B.1Communications settings for the ticket printer ........................................................................103
Index ................................................................................................................................................105
iiMicro Motion® Marine Bunker Transfer Package
1Orientation and planning
Topics covered in this chapter:
•About this application manual
•Overview of the Micro Motion Certified Marine Bunker Measurement Solution
•System types and requirements for the Marine Bunker Transfer Package
•Additional documentation
1.1About this application manual
This application manual provides information required to install and operate the
Series 3000 transmitter with the Marine Bunker Transfer Package.
This application manual is designed for use with the following manual: Micro MotionSeries 3000 MVD Transmitters and Controllers: Configuration and Use Manual .
Orientation and planning
This application manual assumes that the transmitter display is used as the primary
configuration and operation method. However, ProLink II can be used for most
configuration and operation tasks. ProLink II also provides additional reporting and history
features. Use of ProLink II is documented in Chapter 6.
Important
Use this application manual as your main guide for installation, configuration, and operation. You
will be referred to other documentation for specific tasks and information.
1.2Overview of the Micro Motion Certified Marine
Bunker Measurement Solution
The Micro Motion Certified Marine Bunker Measurement Solution is a system that provides
a complete solution for the measurement of marine fuel delivery. The system monitors
aeration (entrained gas or entrained air), and supplies a bunker ticket with time and date,
total amount transferred, and other relevant data.
The Certified Marine Bunker Measurement Solution includes an approved sensor, a
Series 3000 transmitter, the Marine Bunker Transfer Package application running on the
transmitter, the appropriate components from the Marine Bunker Instruments offering,
and Micro Motion field services.
Application Manual 1
Orientation and planning
1.2.1Marine Bunker Transfer Package
The Marine Bunker Transfer Package is a software application installed on a Series 3000
transmitter. The Marine Bunker Transfer Package manages the specialized measurement,
monitoring, and ticket printing functions of the Certified Marine Bunker Measurement
Solution. For Profile and Profile/MID systems, the Marine Bunker Transfer Package also
handles communication with ProLink II.
Measurement
The Marine Bunker Transfer Package provides flow measurement data that complies with
OIML R117-1 and MID 2004/22/EC Annex MI-005. If the appropriate security hardware is
installed, the system has been accredited by a certified technician, and OIML/MIDapproved procedures are followed, the bunker ticket can be used as a legal
(Weights & Measures) document.
OIML R117-1 compliance
The Marine Bunker Transfer Package is designed to comply with measurement and
operational requirements established by OIML. After the initial startup and certification,
OIML R117-1 compliance includes four factors, or checks. For bunker transfer
measurement data to meet OIML R117-1 requirements, the bunker transfer must pass all
four checks.
The four checks are as follows:
•MMQ check: The size of the bunker transfer is above the threshold defined by
Minimum Measured Quantity (MMQ). MMQ is specified during system certification.
•Max Aeration check: The potential measurement error due to aeration (entrained
gas or entrained air), in combination with other sources of measurement error, is
within MID limits as defined in MID 2004/22/EC Annex MI-005. The Aeration Limit
diagnostic is used to monitor this factor.
•Power check: Power was continuous during the transfer (no power interrupt).
•Alarm check: No “bunker-critical” alarms have occurred since the last time a bunker
ticket was printed.
If the bunker transfer fails one or more of these checks, the bunker transfer measurement
data does not meet OIML R117-1 requirements and the ticket will show Overall OIML R117-1:Fail.
Note
Aeration Limit is always calculated and the four checks are always applied, whether or not an OIML/
MID-compliant system was purchased and installed. If the system is not OIML/MID-compliant, there
is no system performance traceability regardless of overall bunker pass/fail results.
Minimum Measured Quantity (MMQ)
Minimum Measured Quantity (MMQ) defines the minimum quantity of fuel in a bunker
transfer that is necessary to meet OIML/MID requirements.
2Micro Motion® Marine Bunker Transfer Package
Orientation and planning
MMQ is used to ensure that the bunker is sized appropriately for the sensor, and also to
ensure that various factors related to starting and stopping flow do not have a significant
effect on measurement accuracy. During initial system configuration, the service
technician calculates and configures a site-specific value for MMQ. This value is typically
not changed unless the piping is changed.
Tip
If you need to change the value of MMQ, contact Micro Motion customer service.
If the mass total of a bunker transfer meets or exceeds MMQ, the bunker transfer passes
the MMQ check.
Aeration and Aeration Limit
Aeration refers to entrained gas or entrained air in the process fluid. Aeration Limit is a realtime diagnostic that monitors the potential measurement error due to aeration and other
factors, and compares the real-time value to the maximum allowable measurement error
as defined by MID 2004/22/EC Annex MI-005. Aeration Limit is expressed as a percentage of
the MID limit. If the value of Aeration Limit at the end of the bunker transfer is below 100%,
the bunker measurement passes the Max Aeration check.
Aeration Limit is calculated continuously. During a bunker transfer, Aeration Limit can
increase, decrease, or even exceed 100%. The current value of Aeration Limit is reported as
follows:
•When the transfer total reaches 20% of Minimum Measured Quantity (MMQ), the
display reports:
Medium Aeration Limit: <On> or <Off>
High Aeration Limit: <On> or <Off>
The thresholds for medium and high aeration are determined by the HI PV values
assigned to Discrete Event 1 and Discrete Event 2. Default settings are 20 and 75
(i.e., 20% of the maximum allowable aeration and 75% of the maximum allowable
aeration).
•When the transfer total reaches 100% of MMQ, the display reports one of the
following:
-Aeration Limit Pass (xxx%)
-Aeration Limit Fail (xxx%)
where xxx is the current value of Aeration Limit.
The display is updated continuously, allowing the operator to take corrective action as
required.
Bunker-critical alarms
If a bunker-critical alarm occurs during a bunker transfer, the transfer fails the Alarm check
and the measurement cannot be used to meet OIML/MID requirements. Not all alarms are
bunker-critical.
ProLink II v2.94 or higher
(Micro Motion Part PLK****)
RS-485 connection to relay (converter
included)
System printer (customer-supplied)
Configuration toolLocal display
ProLink II v2.94 or higher
(Micro Motion Part PLK****)
Operator interfaceLocal display
ProLink II v2.94 or higher
(Micro Motion Part PLK****)
Additional devices (Marine Bunker Instruments)
Pressure instrumentIncluded automatically with order.
Temperature instrumentIncluded automatically with order.
Not available with the Model 3300 or
Model 3350 controller.
For marine approvals, Model 3700 required.
Printer Interface Component. Includes:
• NEMA-approved enclosure
• Factory-mounted relay and relay
power supply
Includes:
• MID-approved ticket printer
• MID-approved RS-485 to RS-232
signal converter
Used only to correct volume measurements to reference temperature, and
not required for MID approval.
8Micro Motion® Marine Bunker Transfer Package
Orientation and planning
System requirements: Profile/MID system (continued)Table 1-6:
RequirementComponentNotes
Level switchesOne or two, depending on sensor ori-
entation. Included automatically with
order.
Check valveIncluded automatically with order if
Vessel option is selected.
MID calibration for sensorMID Calibration order option (BB ap-
pended to sensor model code).
Micro Motion field services• MID-specific site survey
• MID-specific startup services (in-
clude system check and sealing)
1.4Additional documentation
Table 1-7:
Required and recommended documentation for the Certified Marine Bunker Measurement
Solution
DocumentUseNotes
Sensor installation manualBasic installation instructions for the
sensor
Quick Reference Guide for your
Series 3000 transmitter
Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration
and Use Manual
ProLink II manualGeneral installation, connection, and
Vendor documentation for auxiliary
devices
Basic installation instructions for the
transmitter
Additional installation information for
the transmitter
General configuration, operation, and
maintenance information
operation information
General installation, configuration,
and operation information
Provides information on configuring
and operating the Series 3000 transmitter that is not specific to the Marine Bunkering Transfer Package.
Provides information on installing
ProLink II and connecting to the transmitter. Also provides general information on using the ProLink II interface.
Application Manual 9
Orientation and planning
10Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
2Install the Series 3000 transmitter
with the Marine Bunker Transfer
Package
Topics covered in this chapter:
•System options and installation instructions
•Install the Basic system
•Install the Basic/MID system
•Install the Profile system
•Install the Profile/MID system
•Install ferrite beads in transmitter wiring (if required)
2.1System options and installation instructions
The Series 3000 transmitter with the Marine Bunker Transfer Package is available in four
system options. Follow the installation instructions for your system.
2.2Install the Basic system
This procedure provides installation instructions for a system that measures the bunker
delivery and prints bunker tickets. The bunker tickets are not OIML/MID-approved. If you
do not need to print bunker tickets, the ticket printer is not required.
Schematic of Basic systemFigure 2-1:
RS-485 to RS-232 signal converter
Ticket printer
Note
Model 3700 transmitter shown. If marine approvals are not required, the Model 3500 transmitter may also
be used.
Application Manual 11
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Prerequisites
Ensure that the sensor is correctly installed and ready for wiring.
Ensure that the auxiliary devices (level switches, pressure transmitter, and temperature
transmitter) are correctly installed and ready for wiring to the Series 3000 transmitter.
Have the following available:
•Documentation:
-Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use
Manual
-The Quick Reference Guide for your transmitter
-Vendor documentation for all components
•Cable:
-Power cable
-Standard twisted-pair shielded signal cable
Locate all components to meet the following requirements:
•The maximum distance between the sensor and the core processor is 60 feet
(20 meters). In a typical installation, the core processor is mounted directly on the
sensor.
•The maximum distance between the core processor and the transmitter is 1000 feet
(300 meters).
•The maximum length of an RS-485 connection is 3600 feet (1000 meters) at
9600 baud.
•The maximum length of an RS-232 connection is 15 feet (5 meters).
•The ticket printer and signal converter must be installed in a safe area.
Review power requirements for all components and ensure that you will be able to supply
enough power.
Important
For marine approvals (available only with the Model 3700 transmitter, and only if the Marine
Approvals option was ordered), additional requirements apply to the following:
•Wiring between the sensor and the transmitter
•Transmitter I/O wiring
•Transmitter power wiring
See Section 2.6 and incorporate the additional steps into your installation tasks.
Important
During installation, refer to the appropriate integrated wiring diagram. See Section A.1:
•For sensors mounted in a vertical pipe (Flag orientation), see page 84.
•For sensors mounted in a horizontal pipe (Tubes-down orientation), see page 86.
12Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Procedure
1.Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers:
Configuration and Use Manual and the appropriate Quick Reference Guide to perform
the following installation tasks:
a. Mount the transmitter.
b. Wire the transmitter to the sensor.
c. Wire the transmitter’s secondary mA output and frequency output (if they will be
used).
d. Wire power to the transmitter.
e. Ground the transmitter.
2.Wire the level switch (or switches) to Discrete Input 1 and to power.
When Discrete Input 1 is assigned to Start/Stop Totalizers (during configuration), it will
start totalizers when there is liquid in the pipeline, and stop totalizers when there is
no liquid in the pipeline.
3.(Optional) Set up an integrity detection loop and wire it to Discrete Input 2.
The integrity detection loop may be used to detect leaks, cable breakage, short
circuits, and so on. Any preferred method or device can be used.
4.Set up a HART loop that connects the primary mA output to the external pressure
transmitter and the external temperature transmitter.
Notes
• The temperature transmitter is used only to correct volume measurements to reference
temperature. It may not be required in your installation.
• The Field Communicator can be connected to this loop.
5.(Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters andControllers: Configuration and Use Manual to wire Discrete Output 1 and Discrete
Output 2 to signal devices such as lights or horns.
Tip
When the Marine Bunker Transfer Package is installed, a special default configuration is
implemented for Discrete Output 1, Discrete Output 2, Discrete Event 1, and Discrete Event
2:
• Discrete Event 1 is activated if Aeration Limit reaches 20% (medium aeration).
• Discrete Event 2 is activated if Aeration Limit reaches 75% (high aeration).
• Discrete Output 1 is assigned to Discrete Event 1.
• Discrete Output 2 is assigned to Discrete Event 2.
If this default configuration is retained and Discrete Output 1 and Discrete Output 2 are wired
to signal devices, the signal devices will alert the operator if Aeration Limit reaches the 20% or
75% threshold. You can change the thresholds defined for medium and high aeration by
changing the HI PV values for Discrete Event 1 and Discrete Event 2.
Application Manual 13
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
6.(Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters andControllers: Configuration and Use Manual and the appropriate Quick Reference Guide
to wire Discrete Output 3 as desired.
7.Install the ticket printer.
a. Connect the printer to power according to the instructions in the vendor
documentation.
b. Set the DIP switches on the printer as shown in the following table.
DIP switch settings for Epson TM-U295 printerTable 2-1:
DIP switchSettingPrinter communication parameters
1OFFBaud: 9600
2OFF
3OFF
4OFF
5ON
6ON
7OFF
8OFF
9OFF
10OFF
Parity: Even
Data bits: 8
Stop bits: 1
Characters per second: 32
Buffer size: 512
c. Attach the adapter to the signal converter.
An RS-485 to RS-232 signal converter and a DB9 to DB25 adapter were supplied
with the system.
d. Plug the adapter into the terminal block on the printer.
e. Connect the RS-485 terminals on the signal converter to the RS-485 terminals on
the transmitter.
RS-485 connections between signal converter and transmitterTable 2-2:
Transmitter terminals
Model 3500 with
Signal converter ter-
RS-485 terminal
RS-485/ATerminal 112a3225
RS-485/BTerminal 211c3224
minals
Model 3700
screw-type or solder
terminals
Model 3500 with I/O
cables
14Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
2.3Install the Basic/MID system
This procedure provides installation instructions for a system that measures the bunker
delivery and prints bunker tickets. The bunker tickets are OIML/MID-approved.
Schematic of Basic/MID systemFigure 2-2:
RS-485 to RS-232 signal converter
MID-approved
ticket printer
Note
Model 3700 transmitter shown. If marine approvals are not required, the Model 3500 transmitter may also
be used.
Prerequisites
Ensure that the sensor is correctly installed and ready for wiring.
Ensure that the auxiliary devices (level switches, pressure transmitter, and temperature
transmitter) are correctly installed and ready for wiring to the Series 3000 transmitter.
Have the following available:
•Documentation:
-Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use
Manual
-The Quick Reference Guide for your transmitter
-Vendor documentation for all components
•Cable:
-Power cable
-Standard twisted-pair shielded signal cable
Locate all components to meet the following requirements:
•The maximum distance between the sensor and the core processor is 60 feet
(20 meters). In a typical installation, the core processor is mounted directly on the
sensor.
•The maximum distance between the core processor and the transmitter is 1000 feet
(300 meters).
•The maximum length of an RS-485 connection is 3600 feet (1000 meters) at
9600 baud.
Application Manual 15
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
•The maximum length of an RS-232 connection is 15 feet (5 meters).
•The ticket printer and signal converter must be installed in a safe area.
Review power requirements for all components and ensure that you will be able to supply
enough power.
Important
For marine approvals (available only with the Model 3700 transmitter, and only if the Marine
Approvals option was ordered), additional requirements apply to the following:
•Wiring between the sensor and the transmitter
•Transmitter I/O wiring
•Transmitter power wiring
See Section 2.6 and incorporate the additional steps into your installation tasks.
Important
During installation, refer to the appropriate integrated wiring diagram. See Section A.2:
•For sensors mounted in a vertical pipe (Flag orientation), see page 89.
•For sensors mounted in a horizontal pipe (Tubes-down orientation), see page 91.
Procedure
1.Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers:
Configuration and Use Manual and the appropriate Quick Reference Guide to perform
the following installation tasks:
a. Mount the transmitter.
b. Wire the transmitter to the sensor.
c. Wire the transmitter’s secondary mA output and frequency output (if they will be
used).
d. Wire power to the transmitter.
e. Ground the transmitter.
2.Wire the level switch (or switches) to Discrete Input 1 and to power.
When Discrete Input 1 is assigned to Start/Stop Totalizers (during configuration), it will
start totalizers when there is liquid in the pipeline, and stop totalizers when there is
no liquid in the pipeline.
3.(Optional) Set up an integrity detection loop and wire it to Discrete Input 2.
The integrity detection loop may be used to detect leaks, cable breakage, short
circuits, and so on. Any preferred method or device can be used.
4.Set up a HART loop that connects the primary mA output to the external pressure
transmitter and the external temperature transmitter.
16Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Notes
• The temperature transmitter is used only to correct volume measurements to reference
temperature. It may not be required in your installation.
• The Field Communicator can be connected to this loop.
5.(Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters andControllers: Configuration and Use Manual to wire Discrete Output 1 and Discrete
Output 2 to signal devices such as lights or horns.
Tip
When the Marine Bunker Transfer Package is installed, a special default configuration is
implemented for Discrete Output 1, Discrete Output 2, Discrete Event 1, and Discrete Event
2:
• Discrete Event 1 is activated if Aeration Limit reaches 20% (medium aeration).
• Discrete Event 2 is activated if Aeration Limit reaches 75% (high aeration).
• Discrete Output 1 is assigned to Discrete Event 1.
• Discrete Output 2 is assigned to Discrete Event 2.
If this default configuration is retained and Discrete Output 1 and Discrete Output 2 are wired
to signal devices, the signal devices will alert the operator if Aeration Limit reaches the 20% or
75% threshold. You can change the thresholds defined for medium and high aeration by
changing the HI PV values for Discrete Event 1 and Discrete Event 2.
6.(Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters andControllers: Configuration and Use Manual and the appropriate Quick Reference Guide
to wire Discrete Output 3 as desired.
7.Install the ticket printer.
a. Connect the printer to power according to the instructions in the vendor
documentation.
b. Set the DIP switches on the printer as shown in the following table.
CAUTION!
The DIP switches are on the bottom of the printer, under the DIP switch cover. Power
down the printer before removing the DIP switch cover.
DIP switch settings for Epson TM-T88V printerTable 2-3:
Switch bankDIP switch settingsPrinter communication parameters
DSW1Switch 1-1OFFBaud: 38400
Switch 1-2OFF
Switch 1-3OFF
Switch 1-4OFF
Switch 1-5ON
Switch 1-6ON
Parity: Even
Data bits: 8
Stop bits: 1
Characters per second: 400
Buffer size: 1024
Application Manual 17
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
DIP switch settings for Epson TM-T88V printer (continued)Table 2-3:
Switch bankDIP switch settingsPrinter communication parameters
Switch 1-7ON
Switch 1-8ON
DSW2Switch 2-1OFF
Switches 2-2
through 2-8
c. Attach the adapter to the signal converter.
An RS-485 to RS-232 signal converter and a DB9 to DB25 adapter were supplied
with the system.
d. Plug the adapter into the terminal block on the printer.
e. Connect the RS-485 terminals on the signal converter to the RS-485 terminals on
the transmitter as shown in the following table.
RS-485 connections between signal converter and transmitterTable 2-4:
As desired
Transmitter terminals
Model 3500 with
Signal converter ter-
RS-485 terminal
RS-485/ATerminal 112a3225
RS-485/BTerminal 211c3224
minals
Model 3700
screw-type or solder
terminals
2.4Install the Profile system
This procedure provides installation instructions for a system that measures the bunker
delivery and prints bunker tickets and profile reports. The bunker tickets are not OIML/
MID-approved. The profile report is not OIML/MID-approved. If you do not need to print
bunker tickets, the ticket printer is not required.
Model 3500 with I/O
cables
18Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Schematic of Profile systemFigure 2-3:
Printer Interface
Component
RS-485 to RS-232 signal converter
Ticket printer
RS-485
Relay
Power
supply for
relay
RS-485 to USB signal converter
PC with
ProLink II
Existing
connection
Default printer
Note
Model 3700 transmitter shown. If marine approvals are not required, the Model 3500 transmitter may also be used.
Prerequisites
Ensure that the sensor is correctly installed and ready for wiring.
Ensure that the auxiliary devices (level switches, pressure transmitter, and temperature
transmitter) are correctly installed and ready for wiring to the Series 3000 transmitter.
Ensure that ProLink II v2.94 is installed on the PC you will use for bunkering, and that you
have the appropriate ProLink II installation kit.
Have the following available:
•Documentation:
-Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use
Manual
-The Quick Reference Guide for your transmitter
-Vendor documentation for all components
•Cable:
-Power cable
-Standard twisted-pair shielded signal cable
Locate all components to meet the following requirements:
Application Manual 19
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
•The maximum distance between the sensor and the core processor is 60 feet
(20 meters). In a typical installation, the core processor is mounted directly on the
sensor.
•The maximum distance between the core processor and the transmitter is 1000 feet
(300 meters).
•The maximum length of an RS-485 connection is 3600 feet (1000 meters) at
9600 baud.
•The maximum length of an RS-232 connection is 15 feet (5 meters).
•The Printer Interface Component must be installed in a safe area.
•The ticket printer and signal converter must be installed in a safe area.
•The PC and system printer must be installed in a safe area.
Review power requirements for all components and ensure that you will be able to supply
enough power.
Important
For marine approvals (available only with the Model 3700 transmitter, and only if the Marine
Approvals option was ordered), additional requirements apply to the following:
•Wiring between the sensor and the transmitter
•Transmitter I/O wiring
•Transmitter power wiring
See Section 2.6 and incorporate the additional steps into your installation tasks.
Important
During installation, refer to the appropriate integrated wiring diagram. See Section A.3:
•For sensors mounted in a vertical pipe (Flag orientation), see page 94.
•For sensors mounted in a horizontal pipe (Tubes-down orientation), see page 96.
Procedure
1.Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers:
Configuration and Use Manual and the appropriate Quick Reference Guide to perform
the following installation tasks:
a. Mount the transmitter.
b. Wire the transmitter to the sensor.
c. Wire the transmitter’s secondary mA output and frequency output (if they will be
used).
d. Wire power to the transmitter.
e. Ground the transmitter.
2.Mount the Printer Interface Component to any flat surface. See the following figure
for mounting dimensions.
20Micro Motion® Marine Bunker Transfer Package
A
B
C
D
E
F
G
H
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Mounting dimensions for Printer Interface ComponentFigure 2-4:
A. Front view, width: 7.464 in (189.58 mm)
B. Front view, height: 9.360 in (237.73 mm)
C. Side view, width: 6.199 in (157.45 mm)
D. Mounting plate, width: 2× 0.250 in (6.35 mm)
E. Back view, height: 9.625 in (244.48 mm)
F. Back view, space between mounting holes: 8.875 in (225.42 mm)
G. Back view, width: 4.000 in (101.60 mm)
H. Back view, space between mounting holes: 5.000 in (127.00 mm)
∅
I. Back view, size of mounting holes: 4×
0.308 in thru (7.81 mm)
3.Wire the level switch (or switches) to Discrete Input 1 and to power.
When Discrete Input 1 is assigned to Start/Stop Totalizers (during configuration), it will
start totalizers when there is liquid in the pipeline, and stop totalizers when there is
no liquid in the pipeline.
4.(Optional) Set up an integrity detection loop and wire it to Discrete Input 2.
The integrity detection loop may be used to detect leaks, cable breakage, short
circuits, and so on. Any preferred method or device can be used.
5.Set up a HART loop that connects the primary mA output to the external pressure
transmitter and the external temperature transmitter.
Notes
• The temperature transmitter is used only to correct volume measurements to reference
temperature. It may not be required in your installation.
• The Field Communicator can be connected to this loop.
6.(Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters andControllers: Configuration and Use Manual to wire Discrete Output 1 and Discrete
Output 2 to signal devices such as lights or horns.
Application Manual 21
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Tip
When the Marine Bunker Transfer Package is installed, a special default configuration is
implemented for Discrete Output 1, Discrete Output 2, Discrete Event 1, and Discrete Event
2:
• Discrete Event 1 is activated if Aeration Limit reaches 20% (medium aeration).
• Discrete Event 2 is activated if Aeration Limit reaches 75% (high aeration).
• Discrete Output 1 is assigned to Discrete Event 1.
• Discrete Output 2 is assigned to Discrete Event 2.
If this default configuration is retained and Discrete Output 1 and Discrete Output 2 are wired
to signal devices, the signal devices will alert the operator if Aeration Limit reaches the 20% or
75% threshold. You can change the thresholds defined for medium and high aeration by
changing the HI PV values for Discrete Event 1 and Discrete Event 2.
7.Install the ticket printer.
a. Connect the printer to power according to the instructions in the vendor
documentation.
b. Set the DIP switches on the printer as shown in the following table.
DIP switch settings for Epson TM-U295 printerTable 2-5:
DIP switchSettingPrinter communication parameters
1OFFBaud: 9600
2OFF
3OFF
4OFF
5ON
6ON
7OFF
8OFF
9OFF
10OFF
Parity: Even
Data bits: 8
Stop bits: 1
Characters per second: 32
Buffer size: 128
c. Attach the adapter to the signal converter.
An RS-485 to RS-232 signal converter and a DB9 to DB25 adapter were supplied
with the system.
d. Plug the adapter into the terminal block on the printer.
8.Wire the Printer Interface Component.
a. Open the Printer Interface Component.
b. Wire power to the relay power supply according to the instructions in the vendor
documentation.
c. Wire the relay to Discrete Output 3 on the transmitter.
22Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
d. Wire one set of RS-485 terminals on the relay to the RS-485 terminals on the
transmitter.
RS-485 connections between transmitter and relayTable 2-6:
Transmitter terminals
Model 3500 with
screw-type or solder
RS-485 terminalRelay terminals
RS-485/ATerminal 2112a3225
RS-485/BTerminal 1111c3224
Model 3700
terminals
Model 3500 with I/O
cables
e. Wire one set of RS-485 terminals on the relay to the RS-485 terminals on the
signal converter.
RS-485 connections between signal converter and relayTable 2-7:
9.Ensure that the PC is connected to the printer that you will use to print the profile
report, and that this printer is defined as the default printer.
2.5Install the Profile/MID system
This procedure provides installation instructions for a system that measures the bunker
delivery and prints bunker tickets and profile reports. The bunker tickets are OIML/MIDapproved. The profile reports are not OIML/MID-approved.
Application Manual 23
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Schematic of Profile/MID systemFigure 2-5:
Printer Interface
Component
RS-485 to RS-232 signal converter
MID-approved
ticket printer
RS-485
Relay
Power
supply for
relay
RS-485 to USB signal converter
PC with
ProLink II
Default printer
Note
Model 3700 transmitter shown. If marine approvals are not required, the Model 3500 transmitter may also be used.
Prerequisites
Ensure that the sensor is correctly installed and ready for wiring.
Ensure that the auxiliary devices (level switches, pressure transmitter, and temperature
transmitter) are correctly installed and ready for wiring to the Series 3000 transmitter.
Existing
connection
Ensure that ProLink II v2.94 is installed on the PC you will use for bunkering, and that you
have the appropriate ProLink II installation kit.
Have the following available:
•Documentation:
-Micro Motion Series 3000 MVD Transmitters and Controllers: Configuration and Use
Manual
-The Quick Reference Guide for your transmitter
-Vendor documentation for all components
•Cable:
-Power cable
-Standard twisted-pair shielded signal cable
Locate all components to meet the following requirements:
24Micro Motion® Marine Bunker Transfer Package
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
•The maximum distance between the sensor and the core processor is 60 feet
(20 meters). In a typical installation, the core processor is mounted directly on the
sensor.
•The maximum distance between the core processor and the transmitter is 1000 feet
(300 meters).
•The maximum length of an RS-485 connection is 3600 feet (1000 meters) at
9600 baud.
•The maximum length of an RS-232 connection is 15 feet (5 meters).
•The Printer Interface Component must be installed in a safe area.
•The ticket printer and signal converter must be installed in a safe area.
•The PC and system printer must be installed in a safe area.
Review power requirements for all components and ensure that you will be able to supply
enough power.
Important
For marine approvals (available only with the Model 3700 transmitter, and only if the Marine
Approvals option was ordered), additional requirements apply to the following:
•Wiring between the sensor and the transmitter
•Transmitter I/O wiring
•Transmitter power wiring
See Section 2.6 and incorporate the additional steps into your installation tasks.
Important
During installation, refer to the appropriate integrated wiring diagram. See Section A.4:
•For sensors mounted in a vertical pipe (Flag orientation), see page 99.
•For sensors mounted in a horizontal pipe (Tubes-down orientation), see page 101.
Procedure
1.Follow the instructions in Micro Motion Series 3000 MVD Transmitters and Controllers:
Configuration and Use Manual and the appropriate Quick Reference Guide to perform
the following installation tasks:
a. Mount the transmitter.
b. Wire the transmitter to the sensor.
c. Wire the transmitter’s secondary mA output and frequency output (if they will be
used).
d. Wire power to the transmitter.
e. Ground the transmitter.
2.Mount the Printer Interface Component to any flat surface. See the following figure
for mounting dimensions.
Application Manual 25
A
B
C
D
E
F
G
H
Install the Series 3000 transmitter with the Marine Bunker Transfer Package
Mounting dimensions for Printer Interface ComponentFigure 2-6:
A. Front view, width: 7.464 in (189.58 mm)
B. Front view, height: 9.360 in (237.73 mm)
C. Side view, width: 6.199 in (157.45 mm)
D. Mounting plate, width: 2× 0.250 in (6.35 mm)
E. Back view, height: 9.625 in (244.48 mm)
F. Back view, space between mounting holes: 8.875 in (225.42 mm)
G. Back view, width: 4.000 in (101.60 mm)
H. Back view, space between mounting holes: 5.000 in (127.00 mm)
∅
I. Back view, size of mounting holes: 4×
0.308 in thru (7.81 mm)
3.Wire the level switch (or switches) to Discrete Input 1 and to power.
When Discrete Input 1 is assigned to Start/Stop Totalizers (during configuration), it will
start totalizers when there is liquid in the pipeline, and stop totalizers when there is
no liquid in the pipeline.
4.(Optional) Set up an integrity detection loop and wire it to Discrete Input 2.
The integrity detection loop may be used to detect leaks, cable breakage, short
circuits, and so on. Any preferred method or device can be used.
5.Set up a HART loop that connects the primary mA output to the external pressure
transmitter and the external temperature transmitter.
Notes
• The temperature transmitter is used only to correct volume measurements to reference
temperature. It may not be required in your installation.
• The Field Communicator can be connected to this loop.
6.(Optional) Follow the instructions in Micro Motion Series 3000 MVD Transmitters andControllers: Configuration and Use Manual to wire Discrete Output 1 and Discrete
Output 2 to signal devices such as lights or horns.
26Micro Motion® Marine Bunker Transfer Package
Loading...
+ 84 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.