Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are
available: the EU Declaration of Conformity, with all applicable European directives, and the complete ATEX installation drawings
and instructions. In addition, the IECEx installation instructions for installations outside of the European Union and the CSA
installation instructions for installations in North America are available at Emerson.com or through your local Micro Motion
support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found at Emerson.com. For
hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Troubleshooting information can be found in the Configuration Manual. Product data sheets and manuals are available from the
Micro Motion web site at Emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at Emerson.com, or by calling the Micro Motion Customer
Service department.
2
Integration GuideContents
MMI-20029785June 2022
Contents
Chapter 1Before you begin........................................................................................................5
1.1 About this document...................................................................................................................5
1.2 Related documentation............................................................................................................... 5
Chapter 25700 transmitters in Ethernet networks.....................................................................7
2.1 Star topology...............................................................................................................................7
2.2 Ring topology.............................................................................................................................. 8
This document provides information about how to integrate a Model 5700 Ethernet transmitter
communicating with a Siemens Simatic S7-400 PLC using a Simatic Manager project.
Important
This manual assumes that:
• The transmitter has been installed correctly and completely according to the instructions in the
transmitter installation manual.
• Users understand basic transmitter and sensor installation, configuration, and maintenance concepts and
procedures.
1.2 Related documentation
You can find all product documentation via the product documentation DVD shipped with the product or at
Emerson.com.
• Hazardous area installation — see the approval documentation shipped with the transmitter, or download
the appropriate documentation
PROFINET Siemens PLC Integration Guide5
Before you beginIntegration Guide
June 2022MMI-20029785
6Micro Motion 5700 Ethernet transmitters
Integration Guide5700 transmitters in Ethernet networks
MMI-20029785June 2022
2 5700 transmitters in Ethernet networks
• Make sure that each cable is no longer than 328 ft (100 m).
• Connect the 5700 Ethernet transmitter to the host system via a LAN (Local Area Network) and not a WAN
(Wide Area Network).
• Follow all network security best practices.
2.1 Star topology
5700 Ethernet transmitters can be installed in a star network.
Figure 2-1: 5700 star network
A. Programmable Logic Controller (PLC)
B. 5700 with Ethernet output
C. External Ethernet switch
PROFINET Siemens PLC Integration Guide7
5700 transmitters in Ethernet networksIntegration Guide
June 2022MMI-20029785
2.2 Ring topology
5700 Ethernet transmitters can be installed in a ring network.
Figure 2-2: 5700 ring network
A. Programmable Logic Controller (PLC)
B. 5700 with Ethernet output
8Micro Motion 5700 Ethernet transmitters
Integration Guide5700 transmitters in Ethernet networks
MMI-20029785June 2022
2.3 Daisy-chain topology
5700 Ethernet transmitters can be installed in a daisy-chain network.
Figure 2-3: 5700 daisy-chain network
A. Programmable Logic Controller (PLC)
B. 5700 with Ethernet output
PROFINET Siemens PLC Integration Guide9
Establish cyclic dataIntegration Guide
June 2022MMI-20029785
3 Establish cyclic data
3.1 Install the GSDXML file
Procedure
1. Download the GSDXML file using one of the following methods:
OptionDescription
Use a USB
memory drive
a. Insert a USB memory drive into the 5700 Ethernet service port.
The service port connection is located under the transmitter cap.
b. From the transmitter display, choose Menu→USB Options→Transmitter→
USB Drive → Download Support Files → GSD file.
c. Follow the menu to copy the GSDXML file to the USB memory drive.
d. Copy the zip file from the USB memory drive to the PC where SIMATIC Manager
is installed.
e. Unzip the file to a chosen location.
Download the
file
2. To install the 5700 PROFINET GSDXML file into your GSD file catalog using the HW config in SIMATIC
Manager:
a) Choose Options→Install GSD File.
10Micro Motion 5700 Ethernet transmitters
a. Download the GSDXML file from the Micro Motion 5700 Ethernet product
website.
b. Unzip the file to a chosen location.
Integration GuideEstablish cyclic data
MMI-20029785June 2022
Example
b) Select Install.
c) Choose Update Catalog.
3.2 Create a PROFINET network
Procedure
1. Configure the primary protocol as PROFINET in the 5700 device:
a) From the transmitter display, choose Device Tools→Configuration→Network Settings.
PROFINET Siemens PLC Integration Guide11
Establish cyclic dataIntegration Guide
June 2022MMI-20029785
b) Select Profinet.
2. From SIMATIC Manager, choose File→'New Project' Wizard.
3. Follow the wizard to select the CPU for your PLC.
Example
CPU 400
4. In the Component View, click on the CPU.
5. Double-click Connections.
A graphical representation of the network is displayed.
6. Double-click the CPU icon.
The HW Config screen is displayed.
7. Double-click the interface, then click Properties.
Example
The network settings of the S7 400 PLC Ethernet interface are configured.
8. Right-click on the Ethernet interface, and select Insert PROFINET IO System.
12Micro Motion 5700 Ethernet transmitters
Integration GuideEstablish cyclic data
MMI-20029785June 2022
Example
The Ethernet network is created.
9. Double-click on the PROFINET network you just created.
The Properties menu is displayed.
10. Enter the name of the network.
Example
PROFINET Siemens PLC Integration Guide13
Establish cyclic dataIntegration Guide
June 2022MMI-20029785
11. (Optional) To use the network name in the IO device and in the controller, check Use the name in IOdevice/controller.
12. Drag and drop the device called Standard from the GSD file catalog to the 5700 Ethernet network.
The 5700 Ethernet network is located at PROFINET IO→Additional Field Devices→Sensors→Coriolis→5700 Coriolis Meter.
Example
13. Double-click on the device to enter the configuration menu.
14. Enter the Device name.
Note
The Device name must:
• Follow all DNS conventions
• Cannot start with a number
• Cannot contain uppercase alpha characters
15. Make the appropriate IP address configuration of the device, and press Ok.
You can use the Ethernet button if required.
If the Use name in IO device/controller checkbox is checked in the network properties, then Device
name will have the following format: device_name.network_name.
14Micro Motion 5700 Ethernet transmitters
Integration GuideEstablish cyclic data
MMI-20029785June 2022
OptionDescription
Device name when the Use
name in IO device/
controller checkbox is
unchecked
PROFINET Siemens PLC Integration Guide15
Establish cyclic dataIntegration Guide
June 2022MMI-20029785
OptionDescription
Device name when the Use
name in IO device/
controller checkbox is
checked
16. Click on the 5700 Ethernet icon to display the HW configuration in the lower screen.
17. From the HW Catalog, drag the input and output slots to one of the following locations:
• PROFINET IO → Additional Field Devices → Sensors → Coriolis → 5700 Coriolis Meter →
Standard→Input Modules – Slot 1
• PROFINET IO → Additional Field Devices → Sensors → Coriolis → 5700 Coriolis Meter →
Standard→Output Modules – Slot 2
Example
If Empty is selected, delete the slot by right-clicking on the slot, and selecting Delete.
For a description of the Input and Output slots, see Input and output slots.
Example
In this example, Small Configurable Data has been added to Slot 1.
16Micro Motion 5700 Ethernet transmitters
Integration GuideEstablish cyclic data
MMI-20029785June 2022
18. Press Save and Compile.
19. Press Download to Module to download the configuration into the CPU module.
Note
The modules configured and downloaded in the HW Config are set in the transmitter. You do not need
to set the Input or Output modules on the transmitter first. You can configure the variables in the input
data sets using the web server or ProLink III.
Example
The configuration is downloaded into the CPU module. The PLC should show a red LED bus fault.
PROFINET Siemens PLC Integration Guide17
Establish cyclic dataIntegration Guide
June 2022MMI-20029785
3.3 Configure Ethernet IP address and device name
Use this procedure to configure the Ethernet IP address and device name for the Model 5700 Ethernet device.
Procedure
1. Choose PLC→Ethernet→Edit Ethernet Node.
Example
2. To configure the programming machine (PG) to PC interface, choose Options→Set PG/PC Interface…
Example
3. Press Browse to find the Model 5700 Ethernet device on the network.
Tip
If you cannot find the Model 5700 device, turn off your firewall. Firewalls sometimes prevent SIMATIC
Manager from browsing network devices.
Example
18Micro Motion 5700 Ethernet transmitters
Integration GuideEstablish cyclic data
MMI-20029785June 2022
4. Select the device from the list and press Ok.
Example
5. Fill in the appropriate network settings and press Assign IP Configuration.
6. Fill in the device name and press Assign Name.
Make sure the IP configuration and device name are the same as what you configured in Create a
PROFINET network.
Example
7. Press Browse again to make sure the changes were applied to the device.
PROFINET Siemens PLC Integration Guide19
Establish cyclic dataIntegration Guide
June 2022MMI-20029785
Example
8. Choose
Example
PLC → Ethernet → Verify Device Name to verify the device name was properly assigned.
20Micro Motion 5700 Ethernet transmitters
Integration GuideEstablish cyclic data
MMI-20029785June 2022
3.4 Verify communications
Procedure
1. Verify that the PLC shows no faults (red lights).
The most likely error will be a Bus Fault (BF LED is red), which means either the Device Name, the IP
address, the Input Slot, or the Output Slot between the PLC and the Model 5700 Ethernet transmitter
does not match.
2. To verify you are receiving data:
a) In the HW Config, click the Model 5700 Ethernet icon.
b) Right-click on the Input Slot and press Monitor/Modify.
c) Click the I/O Display box and the Monitor box to see the process variables updating.
PROFINET Siemens PLC Integration Guide21
Establish cyclic dataIntegration Guide
June 2022MMI-20029785
Example
3. If the transmitter is still not communicating, from the transmitter display, choose Menu →
Configuration → Ethernet settings → Primary Protocol → Profinet to verify that PROFINET is the
configured primary protocol on the Model 5700 Ethernet transmitter.
3.5 Troubleshooting the PROFINET integration
3.5.1 Cannot download PROFINET into the PLC controller
Use the following procedure if you cannot download the PROFINET program into the PLC controller.
Procedure
1. Choose PLC→Ethernet→Edit Ethernet Node.
2. Select Browse.
A list of network devices with MAC IDs is displayed.
7. To program acyclic write, choose S7 Program→Blocks and double-click OB1.
The OB1 block is a Program Cycle Organization Block. The S7 CPU operating system executes OB1
periodically. When OB1 has been executed, the operating system restarts it. Cyclic execution of OB1 is
started after the start-up has been completed.
a) To edit the program, select OB1.
b) Choose Insert→Network.
c) From SFB blocks, drag SFB53 to Network and and configure the input and output as shown in
8. To create a variable table:
Use the variable table to modify and monitor the connected PLC variables and memory content.
a) From the SIMATIC Manager screen, choose Insert→S7 Block→Variable Table.
b) Enter the values as shown in the following examples and save your changes.
Example
The write request is sent to the Model 5700 using bit memory M1.0.
c) To start the read request, enter 1 (true) in the Modify value field, right-click, and press Modify.
d) To end the request, enter 0 (false) in the Modify value field, right-click, and press Modify.
9. To download a project to PLC:
a) From the SIMATIC Manager screen, select the Download to Module icon.
The configuration is downloaded to your CPU.
b) After the project downloads, open the vat table and make the corresponding M 1.0, 8.2 bits high
for read and read/write.
The read request is sent to the Model 5700 using bit memory M8.2. The write request is sent to
the Model 5700 using bit memory M1.0.
c) Go online to read and write acyclic data into the Model 5700 device module.
PROFINET Siemens PLC Integration Guide31
Input and output slotsIntegration Guide
June 2022MMI-20029785
A Input and output slots
A.1 Input slots
Empty
Use the Empty Input slot when no input data is required. Typically for an Ethernet mass flow meter, the Empty
Input slot is unused because this meter is a measuring device.
Table A-1: Common input data
Assembly
Dword
index
0Mass FlowREAL
1TemperatureREAL
2DensityREAL
3Drive GainREAL
4Totalizer 1 (default = Mass Total)REAL
5Inventory 1 (default = Mass Inventory)REAL
6StatusDWORD
NameData type
Severity (bits 0-15)• Bit #0 = Immediate Failure
• Bit #1 = Last Measure Value Failure
• Bit #2 = Function Check
• Bit #3 = Out of Specification
• Bit #4 = Maintenance Required
Counter/Heartbeat (bits 16-32) The PLC will display the counter/
heartbeat as a signed INT, therefore
the counter can be negative.
32Micro Motion 5700 Ethernet transmitters
Integration GuideInput and output slots
MMI-20029785June 2022
Table A-1: Common input data (continued)
Assembly
Dword
index
7Alert detail• Bit #0 = Electronics Failure
NameData type
• Bit #1 = Sensor Failed
• Bit #2 = Configuration Error
• Bit #3 = Core Low Power
• Bit #4 = Security Breach
• Bit #5 = Sensor-Transmitter
Communication Error
• Bit #6 = Tube Not Full
• Bit #7 = Extreme Primary Purpose
Variable
• Bit #8 = Reserved
• Bit #9 = Flowmeter Initializing
• Bit #10 = Function Check in
Progress
• Bit #11 = Sensor Being Simulated
• Bit #12 = Output Fixed
• Bit #13 = Drive Over Range
• Bit #14 = Process Aberration
• Bit #15 = Discrete Event X Active
• Bit #16 = Output Saturated
• Bit #17 = Function Check Failed
• Bit #18 = Data Loss Possible
DWORD
8Echo Output Data Discrete ActionsDWORD
Table A-2: Liquid volume flow
Assembly
Dword
index
0–8Common input dataSee Table A-1
9Volume FlowREAL
10Totalizer 2 (default = Volume Total)REAL
11Inventory 2 (default = Volume Inventory)REAL
PROFINET Siemens PLC Integration Guide33
NameData type
Input and output slotsIntegration Guide
June 2022MMI-20029785
Table A-3: Gas volume flow
Assembly
Dword
index
0–8Common input dataSee Table A-1
9Gas Volume FlowREAL
10Totalizer 4 (default = Gas Volume Total)REAL
11Inventory 4 (default = Gas Volume Inventory)REAL
NameData type
Table A-4: API referral
Assembly
Dword
index
0–8Common input dataSee Table A-1
9Volume FlowREAL
10Totalizer 2 (default = Volume Total)REAL
11Inventory 2 (default = Volume Inventory)REAL
12Corrected DensityREAL
13Corrected Vol FlowREAL
14Totalizer 3 (default = Corrected Vol Total)REAL
NameData type
15Inventory 3 (default = Corrected Vol Inv)REAL
16Avg DensityREAL
17Avg TemperatureREAL
18CTLREAL
Table A-5: Concentration measurement
Assembly
Dword
index
0–8Common input dataSee Table A-1
9Volume FlowREAL
10Totalizer 2 (default = Volume Total)REAL
11Inventory 2 (default = Volume Inventory)REAL
12Density at ReferenceREAL
13Std Vol Flow RateREAL
14Totalizer 5 (default = Std Vol Total)REAL
15Inventory 5 (default = Std Vol Inv)REAL
16Net Mass Flow RateREAL
NameData type
34Micro Motion 5700 Ethernet transmitters
Integration GuideInput and output slots
MMI-20029785June 2022
Table A-5: Concentration measurement (continued)
Assembly
Dword
index
17Totalizer 6 (default = Net Mass Total)REAL
18Inventory 6 (default = Net Mass Inv)REAL
19Net Vol Flow RateREAL
20Totalizer 7 (default = Net Vol Flow Total)REAL
21Inventory 7 (default = Net Vol Flow Inv)REAL
22ConcentrationREAL
23Density - Fixed SG UnitsREAL
24Density - Special Density UnitsREAL
Table A-6: Batcher
Assembly
Dword
index
0–8Common input dataSee Table A-2
9–11Liquid Volume
12Batch TotalREAL
NameData type
NameData type
13Overshoot Compensation Value (Reg 1457)REAL
14Batch Fill TimeREAL
PROFINET Siemens PLC Integration Guide35
Input and output slotsIntegration Guide
June 2022MMI-20029785
Table A-6: Batcher (continued)
Assembly
Dword
index
15Fill status and diagnostics
NameData type
• Bit #0 - Primary Fill in progress (reg 2495 bit 0)
• Bit #1 - Primary AOC training (reg 2495 bit 9)
• Bit #2 = Primary Valve (reg 2495 bit 5
• Bit #3 = Undefined
• Bit #4 = Undefined
• Bit #5 = Undefined
• Bit #6 - Fill Start Not Okay (reg 2496 bit 0)
• Bit #7 - AOC Flow Rate Too High (reg 2496 bit 1)
• Bit #8 - Maximum Fill Time Exceeded (reg 2496 bit 2)
• Bit #9 - Slug Flow (reg 2496 bit 3)
• Bit #10 - Tube Not Full (reg 2496 bit 4)
• Bit #11 - Drive Overrange (reg 2496 bit 5)
• Bit #12 - Critical Sensor Failure (reg 2496 bit 6)
• Bit #13 - Critical Transmitter Failure (reg 2496 bit 7)
• Bit #14 - Density Out of Limits (reg 2496 bit 8)
• Bit #15 - Temperature Out of Limits (reg 2496 bit 9)
24Smart Meter Verification Run Number (Reg 5826)UINT
25Smart Meter Verification Progress (Reg 3020)UINT
26Code 1 (Abort Code Reg 3002)UINT
27Code 2 – Future UseUINT
28Code 3 – Future UseUINT
A.2 Output slots
Empty
Use the Empty Input slot when no output data is required. No output data is a typical application and is the
default.
Table A-14: Common output data — Discrete actions only
Note
Common output data is required for every output assembly in order to access 5700 functions. Depending on the
application, not all functions may be used.
40Micro Motion 5700 Ethernet transmitters
Integration GuideInput and output slots
MMI-20029785June 2022
Assembly
Dword
index
0Discrete Actions:
NameData type
• Bit #0 – Start Sensor Zero (trigger start with a 1, no abort)
• Bit #1 – Reset All Process Totals (same as setting bits 2-8)
• Bit #2 – Reset Totalizer 1 (Mass Total by default)
• Bit #3 – Reset Totalizer 2 (Volume Total by default)
• Bit #4 – Reset Totalizer 3 (PM Ref Vol Total by default)
• Bit #5 – Reset Totalizer 4 (GSV Total by default)
• Bit #6 – Reset Totalizer 5 (CM Ref Vol Total by default)
• Bit #7 – Reset Totalizer 6 (CM Net Mass Total by default)
• Bit #8 – Reset Totalizer 7 (CM Net Vol Total by default)
• Bit #9 – Start All Totals (trigger start with a 1)
• Bit #10 – Stop All Totals (trigger stop with a 1)
If both start and stop =1, then totals are stopped
• Bit #11 – Start Smart Meter Verification (Continue Measuring Mode
only)
Trigger start with a 1, no abort
• Bit #12 – Reset all Inventory Totals
• Bit #13 – Bit #31 for future expansion
DWORD
Table A-15: External process data
Assembly
Dword
index
0Common output dataSee Table A-14
1External PressureREAL
2External TemperatureREAL
NameData type
Table A-16: Batcher
Assembly
Dword
index
0Common output dataSee Table A-14
1Batch TargetREAL
NameData type
PROFINET Siemens PLC Integration Guide41
Input and output slotsIntegration Guide
June 2022MMI-20029785
Table A-16: Batcher (continued)
Assembly
Dword
index
2Batcher Control – Discrete Actions
NameData type
• Bit #0 – Reserved
• Bit #1 – Start Fill
• Bit #2 – End Fill
• Bit #3 – Pause Fill
• Bit #4 – Resume Fill
• Bit #5 – Reserved
• Bit #6 – Start Training
• Bit #7 – Save AOC Calibration
• Bit #8 – Reset Batch Total
• Bit #9 – Print Batch Ticket
• Bit #10 – Reset Preset 1 Inventory
• Bit #11 – Reset Preset 2 Inventory
• Bit #12 – Reset Preset 3 Inventory
• Bit #13 – Reset Preset 4 Inventory
• Bit #14 – Reset Preset 5 Inventory
• Bit #15 – Reset Preset 6 Inventory
• Bit #16 – Inhibit Totalizer
• Bit #17 – Inhibit Flow
• Bit #18 – Inhibit Batch
• Bit #19 – Bit #31 for future expansion
DWORD
3Maximum Batch Time (Reg 1305)REAL
4Batch PresetUINT
Table A-17: Batcher and external process data
Assembly
Dword
index
0–2External process dataSee Table A-15
3Batch TargetREAL
42Micro Motion 5700 Ethernet transmitters
NameData type
Integration GuideInput and output slots
MMI-20029785June 2022
Table A-17: Batcher and external process data (continued)
The Emerson logo is a trademark and service mark of Emerson
Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct
Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of
their respective owners.
www.emerson.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.