Micro Motion Manual: Marine Bunker Transfer Package | Micro Motion Manuals & Guides

Application Manual
MMI-20017681, Rev AD
May 2014
Micro Motion® Marine Bunker Transfer Package
Certified Marine Bunker Measurement Solution

Micro Motion customer service

Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America Europe and Middle East Asia Pacific
United States 800-522-6277 U.K. 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 318 495 555 New Zealand 099 128 804
Mexico +41 (0) 41 7686 111 France 0800 917 901 India 800 440 1468
Argentina +54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy 8008 77334 China +86 21 2892 9000
Venezuela +58 26 1731 3446 Central & Eastern +41 (0) 41 7686 111 Japan +81 3 5769 6803
Russia/CIS +7 495 981 9811 South Korea +82 2 3438 4600
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudia Arabia 800 844 9564
UAE 800 0444 0684

Contents

Contents
Chapter 1 Orientation and planning ............................................................................................... 1
1.1 About this application manual ..................................................................................................... 1
1.2 Overview of the Micro Motion Certified Marine Bunker Measurement Solution ............................1
1.3 System types and requirements for the Marine Bunker Transfer Package .....................................5
1.4 Additional documentation ...........................................................................................................9
Chapter 2 Install the Series 3000 transmitter with the Marine Bunker Transfer Package ............... 11
2.1 System options and installation instructions ..............................................................................11
2.2 Install the Basic system .............................................................................................................. 11
2.3 Install the Basic/MID system ...................................................................................................... 15
2.4 Install the Profile system ............................................................................................................ 18
2.5 Install the Profile/MID system .................................................................................................... 23
2.6 Install ferrite beads in transmitter wiring (if required) ................................................................ 28
Chapter 3 Start up the system ...................................................................................................... 31
3.1 Power up the system ..................................................................................................................31
3.2 Perform optional startup tasks ...................................................................................................32
Chapter 4 Configure the system using the transmitter display ......................................................33
4.1 Configure auxiliary devices ........................................................................................................ 33
4.2 Configure basic flowmeter parameters ......................................................................................34
4.3 Configure bunker ticket options using the transmitter display ...................................................38
4.4 Configure communications ....................................................................................................... 41
4.5 Secure and seal the transmitter ................................................................................................. 44
Chapter 5 Operate the system from the transmitter display ......................................................... 47
5.1 Transfer a bunker and print a ticket ............................................................................................47
5.2 Transfer a bunker, collect profile data, and print a ticket and/or a profile report .........................50
5.3 Marine Bunkering dashboard during bunker transfer ................................................................. 53
5.4 Process variables during a bunker transfer ................................................................................. 54
5.5 Process noise due to vibration ....................................................................................................55
5.6 Contents of bunker ticket for Basic and Profile systems ..............................................................55
5.7 Contents of bunker ticket for Basic/MID and Profile/MID systems .............................................. 61
5.8 Retrieve and reprint bunker tickets using the transmitter display ...............................................68
Chapter 6 Use ProLink II with the Marine Bunkering Transfer Package .......................................... 69
6.1 Configure bunker ticket options using ProLink II ........................................................................69
6.2 Transfer a bunker using ProLink II ...............................................................................................72
6.3 Print or reprint a bunker ticket using ProLink II ...........................................................................74
6.4 View bunker transfer history ......................................................................................................75
6.5 Contents of profile report .......................................................................................................... 76
6.6 Print or export bunker transfer data using ProLink II ...................................................................80
6.7 Maintain bunker transfer history ................................................................................................80
Appendices and reference
Appendix A Integrated wiring diagrams ..........................................................................................83
A.1 Integrated wiring diagrams for Basic systems ............................................................................ 83
A.2 Integrated wiring diagrams for Basic/MID systems .....................................................................88
Application Manual i
Contents
A.3 Integrated wiring diagrams for Profile systems .......................................................................... 93
A.4 Integrated wiring diagrams for Profile/MID systems ...................................................................98
Appendix B Printer setup .............................................................................................................. 103
B.1 Communications settings for the ticket printer ........................................................................103
Index ................................................................................................................................................105
ii Micro Motion® Marine Bunker Transfer Package
1 Orientation and planning
Topics covered in this chapter:

About this application manual

Overview of the Micro Motion Certified Marine Bunker Measurement Solution

System types and requirements for the Marine Bunker Transfer Package
Additional documentation
1.1 About this application manual
This application manual provides information required to install and operate the Series 3000 transmitter with the Marine Bunker Transfer Package.
This application manual is designed for use with the following manual: Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual .

Orientation and planning

This application manual assumes that the transmitter display is used as the primary configuration and operation method. However, ProLink II can be used for most configuration and operation tasks. ProLink II also provides additional reporting and history features. Use of ProLink II is documented in Chapter 6.
Important
Use this application manual as your main guide for installation, configuration, and operation. You will be referred to other documentation for specific tasks and information.
1.2 Overview of the Micro Motion Certified Marine Bunker Measurement Solution
The Micro Motion Certified Marine Bunker Measurement Solution is a system that provides a complete solution for the measurement of marine fuel delivery. The system monitors aeration (entrained gas or entrained air), and supplies a bunker ticket with time and date, total amount transferred, and other relevant data.
The Certified Marine Bunker Measurement Solution includes an approved sensor, a Series 3000 transmitter, the Marine Bunker Transfer Package application running on the transmitter, the appropriate components from the Marine Bunker Instruments offering, and Micro Motion field services.
Application Manual 1
Orientation and planning

1.2.1 Marine Bunker Transfer Package

The Marine Bunker Transfer Package is a software application installed on a Series 3000 transmitter. The Marine Bunker Transfer Package manages the specialized measurement, monitoring, and ticket printing functions of the Certified Marine Bunker Measurement Solution. For Profile and Profile/MID systems, the Marine Bunker Transfer Package also handles communication with ProLink II.
Measurement
The Marine Bunker Transfer Package provides flow measurement data that complies with OIML R117-1 and MID 2004/22/EC Annex MI-005. If the appropriate security hardware is installed, the system has been accredited by a certified technician, and OIML/MID­approved procedures are followed, the bunker ticket can be used as a legal (Weights & Measures) document.
OIML R117-1 compliance
The Marine Bunker Transfer Package is designed to comply with measurement and operational requirements established by OIML. After the initial startup and certification, OIML R117-1 compliance includes four factors, or checks. For bunker transfer measurement data to meet OIML R117-1 requirements, the bunker transfer must pass all four checks.
The four checks are as follows:
MMQ check: The size of the bunker transfer is above the threshold defined by
Minimum Measured Quantity (MMQ). MMQ is specified during system certification.
Max Aeration check: The potential measurement error due to aeration (entrained
gas or entrained air), in combination with other sources of measurement error, is within MID limits as defined in MID 2004/22/EC Annex MI-005. The Aeration Limit diagnostic is used to monitor this factor.
Power check: Power was continuous during the transfer (no power interrupt).
Alarm check: No “bunker-critical” alarms have occurred since the last time a bunker
ticket was printed.
If the bunker transfer fails one or more of these checks, the bunker transfer measurement data does not meet OIML R117-1 requirements and the ticket will show Overall OIML R117-1: Fail.
Note
Aeration Limit is always calculated and the four checks are always applied, whether or not an OIML/ MID-compliant system was purchased and installed. If the system is not OIML/MID-compliant, there is no system performance traceability regardless of overall bunker pass/fail results.
Minimum Measured Quantity (MMQ)
Minimum Measured Quantity (MMQ) defines the minimum quantity of fuel in a bunker transfer that is necessary to meet OIML/MID requirements.
2 Micro Motion® Marine Bunker Transfer Package
Orientation and planning
MMQ is used to ensure that the bunker is sized appropriately for the sensor, and also to ensure that various factors related to starting and stopping flow do not have a significant effect on measurement accuracy. During initial system configuration, the service technician calculates and configures a site-specific value for MMQ. This value is typically not changed unless the piping is changed.
Tip
If you need to change the value of MMQ, contact Micro Motion customer service.
If the mass total of a bunker transfer meets or exceeds MMQ, the bunker transfer passes the MMQ check.
Aeration and Aeration Limit
Aeration refers to entrained gas or entrained air in the process fluid. Aeration Limit is a real­time diagnostic that monitors the potential measurement error due to aeration and other factors, and compares the real-time value to the maximum allowable measurement error as defined by MID 2004/22/EC Annex MI-005. Aeration Limit is expressed as a percentage of the MID limit. If the value of Aeration Limit at the end of the bunker transfer is below 100%, the bunker measurement passes the Max Aeration check.
Aeration Limit is calculated continuously. During a bunker transfer, Aeration Limit can increase, decrease, or even exceed 100%. The current value of Aeration Limit is reported as follows:
When the transfer total reaches 20% of Minimum Measured Quantity (MMQ), the
display reports:
Medium Aeration Limit: <On> or <Off> High Aeration Limit: <On> or <Off>
The thresholds for medium and high aeration are determined by the HI PV values assigned to Discrete Event 1 and Discrete Event 2. Default settings are 20 and 75 (i.e., 20% of the maximum allowable aeration and 75% of the maximum allowable aeration).
When the transfer total reaches 100% of MMQ, the display reports one of the
following:
- Aeration Limit Pass (xxx%)
- Aeration Limit Fail (xxx%)
where xxx is the current value of Aeration Limit.
The display is updated continuously, allowing the operator to take corrective action as required.
Bunker-critical alarms
If a bunker-critical alarm occurs during a bunker transfer, the transfer fails the Alarm check and the measurement cannot be used to meet OIML/MID requirements. Not all alarms are bunker-critical.
Application Manual 3
Orientation and planning
Bunker-critical alarms and descriptionsTable 1-1:
Alarm code Description
A001 EEPROM Error (Core Processor)
A002 RAM Error (Core Processor)
A003 No Sensor Response
A004 Temperature Overrange
A005 Mass Flow Rate Overrange
A006 Characterization Required
A008 Density Overrange
A009 Transmitter Initializing/Warming Up
A014 Transmitter Failure
A016 Sensor RTD Failure
A017 T-Series RTD Failure
A018 EEPROM Error (Transmitter)
A019 RAM Error (Transmitter)
A020 No Flow Cal Value
A021 Incorrect Sensor Type (K1)
A022 Configuration Database Corrupt (Core Processor)
A023 Internal Totals Corrupt (Core Processor)
A024 Program Corrupt (Core Processor)
A025 Boot Sector Fault (Core Processor)
A026 Sensor/Transmitter Communications Failure
A027 Security Breach
A028 Core Processor Write Failure
A031 Low Power
A032 Meter Verification in Progress: Outputs to Fault
A033 Insufficient Right/Left Pickoff Signal
A103 Data Loss Possible (Totals and Inventories)
A107 Power Reset Occurred
A115 No External Input or Polled Data
A129 Internal Error (Display)
A133 Integrity Breach
A134 Memory Error (Display)
A135 Transmitter/Display Communications Error
4 Micro Motion® Marine Bunker Transfer Package
Orientation and planning

1.2.2 Location

The Certified Marine Bunker Measurement Solution can be installed on a fuel barge or a vessel, or at a terminal.

1.3 System types and requirements for the Marine Bunker Transfer Package

The Marine Bunker Transfer Package can be set up in four different system types. Requirements depend on the type chosen during purchase.
Marine Bunker Transfer Package system typesTable 1-2:
System type Description Requirements list
Basic system Measure the bunker transfer and print bunker tickets only. The flow measure-
ment and bunker tickets are not OIML/MID-approved.
Basic/MID system Measure the bunker transfer and print bunker tickets only. The flow measure-
ment and bunker tickets are OIML/MID-approved.
Profile system Measure the bunker transfer and print bunker tickets and profile reports. The
flow measurement and bunker tickets are not OIML/MID-approved. The pro­file report is not OIML/MID-approved.
Profile/MID system Measure the bunker transfer and print bunker tickets and profile reports. The
flow measurement and bunker tickets are OIML/MID-approved. The profile re­port is not OIML/MID-approved.
See Table 1-3
See Table 1-4
See Table 1-5
See Table 1-6
System requirements: Basic systemTable 1-3:
Requirement Component Notes
Platform Model 3500 or Model 3700 transmit-
ter:
3500***3*****(F or H)**
3700***3****(F or H)**
Ticket printing Non–MID-Approved Printer Option
(Marine Bunker Instruments)
Configuration tool Local display
ProLink II v2.94 or higher (optional) (Micro Motion Part PLK****)
Operator interface Local display
ProLink II v2.94 or higher (optional) (Micro Motion Part PLK****)
(1)
Not available with the Model 3300 or Model 3350 controller.
For marine approvals, Model 3700 re­quired.
Includes:
Standard ticket printer
RS-485 to RS-232 signal converter
Application Manual 5
Orientation and planning
System requirements: Basic system (continued)Table 1-3:
Requirement Component Notes
Additional devices (Marine Bunker In­struments)
Micro Motion field services Site survey
(1) Not required if you do not need to print bunker tickets.
Pressure instrument Included automatically with order.
Temperature instrument Included automatically with order.
Used only to correct volume measure­ments to reference temperature, and not required for MID approval.
Level switches One or two, depending on sensor ori-
entation. Included automatically with order.
Check valve Included automatically with order if
Vessel option is selected.
Startup services
System requirements: Basic/MID systemTable 1-4:
Requirement Component Notes
Platform Model 3500 or Model 3700 transmit-
ter:
3500***3*****(F or H)**
3700***3****(F or H)**
Ticket printing MID-Approved Printer Option (Marine
Bunker Instruments)
Configuration tool Local display
ProLink II v2.94 or higher (optional) (Micro Motion Part PLK****)
Operator interface Local display
ProLink II v2.94 or higher (optional) (Micro Motion Part PLK****)
MID calibration for sensor MID Calibration order option (BB ap-
Additional devices (Marine Bunker In­struments)
Pressure instrument Included automatically with order.
Temperature instrument Included automatically with order.
Level switches One or two, depending on sensor ori-
Not available with the Model 3300 or Model 3350 controller.
For marine approvals, Model 3700 re­quired.
Includes:
MID-approved ticket printer
MID-approved RS-485 to RS-232
signal converter
pended to sensor model code).
Used only to correct volume measure­ments to reference temperature, and not required for MID approval.
entation. Included automatically with order.
6 Micro Motion® Marine Bunker Transfer Package
Orientation and planning
System requirements: Basic/MID system (continued)Table 1-4:
Requirement Component Notes
Check valve Included automatically with order if
Vessel option is selected.
Micro Motion field services MID-specific site survey
MID-specific startup services (in-
clude system check and sealing)
System requirements: Profile systemTable 1-5:
Requirement Component Notes
Platform Model 3500 or Model 3700 transmit-
ter:
3500***3*****(F or H)**
3700***3****(F or H)**
Printing Profile Printing Option (Marine Bunker
Instruments)
Non–MID-Approved Printer Option (Marine Bunker Instruments)
(1)
PC (customer-supplied)
ProLink II v2.94 or higher (Micro Motion Part PLK****)
RS-485 connection to relay (converter included)
System printer (customer-supplied)
Configuration tool Local display
ProLink II v2.94 or higher (Micro Motion Part PLK****)
Operator interface Local display
ProLink II v2.94 or higher (Micro Motion Part PLK****)
Additional devices (Marine Bunker In­struments)
Pressure instrument Included automatically with order.
Temperature instrument Included automatically with order.
Level switches One or two, depending on sensor ori-
Not available with the Model 3300 or Model 3350 controller.
For marine approvals, Model 3700 re­quired.
Printer Interface Component. In­cludes:
NEMA-approved enclosure
Factory-mounted relay and relay
power supply
Includes:
Standard ticket printer
RS-485 to RS-232 signal converter
Used only to correct volume measure­ments to reference temperature, and not required for MID approval.
entation. Included automatically with order.
Application Manual 7
Orientation and planning
System requirements: Profile system (continued)Table 1-5:
Requirement Component Notes
Check valve Included automatically with order if
Vessel option is selected.
Micro Motion field services Site survey
Startup services
(1) Not required if you do not need to print bunker tickets.
System requirements: Profile/MID systemTable 1-6:
Requirement Component Notes
Platform Model 3500 or Model 3700 transmit-
ter:
3500***3*****(F or H)**
3700***3****(F or H)**
Printing Profile Printing Option (Marine Bunker
Instruments)
MID-Approved Printer Option (Marine Bunker Instruments)
PC (customer-supplied)
ProLink II v2.94 or higher (Micro Motion Part PLK****)
RS-485 connection to relay (converter included)
System printer (customer-supplied)
Configuration tool Local display
ProLink II v2.94 or higher (Micro Motion Part PLK****)
Operator interface Local display
ProLink II v2.94 or higher (Micro Motion Part PLK****)
Additional devices (Marine Bunker In­struments)
Pressure instrument Included automatically with order.
Temperature instrument Included automatically with order.
Not available with the Model 3300 or Model 3350 controller.
For marine approvals, Model 3700 re­quired.
Printer Interface Component. In­cludes:
NEMA-approved enclosure
Factory-mounted relay and relay
power supply
Includes:
MID-approved ticket printer
MID-approved RS-485 to RS-232
signal converter
Used only to correct volume measure­ments to reference temperature, and not required for MID approval.
8 Micro Motion® Marine Bunker Transfer Package
Orientation and planning
System requirements: Profile/MID system (continued)Table 1-6:
Requirement Component Notes
Level switches One or two, depending on sensor ori-
entation. Included automatically with order.
Check valve Included automatically with order if
Vessel option is selected.
MID calibration for sensor MID Calibration order option (BB ap-
pended to sensor model code).
Micro Motion field services MID-specific site survey
MID-specific startup services (in-
clude system check and sealing)

1.4 Additional documentation

Table 1-7:
Required and recommended documentation for the Certified Marine Bunker Measurement Solution
Document Use Notes
Sensor installation manual Basic installation instructions for the
sensor
Quick Reference Guide for your Series 3000 transmitter
Micro Motion Series 3000 MVD Trans­mitters and Controllers: Configuration and Use Manual
ProLink II manual General installation, connection, and
Vendor documentation for auxiliary devices
Basic installation instructions for the transmitter
Additional installation information for the transmitter
General configuration, operation, and maintenance information
operation information
General installation, configuration, and operation information
Provides information on configuring and operating the Series 3000 trans­mitter that is not specific to the Ma­rine Bunkering Transfer Package.
Provides information on installing ProLink II and connecting to the trans­mitter. Also provides general informa­tion on using the ProLink II interface.
Application Manual 9
Orientation and planning
10 Micro Motion® Marine Bunker Transfer Package

Install the Series 3000 transmitter with the Marine Bunker Transfer Package

2 Install the Series 3000 transmitter
with the Marine Bunker Transfer Package
Topics covered in this chapter:

System options and installation instructions

Install the Basic system

Install the Basic/MID system
Install the Profile system
Install the Profile/MID system
Install ferrite beads in transmitter wiring (if required)
2.1 System options and installation instructions
The Series 3000 transmitter with the Marine Bunker Transfer Package is available in four system options. Follow the installation instructions for your system.
2.2 Install the Basic system
This procedure provides installation instructions for a system that measures the bunker delivery and prints bunker tickets. The bunker tickets are not OIML/MID-approved. If you do not need to print bunker tickets, the ticket printer is not required.
Schematic of Basic systemFigure 2-1:
RS-485 to RS-232 signal converter
Ticket printer
Note
Model 3700 transmitter shown. If marine approvals are not required, the Model 3500 transmitter may also be used.
Application Manual 11
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Prerequisites
Ensure that the sensor is correctly installed and ready for wiring.
Ensure that the auxiliary devices (level switches, pressure transmitter, and temperature transmitter) are correctly installed and ready for wiring to the Series 3000 transmitter.
Have the following available:
Documentation:
- Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use
Manual
- The Quick Reference Guide for your transmitter
- Vendor documentation for all components
Cable:
- Power cable
- Standard twisted-pair shielded signal cable
Locate all components to meet the following requirements:
The maximum distance between the sensor and the core processor is 60 feet
(20 meters). In a typical installation, the core processor is mounted directly on the sensor.
The maximum distance between the core processor and the transmitter is 1000 feet
(300 meters).
The maximum length of an RS-485 connection is 3600 feet (1000 meters) at
9600 baud.
The maximum length of an RS-232 connection is 15 feet (5 meters).
The ticket printer and signal converter must be installed in a safe area.
Review power requirements for all components and ensure that you will be able to supply enough power.
Important
For marine approvals (available only with the Model 3700 transmitter, and only if the Marine Approvals option was ordered), additional requirements apply to the following:
Wiring between the sensor and the transmitter
Transmitter I/O wiring
Transmitter power wiring
See Section 2.6 and incorporate the additional steps into your installation tasks.
Important
During installation, refer to the appropriate integrated wiring diagram. See Section A.1:
For sensors mounted in a vertical pipe (Flag orientation), see page 84.
For sensors mounted in a horizontal pipe (Tubes-down orientation), see page 86.
12 Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Procedure
1. Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual and the appropriate Quick Reference Guide to perform
the following installation tasks:
a. Mount the transmitter.
b. Wire the transmitter to the sensor.
c. Wire the transmitter’s secondary mA output and frequency output (if they will be
used).
d. Wire power to the transmitter.
e. Ground the transmitter.
2. Wire the level switch (or switches) to Discrete Input 1 and to power.
When Discrete Input 1 is assigned to Start/Stop Totalizers (during configuration), it will start totalizers when there is liquid in the pipeline, and stop totalizers when there is no liquid in the pipeline.
3. (Optional) Set up an integrity detection loop and wire it to Discrete Input 2.
The integrity detection loop may be used to detect leaks, cable breakage, short circuits, and so on. Any preferred method or device can be used.
4. Set up a HART loop that connects the primary mA output to the external pressure transmitter and the external temperature transmitter.
Notes
The temperature transmitter is used only to correct volume measurements to reference
temperature. It may not be required in your installation.
The Field Communicator can be connected to this loop.
5. (Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual to wire Discrete Output 1 and Discrete Output 2 to signal devices such as lights or horns.
Tip
When the Marine Bunker Transfer Package is installed, a special default configuration is implemented for Discrete Output 1, Discrete Output 2, Discrete Event 1, and Discrete Event 2:
Discrete Event 1 is activated if Aeration Limit reaches 20% (medium aeration).
Discrete Event 2 is activated if Aeration Limit reaches 75% (high aeration).
Discrete Output 1 is assigned to Discrete Event 1.
Discrete Output 2 is assigned to Discrete Event 2.
If this default configuration is retained and Discrete Output 1 and Discrete Output 2 are wired to signal devices, the signal devices will alert the operator if Aeration Limit reaches the 20% or 75% threshold. You can change the thresholds defined for medium and high aeration by changing the HI PV values for Discrete Event 1 and Discrete Event 2.
Application Manual 13
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
6. (Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual and the appropriate Quick Reference Guide to wire Discrete Output 3 as desired.
7. Install the ticket printer.
a. Connect the printer to power according to the instructions in the vendor
documentation.
b. Set the DIP switches on the printer as shown in the following table.
DIP switch settings for Epson TM-U295 printerTable 2-1:
DIP switch Setting Printer communication parameters
1 OFF Baud: 9600
2 OFF
3 OFF
4 OFF
5 ON
6 ON
7 OFF
8 OFF
9 OFF
10 OFF
Parity: Even
Data bits: 8
Stop bits: 1
Characters per second: 32
Buffer size: 512
c. Attach the adapter to the signal converter.
An RS-485 to RS-232 signal converter and a DB9 to DB25 adapter were supplied with the system.
d. Plug the adapter into the terminal block on the printer.
e. Connect the RS-485 terminals on the signal converter to the RS-485 terminals on
the transmitter.
RS-485 connections between signal converter and transmitterTable 2-2:
Transmitter terminals
Model 3500 with
Signal converter ter-
RS-485 terminal
RS-485/A Terminal 1 12 a32 25
RS-485/B Terminal 2 11 c32 24
minals
Model 3700
screw-type or solder terminals
Model 3500 with I/O cables
14 Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package

2.3 Install the Basic/MID system

This procedure provides installation instructions for a system that measures the bunker delivery and prints bunker tickets. The bunker tickets are OIML/MID-approved.
Schematic of Basic/MID systemFigure 2-2:
RS-485 to RS-232 signal converter
MID-approved
ticket printer
Note
Model 3700 transmitter shown. If marine approvals are not required, the Model 3500 transmitter may also be used.
Prerequisites
Ensure that the sensor is correctly installed and ready for wiring.
Ensure that the auxiliary devices (level switches, pressure transmitter, and temperature transmitter) are correctly installed and ready for wiring to the Series 3000 transmitter.
Have the following available:
Documentation:
- Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use
Manual
- The Quick Reference Guide for your transmitter
- Vendor documentation for all components
Cable:
- Power cable
- Standard twisted-pair shielded signal cable
Locate all components to meet the following requirements:
The maximum distance between the sensor and the core processor is 60 feet
(20 meters). In a typical installation, the core processor is mounted directly on the sensor.
The maximum distance between the core processor and the transmitter is 1000 feet
(300 meters).
The maximum length of an RS-485 connection is 3600 feet (1000 meters) at
9600 baud.
Application Manual 15
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
The maximum length of an RS-232 connection is 15 feet (5 meters).
The ticket printer and signal converter must be installed in a safe area.
Review power requirements for all components and ensure that you will be able to supply enough power.
Important
For marine approvals (available only with the Model 3700 transmitter, and only if the Marine Approvals option was ordered), additional requirements apply to the following:
Wiring between the sensor and the transmitter
Transmitter I/O wiring
Transmitter power wiring
See Section 2.6 and incorporate the additional steps into your installation tasks.
Important
During installation, refer to the appropriate integrated wiring diagram. See Section A.2:
For sensors mounted in a vertical pipe (Flag orientation), see page 89.
For sensors mounted in a horizontal pipe (Tubes-down orientation), see page 91.
Procedure
1. Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual and the appropriate Quick Reference Guide to perform
the following installation tasks:
a. Mount the transmitter.
b. Wire the transmitter to the sensor.
c. Wire the transmitter’s secondary mA output and frequency output (if they will be
used).
d. Wire power to the transmitter.
e. Ground the transmitter.
2. Wire the level switch (or switches) to Discrete Input 1 and to power.
When Discrete Input 1 is assigned to Start/Stop Totalizers (during configuration), it will start totalizers when there is liquid in the pipeline, and stop totalizers when there is no liquid in the pipeline.
3. (Optional) Set up an integrity detection loop and wire it to Discrete Input 2.
The integrity detection loop may be used to detect leaks, cable breakage, short circuits, and so on. Any preferred method or device can be used.
4. Set up a HART loop that connects the primary mA output to the external pressure transmitter and the external temperature transmitter.
16 Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Notes
The temperature transmitter is used only to correct volume measurements to reference
temperature. It may not be required in your installation.
The Field Communicator can be connected to this loop.
5. (Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual to wire Discrete Output 1 and Discrete Output 2 to signal devices such as lights or horns.
Tip
When the Marine Bunker Transfer Package is installed, a special default configuration is implemented for Discrete Output 1, Discrete Output 2, Discrete Event 1, and Discrete Event 2:
Discrete Event 1 is activated if Aeration Limit reaches 20% (medium aeration).
Discrete Event 2 is activated if Aeration Limit reaches 75% (high aeration).
Discrete Output 1 is assigned to Discrete Event 1.
Discrete Output 2 is assigned to Discrete Event 2.
If this default configuration is retained and Discrete Output 1 and Discrete Output 2 are wired to signal devices, the signal devices will alert the operator if Aeration Limit reaches the 20% or 75% threshold. You can change the thresholds defined for medium and high aeration by changing the HI PV values for Discrete Event 1 and Discrete Event 2.
6. (Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual and the appropriate Quick Reference Guide to wire Discrete Output 3 as desired.
7. Install the ticket printer.
a. Connect the printer to power according to the instructions in the vendor
documentation.
b. Set the DIP switches on the printer as shown in the following table.
CAUTION!
The DIP switches are on the bottom of the printer, under the DIP switch cover. Power down the printer before removing the DIP switch cover.
DIP switch settings for Epson TM-T88V printerTable 2-3:
Switch bank DIP switch settings Printer communication parameters
DSW1 Switch 1-1 OFF Baud: 38400
Switch 1-2 OFF
Switch 1-3 OFF
Switch 1-4 OFF
Switch 1-5 ON
Switch 1-6 ON
Parity: Even
Data bits: 8
Stop bits: 1
Characters per second: 400
Buffer size: 1024
Application Manual 17
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
DIP switch settings for Epson TM-T88V printer (continued)Table 2-3:
Switch bank DIP switch settings Printer communication parameters
Switch 1-7 ON
Switch 1-8 ON
DSW2 Switch 2-1 OFF
Switches 2-2 through 2-8
c. Attach the adapter to the signal converter.
An RS-485 to RS-232 signal converter and a DB9 to DB25 adapter were supplied with the system.
d. Plug the adapter into the terminal block on the printer.
e. Connect the RS-485 terminals on the signal converter to the RS-485 terminals on
the transmitter as shown in the following table.
RS-485 connections between signal converter and transmitterTable 2-4:
As desired
Transmitter terminals
Model 3500 with
Signal converter ter-
RS-485 terminal
RS-485/A Terminal 1 12 a32 25
RS-485/B Terminal 2 11 c32 24
minals
Model 3700
screw-type or solder terminals

2.4 Install the Profile system

This procedure provides installation instructions for a system that measures the bunker delivery and prints bunker tickets and profile reports. The bunker tickets are not OIML/ MID-approved. The profile report is not OIML/MID-approved. If you do not need to print bunker tickets, the ticket printer is not required.
Model 3500 with I/O cables
18 Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Schematic of Profile systemFigure 2-3:
Printer Interface
Component
RS-485 to RS-232 signal converter
Ticket printer
RS-485
Relay
Power
supply for
relay
RS-485 to USB signal converter
PC with
ProLink II
Existing
connection
Default printer
Note
Model 3700 transmitter shown. If marine approvals are not required, the Model 3500 transmitter may also be used.
Prerequisites
Ensure that the sensor is correctly installed and ready for wiring.
Ensure that the auxiliary devices (level switches, pressure transmitter, and temperature transmitter) are correctly installed and ready for wiring to the Series 3000 transmitter.
Ensure that ProLink II v2.94 is installed on the PC you will use for bunkering, and that you have the appropriate ProLink II installation kit.
Have the following available:
Documentation:
- Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use
Manual
- The Quick Reference Guide for your transmitter
- Vendor documentation for all components
Cable:
- Power cable
- Standard twisted-pair shielded signal cable
Locate all components to meet the following requirements:
Application Manual 19
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
The maximum distance between the sensor and the core processor is 60 feet
(20 meters). In a typical installation, the core processor is mounted directly on the sensor.
The maximum distance between the core processor and the transmitter is 1000 feet
(300 meters).
The maximum length of an RS-485 connection is 3600 feet (1000 meters) at
9600 baud.
The maximum length of an RS-232 connection is 15 feet (5 meters).
The Printer Interface Component must be installed in a safe area.
The ticket printer and signal converter must be installed in a safe area.
The PC and system printer must be installed in a safe area.
Review power requirements for all components and ensure that you will be able to supply enough power.
Important
For marine approvals (available only with the Model 3700 transmitter, and only if the Marine Approvals option was ordered), additional requirements apply to the following:
Wiring between the sensor and the transmitter
Transmitter I/O wiring
Transmitter power wiring
See Section 2.6 and incorporate the additional steps into your installation tasks.
Important
During installation, refer to the appropriate integrated wiring diagram. See Section A.3:
For sensors mounted in a vertical pipe (Flag orientation), see page 94.
For sensors mounted in a horizontal pipe (Tubes-down orientation), see page 96.
Procedure
1. Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual and the appropriate Quick Reference Guide to perform
the following installation tasks:
a. Mount the transmitter.
b. Wire the transmitter to the sensor.
c. Wire the transmitter’s secondary mA output and frequency output (if they will be
used).
d. Wire power to the transmitter.
e. Ground the transmitter.
2. Mount the Printer Interface Component to any flat surface. See the following figure for mounting dimensions.
20 Micro Motion® Marine Bunker Transfer Package
A
B
C
D
E
F
G
H
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Mounting dimensions for Printer Interface ComponentFigure 2-4:
A. Front view, width: 7.464 in (189.58 mm) B. Front view, height: 9.360 in (237.73 mm) C. Side view, width: 6.199 in (157.45 mm) D. Mounting plate, width: 2× 0.250 in (6.35 mm) E. Back view, height: 9.625 in (244.48 mm) F. Back view, space between mounting holes: 8.875 in (225.42 mm) G. Back view, width: 4.000 in (101.60 mm) H. Back view, space between mounting holes: 5.000 in (127.00 mm)
I. Back view, size of mounting holes: 4×
0.308 in thru (7.81 mm)
3. Wire the level switch (or switches) to Discrete Input 1 and to power.
When Discrete Input 1 is assigned to Start/Stop Totalizers (during configuration), it will start totalizers when there is liquid in the pipeline, and stop totalizers when there is no liquid in the pipeline.
4. (Optional) Set up an integrity detection loop and wire it to Discrete Input 2.
The integrity detection loop may be used to detect leaks, cable breakage, short circuits, and so on. Any preferred method or device can be used.
5. Set up a HART loop that connects the primary mA output to the external pressure transmitter and the external temperature transmitter.
Notes
The temperature transmitter is used only to correct volume measurements to reference
temperature. It may not be required in your installation.
The Field Communicator can be connected to this loop.
6. (Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual to wire Discrete Output 1 and Discrete Output 2 to signal devices such as lights or horns.
Application Manual 21
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Tip
When the Marine Bunker Transfer Package is installed, a special default configuration is implemented for Discrete Output 1, Discrete Output 2, Discrete Event 1, and Discrete Event 2:
Discrete Event 1 is activated if Aeration Limit reaches 20% (medium aeration).
Discrete Event 2 is activated if Aeration Limit reaches 75% (high aeration).
Discrete Output 1 is assigned to Discrete Event 1.
Discrete Output 2 is assigned to Discrete Event 2.
If this default configuration is retained and Discrete Output 1 and Discrete Output 2 are wired to signal devices, the signal devices will alert the operator if Aeration Limit reaches the 20% or 75% threshold. You can change the thresholds defined for medium and high aeration by changing the HI PV values for Discrete Event 1 and Discrete Event 2.
7. Install the ticket printer.
a. Connect the printer to power according to the instructions in the vendor
documentation.
b. Set the DIP switches on the printer as shown in the following table.
DIP switch settings for Epson TM-U295 printerTable 2-5:
DIP switch Setting Printer communication parameters
1 OFF Baud: 9600
2 OFF
3 OFF
4 OFF
5 ON
6 ON
7 OFF
8 OFF
9 OFF
10 OFF
Parity: Even
Data bits: 8
Stop bits: 1
Characters per second: 32
Buffer size: 128
c. Attach the adapter to the signal converter.
An RS-485 to RS-232 signal converter and a DB9 to DB25 adapter were supplied with the system.
d. Plug the adapter into the terminal block on the printer.
8. Wire the Printer Interface Component.
a. Open the Printer Interface Component.
b. Wire power to the relay power supply according to the instructions in the vendor
documentation.
c. Wire the relay to Discrete Output 3 on the transmitter.
22 Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
d. Wire one set of RS-485 terminals on the relay to the RS-485 terminals on the
transmitter.
RS-485 connections between transmitter and relayTable 2-6:
Transmitter terminals
Model 3500 with screw-type or solder
RS-485 terminal Relay terminals
RS-485/A Terminal 21 12 a32 25
RS-485/B Terminal 11 11 c32 24
Model 3700
terminals
Model 3500 with I/O cables
e. Wire one set of RS-485 terminals on the relay to the RS-485 terminals on the
signal converter.
RS-485 connections between signal converter and relayTable 2-7:
RS-485 terminal Relay terminals Signal converter terminals
RS-485/A 24 Terminal 1
RS-485/B 14 Terminal 2
f. Close the Printer Interface Component.
9. Ensure that the PC is connected to the printer that you will use to print the profile report, and that this printer is defined as the default printer.

2.5 Install the Profile/MID system

This procedure provides installation instructions for a system that measures the bunker delivery and prints bunker tickets and profile reports. The bunker tickets are OIML/MID­approved. The profile reports are not OIML/MID-approved.
Application Manual 23
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Schematic of Profile/MID systemFigure 2-5:
Printer Interface
Component
RS-485 to RS-232 signal converter
MID-approved
ticket printer
RS-485
Relay
Power
supply for
relay
RS-485 to USB signal converter
PC with
ProLink II
Default printer
Note
Model 3700 transmitter shown. If marine approvals are not required, the Model 3500 transmitter may also be used.
Prerequisites
Ensure that the sensor is correctly installed and ready for wiring.
Ensure that the auxiliary devices (level switches, pressure transmitter, and temperature transmitter) are correctly installed and ready for wiring to the Series 3000 transmitter.
Existing
connection
Ensure that ProLink II v2.94 is installed on the PC you will use for bunkering, and that you have the appropriate ProLink II installation kit.
Have the following available:
Documentation:
- Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use
Manual
- The Quick Reference Guide for your transmitter
- Vendor documentation for all components
Cable:
- Power cable
- Standard twisted-pair shielded signal cable
Locate all components to meet the following requirements:
24 Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
The maximum distance between the sensor and the core processor is 60 feet
(20 meters). In a typical installation, the core processor is mounted directly on the sensor.
The maximum distance between the core processor and the transmitter is 1000 feet
(300 meters).
The maximum length of an RS-485 connection is 3600 feet (1000 meters) at
9600 baud.
The maximum length of an RS-232 connection is 15 feet (5 meters).
The Printer Interface Component must be installed in a safe area.
The ticket printer and signal converter must be installed in a safe area.
The PC and system printer must be installed in a safe area.
Review power requirements for all components and ensure that you will be able to supply enough power.
Important
For marine approvals (available only with the Model 3700 transmitter, and only if the Marine Approvals option was ordered), additional requirements apply to the following:
Wiring between the sensor and the transmitter
Transmitter I/O wiring
Transmitter power wiring
See Section 2.6 and incorporate the additional steps into your installation tasks.
Important
During installation, refer to the appropriate integrated wiring diagram. See Section A.4:
For sensors mounted in a vertical pipe (Flag orientation), see page 99.
For sensors mounted in a horizontal pipe (Tubes-down orientation), see page 101.
Procedure
1. Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual and the appropriate Quick Reference Guide to perform
the following installation tasks:
a. Mount the transmitter.
b. Wire the transmitter to the sensor.
c. Wire the transmitter’s secondary mA output and frequency output (if they will be
used).
d. Wire power to the transmitter.
e. Ground the transmitter.
2. Mount the Printer Interface Component to any flat surface. See the following figure for mounting dimensions.
Application Manual 25
A
B
C
D
E
F
G
H
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Mounting dimensions for Printer Interface ComponentFigure 2-6:
A. Front view, width: 7.464 in (189.58 mm) B. Front view, height: 9.360 in (237.73 mm) C. Side view, width: 6.199 in (157.45 mm) D. Mounting plate, width: 2× 0.250 in (6.35 mm) E. Back view, height: 9.625 in (244.48 mm) F. Back view, space between mounting holes: 8.875 in (225.42 mm) G. Back view, width: 4.000 in (101.60 mm) H. Back view, space between mounting holes: 5.000 in (127.00 mm)
I. Back view, size of mounting holes: 4×
0.308 in thru (7.81 mm)
3. Wire the level switch (or switches) to Discrete Input 1 and to power.
When Discrete Input 1 is assigned to Start/Stop Totalizers (during configuration), it will start totalizers when there is liquid in the pipeline, and stop totalizers when there is no liquid in the pipeline.
4. (Optional) Set up an integrity detection loop and wire it to Discrete Input 2.
The integrity detection loop may be used to detect leaks, cable breakage, short circuits, and so on. Any preferred method or device can be used.
5. Set up a HART loop that connects the primary mA output to the external pressure transmitter and the external temperature transmitter.
Notes
The temperature transmitter is used only to correct volume measurements to reference
temperature. It may not be required in your installation.
The Field Communicator can be connected to this loop.
6. (Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use Manual to wire Discrete Output 1 and Discrete Output 2 to signal devices such as lights or horns.
26 Micro Motion® Marine Bunker Transfer Package
Loading...
+ 84 hidden pages