Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion
Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
2
User GuideContents
MMI-20019808April 2022
Contents
Chapter 1Before you begin........................................................................................................5
1.1 About this document...................................................................................................................5
This manual contains information required to install, configure, and use the EtherNet/ IP
Module. The EtherNet/IP Module enables integration of industrial devices into the
Ethernet network with no loss of functionality, control, or reliability. The EtherNet/IP
Module can be used for new or retrofit installations.
The Micro Motion EtherNet/IP Module is a customization of the Anybus Communicator
from HMS Industrial Networks. OEM features not documented here are documented in
the Anybus Communicator User Manual available on the HMS web site.
The information in this document assumes that users understand:
• Basic transmitter and sensor installation, configuration, and maintenance concepts
and procedures
• All corporate, local government, and national government safety standards and
requirements that guard against injuries and death
1.2Hazard messages
This document uses the following criteria for hazard messages based on ANSI standards
Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a
situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration
of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access to protect users' assets. This is true for all
systems used within the facility.
User Guide5
Before you beginUser Guide
April 2022MMI-20019808
1.3Related documentation
See any of the following documents for more information:
• Anybus Communicator User Manual on the HMS web site
• The sensor installation manual
• The transmitter installation manual
• The transmitter configuration and use manual
1.4Functional overview
The EtherNet/IP Module acts as a gateway between the serial output of a Micro Motion
device and an EtherNet/IP network. Using a web browser, the module supports:
• Process monitoring and control
• Configuration
• Administration
The EtherNet/IP Module consists of a Modbus master and an Ethernet slave.
• On the Modbus side, the module polls the transmitter for a standard set of process
variables and stores the data locally.
• On the Ethernet side, the module receives requests for data and responds with the
current values.
• The web browser is used for transmitter configuration and administration, via a
connection to the Micro Motion web pages on the EtherNet/IP Module.
• The configuration loop is used only by the MicroMotion Ethernet Config Tool. In typical
installations, this tool is not needed.
6Micro Motion EtherNet/IP Module
User Guide
Before you begin
MMI-20019808April 2022
Figure 1-1: EtherNet/IP Module with a Model 2700 transmitter
A. PLC
B. Ethernet
C. EtherNet/IP Module
D. Modbus/RS-485
E. Transmitter (see Product Data Sheet for compatible transmitters)
F. To sensor
G. PC with Micro Motion Ethernet Config Tool
H. Configuration loop (with configuration cable)
I. Other devices (SCADA, PC, Inverter)
J. Web browser
Figure 1-2: EtherNet/IP Module in an MVD Direct Connect installation
A. PLC
B. Ethernet
C. EtherNet/IP Module
D. Modbus/RS-485
E. Barrier
F. Core processor
G. To sensor
H. PC with Micro Motion Ethernet Config Tool
I. Configuration loop (with configuration cable)
J. Other devices (SCADA, PC, Inverter)
K. Web browser
User Guide7
Before you beginUser Guide
April 2022MMI-20019808
1.5External view of device
A. Status LEDs
B. Configuration switches
C. Ethernet connector
D. PC connector (configuration)
E. Modbus serial connector (transmitter)
F. Power connector
G. DIN rail connector
1.6Default web pages
The EtherNet/IP Module is preloaded with the Emerson standard web pages. These web
pages allow the user to view process data and alerts, to configure the most commonly
used parameters on the transmitter, to perform maintenance procedures, and to
download support files from the device.
1.7Alternative web pages
To support the petroleum measurement or concentration measurement application,
Micro Motion supplies alternate sets of web pages and configuration files. These are
available for download from the Emerson web site.
8Micro Motion EtherNet/IP Module
User GuideInstallation
MMI-20019808April 2022
2Installation
2.1Components
Ensure that you have all required components:
• Micro Motion EtherNet/IP Module
• Power connector
• Micro Motion EtherNet/IP Resource CD
— Micro Motion EtherNet/IP Module User Manual
— EDS file
— MicroMotion Ethernet Config Tool
• Configuration cable
• Modbus serial cable and connector (included)
• Ethernet cable and connector (not included)
User Guide9
InstallationUser Guide
April 2022MMI-20019808
2.2Set up the module with MVD Direct Connect
Use the following procedures only if you are installing the module with MVD Direct
Connect.
Figure 2-1: MVD Direct Connect installations – Integral core processor, no I.S. barrier
A. Core processor
B. Sensor
C. User-supplied power cable
D. User-supplied RS-485 cable
E. DC power supply
F. Remote host
10Micro Motion EtherNet/IP Module
User GuideInstallation
MMI-20019808April 2022
Figure 2-2: MVD Direct Connect installations – Remote core processor, no I.S. barrier
A. Junction box
B. Sensor
C. Micro Motion 9-wire cable
D. DC power supply
E. User-supplied power cable
F. User-supplied RS-485 cable
G. Core processor
H. Remote host
User Guide11
InstallationUser Guide
April 2022MMI-20019808
Figure 2-3: MVD Direct Connect installations – Integral core processor, I.S. barrier
A. Core processor
B. Sensor
C. 4-wire cable
D. Barrier
E. User-supplied RS-485 cable
F. User-supplied power cable
G. DC power supply
H. Remote host
B. Sensor
C. Micro Motion 9-wire cable
D. 4-wire cable
E. Core processor
F. Barrier
G. User-supplied RS-485 cable
H. User-supplied power cable
I. DC power
J. Remote host
K. Hazardous area
L. Safe area
User Guide13
InstallationUser Guide
April 2022MMI-20019808
2.2.1Installing the MVD Direct Connect I.S. barrier
This step is required only for installations that include the MVD Direct Connect I.S. barrier.
Refer to Figure 2-3 and Figure 2-4.
Figure 2-5: Barrier dimensions in inches and (mm)
2.2.2
A. For mounting on 35 mm DIM rail
Wiring at the MVD Direct Connect I.S. barrier
This step applies only to installations that include the MVD Direct Connectc I.S. barrier.
Refer to Figure 2-3 and Figure 2-4.
Procedure
1. Conect the core processor to the barrier:
a) Connect the RS-485 wires from the core processor to the I.S. RS-485
terminals at the barrier (terminals 43 and 44), matching A and B. See
Table 2-1 and Figure 2-6. If you are using Micro Motion 4-wire cable, you can
identify the wires by color.
b) Connect the power supply wires from the core processor to the I.S. VDC
terminals at the barrier (terminals 42 and 41), matching positive and
negative (+ and –). See Table 2-1 and Figure 2-6. Do not terminate the
shields at the barrier.
14Micro Motion EtherNet/IP Module
User Guide
MMI-20019808April 2022
Table 2-1: Core processor terminals and barrier I. S. terminals
Installation
FunctionWire color (Micro
Motion 4-wire cable
RS-485 AWhite343
RS-485 BGreen444
VDC +Red142
VDC -Black241
2. Connect RS-485 wires to the non-I.S. RS-485 terminals at the barrier (terminals 13
and 14). See Figure 2-6. These wires will be used in the next step to connect the
barrier to the remote host. Do not terminate the shields at the barrier.
3. Connect power supply wires to the non-I.S. VDC terminals at the barrier (terminals
11 and 12). See Figure 2-6. These wires will be used in the next step to connect the
barrier to the power supply.
Figure 2-6: Barrier terminals
Core processor
terminals
Barrier I.S.
terminals
A. I.S. terminals for conection to core processor
B. I.S. terminals for conection to remote host and power supply
2.2.3
User Guide15
Wiring to the remote host
This step is required for all MVD Direct Connect installations.
Procedure
1. At the remote host, open the wiring compartment and identify the RS-485
terminals. Refer to the vendor documentation if required.
2. If you are connecting the RS-485 wires directly from the core processor (see Figure
2-1 and Figure 2-2):
a) Connect the RS-485 wires from the core processor (for the Standard Core
Processor, refer to Figure 2-7 and for the Enhanced Core Processor, refer to
Figure 2-8) to the RS-485 terminals at the remote host.
b) Do not terminate the shield, braid, or drain wire(s) at the remote host.
InstallationUser Guide
April 2022MMI-20019808
c) Do not terminate the RS-485 lines using the standard 60-ohm termination
resistor. If possible, do not terminate the RS-485 lines at all. If the RS-485
cable is 1000 feet (300 meters) long or longer, and termination is required,
the total termination must be 175 ohm or above.
Figure 2-7: Standard Core Wiring
A. Standard Core Processor
B. MVD Direct Connect Barrier
C. To Host
D. Ethernet IP Model
E. Power Supply
F. PC Connector
G. DB9 RS485
H. Ethernet Power Module 24V DC
16Micro Motion EtherNet/IP Module
User Guide
Installation
MMI-20019808April 2022
Figure 2-8: Enhanced Core Wiring
A. Enhanced Core Processor
B. MVD Direct Connect Barrier
C. To Host
D. Ethernet IP Model
E. Power Supply
F. PC Connector
G. DB9 RS485
H. Ethernet Power Module 24V DC
3. If you are connecting the RS-485 wires from the I.S. barrier (see Figure 2-3 and
Figure 2-4).
a) Connect the RS-485 wires from the barrier (see Figure 2-6) to the RS-485
terminals at the remote host.
b) Terminate the shields at the remote host.
User Guide17
InstallationUser Guide
April 2022MMI-20019808
c) The barrier contains internal pull-up/pull-down and termination resistors. Do
not add external resistors.
4. Close the wiring compartment.
2.2.4Wiring to the power suppy
This step is required for all MVD Direct Connect installations.
Procedure
1. You may connect multiple MVD Direct Connect installations to a single power
supply, as long as each installation receives sufficient power.
2. If you are connecting the power supply wires directly from the core processor (see
Figure 2-1 and Figure 2-2):
a) Do not connect any other equipment to the power supply used for MVD
Direct Connect installations.
b) Connect the power supply wires from the core processor (for the Standard
Core Processor, refer to Figure 2-9 and for the Enhanced Core Processor,.
refer to Figure 2-10), matching positive and negative (+ and –).
18Micro Motion EtherNet/IP Module
User GuideInstallation
MMI-20019808April 2022
Figure 2-9: Standard Core Wiring
A. Standard Core Processor
B. MVD Direct Connect Barrier
C. To Host
D. Ethernet IP Model
E. Power Supply
F. PC Connector
G. DB9 RS485
H. Ethernet Power Module 24V DC
User Guide19
Installation
User Guide
April 2022MMI-20019808
Figure 2-10: Enhanced Core Wiring
A. Enhanced Core Processor
B. MVD Direct Connect Barrier
C. To Host
D. Ethernet IP Model
E. Power Supply
F. PC Connector
G. DB9 RS485
H. Ethernet Power Module 24V DC
3. If you are connecting the power supply wires from the I.S. barrier (see Figure 2-3
and Figure 2-4):
a) The power supply may be used to power other equipment.
b) Connect the power supply wires from the barrier (see Figure 2-6), matching
positive and negative (+ and –).
20Micro Motion EtherNet/IP Module
User GuideInstallation
MMI-20019808April 2022
2.2.5Grounding
This step is required for all MVD Direct Connect installations.
NOTICE
Improper grounding could cause measurement error. To reduce the risk of measurement
error:
• Ground the meter to earth, or follow ground network requirements for the facility.
• For installation in an area that requires intrinsic safety, refer to the appropriate Micro
Motion approval documentation.
• For hazardous area installations in Europe, refer to standard EN 60079-14 if national
standards do not apply.
The sensor/core processor assembly (see Figure 2-1 and Figure 2-3) or the sensor alone
(see Figure 2-2 and Figure 2-4) must be grounded. To ground these components, see the
sensor installation manual.
If your installation includes a remote core processor (see Figure 2-2 and Figure 2-4), it
must be grounded. To ground the remote core processor:
• The core processor has two internal ground screws: one 4-wire ground screw and one
9-wire ground screw. Do not use the 4-wire ground screw. The 9-wire ground screw
may be used (see Figure 2-11). To access the 9-wire ground screw, remove the core
processor end-cap (see Figure 2-12).
• Use copper wire, 14 AWG (2,0 mm2) or larger, for grounding.
• Keep all ground leads as short as possible, less than 1 ohm impedance.
• Connect ground leads directly to earth, or follow plant standards.
If your installation includes the MVD Direct Connect I.S. barrier (see Figure 2-3 and Figure
2-4), the barrier is not grounded. Do not ground the barrier.
User Guide21
Installation
April 2022MMI-20019808
Figure 2-11: Core Processor Components
A. Conduit Opening for 4-Wire Cable
B. Conduit Opening for 9-Wire Cable
C. Mounting Bracket
D. Core Processor Cover
E. 4 X Cap Screws (4mm)
F. Core Processor Housing
G. Endcap (to 9-Wire Ground Screw)
User Guide
Figure 2-12: Core Processor 9-wire ground screw
A. 9-wire ground screw
2.3Set up the transmitter
Use this procedure only if you are installing the module with a transmitter.
Procedure
1. Mount the transmitter and wire it to the sensor and to power.
2. Power up the transmitter.
3. Set the Modbus address on the transmitter to 1.
22Micro Motion EtherNet/IP Module
1
2
User GuideInstallation
MMI-20019808April 2022
4. If your transmitter does not support Modbus auto-detect, configure the RS-485
terminals as follows:
• Modbus RTU
• 38400 baud
• 2 stop bits
• No parity
Postrequisites
Continue to Mount, wire, and set the network settings.
2.4Mount, wire, and set the network settings
Use this procedure to mount, wire, and set the network settings for both the transmitter
and MVD Direct Connect configurations.
Procedure
1. Ensure that the following slot registers are available for use by the EtherNet/IP
Module:
• 655–750
• 751–846
If these slot registers are currently in use, you must reprogram your Modbus
interface.
2. Mount the EtherNet/IP Module on the DIN rail.
Figure 2-13: Snap on
User Guide23
2
1
Installation
User Guide
April 2022MMI-20019808
Figure 2-14: Snap off
3. Wire the EtherNet/IP Module to power (24 VDC).
Figure 2-15: Power connections on the EtherNet/IP module
A. 24 VDC
B. Ground
4. Install the Modbus serial cable between the EtherNet/IP Module and the RS-485
terminals on the transmitter (or the I.S. barrier, if present).
Figure 2-16: Modbus serial connector on the EtherNet/IP module
See Modbus terminals and Pin assignments (EtherNet/IP Module).
5. Set the configuration dip switches on the EtherNet/IP module as follows:
24Micro Motion EtherNet/IP Module
User Guide
Installation
MMI-20019808April 2022
• Switches 1–7: Off
• Switch 8: On
The IP addess is set to 192.168.0.1.
6. If you are using a Model 1500, Model 2500, or Series 3000 transmitter, ensure that
the RS-485 terminals are in RS-485 mode.
7. Cycle power to the transmitter and wait 15 seconds before applying power to the
EtherNet/IP Module.
8. Power up the EtherNet/IP Module.
The module will attempt to make a Modbus connection to the transmitter.
9. Is the Subnet Status LED (LED 5) green?
OptionDescription
YesContinue with these steps.
NoSee LED indicators.
10. Set the network settings for the EtherNet/IP Module.
a) Change the Ethernet address setting for your PC so that it is on the same
subnet as the device. When prompted, enter the following:
• IP address: 192.168.0.x, where x is something other than 1
• Subnet mask: 255.255.255.0
b) Disable the popup blocker on your web browser.
c) Use a crossover cable (or a standard cable with a switch) and your web
browser to connect to the device, using the IP address assigned in Step 6:
192.168.0.1.
d) At the login screen, log in as user admin. The default password is admin.
Ignore the auto-configuration popup window.
e) On the Network Settings page, change the settings as required, and close the
web browser.
f) At the EtherNet/IP Module, set all dip switches to Off.
g) Cycle power to the EtherNet/IP Module.
11. Connect the EtherNet/IP Module to the Ethernet network.
See Ethernet connector.
12. Wait for the auto-configuration process to complete.
Important
For initial startup, you must use the auto-configuration process to ensure that
device memory is completely set up.
13. Add the EtherNet/IP Module to the Ethernet network control system. The EDS file is
available on the Resource CD, the EtherNet/IP Module (download from
Administration page), and the Emerson web site.
User Guide25
Installation
April 2022MMI-20019808
Postrequisites
For more information on transmitter installation and wiring, see your transmitter
installation manual. For information on configuring the RS-485 terminals and making an
RS-485 connection, see your transmitter configuration manual.
User Guide
2.4.1Modbus terminals
TransmitterRS-485/ARS-485/B
Model 15003334
Model 1700 with analog outputs56
Model 25003334
Model 2700 with analog outputs56
Model 3500 with screw-type or solder-tail
terminals
• Windows NT v4.0 or higher, Windows 2000, or Windows XP
• Internet Explorer v4.01 SP1 or higher
2.5.2
26Micro Motion EtherNet/IP Module
Install the Ethernet Config Tool
Procedure
1. Install the software program. Locate and run the EtherNet/IP Module setup
program on the EtherNet/IP Module Resource CD and follow the on-screen
instructions.
2. Connect the configuration cable from your PC to the EtherNet/IP Module.
User GuideInstallation
MMI-20019808April 2022
Note
For information on the Micro Motion Ethernet Config Tool user interface, see the
Anybus Communicator manual.
1. From your browser, login to the EtherNet/IP Module as user admin.
2. Choose one of the following:
• NOTICE
Wait for the web pages to automatically configure the EtherNet/IP Module.
• Use the Device Configuration page to configure the EtherNet/IP Module.
3. Set up I/O at your Ethernet host by doing one of the following:
• If you are not using RSLogix, use your standard method. For information on the
I/O assemblies, see I/O data.
• If you are using RSLogix, select ETHERNET-MODULE - Generic Ethernet Module
and enter the required information.
28Micro Motion EtherNet/IP Module
User GuideBasic network configuration
MMI-20019808April 2022
3Basic network configuration
3.1TCP/IP settings
To participate on the Ethernet network, the EtherNet/IP Module needs a valid TCP/IP
configuration.
The EtherNet/IP Module can retrieve the TCP/IP settings from a DHCP or BootP server. If no
such server is found, the EtherNet/IP Module uses the settings from the system file
\ethcfg.cfg. If this file is not found, or the settings are invalid, the EtherNet/IP Module
will halt and report an error on the status LED. However, the network configuration may
still be accessed via the Ethernet Config Tool.
You can define the TCP/IP settings for the EtherNet/IP Module in the following ways:
• Micro Motion Network Configuration web page (recommended)
• Configuration switches on the device
3.1.1
3.1.2
• Ethernet Config Tool
• System file \ethcfg.cfg on the device
Micro Motion web page for network configuration
The Network Configuration page, in the Micro Motion web pages, allows you to set the IP
address, gateway address, and subnet address. If you connect to the EtherNet/IP Module
using a crossover cable and the default IP address, you can set all three parameters. The
changes will take effect at the next connection.
Configuration switches
If the configuration switches on the EtherNet/IP module are set to any non-zero value, the
device is locked to the following network settings:
Table 3-1: Network settings, locked
ParameterValue
IP address192.168.0.x where x is determined by the switches
Gateway192.168.0.255
Subnet255.255.255.0
DHCPOFF
User Guide29
Basic network configurationUser Guide
April 2022MMI-20019808
Table 3-2: Network settings using switches
SwitchIP address
12345678
OFFOFFOFFOFFOFFOFFOFFON192.168.0.1
OFFOFFOFFOFFOFFOFFONOFF192.168.0.2
OFFOFFOFFOFFOFFOFFONON192.168.0.3
………………………
ONONONONONONONOFF192.168.0.254
ONONONONONONONONInvalid
3.1.3Ethernet Config Tool
See the Anybus Communicator manual for instructions.
Note
If you change the network settings using the Ethernet Config Tool, you will not be able to
use the Micro Motion web pages to change network settings in the future. All future
changes to network settings must be performed using the Ethernet Config Tool.
3.1.4
Set the configuration switches with ethcfg.cfg file
To set the network settings using the \ethcfg.cfg file:
Procedure
1. Set all configuration switches on the device to OFF.
2. Make a connection to the device from the Ethernet Config Tool and disable TCP/IP
Settings (Fieldbus parameter section). Alternatively, you can access the TCP/IP
parameters using the TCP/IP Interface Object.
3. From the FTP server, access and edit \ethcfg.cfg as desired.
In this scenario, if no \ethcfg.cfg file is found, the EtherNet/IP Module will
attempt to retrieve the settings via DHCP for 30 seconds. If the attempt fails, the
EtherNet/IP Module will halt and indicate an error via the LEDs.
See the Anybus Communicator manual for more information.
30Micro Motion EtherNet/IP Module
User GuideBasic network configuration
MMI-20019808April 2022
3.1.5IP access control
You can limit the set of IP addresses that are allowed to connect to the EtherNet/IP
Module. This information is stored in the system file \ip_accs.cfg.
Sample file:
[Web]
xxx.xxx.xxx.xxx (All nodes listed can access the EtherNet/IP
Module web
server)
...
[FTP]
xxx.xxx.xxx.xxx (All nodes listed can access the EtherNet/IP
Module FTP
server)
...
[EtherNet/IP]
xxx.xxx.xxx.xxx (All nodes listed can access the EtherNet/IP
Module via
EtherNet/IP)
...
[All]
xxx.xxx.xxx.xxx (Fallback setting; used when one or more of the
above
keys is omitted)
...
3.2Modbus serial network settings
The default parameters for the Modbus serial network are listed in the following table.
Parameter
Baud384001200 to 57600
Data bits8 (Modbus RTU)7 (Modbus ASCII)
ParityNoneNone
Physical layerRS485RS485 (required for EtherNet/IP
Start bits11
Stop bits
(1) For baud rates of 38400 and above, 2 stop bits are required.
(1)
These must match the RS-485 parameters configured in the transmitter. To change them
in the EtherNet/IP Module, you must use the Ethernet Config Tool. See the Anybus
Communicator manual for more information.
Default settingValid values
21
8 (Modbus RTU)
Odd
Even
Module)
2
User Guide31
Basic network configurationUser Guide
April 2022MMI-20019808
32Micro Motion EtherNet/IP Module
User GuideEmerson web server
MMI-20019808April 2022
4Emerson web server
The configuration and administration functions of the Micro Motion EtherNet/IP Module
are implemented as web pages on the device. Users use their web browsers to connect to
the web server. Your browser will automatically directed to the Emerson web pages.
4.1Web server access information
Ports
The web server communicates through port 80.
Users
Two users are predefined for the Emerson web pages. You can change the passwords, but
you cannot add or delete users.
UsernameDefault passwordDescription
adminadminComplete access to all functions on the Emerson
web pages
operatoroperatorRead-only access to the Emerson web pages
4.2Emerson EtherNet/IP Module web pages
When you connect to the EtherNet/IP Module, you are prompted for a user name and
password, then directed to the EtherNet/IP Module home page.
Use the web pages to do the following tasks:
• Administer passwords and the EDS file download
• Administer network configurations
• Monitor, configure, and maintain process data, totalizers, Smart Meter Verification,
etc.
Note
If the EtherNet/IP Module loses communication with the Micro Motion device, the web
page will indicate the communication error between the EIP module and the Micro Motion
transmitters.
For more details, refer to the transmitter configuration manual.
User Guide33
Emerson web serverUser Guide
April 2022MMI-20019808
34Micro Motion EtherNet/IP Module
User GuideIntegrate with Rockwell programming software
MMI-20019808April 2022
5Integrate with Rockwell
programming software
5.1Integrate with Rockwell versions 20 or later
If you have Rockwell RSLogix 5000 or Studio 5000 Logix Designer version 20 or later
firmware and programming software, use this section to load the Electronic Data Sheet
(EDS) and commission the device using the RSLogix 5000 programming package.
Prerequisites
If you are upgrading the EDS from an older version, unregister the old EDS first using the
RSLogix EDS Hardware Installation Tool at Tools→EDS Hardware Installation Tool.
Procedure
1. Connect to the EtherNet/IP module through your web browser and download the
EDS file.
See Emerson web server.
2. In RSLogix 5000, choose Tools→EDS Hardware Installation Tool and register the
EtherNet/IP module EDS file.
3. If you have an established RSLogix Ethernet network, skip this step. If not, follow
these steps to create a network:
a) From RSLogix 5000, right-click the controller/backplane in the tree view.
b) Select New Module.
c) Select the appropriate Ethernet card.
d) Select Create.
e) Enter the Name.
f) Enter the IP Address.
g) Select the Slot where your Ethernet card is located.
h) Select OK.
i) On the Select Module Type window, select Close.
4. To add the Micro Motion EtherNet/IP module to the RSLogix 5000 Ethernet
network, right-click the Ethernet network and select New Module.
a) From the Select Module Type window, select the following options and select
Create:
Pane
Module Type Category FiltersCommunications Adapter
Module Type Vendor FiltersMicro Motion, Inc.
User Guide35
Option
Integrate with Rockwell programming softwareUser Guide
April 2022MMI-20019808
The New Module properties dialog displays. The EDS generates an Add On
Profile (AOP) for the Micro Motion Ethernet/IP module that loads all the
variables into the controller's input and output image tables as named
variables with the correct data types.
b) Enter the Name of the module.
c) Enter the IP Address.
5. Change or keep the current connection type.
Change the connection typeGo to Step 6
Keep the currect connection typeGo to Step 7
6. To change the connection type, select the General tab, change the connection
type.
a) Select the Change button.
b) Select the current connection.
Default = IO Connection
A pull-down menu with all the available connection types displays.
c) Select your appropriate connection, and press OK .
Important
If you change the connection after the device goes online, take the controller
offline for the change to take effect.
7. To keep the current connection type:
a) Select the current connection.
Default = IO Connection
A pull-down menu with all available connection types displays.
b) Select a connection and press OK.
Important
If you change the connection after the device goes online, take the controller
offline for the change to take effect.
8. On the New Module properties dialog, select OK.
9. On the Select Module Type dialog, select Close.
10. Open Controller Tags to verify the data organization.
5.2
36Micro Motion EtherNet/IP Module
Integrate with Rockwell versions 19 or earlier
Use this section if you have Rockwell RSLogix 5000 version 19 or earlier firmware and
programming software. These early versions do not support Micro Motion Ethernet/IP
User GuideIntegrate with Rockwell programming software
MMI-20019808April 2022
module Electronic Data Sheet (EDS)-generated Add On Profile (AOP). Instead, you must
use the generic module hardware tree.
Procedure
1. Connect to the EtherNet/IP module through your web browser and download the
EDS file.
See Emerson web server.
2. In RSLogix 5000, choose Tools→EDS Hardware Installation Tool and register the
EtherNet/IP module EDS file.
3. If you have an established RSLogix Ethernet network, skip this step. If not, follow
these steps to create a network:
a) From RSLogix 5000, right-click the controller/backplane in the tree view.
b) Select New Module.
c) Select the appropriate Ethernet card.
d) Select Create.
e) Enter the Name.
f) Enter the IP Address.
g) Select the Slot where your Ethernet card is located.
h) Select OK.
i) On the Select Module Type window, select Close.
4. From RSLogix 5000, choose File→New.
5. Select your version from the Revision drop-down menu.
6. Enter a Name for your application.
7. Select the Slot where your Ethernet card is located.
8. Press OK.
9. To add the Micro Motion EtherNet/IP module to the RSLogix 5000 Ethernet
network, right-click the Ethernet network and select New Module.
a) Select the ETHERNET-MODULE Generic Ethernet Module and press OK.
10. Select the appropriate assembly instances for your application. Enter the assembly
numbers in the generic module setup, along with the data sizes.
Note
If your Comm Format is anything other than Data-INT, the data sizes will be
different from the sizes shown in the following tables.
Table 5-1: Standard configuration
ParameterEntry
NameMicroMotion_EIP
DescriptionMicro Motion EtherNet/IP Module Basic
Configuration
User Guide37
Integrate with Rockwell programming softwareUser Guide
April 2022MMI-20019808
Table 5-1: Standard configuration (continued)
ParameterEntry
Comm FormatData-INT
IP AddressYour IP address
InputAssembly Instance: 100
Size: 20
OutputAssembly Instance: 150
Size: 7
ConfigurationAssembly Instance: 3
Size: 0
Table 5-2: Concentration measurement
ParameterEntry
NameMicroMotion_EIP
DescriptionMicro Motion EtherNet/IP Module CM
Comm FormatData-INT
IP AddressYour IP address
InputAssembly Instance: 100
Size: 42
OutputAssembly Instance: 150
Size: 7
ConfigurationAssembly Instance: 3
Size: 0
Table 5-3: Petroleum measurement
ParameterEntry
NameMicroMotion_EIP
DescriptionMicro Motion EtherNet/IP Module PM
Comm FormatData-INT
IP AddressYour IP address
InputAssembly Instance: 100
Size: 30
OutputAssembly Instance: 150
Size: 7
38Micro Motion EtherNet/IP Module
User GuideIntegrate with Rockwell programming software
MMI-20019808April 2022
Table 5-3: Petroleum measurement (continued)
ParameterEntry
ConfigurationAssembly Instance: 3
Size: 0
11. Press OK.
12. Open Controller Tags to see the data organization.
13. Use your preferred programming techniques to convert the data from the input and
output image tables to the correct data types.
If you are not using RSLogix or Studio 5000 Logix designer, use your standard
method. For information on I/O assemblies, see I/O data.
User Guide39
Integrate with Rockwell programming softwareUser Guide
April 2022MMI-20019808
40Micro Motion EtherNet/IP Module
User GuideTroubleshooting
MMI-20019808April 2022
6Troubleshooting
6.1LED indicators
LED
number
AModule Status
BNetwork Status
NameStatusDescription
(EtherNet)
(EtherNet)
OffNo power applied to the module.
Solid greenThe module is operating correctly.
Flashing greenStandby. The module has not been initialized.
Flashing redMinor fault. The module may or may not be able
to recover.
Solid redMajor fault. No recovery is possible. The module
must be retuned to Micro Motion for repair. See
the manual for the return policy.
Flashing green/redSelf-test.
OffThe module has not power or no IP address has
been assigned.
Solid greenThe module has at least one established
EtherNet/IP connection.
Flashing greenThere are no EtherNet/IP connections established
to the module.
Flashing redOne or more of the connections to this module
has timed out.
Solid redThe module has detected that its IP address is
already in use.
Flashing green/redSelf-test.
CLinkOffThe module does not sense a link.
GreenThe module is connected to an Ethernet network.
DActivityFlashing greenPacket is received or transmitted.
User Guide41
TroubleshootingUser Guide
April 2022MMI-20019808
LED
number
ESubnet Status
FDevice Status
NameStatusDescription
OffPower off.
(Modbus
Serial)
(Modbus
Serial)
Flashing greenRunning correctly, but one or more transaction
GreenRunning.
RedTransaction error/timeout or network stopped.
Flashing redMissed transactions.
OffPower off.
Flashing red/greenConfiguration missing or invalid.
RedContact customer service.
Flashing redContact customer service.
GreenInitializing.
Flashing greenConfiguration OK.
6.2Common problems
errors has occurred.
Check the Modbus serial network wiring and
configuration, especially the baud.
6.2.1Configuration upload or download problem
Cause
The serial communication failed.
Recommended actions
Try again.
6.2.2
Red Config Line LED
The Config Line LED turns red in the Ethernet Config Tool.
Cause
The serial communication failed.
Recommended actions
Try again.
42Micro Motion EtherNet/IP Module
User Guide
MMI-20019808April 2022
Troubleshooting
6.2.3Cannot connect to the EtherNet/IP Module
The serial port seems to be available, but it is not possible to connect to the EtherNet/
IPModule.
Cause
The serial port may be in use by another application.
Recommended actions
1. Exit the EtherNet/IP Module Configuration Tool and close all other applications,
including the ones in the system tray.
2. Try again.
3. Select another serial port.
4. Try again.
6.2.4
6.2.5
Poor performance
Cause
The serial communication failed.
Recommended actions
1. In the Ethernet Config Tool, right-click Sub-Network in the Navigation window.
a) Select Sub-Network Status to see status and diagnostic information
about the Modbus serial network.
b) If the EtherNet/IP Module reports a large number of re-transmissions,
check your cabling or try a lower baud rate setting for the Modbus serial
network, if possible.
2. Is the Sub-Net Monitor in the Ethernet Config Tool active?
The sub-network monitor has a negative influence on the overall performance
of the gateway, and should be used only when necessary.
3. Is the Node Monitor of the Ethernet Config Tool active?
The node monitor has a negative influence on the overall performance of the
gateway, and should be used only when necessary.
No Modbus serial network functionality
Recommended actions
1. Connect to the device and login to the webserver. Allow the web server to
automatically configure the device's process variable slot.
2. Use the Data logger functionality of the Ethernet Config Tool to record the
serial data communication on the sub-network.
3. If no data is being transmitted, use the Ethernet Config Tool to record the serial
data communication on the sub-network.
User Guide43
TroubleshootingUser Guide
April 2022MMI-20019808
4. If no data is being received, check the cables and connections. Also verify that
the transmitted data is correct.
6.2.6Process variables display or report 0
Recommended actions
Verify the Modbus connection between the EtherNet/IP Module and the device.
44Micro Motion EtherNet/IP Module
User GuideConnector pin assignments
MMI-20019808April 2022
AConnector pin assignments
A.1Ethernet connector
PinSignal
HousingCable shield
1TD+
2TD–
3RD+
4Termination
5Termination
6RD–
7Termination
8Termination
A.2Power connector
PinDescription
124 VDC
2Ground
• Use 60/75 or 75 x C copper (CU) wire only.
• The terminal tightening torque must be between 5 and 7 lbs-in (0.5 to 0.8 Nm).
A.3Micro Motion Ethernet Config Tool installation
(optional)
Related information
Install the Ethernet Config Tool
User Guide45
Connector pin assignmentsUser Guide
April 2022MMI-20019808
A.3.1Ethernet Config Tool system requirements
• Pentium 133 MHz or higher
• 10 MB of free space
• 8 MB RAM
• Windows NT v4.0 or higher, Windows 2000, or Windows XP
• Internet Explorer v4.01 SP1 or higher
A.3.2Install the Ethernet Config Tool
Procedure
1. Install the software program. Locate and run the EtherNet/IP Module setup
program on the EtherNet/IP Module Resource CD and follow the on-screen
instructions.
2. Connect the configuration cable from your PC to the EtherNet/IP Module.
Note
For information on the Micro Motion Ethernet Config Tool user interface, see the
Anybus Communicator manual.
The Modbus serial network is based on an RS-485 physical layer.
A.4.1Bias resistors
When idle, RS-485 enters an indeterminate state, which may cause the serial receivers to
pick up noise from the serial lines and interpret this as data. To prevent this, the serial lines
should be forced into a known state using pull-up and pull-down resistors, commonly
known as bias resistors.
The bias resistors forms a voltage divider, forcing the voltage between the differential pair
to be higher then the threshold for the serial receivers, typically >200 mV. Note that bias
resistors shall only be installed on one node. Installing bias resistors on several nodes may
compromise the signal quality on the network and cause transmission problems.
A.4.2
A.4.3
Termination
To avoid reflections on the serial lines, it is important to properly terminate the subnetwork by placing termination resistors between the serial receivers near the end nodes.
Additionally, if the distance from the EtherNet/IP Module to the transmitter is greater than
100 feet, Micro Motion recommends adding the termination resistors.
The resistor value should ideally match the characteristic impedance of the cable, typically
100 to 120 Ω.
Pin assignments (EtherNet/IP Module)
Figure A-1: Female connection
Pin
15 V output (100mA max)
2Unused
3Unused
Description
4Unused
5Ground
6Unused
7Unused
8RS-485/A (Tx+)
9RS-485/B (Tx–)
(housing)Cable shield
User Guide47
Connector pin assignmentsUser Guide
April 2022MMI-20019808
A.5Typical connection
A. Signal ground
B. Cable shield
C. Node
D. Signal ground
48Micro Motion EtherNet/IP Module
User Guide
MMI-20019808April 2022
Device profile
BDevice profile
B.1Object classes
Table B-1 lists and describes all object classes supported by the EtherNet/IP Module.
Table B-1: Object classes and descriptions
ObjectClass IDOptional/
required
Identity0x01RequiredContains information
Message Router0x02RequiredTracks the accessibility
Assembly0x04RequiredContains a list of
Port0xF4Required
TCP/IP Interface0xF5RequiredGroups settings related
Ethernet Link0xF6RequiredGroups diagnostic
Diagnostic0xAAOptionalGroups diagnostic
Parameter Data Input
Mapping
0xBOOptionalUsed for acyclic access
Description
that uniquely describes
the device
of the object classes
and instances
attributes that data
can be written to (sink)
or read from (source)
to TCP/IP.
information for the
Ethernet interface
information for the
fieldbus interface
to input data
Parameter Data
Output Mapping
0xB1OptionalUsed for acyclic acces
to output data
B.2Object details
B.2.1Identity Object, Class 01h
This object provides identification of and general information about the device. It contains
informational attributes that uniquely describe the device.
Example: The use of attributes Vendor ID, Device Type, Product Code, and Serial Number
together uniquely identify this device.
6GetSerial NumberUDINTSerial number(set at production)
7GetProduct NameSHORT_STRING“Micro Motion
EtherNet/IP
Module”
Name of product
Device status
Bit(s)
0Module Owned
1(reserved)
2Configured
Name
3(reserved)
4... 7Extended Device Status:
ValueMeaning
0000bUnknown
0010bFaulted I/O Connection
50Micro Motion EtherNet/IP Module
User Guide
MMI-20019808April 2022
Bit(s)Name
0011bNo I/O connection established
0100bNon-volatile configuration bad
0110bConnection in Run mode
0111bConnection in Idle mode
(other)(reserved)
8Set for minor recoverable faults
9Set for minor unrecoverable faults
10Set for major recoverable faults
11Set for major unrecoverable faults
12... 15(reserved)
Reset service
When the Identity Object receives a Reset request, it:
Device profile
B.2.2
B.2.3
• Determines if it can provide the type of reset requested
• Responds to the request
• Attempts to perform the type of reset requested
Message Router, Class 02h
The Message Router Object provides a messaging connection point through which a Client
may address a service to any object class or instance residing in the physical device.
Assembly Object, Class 04h
The Assembly Object binds attributes of multiple objects, which allows data to or from
each object to be sent or received over a single connection. Assembly objects can be used
to bind input data or output data. The terms “input” and “output” are defined from the
network's point of view. An input produces data on the network and an output consumes
data from the network.
This object provides access to the I/O Data in the Input and Output Data areas in the Micro
Motion EtherNet/IP Module.
Instance attributes - Instance/Connection Point 64h
This instance corresponds to I/O Data (Input) in the Micro Motion EtherNet/IP Module. The
EtherNet/IP Module supports two different configurations. Specific input assembly
attributes depend on the configuration in use.
ConfigurationInput assembly attributes
BasicSee Input assembly for standard configuration
Concentration measurementSee Input assembly for concentration measurement configuration
Note
The default input data size is non-zero. The actual size depends on the configuration in
use. If the I/O input data size is set to 0, this instance will NOT be initialized.
#AccessNameTypeValueDescription
3GetDataArray of BYTE-Data produced by the Micro Motion
EtherNet/IP Module
Instance attributes - Instance/Connection Point 96h
This instance corresponds to I/O Data (Output) in the Micro Motion EtherNet/IP Module.
The EtherNet/IP Module supports two different configurations. Specific input assembly
attributes depend on the configuration in use.
Configuration
BasicSee Output assembly for standard configuration
Concentration measurementSee Output assembly for concentration measurement configuration
Output assembly attributes
Note
The default output data size is non-zero. The actual size depends on the configuration in
use. If the I/O output data size is set to 0, this instance will NOT be initialized.
#
AccessNameTypeValueDescription
3SetDataArray of BYTE-Data consumed by the Micro
Motion EtherNet/IP Module
Note
Rockwell Automation PLCs have the first four bytes consumed by a device defined as
status information. This behavior is specific to devices from Rockwell Automation and is
not defined in the EtherNet/IP specification. However, since all known PLCs are
52Micro Motion EtherNet/IP Module
User GuideDevice profile
MMI-20019808April 2022
implemented this way, the Micro Motion EtherNet/IP Module adopts this behavior and
strips off the corresponding four bytes from the consumed data.
B.2.4Port Object, Class F4h
Supported services
Class services:
• Get Attribute Single
• Get Attribute All
Instance services:
• Get Attribute Single
• Get Attribute All
Class attributes
#AccessNameTypeValueDescription
1GetRevisionUINT0001hRevision 1
2GetMax InstanceUINT0002h2 is the highest instance number
3GetNo. of instancesUINT0001h1 instance is implemented
8GetEntry PortUINT0002hReturns the instance of the Port
object that describes the port.
9GetAll PortsArray of STRUCT0000h 0000hArray of structure containing
{UINT; UINT;}0000h 0000h
0004h 0002h
attributes 1 and 2 from each
instance. Instance 1 is at byte offset
4. Instance 2 is at byte offset 8, etc.
The 4 bytes at offset 0 shall be 0.
(Default)
Instance attributes, Instance 02h
#
AccessNameTypeValueComments
1GetPort TypeUINT0000hTCP/IP
2GetPort NumberUINT0002hPort 2
3GetPort ObjectStruct of:
Path SizeUINT0002h-
PathPadded EPATH20 F5 24 01hTCP class, Instance 1
4GetPort NameSHORT_STRING“TCP/IP”Name of port
8GetNode AddressPadded EPATH--
User Guide53
Device profileUser Guide
April 2022MMI-20019808
B.2.5TCP/IP Interface Object, Class F5h
This object groups TCP/IP-related settings.
Supported services
Class services:
• Get Attribute All
• Get Attribute Single
Instance services:
• Get Attribute All
• Get Attribute Single
• Set Attribute Single
Class attributes
#AccessNameTypeValueComments
1GetRevisionUINT0001hRevision 1
2GetMax InstanceUINT0001h1 is the highest instance number
3GetNo. of instancesUINT0001h1 instance is implemented
3Get/SetConfiguration Control DWORD-0: Configuration from non-volatile
4GetPort ObjectStruct of:
Path SizeUINT0002h2 words
PathPadded EPATH20 F6 24 01hPath to Ethernet Class, Instance 1
5Get/SetInterface
Configuration
IP AddressUDINT-IP address
DWORD00000016hAttribute #5 is settable. Capable of
obtaining network configuration
via DHCP.
memory
2: Configuration from DHCP
Struct of:
Subnet MaskUDINT-Subnet mask
Gateway AddressUDINT-Gateway Address
Name Server 1UDINT-Primary DNS
Name Server 2UDINT-Secondary DNS
54Micro Motion EtherNet/IP Module
User GuideDevice profile
MMI-20019808April 2022
#AccessNameTypeValueComments
Domain NameSTRING-Default domain name
6Get/SetHost NameSTRING-Host name
B.2.6Ethernet Link Object, Class F6h
This object groups diagnostic information for the Ethernet interface.
Supported services
Class services:
• Get Attribute All
• Get Attribute Single
Instance services:
• Get Attribute All
• Get Attribute Single
Class attributes
#AccessNameTypeValueDescription
1GetRevisionUINT0001hRevision 1
2GetMax InstanceUINT0001h1 is the highest instance number
3GetNo. of instancesUINT0001h1 instance is implemented
Instance attributes
#
AccessNameTypeValueComments
1GetInterface SpeedUDINT10 or 100Actual Ethernet interface speed
2GetInterface FlagsDWORD--
3GetPhysical AddressArray of 6 USINTS(MAC ID)Physical network address
B.2.7Diagnostic Object, Class AAh
This object groups diagnostic information for the fieldbus interface.
Supported services
Class services: Get Attribute All
Instance services: Get Attribute Single
Class attributes
#
AccessNameTypeValueDescription
1GetRevisionUINT0001hRevision 1
User Guide55
Device profileUser Guide
April 2022MMI-20019808
Instance attributes
#AccessNameTypeDescription
01h GetModule serial number UDINTSerial number
02h GetVendor IDUINTManufacturer Vendor ID
03h GetFieldbus TypeUINTFieldbus Type
04h GetModule Software
version
0Ah GetModule TypeUINTModule Type
0Fh GetIN cyclic I/O lengthUINTSize of I/O Input area (in bytes)
11h GetIN total lengthUINTTotal number of IN bytes supported
12h GetOUT cyclic I/O lengthUINTSize of I/O Output area (in bytes)
14h GetOUT total lengthUINTTotal number of OUT bytes supported
UINTModule software version
B.2.8Parameter Data Input Mapping Object, Class B0h
This object can be used to access Input Data acyclically, and is set up dynamically based on
the Parameter Data Mailbox initialization (see Input parameters (explicit data) for standard
configuration).
Supported services
Class services: Get Attribute All
Instance services: Get Attribute Single
Class attributes
#
AccessNameTypeValueDescription
1GetRevisionUINT0001hRevision 1
Instance attributes, Instance 01h
Each attribute corresponds to a block of Input Data.
#
AccessNameTypeDescription
01h GetDataArray of USINTMapped block of Input Data
02h GetDataArray of USINTMapped block of Input Data
...
32h GetDataArray of USINTMapped block of Input Data
The specific parameters in the block depend on the configuration in use.
Configuration
BasicSee Input parameters (explicit data) for standard configuration
56Micro Motion EtherNet/IP Module
Input parameters (explicit data)
User GuideDevice profile
MMI-20019808April 2022
ConfigurationInput parameters (explicit data)
Concentration measurementSee Input parameters (explicit data) for concentration
measurement configuration
B.2.9Parameter Data Output Mapping Object, Class B1h
This object can be used to access Output Data acyclically, and is set up dynamically (see
Output parameters (explicit data) for standard configuration).
Supported services
Class services: Get Attribute All
Instance services:
• Get Attribute Single
• Set Attribute Single
Class attributes
#AccessNameTypeValueDescription
1GetRevisionUINT0001hRevision 1
Instance attributes, Instance 01h
#
AccessNameTypeDescription
01h Get/SetDataArray of USINTMapped block of Output Data
02h Get/SetDataArray of USINTMapped block of Output Data
...
32h Get/SetDataArray of USINTMapped block of Output Data
The specific parameters in the block depend on the configuration in use.
Configuration
BasicSee Output parameters (explicit data) for standard configuration
Concentration measurementSee Output parameters (explicit data) for concentration
Output parameters (explicit data)
measurement configuration
B.3I/O data
B.3.1Input assembly for standard configuration
ByteAccessNameTypeNotes
0–3GetMass flow rateFloat
4–7GetDensityFloat
User Guide57
Device profileUser Guide
April 2022MMI-20019808
ByteAccessNameTypeNotes
8–11GetTemperatureFloat
12–15GetVolume flow rate (liquid
volume)
16–19GetMass totalFloat
20–23GetVolume total (liquid
volume)
24–27GetDrive gainFloat
28–29GetStatus wordU16 or Word• For Model 1700 Analog, Model 2700 Analog,
30–31GetStatus wordU16 or Word• For Model 1700 Analog, Model 2700 Analog,
32–35GetGas standard volume flow
rate
FloatValid only when Gas Standard Volume is not
enabled.
Float
Model 1500 Analog, Model 2500, and all Series
3000 transmitters: SNS Status Word 1 (see
Status Word 1)
• For MVD Direct Connect and 9739 MVD
transmitters: SNS Status Word 2 (see Status
Word 2)
Model 1500 Analog, Model 2500, and all Series
3000 transmitters: SNS Status Word 2 (see
Status Word 2)
• For MVD Direct Connect and 9739 MVD
transmitters: SNS Status Word 1 (see Status
Word 1)
FloatValid only when Gas Standard Volume is enabled.
36–39GetGas standard volume totalFloatValid only when Gas Standard Volume is enabled.
B.3.2Output assembly for standard configuration
ByteAccessNameTypeNotes
0–3Get/SetExternal TemperatureFloat
4–7Get/SetExternal PressureFloat
8Get/SetStart/Stop TotalsByte0: Stop
1: Start
9Get/SetReset All Process TotalsByte0: No action
1: Reset
10Get/SetReset All Inventory TotalsByte0: No action
1: Reset
11Get/SetStart ZeroByte0: Abort or no action
1: Start
12–13Get/SetStart Smart Meter
Verification
WordSee Table B-20
58Micro Motion EtherNet/IP Module
User GuideDevice profile
MMI-20019808April 2022
B.3.3Input parameters (explicit data) for standard
configuration
To update any of these attribute values, the associated trigger byte must be toggled
before reading the attribute value (executing the Get service). See Output parameters
(explicit data) for standard configuration for more information on trigger bytes.
12hGetExternal temperature inputFloatNo trigger byte
13hGetExternal pressure inputFloatNo trigger byte
14hGetGas standard volume flow unitU1610hSee Table B-11
15hGetGas standard volume total/
inventory unit
16hGetSmart Meter Verification:
Status
17hGetSmart Meter Verification: Run
Count
18hGetSmart Meter Verification
Algorithm State
User Guide59
U1610hSee Table B-12
U1613hSee Table B-22
U1613h
U1611hSee Table B-21
Device profileUser Guide
April 2022MMI-20019808
AttributeAccessNameTypeTrigger Byte
WriteAttribute
19hGetSmart Meter Verification Abort
Code
1AhGetSmart Meter Verification State
at Abort
1BhGetSmart Meter Verification
Progress
1ChGetEnable/Disable Gas Standard
Volume Calculations
1DhGetSubnet communication status
(RS-485 connection to
transmitter)
U1611hSee Table B-23
U1611hSee Table B-24
U1612h% complete
U814h
U16No trigger byte0: Communications failure
Description
Any other value:
Communications good
B.3.4Output parameters (explicit data) for standard
configuration
Class B1h, Instance 01h
AttributeAccessNameTypeTrigger byte
write attribute
Description
01hGet/SetStandard or special mass flow
rate unit
02hGet/SetDensity unitU16See Table B-13
03hGet/SetTemperature unitU16See Table B-14
04hGet/SetStandard or special volume
flow rate unit
05hGet/SetPressure unitU16See Table B-15
06hGet/SetZero timeU16Seconds
07hGet/SetZero valueFloat
08hGet/SetGas Standard Volume Flow unit U16See Table B-11
09hGet/SetOutput state during Smart
Meter Verification
0AhGet/SetEnable/Disable Gas Standard
Volume Calculations
0BhGet/SetSmart Meter Verification Index U1616hSmart Meter Verification test
0ChGet/SetTrigger Byte-2U8
U16See Table B-7
U16See Table B-10
U160 = Last measured value
1 = Fault
U8
record.
0 = most recent
...
19 = oldest
0DhGet/SetTrigger Byte-3U8
60Micro Motion EtherNet/IP Module
User GuideDevice profile
MMI-20019808April 2022
AttributeAccessNameTypeTrigger byte
write attribute
0EhGet/SetTrigger Byte-6U8
0FhGet/SetTrigger Byte-9U8
10hGet/SetTrigger Byte-15U8
11hGet/SetTrigger Byte-17U8
12hGet/SetTrigger Byte-18U8
13hGet/SetTrigger Byte-16U8
14hGet/SetTrigger Byte-20U8
15hGet/SetTrigger Byte-23U8
16hGet/SetTrigger Byte-26U8
Description
B.3.5Input assembly for concentration measurement
configuration
ByteAccessNameTypeNotes
0–3GetMass flow rateFloat
4–7GetDensityFloat
8–11GetTemperatureFloat
12–15GetVolume flow rate (liquid
volume)
16–19GetMass totalFloat
20–23GetStandard volume flowFloat
24–27GetStandard volume totalFloat
28–31GetStandard volume inventory Float
32–35GetNet mass flowFloat
36–39GetNet mass totalFloat
40–43GetNetmass inventoryFloat
44–47GetNet volume flowFloat
48–51GetNet volume totalFloat
52–55GetNet volume inventoryFloat
56–59GetReference densityFloat
60–63GetSpecific gravityFloat
64–67GetConcentrationFloat
68–71GetDensity (fixed Baume
units)
Float
Float
72–75GetVolume total (liquid)Float
User Guide61
Device profile
User Guide
April 2022MMI-20019808
ByteAccessNameTypeNotes
76–79GetDrive gainFloat
80–81GetStatus wordU16 or Word• For Model 1700 Analog, Model 2700 Analog,
Model 1500 Analog, Model 2500, and all Series
3000 transmitters: SNS Status Word 1 (see
Status Word 1)
• For MVD Direct Connect and 9739 MVD
transmitters: SNS Status Word 2 (see Status
Word 2)
82–83GetStatus wordU16 or Word• For Model 1700 Analog, Model 2700 Analog,
Model 1500 Analog, Model 2500, and all Series
3000 transmitters: SNS Status Word 2 (see
Status Word 2)
• For MVD Direct Connect and 9739 MVD
transmitters: SNS Status Word 1 (Status Word
1)
B.3.6Output assembly for concentration measurement
configuration
ByteAccessNameTypeNotes
0–3Get/SetExternal TemperatureFloat
4–7Get/SetExternal PressureFloat
8Get/SetStart/Stop TotalsByte0: Stop
1: Start
9Get/SetReset All Process TotalsByte0: No action
1: Reset
10Get/SetReset All Inventory TotalsByte0: No action
1: Reset
11Get/SetStart ZeroByte0: Abort or no action
1: Start
12–13Get/SetStart Smart Meter
Verification
WordSee Table B-20
B.3.7Input parameters (explicit data) for concentration
measurement configuration
To update any of these attribute values, the associated trigger byte must be toggled
before reading the attribute value (executing the Get service). See Output parameters
(explicit data) for standard configuration for more information on trigger bytes.
12hGetExternal temperature inputFloatNo trigger byte
13hGetExternal pressure inputFloatNo trigger byte
14hGetSmart Meter Verification: Run
Count
15hGetSmart Meter Verification:
Status
16hGetSmart Meter Verification
Algorithm State
17hGetSmart Meter Verification Abort
Code
18hGetSmart Meter Verification State
at Abort
19hGetSmart Meter Verification
Progress
1AhGetConcentration units codeU813h
1BhGetDerived variableU1612hSee Table B-17
1ChGetActive matrixU1612h
U160Eh
U160EhSee Table B-22
U160FhSee Table B-21
U160FhSee Table B-23
U160FhSee Table B-24
U1610h% complete
User Guide63
Device profileUser Guide
April 2022MMI-20019808
AttributeAccessNameTypeTrigger Byte
WriteAttribute
1DhGetSubnet communication status
(RS-485 connection to
transmitter)
U16No trigger byte0: Communications failure
Description
Any other value:
Communications good
B.3.8Output parameters (explicit data) for concentration
measurement configuration
Class B1h, Instance 01h
AttributeAccessNameTypeTrigger byte
write attribute
01hGet/SetStandard or special mass flow
rate unit
02hGet/SetDensity unitU16See Table B-13
03hGet/SetTemperature unitU16See Table B-14
04hGet/SetStandard or special volume
flow rate unit
05hGet/SetPressure unitU16See Table B-15
06hGet/SetZero timeU16Seconds
U16See Table B-7
U16See Table B-10
Description
07hGet/SetZero valueFloat
08hGet/SetOutput state during Smart
Meter Verification
09hGet/SetSmart Meter Verification Index U1611hSmart Meter Verification test
0AhGet/SetTrigger Byte-2U8
0BhGet/SetTrigger Byte-3U8
0ChGet/SetTrigger Byte-6U8
0DhGet/SetTrigger Byte-9U8
0EhGet/SetTrigger Byte-14U8
0FhGet/SetTrigger Byte-15U8
10hGet/SetTrigger Byte-16U8
11hGet/SetTrigger Byte-24U8
12hGet/SetTrigger Byte-25U8
13hGet/SetTrigger Byte-17U8
U160 = Last measured value
1 = Fault
record.
0 = most recent
...
19 = oldest
64Micro Motion EtherNet/IP Module
User GuideDevice profile
MMI-20019808April 2022
B.3.9Input assembly for petroleum measurement
configuration
ByteAccessNameTypeNotes
0–3GetMass flow rateFloat
4–7GetDensityFloat
8–11GetTemperatureFloat
12–15GetVolume flow rate (liquid
volume)
16–19GetMass totalFloat
20–23GetVolume totalFloat
24–27GetDrive gainFloat
28–29GetStatus wordU16 or Word• For Model 1700 Analog, Model 2700 Analog,
30-31GetStatus wordU16 or Word• For Model 1700 Analog, Model 2700 Analog,
32–35GetTemperature-corrected
density
Float
Model 1500 Analog, Model 2500, and all Series
3000 transmitters: SNS Status Word 1 (see
Status Word 1)
• For MVD Direct Connect and 9739 MVD
transmitters: SNS Status Word 2 (see Status
Word 2)
Model 1500 Analog, Model 2500, and all Series
3000 transmitters: SNS Status Word 2 (see
Status Word 2)
• For MVD Direct Connect and 9739 MVD
transmitters: SNS Status Word 1 (see Status
Word 1)
Float
36–39GetCTLFloat
40–43GetTemperature-corrected
volume flow
44–47GetTemperature-corrected
volume total
48–51GetTemperature-corrected
volume inventory
52–55GetAverage temperature-
corrected density
56–59GetAverage temperatureFloat
User Guide65
Float
Float
Float
Float
Device profileUser Guide
April 2022MMI-20019808
B.3.10Output assembly for petroleum measurement
configuration
ByteAccessNameTypeNotes
0–3Get/SetExternal TemperatureFloat
4–7Get/SetExternal PressureFloat
8Get/SetStart/Stop TotalsByte0: Stop
1: Start
9Get/SetReset All Process TotalsByte0: No action
1: Reset
10Get/SetReset All Inventory TotalsByte0: No action
1: Reset
11Get/SetStart ZeroByte0: Abort or no action
1: Start
12–13Get/SetStart Smart Meter
Verification
WordSee Table B-20
B.3.11Input parameters (explicit data) for petroleum
measurement configuration
To update any of these attribute values, the associated trigger byte must be toggled
before reading the attribute value (executing the Get service). See Output parameters
(explicit data) for standard configuration for more information on trigger bytes.
The Emerson logo is a trademark and service mark of Emerson
Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct
Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of
their respective owners.
www.emerson.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.