Micro Motion Installation Instructions: Canadian Standards Association Intrinsic Safety Installation Instructions MVD Transmitters | Micro Motion Manuals & Guides

Installation Manual
CSA-D-IS Installation Instructions, MVD Transmitters
Preparation
20001965, Rev ED
January 2022
Safety messages
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The following are available: the EU declaration of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions. In addition the IECEx Installation Instructions for installations outside of the European Union and the CSA Installation Instructions for installations in North America are available on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com. For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. and Ireland 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 70 413
Mexico +52 55 5809 5010 France +33 (0) 800 917
Argentina +54 11 4809 2700 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy +39 8008 77334 China +86 21 2892 9000
Chile +56 2 2928 4800 Central & Eastern +41 (0) 41 7686
Peru +51 15190130 Russia/CIS +7 495 995 9559 South Korea +82 2 3438 4600
Europe and Middle East Asia Pacific
New Zealand 099 128 804
6666
India 800 440 1468
901
Japan +81 3 5769 6803
111
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
2
Installation Manual Contents
20001965 January 2022

Contents

Chapter 1 Before you begin........................................................................................................5
1.1 About this document...................................................................................................................5
1.2 Hazard messages.........................................................................................................................5
1.3 Hazardous area installations........................................................................................................ 6
Chapter 2 800 Enhanced core processor..................................................................................... 7
Chapter 3 1500 and 2500 transmitters....................................................................................... 9
3.1 1500/2500 4-wire installations.................................................................................................... 9
3.2 1500/2500 9-wire installations.................................................................................................. 14
Chapter 4 1700 and 2700 transmitters..................................................................................... 19
4.1 1700 and 2700 transmitter outputs...........................................................................................19
4.2 1700/2700 4-wire installations.................................................................................................. 27
4.3 1700/2700 integral core processor installations........................................................................ 32
4.4 1700/2700 remote core processor installations.........................................................................37
Chapter 5 2750 4-wire with enhanced core processor and sensor............................................. 43
Chapter 6 3500 transmitters.................................................................................................... 45
6.1 3500 4-wire installations............................................................................................................45
6.2 3500 remote core processor installations.................................................................................. 50
Chapter 7 3700 transmitters.................................................................................................... 55
7.1 3700 4-wire installations............................................................................................................55
7.2 3700 core processor installations...............................................................................................60
7.3 3700 remote core processor installations.................................................................................. 62
Chapter 8 4200 transmitters.................................................................................................... 69
Chapter 9 5700 transmitters.................................................................................................... 71
9.1 5700 transmitter outputs.......................................................................................................... 71
9.2 5700 4-wire installations............................................................................................................77
9.3 5700 9-wire installation............................................................................................................. 80
Chapter 10 Booster amplifiers.................................................................................................... 81
10.1 Booster amplifiers with D600 sensors...................................................................................... 81
Chapter 11 Direct host 4-wire.................................................................................................... 85
11.1 Core processor to direct host through a safety barrier..............................................................86
11.2 Enhanced core processor to direct host through a safety barrier.............................................. 87
Chapter 12 LFT 4-wire to LF sensor installation........................................................................... 89
12.1 Remote LFT CIO with LF sensor................................................................................................ 90
12.2 Remote LFT on DIN rail with LF sensor......................................................................................91
12.3 Remote LFT FOUNDATION fieldbus with LF sensor....................................................................... 92
Installation Instructions 3
Contents Installation Manual
January 2022 20001965
12.4 Remote LFT mA Output/Frequency Output with LF sensor.......................................................93
12.5 Remote LFT Profibus-PA with LF sensor....................................................................................94
Appendix A List of drawings........................................................................................................95
4 Micro Motion CSA-D-MVD Transmitter
Installation Manual Before you begin
20001965 January 2022

1 Before you begin

1.1 About this document

Use this manual to ensure that any applicable Micro Motion flow meter installation complies with Canadian Standards Association (CSA) safety standards.
The information in this document assumes that users understand basic transmitter and sensor installation concepts and procedures.
This manual provides only information associated with installation of transmitters through CSA-D-IS, MVD instructions. For complete information on flow meter installation, see the documentation provided with your sensor and transmitter.

1.2 Hazard messages

This document uses the following criteria for hazard messages based on ANSI standards Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access to protect users' assets. This is true for all systems used within the facility.
Installation Instructions 5
Before you begin Installation Manual
January 2022 20001965

1.3 Hazardous area installations

If your cable will be installed in a hazardous area, ensure that it meets the hazardous area requirements.
WARNING
Failure to maintain intrinsic safety in a hazardous area could cause an explosion resulting in injury or death.
To keep sensor wiring intrinsically safe:
Keep intrinsically safe (IS) sensor wiring separate from power supply wiring and output
wiring.
Do not install power cable in the same conduit or cable tray as flow meter cable.
Use this document with the appropriate approvals documentation. These manuals are
shipped with the flow meter or available at www.emerson.com.
For hazardous area installations in Europe, refer to standard EN 60079-14 if national
standards do not apply.
6 Micro Motion CSA-D-MVD Transmitter
Installation Manual 800 Enhanced core processor
20001965 January 2022

2 800 Enhanced core processor

This drawing describes an 800 enhanced core processor installation.
Installation Instructions 7
800 Enhanced core processor Installation Manual
January 2022 20001965
8 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1500 and 2500 transmitters
20001965 January 2022

3 1500 and 2500 transmitters

3.1 1500/2500 4-wire installations

List of drawings
Installation Drawing
1500/2500 4-wire core processor to CMF, F, H, R, CNG, or T sensors
1500/2500 4-wire with core processor and CMF400 sensor with booster amplifier
1500/2500 4-wire with core processor and D600 sensor
1500/2500 4-wire with enhanced core processor and sensor
EB-20001220, Revision A
EB-20001219, Revision A
EB-20001218, Revision A
EB-20003009, Revision A
Installation Instructions 9
1500 and 2500 transmitters Installation Manual
January 2022 20001965

3.1.1 1500/2500 4-wire core processor to CMF, F, H, R, CNG, or T sensors

This drawing does not apply to the CMF300A sensor or to the CMF400 sensor with booster amplifier.
10 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1500 and 2500 transmitters
20001965 January 2022

3.1.2 1500/2500 4-wire with core processor and CMF400 sensor with booster amplifier

Installation Instructions 11
1500 and 2500 transmitters Installation Manual
January 2022 20001965

3.1.3 1500/2500 4-wire with core processor and D600 sensor

12 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1500 and 2500 transmitters
20001965 January 2022

3.1.4 1500/2500 4-wire with enhanced core processor and sensor

Installation Instructions 13
1500 and 2500 transmitters Installation Manual
January 2022 20001965

3.2 1500/2500 9-wire installations

List of drawings
Installation Drawing
1500/2500 with remote core processor and CMF, D, DL, F, H, or T sensors
1500/2500 with remote core processor and CMF400 sensor with booster amplifier
1500/2500 with core processor and D600 sensor
1500/2500 with core processor and DT sensor EB-20001225, Revision A
EB-20001221 Revision BA
EB-20001223, Revision A
EB-20001222, Revision A
14 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1500 and 2500 transmitters
20001965 January 2022

3.2.1 1500/2500 with remote core processor and CMF, D, DL, F, H, or T sensors

This drawing does not apply to the D600, DT, or CMF400 with booster amplifier sensors.
Installation Instructions 15
1500 and 2500 transmitters Installation Manual
January 2022 20001965

3.2.2 1500/2500 with remote core processor and CMF400 sensor with booster amplifier

16 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1500 and 2500 transmitters
20001965 January 2022

3.2.3 1500/2500 with core processor and D600 sensor

Installation Instructions 17
1500 and 2500 transmitters Installation Manual
January 2022 20001965

3.2.4 1500/2500 with core processor and DT sensor

18 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1700 and 2700 transmitters
20001965 January 2022

4 1700 and 2700 transmitters

4.1 1700 and 2700 transmitter outputs

List of drawings
Transmitter Drawing
1700/2700 mA Outputs EB-3600479, Revision CA
1700/2700 intrinsically safe outputs EB-3600629, Revision DA
2700 configurable inputs and outputs EB-3600667, Revision B
1700/2700 FOUNDATION™ fieldbus outputs EB-3600476, Revision DA
1700/2700 fieldbus (FISCO) EB-20007552, Revision B
1700/2700 Profibus-PA outputs EB-3600473, Revision DA
2750 configurable inputs and outputs EB-20011794, Revision A
Installation Instructions 19
1700 and 2700 transmitters Installation Manual
January 2022 20001965

4.1.1 1700/2700 mA Outputs

20 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1700 and 2700 transmitters
20001965 January 2022

4.1.2 1700/2700 intrinsically safe outputs

Installation Instructions 21
1700 and 2700 transmitters Installation Manual
January 2022 20001965

4.1.3 2700 configurable inputs and outputs

22 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1700 and 2700 transmitters
20001965 January 2022

4.1.4 1700/2700 FOUNDATION™ fieldbus outputs

Installation Instructions 23
1700 and 2700 transmitters Installation Manual
January 2022 20001965

4.1.5 1700/2700 fieldbus (FISCO)

24 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1700 and 2700 transmitters
20001965 January 2022

4.1.6 1700/2700 Profibus-PA outputs

Installation Instructions 25
1700 and 2700 transmitters Installation Manual
January 2022 20001965

4.1.7 2750 configurable inputs and outputs

26 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1700 and 2700 transmitters
20001965 January 2022

4.2 1700/2700 4-wire installations

List of drawings
Installation Drawing
1700/2700 4-wire with core processor and sensor
1700/2700 4-wire with core processor and CMF400 sensor with booster amplifier
1700/2700 4-wire with core processor and D600 sensor
1700/2700 4-wire with enhanced core processor and sensor
EB-3600482, Revision B
EB-3005819, Revision C
EB-1005983, Revision B
EB-20003010, Revision A
Installation Instructions 27
1700 and 2700 transmitters Installation Manual
January 2022 20001965

4.2.1 1700/2700 4-wire with core processor and sensor

This drawing does not apply to D600 sensors or CMF400 sensors with a booster amplifier.
28 Micro Motion CSA-D-MVD Transmitter
Installation Manual 1700 and 2700 transmitters
20001965 January 2022

4.2.2 1700/2700 4-wire with core processor and CMF400 sensor with booster amplifier

Installation Instructions 29
1700 and 2700 transmitters Installation Manual
January 2022 20001965

4.2.3 1700/2700 4-wire with core processor and D600 sensor

30 Micro Motion CSA-D-MVD Transmitter