Chapter 1
Using the Modbus Map
1.1About this manual
®
This manual lists Modbus
Modbus protocol.
This manual does not explain how individual registers are used. For detailed information about using
the registers that are listed in this document, see Using Modbus Protocol with Micro Motion Transmitters, available on the CD that is shipped with the transmitter, or on the Micro Motion web
site (www.micromotion.com).
This manual does not explain terminology and procedures for using Modbus protocol, or how to use a
host controller to communicate with other devices in a Modbus-compatible multidrop network. For
detailed information about using Modbus protocol, see www.modbus.org.
This manual does not explain transmitter installation or flowmeter wiring. For information about
installation and wiring, see the appropriate sensor and transmitter manuals.
mapping assignments for Micro Motion® transmitters that support
Modbus MapUsing the Modbus Map
1.2Transmitters that support Modbus protocol
Micro Motion transmitters that support Modbus protocol include:
•RFT9739 transmitters, Version 2 and higher
•Micro Motion MVD
•Series 1000 and 2000 transmitters, all versions
•LF-Series transmitters, all versions
•Series 3000 MVD (4-wire) transmitters
Note: MVD Direct Connect installations do not include a transmitter. However, a Modbus/RS-485
connection can be made to the core processor component, and Modbus commands can be used to
communicate with the core processor. See the MVD Direct Connect flowmeter installation manual for
information on setting up this connection.
In this manual, the term “MVD” refers to all of the above except the RFT9739 transmitters.
1.3How to use this manual
This manual is designed for use as a reference manual. It lists the Modbus registers for transmitter
configuration, calibration, use, and diagnostic procedures. Some procedures are required; others are
optional.
™
Direct Connect™, with or without the MVD Direct Connect I.S. barrier
Modbus Mapping Assignments for Micro Motion Transmitters1
Using the Modbus Map continued
This manual also lists the Modbus registers for the following special applications:
•Petroleum measurement application (API feature)
•Enhanced density application
• Discrete batch application and filling and dosing application
•Net Oil Computer (NOC) application
•Custody transfer application
For each register, checkmarks indicate the transmitters for which the register is enabled.
In addition, this manual lists the integer codes that are used in configuration.
1.3.1Register addresses
Each register is identified by its address (or starting address), which is a 4-digit number.
Depending on the PLC that will be used to communicate with the transmitter, you may need to
subtract 1 from the address or starting address of the register. Refer to your PLC documentation to
know if this applies to you.
Example
This Modbus manual specifies 0042 as the address of the register that
contains the unit for process variables that measure volume flow.
Use 0041 in the data field of the Modbus frame.
1.3.2Register types
The register types are listed and briefly described in Table 1-1.
Note: Micro Motion terminology is a simplified version of Modbus terminology. The term “coil” is
used for both Modbus coils (read-write) and Modbus discrete inputs (read-only), and the term
“register” is used for both Modbus holding registers (read-write) and Modbus input registers (readonly).
Table 1-1Modbus register types
Register typeSizeData typeDescription
Coil1 bitBinaryBoolean (0 or 1, ON or OFF)
Float16 bitFloating-pointUsed in pairs to store 32-bit floating-point values in single precision
Integer16 bitIntegerUnsigned 16-bit integers ranging from 0 to 65535
Long integer16 bitIntegerUsed in pairs to store unsigned 32-bit integers ranging from 0 to
ASCII16 bit8-bit ASCIIOne or more consecutive registers. Each register stores two 8-bit ASCII
IEEE 754 format
4294967295 (0xFFFFFFFF)
characters (16 bits total).
1.3.3Transmitter codes
If a register applies only to a subset of the model or series, codes are used to identify the models to
which the register applies. Codes are listed in Table 1-2.
2Modbus Mapping Assignments for Micro Motion Transmitters
Using the Modbus Map continued
Table 1-2Transm it te r codes
CodeTransmitter
AAll transmitters with the analog outputs option board
IAll transmitters with the intrinsically safe outputs option board
CAll transmitters with the configurable input/outputs option board
FAll transmitters with the
PAll transmitters with the Profibus-PA outputs option board
NNet Oil Computer (Series 3000 transmitters with the NOC application)
1.3.4LF-Series transmitters
The LF-Series transmitters are based on Series 1000 and Series 2000 transmitters, and use the same
Modbus interface. For this reason, they are not called out separately in this manual. All references to
Series 1000 or Series 2000 transmitter also apply to the equivalent LF-Series transmitter:
•Model 1500 includes the LF-Series: DIN Rail Flow Only
•Model 1700 includes the LF-Series: Field Mount Flow Only
•Model 2500 includes the LF-Series: DIN Rail Multivariable
•Model 2700 A includes the LF-Series: Field Mount Multivariable 1mA/1FO
FOUNDATIONFieldbus outputs option board
Modbus MapUsing the Modbus Map
•Model 2700 C includes the LF-Series: Field Mount Multivariable 2mA/1FO configurable
•Model 2700 F includes the LF-Series: Field Mount F
•Model 2700 P includes the LF-Series: Field Mount Profibus-PA
1.3.5Organization
The reference section of this manual is organized as follows:
•All coils, listed numerically by address (Table 2-1)
•All floating-point registers, listed numerically by address (Table 2-2)
•All integer registers, listed numerically by address (Table 2-3)
•All long integer registers, listed numerically by address (Table 2-4)
•All ASCII registers, listed numerically by address (Table 2-5)
•Integer codes, listed by function (Tables 2-6 through 2-44)
Additional information for a specific register or transmitter is provided in a footnote. For each table,
the page on which the footnotes can be found is listed at the top of the page.
1.4Customer service
For customer service, or to order manuals, contact Micro Motion Customer Service. Contact
information is provided on the title page of this manual.
OUNDATION fieldbus
Modbus Mapping Assignments for Micro Motion Transmitters3
4Modbus Mapping Assignments for Micro Motion Transmitters
Chapter 2
Modbus Mapping Assignments
2.1Coil registers
In Table 2-1:
•RW = Read/write
-ON (1) = Start, Reset, Apply, Enable, Resume
-OFF (0) = Stop, Abort, Disable, No action taken
•RO = Read-only
-ON (1) = Condition active
-OFF (0) = Condition inactive
Table 2-1CoilsTransmitter codes on page 3, footnotes on page 9
Modbus Map Using the Modbus Map
Address RO/RWDescription
0002RWStart/stop totalizers√√√√√√√
0003RWReset all totalizers√√√√√√√
0004RWReset all inventories√√√√√√√
0005RWPerform flowmeter zeroing√√√√√√√
0006RWTrim primary mA output at 0 or 4 mA √√√√AIC√
0007RWTrim primary mA output at 20 mA √√√√AIC√
0008RWTrim secondary mA output at 0 or 4 mA√√IC√
0009RWTrim secondary mA output at 20 mA√√IC√
0010RWFix/unfix current level from primary mA output√√√√AIC√
0011RWFix/unfix current level from secondary mA output √√IC√
0012RWFix/unfix frequency from frequency/pulse output √√√√AIC√
0013RWPerform low-density calibration √√√√√√√
0014RWPerform high-density calibration√
0014RWPerform flowing density (FD) calibration √
0015RWPerform temperature offset calibration√√√√√√√
0016RWPerform temperature slope calibration√√√√√√√
0018RWPerform flowing density (FD) calibration √√√√√√
0018RWSave non-volatile data √
0020RWPerform transmitter self-test √√√√√√√
0021RO(E)EPROM checksum failure√√√√√√√
0022RORAM diagnostic failure√√√√√√√
0023ROReal-time interrupt failure√
0024ROSensor failure√√√√√√√
0025ROTemperature sensor failure√√√√√√√
0026ROFlowmeter zeroing failure√√√√√√√
0027ROOther failure occurred√√√√√√√
0028ROTransmitter initializing/warming up√√√√√√√
0029ROPrimary variable out of range√√√√√√√
0030RONon-primary variable out of range√√√√√√√
0031ROMilliamp output(s) saturated√√√√AIC√
0032ROMilliamp output(s) fixed√√√√AIC√
0033ROWatchdog timer error√√√√√√√
RFT9739
MVD DC
Model 1500
Model 1700
Model 2500
1
√√√√√√
1
Model 2700
Series 3000
Modbus Mapping Assignments for Micro Motion Transmitters5
Modbus Mapping Assignments continued
Table 2-1Coils continuedTransmitter codes on page 3, footnotes on page 9
Address RO/RWDescription
RFT9739
MVD DC
Model 1500
Model 1700
Model 2500
Model 2700
Series 3000
0034ROPower reset occurred√√√√√√√
0035ROTransmitter configuration changed√√
0036ROTransmitter electronics failure√√√√√√√
0037ROEvent 1 status√√√√√AIC
0038ROEvent 2 status√√√√√AIC
0039RWReset configuration and calibration registers√
0039RWSave “factory calibration” meter fingerprint data set√√√√√√
0040RWReset meter fingerprint statistics for “current” data set√√√√√√
0041RWPerform reboot√√√√√√√
0044RWPerform T-Series sensor D3/K3 calibration√√√√√√
0045RWPerform T-Series sensor D4/K4 calibration√√√√√√
0046RWFix/set discrete output 1√
0047RWFix/set discrete output 2 √
0048RWFix/set discrete output 3√
0050RWBacklight control (ON=Backlight on; OFF=Backlight off)√
0052RWScreen test√
0053RWReset alarm history√
0054RWReset audit trail event counter and record counter√
2
2
√AIC√
√C√
3, 4
3, 4
AICF
3, 4
√3√
√
5
0055RWReset frequency input total √
0056RWReset mass total√√√√√√
0057RWReset line volume (gross volume) total√√√√√√
0058RWReset API reference volume total (standard volume total)√
0059RWReset enhanced density reference volume total√7√7√
0060RWReset enhanced density net mass total√7√7√
0061RWReset enhanced density net volume total√7√7√
6
√6√6√
6
7
7
7
0062RWReset lifetime temperature statistics√√√√
0065ROEvent 1 or event 2 status√√√AIC
0066ROFlow direction switch status√√√√√
0067ROFlow rate indicator status√√√√√
0068ROZero in progress status√√√√√
0069ROHigh-severity alarm status√√√√√
0071RWEnable/disable line volume flow calculations √√√√√√
0074RWEnable/disable meter fingerprinting√√√√√√
0079RWEnable/disable copper RTD√√√√√√
0081RWEnable/disable cryogenic modulus compensation√√√√√√
0082RWEnable/disable pressure compensation√√√√√√
0083RWEnable/disable burst mode√√√AIC√
0084RWEnable/disable fieldbus simulation modeF
0085RWEnable/disable locked ED curves√
0086RWEnable/disable use externally written temperature (floating-point
register pair 0449–0450) for internal calculations
0089RWEnable/disable fault on unidentified K1/FCF combination√√7√7√7√7√
7, 8√7, 8√7, 9
√7√7√7√
7
7
0090RWEnable/disable auto print at batch end√
0091RWEnable/disable totalizer start/stop from display
4
√
4
√
0092RWEnable/disable display security√
0094RWEnable/disable totalizer reset from display√√
0095RWEnable/disable automatic scrolling of display variables√√
0096RWEnable/disable access to display offline menu√√
0097RWEnable/disable password for access to display offline menu√√
0098RWEnable/disable access to alarm menu from display√√
0099RWEnable/disable acknowledge all alarms function using display√√
0100RWStart/stop (pause) batch
0100RWBegin/end fill
0101RWResume batch/fill
2
√
2
√
10
√
10
√
6Modbus Mapping Assignments for Micro Motion Transmitters
Modbus Mapping Assignments continued
Table 2-1Coils continuedTransmitter codes on page 3, footnotes on page 9
Address RO/RWDescription
RFT9739
MVD DC
Model 1500
Model 1700
Model 2500
Model 2700
0102RWEnable/disable sensor zero from display
0103RWEnable/disable sensor zero via remote communication
0104RWEnable/disable batch reset from display
0105RWEnable/disable batch reset via remote communication
0106RWReset AOC flow rate
0107RWPause fill
0108RWReset fill statistics
0109RWStart/stop cleaning
0110RWOverride blocked start
0111RWEnable purge stage
0112RWEnable 3-position analog valve
2
√
2
√
2
√
2
√
2
√
2
√
2
√
0113RWRead protect calibration factors√
0114RWWrite protect output variables and units√
0115RWWrite protect scaled integers√
0116RWWrite protect sensor and transmitter information√
0117RWWrite protect special units factors√
0118RWWrite protect control output variable√
0119RWWrite protect flow direction√
0120RWWrite protect fault code√
0121RWWrite protect fault limit√
0122RWWrite protect output variables√
0123RWWrite protect flowmeter zeroing and process variable limits√
0124RWWrite protect pressure variables√
0125RWWrite protect calibration factors√
0126RWWrite protect coil 0002 (start/stop totalizer)√
0127RWWrite protect coil 0003 (reset totals)√
0128RWWrite protect coil 0004 (reset inventories)√
0129RWWrite protect coil 0005 (perform flowmeter zeroing)√
0130RWWrite protect coil 0006 (trim primary mA output at 4 mA or 0 mA)√
0131RWWrite protect coil 0007 (trim primary mA output at 20 mA)√
0132RWWrite protect coil 0008 (trim secondary mA output at 4 mA or 0 mA) √
0133RWWrite protect coil 0009 (trim secondary mA output at 20 mA)√
0134RWWrite protect coil 0010 (fix primary mA output)√
0135RWWrite protect coil 0011 (fix secondary mA output)√
0136RWWrite protect coil 0012 (fix frequency output)√
0137RWWrite protect coil 0013 (perform low-density calibration)√
0138RWWrite protect coil 0014 (perform high-density calibration)√
0142RWWrite protect coil 0018 (save non-volatile data)√
0143RWRead/write protect master reset defaults√
0144RWRead/write protect coil 00020 (perform transmitter self-test)√
0145RWRead protect coil 0021 (EEPROM checksum failure)√
0146RWRead protect coil 0022 (RAM diagnostic failure)√
0147RWRead protect coil 0023 (real-time interrupt failure)√
0148RWRead protect coil 0024 (sensor failure)√
0149RWRead protect coil 0025 (temperature sensor failure)√
0150RWRead protect coil 0026 (flowmeter zeroing failure)√
0150RWEnable Coriolis input from sensor√
0151RWTreat sensor alarms as informational until alarm timeout (see register
1150)
Series 3000
5
√
5
√
5
√
5
√
Modbus Map Using the Modbus Map
N
Modbus Mapping Assignments for Micro Motion Transmitters7
Modbus Mapping Assignments continued
Table 2-1Coils continuedTransmitter codes on page 3, footnotes on page 9
0223ROBatch end warning√
0224ROBatch overrun√
0225ROBatch pump√
0226ROBatch/fill primary valve√
0227ROBatch/fill secondary valve√
0228ROStart not okay√
0230ROAOC training active√
0231ROBatch/fill ready to start√
2
2
2
2
2
0259RONOC in continuous modeN
0260RONOC in pause modeN
0269RWPause production measurementsN
0270RWResume production measurementsN
0271RWReset all production measurementsN
0272RWReset back flowN
0273RWReset densityN
0274RWReset drive gainN
0275RWReset gross flowN
0276RWReset mass flowN
Series 3000
10
10
√
10
10
√
10
10
√
10
10
10
10
√
10
√
10
√
10
10
10
10
10
10
10
10
10
√
10
√
10
10
10
10
√
10
√
10
√
10
√
10
√
8Modbus Mapping Assignments for Micro Motion Transmitters
Modbus Mapping Assignments continued
Table 2-1Coils continuedTransmitter codes on page 3, footnotes on page 9
Address RO/RWDescription
0277RWReset net oil rate (min/max/avg)N
0278RWReset net water cut (min/max/avg)N
0279RWReset temperatureN
0280RWReset uncorrected grossN
0281RWReset uncorrected oilN
0282RWReset uncorrected waterN
0283RWReset uncorrected water cutN
0284RWReset water cutN
0285RWEnable continuous run modeN
0286RWEnable well test modeN
0287RWStart purgeN
0288RWStop purgeN
0289RWStart well testN
0290RWStop well testN
0297RWStart determination of produced water densityN
0298RWStop determination of produced water densityN
0300ROConfiguration memory initialized; NOC not configuredN
0301RONOC configuration corruptedN
0302RONOC configuration mismatchedN
0303RONOC configuration invalidN
0304ROTemperature out of rangeN
0305RODensity out of range (slug flow) warningN
0306RODensity out of range (slug flow) alarmN
0307ROContinuous-mode measurements paused for more than 15 minutesN
0308ROTransient bubbles in sensor (TBR) warningN
0309ROTransient bubbles in sensor (TBR) alarmN
0310RODensity calculation completedN
0311ROPurge in progressN
0320RWCalculate water density from manually entered valuesN
0321RWSave results from calculated water densityN
0322RWReset density determination volume totalN
0323RWStart water density determination measurementN
0324RWAbort water density determination measurementN
0325RWSave results from water density determination measurementN
0326RWStart oil density determination measurementN
0327RWAbort oil density determination measurementN
0328RWSave intermediate results from oil density determination measurementN
0329RWCalculate actual oil density at configured reference tempterature from
oil density measurement and user-supplied water cut
0330RWSave actual oil density at configured reference temperatureN
0331RODensity operation complete flag (0 = In progress; 1 = Finished)N
RFT9739
MVD DC
Model 1500
Model 1700
Model 2500
Model 2700
Series 3000
N
(1) For RFT9739 transmitters, coil 14 initiates either high-density (D2) or flowing density calibration. If the flow rate is greater than
50% of full scale, coil 14 initiates a flowing density calibration; otherwise, coil 14 initiates a D2 calibration.
(2) Requires filling and dosing application.
(3) Requires appropriate hardware.
(4) Transmitter software v3.3 and higher.
(5) Requires custody transfer application.
(6) Requires petroleum measurement application (API feature).
(7) Requires enhanced density application.
(8) Transmitter software v4.1 and higher, or, for transmitters with the F
v3.0 and higher.
(9) Transmitter software v6.1 and higher.
(10) Requires discrete batch application.
Modbus Map Using the Modbus Map
Modbus Mapping Assignments for Micro Motion Transmitters9
Modbus Mapping Assignments continued
2.2Floating-point register pairs
In Table 2-2:
•RO = Read-only
•RW = Read/write
Table 2-2Floating-point register pairsTransmitter codes on page 3, footnotes on page 16
AddressRO/RWDescription
RFT9739
MVD DC
Modeo 1500
Model 1700
Model 2500
Model 2700
Series 3000
0141 0142RWSlug flow duration (seconds)√√√√√√√
0143 0144RWFixed current for primary mA output test (milliamps)√√AI√AIC√
0145 0146RWFixed current for secondary mA output test (milliamps) √√IC√
0147 0148RWFixed frequency for frequency output test (Hz) √√AI√AIC√
0149 0150RWCutoff for density√√√√AICF √
0151 0152RWTemperature for temperature offset/slope calibrations
0155 0156RWDensity for low-density calibration (g/cm
0157 0158RWDensity for high-density calibration (g/cm
0157 0158RWDensity for flowing-density calibration (g/cm
• MVD transmitters: °C
• RFT9739 transmitters: configured temperature unit
(register 0041)
3
)√√√√√√√
3
)√√√√√√√
3
)√
√√√√√√√
1
0159 0160RWDensity calibration constant 1 (µsec)√√√√√√√
0161 0162RWDensity calibration constant 2 (µsec)√√√√√√√
0163 0164RWDensity temperature coefficient√√√√√√√
0165 0166ROHigh mass flow limit of sensor√√√√√√
0167 0168ROHigh temperature limit of sensor√√√√√√
0169 0170ROHigh density limit of sensor (g/cm
3
)√√√√√√2√
0171 0172ROHigh volume flow limit of sensor√√√√√√
0173 0174ROLow mass flow limit of sensor√√√√√√
0175 0176ROLow temperature limit of sensor√√√√√√
0177 0178ROLow density limit of sensor (g/cm
)√√√√√√√
0203 0204ROPrimary mA output present current (milliamps)√√√√AIC√
0205 0206RWAdded damping on primary mA output (seconds)√√√√AIC√
0207 0208RWFlow cutoff for primary mA output√√√√AIC√
0209 0210RWPrimary variable at 20 mA√√√√AIC√
0211 0212RWPrimary variable at 0 mA or 4 mA√√√√AIC√
0213 0214ROSecondary mA output present current (milliamps) √ √IC√
0215 0216RWAdded damping on secondary mA output (seconds) √ √IC√
0217 0218RWFlow cutoff for secondary mA output√ √IC√
0219 0220RWSecondary variable at 20 mA√√IC√
0221 0222RWSecondary variable at 0 mA or 4 mA √√IC√
0223 0224RWFrequency factor or number of pulses (Hz)√√√√AIC√
0225 0226RWFlow rate or total represented by frequency or number of pulses√√√√AIC√
0227 0228RWFrequency maximum pulse width (milliseconds; 0 = 50% duty
cycle)
√√√√AIC√
0229 0230ROFrequency/pulse output present frequency (Hz)√√√√AIC√
0231 0232ROFlowmeter zeroing standard deviation (units in µsec)√√√√√√√
0233 0234RWPresent flow signal offset at zero flow (units in µsec)√√√√√√√
10Modbus Mapping Assignments for Micro Motion Transmitters
Modbus Mapping Assignments continued
Table 2-2Floating-point register pairs continuedTransmitter codes on page 3, footnotes on page 16
AddressRO/RWDescription
0235 0236ROFailed DensCal/TempCal/ZeroCal value (valid only if last
calibration failed)
RFT9739
MVD DC
Modeo 1500
Model 1700
Model 2500
√√√√√√
Model 2700
Series 3000
0235 0236RWFlowmeter zeroing standard deviation limit√
0237 0238RWSpecial mass unit conversion factor√√√√√√√
0239 0240RWSpecial volume unit conversion factor√√√√√√√
0241 0242RWEvent 1 setpoint√√√√√AIC
0243 0244RWEvent 2 setpoint√√√√√AIC
0245 0246RO1(E)EPROM checksum failure√√√√√√√
2RAM diagnostic failure√√√√√√√
4Sensor failure√√√√√√√
8Temperature sensor failure√√√√√√√
16Input overrange√√√√√√√
32Frequency/pulse output saturated√√√√AIC√
64Transmitter not configured√√√√√√√
128Real-time interrupt failure√√√√√√√
256Primary mA output saturated√√√√AIC√
512Secondary mA output saturated√√IC√
1024Primary mA output fixed√√√√AIC√
2048Secondary mA output fixed√√IC√
4096Density overrange√√√√√√√
8192Flowmeter zeroing failure√√√√√√√
16384Zero value too low√√√√√√√
32768Zero value too high√√√√√√√
65536Transmitter electronics failure√√√√√√√
131072 Flowmeter zeroing in progress√√√√√√√
262144 Slug flow√√√√√√√
524288 Power reset occurred√√√√√√√
1048576 Transmitter configuration changed√√
2097152 Transmitter initializing/warming up√√√√√√√
0247 0248ROMass flow rate√√√√√√√
0249 0250RODensity√√√√√√√
0251 0252ROTemperature√√√√√√√
0253 0254ROVolume flow rate√√√√√√√
0257 0258ROPressure (internally derived)√√
0259 0260ROMass total√√√√√√√
0261 0262ROVolume total√√√√√√√
0263 0264ROMass inventory√√√√√√√
0265 0266ROVolume inventory√√√√√√√
0267 0268RWPressure correction factor for flow√√√√√√√
0269 0270RWPressure correction factor for density√√√√√√√
0271 0272RWFlow calibration pressure√√√√√√√
0273 0274RWPressure input at 4 mA√
0275 0276RWPressure input at 20 mA√
0277 0278RWDensity for flowing-density calibration√√√√√√
0277 0278RWFlowing density calibration constant√
0279 0280RWMass flow rate meter factor√4√√√√√√
0281 0282RWVolume flow rate meter factor√
0283 0284RWDensity meter factor√
0285 0286RORaw tube frequency (Hz)√
0287 0288ROLeft pickoff voltage (millivolts)√
0289 0290RORight pickoff voltage (millivolts)√
0291 0292RODrive gain (% for MVD Direct Connect, Series 1000, Series 2000,
Series 3000; volts for RFT9739)
0293 0294ROMass flow live zero flow√
0303 0304RWFlowing-density calibration constant √
0319 0320RWAPI reference temperature √
0323 0324RWAPI thermal expansion coefficient√
0325 0326ROTemperature-corrected density√
3
3
√√√√√√
3
√√√√√√
3
√√√√√√
3
√√√√√√
3
√√√√√√
3
√√√√√√
√
5
√√√√√√
6
√√√√√√
7
7
7
√7√
√7√
√7√
7
7
√
7
7
√
7
7
√
Modbus Map Using the Modbus Map
Modbus Mapping Assignments for Micro Motion Transmitters11
Modbus Mapping Assignments continued
Table 2-2Floating-point register pairs continuedTransmitter codes on page 3, footnotes on page 16
0367 0368RODeltaT (seconds)√√√√√√
0369 0370ROTube period (seconds)√√√√√√
0371 0372ROTemperature: Line RTD (Std RTD on all sensors); (°C)√√√√√√
0373 0374ROTemperature: Meter RTD (T-Series sensors only); (°C)√√√√√√
0379 0380ROLPO amplitude (volts)√√√√√√
0381 0382RORPO amplitude (volts)√√√√√√
0383 0384ROBoard temperature (°C)√√√√√√
0385 0386ROInput voltage (volts)√√√√√√
0407 0408RWAltus-compatibility
0409 0410RWAltus-compatibility
0411 0412RWAltus-compatibility
0413 0414RWAltus-compatibility
8
flow calibration factor (FCF)√√√√√√
8
temperature coefficient for flow (FT)√√√√√√
9
tempcal slope√√√√√√
9
tempcal offset√√√√√√
0435 0436ROSensor maximum recorded temperature√√√√√√
0437 0438ROSensor minimum recorded temperature√√√√√√
0439 0440ROSensor average recorded temperature√√√√√√
0441 0442RWElectronics flow offset compensation for mass flow (nom 0, units
√√√√√√
µsec)
0449 0450RWExternal temperature input value√√√√√√
0451 0452RWExternal pressure input value√√√√√√
0453 0454RWGas density used to calculate reference volume gas and flow totals√√
0455 0456ROReference volume gas flow rate (not valid when petroleum
measurement application or enhanced density application is
enabled)
0457 0458ROReference volume gas total (not valid when petroleum
measurement application or enhanced density application is
enabled)
0459 0460ROReference volume gas inventory (not valid when petroleum
measurement application or enhanced density application is
10√10√10√10√11
√√10√10√10√10√
√√10√10√10√10√
√√10√10√10√10√
11
11
11
enabled)
0463 0464ROElectronics maximum recorded temperature√√√√√√
0465 0466ROElectronics minimum recorded temperature√√√√√√
0467 0468ROElectronics average recorded temperature√√√√√√
0469 0470ROWire (cable) RTD resistance (ohms)√√√√√√
0471 0472ROOn-board thermistor resistance (ohms)√√√√√√
0473 0474ROMeter RTD resistance (ohms)√√√√√√
0475 0476ROLine RTD resistance (ohms)√√√√√√
0503 0504RWT-Series K3 density constant√√√√√√
0505 0506RWT-Series FTG value√√√√√√
0507 0508RWT-Series FFQ value√√√√√√
0509 0510RWDensity for T-Series sensor D3 density calibration√√√√√√
0511 0512RWDensity for T-Series sensor D4 density calibration√√√√√√
0513 0514RWT-Series DTG value√√√√√√
0515 0516RWT-Series DFQ1 value√√√√√√
0517 0518RWT-Series DFQ2 value√√√√√√
0519 0520RWT-Series K4 density constant√√√√√√
0531 0532RWEnhanced density: Curve
0533 0534RWEnhanced density: Curven (6x5) density at
(x-axis)
temperature isotherm
(6x1) temperature isothermx value
n
, concentration
x
y
0535 0536RWEnhanced density: Curven (6x5) coefficient at
temperature isotherm
0537 0538RWEnhanced density: Curven (1x5) concentrationy value
(label for y-axis)
, concentration
x
y
0539 0540RWEnhanced density: Curven (1x6) density at concentrationy
√12√12√
√12√12√
√12√12√
√12√12√
√12√12√
12
12
12
12
12
(at reference temperature)
12Modbus Mapping Assignments for Micro Motion Transmitters
Modbus Mapping Assignments continued
Table 2-2Floating-point register pairs continuedTransmitter codes on page 3, footnotes on page 16
AddressRO/RWDescription
0541 0542RWEnhanced density: Curven (1x6) coefficient at concentrationy
(at reference temperature)
0543 0544RWEnhanced density: Curven (1x6) concentrationy value (y-axis)√12√
0545 0546RWEnhanced density: Curven reference temperature√12√
0547 0548RWEnhanced density: Curven specific gravity water reference
temperature
0549 0550RWEnhanced density: Curven specific gravity water reference density√12√
0551 0552RWEnhanced density: Curven curve trim: slope√12√
0553 0554RWEnhanced density: Curven curve trim: offset√12√
0555 0556RWEnhanced density: Curven extrapolation alarm limit: %√12√
0571 0572RWEnhanced density: Curven curve fit expected accuracy√12√
0611 0612RWDiscrete event x setpoint A (For x, see register 0609)√√10√10√10AIC10√
0613 0614RWDiscrete event x setpoint B (For x, see register 0609)√√
0629 0630ROFingerprint data for process/transmitter variable x, instantaneous
(valid only for “current” data set) (for x, see register 0626)
0631 0632ROFingerprint data for process/transmitter variable, average (1-minute
RFT9739
MVD DC
Modeo 1500
Model 1700
Model 2500
12√12
√12√
12√12
12√12
12√12
√12√
12√12
12√12
12√12
12√12
12√12
10√10√10
AIC10√
√√√√√√
√√√√√√
Model 2700
Series 3000
rolling) (for x, see register 0626)
0633 0634ROFingerprint data for process/transmitter variable, standard
0635 0636ROFingerprint data for process/transmitter variable, maximum (since
deviation (1-minute rolling) (for x, see register 0626)
last statistics reset) (for x, see register 0626)
0637 0638ROFingerprint data for process/transmitter variable, minimum (since
√√√√√√
√√√√√√
√√√√√√
last statistics reset) (for x, see register 0626)
0687 0688RWSlot 0 value register pair for mapped address slots (Slot Type 1)√√√√√√
0689 0690RWSlot 1 value register pair for mapped address slots (Slot Type 1)√√√√√√
0691 0692RWSlot 2 value register pair for mapped address slots (Slot Type 1)√√√√√√
0693 0694RWSlot 3 value register pair for mapped address slots (Slot Type 1)√√√√√√
0695 0696RWSlot 4 value register pair for mapped address slots (Slot Type 1)√√√√√√
0697 0698RWSlot 5 value register pair for mapped address slots (Slot Type 1)√√√√√√
0699 0700RWSlot 6 value register pair for mapped address slots (Slot Type 1)√√√√√√
0701 0702RWSlot 7 value register pair for mapped address slots (Slot Type 1)√√√√√√
0703 0704RWSlot 8 value register pair for mapped address slots (Slot Type 1)√√√√√√
0705 0706RWSlot 9 value register pair for mapped address slots (Slot Type 1)√√√√√√
0707 0708RWSlot 10 value register pair for mapped address slots (Slot Type 1)√√√√√√
0709 0710RWSlot 11 value register pair for mapped address slots (Slot Type 1)√√√√√√
0711 0712RWSlot 12 value register pair for mapped address slots (Slot Type 1)√√√√√√
0713 0714RWSlot 13 value register pair for mapped address slots (Slot Type 1)√√√√√√
0715 0716RWSlot 14 value register pair for mapped address slots (Slot Type 1)√√√√√√
0717 0718RWSlot 15 value register pair for mapped address slots (Slot Type 1)√√√√√√
0719 0720RWSlot 16 value register pair for mapped address slots (Slot Type 1)√√√√√√
0721 0722RWSlot 17 value register pair for mapped address slots (Slot Type 1)√√√√√√
0723 0724RWSlot 18 value register pair for mapped address slots (Slot Type 1)√√√√√√
0725 0726RWSlot 19 value register pair for mapped address slots (Slot Type 1)√√√√√√
0727 0728RWSlot 20 value register pair for mapped address slots (Slot Type 1)√√√√√√
0729 0730RWSlot 21 value register pair for mapped address slots (Slot Type 1)√√√√√√
0731 0732RWSlot 22 value register pair for mapped address slots (Slot Type 1)√√√√√√
0733 0734RWSlot 23 value register pair for mapped address slots (Slot Type 1)√√√√√√
0735 0736RWSlot 24 value register pair for mapped address slots (Slot Type 1)√√√√√√
0737 0738RWSlot 25 value register pair for mapped address slots (Slot Type 1)√√√√√√
0739 0740RWSlot 26 value register pair for mapped address slots (Slot Type 1)√√√√√√
0741 0742RWSlot 27 value register pair for mapped address slots (Slot Type 1)√√√√√√
0743 0744RWSlot 28 value register pair for mapped address slots (Slot Type 1)√√√√√√
0745 0746RWSlot 29 value register pair for mapped address slots (Slot Type 1)√√√√√√
0747 0748RWSlot 30 value register pair for mapped address slots (Slot Type 1)√√√√√√
0749 0750RWSlot 31 value register pair for mapped address slots (Slot Type 1)√√√√√√
Modbus Map Using the Modbus Map
Modbus Mapping Assignments for Micro Motion Transmitters13