Micro Motion Manual: Micro Motion 1600 Ethernet Transmitters Manuals & Guides

Installation Manual
00825-0100-1600, Rev AB
March 2022
Micro Motion™ 1600 Ethernet Transmitters
Ethernet Installations
Safety messages
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are available: the EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions. In addition the IECEx Installation Instructions for installations outside of the European Union and the CSA Installation Instructions for installations in North America are available on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com. For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. and Ireland 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 70 413
Mexico +52 55 5809 5010 France +33 (0) 800 917
Argentina +54 11 4809 2700 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy +39 8008 77334 China +86 21 2892 9000
Chile +56 2 2928 4800 Central & Eastern +41 (0) 41 7686
Peru +51 15190130 Russia/CIS +7 495 995 9559 South Korea +82 2 3438 4600
Europe and Middle East Asia Pacific
New Zealand 099 128 804
6666
India 800 440 1468
901
Japan +81 3 5769 6803
111
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
2
Installation Manual Contents
00825-0100-1600 March 2022

Contents

Chapter 1 Before you begin........................................................................................................5
1.1 About this document...................................................................................................................5
1.2 Hazard messages.........................................................................................................................5
1.3 Related documentation............................................................................................................... 6
Chapter 2 Planning.................................................................................................................... 7
2.1 Installation checklist.................................................................................................................... 7
2.2 Additional considerations for retrofitting existing installations.................................................... 8
2.3 Power requirements.................................................................................................................... 9
2.4 1600 transmitters in Ethernet networks.....................................................................................10
Chapter 3 Mounting and sensor wiring.................................................................................... 13
3.1 Mounting and sensor wiring for integral-mount transmitters.....................................................13
3.2 Ground the meter components................................................................................................. 13
3.3 Rotate the transmitter on the sensor (optional)......................................................................... 15
3.4 Rotate the transmitter display................................................................................................... 15
Chapter 4 Wiring the channels................................................................................................. 17
4.1 Available channels..................................................................................................................... 17
4.2 Wire the I/O channel.................................................................................................................. 17
4.3 Wire the Ethernet channels........................................................................................................23
Chapter 5 Power supply wiring................................................................................................ 25
5.1 Wiring the VDC power supply.................................................................................................... 25
5.2 Wiring the Power over Ethernet (PoE) power............................................................................. 26
5.3 Wire the power supply using an M12-terminated cable (optional)............................................. 27
Chapter 6 Set up the printer..................................................................................................... 29
6.1 Set up the printer by changing the printer default IP address..................................................... 29
6.2 Set up the printer using the printer default IP address................................................................31
6.3 Reset the interface settings....................................................................................................... 32
6.4 Function Check Failed................................................................................................................ 33
Chapter 7 Power up the transmitter.........................................................................................35
Chapter 8 Guided setup............................................................................................................37
Chapter 9 Components of the transmitter display.................................................................... 39
9.1 Access and use the display menus..............................................................................................40
Chapter 10 Available service port connection............................................................................. 45
Appendix A Wire the 1600 to the 3100 relays..............................................................................47
Installation Manual 3
Contents Installation Manual
March 2022 00825-0100-1600
4 Micro Motion 1600 Ethernet Transmitters
Installation Manual Before you begin
00825-0100-1600 March 2022

1 Before you begin

1.1 About this document

This manual provides information on planning, mounting, wiring, and initial setup of the 1600 Ethernet transmitter. For information on full configuration, maintenance, troubleshooting, or service of the transmitter, see the configuration and use manual.
The information in this document assumes that users understand basic transmitter and sensor installation, configuration, and maintenance concepts and procedures.

1.2 Hazard messages

This document uses the following criteria for hazard messages based on ANSI standards Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access to protect users' assets. This is true for all systems used within the facility.
Installation Manual 5
Before you begin Installation Manual
March 2022 00825-0100-1600

1.3 Related documentation

You can find all product documentation on the product documentation DVD shipped with the product or at www.emerson.com.
See any of the following documents for more information:
Micro Motion 1600 Product Data Sheet
Micro Motion 1600 with Ethernet Transmitters: Configuration and Use Manual
Micro Motion 1600 Transmitters Ethernet Rockwell RSLogix Integration Guide
Micro Motion Ethernet PROFINET Siemens Integration Guide
Sensor installation manual
6 Micro Motion 1600 Ethernet Transmitters
Installation Manual Planning
00825-0100-1600 March 2022

2 Planning

2.1 Installation checklist

If possible, install the transmitter in a location that will prevent direct exposure to
sunlight. The environmental limits for the transmitter may be further restricted by hazardous area approvals.
If you plan to mount the transmitter in a hazardous area:
WARNING
Verify that the transmitter has the appropriate hazardous area approval. Each
transmitter has a hazardous area approval tag attached to the transmitter housing.
Ensure that any cable used between the transmitter and the sensor meets the
hazardous area requirements.
For ATEX/IECEx installations, strictly adhere to the safety instructions
documented in the ATEX/IECEx approvals documentation available on the product documentation DVD shipped with the product or at www.emerson.com.
Verify that you have the appropriate cable and required cable installation parts for your
installation. For wiring between the transmitter and sensor, verify the maximum cable length does not exceed 60 ft (18 m).
Ensure that you use the following cables for the different connections:
A twisted-pair instrument cable for the Channel B I/O connectionA suitable shielded or unshielded Cat5e or a higher-rated instrumentation cable for
the Ethernet connections to connect the meter
Note
If the transmitter is powered by the PoE connection, use shielded Cat5e cables to meet the requirements of NAMUR NE-21.
Note
The instrumentation cable should have an overall screen to cover all cores. Where permissible, connect the overall screen to earth at the host end (360° bonded).
(1)
You can mount the transmitter in any orientation as long as the conduit openings or
transmitter display do not point upward. Installing the transmitter with the conduit openings or transmitter display facing
upward risks condensation moisture entering the transmitter housing, which could damage the transmitter.
Following are examples of possible orientations for the transmitter.
Connections must meet the EC Directive for Electromagnetic Compatibility (EMC).
(1)
Installation Manual 7
Planning Installation Manual
March 2022 00825-0100-1600
Preferred orientation Alternate orientations
Mount the meter in a location and orientation that satisfies the following conditions:
Allows sufficient clearance to open the transmitter housing cover. Install with 8 in
(203 mm) to 10 in (254 mm) clearance at the wiring access points.
Provides clear access for installing cabling to the transmitter.Provides clear access to all wiring terminals for troubleshooting.

2.2 Additional considerations for retrofitting existing installations

The transmitter installation may require 3 in (76 mm) to 6 in (152 mm) of additional
wiring for the input/output and power connections. This length would be in addition to the currently installed wiring. Confirm you have the additional wiring necessary for the new installation.
Before removing the existing transmitter, be sure to record the configuration data for
the currently installed transmitter. At initial startup of the newly installed transmitter, you will be prompted to configure the meter via a guided setup.
Record the following information (if applicable):
Variable
Tag
Mass flow units
Volume flow units
Density units
Temperature units
Channel configuration
mA Output (if licensed) Power (Internal or External):
Setting
Source:
Scaling (LRV, URV):
Fault Action:
8 Micro Motion 1600 Ethernet Transmitters
Installation Manual
Planning
00825-0100-1600 March 2022
Variable Setting
Frequency Output (if licensed) Power (Internal or External):
Source:
Scaling (Frequency Factor or Flow Rate Factor):
Fault Action:
Fault Frequency:
Discrete Output (if licensed) Power (Internal or External):
Source:
Scaling:
Fault Action:
Calibration parameters (for 9-wire installations only)
Flow calibration factor FCF (Flow Cal or Flow Calibration Factor):
Density calibration factors D1:
D2:
K1:
K2:
TC:
FD:

2.3 Power requirements

The 1600 supports DC power or Power Over Ethernet (POE) through the Channel A Ethernet RJ-45 port.
DC power
Power range is 18-30 VDC
Typical power is 3.5 watts
Maximum power is 8 watts
Polarity sensitive
POE power
Power range is 44-57 VDC
Power Delivery (PD) classification is 3
Cable sizing formula
M = 18V + (R x L x 0.5A)
M: minimum supply voltage
R: cable resistance (in Ω/ft)
Installation Manual 9
Planning Installation Manual
March 2022 00825-0100-1600
L: cable length (in ft)
Typical power cable resistance at 68 °F (20.0 °C)
Wire gauge Resistance
14 AWG 0.0050 Ω/ft
16 AWG 0.0080 Ω/ft
18 AWG 0.0128 Ω/ft
20 AWG 0.0204 Ω/ft
2.5 mm
1.5 mm
1.0 mm
0.75 mm
0.50 mm
2
2
2
2
2
0.0136 Ω/m
0.0228 Ω/m
0.0340 Ω/m
0.0460 Ω/m
0.0680 Ω/m

2.4 1600 transmitters in Ethernet networks

Install the 1600 Ethernet transmitter in a star network using an industrial-rated shielded Ethernet cable.
Make sure that each cable is no longer than 328 ft (100 m).
Connect the 1600 Ethernet transmitter to the host system via a LAN (Local Area
Network) and not a WAN (Wide Area Network).
Follow all network security best practices.
10 Micro Motion 1600 Ethernet Transmitters
Installation Manual Planning
00825-0100-1600 March 2022

2.4.1 Star topology

1600 Ethernet transmitters are installed in a star network.
Figure 2-1: 1600 star network
A. Programmable Logic Controller (PLC)
B. 1600 with Ethernet output
C. External Ethernet switch
Installation Manual 11
Planning Installation Manual
March 2022 00825-0100-1600
12 Micro Motion 1600 Ethernet Transmitters
Installation Manual Mounting and sensor wiring
00825-0100-1600 March 2022

3 Mounting and sensor wiring

3.1 Mounting and sensor wiring for integral­mount transmitters
There are no separate mounting requirements for integral transmitters, and no need to connect wiring between the transmitter and the sensor.

3.2 Ground the meter components

Prerequisites
NOTICE
Improper grounding could cause inaccurate measurements or meter failure.
WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion causing death or serious injury.
Note
For hazardous area installations in Europe, refer to standard EN 60079-14 or national standards.
If national standards are not in effect, adhere to the following guidelines for grounding:
Use copper wire, 14 AWG (2.08 mm2) or larger wire size.
Keep all ground leads as short as possible, less than 1 Ω impedance.
Connect ground leads directly to earth, or follow plant standards.
Procedure
1. Ground the Coriolis sensor according to the instructions in the sensor installation manual for your Coriolis sensor.
2. Ground the transmitter according to applicable local standards, using the transmitter’s internal or external ground screw.
The internal ground screw is located inside the power wiring compartment.
Installation Manual 13
Mounting and sensor wiring Installation Manual
March 2022 00825-0100-1600
Figure 3-1: Internal ground screw
The earth ground terminal is located inside the power wiring compartment.
The external ground screw is located on the outside of the transmitter housing
below the transmitter tag.
Figure 3-2: External ground screw
14 Micro Motion 1600 Ethernet Transmitters
Installation Manual Mounting and sensor wiring
00825-0100-1600 March 2022

3.3 Rotate the transmitter on the sensor (optional)

In integral installations, you can rotate the transmitter on the sensor up to 360º in 45º increments.
Procedure
1. Using a 4 mm hex key, loosen and remove the clamp securing the transmitter head in place.
Figure 3-3: Removal of the sensor clamp
2. Gently lift the transmitter straight up, and rotate the transmitter to the desired position.
You can rotate the transmitter to any of the eight positions, but a stop exists that will not allow a full 360° rotation.
3. Gently lower the transmitter onto the base, confirming that the transmitter is in a locked position.
4. Replace the clamp in its original position and tighten the cap screw. Torque to 29 in lbf (3.28 N m) to 31 in lbf (3.50 N m).

3.4 Rotate the transmitter display

Configure the software to rotate the transmitter display 0°, 90°, 180°, or 270°. You cannot physically rotate the display.
Procedure
1. Choose Menu Configuration Display Settings Rotation.
2. Select the appropriate direction.
Installation Manual 15
Loading...
+ 33 hidden pages