pursues a policy of continuous development and product improvement. The specification in this document
may therefore be changed without notice. To the best of our knowledge, the information contained in this document is
accurate and Micro Motion
No part of this document may be photocopied or reproduced without prior written consent of Micro Motion
®
cannot be held responsible for any errors, omissions or other misinformation contained herein.
®
.
Cont-2
7835/45/46/47 Technical Manual Contents
IMPORTANT NOTICE
DO NOT drop the meter. Handle with care.
DO NOT use liquids incompatible with the MATERIALS OF CONSTRUCTIONS.
DO NOT position RUPTURE DISC where failure could cause personal injury.
DO NOT allow axial loading from PIPEWORK STRESSES to exceed ½ TONNE.
DO NOT operate the meter above its RATED PRESSURE.
DO NOT PRESSURE TEST above the specified TEST PRESSURE.
DO NOT expose the meter to excessive vibration (of >0.5g continuous).
ENSURE all ELECTRICAL SAFETY requirements are applied.
ENSURE meter and associated pipework are PRESSURE TESTED to 1½ times the
maximum operating pressure after installation.
ENSURE meter is not TRANSPORTED when it contains hazardous fluids. This
includes fluids that may have leaked into, and are still contained, within the case.
Returns Forms are included as Appendix J.
Cont-3
Contents 7835/45/46/47 Technical Manual
Contents
Chapter 1 Introduction
1.1 About this manual ......................................................................................................................1-1
---- Part Number Identification tables for 7835, 7845, 7846 and 7847 ..........................................1-5
Chapter 2 Mechanical Installation
2.1 General ........................................................................................................................................2-1
2.2 Planning an installation .............................................................................................................2-2
2.3 Meter mounting and pipework ..................................................................................................2-3
2.4 Pressure drop in the meter........................................................................................................ 2-6
2.5 Special considerations for hygienic applications ...................................................................2-7
Chapter 3 Advanced Unit Electrical Installation and Configuration
3.1 General ........................................................................................................................................3-1
3.2 Planning an electrical installation.............................................................................................3-2
3.3 Electrical installation in safe areas...........................................................................................3-3
3.4 Electrical installation in hazardous areas ................................................................................3-6
Chapter 4 Standard Density Unit Electrical Installation
4.1 General ........................................................................................................................................4-1
Chapter 5 Entrained Gas Electronics Electrical Installation
5.1 General ........................................................................................................................................5-1
6.1 General ........................................................................................................................................6-1
6.2 Interpretation of calibration certificate.....................................................................................6-1
This manual covers the complete range of Micro Motion® 7835/45/46/47 Liquid Density Meters and the various electronics
configurations available.
From the schematic diagram below, you can see which of the chapters in this manual refer to the part icular instrument
that you have. The remaini ng chapters can be placed at the back or removed from the manual.
Advanced Electronics
Standard ElectronicsEntrained Gas Electronics
Chapter 1
HART OPTION
2
3
6
8
Chapter 1
7835/45/46/47
LIQUID DENSITY METER
2
4
6
8
ENTRAINED GAS AMPLIFIERSTANDARD AMPLIFIERADVANCED BASEBOARD
Chapter 8: General Maintenance
Chapter 9: Using Adview
Installation & Configuration
Electrical Install ation
Electrical Install ation
Communications
Meter Mechanics
Chapter 1
2
6
8
7965 Remote Display
Chapter 1
2
3
6
7
8
Figure 1.1
Page 1-1
Introduction 7835/45/46/47 Technical Manual
1.2 Product Overview
All of the products consist of a mechanical meter and an electronics unit that is normally mounted inside the meter
electronics housing. Together, the electronics and meter provide a system for continuous on-line measurement of
liquid density and temperature.
In applications where the pipeline te mp era ture could exceed 110°C (230°F), the electronics should be mounted in a
Remote Amplifier Box (see Chapters 3 and 4 for more details.)
Electronics Enclosure
transducers
Meter
Figure 1.2
Liquid density is determi ned from the resonant freque ncy of a vibrating tube containing the liquid, and liquid temperature
is determined from a 100 Platinum Resistance Thermometer (PRT). For information on the calculation of density and
temperature, please refer to Chapter 6 and Appendix G respectively.
1.3 Meter Product Range
The meters are identical m echanically, except for the material used in the wetted parts and the flanges/couplings. A fully
welded design is utilised to ensure maximum reliability in the most severe environments. A rupture disc is embodied in the
meter end plate furthest from the amplifier housing. This disc will rupture if a pressure build-up occurs within the case, in the
unlikely event of a tube assembly leak; the operation of the rupture disc is shown in Figure 2.2.
The range of meters is ou tlined below. For furt her details, please refer to Appendices A to C.
Meter Tube material Features
7835 NI-SPAN-C® Low temperature coeffi ci en t and long te rm sta bi li ty , appr op riate fo r fisc al
7845 316L Stainless
steel
applications.
Good resistance to corrosion.
7846 Alloy C22 Very high resistance to corrosion.
7847 316L Stainless
steel
Designed for the hygiene requireme nts of th e food pro c es sing in dus t ry and has
“3A’s” authorisation. Please refer to Section 2.4 for special cleaning and
installation requirem ent s in hygi en i c appl i cat ion s .
Page 1-2
7835/45/46/47 Technical Manual Introduction
1.4 Electronics Product Range
The meters described above may be operated with any of the following electronics options. However, the electronics
options are not
the Standard electronics boards, and so only fit in the extended electronics enclosures provided with an Advanced meter.
It should be noted that the Standard Entrained Gas Electronics are NOT suitable for operation in hazardous areas,
whereas all of the other electronics boards are suitable.
For further details of th e performance of the different electronics boards, please refer to the appropriate chapters and
Appendices D and E.
Standard
Electronics
Density
version
Entrained
gas version
all directly interchangeable; this is because the Advanced electronics boards are physically longer than
Table 1.1
Basic amplifier circuit providing a frequency signal (indicating liquid
density) and PRT resistance (indicating liquid temperature). Interfaces
with a Signal Converter or Flow Computer.
Similar amplifier circuit to the above but meter operating at a lo wer
frequency which is more insensitive to entrained gas. It is NOT suitable
for operation in hazardous areas.
Advanced
Electronics
Density
version
Entrained
gas version
Remote Amplifier Box
Advanced
Electronics
Microprocessor control led circuit with a choice of analogue and digital
outputs providing a direct measurement of density and temperature. Also
providing a selection of calculated parameters and several diagnostic
functions.
As above but meter operating at a lower frequency more appropriate for
liquids with entrained gas. Suitable for operation in hazardous areas.
Suitable for operation in hazardous areas.
784521A: IIB Approval (ATEX)
784522A: IIC Approval (ATEX)
784523A: CSA Approval
784524A: Non-classified (supplied as spare for customer installation).
Note that the advanced electronics’ amplifier cannot be fitted into the
Standard electronics’ Remote Amplifier Box.
Page 1-3
Introduction 7835/45/46/47 Technical Manual
1.5 Advanced Electronics
In contrast to a meter fitted with Standard electronics (which requires a Flow computer or Signal Co nverter for
operation), the meter with Advanced electronics will provide a complete measurement system.
An Advanced Baseboard plus meter provides a complete system for measuring liqui d densi ty and liquid temperature. A
Remote Display or one of the optional boards may be required if outputs need to be configured in the field o r if additional
functionality is required.
For convenience, the Adva nced system design and performance are outlined below ; full performance specifications are
given in Appendices D and E.
Option board
Remote Display
7965 DISPLAY
Baseboard
Figure 1.3
1.5.1 Baseboard
The Baseboard can be considered the heart of the system. Along with a liquid density meter, it provides a complete
system for measuring liqu id density and liquid temperature. The Baseboard performs a range of useful calculations and
provides the follow ing outputs:
Two fully configurable 4-20mA outputs.
One pulse output providing either an alarm status signal or the meter tube frequency.
An RS485 digital communications link using RTU Modbus protocol.
1.5.2 Option board
The option board fits directly onto the Baseboard. One option board is presently available:
®
HART
Only one board may be fitted at a time.
board - providing an additional 4-20mA output and full HART® communications.
1.5.3 Remote Display
The 7965 Remote Display unit is intended for either hand-held or wall-mounted use. It provides a convenient means for
displaying calculated data and for con f ig uring or analysing the system set-up. It communicates via th e Base bo ar d RS48 5
digital communication link. One remote display can communicate with a number of meters if they are connected together
on the same RS485 link. Further details of the 7965 Display are given in Chapter 7.
Page 1-4
7835/45/46/47 Technical Manual Introduction
PART NUMBER IDENTIFICATION FOR 7835
Code Product
7835
NI-SPAN-C
A 1” ANSI 900 RF
B 1” ANSI 600 RF
D 1” ANSI 600 RTJ
E 1” ANSI 900 RTJ
F 1” ANSI 600 RF Smooth Face
H 25mm DIN 2635 DN25/PN40
J 25mm DIN 2635/2512 GVD DN25/PN40
L 25mm DIN 2637 RF DN25/PN100
Z Special
A
E
F
A Standard Stainless Steel for tube, mounted ampl ifier or remote amplifier.
B Outer containment (1/4 NPT), stainless ste el for tube , mount ed amp lifiers o r remote amplifie r.
C Secondary containment B31.3 (1/2 NPT) for tube, mounted amplifier or remote amplifier (100Bar)
F Tube mounted flat box in stainless steel.
A Std frequency out, EEx ia IIC T4 (-4 0°C…+40°C) or T4 (-40 °C…+70°C)
B Advanced board: 2 x 4-20mA outputs, EEx ia IIC T4 (-40°C…+60°C)
D
Code Safety Approval and Label J ATEX intrinsically safe (see “On-board Electronics” for rating)
L CSA intrinsically safe (Canada and USA)
A API Degrees (Americas) – Advanced board only.
B Base density to API tables (Metric) – Advanced only.
C Line density only – Advanced board only.
D General process incl. matrix (user data) – Advanc’d only.
T Frequency version – no software to configure.
Z Special
A Instrument standard.
D UKAS calibration (water).
E UKAS calibrati on (3 liquids).
Z Special
Code ASME IX
A None.
B Dye penetratio n (internal welds)
C Dye penetration (all welds)
D Radiography of flange welds + B
E Radiography of flange welds + C
F Radiography of flange welds
tube, S.S. bellows and input, Hastelloy® outer case
®
tube, S.S. bellows and input, Duplex outer case
Code On-board Electronics
®
Advanced board: HART
Code Default Configuration
, 3 x 4-20mA outputs, EEx ia IIB T4 (-40°C… +60°C)
Code Calibration
Code Traceability
(Typical Code)
Page 1-5
Introduction 7835/45/46/47 Technical Manual
PART NUMBER IDENTIFICATION FOR 7845
Code Product
7845 316L STAINLESS STE EL L iqu i d Densi t y Mete r
C 1” ANSI 300 RF
K 1” ANSI 600 RF
H 25mm DIN 2635 DN25/PN40
J 25mm DIN 2635/2512 GVD DN25/PN40
L 25mm DIN 2637 RF DN25/PN100
Z Special
B Wetted parts: 316L Stainless Steel, 316L Stainless Steel outer case
D Wetted parts: Alloy C22 bellows, 316L Stainless Steel tube, flanges and outer case. NACE.
A Standard Stainless Steel for tube, mounted amplifier or remote amplifier.
B Outer containment (1/4 NPT), stainless steel for tube, mount ed ampl ifiers o r remote ampli fier.
C Secondary containment B31.3 (1 /2 NPT) for tube, mounted amplifier or remote amplifier (100Bar)
F Tube mounted flat box in stainless steel.
Code On-board Electronics A Std frequency out, EEx ia IIC T4 ( -40°C…+40°C ) or T 4 (-40°C…+70°C )
B Advanced board: 2 x 4-20mA outputs, EEx ia IIC T4 (-40°C…+60°C)
D
E Entrained gas – frequency output (safe area only)
F Entrained gas – Advanced board: 2 x 4-20mA outputs, EEx rating as B.
J ATEX intrinsically safe (see “On-board Electronics” for rating)
L CSA intrinsically safe (Canada and USA)
S Safe area only (entrained gas option).
A API Degrees (Americas) – Advanced board only.
B Base density to API tables (Metric) – Advanced only.
C Line density only – Advanced board only.
D General process incl. matr ix (user d ata) – Ad vanc’d o nly.
T Frequency version – no software to configure.
Z Special
A Instrument standard.
D UKAS calibration (water).
E UKAS calibration (3 liquids).
Z Special
A None.
B Dye penetration (internal welds)
C Dye penetration (all welds)
D Radiography of flange welds + B
E Radiography of flange welds + C
F Radiography of flange welds
A None
X Certificates of material
7845 C B A F B J B A A A
Code Process Connections
Code Material Options
Code Meter Outer Containment
Code Amplifier Enclosure
Advanced board: HART
H
Entrained gas – Advanced board: HART
Code Safety Approval and Label
Code Default Configuration
®
Code Calibration
, 3 x 4-20mA outputs, EEx ia IIB T4 ( -40°C…+60 °C)
®
, 3 x 4-20mA outputs, EEx as C.
Code ASME IX
Code Traceability
(Typical Code)
Page 1-6
7835/45/46/47 Technical Manual Introduction
PART NUMBER IDENTIFICATION FOR 7846
Code Product
7846
HASTELLOY
C 1” ANSI 300 RF
H 25mm DIN 2635 DN25/PN40
J 25mm DIN 2635/2512 GVD DN25/PN40
Z Special
A Standard Stainless Steel for tube, mounted ampl ifier or remote amplifier.
B Outer containment (1/4 NPT), stainless ste el for tube , mount ed amp lifiers o r remote amplifie r.
C Secondary containment B31.3 (1/2 NPT) for tube, mounted amplifier or remote amplifier (100Bar)
F Tube mounted flat box in stainless steel.
Code On-board Electronics A Std frequency out, EEx ia IIC T4 (-4 0°C…+40°C) or T4 (-40 °C…+70°C)
B Advanced board: 2 x 4-20mA outputs, EEx ia IIC T4 (-40°C…+60°C)
D
E Entrained gas – frequency output (safe area only)
F Entrained gas – Advanced board: 2 x 4-20mA outputs, EEx rating as B.
H
J ATEX intrinsically safe (see “On-board Electronics” for rating)
L CSA intrinsically safe (Canada and USA)
S Safe area only (entrained gas option).
A API Degrees (Americas) – Advanced board only.
B Base density to API tables (Metric) – Advanced only.
C Line density only – Advanced board only.
D General process incl. matrix (user data) – Advanc’d only.
T Frequency version – no software to configure.
Z Special
A Instrument standard.
D UKAS calibration (water).
E UKAS calibrati on (3 liquids).
Z Special
A None.
B Dye penetratio n (internal welds)
C Dye penetration (all welds)
D Radiography of flange welds + B
E Radiography of flange welds + C
F Radiography of flange welds
A None
X Certificates of material
7846 C C A F B J B A A A (Typical Code)
Code Process Connect ions
®
C22® Liquid Density Meter
Code Material Options
Code Meter Outer Containment
Code Amplifier Enclosure
®
Advanced board: HART
Entrained gas – Advanced board: HAR T
Code Safety Approval and Label
Code Default Configuration
, 3 x 4-20mA outputs, EEx ia IIB T4 (-40°C… +60°C)
Code Calibration
Code ASME IX
®
, 3 x 4-20mA outputs, EEx as C.
Code Traceability
Page 1-7
Introduction 7835/45/46/47 Technical Manual
PART NUMBER IDENTIFICATION FOR 7847
Code Product
7847 316L STAINLESS STEEL Li qu id Dens ity Meter (HYGIENIC)
C 1” ANSI 300 RF
H 25mm DIN 2635 DN25/PN40
J 25mm DIN 2635/2512 GVD DN25/PN40
P 1” Ladish Tri-Clamp (Hygienic)
S 25mm DIN 11851
Z Special
B Wetted parts 316L Stainless Steel, 316L Stainless Steel outer case.
A Standard Stainless Steel for tube, mounted amplifier or remote amplifier.
F Tube mounted flat box in stainless steel.
A Std frequency out, EEx ia IIC T4 ( -40°C…+40°C ) or T 4 (-40°C…+70°C )
B Advanced board: 2 x 4-20mA outputs, EEx ia IIC T4 (-40°C…+60°C)
D
E Entrained gas – frequency output (safe area only)
F Entrained gas – Advanced board: 2 x 4-20mA outputs, EEx rating as B.
H
J ATEX intrinsically safe (see “On-board Electronics” for rating)
L CSA intrinsically safe (Canada and USA)
S Safe area only (entrained gas option).
T Safe area only (3A’s approved label).
A API Degrees (Americas) – Advanced board only.
B Base density to API tables (Metric) – Advanced only.
C Line density only – Advanced board only.
D General process incl. matr ix (user d ata) – Ad vanc’d o nly.
T Frequency version – no software to configure.
Z Special
A Instrument standard.
D UKAS calibration (water).
E UKAS calibration (3 liquids).
Z Special
A None.
B Dye penetration (internal welds)
C Dye penetration (all welds)
D Radiography of flange welds + B
E Radiography of flange welds + C
F Radiography of flange welds
A None
X Certificates of material
7847 C B A F B J B A A A
Code Process Connections
Code Material Options
Code Meter Outer Containment
Code Amplifier Enclosure
Code On-board Electronics
Advanced board: HART
Entrained gas – Advanced board: HART
Code Safety Approval and Label
Code Default Configuration
Code Calibration
®
, 3 x 4-20mA outputs, EEx ia IIB T4 ( -40°C…+60 °C)
This chapter describes t he mechanical installation of the Micro Motion® 7835/45/46/47 Liquid Density Meters.
Remember! ALWAYS handle the meters with care
Figure 2.1
When handling…
Don’t drop the meter or subject it to sever mechanic a l shock.
Don’t expose the meter to excessive vibration.
When installing…
Don’t position the rupture disk where failure could cause personal injury.
Ensure axial loading from pipework does not exceed ½ tonne.
Ensure electrical safety requirements are met.
Ensure that the meter and associated pipework are pressure teste d to 1½ time s the maximu m op e rati ng
pressure.
When operating…
Don’t use liquids incompatible with the construction.
Don’t operate the meter above its rated pressure.
When transporting…
Ensure the meter does not contain hazardous fluids, including those that may have leaked into the case.
When planning the installation of a meter it is important to consider the following factor s:
Safety The meter should be orientated such that, if there is a mechanical structure failure within
Serviceability
Installing the meter in a by-pass configurat ion allows it to be removed for servicing or
Performance
the instrument, the liqui d is discharged from the rupture disc in a safe manner. Please
refer to figure 2.2b for details.
calibration without affecting the main pipeline. Possible by-pass configurations are shown
in Figure 2.2c
Pipe stresses and
vibration
Axial load should not exceed ½ tonne, so pipework should ha ve a degree of flexibility.
Excessive pipe vibration should be av oide d.
Gas bubbles The presence of gas bubbles can seriously affect the meter performance and so the
following points shou ld be considered:-
The liquid must alw ays be at a pressure substantially above its vapour pressure.
All pipework couplings and joints must be air tight.
No vortex should be present at the inlet to the meter.
Cavitations, caused by pumping, should not gene rat e bub bles from di s sol ved ga ses.
If a pump is used it is should ‘push’ rather than ‘pull’ the product through the meter.
Note: For entrained gas unit s where the density of aerated m ixtures is to be measured
some of the above recommendations may not be applicable.
Meter orientation
For low flow rates, e.g. 750 litres/hour (2.7 gal/min.), the meter should preferably be
mounted vertically or at an incline, with the flow in an upwards direction.
If the liquid contains solid particles, the direction of flow should be upwards unless the
particles are large enough not to be carried with the flow, in which case the direction
of flow should be reversed.
The meter should be mounted with the electric cable running downwards thereby
minimising the ingress of water should a cable gland become defective.
Flow rate
A fast flow rate, e.g. 3000 litres /hour (11 gal/min.), will help to achieve good
temperature equilibrium and ha ve a self -cle an i ng action .
A low flow rate, e.g. 1000 litres/hour (3.7 gal/min.), is recommended if the product
contains particles which may cause erosio n .
The meters exhibit a small flow dependent density reading. For flow rates up to 15000
litres per hour (55 ga l/min) and assuming no consequent line pressure or product
changes, the maximum density offset will be less than 0.2kg/m
3
.
Temperature
Stability
The inlet pipework should be thermally lagged to ensure good temperature
This section considers in more detai l the moun ting of the meters and the design of the associa ted pipe work, includin g the
calculation of pressure drop in the meter.
Installation drawings for all the meter versions are reproduced in the Appendices, along with detailed drawings of the
flanges/couplings. The preferre d meth od s of supp ortin g th e met er are show n in Figure 2.2a.
1st
Meter supported
in two positions around
1” schedule 80 pipe.
Figure 2.2a: Preferred Methods of Mounting Meter
For continuously high flow rates, the mounting position can be selected to simplify the associated pipework and help
minimise the pressure and temperature losses. (See Figure 2.2b below).
2nd
Meter supported
in two positions around
the immediate pipework.
3rd
Meter supported
in two positions around
outer case (4” diameter).
The meter should be considered as a straight pipe of 23.6mm (0.929”) internal diameter and 1.03m (40.551”) in length.
The following formula has b een proven to apply to the meter by measurements at 12000 litre s per hour (44 gal/min).
).
V
).
(
V
m/s)
= 2cS =10cS
2
VLf200
h =
Dg
Where:
For viscous or laminar flow (Reynolds N umber
Frictional Coefficient (
For turbulent flow (
R
Frictional Coefficient (
f ) =
greater than 2500)
e
) =
f
and:
h = Pressure drop (bars)
= Friction coefficient
f
L = Pipe length (m) = 1.03
D = Internal pipe diameter (mm) = 23.6
V = Mean fluid velocity (m/s)
= Fluid density (g/cc)
= 9.81 (m/s2)
g
R less than 2000)
e
16
R
e
064.0
where: Pipe
23.0
R
e
R =
e
DV 1000
= Kinematic viscosity (cS)
In addition to the pressure drop ca used by the liquid flow through the instru ment, it will be necessary to calcu late the
pressure drop in any associated sample pipework before concluding the system design requirements.
2.5 Special considerations for h ygienic applications
The 7847 meter is specially designed for use in hygienic applications. The following points should be considered when
planning an installation for a hygienic application.
Meter orientation The 7847 should be installed in the vertical plane to prevent the accumulation of product
residue in the convolutions of the bellows, caus ing contamination, especially during the final
rinse when cleaning.
Meter mounting The method of meter mounting should be suitable for the application and cleaning processes
Steam cleaning Where it is necessary to sterilise the meter using the stea m cleaning process, ensure the
Post installation Ensure the cable glands, blanking plugs, lid, and seal are in place and tightened to prevent
used. Process seals appropriate for the media should be used.
temperature and duration of cleaning does not exceed 250 °F (121 °C) for a period of
30 minutes. Exceeding this limit may permanently damage the meter’s amplifier circuit.
moisture and dust ingress.
2.6 Post-Installation Checks
After installation the meter should be pressure tested t o 1.5 times the maximum working pressure of the syst em but NOT
to a value exceeding the meter test figure shown on the meter label.
CAUTION: If the pressure test figure is exceeded, the meter may be irrevocably damaged.
7835/45/46/47 Technical Manual Advanced Unit Electrical Installation and Configuration
Chapter 3
Advanced Unit Electrical Installation and
Configuration
3.1 General
This chapter describes the electrical installation of the 7835 and the 7845, 7846, 7847 Liquid Density Meters when fitted
with the Advanced electronics option.
Option board
Baseboard
Figure 3.1
The first sections of this chapter address the installation and configuration of the Advanced Baseboard, and the later
sections concern the Advanced option boards. Further details about the installation of the Remote Display are given in
Chapter 7.
Remote Display
7965 DISPLAY
Page 3-1
Advanced Unit Electrical Installation and Configuration 7835/45/46/47 Technical Manual
3.2 Planning an Electrical Installation
When planning the electrical installation of an Advanced unit, it is important to consider the points given below.
Safety
• Electrical installation in hazardous areas requires strict
• For installation of the CSA certified unit in a hazardous area, refer to Append i x K.
• For installation of the A TEX certified unit in a hazardous area, refer to the appropriate safety
instructions booklet (78355015/SI, 7835 5038/SI, or 78355065/SI).
adherence to local codes of practice.
Power supply
Ground connections
Cable parameters
• The Advanced electronics operate from a nominal 24V supply, but will operate from any supply
in the range 9.5V to 28V, meas ured at the supply terminals on the baseboard.
• The output circuits on the baseboard are all loop-pow ered and are isolated from the main
circuit. If required, the main circuit and the output circuits can be powered from a common
power supply.
• When selecting a suitable pow er supply voltage, you must take into account voltage drops
caused by the connecting cable (see below) and in hazardous areas, across zener barriers or
galvanic isolators.
• The earthing pads on the baseboard (see Figure 3.3a) must make good contact with the meter
case via the M3 bolts.
®
• If a HART
baseboard earthing points.
• The 0V power supply lead should be earthed at the supply end, or at the safety barriers if
applicable.
• Where long cable lengths are required the cable resistance may be significant. When
operating from a 24V supply in safe areas the following limits apply:
Power supply 260
Remote Display 60
Outputs 500
For further details relating to the maximum line resistance, please refer to Appendix D.
• When calculating the maximum cable lengths please note that the current loop is 2 times the
cable length, and so the cable resistance is given by:
• Typical cables would comply with BS5308 Type 1 or 2.
option board is used, the indicated earthing point must make good contact with the
Maximum line resistance (Ω)
2 x (dc resistance per unit length) x (cab le length)
EMC
Page 3-2
• To meet the EC Directive for EMC (Electromagnetic Compatibility), it is recommended that the
meter be connected using a suitable instrumentation cable.
The instrumentation cable should have individual screen(s), foil or braid over each twisted pair
and an overall screen to cover all cores. Where permissible, the overall screen should be
connected to earth at both ends (360° bonded at both ends). The inner individual screen(s)
should be connected at only one end, the controller (e.g. signal conver ter) end.
• Note that for intrinsic safety, termination of the inne r individual screen(s) to earth in the
hazardous area is NOT generally permitted.
• Metal cable glands should be used where the cables enter the meter amplifier box. Unused
cable ports should be fitted with metal blank ing plugs.
• When the 78452 (Advanced Remote Amplifier) is used, the ferrite ring, which is supplied, must
be fitted around the connecting cab le. For ins t all ation in hazardous areas, refer to the certified
system drawings in Appendix K, and the safety inst ruc ti on bo okl et (7 83 550 1 5/ SI or
78355038/SI) that came with the meter.
7835/45/46/47 Technical Manual Advanced Unit Electrical Installation and Configuration
3.3 Electrical installation in safe areas
All connections to the baseboard are made to terminals 1 to 12 of the terminal block PL2 as shown in Figure 3.2.
Earthing Point
1
234 5
6
7
89
10
11
12
+
PULSE 1
-
+
ANALOG 1
-
+
ANALOG 2
-
SUPPLY +
0V
-
+
DISPLAY
A
B
OPTIONAL
BOARD
Analog 1
22mA
2mA
Alarm
Analog 2
22mA
2mA
Alarm
P/U1
P/U2
PRT -
SIG -
SIG +
PRT +
DRIVE
PL1
1
234
0V
5
6
78
9
PL2
Earthing Point
Jumper Links
Foam support strip
Figure 3.2: Baseboard Layout
Note: There is no reason to remove the baseboard under normal circumstances. If it is removed, however, care should
be taken, when replacing the board, to push it firmly against the foam strip, as this helps to prevent the board from
excessive flexing.
Page 3-3
Advanced Unit Electrical Installation and Configuration 7835/45/46/47 Technical Manual
Figure 3.3 shows a schematic representation of the electrical connection diagram for the Advanced Baseboard and Remote
Display in safe areas. In this example, the pulse output is shown driving an alarm device such as a relay.
+5V to 28V
Pulse
Output
Analog
Output
Analog
Output
(as above)
500Ω MAX
+16V to 28V
0V
500Ω minimum
1000Ω typical
0V
9.5V to 28V dc
Power Supply
_
+
Load
Advanced
Density
Baseboard
1 +
Pulse
}
2 -
PL2 Connections
3 +
Analog 1
}
4 -
5 +
Analog 2
}
6 -
7 +
Supply
}
Cable Screen 1
Remote
Display
Page 3-4
0V Power 2
+ve Power 3
A 4
B 5
Figure 3.3: Connection Diagram (Safe areas)
8 -
9 -
10 +
11 A
12 B
}
Remote
Display
7835/45/46/47 Technical Manual Advanced Unit Electrical Installation and Configuration
3.3.1 Electrical Installation with Signal Converter / Flow Computer
Figure 3.4 shows a typical electrical connection diagram for use in safe areas using flow computers and signal converters.
7835/45/46/47 with
Advanced Electronics
Freq/Alarm
+VE
1
-VE
2
Analog 1 (Analog 2)
(5)
+VE
3
(6)
4
-VE
Power Supply
7
+VE
8
-VE
1000Ω
7950/51/55
7915/25/26/45/46
+ Density Pwr
+ Density Input
- Density Pwr
- Density Input
+ Density Pwr
+ Analog Input
- Density Pwr
- Analog Input
+Density Pwr
- Density Pwr
SEE FLOW
COMPUTER/
SIGNAL
CONVERTER
HANDBOOK
FOR
CONNECTION
DETAILS
Figure 3.4: Electrical connection diagram when using a flow computer / signal converter (Safe area)
Page 3-5
Advanced Unit Electrical Installation and Configuration 7835/45/46/47 Technical Manual
Ω
Ω
3.4 Electrical installation in hazardous areas
When used in hazardous areas, safety barriers MUST be interposed between the meter and the signal processing
equipment. Some of the safety barriers are unsuitable for certain installations, as discussed below.
Note:
• For installation of the CSA certified unit in a hazardous area, refer to Appendix K.
• For installation of the ATEX certified unit in a hazardous area, refer to the appropriate safety
instructions booklet (78355015/SI, 78355038/SI, or 78355065/SI).
3.4.1 Safety Barrier and Galvanic Isolator Selection
3.4.1.1. Power Supply (PL2 terminals 7 and 8)
As a general rule, the IIB safety barrier should be used where possible as this allows the maximum power to the meter,
facilitating a wide range of installations and system configurations.
Where the installation requires the IIC safety barrier, it is important to check that sufficient power is available to power
the meter and all of the options. The table below summarises the maximum line resistances allowable for the main
system configurations assuming a 24V supply and a minimum of 9.5V available at the supply terminals on the baseboard.
Table 3.1
Advanced System combination
Baseboard 340
Baseboard + remote display 260
Baseboard + locally powered remote display 280
Baseboard + HART® board 270
Baseboard + HART® + display 250
Zener Safety Barriers
Power to the main circuit may be obtained through a simple 164Ω barrier or two 300Ω 28V barriers in parallel for IIB
applications, or through a single 234Ω 28V barrier in IIC applications.
The main characteristics of the safety barriers are given here. Using this information and the information given in the
table above the most suitable barriers for a particular application can be ascertained.
Table 3.2
Type Group
MTL 729P IIB 164 184
MTL 728P IIC 234 253
P&F Z728H IIC 240 250
Note: The power supply input is protected internally by an 8.2V±5% clamp diode and a 1Ω resistor. This limits the
maximum current that can flow into the device:
I
max
Maximum voltage from barrier
=
Safety Description (
Minimum resistance of barrier/input combination
Maximum line resistance (
) Max. resistance (Ω)
- Minimum voltage at input
) (barrier + cable)
For example, if two 28V, 300Ω barriers are used in parallel, the effective resistance is 150Ω.
The maximum current is:
()
95.02.828
I
=
max
…and not 185mA, as might be expected if the input protection diode was not present.
Page 3-6
×−
= 134mA
1150
+
7835/45/46/47 Technical Manual Advanced Unit Electrical Installation and Configuration
Ω
Galvanic Isolators
Galvanic isolators are suitable for powering the main board in IIB applications, but are NOT suitable for powering the main
board in
IIC applications. Also, IIC isolators are not suitable for use when Modbus communications are required.
The main characteristics of the galvanic isolators are given here. Using this information and the information given in the
table above, the most suitable galvanic isolators for a particular application can be ascertained.
Table 3.3
Type Group
Max output impedance (
)
MTL 3022 IIB 165
P&F KFD2-SD-Ex1.36 IIB 160
P&F KFD2-SL-Ex1.36 IIB 160
MTL 5022 IIB 143
3.4.1.2. Analogue (4 to 20mA) outputs including HART
®
(PL2 terminals 3 & 4, 5 & 6 and HART PL3 3 & 4)
Any of the zener safety barriers listed on the system certificates are suitable for operation with the Advanced Density
analogue outputs. Some galvanic isolators may not be capable of driving the 2mA and 22mA out-of-range alarm states
available on the Advanced Density system; for details please check with the barrier supplier.
3.4.1.3. Pulse output
(PL2 terminals 1 & 2)
The pulse output can be configured to output either a status / alarm signal or the resonant frequency of the density meter;
the latter requires the safety barrier to have a bandwidth of at least 1 kHz.
The table below indicates which galvanic isolators may be used for frequency configured pulse output; zener barriers may
be used for either configuration.
Table 3.4
Isolator type Output description Pulse output configuration
MTL3011 Relay Status / alarm
MTL3012 Solid state (dc to 2kHz) All
MTL4013 Solid state (dc to 5kHz) All
MTL4014 Relay Status / alarm
MTL5011 Relay Status / alarm
MTL5016 Relay Status / alarm
MTL5017 Relay Status / alarm
Page 3-7
Advanced Unit Electrical Installation and Configuration 7835/45/46/47 Technical Manual
3.5 Baseboard Configuration
The baseboard is supplied with one of the following two software versions:
•
General software version - normally used in the food and process industries.
•
Fiscal software version - normally used in Crude oil or refined petroleum applications.
The only difference between the two software versions is the available calculations.
Irrespective of which software version is running, when the unit is received from the factory, it is pre-configured to output
the following signals:
Table 3.5
Output Output Parameter
Analog 1 (4-20mA) = Line density (500 to 1500 kg/m³)
Analog 2 (4-20mA) =
Pulse output = Alarm - normally on
For many applications, the factory default configuration described above will be quite acceptable. However, if any of the
additional calculated parameters or different output ranges are required, then a simple Baseboard re-configuration can be
performed using a Remote Display, or PC.
For details on the available calculations and other Baseboard configuration factors, please refer to Appendix E.
Temperature (0 to 100
°C)
Page 3-8
Loading...
+ 126 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.