This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EC declaration of conformity for directives that apply to this product. The EC declaration of
conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on
the internet at www.micromotion.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive can be found on the internet at
www.micromotion.com/documentation.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the transmitter
configuration manual. Product data sheets and manuals are available from the Micro Motion web site at
www.micromotion.com/documentation.
Return policy
Micro Motion procedures must be followed when returning equipment. These procedures ensure legal compliance with
government transportation agencies and help provide a safe working environment for Micro Motion employees. Failure to follow
Micro Motion procedures will result in your equipment being refused delivery.
Information on return procedures and forms is available on our web support system at www.micromotion.com, or by phoning the
Micro Motion Customer Service department.
Emerson Flow customer service
Email:
•Worldwide: flow.support@emerson.com
•Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
United States800-522-6277U.K.0870 240 1978Australia800 158 727
Minimum wire gauge (AWG per foot or meter)Figure 1-1:
Planning
A.AWG maximum
B.Distance of installation
Minimum wire area (mm2 per meter or foot)Figure 1-2:
Installation Manual 3
A.Minimum wire area (mm2)
B.Distance of installation
A
STATUS
SCROLLSELECT
Planning
1.4Other installation considerations
Numerous external factors can affect the meter's successful operation. To ensure that your
system works correctly, consider the factors covered in this section when designing your
installation.
1.4.1Boundary effect
Boundary effect refers to the distortion in the wave forms in the process fluid that are
caused by reflections from the pipe wall. If the pipe wall is within the meter's effective
measurement region, the boundary effect produces measurement inaccuracy.
Region of measurement boundary or sensitivity (plan view)Figure 1-3:
A.Sensitive, or effective, region
The factory calibration compensates for the boundary effect. The meter can be calibrated
for 2-inch, 2.5-inch, or 3-inch pipe. If the meter is installed in a pipe that does not match
the calibration size, the compensation will be inaccurate, and process measurement will
be inaccurate.
Verify that the meter was calibrated for the pipe size you plan to use.
4 Micro Motion Fork Viscosity Meter
1.4.2Flow rates
Maintain constant flow rates and velocities that are within the limits specified for the
meter. The fluid flow provides a steady heat flow into the meter installation, and the flow
rate influences the self-cleaning of the meter tines, the dissipation of bubbles, and the
solid contaminants around the meter.
If you install the meter in a bypass configuration (such as in a flow-through chamber), use a
pressure drop, pitot scoop, or a sample pump to maintain flow. When using a sample
pump, place the pump upstream from the meter.
1.4.3Entrained gas
Entrained gas, or gas pockets, can disrupt the measurement of a fluid. A brief disruption in
the signal caused by transient gas pockets can be corrected in the meter configuration,
but you must avoid more frequent disruptions or serious gas entrainment to ensure
accurate and reliable fluid measurement.
To minimize the possibility of entrained gas:
•Keep pipelines full of fluid at all times.
•Vent any gas prior to the meter installation location.
•Avoid sudden pressure drops or temperature changes that may cause dissolved
gases to break out of the fluid.
•Maintain a back pressure on the system that is sufficient to prevent gas breakout.
•Maintain flow velocity at the sensor within the specified limits.
Planning
1.4.4Solid contamination
To avoid issues related to solids contamination:
•Avoid sudden changes of the fluid velocity that may cause sedimentation.
•Install the meter far enough downstream from any pipework configuration that may
cause centrifuging of solids (such as at a pipe bend).
•Maintain flow velocity at the meter installation that is within the specified limits.
•Use filtration in your process, if necessary.
1.4.5Temperature gradients and insulation
For high-viscosity fluids, minimize any temperature gradients in the fluid, and in the piping
and fittings immediately upstream and downstream of the meter. Minimizing
temperature gradients reduces the effect of viscosity changes. Micro Motion recommends
using the following guidelines to reduce the thermal effects to your meter installation:
•Always insulate the meter and surrounding pipework thoroughly.
-Avoid insulating the transmitter housing.
-Use rock wool or any equivalent heat jacket material that is at least 1 inch (25
mm) thick, but preferably 2 inches (50 mm) thick.
Installation Manual 5
Planning
-Enclose insulation in a sealed protective casing to prevent moisture ingress, air
circulation, and crushing of the insulation.
-For flow-through chamber installations, use the special insulation jacket
provided by Micro Motion.
•Avoid direct heat or cold on the meter or on the associated upstream or
downstream pipe work that is likely to create temperature gradients.
•If it is necessary to protect against cooling because of flow loss, you can apply
electrical-trace heating. If you use electrical-trace heating, use a thermostat that
operates below the minimum operating temperature of the system.
1.5Recommended installations for short-stem
meters
Micro Motion recommends three standard installations for the short-stem meter to
alleviate any need for onsite calibration. All meters are factory calibrated for these types of
installations and take into consideration the potential boundary effect of each installation.
Table 1-1 highlights these different installations according to specific conditions or
requirements that may exist for your process environment.
Standard installation types: short-stem metersTable 1-1:
Flow-through
Installation type:Free streamT-Piece
Meter placementMeter tines are
inserted directly into
the main fluid flow.
The meter must always
be installed
horizontally and
oriented so that the
gap between the tines
is vertical.
Flow rate0.3 to 0.5 m/s (at the
meter)
ViscosityUp to 500 cPUp to 100 cP (250 cP in
Temperature–50 °C to 200 °C (–58
°F to 392 °F)
Meter tines are
contained in a side
pocket off the main
flow.
The meter must always
be installed
horizontally and
oriented so that the
gap between the tines
is vertical.
0.5 to 3 m/s (at main
pipe wall)
some cases)
–50 °C to 200 °C (–58
°F to 392 °F)
chamber
Meter tines are
contained in a flowthrough chamber in
which fluid is
circulated from the
main flow.
10 to 30 l/min
Up to 500 cP
–50 °C to 200 °C (–58
°F to 392 °F)
6 Micro Motion Fork Viscosity Meter
Standard installation types: short-stem meters (continued)Table 1-1:
Installation type:Free streamT-Piece
Main flow pipe size• Horizontal pipe:
minimum
diameter, 100 mm
(4 inch)
• Vertical pipe:
minimum
diameter, 150 mm
(6 inch)
Advantages• Simple installation
in large bore pipes
• Ideal for clean
fluids and nonwaxing oils
• Suitable for line
viscosity
measurement and
simple referrals
RecommendationsDo not use with:
• Dirty fluids
• Low or unstable
flow rates
• Where step
changes in
viscosity can occur
• For small bore
pipes
Minimum diameter, 50
mm (2 inch)
• Simple installation
in large bore pipes
• Ideal for clean
fluids and nonwaxing oils
• Suitable for line
viscosity
measurement and
simple referrals
Do not use with:
• Dirty fluids
• Low or unstable
flow rates
• Where step
changes in
viscosity can occur
• For small bore
pipes
• Where
temperature
effects are
significant
Planning
Flow-through
chamber
Suitable for all sizes, if
mounted in a bypass
(slipstream)
configuration
• Adaptable
installation to any
diameter main
pipe and for tank
applications
• Ideal for flow and
temperature
conditioning
• Suitable for
complex referrals
and for use with
heat exchangers
• Suitable for step
changes in
viscosity
• Fast response
• Ideal for analyzer
cubicles
• Do not use with
uncontrolled flow
rates.
• Careful system
design is required
to ensure
representative
measurement.
• Frequently requires
the use of a pump.
1.6Perform a pre-installation meter check
1.Remove the meter from the box.
Installation Manual 7
Planning
CAUTION!
Handle the meter with care. Follow all corporate, local, and national safety regulations
for lifting and moving the meter.
2.Visually inspect the meter for any physical damage.
If you notice any physical damage to the meter, immediately contact Micro Motion
Customer Support at flow.support@emerson.com.
3.Position and secure the meter in a vertical position with the flow arrow pointing
upward.
4.Connect the power wiring, and power up the meter.
Remove the back transmitter housing cover to access the PWR terminals.
Power supply wiring terminalsFigure 1-4:
A. 24 VDC
5.Perform a Known Density Verification (KDV) check.
Use the Known Density Verification procedure to match the current meter
calibration with the factory calibration. If the meter passes the test, then it has not
drifted or changed during shipment.
For more information on performing a KDV check, see the configuration and use
manual that shipped with the product.
8 Micro Motion Fork Viscosity Meter
2Mounting
Topics covered in this chapter:
•Mount in free-stream application (flanged fitting)
•Mount in free-stream application (weldolet fitting)
•Mount with a T-piece (flanged fitting)
•Mount with a flow-through chamber
•Mount in an open tank (long-stem meter)
•Mount in a closed tank (long-stem meter)
•Attach the PFA ring and circlip
•Rotate the electronics on the meter (optional)
•Rotate the display on the transmitter (optional)
Mounting
2.1Mount in free-stream application (flanged
fitting)
Prerequisites
Free-stream (flanged) installations are recommended for processes with the following
conditions:
Flow0.3 to 0.5 m/s (at the meter)
Viscosity0.5 to 12,500 cP
Temperature-50 °C to 200 °C (–58 °F to 392 °F)
-40 °C to 200 °C (-40 °F to 392 °F) in hazardous
areas
Procedure
See Figure 2-1 for information on installing the meter (with a flanged fitting) in a freestream application.
Important
Always install the meter horizontally and oriented so that the gap between the tines is vertical. This
position helps to prevent the trapping of bubbles or solids on the meter – allowing the solids to sink
and the bubbles to rise. You can use the scribe mark on the spigot (located between the flange and
transmitter) as a reference for the tine orientation. Always orient the meter so the scribe mark is at
either the 12 o’clock or 6 o’clock position.
Installation Manual 9
B
A
STATUS
SCROLLSELECT
Plan view of a vertical pipe installation
Mounting
Free-stream (flanged fitting) meter installationFigure 2-1:
A. 4-inch pipe for horizontal installations; 6-inch (152 mm) pipe for vertical installations
B. Size the recess mount so that the meter tines are inserted fully into the liquid [approximately 2.75 in
(70 mm)].
2.2Mount in free-stream application (weldolet
fitting)
The weldolet for free-stream installations has a 1.5-inch taper lock fitting and is supplied to
be welded on 4-inch, 6-inch, 8-inch or 10-inch pipelines. A weldolet installation ensures
that the tines of the meter are oriented correctly and are fully inserted into the fluid
stream.
Prerequisites
•Free-stream (weldolet) installations are recommended for processes with the
following conditions:
Flow0.3 to 0.5 m/s (at the meter)
Viscosity0.5 to 12,500 cP
Temperature–50 °C to 200 °C (–58 °F to 392 °F)
–40 °C to 200 °C (–40 °F to 392 °F) in
hazardous areas
Note
If temperature variations are a critical factor in your process, the reduced thermal mass of the
taper-lock fitting of the weldolet can track changes in temperature more efficiently.
•Before fitting the weldolet, you must bore a 2.1 in (52.5 mm) diameter opening in
the pipeline to accept the meter. You must weld the weldolet to the pipeline
concentrically with the pre-bored hole.
10 Micro Motion Fork Viscosity Meter
Loading...
+ 32 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.