This chapter provides an orientation to the use of this manual, and includes a pre-configuration
worksheet. This manual describes the procedures required to start, configure, use, maintain, and
troubleshoot the following LF-Series transmitters:
•LF-Series field-mount transmitter with the 1 mA/1 FO outputs option board (flow-only)
•LF-Series field-mount transmitter with the 1 mA/1 FO outputs option board (multivariable)
•LF-Series field-mount transmitter with the 2 mA/1 FO outputs option board (multivariable,
configurable)
•LF-Series DIN rail mount transmitter with the 1 mA/1 FO outputs option board (flow-only)
•LF-Series DIN rail mount transmitter with the 2 mA/1 FO outputs option board (multivariable,
configurable), with or without the Filling and Dosing application
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
If you do not know what transmitter you have, see Section 1.4 for instructions on identifying the
transmitter type from the model number on the transmitter’s tag.
Note: Information on configuration and use of LF-Series transmitters with F
outputs is provided in a separate manual. See the manual for your transmitter.
1.2Safety
Safety messages are provided throughout this manual to protect personnel and equipment. Read each
safety message carefully before proceeding to the next step.
1.3Transmitter codes used in this manual
In this manual, codes are used to identify specific LF-Series transmitter types. The codes are listed in
Tabl e 1 -1 .
Table 1-1Transmitter codes
Transmitter typeCode
All LF-Series field-mount transmittersFM
LF-Series field-mount transmitter with the 1 mA/1 FO outputs option board (flow-only)FM AN F
LF-Series field-mount transmitter with the 1 mA/1 FO outputs option board (multivariable)FM AN M
LF-Series field-mount transmitter with the 2 mA/1 FO outputs option board (multivariable,
configurable)
LF-Series field-mount transmitter with the FOUNDATION fieldbus outputs option boardFM FB
All LF-Series DIN rail mount transmittersDIN
OUNDATION
™
fieldbus
FM CIO
Configuration and Use Manual1
Before You Begin
Table 1-1Transmitter codes continued
Transmitter typeCode
LF-Series DIN rail mount transmitter with the 1 mA/1 FO outputs option board (flow-only)DIN AN
LF-Series DIN rail mount transmitter with the 2 mA/1 FO outputs option board (multivariable,
configurable)
LF-Series DIN rail mount transmitter with the 2 mA/1 FO outputs option board (multivariable,
configurable) with the Filling and Dosing Application
1.4Determining your transmitter type and version
To configure, use, and troubleshoot the transmitter, you must know your transmitter type. This section
provides instructions for this information. Record this information in the pre-configuration worksheet
in Section 1.8.
1.4.1Transmitter type and outputs option board
To determine your transmitter type:
1. Obtain the transmitter's model number, which is provided on a tag attached to the side of the
transmitter.
DIN CIO
DIN CIO FD
2. The fourth character in the model number (
LFTXxxxxxxx) represents the transmitter type
that was ordered:
•
1 = FM AN flow-only
•
2 = DIN AN
•
3 = FM AN multivariable
4 = FM CIO
•
•
5 = DIN CIO
•
6 = FM FB
8 = DIN CIO with the Filling and Dosing application
•
1.4.2Version
Different configuration options are available with different versions of the components. Table 1-2 lists
the version information that you may need and describes how to obtain the information.
This manual describes features and procedures that apply to most or all of the
LF-Series transmitters. To help you identify the topics that apply to your transmitter,
a list of transmitters is supplied with topic headings (see the example to the left of
this paragraph). If no list is supplied with the topic heading, the topic is applicable
to all transmitters.
1.6.1Communication tools
Most of the procedures described in this manual require the use of a communication tool. Table 1-4
lists the transmitters discussed in this manual, and the communication tools that can be used with
them.
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
Table 1-4Transmitters and communication tools
Transm itter
Transm itter
FM AN F✓✓✓
FM AN M✓✓✓
FM CIO✓✓✓
DIN AN✓
DIN CIO✓
DIN CIO FD✓
(1) LF-Series FM transmitters may be ordered with or without a display.
(2) Requires ProLink II v2.1 or later.
(3) Requires ProLink II v2.3 or later.
display
(1)
ProLink II
softwareCommunicator
(2)
(2)
(3)
✓
✓
In this manual:
•Basic information on using the display is provided in Chapter 2.
•Basic information on ProLink II and connecting ProLink II to your transmitter is provided in
Chapter 3. For more information, see the ProLink II manual, available on the Micro Motion
website (www.micromotion.com).
•Basic information on the 375 Field Communicator and connecting the Communicator to your
transmitter is provided in Chapter 4. For more information, see the Field Communicator
documentation available on the Micro Motion web site (www.micromotion.com).
Configuration and Use Manual3
You may be able to use other tools from Emerson Process Management, such as AMS. Use of AMS is
not dicussed in this manual; however, the user interface that AMS provides is similar to the ProLink II
user interface.
Before You Begin
1.7Planning the configuration
The pre-configuration worksheet in Section 1.8 provides a place to record information about your
flowmeter (transmitter and sensor) and your application. This information will affect your
configuration options as you work through this manual. Fill out the pre-configuration worksheet and
refer to it during configuration. You may need to consult with transmitter installation or application
process personnel to obtain the required information.
If you are configuring multiple transmitters, make copies of this worksheet and fill one out for each
individual transmitter.
1.8Pre-configuration worksheet
Note: Not all options are available for all transmitters.
ItemConfiguration data
Transmitter model number
Transmitter model
Transmitter software
version
Sensor software version
______________________________________
FM AN F
FM AN M
FM CIO
DIN AN
DIN CIO
DIN CIO FD
______________________________________
OutputsTerminals 1 & 2
Process variable or
assignment
Terminals 21 & 22 or
Channel A
Terminals 3 & 4
Terminals 23 & 24 or
Channel B
Terminals 5 & 6
Terminals 31 & 32 or
Channel C
Terminals 1 & 2
Terminals 21 & 22 or
Channel A ______________________________________
Terminals 3 & 4 or
Terminals 23 & 24 or
Channel B ______________________________________
Terminals 5 & 6 or
Terminals 31 & 32 or
Channel C ______________________________________
For technical assistance, phone the Micro Motion Customer Service department:
______________________________________
Volume flow
______________________________________
Density
______________________________________
Pressure
______________________________________
Temperature
______________________________________
______________________________________
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
•In the U.S.A., phone 800-522-MASS (800-522-6277) (toll free)
•In Canada and Latin America, phone +1 303-527-5200 (U.S.A.)
•In Asia:
-In Japan, phone 3 5769-6803
-In other locations, phone +65 6777-8211 (Singapore)
•In Europe:
-In the U.K., phone 0870 240 1978 (toll-free)
-In other locations, phone +31 (0) 318 495 555 (The Netherlands)
Customers outside the U.S.A. can also email Micro Motion customer service at
International.MMISupport@Emerson.com.
Configuration and Use Manual5
6Micro Motion® LF-Series Transmitters
Chapter 2
•FM AN F
•FM AN M
•FM CIO
Current value
Units of measure
Process variable
Scroll optical switchSelect optical switch
Optical switch indicator
Status LED
Using the Transmitter Display
2.1Overview
The transmitter display provides basic configuration and management functionality.
This chapter describes the user interface of the transmitter display. The following
topics are discussed:
•Display components (see Section 2.2)
•Using the
•Using the display (see Section 2.4.2)
Note: The DIN rail mount transmitters do not have displays, and the field-mount transmitters can be
ordered with or without displays.
Not all configuration and use functions are available through the display. If you need the added
functionality, or if your transmitter does not have a display, you must use either ProLink II or the
Communicator to communicate with the transmitter.
Scroll and Select optical switches (see Section 2.3)
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
2.2Components
Figure 2-1 illustrates the display components.
Figure 2-1Display components
Configuration and Use Manual7
Using the Transmitter Display
2.3Using the optical switches
The
Scroll and Select optical switches are used to navigate the transmitter display. To activate an
optical switch, touch the glass in front of the optical switch or move your finger over the optical
switch close to the glass. The optical switch indicator will be solid red when a single switch is
activated, and will flash red when both switches are activated simultaneously.
Removing the display cover in an explosive atmosphere can cause an explosion. When using the
optical switches, do not remove the display cover. To activate an optical switch, touch the glass of the
display cover or move your finger over the switch close to the glass.
2.4Using the display
In ordinary use, the
Units of measure line shows the measurement unit for that process variable.
the
Process variable line on the display shows the configured display variables, and
•See Section 8.14.4 for information on configuring the display variables.
•See Appendix H for information on the codes and abbreviations used for display variables.
If more than one line is required to describe the display variable, the
between the measurement unit and the additional description. For example, if the display is showing a
mass inventory value, the
name of the inventory (
MASSI).
Auto scroll may or may not be enabled:
Units of measure line alternates
Units of measure line alternates between the measurement unit (G) and the
•If Auto scroll is enabled, each configured display variable will be shown for the number of
seconds specified for Scroll rate.
•Whether Auto scroll is enabled or not, the operator can manually scroll through the configured
display variables by activating
Scroll.
For more information on using the display to view process variables or manage totalizers and
inventories, see Chapter 7.
2.4.1Display menus
To enter the display menus, activate
will flash. Hold
Scroll and Select until the words SEE ALARM or OFF-LINE MAINT appear.
To move through a list of options, activate
To select from a list, scroll to the desired option, then activate
Scroll and Select simultaneously. The optical switch indicator
Scroll.
Select.
To exit a display menu without making any changes:
•Use the
•If the
EXIT option if available.
EXIT option is not available, activate Scroll and Select simultaneously, and hold until
the screen returns to the previous display.
2.4.2Display password
Some of the display functions, such as the off-line menu and resetting totalizers, can be protected by a
password. For information about enabling and setting the password, refer to Section 8.14.
Note: If the petroleum measurement application is enabled on your transmitter, an off-line password
is always required to start, stop, or reset a totalizer, even if the display off-line password parameter is
disabled.
8Micro Motion® LF-Series Transmitters
Using the Transmitter Display
SX.XXXESY
Sign
For positive numbers,
leave this space
blank. For negative
numbers, enter a
dash (–).
Digits
Enter a four-digit
number; three digits
must fall to the right
of the decimal point.
E
Indicates
exponents.
Sign
Exponent
Enter the
power of 10 by
which the
digits will be
multiplied.
–8.100E 5
If a password is required, the word CODE? appears at the top of the password screen. Enter the digits
of the password one at a time by using
digit.
If you encounter the display password screen but do not know the password, wait 60 seconds without
activating any of the display optical switches. The password screen will time out automatically and
you will be returned to the previous screen.
2.4.3Entering milliamp and frequency range values with the display
If you are using the display to change transmitter settings, the display uses a standard format and
procedure for entering range values for either mA or frequency outputs.
Enter range and scale values in scientific notation according to the following format:
Scroll to choose a number and Select to move to the next
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
Example of range value format
The correct format for the number –810,000 is shown below:
To enter mA or frequency range values with the display:
Note: This procedure assumes that you are already at the correct point in the display menu to begin
entering the range values.
Scroll, if necessary, until the first space is either a minus sign (–) for a negative number or a
1.
blank space for a positive number.
2.
Select.
Scroll until the first digit is the correct number.
3.
4.
Select.
5.
Scroll until the second digit is the correct number.
Select.
6.
7.
Scroll until the third digit is the correct number.
8.
Select.
Scroll until the fourth digit is the correct number.
9.
10.
Select.
11.
Scroll, if necessary, until the sign for the exponent is either a dash (–) for a negative exponent
or a blank space for a positive exponent.
Configuration and Use Manual9
Using the Transmitter Display
12. Select.
13.
Scroll until the exponent is the correct power of 10.
14.
Scroll and Select simultaneously for four seconds to save and exit.
10Micro Motion® LF-Series Transmitters
Chapter 3
•FM AN F
•FM AN M
•FM CIO
•DIN AN
•DIN CIO
• DIN CIO FD
Connecting with ProLink II Software
3.1Overview
ProLink II is a Microsoft
Micro Motion transmitters. It provides complete access to transmitter functions and
data.
This chapter provides basic information for connecting ProLink II to your
transmitter. The following topics and procedures are discussed:
•Requirements (see Section 3.2)
•Configuration upload/download (see Section 3.3)
•Connecting to a field-mount transmitter (see Section 3.4)
•Connecting to a DIN rail mount transmitter (see Section 3.5)
The instructions in this manual assume that users are already familiar with ProLink II software. For
more information on using ProLink II, or for detailed instructions on installing ProLink II, see the
ProLink II software manual, which is available on the Micro Motion web site
(www.micromotion.com).
®
Windows-based configuration and management tool for
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
Note: ProLink II uses the Model 1500/1700/2500/2700 device descriptions for the LF-Series
field-mount transmitters. Accordingly, when you connect to an LF-Series transmitter, you will see a
Model 1500/1700/2500/2700 model code on the ProLink II screen.
3.2Requirements
To use ProLink II with an LF-Series transmitter, the following are required:
•ProLink II v2.0 or later (some LF models require later versions of ProLink II)
•Signal converter, to convert the PC’s serial port signal to the signal used by the transmitter
-For RS-485 connections, an RS-485 to RS-232 signal converter. The Black Box
RS-232 <-> 2-wire RS-485 Interface Converter (Code IC521A-F) signal converter is
available from Micro Motion. Contact Micro Motion if you need an RS-485 signal
converter.
-For Bell 202 connections, a HART interface. The MACTek
Interface is available from Micro Motion. Contact Micro Motion if you need a HART
interface.
•25-pin to 9-pin adapter (if required by your PC)
®
®
Viator® RS232 HART®
Async
Configuration and Use Manual11
Connecting with ProLink II Software
•FM AN F
•FM AN M
•FM CIO
3.3ProLink II configuration upload/download
ProLink II provides a configuration upload/download function which allows you to save configuration
sets to your PC. This allows:
•Easy backup and restore of transmitter configuration
•Easy replication of configuration sets
Micro Motion recommends that all transmitter configurations be downloaded to a PC as soon as the
configuration is complete.
To access the configuration upload/download function:
1. Connect ProLink II to your transmitter as described in this chapter.
2. Open the
•To save a configuration file to a PC, use the
File menu.
Load from Xmtr to File option.
•To restore or load a configuration file to a transmitter, use the
option.
3.4Connecting from a PC to an LF-Series field-mount transmitter
Depending on your transmitter, there are several options for connecting ProLink II to your transmitter.
See Table 3-1.
Note: Service port connections use standard settings, do not require transmitter configuration, and
are always available. Therefore, they are easy and convenient. However, service port connections
require opening the power supply compartment. Accordingly, service port connections should be used
only for temporary connections, and may require extra safety precautions.
Note: Due to the design of HART protocol, connections made using HART protocol are slower than
connections that use Modbus protocol. If you use HART protocol, you cannot open more than one
ProLink II window at a time.
Table 3-1Connection options for field-mount transmitters
ConnectionPhysical layerProtocol
Service port
(see Section 3.4.1)
RS-485 terminals or
RS-485 network
(see Section 3.4.2)
Primary mA terminals or
HART network
(see Section 3.4.3)
RS-485Modbus✓✓
RS-485Modbus✓
RS-485HART✓
Bell 202HART✓✓
FM AN AFM CIO
Send to Xmtr from File
Transm itter
12Micro Motion® LF-Series Transmitters
3.4.1Connecting to the service port
To connect to the service port, which is located in the non-intrinsically safe power
supply compartment (see Figure 3-1):
1. Attach the signal converter to the serial port of your PC, using a 25-pin to
9-pin adapter if required.
2. Open the cover to the wiring compartment.
Connecting with ProLink II Software
Service port
RS-485 to RS-232
signal converter
25-pin to 9-pin serial port
adapter (if necessary)
LF-Series field-mount transmitter
terminal compartment
RS-485/A
RS-485/B
PC
Opening the wiring compartment in a hazardous area can cause an explosion. When the transmitter is
in an explosive atmosphere, do not use the service port to connect to your transmitter.
3. Open the power supply compartment.
Opening the power supply compartment in a hazardous area while the power is on can cause an
explosion. Before using the service port to communicate with the transmitter in a hazardous area, make
sure the atmosphere is free of explosive gases.
Opening the power supply compartment can expose the operator to electric shock. Do not touch the
power supply wires or terminals while using the service port.
4. Connect the signal converter leads to the service port terminals. See Figure 3-1.
Figure 3-1Service port connections to an LF-Series field-mount transmitter
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
5. Start ProLink II software. From the Connection menu, click on
Connect to Device. In the
screen that appears, specify:
•
Protocol: Service Port
•
COM Port: as appropriate for your PC
All other parameters are set to service port required values and cannot be changed.
6. Click the
Connect button. ProLink will attempt to make the connection.
7. If an error message appears:
a.Swap the leads between the two service port terminals and try again.
Configuration and Use Manual13
b.Ensure that you are using the correct COM port.
c.Check all the wiring between the PC and the transmitter.
Connecting with ProLink II Software
•FM AN F
•FM AN M
RS-485 to RS-232
signal converter
25-pin to 9-pin serial port
adapter (if necessary)
LF-Series field-mount transmitter
terminal compartment
(FM AN transmitters only)
PC
3.4.2Connecting to the RS-485 terminals or an RS-485 network
To connect a PC to the RS-485 terminals or an RS-485 network:
1. Attach the signal converter to the serial port of your PC, using a 25-pin to 9-pin adapter if
required.
2. To connect to the RS-485 terminals, open the cover to the wiring compartment and connect the
signal converter leads to the transmitter terminals labeled
these terminals. See Figure 3-2.
3. To connect to an RS-485 network, connect the signal converter leads to any point in the
network. See Figure 3-3.
4. For long-distance communication, or if noise from an external source interferes with the
signal, install 120 Ω, 1/2 watt resistors in parallel with the output at both ends of the
communication segment.
Figure 3-2RS-485 terminal connections to LF-Series FM AN transmitter
5 and 6, or to the output wires from
14Micro Motion® LF-Series Transmitters
Connecting with ProLink II Software
DCS or PLC
Add resistance if necessary
(see Step 4)
RS-485 to RS-232
signal converter
25-pin to 9-pin serial port
adapter (if necessary)
PC
Figure 3-3RS-485 network connections to LF-Series FM AN transmitter
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
5. Start ProLink II software. From the Connection menu, click on
Protocol, Baud Rate, Stop Bits, and Parity to the RS-485 values configured in the
6. Set
Connect to Device.
transmitter. See Section 8.15.
Note: If you do not know the transmitter’s RS-485 configuration, you can connect through the service
port, which always uses default settings, or you can use the Communicator or the display to view or
change the transmitter’s RS-485 configuration. Default RS-485 communication parameters are listed
in Table 8-8.
7. Set the
Address/Tag value to the Modbus or HART polling address configured for the
transmitter. The default Modbus address is 1; the default HART polling address is 0. See
Section 8.15.
8. Set the
9. Click the
COM Port value to the PC COM port assigned to this connection.
Connect button. ProLink will attempt to make the connection.
10. If an error message appears:
a.Swap the leads and try again.
b.You may be using incorrect connection parameters.
-Ensure you are using the correct COM port.
-Connect using the service port and check the RS-485 configuration. If required,
change the configuration or change your RS-485 connection parameters to match the
existing configuration.
-If you are unsure of the transmitter’s address, use the
Poll button in the Connect
window to return a list of all devices on the network.
c.Check all the wiring between the PC and the network. You may need to add resistance. See
Figure 3-3.
Configuration and Use Manual15
Connecting with ProLink II Software
•FM AN F
•FM AN M
•FM CIO
VIATOR
1 (+)
2 (–)
R2
See Step 4
R3
See Step 4
DCS or
PLC
R1
See Step 4
3.4.3Connecting to the primary mA terminals or to a HART multidrop network
Connecting a HART device to the transmitter’s primary mA output
terminals could cause transmitter output error. Set control devices for
manual operation before connecting a HART interface to the transmitter’s
primary mA output loop.
To connect a PC to the primary mA terminals or to a HART multidrop network:
1. Attach the HART interface to the serial port of your PC.
2. To connect to the primary mA terminals, open the cover to the wiring compartment and
connect the HART interface leads to the terminals labeled
1 and 2, or to the output wires from
these terminals.
3. To connect to a HART multidrop network, connect the HART interface leads to any point on
the network.
Figure 3-4HART/Bell202 connections to LF-Series field-mount transmitters
16Micro Motion® LF-Series Transmitters
4. Add resistance as required. The Viator HART interface must be connected across a resistance
5. Start ProLink II software. From the Connection menu, click on
6. Set
7. Set the
8. Set the
of 250–600 Ω. To meet the resistance requirements, you may use any combination of resistors
R1, R2, and R3 (see Figure 3-4).
Protocol to HART Bell 202. Baud rate, Stop bits, and Parity are automatically set to the
values required by HART protocol.
Address/Tag value to the HART polling address configured for the transmitter. The
Connect to Device.
default HART polling address is 0. See Section 8.15 for information on the HART polling
address.
COM Port value to the PC COM port assigned to this connection.
Connecting with ProLink II Software
•DIN AN
•DIN CIO
• DIN CIO FD
9. Set Master as appropriate:
•If another host such as a DCS is on the network, set
•If no other host is on the network, set
Master to Primary.
Note: The 375 Field Communicator is not a host.
10. Click the
Connect button. ProLink will attempt to make the connection.
11. If an error message appears:
a.You may be using incorrect connection parameters.
-Ensure you are using the correct COM port.
-If you are unsure of the transmitter’s address, use the
window to return a list of all devices on the network.
b.Check all the wiring between the PC and the transmitter.
c.Increase or decrease resistance.
3.5Connecting from a PC to an LF-Series DIN rail mount transmitter
ProLink II software can communicate with an LF-Series DIN Rail mount
transmitter using:
•Modbus/RS-485 protocol (see Section 3.5.1
-Configurable connection
-SP (service port) standard connection
•A HART/Bell202 connection (see Section 3.5.2
Master to Secondary.
Poll button in the Connect
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
)
)
Note: Service port connections use standard settings and do not require transmitter configuration.
Therefore, they are easy and convenient. However, service port connections are available only for the
10-second interval after power-up. See Step 5 in the following section.
Note: Due to the design of HART protocol, connections made using HART protocol are slower than
connections that use Modbus protocol. If you use HART protocol, you cannot open more than one
ProLink II window at a time.
3.5.1Connecting to the RS-485 terminals or an RS-485 network
To connect a PC to the RS-485 terminals or an RS-485 network:
1. Attach the signal converter to the serial port of your PC, using a 25-pin to 9-pin adapter if
required.
2. To connect to the RS-485 terminals, connect the signal converter leads to terminals 33 and 34.
See Figure 3-5.
3. To connect to an RS-485 network, connect the signal converter leads to any point in the
network. See Figure 3-6.
4. For long-distance communication, or if noise from an external source interferes with the
signal, install 120 ohm, 1/2 watt resistors in parallel with the output at both ends of the
communication segment.
Configuration and Use Manual17
Connecting with ProLink II Software
RS-485/B
RS-485/A
RS-485 to RS-232
signal converter
25-pin to 9-pin serial port
adapter (if necessary)
PC
DCS or PLC
Add resistance if necessary
(see Step 4)
RS-485 to RS-232
signal converter
25-pin to 9-pin serial port
adapter (if necessary)
PC
RS-485 B
RS-485 A
Figure 3-5RS-485 terminal connections to LF-Series DIN rail mount transmitter
Figure 3-6RS-485 network connections to LF-Series DIN rail mount transmitter
5. Start ProLink II software. From the Connection menu, click on
screen that appears, specify connection parameters appropriate to your connection:
•Immediately after the transmitter is powered up, terminals 33 and 34 are available in
service port mode for 10 seconds. To connect during this period, set
Port, and set
Parity are set to standard values and cannot be changed (see Table 3-2).
COM port to the appropriate value for your PC. Baud rate, Stop bits, and
•If no connection is made during the 10-second period, the terminals are automatically
reset to the configured RS-485 communication parameters. To connect, set the connection
parameters to the values configured in your transmitter (see Table 3-2).
Connect to Device. In the
Protocol to Service
18Micro Motion® LF-Series Transmitters
Connecting with ProLink II Software
Table 3-2Modbus connection parameters for ProLink II
Connection type
Connection parameterConfigurable (RS-485 mode)SP standard (service port mode)
ProtocolAs configured in transmitter
(default = Modbus RTU)
Baud rateAs configured in transmitter (default = 9600)38,400
Stop bitsAs configured in transmitter (default = 1)1
ParityAs configured in transmitter (default = odd)None
Address/TagConfigured Modbus address (default = 1)111
COM portCOM port assigned to PC serial portCOM port assigned to PC serial port
(1) Required value; cannot be changed by user.
Modbus RTU
(1)
(1)
(1)
(1)
(1)
6. Click the Connect button. ProLink will attempt to make the connection.
7. If an error message appears:
a.Swap the leads between the two terminals and try again.
b.Ensure you are using the correct COM port.
c.If you are in RS-485 mode, you may be using incorrect connection parameters.
-Connect using the service port and check the RS-485 configuration. If required,
change the configuration or change your RS-485 connection parameters to match the
existing configuration.
-If you are unsure of the transmitter’s address. use the
Poll button in the Connect
window to return a list of all devices on the network.
d.Check all the wiring between the PC and the transmitter.
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
3.5.2HART/Bell202 connections
Connecting a HART device to the transmitter’s primary mA output terminals could cause transmitter
output error. Set control devices for manual operation before connecting a HART interface to the
transmitter’s primary mA output loop.
HART/Bell202 connections are made through terminals 21 and 22. See Figure 3-7.
Configuration and Use Manual19
Connecting with ProLink II Software
VIATOR
250–600 Ω
Figure 3-7HART/Bell202 connections to LF-Series DIN rail mount transmitter
Follow the instructions below to make the connection.
1. Connect the HART interface to your PC’s serial port. Then connect the leads of the HART
interface to terminals 21 and 22.
2. Add 250–600 Ω resistance to the connection, as required.
3. Start ProLink II software. From the Connection menu, click on
4. In the screen that appears, set
Protocol to HART Bell 202. Baud rate, Stop bits, and Parity
Connect to Device.
are automatically set to the values required by HART protocol. Specify the remaining
connection parameters as shown in Table 3-3.
Table 3-3HART connection parameters for ProLink II
Connect button. ProLink will attempt to make the connection.
6. If an error message appears:
a.Ensure that you are using the correct COM port.
b.Check all the wiring between the PC and the transmitter.
c.Increase or decrease the resistance.
20Micro Motion® LF-Series Transmitters
Chapter 4
•FM AN F
•FM AN M
•FM CIO
•DIN AN
•DIN CIO
Connecting with the 375 Field Communicator
4.1Overview
The 375 Field Communicator is a handheld configuration and management tool for
HART-compatible devices, including Micro Motion transmitters. It provides
complete access to transmitter functions and data.
Note: The DIN CIO FD transmitter can only be configured using ProLink II.
This chapter provides basic information for connecting the 375 Field Communicator
to your transmitter. The following topics and procedures are discussed:
•Communicator device descriptions (see Section 4.2)
•Connecting to a transmitter (see Section 4.3)
•Conventions used in this manual (see Section 4.4)
The instructions in this manual assume that users are already familiar with the Communicator and can
perform the following tasks:
•Turn on the Communicator
•Navigate the Communicator menus
•Establish communication with HART-compatible devices
•Transmit and receive configuration information between the Communicator and
HART-compatible devices
•Use the alpha keys to type information
•If you are unable to perform the tasks listed above, consult the Communicator manual before
attempting to use the software. The documentation is available on the Micro Motion website
(www.micromotion.com).
Using DisplayUsing HART CommunicatorUsing ProLink IIBefore You Begin
4.2Communicator device descriptions
Configuration and Use Manual21
The Communicator uses the Model 1500/1700/2500/2700 device descriptions for the LF-Series
field-mount transmitters. Accordingly, when you connect to an LF-Series transmitter, you may see a
Model 1500/1700/2500/2700 model code on the Communicator display.
Table 4-1 lists the Communicator device descriptions that are available for LF-Series transmitters.
Connecting with the 375 Field Communicator
•FM AN F
•FM AN M
•FM CIO
•DIN AN
•DIN CIO
Table 4-1Transmitter models and device descriptions
TransmitterDevice description
DIN AN1500 Mass Flow
FM AN F1000 Mass Flow
FM CIO2000C Mass Flow
FM AN M2000 Mass Flow
DIN CIO2000C Mass Flow
To view the device descriptions that are installed on your 375 Field Communicator:
1. At the HART application menu, select
Utility.
2. Select
3. Select
Available Device Descriptions.
Micro Motion.
If you do not see the appropriate device description, contact Micro Motion Customer Support.
4.3Connecting to a transmitter
You can connect the Communicator directly to the transmitter’s mA/HART
terminals or to a point on a HART network.
Note: If you are using the mA/HART terminals to report a process variable and also
for HART communication, see the transmitter installation manual for wiring
diagrams.
4.3.1Connecting to communication terminals
To connect the Communicator directly to the transmitter’s mA/HART terminals:
Connecting a HART device to the transmitter’s primary mA output terminals could cause transmitter
output error. Set control devices for manual operation before connecting a HART interface to the
transmitter’s primary mA output loop.
1. If you are connecting to an LF-Series field-mount transmitter, open the cover to the wiring
compartment.
22Micro Motion® LF-Series Transmitters
Opening the wiring compartment in a hazardous area can cause an explosion. When the transmitter is
in an explosive atmosphere, do not use the mA terminals to connect to your transmitter.
2. Connect the Communicator leads to the transmitter’s primary mA output terminals:
•FM transmitters: terminals 1 and 2 (see Figure 4-1)
•DIN transmitters: terminals 21 and 22 (see Figure 4-2)
3. The Communicator must be connected across a resistance of 250–600 Ω. Add resistance to the
connection. See Figure 4-1.
Loading...
+ 198 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.