ProLink, MVD Direct Connect, and PlantWeb are marks of one of the Emers on Process Management family of companies. All
other trademarks are property of their respective owners.
Micro Motion pursues a policy of continuous development and product improvement. The specification in this document may
therefore be changed without notice. To the best of our knowledge, the information contained in this document is accurate and
Micro Motion cannot be held responsible for any errors, omissions, or other misinformation contained herein. No part of this
document may be photocopied or reproduced without prior written consent of Micro Motion.
ivMicro Motion 7826/7828 Insertion Liquid Density Meters
Page 7
Chapter 1
Introduction
1.1Safety guidelines
Handle the 7826/7828 liquid density meter with great care.
•Do not drop the meter.
•Do not use liquids incompatible with materials of construction.
•Do not operate the meter above its rated pressure or maximum temperature.
•Do not pressure test beyond the specified test pressure.
•Do not expose the meter to excessive vibration (> 0.5 g continuous).
•Do not modify this instrument in any way (mechanical or electrical) or the factory warranty
will be invalidated. This meter can be ordered with Zirconium wetted parts. In this case,
mechanical modifications of any kind may produce a safety hazard and must not be
performed.
Installation (Short Stem)
•Do not exceed the stated supply voltage range, otherwise the meter may be damaged and a
hazard may exist.
•Ensure all explosion-proof requirements have been applied.
•Ensure the meter and associated pipework are pressure tested to 1-1/2 times the maximum
operating pressure after installation.
•Ensure the transmitter housing covers are tightened properly after wiring to maintain ingress
protection.
•Take great care not to damage the meter as this may affect the meter calibration and can result
in failure. Take extra care when handling PFA-coated tines as the coating is not resistant to
impact damage. Always fit the protective cover when the meter is not in use.
•Always store and transport the meter in its original packaging. For the long-stem meters, be
sure to include the transit cover secured by the grub screws.
•To return a meter, refer to the Return Policy appendix for more information on the
Micro Motion return policy.
Safety messages are provided throughout this manual to protect personnel and equipment. Read each
safety message carefully before proceeding to the next step.
1.2About the 7826/7828 liquid density meter
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
1.2.1What is it?
The 7826/7828 liquid density meter is based on the proven tuning fork technology. It is an all-welded
sensor that is designed for insertion into a pipeline, open tank, or closed tank.
Installation and Configuration Manual1
Page 8
Introduction
Electronics housing
Spigot
Tines
Stem:
• Is sealed at both ends
and air filled
• Is available in varying
lengths
Fluid density is determined directly from the resonant frequency of the tuning fork immersed in the
fluid. A temperature sensor (RTD) is also fitted within the transmitter to indicate the operating
temperature.
The 7826/7828 meter is available in the following options:
•a short-stem or long-stem version
The long-stem version can come in lengths up to 13 ft (4 m). The long-stem version is ideally
suited to open tank and closed tank applications.
•a frequency output version (7826 meter only) or an Advanced electronics version.
The 7826 meter with frequency output outputs the density measurement as a square wave
signal, and features a RTD to output the operating temperature measurement. It is typically
used with a signal converter, such as the 795x Series, and offers a powerful tool in critical
density applications.
The 7826/7828 meter with Advanced electronics incorporates much of the 795x signal
converter functionality, such that online density calculations are performed locally within the
electronics housing of the 7826/7828 meter. It features two 4–20 mA outputs and
RS-485/Modbus communications, providing simple accessibility to all calculated values.
1.2.2What is it used for?
The 7826/7828 meter is ideally suited to applications where continuous, real-time measurement of
density is required. For example, it can be used in process control where density is the primary
control parameter for the end product, or is an indicator of some other quality control parameter such
as % solids, or % concentration.
1.2.3Measurements and calculations
The Advanced electronics version contains integral processing electronics to provide full in-situ
configuration, enabling it to perform a variety of calculations.
2Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 9
Introduction
The 7826/7828 meter continuously measures the following fluid properties:
From these properties, the following are calculated:
•Line density (measured in kg/m
3
, g/cc, lb/gal, or lb/ft3)
•Operating temperature (measured in °C or °F)
•API base density at 15 °C, 1.013 bar (60 °F, 14.5 psi)
•Base density (by using the matrix referral method)
•°API
•Specific gravity
•Special function calculations such as °Brix, °Baume, °Twaddle, % solids, etc.
1.2.4Outputs from frequency output version (7826 meter only)
Outputs from the frequency output version of the 7826 meter include:
•Line density in g/cc – as a frequency (periodic time) signal
•Line (operating) temperature in °C – as a RTD signal
These outputs can be taken directly in by a 795x signal converter (or flow computer), which can then
calculate live density-related parameters:
•Base/referred density (using API tables or a matrix referral)
•Specific gravity
•°API
•°Brix
•% Solids
•% Mass
•% Volume
•% Concentration
Note: Features vary between versions and issues of 795x liquid software.
For information on electrical connections between the 7826 meter and a 795x unit, see the Electrical
Connections (Frequency Output) chapter.
Installation (Short Stem)
Installation (Long Stem)Introduction
1.2.5Outputs from the Advanced electronics version
No signal converter is required, which simplifies wiring and enables the 7826/7828 meter to be
connected directly to plant monitoring and control systems and/or a local indicator.
Installation and Configuration Manual3
Electrical Connections (Frequency
Output) - 7826 Only
Page 10
Introduction
Two forms of output are available:
•Two 4–20mA analog outputs, factory set but individually configurable span, bias, limits, and
filter options. The standard factory settings for these outputs are Line density on Analog
Output 1, and Line temperature on Analog Output 2. Alternatively, the analog outputs may be
controlled by one of the following:
•Line density
•Line temperature
•°API
•Specific gravity
•Base density (API)
•Base density (matrix referral method)
•Special calculation result
•An RS-485 (Modbus) interface, giving access to other measurement results, system
information and configuration parameters.
The 7826/7828 meter is factory set to perform either API or Matrix referrals.
Re-configuration of the meter default settings (see Appendix A) is achieved by linking a PC to
the Modbus (RS-485) connection and running ADView or ProLink II (version 2.9 or later)
software. After the 7826/7828 meter is configured, the PC can be removed.
1.2.6Typical meter application with Advanced electronics
Net Mass flow rate calculation
Figure 1-1 shows an outline of a typical wet process mineral application where the 7826/7828 meter
provides a 4–20 mA signal of the % solids determination from the slurry stream. From this signal and
the measured volumetric flow rate, net mass flow rate is determined.
The output signal could also be used for % solids control, or for net mass flow rate ratio blend control.
The optional 7826/7828 meter (Modbus) connection to a PC running ADView or ProLink II software
can be used for configuration and access to other measured values.
4Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 11
Introduction
Figure 1-1.Typical meter application with Advanced electronics
Installation (Short Stem)
1.3Principle of Operation
The 7826/7828 liquid density meter operates on the vibrating element principle, the element in this
case being a tuning fork structure that is immersed in the liquid being measured. The tuning fork is
excited into oscillation by a piezoelectric device internally, secured at the root of one tine. The
frequency of vibration is detected by a second piezoelectric device, which is secured in the root of the
other tine.
The meter sensor is maintained at its natural resonant frequency, as modified by the surrounding
liquid, by an amplifier circuit located in the electronic housing. This frequency of vibration is a
function of the overall mass of the tine element and the density of the liquid in contact with it. As the
density of the liquid changes, the overall vibrating mass changes, and therefore the resonant frequency
changes.
By measuring this frequency and applying the following equation, the density of the liquid can be
calculated.
ρ = K0 + K1τ + K2τ
Where:
•ρ= Fluid uncorrected density (kg/m
•τ= Time period of meter (µs)
•K0, K1, K2= meter calibration coefficients
Installation (Long Stem)Introduction
Electrical Connections (Frequency
2
Output) - 7826 Only
3
)
Installation and Configuration Manual5
Page 12
Introduction
6Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 13
Chapter 2
Installation (Short Stem)
For information on installing a long-stem version of the 7826/7828 liquid density meter, see
Chapter 3.
2.1Introduction
All drawings and dimensions given in this manual are given here for planning purposes only. Before
commencing fabrication, reference should always be made to the current issue of the appropriate
drawings. Contact Micro Motion for details.
For further information on handling and using the meter, see “Safety guidelines” on page 1 and “Safety
Information” on page 8.
There are a variety of external factors that affect the ability of the 7826/7828 liquid density meter to
operate successfully. In order to ensure that your system works correctly, the effects of these factors
must be taken into consideration when designing your installation.
There are two main aspects to consider:
•The accuracy and repeatability of the measurements
•The relevance of the measurements to the overall purpose of the system
Factors which may adversely affect accuracy and repeatability include:
•The presence of gas or bubbles within the fluid being measured
•Non-uniformity of the fluid
•The presence of solids as contaminants
•Fouling of the meter
Installation (Short Stem)
Installation (Long Stem)Introduction
•Temperature gradients
•Cavitations and swirls
•Operating at temperatures below the wax point of crude oils
•The correct pipe diameter that corresponds to the calibration of the meter.
In some applications, absolute accuracy is less important than repeatability. For example, in a system
where the control parameters are initially adjusted for optimum performance, and thereafter only
checked periodically.
Installation and Configuration Manual7
Electrical Connections (Frequency
Output) - 7826 Only
Page 14
Installation (Short Stem)
The term achievable accuracy can be used to describe a measure of the product quality that can be
realistically obtained from a process system. It is a function of measurement accuracy, stability and
system response. High accuracy alone is no guarantee of good product quality if the response time of
the system is measured in tens of minutes, or if the measurement bears little relevance to the operation
of the system. Similarly, systems which require constant calibration and maintenance cannot achieve
good achievable accuracy.
Factors which may adversely affect the relevance of the measurements could include:
•Measurement used for control purposes being made too far away from the point of control, so
that the system cannot respond properly to changes.
•Measurements made on fluid which is unrepresentative of the main flow.
2.2Safety Information
2.2.1General information applicable to the complete system
•These safety instructions are to be used whenever handling or operating this product. Suitably
trained personnel shall carry out the installation both mechanical and electrical in accordance
with the applicable local and national regulations and codes of practice for each discipline.
•Safe working practices for the media and process concerned must be followed during the
installation and maintenance of the equipment. Depressurize and isolate the system before
starting to loosen or remove any connection.
•If the equipment is likely to come into contact with aggressive substances, it is the
responsibility of the user to take suitable precautions that prevent it from being adversely
affected.
•It is the responsibility of the installer/user of this equipment to ensure:
•This product is not used as a support for other equipment or personnel.
•This product is protected from impact.
•It is important that this sensor is handled with care due to its sensitivity to impact.
2.2.2Pressure bearing parts
•It is the responsibility of the installer/user of this equipment to ensure:
•The materials of construction are suitable for the application.
•All piping connections conform to the local and national regulations and codes of practice.
•The pressure and temperature limits for this equipment are not exceeded, if necessary by
the use of suitable safety accessories. See Table 2-1 for pressure and temperature limits for
Zirconium 702 process connections. Pressure and temperature ratings for other materials
are in accordance with the relevant flange standard.
8Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 15
Installation (Short Stem)
Table 2-1 Zirconium 702 Pressure and temperature flange ratings
•Correct gaskets/seals are fitted and are compatible with the media and process.
•The installed sensor is adequately supported for weight and vibration effects.
•Personnel are protected from hot burns by guards, thermal lagging or limited access.
Allow time to cool prior to carrying out maintenance operations. It is recommended that
“HOT” notices are fitted in the vicinity of the equipment where applicable.
•Regular inspection for corrosion and wear are carried out, both internal and external.
•The sensor must not be fitted until all installation work and final precommissioning checks are
carried out. Do not remove blanking plugs until the sensor is fitted.
•The sensor must be installed in compliance with this manual, to ensure correct fitting. This
applies to all variants.
•The user should not repair this equipment, but general maintenance can be applied as
described within this manual.
Installation (Short Stem)
2.3Boundary effects
Any insertion device or meter can only measure the properties of the fluid within the region of fluid to
which it is sensitive.
For practical reasons, it is helpful to consider the sensitive, or effective region, for the meter as an
ovoid centered on the tips of the tines with its long axis aligned with the direction in which the tines
vibrate, as shown below. The 7826/7828 meter is insensitive to the properties of the fluid outside this
region and progressively more sensitive to fluid properties the closer the fluid is to the tines.
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
Installation and Configuration Manual9
Page 16
Installation (Short Stem)
lon g a x is
short
axis
Top or P lan view
4” horizontal pipe
2”Schedule 40
Pocket or “T”
If part of this volume is taken up by the pipework or fittings there is said to be a boundary effect; i.e.,
the intrusion of the pipe walls will alter the calibration. The diagram below illustrates the 7826/7828
meter installed in a pocket on the side of a 4" (100 mm) horizontal pipe line (viewed from above). The
effective region is completely enclosed within the pipe line and thus is completely fluid.
This next view shows other pipe outlines superimposed:
10Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 17
Installation (Short Stem)
The smaller circle represents a 4" (100 mm) vertical pipe, which because the 7826/7828 meter
orientation is constant irrespective of pipe orientation intersects the effective region. The 6" (150
mm) pipe is the smallest pipe diameter to completely enclose the effective region when the pipe is
vertical. Thus smaller pipe diameters can lead to a variety of different geometries which would each
require a separate calibration.
An alternative condition is shown in the next diagram where the side pocket is extended until it passes
completely through the effective region producing a “core”:
Installation (Short Stem)
From this, it would appear that almost every installation requires a separate in-situ calibration – a very
undesirable situation. The problem is resolved by providing standard calibration geometries which
can be used in all pipe work configurations and thereby allow the factory calibration conditions to be
reproduced in the process.
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
Installation and Configuration Manual11
Page 18
Installation (Short Stem)
2.4Viscosity effects
The 7826/7828 liquid density meter can be affected by the viscosity of the fluid surrounding it, which
is manifested in two ways:
•An error in the density measurement, that is due to the effect of viscosity on the vibration of
the fork tines.
•In T-piece installations, where the 7826/7828 meter is retracted into a pocket but away from
the main fluid flow, high viscosity impedes the flushing of fluid near the tines. This may mean
that, if a step change in density occurs, the fluid being measured will not representative of the
fluid in the main flow, and the density response time may be extended significantly.
A summary of these effects and the action to be taken to minimize them is given in Table 2-2.
Table 2-2Viscosity effects
Viscosity rangeRemedy
T-piece installations only
• Less than 100 cPNone required.
• Greater than 100 cPDensity measurements may be unpredictable; use flow-through
All other installations
• Up to 500 cPNone required
• Above 500 cPDensity measurements may be unpredictable.
chamber or free stream installation.
(Where the main flow is greater than 1.5 m/s and there is no waxing
present, the T-piece installation can be used for viscosities not
exceeding 250 cP.)
2.5Standard installations
2.5.1Overview
To overcome the need for in-situ calibration for every installation, three standard installations are
proposed. If an installation conforms to one of these standards, the factory calibration of the
7826/7828 meter is valid, and in-situ calibration unnecessary. Table 2-3 summarizes the three
installations. For tank installations, consult Micro Motion.
• Suitable for line viscosity
measurement and simple
referrals.
• Dirty fluids.
• Low or unstable flow rates.
• Where step changes in
viscosity can occur.
• For small bore pipes.
-50 to 200°C
(-58 to 392°F)
100 mm (4") horizontal or
larger
• Simple installation in large
bore pipes.
• Ideal for clean fluids and
non-waxing oils.
• Suitable for line viscosity
measurement and simple
referrals.
• Dirty fluids
• Low or unstable flow rates.
• Where step changes in
viscosity can occur.
• for small bore pipes.
• Where temperature effects
are significant.
-50 to 200°C
(-58 to 392°F)
Any
• Adaptable installation to
any diameter main pipe
and for tank applications.
• Ideal for flow and
temperature conditioning.
• Suitable for complex
referrals and for use with
heat exchangers.
• Suitable for step changes
in viscosity.
• Fast response.
• Ideal for analyzer
cubicles.
• Uncontrolled flow rates.
• Careful system design
required to ensure
representative
measurement.
• Frequently requires the
use of a pump.
Installation (Short Stem)
(1)
Approval for use in hazardous areas is limited to –40 to +200°C (–40 to +392°F)
2.5.2Meter orientation
For free stream and T-piece installations, the meter must always be installed horizontally and
orientated to allow flow in the gap between the tines. This is irrespective of the pipe line orientation,
and helps to prevent the trapping of bubbles or solids on the meter.
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
Installation and Configuration Manual13
Page 20
Installation (Short Stem)
Bub bles ri se!
Solids sink!
the slot
must be
vertical
.
For ALL pipe and flow direc tions
.
the meter
mus t be
horizontal
Figure 2-1Meter orientation
Note: All drawings and dimensions given in the following sections are derived from detailed
dimensional drawings. They are given here for planning purposes only. Before commencing
fabrication, reference should always be made to the current issue of the appropriate drawings contact Micro Motion for details.
2.5.3Free stream installation - flanged fitting
Conditions:
•Flow: 0.3 to 0.5 m/s (at the meter)
•Viscosity: Up to 500 cP
•Temperature: -50 °C to 200 °C (–58 °F to 392 °F)
[-40 °C to 200 °C (-40 °F to 392 °F) in hazardous areas]
Note: The thermal mass of the flanges may affect the response time of the meter to temperature
changes.
The view shown below is schematic to show the dimensions of the side pocket, which is fabricated by
the end user.
14Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 21
Installation (Short Stem)
4” or larg er;
horizontal
6” or larger ;
vertical
2.75”
(70 mm ±2 mm)
7.75”
(197 mm)
Free Stream; flanged
2” (52.3 mm)
wall thickness
at least
0.15” (3 .9 12 mm)
2” Schedule 40
4.37”
(111 mm)
0.47” (1 2 m m)
PTFE
ring
PTFE
ring
PFA
ring
Circlip
(not Zirconium)
Installation (Short Stem)
The pocket geometry must be consistent with 2" schedule 40 tube in both internal diameter and
minimum wall thickness, such as:
•Internal diameter: 2" (52.5 mm)
•Wall thickness: minimum 0.15" (3.912 mm)
Weld neck or slip-on flanges may be used, according to the flange rating selected. However, for
higher rated flanges, only slip-on flanges may give the necessary clearances.
How to fit the circlip and PFA ring
The meter is supplied with a PFA ring which may be attached to the location step with a circlip to
center the tines within the 2” schedule 40 or 80 pipe. An exception is the Zirconium version of the
meter, which uses a self-locking PFA ring and does not require a circlip.
Prior to installation, place the PFA ring around the boss on the underside of the meter flange. Then
attach the circlip to hold the PFA ring in place (see Figure 2-2). The PFA ring and circlip are supplied
with the meter.
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
Installation and Configuration Manual15
Page 22
Installation (Short Stem)
Before fittings
After fittings
Circlip (not Zirconium)
PFA ring
The Zirconium version of
the meter uses a
self-locking PFA ring and
does not require a circlip.
Figure 2-2How to fit the circlip and PFA ring
2.5.4Free stream installation - weldolet
This is the preferred option where temperature variations are a critical factor. The reduced thermal
mass of the weldolet's taper-lock fitting renders it more able to track rapid changes in temperature.
Conditions:
•Flow: 0.3 to 0.5 m/s (at the meter)
•Viscosity: Up to 500 cP
•Temperature: -50 °C to 200 °C (–58 °F to 392 °F)
[-40 °C to 200 °C (-40 °F to 392 °F) in hazardous areas]
The weldolet has a 1.5" taper lock fitting, and is supplied to be welded on 4", 6", 8" or 10" pipelines.
Use of the weldolet ensures that the tines of the 7826/7828 meter are orientated correctly and are fully
inserted into the fluid stream.
Before fitting the weldolet, the pipeline must be bored through at 2.1" (52.5 mm) diameter to accept
the meter. The weldolet must be welded to the pipeline concentrically with the pre-bored hole.
The view shown below is a schematic to show the relevant dimensions.
16Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 23
Installation (Short Stem)
10” (254 mm)
Horizontal: 4” or larger
Vertical: 6” or larger
Weld
4.4” (111 mm)
Free stream weldolet
to suit pipe diameter
(4, 6, 8 or 10” N.B.)
2.1” (52.5 mm)
min
Figure 2-3Free stream 1.5" Swagelock fitting
The installation will conform generally to Schedule 40 pressure ratings. The weldolet fabrication is
rated to 100 Bar at ambient temperature.
Installation (Short Stem)
Note: Correct installation and pressure testing of the fitting is the responsibility of the user.
2.5.5T-piece installation
Conditions:
The thermal mass of the flanges may affect the response time of the meter to temperature changes.
Flow velocity at the pipe wall and fluid viscosity must be within the limits shown to ensure that the
fluid within the pocket is refreshed in a timely manner. This installation will not respond as rapidly as
the free-stream installation to step changes in viscosity.
The view shown is a schematic to show the dimensions of the side pocket, which is fabricated by the
end user.
•Flow: 0.5 to 3.0 m/s (at the pipe wall)
•Viscosity: Up to 100 cP, or 250 cP under some conditions
•Temperature: -50 °C to 200 °C (–58 °F to 392 °F)
[-40 °C to 200 °C (-40 °F to 392 °F) in hazardous areas]
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
Installation and Configuration Manual17
Page 24
Installation (Short Stem)
“T” piece Flanged
D
4” or larg er;
horizontal
or vertical
6.9”
(175 mm ±2
mm)
7.75”
(197 mm)
2” (52. 3 mm)
wall t hickness
at least
0.15” (3.912 mm)
2” Schedule 40
PFA
ring
Circlip
(not Zircon ium)
0.47” (12 mm)
4.37” (111 m m )
The pocket geometry must be consistent with 2" schedule 40 tube in both internal diameter and
minimum wall thickness, i.e.:
•Internal diameter: 2.1" (52.5 mm)
•Wall thickness : minimum 0.15" (3.912 mm)
Alternatively, schedule 80 tube may be used, but this affects the calibration, and must be specified
when ordering the sensor.
Weld neck or slip-on flanges may be used, according to the flange rating selected. However, for
higher rated flanges, only slip-on flanges may give the necessary clearances.
For normal flow conditions (up to 3 m/s at the pipewall), the tines should be retracted 1” (25 mm)
from the main pipe wall. For higher flow rates, increase this by 10 mm for every 1 m/s increase in
main flow rate.
For hygienic applications, normal 2” hygienic tube is too thin for this application; (it can vibrate in
sympathy with the fork, causing measurement errors). Use 3” hygienic tube and fittings instead, or
fabricate hygienic fittings with the same wall thickness and internal diameter as those shown in the
diagram above.
Prior to installation, place the PFA ring around the boss on the underside of the meter flange, and then
attach the circlip to hold the PFA ring in place. An exception is the Zirconium version of the meter,
which uses a self-locking PFA ring and does not require a circlip. See “How to fit the circlip and PFA
ring” on page 15.
2.5.6T-piece weldolet installation
18Micro Motion 7826/7828 Insertion Liquid Density Meters
This is the preferred option where temperature variations are a critical factor. The reduced thermal
mass of the weldolet's taper-lock fitting renders it more able to track rapid changes in temperature.
Page 25
Installation (Short Stem)
D
X
10.4” (264 mm)Y
O2.1” (52.5 mm) min
DimY = Dim X - DimD + 1.8” (or 43 mm)
3 m/s
4 m/s
5 m/s
6 m/s
Max flowrate
1”
1.4”
1.8”
2.2”
Dim X Inch
Carbon Steel
Stainless Stee l
25.4
35.4
45.4
55.4
Dim X mm
Conditions:
•Flow: 0.5 to 3.0 m/s at the main pipe wall. (Operation is possible with higher flow rates, if
dimension X is increased (see diagram below).
•Viscosity limit: Up to 100 cP, or 250 cP under some conditionss
•Temperature: -58 to +392 °F (-50 °C to +200 °C)
The weldolet has a 1.5" taper lock fitting, and is supplied to be welded on 4", 6", 8" or 10" pipelines.
Use of the weldolet ensures that the tines of the 7826/7828 meter are orientated correctly and are fully
inserted into the fluid stream. The length of the weldolet is determined by the flow rate in the main
pipeline (refer to the table in Figure 2-4), and is chosen to ensure that the tines of the 7826/7828 meter
are sufficiently retracted from the main pipe wall. Dimension X should be the smallest possible,
consistent with the maximum expected flow rate.
Before fitting the weldolet, the pipeline must be bored through at 2” (52.5 mm) diameter to accept the
meter. The weldolet must be welded to the pipeline concentrically with the pre-bored hole. The view
shown below is schematic to show the relevant dimensions.
Flow velocity at the pipe wall and fluid viscosity must be within the limits shown to ensure that the
fluid within the pocket is constantly refreshed. This installation will not respond as rapidly as the
free-stream installation to step changes in viscosity.
Installation (Short Stem)
Figure 2-4T-Piece weldolet installation
The installation must conform to Schedule 40 pressure ratings. Alternatively, schedule 80 tube may be
used, but this will affect the calibration, and must be specified when ordering the sensor.
The weldolet fabrication is rated to 1450 psi (100 Bar) at ambient temperature.
Note: Correct installation and pressure testing of the fitting is the responsibility of the user.
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
2.5.7Flow-through chamber installation
Flow-through chambers are fabricated by Micro Motion, and are available with either weld prepared
ends or with flange or compression fittings for connection into the process pipe lines. They are
available with 1" NB, 2" NB, or 3" NB inlet and outlet pipes.
Installation and Configuration Manual19
Page 26
Installation (Short Stem)
Dimensions shown in inches (mm)
Note: The length of the inlet and outlet pipes must not be altered, otherwise the temperature response
and stability of the fitting may be adversely affected.
Conditions:
•Flow: constant, between 10 and 30 l/min for 2" sch 40 calibration bore section, 5–300 l/min
for 3" sch 80 calibration bore.
•Viscosity: Up to 1000 cP
•Temperature: -50 °C to 200 °C (–58 °F to 392 °F)
[-40 °C to 200 °C (-40 °F to 392 °F) in hazardous areas]
•Pressure: 70 bar @ 204 °C, subject to process connections.
The RTD is a direct insertion type, without a thermowell, and uses a
The diagram below shows an example of this type of standard installation.
½" Swagelok connection.
The three compression fittings on the flow pockets (½" drain, ¾" temp probe, and 1-½" mounting nut
for the meter) are rated to above the working pressure of the flow pocket. The fittings may be
Swagelok or Parker; both are used in manufacture.
The fittings are certified to the following standards:
•Swagelok: SO9001 / 9002, ASME,TUV,CSA,DNV
•Parker: ISO 9001 / 9002, TUV, DNV, LLOYDS
20Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 27
Installation (Short Stem)
2.6Installation in the pipeline or system
Density is a highly sensitive indicator of change in a fluid – a key reason why density measurement is
increasingly being chosen as a process measurement.
This sensitivity means that the measurement can be very sensitive to extraneous effects and therefore
great care must be taken to consider all the factors which affect measurement when assessing the
installation requirements.
Like many other meters, the optimum performance of the meter depends upon certain conditions of
the fluid and configuration of the process pipe-work. By introducing appropriate flow conditioning,
the optimum performance of the 7826/7828 meter can be achieved at any chosen location in the
process system.
You must first select a location which serves the application objective; e.g. installed close to the point
of control. Then, consideration can be given to fluid conditioning at that point. Where the application
requirements allow a degree of tolerance in the point chosen for installation, the installation may be
able to take advantage of natural flow conditioning.
The choice of mechanical installation (free stream, “T” piece or flow-through chamber) will be
dictated partly by application needs and partly by the fluid conditions, such as:
•Condition of fluid at the sensor
•Thermal effects
•Flow rate
•Entrained gas
•Solids contamination
•Lined pipework
Fluid at the sensor
The fluid in the effective zone of the 7826/7828 meter must be of uniform composition and at uniform
temperature. It must be representative of the fluid flow as a whole.
This is achieved either by mixing of the fluid either using a static inline mixer or taking advantage of
any natural pipe condition that tends to cause mixing, such as pump discharge, partially open valves.
The meter should be installed downstream where the flow is just returning to laminar flow conditions.
Installation (Short Stem)
Installation (Long Stem)Introduction
Thermal effects
For high viscosity fluids, temperature gradients in the fluid and in the pipe work and fittings
immediately upstream and downstream of the meter should be minimized in order to reduce the effect
of viscosity changes.
Always insulate the meter and surrounding pipework thoroughly. Insulation must be at least
1" (25 mm) of rockwool, preferably 2" (50 mm) (or equivalent insulating heat jacket) and enclosed in
a sealed protective casing to prevent moisture ingress, air circulation, and crushing of the insulation.
Special insulation jackets are available from Micro Motion for the flow-through chambers, which,
because of the low volumetric flow rates and hence low heat flow, are more vulnerable to temperature
effects.
Avoid direct heating or cooling of the meter and associated pipe work upstream and downstream that
is likely to create temperature gradients. If it is necessary to provide protection against cooling due to
loss of flow, electrical trace heating may be applied, provided it is thermostatically controlled and the
thermostat is set to operate below the minimum operating temperature of the system.
Installation and Configuration Manual21
Electrical Connections (Frequency
Output) - 7826 Only
Page 28
Installation (Short Stem)
In cases where it is necessary to heat or cool the fluid - to bring it within the temperature range of the
meter, for example - heat exchangers can be installed in the fluid flow. The factory can provide more
details on this, or provide a complete system, if required.
Flow rate
Flow rates and velocities should be maintained relatively constant within the limits given. The fluid
flow provides a steady heat flow into the meter section, and the flow rate influences the self cleaning
of the sensor and the dissipation of bubbles and solid contaminants.
Where it is necessary to install the meter in a by-pass (either using the free stream installation in a 4"
diameter horizontal by-pass, or a flow-through chamber), flow may be maintained using pressure
drop, pitot scoop, or by a sample pump. Where a pump is used, the pump should be upstream of the
meter.
Entrained gas
Gas pockets can disrupt the measurement. A brief disruption in the signal caused by transient gas
pockets can be negated in the signal conditioning software, but more frequent disruptions or serious
gas entrainment must be avoided. This can be achieved by observing the following conditions:
•Keep pipe lines fully flooded at all times
•Vent any gas prior to the meter
•Avoid sudden pressure drops or temperature changes which may cause dissolved gases to
break out of the fluid
•Maintain a back pressure on the system sufficient to prevent gas break out (e.g. back pressure
equivalent to twice the ‘head loss’ plus twice the vapor pressure)
•Maintain flow velocity at the sensor within the specified limits.
Solids contamination
•Avoid sudden changes of velocity that may cause sedimentation.
•Install the meter far enough downstream from any pipework configuration which may cause
centrifuging of solids (e.g. bends).
•Maintain flow velocity at the sensor within the specified limits.
•Use filtration if necessary.
Lined pipe work
Some installations may require lined pipe work for corrosion resistance reasons. In such cases, if the
internal diameter of the pipe work surrounding the fork differs from the ordered calibration boundary,
an on-site calibration adjustment may be required.
Example installation
The diagram below illustrates some of the principles outlined in this section. It shows a free-stream
meter installation with an additional sample take off. The position of both is such that the static
mixing (which could be caused by pump discharge or partially closed valve), has negated the adverse
effects of bends and established laminar flow, and has ensured that the fluid is thoroughly mixed and
thus of uniform composition and temperature. The ideal place for a free stream or “T” piece
installation, or for the by-pass take off point is where the flow has just begun to be laminar.
Note: The insulation extends upstream and downstream far enough to prevent conduction losses in the
pipe walls from degrading the temperature conditioning of the fluid at the sensor.
22Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 29
Installation (Short Stem)
Mixing produces a fluid
which has uniform
composition, and
temperature and hence
uniform density
Temperature
Centre
Wall
Swirl
Static mixing
(or natural turbulence)
Turbulent flow
Onset of
heat loss effects
Critical Insulation
Onset
of laminar flow
Fork D ensitometers
or
sample take off for
by-pass installed sensors
Heat
Loss
Heat
Loss
Higher temperature
Lower density
Lower temperature
Higher density
Density
Installation (Short Stem)
2.7Commissioning
1. Once the pipework installation has been prepared, and before installing the meter, fit a
blanking flange or compression nut to the meter mounting, and pressurize and flush the
system.
2. Isolate the system, depressurize and remove the blanking flange or compression nut.
3. Install the meter.
4. Slowly pressurize the system and check for leaks, particularly if the normal operating
temperature is high, or the sensor has been fitted cold; tighten as necessary.
5. Once the system has stabilized and is leak free, fit the insulation material, remembering also to
insulate any flanges.
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
Installation and Configuration Manual23
Page 30
Installation (Short Stem)
Dimensions in inches (mm)
5.5 (140)
∅4.3 (109)
Mounting to suit 1.5″ Swagelok or
similar cone
1.2
(31)
1/2″ NPT both sides
4.8 (121)
0.5
(12)
7826: 5.8 (148.4)
7828: 4.9 (125.4)
∅1.38 (35)
2.8Short Stem Dimensional Drawings
2.8.1Cone-seat connection
Figure 2-5Cone-seat connection details
24Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 31
Installation (Short Stem)
Dimensions in inches (mm)
7826: 5.8 (148.4)
7828: 4.9 (125.4)
5.5 (140)
∅4.3 (109)
1.2
(31)
1/2″ NPT both sides
4.8 (121)
0.5
(12)
∅1.38 (35)
2.8.2Flange connection
Figure 2-6.Flange connection details
Installation (Short Stem)
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
Installation and Configuration Manual25
Page 32
Installation (Short Stem)
26Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 33
Chapter 3
Installation (Long Stem)
For information on installing a short-stem version of the 7826/7828 liquid density meter, see
Chapter 2.
3.1Introduction
All drawings and dimensions given in this manual are given here for planning purposes only. Before
commencing fabrication, reference should always be made to the current issue of the appropriate
drawings. Contact Micro Motion for details.
To protect the tines from damage, a Transit Cover is fitted prior to shipment from the factory. The Transit
Cover is held in place by 2 grub screws. Be sure to remove and store the Transit Cover prior to
installation. Re-fit the Transit Cover if storing or transporting, such as for repair. If the Transit Cover has
been lost, it can be purchased from Micro Motion.
For further information on handling and using the meter, see Safety Guidelines in Chapter 1.
There are a variety of external factors that affect the ability of the 7826/7828 liquid density meter to
operate successfully. In order to ensure that your system works correctly, the effects of these factors
must be taken into consideration when designing your installation.
There are two main aspects to consider:
•The accuracy and repeatability of the measurements
Installation (Short Stem)
Installation (Long Stem)Introduction
•The relevance of the measurements to the overall purpose of the system
Factors which may adversely affect accuracy and repeatability include:
•The presence of gas or bubbles within the fluid being measured
•Non-uniformity of the fluid
•The presence of solids as contaminants
•Fouling of the meter
•Temperature gradients
•Cavitations and swirls
•Operating at temperatures below the wax point of crude oils
In some applications, absolute accuracy is less important than repeatability. For example, in a system
where the control parameters are initially adjusted for optimum performance, and thereafter only
checked periodically.
Installation and Configuration Manual27
Electrical Connections (Frequency
Output) - 7826 Only
Page 34
Installation (Long Stem)
The term achievable accuracy can be used to describe a measure of the product quality that can be
realistically obtained from a process system. It is a function of measurement accuracy, stability and
system response. High accuracy alone is no guarantee of good product quality if the response time of
the system is measured in tens of minutes, or if the measurement bears little relevance to the operation
of the system. Similarly, systems which require constant calibration and maintenance cannot achieve
good achievable accuracy.
Factors which may adversely affect the relevance of the measurements could include:
•Measurement used for control purposes being made too far away from the point of control, so
that the system cannot respond properly to changes.
•Measurements made on fluid which is unrepresentative of the main flow.
3.2Safety Information
3.2.1General information applicable to the complete system
•These safety instructions are to be used whenever handling or operating this product. Suitably
trained personnel shall carry out the installation both mechanical and electrical in accordance
with the applicable local and national regulations and codes of practice for each discipline.
•Safe working practices for the media and process concerned must be followed during the
installation and maintenance of the equipment. Depressurize and isolate the system before
starting to loosen or remove any connection.
•If the equipment is likely to come into contact with aggressive substances, it is the
responsibility of the user to take suitable precautions that prevent it from being adversely
affected.
•It is the responsibility of the installer/user of this equipment to ensure:
•This product is not used as a support for other equipment or personnel.
•This product is protected from impact.
•It is important that this sensor is handled with care due to its sensitivity to impact.
28Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 35
Installation (Long Stem)
3.2.2Pressure bearing parts
•It is the responsibility of the installer/user of this equipment to ensure:
•The materials of construction are suitable for the application.
•All piping connections conform to the local and national regulations and codes of practice.
•The pressure and temperature limits for this equipment are not exceeded, if necessary by
the use of suitable safety accessories.
•Correct gaskets/seals are fitted and are compatible with the media and process.
•The installed sensor is adequately supported for weight and vibration effects.
•Personnel are protected from hot burns by guards, thermal lagging or limited access.
Allow time to cool prior to carrying out maintenance operations. It is recommended that
“HOT” notices are fitted in the vicinity of the equipment where applicable.
•Regular inspection for corrosion and wear are carried out, both internal and external.
•The sensor must not be fitted until all installation work and final precommissioning checks are
carried out. Do not remove blanking plugs until the sensor is fitted.
•The sensor must be installed in compliance with this manual, to ensure correct fitting. This
applies to all variants.
•The user should not repair this equipment, but general maintenance can be applied as
described within this manual.
Installation (Short Stem)
3.3Installation considerations
Density is a sensitive indicator of change in a fluid - a key reason why density measurement is
increasingly being chosen as a process measurement. However, density measurements can be
sensitive to extraneous effects and, therefore, great care must be taken to consider all the factors
which may affect measurement when assessing the installation requirements.
Like many other meters, the optimum performance of the meter depends upon certain conditions of
the fluid. You must first select a suitable position where the fork’s tines are always completely
immersed in the fluid. Although tolerant of solids, turbulence and bubbles, there should be at least a
200 mm clearance from objects e.g. impellers, pipe stubs, etc.
Then consideration can be given to fluid conditioning at that point. Where the application
requirements allow a degree of tolerance in the point chosen for installation, the installation may be
able to take advantage of natural flow conditioning.
The choice of mechanical installation will be dictated partly by application needs and partly by the
fluid conditions, such as:
•Condition of fluid at the sensor
•Flow rate
•Entrained gas
•Solids contamination
3.3.1Fluid at the sensor
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
The fluid in the effective zone of the long stem 7826/7828 meter must be of uniform composition and
at uniform temperature. It must be representative of the fluid as a whole. This is achieved by taking
advantage of any natural tank condition that tends to cause mixing, such as pump discharge, partially
open valves etc.
Installation and Configuration Manual29
Page 36
Installation (Long Stem)
3.3.2Flow rate
If there is flow in the tank, the rate of flow should ideally be not more than 0.5 m
exceed this, a ‘shift’ will be introduced into density readings. The higher the flow rate is, the larger
the ‘shift’. Measurements also become ‘noisy’.
3.3.3Entrained gas
Gas pockets can disrupt the measurement. A brief disruption in the signal caused by transient gas
pockets can be negated in the internal signal conditioning software, but more frequent disruptions or
serious gas entrainment must be avoided. This can be achieved by observing the following
conditions:
•Vent any gas prior to the meter.
•Avoid sudden pressure drops or temperature changes which may cause dissolved gases to
break out of the fluid.
3.3.4Solids contamination
•Avoid sudden changes of velocity that may cause sedimentation.
3
/s. If flow rates
•Install the meter far enough away from any build-up of solids.
•Maintain flow velocity at the sensor within the specified limits.
•Specify the long-stem 7826/7828 meter with a non-stick PFA protective layer.
3.4Open-tank installation
Only the safe area model may be used in open-tank installation.
1. For open-tank installations, the long-stemmed 7826/7828 meter is clamped to a structure (see
Figure 3-1). The position of the clamp determines the insertion depth.
Figure 3-1Open-tank installation
30Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 37
Installation (Long Stem)
2. Keep the tines away from the tank wall (see Figure 3-2).
Figure 3-2Keeping tines away from the tank wall (Open-tank)
3. Keep the tines immersed in fluid (see Figure 3-3).
Figure 3-3Keeping tines immersed (Open-tank)
Installation (Short Stem)
4. Keep tines away from objects and disturbed flow (see Figure 3-4).
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
Installation and Configuration Manual31
Page 38
Installation (Long Stem)
Figure 3-4Keeping tines away from objects and disturbed flow (open tank)
5. If there is flow, align the tines such that the flow is directed towards the gap between the tines
(see Figure 3-5).
Figure 3-5Aligning the tines in flow (Open-tank)
6. Keep away from deposit build-up (see Figure 3-6).
32Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 39
Installation (Long Stem)
Figure 3-6Avoid deposit build-up (Open-tank)
3.5Closed-tank installation
1. For closed-tank installations, the long-stemmed 7826/7828 meter should have a factory fitted
flange attachment. (This is an option that is specified as a code in the part number – see a list
of the product options in the product data sheet available at www.micromotion.com.) (See
Figure 3-7).
Installation (Short Stem)
Figure 3-7Closed-tank installation
2. To vary the insertion depth, a standoff section with flange (not supplied) can be used (see
Figure 3-8).
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
Installation and Configuration Manual33
Page 40
Installation (Long Stem)
Figure 3-8Use of standoff section (not supplied)(closed-tank)
3. Keep the tines immersed in fluid (see Figure 3-9).
Figure 3-9Keeping tines immersed (closed tank)
4. Keep the tines away from the tank wall (see Figure 3-10).
Figure 3-10 Keeping away from tank wall (closed tank)
5. Allow for flexing of the tank lid, preventing the long-stemmed 7826/7828 meter from being
pushed towards a tank wall or into the path of disturbed flow (see Figure 3-11).
34Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 41
Installation (Long Stem)
Figure 3-11 Allowing for tank lid flexing (closed tank)
6. Keep tines away from objects and disturbed flow (see Figure 3-12).
Figure 3-12 Keeping tines away from objects and disturbed flow (Closed-tank)
Installation (Short Stem)
Installation (Long Stem)Introduction
7. If there is flow, align the tines such that the flow is directed towards the gap in the tines (see
Figure 3-13)
Installation and Configuration Manual35
Electrical Connections (Frequency
Output) - 7826 Only
Page 42
Installation (Long Stem)
Figure 3-13 Aligning the tines in flow (closed tank)
8. Keep away from deposit build-up (see Figure 3-14).
Figure 3-14 Avoid deposit build-up (closed tank)
3.6Calibration
The log-stemmed 7826/7828 meter is factory calibrated and no further calibration is necessary. The
calibration is traceable to Micro Motion onsite ISO17025-accredited laboratory.
For calibration range, see the 7826/7828 liquid density meter product data sheet available at
www.micromotion.com.
3.7If the tank is pressurized
1. Once the installation has been prepared, and before installing the 7826/7828 meter, fit a
blanking flange or compression nut to the 7826/7828 meter mounting, and pressurize and flush
the system.
2. Isolate the system, depressurize and remove the blanking flange or compression nut.
3. Install the 7826/7828 meter.
4. Slowly pressurize the system and check for leaks, particularly if the normal operating
temperature is high, or the sensor has been fitted cold; tighten as necessary.
36Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 43
Installation (Long Stem)
∅4.29 (109)
5.75 (146)
4.53 (115)
Pipe must be securely
clamped in at least two
places along this length.
Electronic housing
External Earth
connector
Lower nodal mass
Long stem 1.5″ SCH 80 tube
Vibrating element
Dimensions in inches (mm)
Mounting hardware is customer specific, and is not supplied.
7826: 6.7 (170)
7828: 5.71 (145)
∅1.38 (35)
Stem length is to customer specification. Can be between
19.68 (500) (minimum) to 78.74 (2000) (maximum) .
5. Once the system has stabilized and is leak free, fit the insulation material, remembering also to
insulate any flanges.
3.8Long Stem Dimensional Drawings
3.8.1Open-tank connection
Figure 3-15 Open-tank connection (cast housing)
Installation (Short Stem)
Installation (Long Stem)Introduction
Electrical Connections (Frequency
Output) - 7826 Only
Installation and Configuration Manual37
Page 44
Installation (Long Stem)
∅4.75 (120)
6.89 (175)
5.04 (128)
Pipe must be securely clamped
in at least two places along this
length.
Amplifier housing
External Ear th
screw
Lower nodal mass
Long stem 1.5″ SCH 80 tube
Vibrating element
Dimensions in inches (mm)
Mounting hardware is customer specific, and is not supplied.
Upper nodal mass
Cover lock screw
M4 x 5 ST.STL -
Kept captive by
data label
NPT
7826: 6.7 (170)
7828: 5.71 (145)
∅1.38 (35)
Stem length is to customer specification. Can be between
19.68 (500) (minimum) to 78.74 (2000) (maximum).
∅4.29 (109)
11.4 (290)
4.53 (115)
Connection to pipeline (Zone 0 area) by means
of a standardized industr y flange (for example,
DIN, ANSI, BS, or JIS Limit ANSI 1500
equivalent)
Electronic housing
External Earth
connector
Lower nodal mass
Long stem 1.5″ SCH 80 tube
Vibrating element
Dimensions in inches (mm)
5.5 (140)
NPT
7826: 6.7 (170)
7828: 5.71 (145)
Stem length is to customer specification.
Can be between 19.68 (500) (minimum) to
40Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 47
Electrical Connections (Frequency Output) – 7826 Only
Chapter 4
Electrical Connections (Frequency Output) – 7826
Only
The following information is applicable to the 7826 liquid density meter only. For information on
making the electrical connections for the 7826 and 7828 liquid density meters with Advanced
electronics, see Electrical Connnections (Advanced) chapter.
For installations in hazardous areas:
•For ATEX installations, the electrical installation must strictly adhere to the safety information
given in the ATEX safety instructions booklet shipped with this manual. See Safety Information in
Chapter 1 for important information.
•For installations in USA and Canada, the electrical installation must strictly adhere to the Electrical
Codes and a conduit seal is required within 2” (50 mm) of the enclosure.
This chapter shows you how to wire up the 7826 liquid density meter and then connect it to the
®
Micro Motion
795x series of computers.
4.2Installation considerations
4.2.1Power supply
The power supply to the 7826 liquid density meter must have the following requirements:
•Voltage: Nominally 24 VDC, but in the range 23 to 27 VDC.
•Current: 50 mA
4.2.2EMC
To meet the EC Directive for EMC (Electromagnetic Compatibility), it is recommended that the 7826
meter be connected using a suitable instrumentation cable containing an overall screen. This should
be earthed at both ends of the cable. At the 7826 meter, the screen can be earthed to the meter body
(and therefore to the pipework), using a conductive cable gland.
It is not necessary to earth the meter through a separate connection; this is usually achieved directly
through the metalwork of the installation.
Installation Manual41
Page 48
Electrical Connections (Frequency Output) – 7826 Only
4.2.4Cabling requirements
Although it is possible to connect separate cables to the 7826 meter for power and the signal outputs,
it is recommended that all connections are made through one instrumentation-grade cable.
The instrumentation cable should be individually screened twisted-pairs with an overall screen, foil or
braid for the cable. Where permissible, the screen should be connected to earth at both ends. (At the
7826 meter, this is best done using a conductive cable gland.)
Cables should conform to BS2538. In the USA, use Belden 9402 (two-pair) or Beldon 85220
(single-pair). Other cables that are suitable are those that meet BS5308 Multi-pair Instrumentation
Types 1 and 2, Belden Types 9500, 9873, 9874, 9773, 9774 etc.
The typical maximum recommended cable length for the above cable types is 1000 m (3200 ft), but
care must be taken to ensure that the power supply at the meter is at least 23 V. Thus, for 24 V power
supply, the overall resistance for the power supply connections (both wires in series) must be less than
100 ohms.
In order to complete the wiring, you will need the following parts:
•½” NPT to M20 gland adapter
•½” NPT blanking plug
•M20 x 1 cable gland (not supplied).
The gland adapter and blanking plug are supplied with the 7826 meter – these two parts are
Ex d rated. However, you will need to get a suitably rated cable gland:
•For non-hazardous area installations, use an IP68 or higher rated cable gland.
•For hazardous area installations use an Ex d-rated cable gland.
In hazardous areas, all parts must be explosion-proof. Alternative parts may be required in order to
meet local electrical installation regulations.
4.2.5Surge protection
Careful consideration should be given to the likelihood of power supply surges or lightning strikes.
The power supply connections of the 7826 meter have a surge arrestor fitted that gives protection
against power supply transients.
If there is a possibility of lightning strikes, external surge protection devices - one for each pair of
signals and the power supply - should be installed as close to the 7826 meter as possible.
Another method of surge protection is to connect an MOV (Metal Oxide Varistor) (breakdown voltage
>30 V) with an NE-2 neon bulb in parallel across each wire and ground. These can be mounted in a
junction box close to the 7826 meter.
4.2.6Installation in explosive areas
For installations in hazardous areas:
•For ATEX installations, the electrical installation must strictly adhere to the safety
information given in the ATEX safety instructions booklet shipped with this manual. See
Safety Information in Chapter 1 for important information.
•For installations in USA and Canada, the electrical installation must strictly adhere to the
Electrical Codes and a conduit seal is required within 2” (50 mm) of the enclosure.
42Micro Motion 7826/7828 Insertion Liquid Density Meter
Page 49
Electrical Connections (Frequency Output) – 7826 Only
GRUB
HOLE
1/ 2" N P T
HOLE
1/2" NPT PLUG Exd IIC
1/2" TO M20 x 1 ADAPTOR
Exd IIC
M20 x 1 CABLE GLAND
Exd IIC
SUPPL Y SIG
200 mm OF UNSCRE ENED WIRE
TERMINAL BOARD
A
CABLE GLAND
The 7826 meter is an explosion-proof and flameproof device. However, it is essential to observe the
rules of compliance with current standards concerning flameproof equipment:
•Electronics housing caps should be tightened securely and locked in position by their locking
screws.
•The electrical cable or conduit should have an appropriate explosion-proof cable gland fitted.
•If any electrical conduit entry port is not used, it should be blanked off using the appropriate
explosion-proof blanking plug, with the plug entered to a depth of at least five threads.
•The spigot must be locked in place.
4.2.7Installation in non-hazardous areas
Typically the 7826 meter will operate over cable lengths up to 2 km from a 24 V supply.
Micro Motion recommend cables similar to BS 5308 or RS 368.
1. Open the Terminal Board side of the
meter’s electronics housing by
undoing the grub screw and
unscrewing the lid anticlockwise.
2. The meter is normally mounted
horizontally such that the 1/2” NPT
holes are on a vertical plane. This
minimizes water ingress. Identify the
1/2" NPT hole which is lowest and
attach the multi-core cable to it.
3. Assemble the adaptor, cable gland and
cable so that the multi-core cable is
gripped leaving 200 mm of free,
unscreened wire to connect to the
terminal blocks.
Electrical Connections (Frequency Output) – 7826 Only
NEST WIRES
PRT
Term 1
SUPPLY SIG
+ - + -
VIEW FROM UNDERNEATH THE ELECTRONICS
5. The adjacent diagram shows all the
electrical connections to the meter
terminal block.
6. When you have screwed the wires into
the correct terminals, carefully tuck
the wires around the electronics, and
tighten the cable gland.
erm 8
7. Screw the housing cap on fully and
tighten the locking grub screw using
the 2.5 mm AF hex drive.
4.4Connecting the meter to a 795x series computer
4.4.1Overview
The meter requires a 795x series computer (Signal Converter or Flow Computer) with liquid-based
application software for it to be functional. This section provides a guide to possible wiring
connections between the meter and the 795x. Configuration of the 795x is outside the scope of this
manual. For this task, refer to the 795x operating manual that was supplied with the 795x instrument.
795x computers are available as a 7950 Wall Mount unit or 7951 Panel Mount unit. Each type of unit
has a different position and layout for the physical connections. There is even a choice of two
connection panels for the 7951 - Klippon or D-type (Cannon).
TIGHTEN
CAP
TIGHTEN
GRUB
:
44Micro Motion 7826/7828 Insertion Liquid Density Meter
Page 51
Electrical Connections (Frequency Output) – 7826 Only
Frequency Output
7826
1
+
Supply
2
-
3
+
Signal
4
-
5
6
7
8
RTD
Density power +
PL9/1
Ch.1
PL9/2
PL9/3
PL9/4
PL12/1
PL12/2
PL12/3
PL12/4
PL9/5
Ch.2
PL9/6
PL9/7
PL9/8
PL12/5
PL12/6
PL12/7
PL12/8
Density input +
Density input -
Density power -
RTD power +
RTD signal +
RTD signal -
RTD power -
7950 Flow Computer/Signal Converter
PL9/9
PL9/10
Ground
PL12/9
PL12/10
Ground
795xConnectors used
795010-way Klippon
795125-way D-type (Cannon) or 10-way Klippon
Note: The choice of rear panel connectors for the 7951 is done prior to ordering the unit so that it is
manufactured to satisfy the customers connector requirement.
Use this table to quickly find the appropriate connection diagrams.
795xFigure
7950Signal Converter/Flow ComputerFigure 4-1
7951Signal Converter/Flow ComputerFigure 4-2
Note: “Signal Converter” and “Flow Computer” are terms that are often used to identify the basic
purpose of the 795x application software. Refer to the supplied 795x operating manual if in doubt
about identification.
Electrical Connections (Frequency Output) – 7826 Only
Frequency Output
7826
1
+
Supply
2
-
3
+
Signal
4
-
5
6
7
8
RTD
7951 Signal Converter/Flow Computer
24V pwr +
PL5/9 (SK6/22)
Ch.1
PL5/1 (SK6/14)
PL5/2 (SK6/15)
PL5/10 (SK6/24)
PL7/1 (SK7/14)
PL7/2 (SK7/15)
PL7/3 (SK7/16)
PL7/4 (SK7/17)
PL5/9 (SK6/22)
Ch.2
PL5/3 (SK6/16)
PL5/4 (SK6/17)
PL5/10 (SK6/24)
PL7/5 (SK7/18)
PL7/6 (SK7/19)
PL7/7 (SK7/20)
PL7/8 (SK7/21)
Den ip +
Den ip -
24V pwr -
RTD pwr +
RTD sig +
RTD sig -
RTD pwr -
(0V dc)
(+24V dc)
(Den +)
(Den -)
PL9/9 (SK6/25)
PL9/10 (SK6/25)
Ground
(0Vdc)
PL5/10 (SK6/25)
PL12/10 (SK6/25)
Ground
(0Vdc)
Figure 4-2Connecting a meter to a 7951 Signal Converter/Flow computer (non-hazardous area)
4.5System connections (customer’s own equipment)
Incorrectly connecting the meter can damage the unit.
The power supply requirements from the customer’s own equipment are as follows:
•For Density Meter: 23 to 27 VDC, 50 mA minimum
•For Meter RTD: 5 mA DC maximum
The frequency at which the meter is operating can be detected using a timer counter connected
between the density output line and the negative power line.
The electrical connections to be made are shown in Figure 4-3.
46Micro Motion 7826/7828 Insertion Liquid Density Meter
Page 53
Electrical Connections (Frequency Output) – 7826 Only
Frequency Output
7826
1
+
Supply
2
-
3
+
Signal
4
-
5
6
7
8
RTD
Power +
Power -
Signal +
Signal -
6V pk to pk
RTD Supply +
RTD Supply -
RTD Signal
}
Figure 4-3Electrical connections for use with customer’s own equipment (non-hazardous area)
Electrical Connections (Frequency Output) – 7826 Only
The τB value can be easily monitored by a 795x computer with the “Health Check” facility.
Perform the following 795x front panel keyboard sequence if this facility is required:
a.Press the bottom-right grey MAIN MENU key.
b.Use the DOWN-ARROW key (at the left of the display) to page down through the menu
options until “Health Check” (or similar) appears.
c.Select the “Health check” option using the appropriate blue key at the right side of the
display.
d.Use the blue DOWN-ARROW key (at the left side) to page down through the menu
options until “Time period inputs” (or similar) appears.
e.Select the relevant “Time Period i/p 2”, “Time Period i/p 3” or “Time Period i/p 4” option
according to the physical connections made to the 795x.
f.Refer to the supplied 795x operating manual for information about front panel key
operations and navigating the menu structure.
48Micro Motion 7826/7828 Insertion Liquid Density Meter
Page 55
Electrical Connections (Advanced)
Chapter 5
Electrical Connections (Advanced)
For information on making the electrical connections for the 7826 liquid density meter with
Frequency Output electronics, see Electrical Connections (Frequency Output) chapter.
For installations in hazardous areas:
•For ATEX installations, the electrical installation must strictly adhere to the safety information
given in the ATEX safety instructions booklet shipped with this manual. See Safety Information in
Chapter 1 for important information.
•For installations in USA and Canada, the electrical installation must strictly adhere to the Electrical
Codes and a conduit seal is required within 2” (50 mm) of the enclosure.
5.1Introduction
The 7826/7828 liquid density meter with Advanced electronics has two types of output:
•Two off 4–20 mA analog outputs that give an output proportional to a user-specified range.
The parameters that can be output on each analog output are as follows:
Analog Output 1Analog Output 2
Line density
Base or referred density
Line temperatureLine temperature
Special function parameterSpecial function parameter
(1) Factory default selection for product option codes A and C.
(2) Factory default selection for product option code B.
(3) Factory default selection for all product options.
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
(1)
(2)
Line density
Base or referred density
(3)
•A Modbus (RS-485) interface, giving access to other measurement results, system information
and configuration parameters. The Modbus interface is also used to configure the 7826/7828
meter, using a PC running the Micro Motion ADView or ProLink II software (see the Using
ADView and ProLink II chapter).
It is recommended that both output types are installed, requiring a minimum of eight wires (two for
each output, and two for power). Although you may not immediately require the Modbus connection,
it may be required for in-situ calibration adjustment and future system enhancements, and the cost of
the additional wires is trivial compared to the expense of installing them retrospectively.
Installation and Configuration Manual49
Page 56
Electrical Connections (Advanced)
A number of factors must be taken into account when planning the electrical installation. These
include:
•Power supply
•EMC
•Ground connections
•Cables
•Surge protection
•Installation in explosive area
•Modbus connections
•Analog connections
5.2Installation considerations
5.2.1Power supply
The power supply to the 7826/7828 liquid density meter must have the following requirements:
•Voltage: Nominally 24 VDC, but in the range 20 to 28 VDC.
•Current: for transmitter – 50 mA; for mA outputs – 22 mA per output.
If several 7826/7828 meters are to be used within a local area, one power supply can be used to power
them all; where the meters are distributed over a wide area and cabling costs are high, it may be more
cost effective to use several smaller, local power supplies.
Upon leaving the factory, the two 4-20 mA analog outputs are non-isolated as they are powered
through internal links to the power supply input. However, if split-pads “LNK A” (Analog Output 1)
and “LNK B” (Analog Output 2) by the terminal block are ‘broken’, they become isolated and require
a separate 20-28 VDC power supply (see the 4–20 mA outputs section for details).
If an RS-232 to RS-485 converter is used (for example to connect to a serial port on a PC), this may
also require a power supply (see the Further information on RS-485 section for details).
Care should be taken where there is the possibility of significant common-mode voltages
between different parts of the system. For example, if the 7826/7828 meter is locally powered
from a power supply which is at a different potential to the RS-485 ground connection (if used).
5.2.2EMC
To meet the EC Directive for EMC (Electromagnetic Compatibility), it is recommended that the
7826/7828 meter be connected using a suitable instrumentation cable containing an overall screen.
This should be earthed at both ends of the cable. At the 7826/7828 meter, the screen can be earthed to
the meter body (and therefore to the pipework), using a conductive cable gland.
5.2.3Ground connections
It is not necessary to earth the meter through a separate connection; this is usually achieved directly
through the metalwork of the installation.
The electronics and communications connections (RS-485/Modbus and 4-20 mA analog output) of
the 7826/7828 meter are not connected to the body of the meter. This means that the negative
terminal of the power supply can be at a different potential to the earthed bodywork.
50Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 57
Electrical Connections (Advanced)
In the majority of applications, it is not necessary to connect the RS-485 ground connection. In areas
where there is a significant amount of electrical noise, higher communications integrity may be
obtained by connecting the negative power terminal (pin 2) of the 7826/7828 meter to the
communications ground. If this is done, it is important to ensure that the possibility of ground loops
(caused by differences in earth potential) is eliminated.
5.2.4Cabling requirements
Although it is possible to connect separate cables to the 7826/7828 meter for power, RS-485 and the
4-20 mA analog output, it is recommended that all connections are made through one
instrumentation-grade cable.
Connections for the Analog and Modbus signals should be individually screened twisted-pairs with an
overall screen, foil or braid for the cable. Where permissible, the screen should be connected to earth
at both ends. (At the 7826/7828 meter, this is best done using a conductive cable gland.)
Cables should conform to BS2538. In the USA, use Belden 9402 (two-pair) or Beldon 85220
(single-pair). Other cables that are suitable are those that meet BS5308 Multi-pair Instrumentation
Types 1 and 2, Belden Types 9500, 9873, 9874, 9773, 9774 etc.
The typical maximum recommended cable length for the above cable types is 1000 m (3200 ft), but
care must be taken to ensure that the power supply at the meter is at least 20 V. Thus, for 24 V power
supply, the overall resistance for the power supply connections (both wires in series) must be less than
100 ohms.
In order to complete the wiring, you will need the following parts:
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
•½” NPT to M20 gland adapter
•½” NPT blanking plug
•M20 x 1 cable gland (not supplied).
The gland adapter and blanking plug are supplied with the 7826/7828 meter – these two parts are Exd
rated. However, you will need to get a suitably rated cable gland:
•For non-hazardous area installations, use an IP68 or higher rated cable gland.
•For hazardous area installations use an Exd-rated cable gland.
In hazardous areas, all parts must be explosion-proof. Alternative parts may be required in order to
meet local electrical installation regulations.
5.2.5Surge protection
Careful consideration should be given to the likelihood of power supply surges or lightning strikes.
The power supply connections of the 7826/7828 meter have a surge arrestor fitted that gives
protection against power supply transients.
If there is a possibility of lightning strikes, external surge protection devices - one for each pair of
signals and the power supply - should be installed as close to the 7826/7828 meter as possible.
Another method of surge protection is to connect an MOV (Metal Oxide Varistor) (breakdown voltage
> 30 V) with an NE-2 neon bulb in parallel across each wire and ground. These can be mounted in a
junction box close to the 7826/7828 meter.
If the RS-485/Modbus output is permanently connected to a PC, an independently powered, fully
isolated RS-485 to RS-232 converter should be used. (See the Further information on RS-485 section
for details).
Installation and Configuration Manual51
Page 58
Electrical Connections (Advanced)
HAZARDOU S AREASAFE AREA
Meter
Power +
Power -
RS-485 A
RS-485 B
4-20 mA output 1 +
4-20 mA output 1 -
Power supply
(
20...28 Vdc at 50 mA)
+ 24V
0V
RS-485/232
converter
To RS-232 port on a PC running
ADView or ProL ink II (v2.9 or later)
software for monitoring,
maintenance and configuration.
Analog o/p +
An al og o/p -
1
2
4
3
5
6
4-20 mA output 2 +
4-20 mA output 2 -
Analog o/p -
7
8
Analog o/p +
Passive outputs
(see the 4-20 mA
outputs section for
more information)
5.2.6Installation in explosive areas
For installations in hazardous areas:
•For ATEX installations, the electrical installation must strictly adhere to the safety
information given in the ATEX safety instructions booklet shipped with this manual. See
Safety Information in Chapter 1 for important information.
•For installations in USA and Canada, the electrical installation must strictly adhere to the
Electrical Codes and a conduit seal is required within 2” (50 mm) of the enclosure.
The 7826/7828 meter is an explosion-proof and flameproof device. However, it is essential to observe
the rules of compliance with current standards concerning flameproof equipment:
•Electronics housing caps should be tightened securely and locked in position by their locking
screws.
•The electrical cable or conduit should have an appropriate explosion-proof cable gland fitted.
•If any electrical conduit entry port is not used, it should be blanked off using the appropriate
explosion-proof blanking plug, with the plug entered to a depth of at least five threads.
•The spigot must be locked in place.
Figure 5-1Wiring diagram
52Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 59
Electrical Connections (Advanced)
Notes
1. The main 24 VDC power supply must supply the following: 20 to 28 VDC at 50 mA for
transmitter; and, 22 mA per analog output used.
2. The RS-485/232 converter and PC are not normally installed permanently. However it is
strongly recommended that the wiring to the 7826/7828 meter is made at installation.
3. Upon leaving factory, the two analog outputs are non-isolated as they are powered through
internal links to Power Supply Input.
4. If split-pads “LNK A” (Analog Output 1) and “LNK B” (Analog Output 2) by the terminal
block are broken, the two 4-20 mA analog outputs become isolated; direct connections to an
external power supply is then required. A second or third external 20 to 28 VDC power supply
can be used. (See 4-20 mA outputs section for more details).
5. Typically, four pairs of shielded 19/0.30 mm
are used for wiring.
6. The naming conventions for RS-485 signals differ between manufacturers. If RS-485
communications do not function correctly, try swapping the ‘A’ and ‘B’ signals over at one end
of the link.
2
(#16 AWG) to 19/0.15 mm2 (#22 AWG) wires
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
5.3Wiring the meter
Figure 5-2 shows the terminal board of the 7826/7828 liquid density meter. To reveal the terminal
board, it is necessary to unscrew the housing cap; the procedure is described in the Wiring Procedure
section.
Note: If the 7826/7828 meter is to be used in hazardous areas, the electrical installation must strictly
adhere to the safety information given in the ATEX safety instructions booklet that shipped with this
manual. See Safety Information in Chapter 1 for more information.
The connections to the 7826/7828 meter are:
•Power
•Modbus (RS-485) communications
•Analog outputs (4-20 mA).
It is recommended that you install all connections (eight cores) at installation, to avoid the possibility
of expensive alterations to the cabling at a later date. Typically, four pairs of shielded 19/0.30 mm
(#16 AWG) to 19/0.15 mm
Figure 5-2View of the terminal board
2
(#22 AWG) wires are used.
2
Installation and Configuration Manual53
Page 60
Electrical Connections (Advanced)
5.4Power supply input
Terminals 1 and 2 are for connecting an external 24 VDC power supply, as guided in Figure 5-3.
Ensure that the loop resistance of the cable(s) is such that the voltage at the meter terminals is greater
than 20 volts. (The maximum voltage at the meter terminals is 28 VDC.)
Figure 5-3Power supply connections
5.54-20 mA outputs
Terminals 5, 6, 7 and 8 are for connecting the two 4-20 mA analog outputs to external devices, such
as a PLC or DCS. Upon leaving the factory, the two 4-20 mA analog outputs are non-isolated as they
are powered through internal links to the Power Supply Input.
Figure 5-44–20 mA output using a single power supply
54Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 61
Electrical Connections (Advanced)
However, if split-pads “LNK A” (Analog Output 1) and “LNK B” (Analog Output 2) by the terminal
block are ‘broken’, they become isolated and require direct connections to another external
20–28 VDC power supply (see Section 5.5.1 for more information on isolating the analog outputs). A
second or third external 20–28 VDC supply can be used.
Figure 5-54–20 mA output using up to three independent power supplies
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
Note: The external device must be located in a non-hazardous (safe) area unless it is explosion proof
and suitably certified.
Fault conditions within the 7826/7828 meter are indicated by a 2 mA output. If this is detected, the
Modbus link can be used to interrogate the meter to establish the likely cause of the problem.
5.5.1Isolating the analog outputs from internal power
To isolate the analog outputs from internal power, use a sharp knife to cut the fine metal strip (or
trace) for the appropriate split-pad (see Figure 5-6).
Installation and Configuration Manual55
Page 62
Electrical Connections (Advanced)
Example split-pads
Non-isolated analog output
(default)
Connected to internal power
(split-pad with trace)
Isolated output
Disconnected from internal power
for external power connection
(split-pad with broken, or cut, trace)
Location of LNK A and LNK B split-pads
1 243
56
5 6 7 8
Ex
AB
Ex
This figure shows a serial port connection. A USB port connection
is also available.
25-to-9 pin adapter, if necessary;
or RS-232 to USB adapter
RS-485/232 signal
converter
Figure 5-6Isolating an analog output from internal power (for external power connection)
5.6Modbus (RS-485)
Terminals 3 and 4 are for RS-485/Modbus connections to a PC, as shown in Figure 5-7. Connect the
RS-485/232 signal converter to your PC’s serial or USB port, using adapters as required. Figure 5-7
shows a serial port connection, but a USB port connection is also available.
Note: The PC and converter are always located in a non-hazardous (safe) area.
The RS-485/232 converter and PC are not normally installed permanently. However it is strongly
recommended that the wiring to the 7826/7828 meter is made at the time of installation.
For detailed information on RS-485, see the Further information on RS-485 section.
Note: If you encounter communication difficulties with RS-485, swap over the ‘A’ and ‘B’ signal
connections at one end of the network.
Figure 5-7Modbus connections
56Micro Motion 7826/7828 Insertion Liquid Density Meters
1. Open the Terminal Board side of the
meter’s electronics housing by
undoing the 2.5 mm AF grub screw
and unscrewing the lid anticlockwise.
2. Fit the M20 gland adaptor into the
most convenient ½” NPT hole.
3. Fit the M20 x 1 cable gland to the
adapter. Fit a ½” NPT blanking plug to
the unused hole.
UNDO THIS CAP
SCREW
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
4. Insert the cable through the cable
gland and adaptor so that the
multi-core cable is gripped leaving
200 mm of free, unscreened wire to
connect to the terminal blocks.
Installation and Configuration Manual57
Page 64
Electrical Connections (Advanced)
VIEW FROM UNDERNEATH THE ELECTRONICS
5. Wire up the cable cores as shown
6. When you have screwed the wires into
the correct terminals, carefully tuck
the wires around the electronics, and
tighten the cable gland.
7. Screw the housing cap on fully and
tighten the locking grub screw using
the 2.5 mm AF hex drive.
5.8Further information on RS-485
5.8.1RS-485
The 7826/7828 meter’s Modbus communications uses the RS-485 electrical standard. This uses the
difference between the two signal cores to transmit and detect logic levels, and is therefore able to
tolerate significantly higher levels of common mode noise than RS-232, which uses the voltage
between the signal core and a common earth. A brief summary of some typical characteristics of the
two standards is given below.
TIGHTEN
CAP
TIGHTEN
GRUB
:
Signal detectionDifferentialSingle-ended
Receiver threshold200 mV+1.5 V
Meter output swing0 to +5 V (no load)
A converter is required for communication between the two standards. Further details are given in
Section 5.8.2.
Only two signal connections are required for RS-485, usually called A and B, sometimes ‘+’ and ‘–‘.
Note: Unfortunately, different manufacturers have interpreted the standard in different ways. Some
have a ‘logic 1’ represented by signal A being more positive than signal B, others have made the
opposite interpretation. If you encounter communication difficulties with RS-485, the first remedy is
to swap over the ‘A’ and ‘B’ signal connections at one end of the network.
58Micro Motion 7826/7828 Insertion Liquid Density Meters
RS-485RS-232
± 8 V
+2 to +3 V (120 ohm load)
Page 65
Electrical Connections (Advanced)
For areas which may experience high common mode signals, a third conductor can be used as a
ground reference for the communications signals. If used, this should be connected to Terminal 2
(Power supply negative) on the 7826/7828 meter.
5.8.2RS-485 to RS-232
Converters are available from a number of sources, and can range from simple in-line devices that
simply plug into a PC’s RS-232 port, to programmable devices with full isolation between the two
networks.
Note: The 7826/7828 meter uses a half-duplex implementation of RS-485, such that the A and B
signals are used for data transmission in both directions. This requires that the RTS line is toggled to
indicate the transmission direction. This can be done by the host computer, or automatically by an
RS-485/232 converter which has the facility to do so. If you are using Windows 2000, XP or Vista on
your PC, you should use a converter which automatically changes RTS (as detailed below) otherwise
the link may not work correctly.
For simple installations, where the following conditions are valid, a simple in-line converter will be
satisfactory:
•The Modbus network is less than about 150 ft (50 m).
•The number of devices on the bus is low.
•No common mode problems.
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
The converter derives its power from the PC’s RS-232 port RTS or DTR line, which must be held
permanently in the high state. This is normally adequate for short distances where there are only a
few devices on the network. However, the ability of the port to supply sufficient power is not
guaranteed, especially for laptop PCs, and it may be necessary to connect an external power supply.
This may also be necessary if using Windows 2000, XP, or Vista.
To check the voltage levels, measure the voltages on the RTS input and the DTR input while the
converter is connected to the PC (or other RS-232 device). This procedure needs a break-out box (not
supplied). Whichever input is powering the converter must have at least +6 V during
communications. Where the power is found to be insufficient, a 9 VDC supply can be connected
between (+) and GND of the RS-232 connector.
Installation and Configuration Manual59
Page 66
Electrical Connections (Advanced)
Tx
Rx
RTS In
Port 1 GND
Power Input
1
2
3
4
5
6
7
8
-
+
6
5
4
3
2
1
Port 2
RS485
RxB
Port 2 GND
RxA
TxA
TxB
A
B
A
B
GND
GND
3
4
2
A
B
GND
3
4
2
5.8.3RS-485 multi-drop
When several devices are connected in parallel on an RS-485 network, this is known as a multi-drop
network. Although it is theoretically possible to have up to 256 devices, in practice this is limited to
around 32 or less, depending largely on the driving power of the Master. Each device has a unique
slave address. For the 7826/7828 meter, this address must be individually programmed using the
ADView or ProLink II (v2.9 or later) software, before being connected to the multi-drop network (see
section 4.4.3 for details).
Wiring is quite straightforward: simply connect ‘B’ terminal to ‘A’ terminal, A to B. On some
devices, the RS-485 signals may be marked + and –. The + signal generally corresponds to the A
signal, and the – signal to B. If you encounter communication difficulties with RS-485, the first
remedy is to swap over the ‘A’ and ‘B’ connections at one end of the network.
5.8.4Transmission mode
The 7826/7828 meter’s RS-485 interface uses the following parameter settings, which are not
selectable:
•Baud rate: 9600
•Bits:8
•Parity:None
•Stop bits:2
60Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 67
Chapter 6
Using ADView and ProLink II (Advanced version)
6.1Using ADView software
6.1.1What is ADView?
ADView is a software package provided by Micro Motion to enable you to:
•Configure our density and viscosity meters.
•View and save data from them.
•Check that they are functioning correctly.
ADView is installed on a PC and interacts with the density/viscosity meter through one of the PC’s
standard serial (RS-232) ports.
ADView requires Microsoft’s Windows operating system: Windows 95, 98, 2000, XP or Vista.
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
Note: To connect to an RS-485/Modbus device, such as the 7826/7828 meter, you will need an adapter
between the PC and the meter (see Electrical Connections chapter).
ADView provides many useful facilities, such as:
•Setting up serial link to communicate with the meter
•Configuring the meter
•Displaying data in real time, or as a graph
•Logging data to a file
•Verifying correct operation of the system, and diagnosing faults
•Loading or storing Modbus register values
•Read/write to individual Modbus registers.
6.1.2Installing ADView
ADView software is available for the PC on a variety of media (for example, CD-ROM) and is freely
available to download from the Micro Motion web site (at www.micromotion.com).
1. Identify the media containing the installation files for ADView.
2. Insert the media into an appropriate drive on your PC.
3. If the installation program does not begin automatically, run the set-up ‘.exe’ file that is on the
media. This does vary between different PC operating systems. In general, open the File
Manager or Windows Explorer, browse the drive containing the media and double-click on the
set-up ‘.exe’.)
Installation and Configuration Manual61
Page 68
Using ADView and ProLink II (Advanced version)
4. When the installation program starts, you will be asked to supply your name and company
name for registration purposes, and supply a directory path into which ADView’s files can be
loaded (a default directory path will be suggested).
5. Follow the installation instructions until installation is complete. It will normally only take a
few minutes. You can abandon the installation if you need to do so.
6.1.3Starting ADView
Start the ADView software by navigating through the Start Menu to the program entry of ADView 6.
Left-click on it once and the window shown below will then appear.
Note: Developments in ADView may mean that the screen shots differ slightly from the ones you will see on
your PC screen.
Each of the six icons gives you access to the various facilities of ADView. You can choose to connect
a Modbus device to one of the PC’s serial ports, or you can use ADView’s built-in simulation of the
meter.
62Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 69
Using ADView and ProLink II (Advanced version)
To run the simulation, choose Options > Simulate board response from the menu bar and choose
the appropriate densitometer option. Then, click on the
ADView screen. When simulation is chosen, ADView ignores the serial port and supplies simulated
data. However, you do still need to click on the
Connect button. Then, click on the OK buttons, as necessary, to return to the main ADView screen.
Setting up serial communications
To operate with a real Modbus device, you will need to connect it to a suitable power supply (see the
technical manual for the device) and need a connection to a serial port on the PC. Full details for
connecting to the Modbus (RS-485) link on the meter are in Chapter 5.
ADView automatically configures the selected port with the correct settings for the device. For the
meter, this is 9600 baud rate, 8 data bits, no parity, 1 stop bit, and Xon/Xoff (software) flow control.
6.1.4Understanding ADView features
ADView facilities
The main ADView window gives access to the various facilities available. A brief description of each
is listed below. Using the facilities is largely intuitive so that you can quickly learn the system.
OK buttons, as necessary, to return to the main
Communications Setup button followed by the
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
Communications Setup
Sets up and checks RS-232/RS-485 communications.
Board Configuration
• Enables you to select the measured parameter and range for the analog output,
and to configure density referral by entering matrix values or K factors, as well
as special calculations, line pressure and averaging time.
• Displays instantaneous values of a selectable output parameter and the analog
output.
Data logging
• Provides tabular data from meters of line and base density, temperature and
special function. One parameter can be displayed as a graph.
• Data can also be logged to a file in either Excel (tab delimited) or Notepad
(space delimited) formats.
• The frequency at which results are logged can be set, and logging can be
started and stopped.
Register dump/load
With this facility you can dump the contents of all (or selected) Modbus registers
from the device, or alternatively transmit values to them. File format is selectable
(Excel/tab delimited, or Notepad/Space delimited).
Meter details
Shows a list of meter details such as type, serial number, calibration dates,
software version, etc.
Installation and Configuration Manual63
Page 70
Using ADView and ProLink II (Advanced version)
Diagnostics
Enables you to view:
- live sensor readings
- the status of the meter
- values of working coefficients
You can also verify calculations.
Menu bar
File
Tools
Options
Window
Help
ExitExit ADView program.
Health CheckDetermines whether the system is functioning correctly.
Register Read/WriteA facility for reading or writing to any of the Modbus
Direct Comms.Enables you to specify exactly what will be transmitted on
Engineer StatusOnly used by Micro Motion service engineers.
Simulate board response/
Actual Board
Enable / disable screensaverAllows you to select between these two options. When
About ADViewDisplays software version number.
registers (see Appendix D).
the Serial link (see Appendix D).
Allows you to select between these two options
enabled, the screensaver operates as configured by the
Windows system settings.
Provides a means of opening or selecting ADView’s
facilities.
Configuring a slave address
The factory configuration sets the slave address to 1. However, in many applications it will be
necessary to allocate another address. In a multi-drop application, where several Modbus devices are
connected on the same network, it is essential to configure unique slave addresses for each device.
To do this, you will need to run ADView and use the Register Read/Write facility, detailed in
“Register Read / Write” on page 67. Check the value in Register 30 (Modbus Slave Address). If it is
not the required value, enter the desired value and click on the write button. The meter will now be
configured with the new slave address.
Board configuration
The board configuration controls the way in which the meter will process and present data, user
settings, calibration constants and other factors. This data is stored in non-volatile memory known as
registers; a full list of the registers used in the meter is given in Appendix D.
To configure the meter, it is necessary to write data into the configuration registers using the
RS-485/Modbus link. ADView provides a convenient and graphical way of doing this without you
needing to know about register addresses and data formats.
Certain parameters are not available for configuration by ADView, including the Density Offset value
which may be required to fine tune the calibration of the meter. However, ADView does have tools for
reading and writing to individual Modbus registers (using the
and for direct communication on the Modbus (using
Tools > Direct Comms). More details and
Tools > Register Read/Write facility),
examples are given in Appendix D, but for the significant majority of applications these tools will not
be required.
64Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 71
Using ADView and ProLink II (Advanced version)
There is no facility within ADView or the meter to ‘reset’ to a default configuration. Therefore,
before attempting any alterations to the configuration, you are strongly advised to use the
Register Dump/Load facility in ADView to store the existing configuration (see “Register Dump /
Load” on page 67). Then, if any mishap occurs, you will be able to restore the configuration from
the saved file.
ADView’s Board Configuration window is shown below:
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
To exit from any of the configuration windows without making any changes, press the
Esc key on
your computer keyboard.
Density referral (Configure… button)
To configure the density referral calculation, you will need to enter the relevant information.
•For matrix referral, this is a set of four values of density for each of up to five different
temperatures; Appendix B gives more details on this.
•For API referral, you can select the product type, which automatically adjusts the coefficients
of the General Density Equation, or enter your own values.
Special function (Configure… button)
The range of special functions (calculated parameters) that are available depends on the referral type
selected.
Installation and Configuration Manual65
Page 72
Using ADView and ProLink II (Advanced version)
The Log Setup button – which is
activated when logging has been
stopped – enables you to configure
the frequency of logging, where the
logged data will be filed, and the
format of the data.
Display Selection dropdown
list to select the transmitter
and parameter to be displayed
on the graph
For selecting the
parameter to be
Click Show Graph
to configure and
display graph
For multi-drop
configurations, the
output of up to three
transmitters can be
displayed
simultaneously.
Tabular display of
instantaneous
output of
transmitter.
Select analog
output of another
transmitter.
Click OK to close
Data Logging window
Graphical
representation of
analog output.
Click Start to
start logging.
Click Stop to stop
logging
Special FunctionAPI referralMatrix referral
Specific Gravity✓✓
API°✓
% mass✓
% volume✓
° Baumé✓
° Brix✓
User defined quartic✓
None✓✓
When you select the Special Function you require, the configuration window will alter to allow you to
input the relevant parameters, if applicable. Note that you can only select one Special Function to be
available at any one time.
When you are satisfied with the configuration, you should save it to a file, using the
Dump/Load
facility, as a safeguard against subsequent loss or alteration.
Register
Data logging
ADView’s Data Logging function is a useful tool for checking setups and performing experimental
data capture. The diagram below explains some of the features.
66Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 73
Using ADView and ProLink II (Advanced version)
Address of unit
being accessed
Enter desired filename
for Dump, or required
filename for Load.
Choose which sets of
registers to save to file,
or simply save all of
them.
You can also specify
individual registers.
Choose data delimiter
(Dump only)
Restore a previously
saved set of register
data from file.
Store the selected
register data to a file.
Register Dump / Load
This facility is essential for saving the configuration of your meter. You should use it to save the
current configuration before you start to alter it, in order to restore it if things go wrong for any
reason. Also, if you send the meter away for servicing or re-calibration, you should save the current
configuration. Details are given below.
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
Register Read / Write
In a few cases, it may be useful to write directly to a single Modbus register. Two likely occasions for
using this feature are to set the Slave Address of the unit and to configure a density offset. The
Modbus Communications appendix has a complete list of the registers.
Before making any changes to individual registers, you should save the current configuration to
a file to safeguard your configuration if anything goes wrong. See “Data Logging” for more
information.
From ADView’s menu bar, select
Tools > Register Read/Write.
Installation and Configuration Manual67
Page 74
Using ADView and ProLink II (Advanced version)
To see a complete list of
Modbus register numbers
and descriptors, click
here.
Choose the one you want
to access.
For non-numerical
values, click here to see
complete list of possible
entries and select one to
write into the register.
Enter numerical values
directly.
The Write button
causes the current
value to be written to
the selected register.
You can read and write to any
number of registers. When you
have done all you want to, click
OK.
The Read button
causes the current
value of the chosen
register to be
displayed.
The current
register number
appears here.
6.2Using ProLink II software
Note: For more detailed information on installing and using the ProLink II software application, see
the user manual available at www.micromotion.com or on the Micro Motion product documentation
CD.
6.2.1Overview
ProLink II is a Windows-based configuration and management tool for Micro Motion meters. It
provides complete access to meter functions and data.
This chapter provides basic information for connecting ProLink II to your meter. The following topics
and procedures are discussed:
•Requirements (see Section 6.2.2)
•Configuration upload/download (see Section 6.2.4)
The instructions in this manual assume that users are already familiar with ProLink II software. For
more information on using ProLink II, see the ProLink II manual.
6.2.2Requirements
To use ProLink II with a 7826/7828 liquid density meter, the following are required:
•ProLink II v2.9 or later
•Signal converter(s), to convert the PC port’s signal to the signal used by the meter
-For RS-485 connections, an RS-485 to RS-232 signal converter.
6.2.3Connecting from a PC to a meter
The following table describes the options for connecting ProLink II to your meter.
68Micro Motion 7826/7828 Insertion Liquid Density Meters
-25-pin to 9-pin adapter (if required by your PC)
Page 75
Using ADView and ProLink II (Advanced version)
ConnectionPhysical layerProtocol
RS-485 terminals or RS-485 networkRS-485Modbus
6.2.4ProLink II configuration upload/download
ProLink II provides a configuration upload/download function which allows you to save configuration
sets to your PC. This allows:
•Easy backup and restore of meter configuration
•Easy replication of configuration sets
Micro Motion recommends that all meter configurations be downloaded to a PC as soon as the
configuration is complete.
To access the configuration upload/download function:
1. Connect ProLink II to your meter.
2. In the ProLink II software application, open the
•To save a configuration file to a PC, use the
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
File menu.
Load from Xmtr to File option.
•To restore or load a configuration file to a meter, use the
6.2.5ProLink II language
ProLink II can be configured for the following languages:
•English
•French
•German
To configure the ProLink II language, choose
Tools > Options.
In this manual, English is used as the ProLink II language.
Send to Xmtr from File option.
Installation and Configuration Manual69
Page 76
Using ADView and ProLink II (Advanced version)
70Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 77
Chapter 7
Calibration Check
7.1Calibration
7.1.1Factory calibration
Prior to leaving the factory, the 7826/7828 liquid density meter is calibrated within a standard
physical boundary (typically 52.5 mm diameter) against Transfer Standard instruments traceable to
National Standards.
Three fluids ranging in density from 1 to 1000 kg/m
constants K0, K
derived from the air-point and material properties.
The calibration procedure relies on units being immersed in fluids whose density is defined by
Transfer Standards. Great attention is paid to producing temperature equilibrium between the fluid,
the unit under test and the Transfer Standard (see Section 7.1.2). In this way, accurate calibration
coefficients covering the required density range can be produced.
1, and K2 (see Section 7.1.4). The temperature coefficients (K18 and K19) are
3
are used to establish the general density equation
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
All instruments are over-checked on water to verify the density calibration, and with two different
fluids to check the viscosity calibration. This check is monitored by the Micro Motion Quality
Assurance Department.
7.1.2Calibration of Transfer Standards
For density calibration, Transfer Standard instruments used in the calibration are selected instruments
which are calibrated by the British Calibration Service Calibration Laboratory and are certified.
Transfer Standard calibration uses a number of density-certified liquids, one of which is water. The
densities of these reference liquids are obtained using the Primary Measurement System whereby
glass sinkers of defined volume are weighed in samples of the liquids.
Calibration of the Transfer Standard instruments is performed under closely controlled laboratory
conditions and a calibration certificate is issued. Calibrations are repeated, typically every six
months, producing a well-documented density standard.
7.1.3Instrument calibration
Each meter is issued with its own calibration which is programmed into the instrument electronics
before it leaves the factory. Under normal circumstances it should not be necessary to re-calibrate the
7826/7828 meter provided it is used in the environment for which it was calibrated originally.
Installation and Configuration Manual71
Page 78
Calibration Check
The calibration data is shown on a calibration certificate supplied with the instrument. The calibration
contains the following:
•The instrument serial number
•Several sample points from the output signal/density relationship. These have been calculated
•Temperature coefficient data, K18 and K19; this defines the correction which should be
•One instrument air (density) data point for check calibration purposes.
7.1.4General density equation
The General Density Equation, used to calibrate the 7826/7828 meter and shown in the Calibration
certificate is:
where ρ is the calculated density, τ is the time period (in μs) of the tuning fork, and K0, K1 and K2
are density coefficients, derived from the factory calibration data and selected to optimize the
accuracy of the density measurement across the calibrated density range.
Temperature effects are also compensated for using a second equation:
using the general density equation with the calibrated coefficients listed.
applied to achieve the best density accuracy if the instrument is operating at product
temperatures other than 20 °C.
ρ = K0 + K1τ + K2τ
2
ρ’ = ρ( 1 + K18(t - 20)) + K19(t - 20)
where ρ’ is the new (temperature compensated) density value, t is the measurement temperature, and
K18 and K19 are temperature correction coefficients.
Note: For the 7826/7828 meter with the Advanced electronics, values for the K coefficients, shown on
the calibration certificate, are programmed into the meter registers and should not be altered. If the
meter is used in an application dissimilar to the one for which it was originally calibrated, it may be
necessary to recalculate the K coefficients. Contact the factory for further details.
7.2Calibration certificate examples
Note: These certificates are examples only - they are NOT the calibration certificate for your
7826/7828 meter.
72Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 79
Calibration Check
CALIBRATION CERTIFICATE
7826F LIQUID DENSITY METER Serial No : XXXXXX
Cal. Date : 09MAY06
Pressure Test : 230 BARS
------------- | FINAL TEST & |
| INSPECTION |
| |
| |
| |
| |
--------------
Ref No:- XX7826/Vx.x/XX/X DATE : 10MAY06
Figure 7-2Example calibration certificate (in imperial/US units)
74Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 81
Calibration Check
7.3User calibration checks
7.3.1Ambient air calibration check
An air check is a simple and convenient method to see if any long term drift or corrosion and
deposition on the tines has occurred.
Ambient air check procedure:
1. Isolate and, if necessary, disconnect the meter from the pipeline.
2. Clean and dry the wetted parts of the meter and leave them open to the ambient air.
3. Apply power to the instrument and check that the time period of the instrument agrees with the
figure shown on the calibration certificate to within ±100 ns. If the 7826/7828 meter is not at
20°C, compensate for this by adding an offset of +110 ns for every °C above 20°C, or by
subtracting an offset of +110 ns/°C below 20°C.
4. Re-fit the meter to the pipeline if serviceable or remove for further servicing.
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
7.3.2On-line calibration adjustment
An on-line calibration adjustment may be required if:
•The physical boundary surrounding the tines is different from the physical boundary used for
the factory calibration.
•The unit has suffered long term drift or corrosion of the tines.
The 7826/7828 meter is a very accurate and stable instrument, and will normally provide good
measurements. If it is suspected of giving incorrect results, you should confirm this by carefully
checking the integrity of the fluid temperature measurement, and compare this with the temperature
measurement given by 7826/7828 meter. You should also verify the integrity of the density check
measurement. It is only after you have eliminated all other possible causes of error that you should
attempt to make adjustments to the calibration of 7826/7828 meter.
Normally the density calibration adjustment is made by configuring a simple density offset into the
instrument. If a more detailed calibration adjustment is required, such as a two- or three-fluid
calibration adjustment for offset and scale, then refer to Micro Motion.
Calibration adjustment - stable liquids (with Frequency Output electronics) – 7826 meter only:
1. On the signal processing equipment, set the line density offset to 0, and the line density scaling
factor to 1.
2. Ensure that the system has reached its stable operating temperature.
3. With the meter operating at typical process conditions, draw off a sample of the liquid into a
suitable container, and note the meter density reading and the operating temperature.
4. Measure the density of the sample under defined laboratory conditions using a hydrometer or
other suitable equipment. Refer this to the operating conditions at the meter.
5. Calculate the density offset required to make the meter measurement the same as the measured
density of the sample.
6. On the signal processing equipment, enter the calculated line density offset.
1. Using ADView (see Using ADView and ProLink II chapter), reset the line density offset
2. Ensure that the system has reached its stable operating temperature.
3. With the meter operating at typical process conditions, draw off a sample of the liquid into a
4. Measure the density of the sample under defined laboratory conditions using a hydrometer or
5. Calculate the density offset required to make the meter measurement the same as the measured
6. Using ADView’s Register Read/Write tool, configure the meter with the calculated line
Calibration adjustment - unstable or high vapor pressure liquids (with Frequency Output electronics)
– 7826 meter only:
A pressure pyknometer and its associated pipework can be coupled to the pipeline so that a sample of
the product flows through it.
1. On the signal processing equipment, set the line density offset to 0, and the line density scaling
2. Ensure that the system has reached its stable operating temperature.
3. When equilibrium conditions of product flow are reached, note the meter density reading and
4. Remove the pyknometer for weighing to establish the product density.
(register 173) to 0, and the line density scaling factor (register 174) to 1.
suitable container, and note the meter density reading and the operating temperature.
other suitable equipment. Refer this to the operating conditions at the meter.
density of the sample.
density offset (Register 173).
factor to 1.
temperature and simultaneously isolate the pyknometer from the sample flow.
5. Compare the pyknometer reading with the meter reading and compute the density offset
required.
6. On the signal processing equipment, enter the calculated line density offset.
Calibration adjustment - unstable or high vapor pressure liquids (with Advanced electronics):
A pressure pyknometer and its associated pipework can be coupled to the pipeline so that a sample of
the product flows through it.
1. Using ADView (see Using ADView and ProLink II chapter), reset the line density offset
(register 173) to 0, and the line density scaling factor (register 174) to 1.
2. Ensure that the system has reached its stable operating temperature.
3. When equilibrium conditions of product flow are reached, note the 7826/7828 meter density
reading and temperature and simultaneously isolate the pyknometer from the sample flow.
4. Remove the pyknometer for weighing to establish the product density.
5. Compare the pyknometer reading with the 7826/7828 meter reading and compute the density
offset required.
6. Using ADView’s Register Read/Write tool, configure the 7826/7828 meter with the calculated
line density offset (Register 173).
For further details on these procedures, reference should be made to:
Energy Institute:HM7. Density, sediment and water. Section 1: General
guidance on test methods (formerly PMM Part VII, S1)
1st ed 1996 ISBN 978-0-85293-154-7
76Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 83
Calibration Check
Energy Institute:HM8. Density, sediment and water. Section 2: Continuous
density measurement (formerly PMM Part VII, S2)
2nd ed Sept 1997 ISBN 978-0-85293-175-2
American Petroleum Institute: Manual of Petroleum Measurement Standards
Chapter 14 - Natural Gas Fluids - Section 6: Installing and
proving density meters used to measure hydrocarbon liquid
with densities between 0.3 and 0.7 g/cc at 15.56°C (60°F)
and saturation vapour pressure, April 1991.
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
Installation and Configuration Manual77
Page 84
Calibration Check
78Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 85
Chapter 8
General Maintenance
8.1Overview
Care is essential in handling of the meter during its removal from and fitment to the pipeline/tank and
during transportation. Wherever possible, retain and use the original packaging.
The 7826/7828 liquid density meter is rugged and robust, and has no moving parts. When correctly
installed and operated, servicing is not normally required, even with poor quality fluid, and no
periodic maintenance procedure is specified. It is recommended that a visual inspection is carried out
at intervals to check for leaks and physical damage, and corrective maintenance carried out when
required.
ADView’s Data Logging facility can be used whenever necessary to verify that the meter is
functioning correctly.
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
Check calibrations should be carried out at specified intervals in order to identify a malfunction or
deterioration in meter performance. If a fault or a drop in performance is detected, further tests are
required to identify the cause of the fault. Remedial action is limited to cleaning the meter tines,
making good any poor connections, and replacing the internal electronics. In the extreme cases the
complete meter may need to be replaced.
Note: The electronics within the 7826/7828 meter contain calibration information relevant to that
particular meter only. The circuit boards operate as a pair, and therefore both boards must be
changed together. Contact Micro Motion for more details if you need to change the boards.
8.2General maintenance
No periodic maintenance procedure is specified, but the following procedure is recommended for
periodic inspection. It can also be used when fault finding.
8.2.1Physical checks
1. Examine the meter, its electronics housing and cables for any signs of damage and corrosion.
2. Make sure that the spigot connection is tight.
3. Check the meter for sign of leakage.
4. Check that there is no ingress of water/fluid into the electronics housing.
5. Ensure that the threads on the covers are well greased (graphite grease) and that the O-rings
are in good condition.
Note: The covers MUST be completely screwed down and, in the case of an explosion-proof enclosure
application, DO NOT FAIL to tighten the locking screws.
Installation and Configuration Manual79
Page 86
General Maintenance
8.2.2Electrical check (for meters with Frequency Output electronics)
1. Carry out power supply and current consumption test at the meter terminals T1 and T2. These
should give:
If the current consumption is too high, replace the meter amplifier module.
2. For a 7826 meter with a frequency output, and with the power supply still connected, ensure
that the periodic time signal is present at terminals T3 and T4 (or T12 and T4 as on older
models). This should give a signal amplitude of:
3. For a 7826 meter with a frequency output: check the 100 Ω RTD (Platinum Resistor
Thermometer) element by disconnecting the wiring to terminals T5 to T8 (T7 to T10)
inclusive and measuring the resistance between terminals T6 and T7 (T8 and T9 for older
versions). The value of resistance is temperature dependent and can be found in the Appendix
E of this manual.
4. Carry out an insulation test on the meter electrics as follows:
a.Disconnect all external leads from the terminal board.
b.Now short-circuit all the terminals together. Carry out an insulation test between the
•25 mA to 42 mA at 22.8 VDC to 25.2 VDC
•Approximately 12V peak-to-peak (in air)
terminals and the meter body, using the 500 VDC insulation tester. The resistance must be
greater than 2 M
Ω (current limited to 5 mA).
c.Remove all short-circuits and reconnect the leads if required.
8.2.3Electrical check (for meters with Advanced electronics)
Check the power supply and current consumption at the meter terminals, pins 1 and 2, having
disconnected all analog outputs. These should give 35 mA to 42 mA at 22.8 V to 25.2 V.
If the current consumption is outside this range, contact Micro Motion.
8.2.4Performance check
When several systems are run in parallel and use the same fluid source, comparison of the line
viscosity, base density and temperature readings between installations can be a useful indicator of
possible system faults. Differences between readings, or changes from the normally observed
conditions should always be investigated to confirm that instrumentation is functioning correctly.
8.2.5Calibration check
1. Carry out a check calibration as detailed in the Calibration Check chapter.
2. Compare the results obtained with the previous calibration figures to identify any substantial
deterioration in meter performance or any malfunction.
Note: A drop in meter performance is likely due to a build up of deposition on the tines which can be
removed by the application of a suitable solvent. See Mechanical Servicing below.
Note: Malfunctions generally could be the result of electrical/electronic faults in either the meter or
the readout equipment. Always check the readout equipment first before attention is directed to the
meter.
80Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 87
General Maintenance
8.3Fault analysis and remedial action
A fault may be categorized as either an erratic reading or a reading which is outside limits.
Electrical faults can also cause symptoms which appear to affect the readings and it is recommended
that the electrical system is checked first, before removing the meter for servicing.
8.3.1Troubleshooting faults
Table 8-1Faults and possible causes
FaultPossible causesRemedy
Readings fluctuate slightly,
i.e., are noisy
Erratic readingsOne or more of:
Readings outside limitsDeposition and/or corrosion on
Analog output = 0 mANo power to analog outputIf voltage across pins 5 and 6 is not 15 to
Analog output is 2 mAAlarm condition caused by
Analog output averaging time
not long enough
Gas bubbles around tines;
cavitations; severe vibration or
electrical interference; large
amount of contaminants
the tines.
Analog output circuit failureUse ADView’s facility to set the analog output
lack of power to 7826/7828
meter
Alarm condition caused by
other internal failure
Increase the averaging time using ADView’s
Board Configuration facility (see the Using
ADView and ProLink II chapter).
Remove primary cause; e.g.:
-install air release units to release gas;
-apply back pressure to discourage formation
of bubbles;
-remove cause of vibration
Alternatively, it may be necessary to adjust
the Time Period Trap.
Clean tines.
28 V, replace power supply.
to 4, 12 or 20 mA (in Board Configuration) to
check whether the output is functioning. If not,
replace circuit boards.
If voltage across pins 1 and 2 is not 20 to
28 V, check and replace main power supply.
Use ADView Diagnostics to check that phase
locked loop is in lock.
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
Temperature readings
incorrect
Installation and Configuration Manual81
If analog output and Modbus
appear to be functioning
correctly, the temperature
sensor has probably failed.
Return the meter to Micro Motion for
servicing.
Page 88
General Maintenance
Table 8-1Faults and possible causes continued
FaultPossible causesRemedy
7826/7828 meter does not
communicate with ADView
Power failure to 7826/7828
meter
Check power supply to 7826/7828 meter and
converter; replace if necessary
Power supply to RS-485/232
converter failed.
A and B Modbus connections
reversed
RS-485/232 converter failed,
wired incorrectly, or connected
the wrong way round
ADView incorrectly installed
on PC
Incorrect Slave address
chosen for 7826/7828 meter
RS-232 port on PC failed.Connect to another free RS-232 port on the
Check wiring
Check wiring
Try another converter
Re-install ADView
Check slave address
PC, if available.
Alternatively connect a known working
RS-232 device to the PC to check that the
port is working.
8.3.2Mechanical servicing
This mainly comprises the cleaning of any deposition or corrosion from the tines. Deposition is
removed by the use of a suitable solvent. For corrosion, solvent and the careful use of a fine abrasive
will usually be sufficient. Take care not to damage the PFA lamination if installed. However where
extensive corrosion has been treated, it is highly recommended that a full calibration is carried out to
check the meter characteristics.
Care is essential in handling the meter during transit, installation, and removal from the pipeline/tank.
8.3.3Time period trap
Disturbances in the fluid caused by bubbles, cavitations or contaminants can cause sudden changes in
the measured output, which may, under some circumstances, give rise to instability (i.e. hunting) in a
control system relying on the measurement. The 7826/7828 meter can maintain the analog output
during such perturbations by ignoring the aberrant measurement, and maintaining the output at the
last good measured value. This facility is known as the Time Period Trap (TPT).
Under all normal circumstances, the factory settings for the TPT should be used. However, in extreme
cases it may be necessary to alter the settings to meet the demands of a particular system. This should
only be done after monitoring the behavior of the system for some time, to establish the normal
running conditions.
Great care must be taken not to reduce the sensitivity of the meter so that normal response to
fluctuations in the fluid is impaired.
The time period trap facility works as follows:
82Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 89
General Maintenance
After each measurement of the time period (of the 7826/7828 meter’s vibrating tines) the new
value is compared with the previous value. If the difference between them is smaller than the
allowable tolerance, the output is updated to correspond to the new measured value, and the TPT
remains inoperative; i.e., operation is normal. If the difference exceeds the allowable tolerance,
the output remains at the its previous level, and does not follow the apparent sudden change in
value.
This process is repeated until either of the following:
•The latest measured value falls back to the level of the original value, indicating that the
transient has passed; or
•The TPT count is reached. At this point it is assumed that the change in value is not due to a
random disturbance, and the output adopts the value of the latest reading.
Two Modbus Registers control the operation of the Time Period Trap facility. These can be changed,
if necessary, using ADView’s Register Read/Write facility.
•Modbus Register 138: contains the maximum allowable change in the time period between
readings, specified in μs. The preset value is 10.
•Modbus Register 137: contains the Time period count, which is the maximum number of
measurements to be rejected before resuming normal operation; the preset value is 2. If the
value is set to 0, TPT is disabled, and the output will always follow the time period
measurement. If you want to program another value, it should be determined experimentally,
and be equal to the length of the longest undesirable transients which are likely to arise. If the
value is set too high, the meter will be slow to respond to genuine changes in the fluid
properties.
Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)Using ADView and ProLink IIGeneral MaintenanceCalibration CheckElectrical Connections (Advanced)
Installation and Configuration Manual83
Page 90
General Maintenance
84Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 91
Appendix A
7826/7828 Specifications
A.1Density performance
7826/7828 Specifications
Accuracy
Operating Range
Repeatability±0.0001 g/cc ±0.1 kg/m3 ±0.006 lb/ft
Process Temperature Effect
(Corrected)
Process Pressure Effect
(Corrected)
(1) Stated accuracy is for calibrated range 0.6–1.25 g/cc (600–1250 kg/m3).
(2) With the 7826, the viscosity of the liquid can be up to a maximum of 500 cP. However, with the 7828, the viscosity of the liquid
(3) Temperature effect is the maximum measurement offset due to process fluid temperature changing away from the factory
(4) Pressure effect is defined as the change in sensor flow and density sensitivity due to process pressure changing away from
(1)
(2)
(3)
(4)
can be up to a maximum of 20,000 cP.
calibration temperature.
the calibration pressure. To determine factory calibration pressure, refer to calibration document shipped with the 7826/7828.
If data is unavailable, contact the factory.
±0.001 g/cc±1.0 kg/m3
0 to 3 g/cc 0 to 3000 kg/m3 0 to 187.4 lb/ft
3
±0.0001 g/cc ±0.1 kg/m3 (Per °C)
Negligible
3
A.2Temperature specification
Calculated ParametersModbus Communications
Safety Certification
Process
Ambient
7826/7828 short-stem version
7826/7828 long-stem version
–40 °F to +185 °F (–40 °C to +85 °C)
–58 °F to +392 °F (–50 °C to +200
°C)
–40 °F to +302 °F (–40 °C to +150
°C)
A.2.1Integral temperature sensor
Technolo gy100-Ω RTD (4 wire)
AccuracyRTD BS1904 Class B, DIN 43760 Class B.
Installation and Configuration Manual85
Page 92
7826/7828 Specifications
A.3Pressure ratings
Maximum operating
pressure
Test pressureTested to 1.5 x the maximum operating pressure
PED complianceOutside the scope of European directive 97/23/EC on Pressure Equipment.
(1) Actual maximum operating pressures are limited by the process connection rating.
(2) For Zirconium flanges, the maximum operating pressure is dependent on the working temperature. See “Zirconium 702
(1) (2)
pressure and temperature flange ratings” for more information.
7826/7828 short-stem version
7826/7828 long-stem version
3000 psi (207 bar)
1450 psi (100 bar)
A.3.1Zirconium 702 pressure and temperature flange ratings
The 7826/7828 liquid density meter can be supplied in the following configurations. The default
values for these configurations are shown in Table A-1.
23 to 27 VDC, 50 mA
20 to 28 VDC, 50 mA
22 mA per output
Current modulation on power supply line
2 wires (6V peak nominal)
100-Ω RTD (4 wire)
Two passive 4–20 mA
±0.1% of reading, ±0.05% of full scale at 20 °C
±0.05% of full scale, over range –40 °C to +85 °C
3.9 or 20.8 mA on 4–20 mA
2 or 22 mA on 4–20 mA (Programmable alarm state)
88Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 95
7826/7828 Specifications
Table A-1Default configuration for analog outputs continued
Option AOption BOptions C &D
Density of Product B000
Quadratic coefficients
(A,B,C)
Output averaging
time
Modbus
Slave address111
Byte orderBig EndianBig EndianBig Endian
Register size16 bit16 bit16 bit
Hardware type
(1) For Option C, the Matrix referral constants will have been configured to the customer’s specification.
000
5 s5 s5 s
Advanced forkAdvanced forkAdvanced fork
7826/7828 Specifications
Calculated ParametersModbus Communications
Safety Certification
Installation and Configuration Manual89
Page 96
7826/7828 Specifications
90Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 97
Appendix B
Calculated Parameters (Advanced version)
B.1Overview
The 7826/7828 liquid density meter is capable of calculating a number of parameters based on the
measured line density and temperature. These calculated parameters are often referred to as ‘special
functions.’ Only one calculated parameter is available at any one time; it can be used to control the
analog (4-20 mA) output, and can also be accessed as a digital value (Modbus Register 260).
This section describes the algorithms used in these calculations.
The availability of the calculated parameters is dependent on whether Matrix or API is chosen as the
density referral method.
7826/7828 Specifications
Calculated ParametersModbus Communications
Special FunctionAPI referralMatrix referral
Specific Gravity
API°
% mass
% volume
° Baumé
° Brix
User defined quartic
None
B.2Base density referral
Base density is the density of the fluid at a specified base (or referral) temperature which is different
to the line (i.e., the actual) temperature of the fluid. Base density can be calculated by either a Matrix
referral method or by the API Referral method.
B.2.1Matrix density referral
99
9
9
9
9
9
9
99
Safety Certification
The Matrix Density Referral method uses a process of interpolation and extrapolation between a
matrix of known density and temperature reference points to determine the liquid density at a
specified base temperature different to the line temperature. A typical referral matrix is shown below.
Installation and Configuration Manual91
Page 98
Calculated Parameters (Advanced version)
Temperature
Density
T
5
T
4
T
3
T
2
T
1
D1D2D3D
4
Line Temperature
(measured)
Line Density ρ
(measured)
Base (Referred)
Density ρ
B
(calculated)
The lines D1 to D4 plot the density of four product types for which the density is known at five
different reference temperatures, T
temperature, the 7826/7828 meter calculates the base density at the base temperature.
The information required for the referral is:
•Five reference temperatures
•The density for each of four product types at the five reference temperatures (20 reference
points in all)
•The base temperature, which must be one of the five reference temperatures.
to T5. Using this information, and the measured line density and
1
All 20 reference points must be specified, otherwise the 7826/7828 meter cannot calculate the base
density. If you do not have all the relevant data, enter a sensible estimate for the missing reference
points.
The easiest way of entering these values is by using the Board Configuration facility of ADView.
Section 4 tells you how to do this.
B.2.2API density referral
This calculation uses an iterative process to determine the density at the base temperature by applying
temperature and pressure corrections using the API-ASTM-IP petroleum measurement tables.
The information required for the API density is:
•Reference pressure and reference temperature.
•Line pressure: This is not measured by 7826/7828 meter, and must be entered as part of the
configuration.
•Product type: Refined product, crude product, or user defined.
Density / temperature relationship
Correction factors in the revised API-ASTM-IP petroleum measurement tables are based on the
following correlation equations:
ρt / ρ
=exp [-α15 Δt (1 + 0.8 α15 Δt)]
15
92Micro Motion 7826/7828 Insertion Liquid Density Meters
Page 99
Calculated Parameters (Advanced version)
2
15
1510
15
KK
ρ
ρ+
=α
t
1
1
0
P
V
V
1
⎥
⎦
⎤
⎢
⎣
⎡
δ
=β
where:
•ρt = Density at line temperature t °C
•ρ
= Density at base temperature 15 °C.
15
•Δt = (t - 15) °C
•α
= Tangent thermal expansion coefficient per °C at base temperature of 15 °C.
15
The tangent coefficient differs for each of the major groups of hydrocarbons. It is obtained from the
following relationship:
where K
and K1 are known as the API factors.
0
Hydrocarbon group selection
The hydrocarbon group can be selected as:
•General refined products
•General crude products
•User defined
and K1 are programmed into the 7826/7828 meter for the first two groups. For refined products the
K
0
values of K
Hydrocarbon Group
Gasolines654 to 779346.422780.43884
Jet Fuels779 to 839594.541800.0000
Fuel Oils839 to 1075186.96960.48618
and K1 are automatically selected according to the corrected density: