2-11
Loading...
+ 39 hidden pages