This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EC declaration of conformity for directives that apply to this product. The EC declaration of
conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available on
the internet at www.micromotion.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive can be found on the internet at
www.micromotion.com/documentation.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the transmitter
configuration manual. Product data sheets and manuals are available from the Micro Motion web site at
www.micromotion.com/documentation.
Return policy
Micro Motion procedures must be followed when returning equipment. These procedures ensure legal compliance with
government transportation agencies and help provide a safe working environment for Micro Motion employees. Failure to follow
Micro Motion procedures will result in your equipment being refused delivery.
Information on return procedures and forms is available on our web support system at www.micromotion.com, or by phoning the
Micro Motion Customer Service department.
Emerson Flow customer service
Email:
•Worldwide: flow.support@emerson.com
•Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
United States800-522-6277U.K.0870 240 1978Australia800 158 727
Minimum wire gauge (AWG per foot or meter)Figure 1-1:
Planning
A.AWG maximum
B.Distance of installation
Minimum wire area (mm2 per meter or foot)Figure 1-2:
Installation Manual 3
A.Minimum wire area (mm2)
B.Distance of installation
Page 8
A
STATUS
SCROLLSELECT
Planning
1.4Other installation considerations
Numerous external factors can affect the meter's successful operation. To ensure that your
system works correctly, consider the factors covered in this section when designing your
installation.
1.4.1Boundary effect
Boundary effect refers to the distortion in the wave forms in the process fluid that are
caused by reflections from the pipe wall. If the pipe wall is within the meter's effective
measurement region, the boundary effect produces measurement inaccuracy.
Region of measurement boundary or sensitivity (plan view)Figure 1-3:
A.Sensitive, or effective, region
The factory calibration compensates for the boundary effect. The meter can be calibrated
for 2-inch, 2.5-inch, or 3-inch pipe. If the meter is installed in a pipe that does not match
the calibration size, the compensation will be inaccurate, and process measurement will
be inaccurate.
Verify that the meter was calibrated for the pipe size you plan to use.
4 Micro Motion Fork Viscosity Meter
Page 9
1.4.2Flow rates
Maintain constant flow rates and velocities that are within the limits specified for the
meter. The fluid flow provides a steady heat flow into the meter installation, and the flow
rate influences the self-cleaning of the meter tines, the dissipation of bubbles, and the
solid contaminants around the meter.
If you install the meter in a bypass configuration (such as in a flow-through chamber), use a
pressure drop, pitot scoop, or a sample pump to maintain flow. When using a sample
pump, place the pump upstream from the meter.
1.4.3Entrained gas
Entrained gas, or gas pockets, can disrupt the measurement of a fluid. A brief disruption in
the signal caused by transient gas pockets can be corrected in the meter configuration,
but you must avoid more frequent disruptions or serious gas entrainment to ensure
accurate and reliable fluid measurement.
To minimize the possibility of entrained gas:
•Keep pipelines full of fluid at all times.
•Vent any gas prior to the meter installation location.
•Avoid sudden pressure drops or temperature changes that may cause dissolved
gases to break out of the fluid.
•Maintain a back pressure on the system that is sufficient to prevent gas breakout.
•Maintain flow velocity at the sensor within the specified limits.
Planning
1.4.4Solid contamination
To avoid issues related to solids contamination:
•Avoid sudden changes of the fluid velocity that may cause sedimentation.
•Install the meter far enough downstream from any pipework configuration that may
cause centrifuging of solids (such as at a pipe bend).
•Maintain flow velocity at the meter installation that is within the specified limits.
•Use filtration in your process, if necessary.
1.4.5Temperature gradients and insulation
For high-viscosity fluids, minimize any temperature gradients in the fluid, and in the piping
and fittings immediately upstream and downstream of the meter. Minimizing
temperature gradients reduces the effect of viscosity changes. Micro Motion recommends
using the following guidelines to reduce the thermal effects to your meter installation:
•Always insulate the meter and surrounding pipework thoroughly.
-Avoid insulating the transmitter housing.
-Use rock wool or any equivalent heat jacket material that is at least 1 inch (25
mm) thick, but preferably 2 inches (50 mm) thick.
Installation Manual 5
Page 10
Planning
-Enclose insulation in a sealed protective casing to prevent moisture ingress, air
circulation, and crushing of the insulation.
-For flow-through chamber installations, use the special insulation jacket
provided by Micro Motion.
•Avoid direct heat or cold on the meter or on the associated upstream or
downstream pipe work that is likely to create temperature gradients.
•If it is necessary to protect against cooling because of flow loss, you can apply
electrical-trace heating. If you use electrical-trace heating, use a thermostat that
operates below the minimum operating temperature of the system.
1.5Recommended installations for short-stem
meters
Micro Motion recommends three standard installations for the short-stem meter to
alleviate any need for onsite calibration. All meters are factory calibrated for these types of
installations and take into consideration the potential boundary effect of each installation.
Table 1-1 highlights these different installations according to specific conditions or
requirements that may exist for your process environment.
Standard installation types: short-stem metersTable 1-1:
Flow-through
Installation type:Free streamT-Piece
Meter placementMeter tines are
inserted directly into
the main fluid flow.
The meter must always
be installed
horizontally and
oriented so that the
gap between the tines
is vertical.
Flow rate0.3 to 0.5 m/s (at the
meter)
ViscosityUp to 500 cPUp to 100 cP (250 cP in
Temperature–50 °C to 200 °C (–58
°F to 392 °F)
Meter tines are
contained in a side
pocket off the main
flow.
The meter must always
be installed
horizontally and
oriented so that the
gap between the tines
is vertical.
0.5 to 3 m/s (at main
pipe wall)
some cases)
–50 °C to 200 °C (–58
°F to 392 °F)
chamber
Meter tines are
contained in a flowthrough chamber in
which fluid is
circulated from the
main flow.
10 to 30 l/min
Up to 500 cP
–50 °C to 200 °C (–58
°F to 392 °F)
6 Micro Motion Fork Viscosity Meter
Page 11
Standard installation types: short-stem meters (continued)Table 1-1:
Installation type:Free streamT-Piece
Main flow pipe size• Horizontal pipe:
minimum
diameter, 100 mm
(4 inch)
• Vertical pipe:
minimum
diameter, 150 mm
(6 inch)
Advantages• Simple installation
in large bore pipes
• Ideal for clean
fluids and nonwaxing oils
• Suitable for line
viscosity
measurement and
simple referrals
RecommendationsDo not use with:
• Dirty fluids
• Low or unstable
flow rates
• Where step
changes in
viscosity can occur
• For small bore
pipes
Minimum diameter, 50
mm (2 inch)
• Simple installation
in large bore pipes
• Ideal for clean
fluids and nonwaxing oils
• Suitable for line
viscosity
measurement and
simple referrals
Do not use with:
• Dirty fluids
• Low or unstable
flow rates
• Where step
changes in
viscosity can occur
• For small bore
pipes
• Where
temperature
effects are
significant
Planning
Flow-through
chamber
Suitable for all sizes, if
mounted in a bypass
(slipstream)
configuration
• Adaptable
installation to any
diameter main
pipe and for tank
applications
• Ideal for flow and
temperature
conditioning
• Suitable for
complex referrals
and for use with
heat exchangers
• Suitable for step
changes in
viscosity
• Fast response
• Ideal for analyzer
cubicles
• Do not use with
uncontrolled flow
rates.
• Careful system
design is required
to ensure
representative
measurement.
• Frequently requires
the use of a pump.
1.6Perform a pre-installation meter check
1.Remove the meter from the box.
Installation Manual 7
Page 12
Planning
CAUTION!
Handle the meter with care. Follow all corporate, local, and national safety regulations
for lifting and moving the meter.
2.Visually inspect the meter for any physical damage.
If you notice any physical damage to the meter, immediately contact Micro Motion
Customer Support at flow.support@emerson.com.
3.Position and secure the meter in a vertical position with the flow arrow pointing
upward.
4.Connect the power wiring, and power up the meter.
Remove the back transmitter housing cover to access the PWR terminals.
Power supply wiring terminalsFigure 1-4:
A. 24 VDC
5.Perform a Known Density Verification (KDV) check.
Use the Known Density Verification procedure to match the current meter
calibration with the factory calibration. If the meter passes the test, then it has not
drifted or changed during shipment.
For more information on performing a KDV check, see the configuration and use
manual that shipped with the product.
8 Micro Motion Fork Viscosity Meter
Page 13
2Mounting
Topics covered in this chapter:
•Mount in free-stream application (flanged fitting)
•Mount in free-stream application (weldolet fitting)
•Mount with a T-piece (flanged fitting)
•Mount with a flow-through chamber
•Mount in an open tank (long-stem meter)
•Mount in a closed tank (long-stem meter)
•Attach the PFA ring and circlip
•Rotate the electronics on the meter (optional)
•Rotate the display on the transmitter (optional)
Mounting
2.1Mount in free-stream application (flanged
fitting)
Prerequisites
Free-stream (flanged) installations are recommended for processes with the following
conditions:
Flow0.3 to 0.5 m/s (at the meter)
Viscosity0.5 to 12,500 cP
Temperature-50 °C to 200 °C (–58 °F to 392 °F)
-40 °C to 200 °C (-40 °F to 392 °F) in hazardous
areas
Procedure
See Figure 2-1 for information on installing the meter (with a flanged fitting) in a freestream application.
Important
Always install the meter horizontally and oriented so that the gap between the tines is vertical. This
position helps to prevent the trapping of bubbles or solids on the meter – allowing the solids to sink
and the bubbles to rise. You can use the scribe mark on the spigot (located between the flange and
transmitter) as a reference for the tine orientation. Always orient the meter so the scribe mark is at
either the 12 o’clock or 6 o’clock position.
Installation Manual 9
Page 14
B
A
STATUS
SCROLLSELECT
Plan view of a vertical pipe installation
Mounting
Free-stream (flanged fitting) meter installationFigure 2-1:
A. 4-inch pipe for horizontal installations; 6-inch (152 mm) pipe for vertical installations
B. Size the recess mount so that the meter tines are inserted fully into the liquid [approximately 2.75 in
(70 mm)].
2.2Mount in free-stream application (weldolet
fitting)
The weldolet for free-stream installations has a 1.5-inch taper lock fitting and is supplied to
be welded on 4-inch, 6-inch, 8-inch or 10-inch pipelines. A weldolet installation ensures
that the tines of the meter are oriented correctly and are fully inserted into the fluid
stream.
Prerequisites
•Free-stream (weldolet) installations are recommended for processes with the
following conditions:
Flow0.3 to 0.5 m/s (at the meter)
Viscosity0.5 to 12,500 cP
Temperature–50 °C to 200 °C (–58 °F to 392 °F)
–40 °C to 200 °C (–40 °F to 392 °F) in
hazardous areas
Note
If temperature variations are a critical factor in your process, the reduced thermal mass of the
taper-lock fitting of the weldolet can track changes in temperature more efficiently.
•Before fitting the weldolet, you must bore a 2.1 in (52.5 mm) diameter opening in
the pipeline to accept the meter. You must weld the weldolet to the pipeline
concentrically with the pre-bored hole.
10 Micro Motion Fork Viscosity Meter
Page 15
STATUS
SCROLLSELECT
A
C
D
B
Plan view of a vertical pipe installation
Mounting
Procedure
See Figure 2-2 for information on installing the meter (with a weldolet fitting) in a freestream application.
Important
Always install the meter horizontally and oriented so that the gap between the tines is vertical. This
position helps to prevent the trapping of bubbles or solids on the meter – allowing the solids to sink
and the bubbles to rise. You can use the scribe mark on the spigot (located between the flange and
transmitter) as a reference for the tine orientation. Always orient the meter so the scribe mark is at
either the 12 o’clock or 6 o’clock position.
Free-stream (weldolet fitting) meter installationFigure 2-2:
A. 4-inch pipe for horizontal installations; 6-inch (152 mm) pipe for vertical installations
B. 2.1 in (52.5 mm) meter opening in pipeline
C. Weld
D. Free-stream weldolet (purchased to fit pipe diameter)
2.3Mount with a T-piece (flanged fitting)
Prerequisites
•T-piece (flanged) installations are recommended for processes with the following
conditions:
Flow0.5 to 3 m/s (at the pipe wall)
Viscosity0.5 to 100 cP
Temperature--50 °C to 200 °C (–58 °F to 392 °F)
--40 °C to 200 °C (-40 °F to 392 °F) in
hazardous areas
Installation Manual 11
Page 16
STATUS
SCROLLSELECT
B
A
C
Plan view of a vertical pipe installation
Mounting
Note
-Flow velocity at the pipe wall and fluid viscosity must be within the limits shown to ensure
that the fluid within the pocket is refreshed in a timely manner. This installation will not
respond as rapidly as the free-stream installation to step changes in viscosity.
-The thermal mass of the flanges may affect the response time of the meter to
temperature changes.
•Attach the PFA ring and circlip to the underside of the meter flange before installing
the meter in your application (see Section 2.7).
Procedure
See Figure 2-3 for information on installing the meter (with a flanged fitting) in a T-piece.
Size the T-piece so that the meter tines are retracted 1 in (25 mm) from the main pipe wall.
For higher flow rates, increase this by 0.4 in (10 mm) for every 1 m/s increase in the main
flow rate.
Important
Always install the meter horizontally and oriented so that the gap between the tines is vertical. This
position helps to prevent the trapping of bubbles or solids on the meter – allowing the solids to sink
and the bubbles to rise. You can use the scribe mark on the spigot (located between the flange and
transmitter) as a reference for the tine orientation. Always orient the meter so the scribe mark is at
either the 12 o’clock or 6 o’clock position.
T-piece (flanged fitting) meter installationFigure 2-3:
A. 4-inch pipe or larger for horizontal or vertical installations
B. Distance of meter tines from main pipe wall is determined by the maximum flow rate of the process.
C. PFA ring and circlip
12 Micro Motion Fork Viscosity Meter
Page 17
2.4Mount with a flow-through chamber
Flow-through chambers are manufactured by Micro Motion, and are available with either
of the following:
•Welded ends or compression fittings that connect into the process pipelines
•1- inch, 2-inch, or 3-inch inlet and outlet pipes
Important
Do not alter the length of the inlet and outlet pipes. Pipe alterations can adversely affect the fitting
temperature response and stability.
A. Standoff height can vary (provided by customer)
3.Confirm the meter tines are away from the tank wall.
Meter placement (away from tank wall)Figure 2-13:
A. 200 mm
B. 50 mm
4.Confirm the meter tines are immersed in fluid.
Installation Manual 19
Page 24
A
A
AA
Mounting
Meter placement (immersed in fluid)Figure 2-14:
5.Confirm the meter placement has allowed for the flexing of the tank lid to prevent
the meter from being pushed towards a tank wall or into the path of disturbed flow.
Meter placement (allowance for tank lid flexing)Figure 2-15:
A. 200 mm
6.Confirm the meter tines are placed away from objects and disturbed flow.
Meter placement (distance from objects and disturbed flow)Figure 2-16:
A. 200 mm
7.If flow exists, confirm the meter tines are aligned so that the flow is directed towards
or through the gap between the tines.
20 Micro Motion Fork Viscosity Meter
Page 25
Meter placement (flow direction through tine gap)Figure 2-17:
8.Confirm the meter tines are kept away from deposit buildup.
Mounting
Meter placement (away from deposit buildup)Figure 2-18:
2.7Attach the PFA ring and circlip
You attach the PFA ring (and circlip) around the boss on the underside of the meter flange
to center the meter tines within a 2-inch Schedule 40 or 80 pipe. The circlip holds the ring
in place.
Note
If you are using the Zirconium version of the meter, a self-locking PFA ring is provided and does not
require a circlip to keep it in place.
Installation Manual 21
Page 26
B
A
C
A
Mounting
Procedure
See Figure 2-19 for information on attaching the PFA ring and circlip to the meter.
Attaching a PFA ring and circlipFigure 2-19:
A. Circlip (not provided with self-locking PFA rings)
B. PFA ring
C. PFA ring and circlip attached
2.8Rotate the electronics on the meter (optional)
You can rotate the transmitter on the meter up to 90°.
1.Using a 4 mm hex key, loosen the cap screw that holds the transmitter in place.
Component to secure transmitter in placeFigure 2-20:
A. M5 socket-head cap screw
22 Micro Motion Fork Viscosity Meter
Page 27
2.Rotate the transmitter clockwise to the desired orientation up to 90°.
B
C
D
A
D
E
3.Secure the cap screw in place and tighten to 60 lb·in (6.8 N·m).
2.9Rotate the display on the transmitter
(optional)
The display on the transmitter electronics module can be rotated 90° or 180° from the
original position.
2.Turn the display cover counterclockwise to remove it from the main enclosure.
3.Carefully loosen (and remove if necessary) the semi-captive display screws while
holding the display module in place.
4.Carefully pull the display module out of the main enclosure until the sub-bezel pin
terminals are disengaged from the display module.
Note
If the display pins come out of the board stack with the display module, remove the pins and
reinstall them.
Installation Manual 23
Page 28
Mounting
5.Rotate the display module to the desired position.
6.Insert the sub-bezel pin terminals into the display module pin holes to secure the
display in its new position.
7.If you have removed the display screws, line them up with the matching holes on the
sub-bezel, then reinsert and tighten them.
8.Place the display cover onto the main enclosure.
9.Turn the display cover clockwise until it is snug.
10.If appropriate, power up the meter.
24 Micro Motion Fork Viscosity Meter
Page 29
3Wiring
Topics covered in this chapter:
•Terminals and wiring requirements
•Explosion-proof/flameproof or non-hazardous output wiring
•Processor wiring for remote-mount 2700 FOUNDATION™ fieldbus option
•Wiring to external devices (HART multidrop)
•Wiring to signal converters and/or flow computers
3.1Terminals and wiring requirements
Three pairs of wiring terminals are available for transmitter outputs. These outputs vary
depending on your transmitter output option ordered. The Analog (mA), Time Period
Signal (TPS), and Discrete (DO) outputs require external power, and must be connected to
an independent 24 VDC power supply.
Wiring
The screw connectors for each output terminal accept a maximum wire size of 14 AWG
(2.5 mm2).
Important
•Output wiring requirements depend on whether the meter will be installed in a safe area or a
hazardous area. It is your responsibility to verify that this installation meets all corporate,
local, and national safety requirements and electrical codes.
•If you will configure the meter to poll an external temperature or pressure device, you must
wire the mA output to support HART communications. You may use either HART/mA singleloop wiring or HART multi-drop wiring.
Transmitter outputsTable 3-1:
Output channels
Transmitter version
Analog4–20 mA + HART4–20 mAModbus/RS-485
Discrete4–20 mA + HARTDiscrete outputModbus/RS-485
ABC
Installation Manual 25
Page 30
Wiring
3.2Explosion-proof/flameproof or non-hazardous
output wiring
3.2.1Wire the Analog outputs version in an explosion-proof/
flameproof or non-hazardous area
CAUTION!
Meter installation and wiring should be performed by suitably trained personnel only in
accordance with the applicable code of practice.
Procedure
Wire to the appropriate output terminal and pins (see Figure 3-1).
26 Micro Motion Fork Viscosity Meter
Page 31
mA1+
HART
RS-485
PWR
mA2
AA
B
RS-485 A
RS-485 B
C
D
B
B
A
A
A
Wiring
Wiring the Analog outputsFigure 3-1:
A. 24 VDC
B. R
(250 Ω resistance)
load
C. HART-compatible host or controller; and/or signal device
D. Signal device
Note
Ω
For operating the milliamp outputs with a 24V supply, a maximum total loop resistance of 657
is
allowed.
CAUTION!
• To meet the EC Directive for Electromagnetic Compatibility (EMC), use a suitable
instrumentation cable to connect the meter. The instrumentation cable should have individual
screens, foil or braid over each twisted pair, and an overall screen to cover all cores. Where
permissible, connect the overall screen to earth at both ends (360° bonded at both ends).
Connect the inner individual screens at only the controller end.
• Use metal cable glands where the cables enter the meter amplifier box. Fit unused cable ports
with metal blanking plugs.
Installation Manual 27
Page 32
Wiring
3.2.2Wire the Discrete output version in an explosion-proof/
flameproof or non-hazardous area
CAUTION!
Meter installation and wiring should be performed by suitably trained personnel only in
accordance with the applicable code of practice.
Procedure
Wire to the appropriate output terminal and pins (see Figure 3-2).
28 Micro Motion Fork Viscosity Meter
Page 33
mA1+
HART
RS-485
PWR
DO
AA
B
RS-485 A
RS-485 B
C
E
D
B
A
A
A
Wiring
Wiring the Discrete output versionFigure 3-2:
A. 24 VDC
B. R
(250 Ω resistance)
load
C. HART-compatible host or controller; and/or signal device
Ω
D. R
load
resistance recommended)
(500
E. Discrete input device
Note
Ω
• For operating the milliamp output with a 24V supply, a maximum total loop resistance of 657
is
allowed.
• When operating the Discrete output with a 24 VDC power supply, a maximum total loop resistance of
1300 Ω is allowed.
CAUTION!
• To meet the EC Directive for Electromagnetic Compatibility (EMC), use a suitable
instrumentation cable to connect the meter. The instrumentation cable should have individual
screens, foil or braid over each twisted pair, and an overall screen to cover all cores. Where
permissible, connect the overall screen to earth at both ends (360° bonded at both ends).
Connect the inner individual screens at only the controller end.
• Use metal cable glands where the cables enter the meter amplifier box. Fit unused cable ports
with metal blanking plugs.
Installation Manual 29
Page 34
Wiring
3.3Processor wiring for remote-mount 2700
FOUNDATION™ fieldbus option
3.3.1RS-485 entity parameters for the remote-mount 2700
FOUNDATION™ fieldbus option
DANGER!
Hazardous voltage can cause severe injury or death. To reduce the risk of hazardous voltage,
shut off power before wiring the meter.
DANGER!
Improper wiring in a hazardous environment can cause an explosion. Install the meter only in
an area that complies with the hazardous classification tag on the meter.
RS-485 output and cable entity parametersTable 3-2:
Cable parameters for intrinsically safe circuit (linear)
Voltage (Ui)17.22 VDC
Current (Ii)484 mA
Maximum capacitance (Ci)1 nF
Maximum inductance (Li)Negligible
Cable parameters for Ex ib IIB, Ex ib IIC
Voltage (Uo)9.51 VDC
Current (instantaneous) (Io)480 mA
Current (steady state) (I)106 mA
Power (Po)786 mW
Internal resistance (Ri)19.8 Ω
Cable parameters for Group IIC
Maximum external capacitance (Co)85 nF
Maximum external inductance (Lo)25 µH
Maximum external inductance/resistance ratio
(Lo/Ro)
Cable parameters for Group IIB
Maximum external capacitance (Co)660 nF
Maximum external inductance (Lo)260 µH
Maximum external inductance/resistance ratio
(Lo/Ro)
31.1 µH/Ω
124.4 µH/Ω
30 Micro Motion Fork Viscosity Meter
Page 35
3.3.2Prepare the 4-wire cable
Important
For user-supplied cable glands, the gland must be capable of terminating the drain wires.
Note
If you are installing unshielded cable in continuous metallic conduit with 360º termination shielding,
you only need to prepare the cable – you do not need to perform the shielding procedure.
Wiring
Installation Manual 31
Page 36
Wiring
4-wire cable preparationFigure 3-3:
Cable glands
Micro Motion
cable gland
Pass the wires through the gland nut and clamping insert.
Gland nut
Clamping
insert
NPT
Gland supplier
Gland type
Remove the integral processor
cover
Cable layout
M20
User-supplied
cable gland
Pass the wires
through the gland.
Terminate the drain
wires inside the
gland.
Metal conduit
Run conduit to
sensor
Lay cable in conduit
Done
(do not perform the
shielding procedure)
1. Strip 4-1/2 inch (115 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Strip all but 3/4 inch (19 mm) of shielding.
Wrap the drain wires twice around the shield and cut off
the excess drain wires.
Go to the shielding
1. Strip 4-1/4 inch (108 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Strip all but 1/2 inch (12 mm) of shielding.
Drain wires
wrapped around
shield
procedure
32 Micro Motion Fork Viscosity Meter
Page 37
Wiring
4-wire cable shieldingFigure 3-4:
From the preparation
procedure
Micro Motion
cable gland
Braided
(armored cable)
Apply the Heat Shrink
1. Slide the shielded heat shrink over the drain wires. Ensure that the
wires are completely covered.
2. Apply heat (250 °F or 120 °C) to shrink the tubing. Do not burn the
cable.
3. Position the clamping insert so the interior end is flush with the braid
of the heat shrink.
Assemble the Gland
1. Fold the shield or braid back over the clamping insert and 1/8 inch
(3 mm) past the O-ring.
2. Install the gland body into the conduit opening on the core processor housing.
3. Insert the wires through gland body and tighten the gland nut onto the gland body.
Cable shield
type
Shielded heat
shrink
Foil
(shielded cable)
NPT
Gland supplier
Gland typeM20
After heat applied
User-supplied
cable gland
Trim 7 mm from the shielded
heat shrink
Trim
Terminate the shield
and drain wires in the
Assemble the gland
according to vendor
gland
instructions
Shield folded back
Done
Gland body
4-wire cable types and usage
Micro Motion offers two types of 4-wire cable: shielded and armored. Both types contain
shield drain wires.
The 4-wire cable supplied by Micro Motion consists of one pair of red and black 18 AWG
(0.75 mm2) wires for the VDC connection, and one pair of white and green 22 AWG
(0.35 mm2) wires for the RS-485 connection.
User-supplied 4-wire cable must meet the following requirements:
Installation Manual 33
Page 38
A
B
C
D
Wiring
•Twisted pair construction.
•Applicable hazardous area requirements, if the core processor is installed in a
hazardous area.
•Wire gauge appropriate for the cable length between the core processor and the
transmitter.
•Wire gauge of 22 AWG or larger, with a maximum cable length of 1000 feet.
3.3.3Processor wiring for the remote-mount 2700
FOUNDATION fieldbus™ option
The following figure illustrates how to connect the individual wires of a 4-wire cable to the
processor terminals. For detailed information on mounting and wiring to the remotemount 2700 FOUNDATION fieldbus transmitter, see the transmitter installation manual.
Figure 3-5:
Processor (Modbus/RS-485) connections to the remote-mount 2700 FF
transmitter
A.White wire to RS-485/A terminal
B.Green wire to RS-485/B terminal
C.Red wire to Power supply (+) terminal
D.Black wire to Power supply (–) terminal
Important
•To meet the EC Directive for EMC (Electromagnetic Compatibility), it is recommended that the
meter be connected using a suitable instrumentation cable. The instrumentation cable should have
individual screen(s), foil or braid over each twisted pair and an overall screen to cover all cores.
Where permissible, the overall screen should be connected to earth at both ends (360° bonded at
both ends). The inner individual screen(s) should be connected at only one end, the controller end.
•Metal cable glands should be used where the cables enter the meter amplifier box. Unused cable
ports should be fitted with metal blanking plugs.
34 Micro Motion Fork Viscosity Meter
Page 39
3.4Wiring to external devices (HART multidrop)
You can wire up to three external HART devices with the meter. The following information
provides wiring diagrams for making those connections in safe and hazardous
environments.
3.4.1Wire mA1 in a HART multi-drop environment
Important
To wire power and outputs, see Wire power and outputs in a HART single-loop environment.
Wiring
Installation Manual 35
Page 40
250 Ω
24 VDC
mA1+
HART
A
B
C
E
D
Wiring
Wire mA1 in a HART multi-drop environmentFigure 3-6:
•To meet the EC Directive for Electromagnetic Compatibility (EMC), use a suitable instrumentation cable to connect
the meter. The instrumentation cable should have individual screens, foil or braid over each twisted pair, and an
overall screen to cover all cores. Where permissible, connect the overall screen to earth at both ends (360° bonded
at both ends). Connect the inner individual screens at only the controller end.
•Use metal cable glands where the cables enter the meter amplifier box. Fit unused cable ports with metal
blanking plugs.
36 Micro Motion Fork Viscosity Meter
Page 41
3.5Wiring to signal converters and/or flow
computers
For meters with a Time Period Signal (TPS) output, you can wire the meter to an signal
converter or flow computer directly. The following information provides wiring diagrams
for making those connections in safe and hazardous environments.
When wiring the meter to an active HART host or signal converter/flow computer, you are
not required to provide external power to the output connections. These active devices
provide the 24 VDC necessary for these connections.
Wiring
Installation Manual 37
Page 42
mA1+
HART
RS-485
PWR
TPS
AA
B
24 VDC
RS-485 A
RS-485 B
A
B
Wiring
3.5.1Wire to a signal converter/flow computer in an
explosion-proof/flameproof or non-hazardous area
Figure 3-7:
Wiring to a signal converter/flow computer in an explosion-proof/
flameproof or non-hazardous area
A.Active HART host
B.Active signal converter/flow computer
CAUTION!
•To meet the EC Directive for Electromagnetic Compatibility (EMC), use a suitable
instrumentation cable to connect the meter. The instrumentation cable should have
individual screens, foil or braid over each twisted pair, and an overall screen to cover all
cores. Where permissible, connect the overall screen to earth at both ends (360° bonded at
both ends). Connect the inner individual screens at only the controller end.
•Use metal cable glands where the cables enter the meter amplifier box. Fit unused cable
ports with metal blanking plugs.
38 Micro Motion Fork Viscosity Meter
Page 43
4Grounding
The meter must be grounded according to the standards that are applicable at the site.
The customer is responsible for knowing and complying with all applicable standards.
Prerequisites
Micro Motion suggests the following guides for grounding practices:
•In Europe, EN 60079-14 is applicable to most installations, in particular Sections
12.2.2.3 and 12.2.2.4.
•In the U.S.A. and Canada, ISA 12.06.01 Part 1 provides examples with associated
applications and requirements.
•For IECEx installations, IEC 60079-14 is applicable.
If no external standards are applicable, follow these guidelines to ground the meter:
The Emerson logo is a trademark and service mark of Emerson
Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct
Connect marks are marks of one of the Emerson Process
Management family of companies. All other marks are property of
their respective owners.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.