20.10.1 Perform loop tests using ProLink II .............................................................................274
20.10.2 Perform loop tests using ProLink III .............................................................................276
20.10.3 Perform loop tests using the PROFIBUS EDD ..............................................................277
20.10.4 Perform loop tests using PROFIBUS bus parameters ...................................................279
20.11 Trim mA outputs ......................................................................................................................282
20.11.1 Trim mA outputs using ProLink II ................................................................................282
20.11.2 Trim mA outputs using ProLink III ...............................................................................282
20.11.3 Trim mA outputs using the PROFIBUS EDD .................................................................283
20.11.4 Trim mA outputs using PROFIBUS bus parameters .....................................................283
20.12 Check Lower Range Value and Upper Range Value ....................................................................284
20.13 Check mA Output Fault Action ..................................................................................................284
20.14 Check for radio frequency interference (RFI) .............................................................................285
20.15 Check Frequency Output Maximum Pulse Width ......................................................................285
20.16 Check Frequency Output Scaling Method .................................................................................285
20.17 Check Frequency Output Fault Action .......................................................................................285
20.18 Check Flow Direction ................................................................................................................286
20.19 Check the cutoffs ......................................................................................................................286
20.20 Check for slug flow (two-phase flow) ........................................................................................286
20.21 Check the drive gain .................................................................................................................287
20.21.1 Collect drive gain data ................................................................................................288
20.22 Check the pickoff voltage .........................................................................................................289
20.22.1 Collect pickoff voltage data ........................................................................................289
20.23 Check for electrical shorts .........................................................................................................290
Appendices and reference
Appendix A Default values and ranges ...........................................................................................291
A.1Default values and ranges .........................................................................................................291
Appendix B Using ProLink II with the transmitter ...........................................................................295
B.1Basic information about ProLink II .............................................................................................295
B.2Menu maps for ProLink II ...........................................................................................................296
Appendix C Setting up and using the PROFIBUS interfaces .............................................................301
C.1PROFIBUS-DP functionality supported by transmitter ...............................................................301
C.2Options for PROFIBUS communications ....................................................................................302
C.3Menu maps for the PROFIBUS EDD ............................................................................................302
C.4Set up the GSD ..........................................................................................................................310
C.4.1Input modules in the GSD ...........................................................................................311
vi Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
Contents
C.4.2Output modules in the GSD ....................................................................................... 315
C.4.3Contents of Diagnostic Bytes 11 through 24 .............................................................. 316
C.5Use PROFIBUS bus parameters ..................................................................................................321
C.5.1PROFIBUS data types ..................................................................................................322
C.5.2PROFIBUS Measurement block (Slot 1) and related information ................................. 322
C.5.3PROFIBUS Calibration block (Slot 2) and related information ......................................328
C.5.4PROFIBUS Diagnostic block (Slot 3) and related information ...................................... 332
C.5.5PROFIBUS Device Information block (Slot 4) and related information .........................342
C.5.6PROFIBUS Filling block and related information ..........................................................345
C.5.7PROFIBUS Identification and Maintenance Functions block ........................................ 357
Index ................................................................................................................................................361
Configuration and Use Manual vii
Contents
viii Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
Part I
Getting started
Chapters covered in this part:
Introduction to filling with the Filling Mass Transmitter
•
Quick start using ProLink II
•
Quick start using the PROFIBUS EDD
•
Quick start using PROFIBUS bus parameters
•
Getting started
Configuration and Use Manual 1
Getting started
2 Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
Introduction to filling with the Filling Mass Transmitter
1Introduction to filling with the Filling
Mass Transmitter
Topics covered in this chapter:
The Filling Mass Transmitter from Micro Motion
•
Fill types and fill options
•
Options for user interface
•
1.1The Filling Mass Transmitter from
Micro Motion
The Filling Mass Transmitter is designed for any process that requires high-speed highaccuracy filling or dosing.
The Filling Mass Transmitter, paired with a Coriolis sensor from Micro Motion, enables
mass-based measurement that is immune to variations in process fluid, temperature, or
pressure. Integrated-valve-control fills are implemented via high-precision discrete
outputs, for the fastest possible valve response. Automatic Overshoot Compensation
adjusts the system to minimize processing delays in valve control. Volume-based filling is
also available.
The Filling Mass Transmitter implements all of the advanced digital signal processing
algorithms, diagnostics, and features of the Micro Motion family of transmitters.
1.2
Fill types and descriptionsTable 1-1:
Transmitter model codeSupported fill typesDescription
FMT*P
FMT*Q
FMT*R
FMT*S
FMT*T
Fill types and fill options
Depending on your purchase option, the Filling Mass Transmitter supports either
integrated-valve-control fills or external-valve-control fills. For integrated-valve-control
installations, there are five types of integrated-valve-control fills and three fill options. Each
fill type and combination has different output requirements and is configured differently.
External valve controlThe transmitter measures flow and sends flow data to a host
over the frequency/pulse output. The host opens and closes
the valves and performs fill measurement. The transmitter is
unaware of the filling application.
Integrated valve controlThe host inititates the fill. The transmitter resets the fill total,
opens the valves, performs fill measurement, and closes the
valves.
Configuration and Use Manual 3
Introduction to filling with the Filling Mass Transmitter
Fill types and descriptions (continued)Table 1-1:
Transmitter model codeSupported fill typesDescription
FMT*U
FMT*V
One-stage discreteThe fill is controlled by a single discrete (ON/OFF) valve. The
valve opens completely when the fill begins, and closes completely when Fill Target is reached, or the fill is paused or ended.
Two-stage discreteThe fill is controlled by two discrete valves: a primary valve and
a secondary valve. One valve must open at the beginning of
the fill; the other opens at a user-defined point. One valve
must stay open until the end of the fill; the other closes at a
user-defined point.
TimedThe valve is open for the specified number of seconds.
Dual-fillheadFill sequence:
1. Container #1 is moved into position.
2. Fillhead #1 begins filling Container #1, and Container #2 is
moved into position.
3. Fill #1 ends. Fillhead #2 begins filling Container #2. Container #1 is replaced by a new container.
Standard one-stage filling control is implemented for both fills:
The valve opens completely when the fill begins, and closes
completely when Fill Target is reached, or the fill is paused or
ended.
Dual-fillhead timedFill sequence:
1. Container #1 is moved into position.
2. Fillhead #1 begins filling Container #1, and Container #2 is
moved into position.
3. Fill #1 ends. Fillhead #2 begins filling Container #2. Container #1 is replaced by a new container.
Timed control is implemented for both fills: Each valve is open
for the specified number of seconds.
Fill options and descriptionsTable 1-2:
OptionDescriptionCompatibility
PurgeThe Purge feature is used to control an auxiliary valve that
can be used for any non-filling purpose. For example, it can
be used for adding water or gas to the container after the
fill ends, or “padding.” Flow through the auxiliary valve is
not measured by the transmitter.
PumpThe Pump feature is used to increase pressure during the
fill by starting an upstream pump just before the fill begins.
Automatic Overshoot Compensation (AOC)
Automatic Overshoot Compensation (AOC) is used to adjust fill timing to compensate for the time required to
transmit the valve close command or for the valve to close
completely.
Compatible with:
• One-stage discrete fills
• Two-stage discrete fills
• Timed fills
Compatible with:
• One-stage discrete fills
Compatible with:
• One-stage discrete fills
• Two-stage discrete fills
• Dual-fillhead fills
4 Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
Introduction to filling with the Filling Mass Transmitter
1.2.1I/O requirements
To implement a specific fill type and fill option, the transmitter outputs must be wired to
the appropriate valves or devices, and configured appropriately.
I/O requirements for fill types and fill optionsTable 1-3:
Timed with purgePrimary valveN/APurge valveAs desiredN/A
Dual-fillheadValve in
Timed dual-fillheadValve in
DO1
Primary valveN/APurge valveAs desiredN/A
Primary valvePumpAs desiredAs desiredN/A
Primary valveSecondary
Fillhead #1
Fillhead #1
Precision
DO2
valve
valve
Valve in
Fillhead #2
Valve in
Fillhead #2
operating as
DOmA output
As desiredAs desiredN/A
Purge valveAs desiredN/A
As desiredAs desiredN/A
As desiredAs desiredN/A
Frequency
output
1.3Options for user interface
Your options for user interface and fill operation depend on the protocol supported by
your transmitter. Your transmitter's model code identifies the protocol.
Transmitter protocol and user interface optionsTable 1-4:
Transmitter model
codeSupported protocol
FMT*P
FMT*R
FMT*S
FMT*T
Modbus• ProLink II
Configuration, maintenance,
and troubleshootingFill operation
• Modbus utility
Configuration and Use Manual 5
User interface options
• ProLink II
• Modbus host
Introduction to filling with the Filling Mass Transmitter
Transmitter protocol and user interface options (continued)Table 1-4:
Transmitter model
codeSupported protocol
FMT*Q
FMT*U
FMT*V
PROFIBUS-DP• ProLink II
User interface options
Configuration, maintenance,
and troubleshootingFill operation
• ProLink II
• EDD
• Bus parameters
• EDD
• GSD
• Bus parameters
6 Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
2Quick start using ProLink II
Topics covered in this chapter:
Power up the transmitter
•
Check flowmeter status
•
Connect from ProLink II to the transmitter
•
Complete the configuration and commissioning process
•
2.1Power up the transmitter
The transmitter must be powered up for all configuration and commissioning tasks, or for
process measurement.
1.Follow appropriate procedures to ensure that a new device on the network does not
interfere with existing measurement and control loops.
2.Ensure that the cables are connected to the transmitter, as described in Micro MotionFilling Mass Transmitters: Installation Manual .
3.Ensure that all transmitter and sensor covers and seals are closed.
Quick start using ProLink II
2.2
CAUTION!
To prevent ignition of flammable or combustible atmospheres, ensure that all covers
and seals are tightly closed. For hazardous area installations, applying power while
housing covers are removed or loose can cause an explosion.
4.Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. During this period,
Alarm 009 is active. The diagnostic routines should complete in approximately
30 seconds.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics
can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the initial
startup, or if power is been off long enough to allow components to reach ambient
temperature, allow the electronics to warm up for approximately 10 minutes before
relying on process measurements. During this warm-up period, you may observe minor
measurement instability or inaccuracy.
Check flowmeter status
Check the flowmeter for any error conditions that require user action or that affect
measurement accuracy.
Configuration and Use Manual 7
Quick start using ProLink II
1.Wait approximately 10 seconds for the power-up sequence to complete.
Immediately after power-up, the transmitter runs through diagnostic routines and
checks for error conditions. During the power-up sequence, Alarm A009 is active.
This alarm should clear automatically when the power-up sequence is complete.
2.Connect to the transmitter and check for active alarms.
Postrequisites
For information on viewing the list of active alarms, see Section 18.3.
For information on individual alarms and suggested resolutions, see Section 20.1.
2.3Connect from ProLink II to the transmitter
Making a connection from ProLink II allows you to view process data, use ProLink II to
configure the transmitter, perform maintenance and troubleshooting tasks, or run a fill.
Prerequisites
You must have the following installed and ready to use:
•ProLink II v2.91 or later
•ProLink II installation kit for Modbus/RS-485 connections
Procedure
1.Attach the leads of your signal converter to the wires that are attached to the
RS-485 or service port pins on the transmitter. See Micro Motion Filling MassTransmitters: Installation Manual for more information.
2.Start ProLink II and choose Connect > Connect to Device.
3.In the Connection dialog box, enter parameters as shown here, then click Connect.
Transmitter protocol
Connection parameter
ProtocolModbus RTUService Port
COM Port
Address
ModbusPROFIBUS-DP
The port on your PC that you
are using for this connection
The port on your PC that you
are using for this connection
N/A
Note
The transmitter automatically analyzes the incoming connection request and responds to all
connection requests with any setting for parity and stop bits, and all network speeds between
1200 and 38,400 baud. You do not need to set values for these connection parameters.
8 Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
If the connection is successful, ProLink II displays the Process Variables screen.
Need help? If an error message is displayed:
•Ensure that you have specified the correct COM port.
•Check all the wiring between your PC and the transmitter.
•Add 120-Ω, 1/2-watt terminating resistors at both ends of the segment.
2.4Complete the configuration and
commissioning process
Use the following procedure as a general guideline to complete transmitter configuration
and commissioning.
1.Configure the fill.
• For integrated-valve-control fills, see Chapter 6.
• For external-valve-control fills, see Chapter 12.
2.Perform any required transmitter configuration that is not specifically related to
filling.
Quick start using ProLink II
2.4.1
See Chapter 15, Chapter 16, and Chapter 17.
3.Test or tune your system using sensor simulation.
See Section 2.4.1.
4.Back up the transmitter configuration to a file on your PC.
See Section 2.4.2.
Need help? At any time, you can restore the factory configuration to return the transmitter to a
known operational configuration. See Section 2.4.3.
Test or tune the system using sensor simulation
Use sensor simulation to test the system's response to a variety of process conditions,
including boundary conditions, problem conditions, or alarm conditions, or to tune the
loop.
Prerequisites
Before enabling sensor simulation, ensure that your process can tolerate the effects of the
simulated process values.
Procedure
1.Navigate to the sensor simulation menu.
Configuration and Use Manual 9
Quick start using ProLink II
2.Enable sensor simulation.
3.For mass flow, set Wave Form as desired and enter the required values.
4.For density, set Wave Form as desired and enter the required values.
Option
Fixed
Sawtooth
Sine
Required values
Fixed Value
Period
Minimum
Maximum
Period
Minimum
Maximum
5.For temperature, set Wave Form as desired and enter the required values.
Option
Fixed
Sawtooth
Sine
Required values
Fixed Value
Period
Minimum
Maximum
Period
Minimum
Maximum
6.Observe the system response to the simulated values and make any appropriate
changes to the transmitter configuration or to the system.
7.Modify the simulated values and repeat.
10 Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
Quick start using ProLink II
8.When you have finished testing or tuning, disable sensor simulation.
Sensor simulation
Sensor simulation allows you to test the system or tune the loop without having to create
the test conditions in your process. When sensor simulation is enabled, the transmitter
reports the simulated values for mass flow, density, and temperature, and takes all
appropriate actions. For example, the transmitter might apply a cutoff, activate an event,
or post an alarm.
When sensor simulation is enabled, the simulated values are stored in the same memory
locations used for process data from the sensor. The simulated values are then used
throughout transmitter functioning. For example, sensor simulation will affect:
•All mass flow rate, temperature, and density values shown on the display or
reported via outputs or digital communications
•The mass total and mass inventory values
•All volume calculations and data, including reported values, volume totals, and
volume inventories
•All mass, temperature, density, or volume values logged to Data Logger
2.4.2
Sensor simulation does not affect any diagnostic values.
Unlike actual mass flow rate and density values, the simulated values are not temperaturecompensated (adjusted for the effect of temperature on the sensor’s flow tubes).
Back up transmitter configuration
ProLink II and ProLink III provide a configuration upload/download function which allows
you to save configuration sets to your PC. This allows you to back up and restore your
transmitter configuration. It is also a convenient way to replicate a configuration across
multiple devices.
Prerequisites
One of the following:
•An active connection from ProLink II
•An active connection from ProLink III
Restriction
This function is not available with any other communications tools.
Procedure
•To back up the transmitter configuration using ProLink II:
1. Choose File > Load from Xmtr to File.
2. Specify a name and location for the backup file, and click Save.
Configuration and Use Manual 11
Quick start using ProLink II
3. Select the options that you want to include in the backup file, and click DownloadConfiguration.
•To back up the transmitter configuration using ProLink III:
1. Choose Device Tools > Configuration Transfer > Save or Load Configuration Data.
2. In the Configuration groupbox, select the configuration data you want to save.
3. Click Save, then specify a file name and location on your computer.
4. Click Start Save.
The backup file is saved to the specified name and location. It is saved as a text file and can
be read using any text editor.
ProLink IIIDevice Tools > Configuration Transfer > Restore Factory Configuration
Overview
Restoring the factory configuration returns the transmitter to a known operational
configuration. This may be useful if you experience problems during configuration.
Tip
Restoring the factory configuration is not a common action. You may want to contact Micro Motion
to see if there is a preferred method to resolve any issues.
12 Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
Quick start using the PROFIBUS EDD
3Quick start using the PROFIBUS EDD
Topics covered in this chapter:
Power up the transmitter
•
Check flowmeter status
•
Set up the PROFIBUS EDD
•
Make a PROFIBUS EDD connection to the transmitter
•
Complete the configuration and commissioning process
•
3.1Power up the transmitter
The transmitter must be powered up for all configuration and commissioning tasks, or for
process measurement.
1.Follow appropriate procedures to ensure that a new device on the network does not
interfere with existing measurement and control loops.
2.Ensure that the cables are connected to the transmitter, as described in Micro MotionFilling Mass Transmitters: Installation Manual .
3.Ensure that all transmitter and sensor covers and seals are closed.
CAUTION!
To prevent ignition of flammable or combustible atmospheres, ensure that all covers
and seals are tightly closed. For hazardous area installations, applying power while
housing covers are removed or loose can cause an explosion.
4.Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. During this period,
Alarm 009 is active. The diagnostic routines should complete in approximately
30 seconds.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics
can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the initial
startup, or if power is been off long enough to allow components to reach ambient
temperature, allow the electronics to warm up for approximately 10 minutes before
relying on process measurements. During this warm-up period, you may observe minor
measurement instability or inaccuracy.
Configuration and Use Manual 13
Quick start using the PROFIBUS EDD
3.2Check flowmeter status
Check the flowmeter for any error conditions that require user action or that affect
measurement accuracy.
1.Wait approximately 10 seconds for the power-up sequence to complete.
Immediately after power-up, the transmitter runs through diagnostic routines and
checks for error conditions. During the power-up sequence, Alarm A009 is active.
This alarm should clear automatically when the power-up sequence is complete.
2.Connect to the transmitter and check for active alarms.
Postrequisites
For information on viewing the list of active alarms, see Section 18.3.
For information on individual alarms and suggested resolutions, see Section 20.1.
3.3Set up the PROFIBUS EDD
3.4
The PROFIBUS EDD supports acyclic communications between the transmitter and a
PROFIBUS host. You can use the EDD to configure the transmitter and perform manual
operation and maintenance functions.
1.Download the EDD for your transmitter from the Emerson web site.
a. Use your browser to go to www.micromotion.com.
b. In the Quick Links list, click Software Downloads , then navigate to the Device
Drivers page.
c. Drill down to the device install kit for your transmitter, select the EDD, and
download it to your PC.
2.Import the EDD into your PROFIBUS host.
3.Configure your PROFIBUS host with the transmitter's node address and any other
required data.
Tip
The transmitter's node address was set during transmitter installation. See Micro Motion Filling
Mass Transmitters: Installation Manual for more information.
Make a PROFIBUS EDD connection to the
transmitter
Making a PROFIBUS EDD connection allows you to use the PROFIBUS EDD and your
PROFIBUS tool to view process data, configure the transmitter, perform maintenance and
troubleshooting tasks, or run a fill.
14 Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
Prerequisites
You must have a PROFIBUS configuration tool such as Siemens Simatic PDM.
The EDD from Micro Motion must be installed.
Procedure
1.Launch your PROFIBUS configuration tool.
2.Connect to the transmitter using the methods appropriate to your environment.
Tip
The transmitter's node address was set during transmitter installation. See Micro Motion Filling
Mass Transmitters: Installation Manual for more information.
3.5Complete the configuration and
commissioning process
Quick start using the PROFIBUS EDD
Use the following procedure as a general guideline to complete transmitter configuration
and commissioning.
1.Configure the fill.
• For integrated-valve-control fills, see Chapter 8.
• For external-valve-control fills, see Chapter 13.
2.Perform any required transmitter configuration that is not specifically related to
filling.
See Chapter 15, Chapter 16, and Chapter 17.
Configuration and Use Manual 15
Quick start using the PROFIBUS EDD
16 Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
Quick start using PROFIBUS bus parameters
4Quick start using PROFIBUS bus
parameters
Topics covered in this chapter:
Power up the transmitter
•
Check flowmeter status
•
Make a PROFIBUS bus parameters connection to the transmitter
•
Complete the configuration and commissioning process
•
4.1Power up the transmitter
The transmitter must be powered up for all configuration and commissioning tasks, or for
process measurement.
1.Follow appropriate procedures to ensure that a new device on the network does not
interfere with existing measurement and control loops.
2.Ensure that the cables are connected to the transmitter, as described in Micro Motion
Filling Mass Transmitters: Installation Manual .
3.Ensure that all transmitter and sensor covers and seals are closed.
CAUTION!
To prevent ignition of flammable or combustible atmospheres, ensure that all covers
and seals are tightly closed. For hazardous area installations, applying power while
housing covers are removed or loose can cause an explosion.
4.Turn on the electrical power at the power supply.
The transmitter will automatically perform diagnostic routines. During this period,
Alarm 009 is active. The diagnostic routines should complete in approximately
30 seconds.
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics
can take up to 10 minutes to reach thermal equilibrium. Therefore, if this is the initial
startup, or if power is been off long enough to allow components to reach ambient
temperature, allow the electronics to warm up for approximately 10 minutes before
relying on process measurements. During this warm-up period, you may observe minor
measurement instability or inaccuracy.
Configuration and Use Manual 17
Quick start using PROFIBUS bus parameters
4.2Check flowmeter status
Check the flowmeter for any error conditions that require user action or that affect
measurement accuracy.
1.Wait approximately 10 seconds for the power-up sequence to complete.
Immediately after power-up, the transmitter runs through diagnostic routines and
checks for error conditions. During the power-up sequence, Alarm A009 is active.
This alarm should clear automatically when the power-up sequence is complete.
2.Connect to the transmitter and check for active alarms.
Postrequisites
For information on viewing the list of active alarms, see Section 18.3.
For information on individual alarms and suggested resolutions, see Section 20.1.
4.3Make a PROFIBUS bus parameters connection
4.4
to the transmitter
Making a PROFIBUS bus parameters connection allows you to use PROFIBUS bus
parameters and your PROFIBUS tool to view process data, configure the transmitter,
perform maintenance and troubleshooting tasks, or run a fill.
Prerequisites
You must have a PROFIBUS tool that supports DP-V1 read and write services.
Procedure
1.Launch your PROFIBUS tool.
2.Connect to the transmitter using the methods appropriate to your environment.
Tip
The transmitter's node address was set during transmitter installation. See Micro Motion Filling
Mass Transmitters: Installation Manual for more information.
Complete the configuration and
commissioning process
Use the following procedure as a general guideline to complete transmitter configuration
and commissioning.
1.Configure the fill.
• For integrated-valve-control fills, see Chapter 10.
• For external-valve-control fills, see Chapter 14.
18 Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
Quick start using PROFIBUS bus parameters
2.Perform any required transmitter configuration that is not specifically related to
filling.
See Chapter 15, Chapter 16, and Chapter 17.
Need help? At any time, you can restore the factory configuration to return the transmitter to a
known operational configuration. See Section 4.4.1.
4.4.1Restore the factory configuration using PROFIBUS bus
parameters
Restoring the factory configuration returns the transmitter to a known operational
configuration. This may be useful if you experience problems during configuration.
Prerequisites
You must have a PROFIBUS configuration tool that supports DP-V1 read and write services,
and you must be connected to the transmitter.
Procedure
Write 1 to the Diagnostic block, Index 51.
Configuration and Use Manual 19
Quick start using PROFIBUS bus parameters
20 Micro Motion® Filling Mass Transmitters with PROFIBUS-DP
Loading...
+ 350 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.