Micro Motion Guide: Guidelines for the Selection and Operation of Provers with ELITE Coriolis Flow Meters | Micro Motion Manuals & Guides

Reference Guide
MC-001597 Rev E
1/2018
ELITE® Coriolis Flow Meters
Guidelines for the Selection and Operation of Provers with Micro Motion ELITE
®
Coriolis
Flow Meters
Micro Motion® ELITE® ow meters are high-
precision Coriolis ow meters that are often used in the oil and gas industry in conjunction with volume provers. These guidelines are designed to aid in the selection of a prover size that will result in consistent proving repeatability, while taking into consideration the balance between:
• Maximum proving efciency
• Minimum prover size and cost
• Minimum prover wear and maintenance
Substantial experience from laboratory testing and eld proving forms the basis of the prover size recommendations and the Total Prove Time (TPT) predictions in these guidelines. However, results may vary if unstable process conditions exist during proving.
It should be noted that these guidelines are based on conservative estimates from the available data. If repeatability requirements are already consis­tently being met, there is no need to change the process or the prover size.
Proving Methods and Proving Data Evaluation
The American Petroleum Industry (API) Manual of Petroleum Measurement Standards (MPMS) Chapter 4.8, Second Edition, Operation of Proving Systems, Annex A, Evaluating Meter Proving Data explains the relationship between the number
of proving runs, the observed repeatability, and the random uncertainty of the resulting meter factor. One important principal is that a lower meter factor uncertainty will always result as more runs are collected and averaged.
Prover Sizing and Selection for Fixed­Volume Provers (Does Not Apply to Master Meter Provers)
Important Note: The prover size should never result in a pass time of less than 0.5 seconds or a pre-run time of less than 0.25 seconds.
Total Prove Time (TPT) is dened as the total
accumulated amount of time during which the prover displacer was travelling between the detector switches. The minimum TPT that is needed to achieve the target meter factor random uncertainty can be used to size the prover.
Estimated minimum TPT values that may be expected to pass repeatability requirements for
different meter sizes and ow rates are shown in Table 1. The velocity of the uid as it travels through the meter ow tubes is also shown in Table 1 in
units of feet per second (fps). Velocities above 60 fps are not recommended when proving with
a xed-volume prover and may result in excessive
TPT to pass repeatability. For applications above 60 fps, master meter proving is recommended instead of xed-volume provers.
Equation 1 describes TPT:
www.Emerson.com/MicroMotion
Base Prover Volume(BPV)
𝑇𝑃𝑇 
Flow rate
×(# 𝑜 𝑟𝑢𝑛𝑠󰇜 × (# 𝑜 𝑝𝑎𝑠𝑠𝑒𝑠 𝑝𝑒𝑟 𝑟𝑢𝑛󰇜
Reference Guide
MC-001597 Rev E
1/2018
ELITE® Coriolis Flow Meters
To use Table 1 to size a prover, there are two methods to select from:
Method 1 (Determine the BPV): Find the minimum
TPT value from Table 1. Multiply the ow rate by
0.0117 to convert from BPH to gallons per second. Then enter the TPT, ow rate, the number of runs,
and the passes per run (if averaging multiple passes
per run) into Equation 2 to nd the minimum BPV
needed in gallons.
Equation 2:
𝐵𝑃 
TPT x Flow Rate
(# 𝑜 R𝑢𝑛𝑠󰇜×(Passes pe Run󰇜
Example: CMFHC4 meter at 6500 BPH
• From Table 1: Velocity ≈ 30 fps. TPT =
20 seconds.
• Convert: 6500 BPH X 0.0117 = 76 gallons per second
• If 5 single-pass runs are required, BPV = (20 seconds X 76 gallons per second) ÷ (5 runs X 1 pass per run) = 304 gallons or 7.2 BBLS.
• If 10 runs and 3 passes per run are acceptable, BPV = (20 seconds X 76 gallons per second) ÷ (10 runs X 3 pass per run) = 50 gallons or
1.2 BBLS.
Method 2 (Determine the Number of Passes Needed): Find the minimum TPT value from
Table 1. Multiply the ow rate by 0.0117 to convert from BPH to gallons per second. Then, insert the ow rate and a BPV in gallons into Equation
3 to estimate the total number of passes that
will be needed for a prover size with that BPV. If
averaging multiple passes per run, divide the total number of passes needed by the number of runs and round up to determine the minimum number
of passes per run needed. For single-pass runs,
the number of runs needed will equal the total number of passes needed.
Equation 3:
𝑇𝑜𝑡𝑎 # 𝑜 𝑃𝑎𝑠𝑠𝑒𝑠  𝑇𝑃𝑇×
Flow rate
Base Prover Volume(BPV)
Example: CMF400 meter at 2300 BPH
• From Table 1: Velocity ≈ 40 fps. TPT ≈
30 seconds.
• Convert: 2300 BPH X 0.0117 = 27 gallons per second
• If the BPV is 170 gallons (4 BBLS), Total # of passes = 30 seconds X 27 gallons per second ÷ 170 gallons = 5 total passes
(5 total passes ÷ 5 runs = 1 pass per run
for 5 runs).
Page 2
• If the BPV is 65 gallons (1.55 BBLS), Total # of passes = 30 seconds X 27 gallons per second ÷ 65 gallons = 12 total passes
(12 total passes ÷ 5 runs = 3 passes per run for 5 runs).
Loading...
+ 4 hidden pages