Micro Motion Installation Manual: Filling Mass Transmitters | Micro Motion Manuals & Guides

Installation Manual
MMI-20017127, Rev AH
Micro Motion™ Filling Mass Transmitter
May 2021
Safety messages
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are available: the EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions. In addition the IECEx Installation Instructions for installations outside of the European Union and the CSA Installation Instructions for installations in North America are available on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com. For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. and Ireland 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 70 413
Mexico +52 55 5809 5010 France +33 (0) 800 917
Argentina +54 11 4809 2700 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy +39 8008 77334 China +86 21 2892 9000
Chile +56 2 2928 4800 Central & Eastern +41 (0) 41 7686
Peru +51 15190130 Russia/CIS +7 495 995 9559 South Korea +82 2 3438 4600
Europe and Middle East Asia Pacific
New Zealand 099 128 804
6666
India 800 440 1468
901
Japan +81 3 5769 6803
111
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
2
Installation Manual Contents
MMI-20017127 May 2021

Contents

Chapter 1 Planning.................................................................................................................... 5
1.1 Meter components...................................................................................................................... 5
1.2 Accessibility for maintenance...................................................................................................... 5
1.3 Discrete Output wiring requirements...........................................................................................5
1.4 Power requirements.................................................................................................................... 6
Chapter 2 Wiring for all Filling Mass Transmitters...................................................................... 7
2.1 I/O wiring connectors location and identification.........................................................................7
Chapter 3 Wiring for Filling Mass Transmitters with PROFIBUS-DP............................................. 9
3.1 Set the PROFIBUS-DP network switches....................................................................................... 9
3.2 Connect wires for output option Q.............................................................................................10
3.3 Connect wires for output option U.............................................................................................12
3.4 Connect wires for output option V............................................................................................. 15
Chapter 4 Wiring for Filling Mass Transmitters with Modbus....................................................19
4.1 Connect wires for output option P............................................................................................. 19
4.2 Connect wires for output option R............................................................................................. 20
4.3 Connect wires for output option S............................................................................................. 23
4.4 Connect wires for output option T............................................................................................. 24
Chapter 5 Supplementary information.....................................................................................27
5.1 Install a replacement electronics module...................................................................................27
Appendix A Specifications...........................................................................................................29
A.1 Physical specifications............................................................................................................... 29
A.2 Electrical connections................................................................................................................36
A.3 Input/output signals.................................................................................................................. 38
A.4 Digital communications............................................................................................................ 47
A.5 Host interface............................................................................................................................47
A.6 Power supply............................................................................................................................. 48
A.7 Environmental limits..................................................................................................................48
A.8 Environmental effects................................................................................................................48
A.9 Hazardous area classifications................................................................................................... 49
Installation Manual 3
Contents Installation Manual
May 2021 MMI-20017127
4 Micro Motion Filling Mass Transmitter
Installation Manual Planning
MMI-20017127 May 2021

1 Planning

1.1 Meter components

A meter consists of the following components:
A transmitter
A sensor
The following sensors are compatible with the FMT:
All CMFS sensors
F025 - F100
H025 - H100
T025 - T150
A core processor that provides additional memory and processing functions

1.2 Accessibility for maintenance

Mount the transmitter in a location and orientation that satisfies the following conditions:
Allows sufficient clearance to open the transmitter housing cover. Micro Motion
recommends 8 in (203 mm) – 10 in (254 mm) clearance at the rear of the transmitter.
Provides clear access for installing cabling to the transmitter.

1.3 Discrete Output wiring requirements

To implement a specific fill type and fill option, the Discrete Outputs on the transmitter must be wired to the appropriate valves or devices.
See Table 1-1 for requirements for discrete output wiring.
Notes
The information presented here applies only to transmitters with Discrete Outputs.
Only supported options are listed.
The term Configurable DO refers to the Configurable Discrete Input/Discrete Output
when configured as a Discrete Output. When the fill type and option do not require this output for the purge valve, the Configurable Discrete Output/Discrete Input can be used for a variety of other application purposes as needed.
If the internal power source is used, do not connect any terminal to ground.
Installation Manual 5
Planning Installation Manual
May 2021 MMI-20017127
Table 1-1: Wiring requirements for fill types and fill options
Fill type with options Precision DO1 Precision DO2 Configurable DO
Standard one-stage Primary valve N/A N/A
Standard one-stage with purge Primary valve N/A Purge valve
Standard one-stage with pump Primary valve Pump As needed
Standard two-stage Primary valve Secondary valve As needed
Standard two-stage with purge Primary valve Secondary valve Purge valve
Timed Primary valve N/A As needed
Timed with purge Primary valve N/A Purge valve
Dual-fillhead Valve in Fillhead #1 Valve in Fillhead #2 As needed
Timed dual-fillhead Valve in Fillhead #1 Valve in Fillhead #2 As needed

1.4 Power requirements

The transmitter is powered by one of the Eurofast (M-12) connectors. Refer to the wiring instructions for your output configuration.
The power supply requirements are:
24 VDC
5.5 W plus I/O requirements
1 A maximum at the 24 VIO passthrough
NOTICE
Do not connect +24VDCin (–) to +24VI/O (–) external to the device. The +24VI/O passthrough supply should remain floating. Making this connection externally will prevent proper operation of the +24VI/O current limit.
6 Micro Motion Filling Mass Transmitter

Installation Manual Wiring for all Filling Mass Transmitters

MMI-20017127 May 2021
2 Wiring for all Filling Mass
Transmitters

2.1 I/O wiring connectors location and identification

Use the figure below to locate and identify the three I/O wiring connectors on the transmitter. These connectors are referred to by their letter names, “A”, “B”, and “C”.
Note
The pin numbers are not labeled on the transmitter or connectors. Compare the pin positions in the figure with the positions on the transmitter and connectors to determine the proper pin numbering.
Figure 2-1: I/O wiring connectors
5
6 4
8
5
8
2 1
3
21
64
7
C
A
B
4
1
3
2
7
3
A. 8-pin male power and Modbus® connector
B. 5-pin female PROFIBUS® connector
C. 8-pin female discrete I/O connector or Frequency Output and I/O power (depending
upon configuration option)
Installation Manual 7
Wiring for all Filling Mass Transmitters Installation Manual
May 2021 MMI-20017127
8 Micro Motion Filling Mass Transmitter
A
B
C D E
F

Installation Manual Wiring for Filling Mass Transmitters with PROFIBUS-DP

MMI-20017127 May 2021
3 Wiring for Filling Mass Transmitters
with PROFIBUS-DP

3.1 Set the PROFIBUS-DP network switches

Before connecting the transmitter to the PROFIBUS network, you must set the device parameters using the internal PROFIBUS network address and network termination switches.
The network address and network termination switches are located inside the transmitter housing. See Figure 3-1.
Figure 3-1: PROFIBUS network switches
A. 4 x 5/16" bolts
B. Housing cover C. Network address switch – ones digit D. Network address switch – tens digit
E. Network address switch – hundreds digit
F. Network termination DIP switches
Procedure
Installation Manual 9
1. Loosen the four 5/16" bolts securing the housing cover.
2. Lift the housing cover straight up.
Wiring for Filling Mass Transmitters with PROFIBUS-DP Installation Manual
May 2021 MMI-20017127
3. Set the PROFIBUS network address switches as appropriate for your network.
The allowable address range for PROFIBUS-DP devices is 000 to 126. The default address is 126.
4. Set the two network termination DIP switches. Both switches must be set the same.
Option Description
ON/ON Use this option when there is a termination resistor on the local network
segment.
OFF/OFF Use this option when there is not a termination resistor on the local
network segment.
5. Lower the housing cover onto the base of the transmitter.
6. Tighten the four 5/16" bolts.

3.2 Connect wires for output option Q

The FMT transmitter with output option Q has a combined 24V/mA connector, a Frequency Output connector, and a PROFIBUS-DP connector.
Prerequisites
Before connecting the PROFIBUS-DP plug, you must set the internal PROFIBUS network switches.
Procedure
Insert an appropriate cable into each of the connectors shown in Figure 3-2.
10 Micro Motion Filling Mass Transmitter
Installation Manual Wiring for Filling Mass Transmitters with PROFIBUS-DP
MMI-20017127 May 2021
Figure 3-2: Option Q connectors
mA (+)
mA (–)
Service port A
Service port B
A
+24 VDC in (–)
+24 VDC in (+)
5
6 4
7
8
3
21
+24 V I/O (+)
+24 V I/O (–)
5
64
3
8
2 1
7
Frequency output (–)
Frequency output (+)
C
B
PROFIBUS B
4
3
2
PROFIBUS A
A. 8-pin male power and Modbus connector
B. 5-pin female PROFIBUS connector C. 8-pin female Frequency Output and I/O power connector
Table 3-1: Option Q - power and Modbus connector
Pin identification Wire color Outputs
Pin 1 White +24 VDC in (+)
Pin 2 Brown RS-485B/Universal Service Port (USP)
Pin 3 Green RS-485A/Universal Service Port (USP)
Pin 4 Yellow mA (-)
1
Pin 5 Gray mA (+)
Pin 6 Pink Inactive
Pin 7 Blue +24 VDC in (-)
Pin 8 Red Inactive
Installation Manual 11
Wiring for Filling Mass Transmitters with PROFIBUS-DP Installation Manual
May 2021 MMI-20017127
Table 3-2: Option Q - PROFIBUS connector
Pin identification Wire color Outputs
Pin 1 Inactive Inactive
Pin 2 Green PROFIBUS A
Pin 3 Inactive Inactive
Pin 4 Red PROFIBUS B
Pin 5 Inactive Inactive
Table 3-3: Option Q - Frequency Output and I/O power connector
M12 pin Wire color Outputs
Pin 1 White Frequency Output (+)
Pin 2 Brown Inactive
Pin 3 Green +24 V I/O (-)
Pin 4 Yellow +24 V I/O (+)
Pin 5 Gray Inactive
Pin 6 Pink Inactive
Pin 7 Blue Frequency Output (-)
Pin 8 Red Inactive
Note
Inactive outputs should not be used for this configuration.

3.3 Connect wires for output option U

The FMT with output option U has a combined 24V/mA connector, a discrete output/ discrete input connector, and a PROFIBUS-DP connector. This output configuration enables direct wiring to the valve, including power output to the valve.
Prerequisites
Before connecting the PROFIBUS-DP plug, you must set the internal PROFIBUS network switches.
Procedure
Insert an appropriate cable into each of the connectors shown in Figure 3-3.
12 Micro Motion Filling Mass Transmitter
Installation Manual Wiring for Filling Mass Transmitters with PROFIBUS-DP
MMI-20017127 May 2021
Figure 3-3: Option U connectors
mA (+)
mA (–)
Precision DO1 (+)
Configurable DO/DI (+)
Service port A
Service port B
Precision DO1 (-)
Configurable DO/DI (-)
A
C
B
PROFIBUS B
4
3
PROFIBUS A
1
2
+24 VDC in (–)
+24 VDC in (+)
+24 V I/O (+)
+24 V I/O (–)
Precision DO2 (+)
Precision DO2 (-)
5
6 4
7
8
5
3
8
2 1
3
21
64
7
A. 8-pin male power and Modbus connector
B. 5-pin female PROFIBUS connector C. 8-pin female discrete I/O connector
Table 3-4: Option U - power and Modbus connector
Pin identification Wire color Outputs
Pin 1 White +24 VDC in (+)
Pin 2 Brown RS-485B/Universal Service Port (USP)
Pin 3 Green RS-485A/Universal Service Port (USP)
Pin 4 Yellow mA (-)
Pin 5 Gray mA (+)
Pin 6 Pink Inactive
Pin 7 Blue +24 VDC in (-)
Pin 8 Red Inactive
Installation Manual 13
Wiring for Filling Mass Transmitters with PROFIBUS-DP Installation Manual
May 2021 MMI-20017127
Table 3-5: Option U - PROFIBUS connector
Pin identification Wire color Outputs
Pin 1 Inactive Inactive
Pin 2 Green PROFIBUS A
Pin 3 Inactive Inactive
Pin 4 Red PROFIBUS B
Pin 5 Inactive Inactive
Table 3-6: Option U - discrete I/O connector
M12 pin Wire color Outputs
Pin 1 White Configurable DO/DI (+)
Pin 2 Brown Precision DO2 (-)
Pin 3 Green +24 V I/O (-)
Pin 4 Yellow +24 V I/O (+)
Pin 5 Gray Precision DO1 (+)
Pin 6 Pink Precision DO1 (-)
Pin 7 Blue Configurable DO/DI (-)
Pin 8 Red Precision DO2 (+)
Isolated output wiring
Figure 3-4 shows an example wiring arrangement for a primary fill valve.
14 Micro Motion Filling Mass Transmitter
Installation Manual Wiring for Filling Mass Transmitters with PROFIBUS-DP
MMI-20017127 May 2021
Figure 3-4: Example isolated output wiring
+24 V I/O (+)
+24 V I/O (–)
Precision DO1 (+)
5
3
8
2 1
Precision DO (-)
64
7
A
C
Valve or pilot valve solenoid
A. 8-pin male power and Modbus connector
B. 5-pin female PROFIBUS connector C. 8-pin female discrete I/O connector

3.4 Connect wires for output option V

B
The FMT with output option V has a combined 24V/mA connector, a Discrete Output/ Discrete Input connector, and a PROFIBUS-DP connector. This output configuration enables direct wiring to the valve, including power output to the valve.
Prerequisites
Before connecting the PROFIBUS-DP plug, you must set the internal PROFIBUS network switches.
Procedure
Insert an appropriate cable into each of the connectors shown in Figure 3-5.
Installation Manual 15
Loading...
+ 35 hidden pages