Micro Motion, ELITE, BASIS and ProLink are registered trademarks of Micro Motion,
Inc., Boulder, Colorado. Rosemount and SMART FAMILY are registered trademarks
of Rosemount, Inc., Ede n Prai rie, Minnesota. HART is a registered tradem ark of the
HART Communication Foundation, Austin, Texas. Modbus is a registered trademark
of Modicon, Inc., North Andover, Massachusetts.
This instruction manual explains how to install the Micro Motion® Model
RFT9709 transmitter for use with Micro Motion Coriolis flow sensors. For
more information about the sensor, see the appropriate sensor
instruction manual.
CAUTION
Improper installation could cause measurement error
or transmitter failure.
For personal and system safety, follow all instructions to
ensure transmitter will operate correctly.
The Model RFT9709 transmitter is a microprocessor-based transmitter
for fluid process measurement. The transmitter works with Micro Motion
sensors to measure mass or volume flow, density, and temperature.
Components of the transmitter are illustrated on the following page.
An RFT9709 transmitter and a sensor are ordered together as a Coriolis
flowmeter. The factory can provide any of three standard configuration
options:
• Gross volume, API table 5A
• Gross standard volume, API table 5A
• Not configured
WiringStartupTroubleshootingBefore You BeginMounting
RFT9709 Transmitter Inst ruction Manual
For specific configuration details, see the calibration certificate that is
shipped with the sensor. To meet API requirements, the user must
supply an external RTD that is accurate to ±0.1°F. The external RTD
calibration must be configured in the transmitter. The factory can
configure the transmitter if the RTD calibration is provided.
Changes to the configuration are possible with a custom version of
Micro Motion’s ProLink
RFT9709.
• The standard ProLink software cannot be used with the RFT9709.
Contact the factory for additional ProLink information.
• The Rosemount
with the RFT9709.
®
software program, designed specifically for the
®
hand-held HART® Communicator cannot be used
1
Before You Begin
continued
Proving the Coriolis flowmeter
RFT9709 components
Sensor cable
wiring connector
Mounting
boss
Zero button
Proving Micro Motion flowmeters can be accomplished using
conventional proving methods. Micro Motion publishes a comprehensive
applications manual, which describes in detail how to prove Coriolis
meters. For additional information, contact the Micro Motion Customer
Service Depa rtment:
• In the U.S.A., phone
1-800-522-MASS
(1-800-522-6277)
• Outside the U.S.A., phone 303-530-8400
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155
Diagnostic LED
Configuration switches
Output wiring
connector
Wiring
access
cover
shown
open
Mounting boss
Channel for
routing
sensor cable
Slots for cable ti e
16-pin connector for
future application
Power-supply
wiring ter m in al s
2
RFT9709 Transmitter Ins truction Manual
Installation
Step 1Mounting
1.1Location requirements
Hazardous area
installations
• Mount the RFT9709 in a user-supplied or factory-supplied NEMA-4
(IP65) enclosure.
• Locate the RFT9709 where it is accessible for service.
• Locate the RFT9709 where the ambient temperature remains between
–40 and 122°F (–40 and 50°C).
• Locate the RFT9709 where humidity is less than 90%.
• Total length of cable from the sensor to the RFT9709 must not exceed
1000 feet (300 meters).
• In hazardous areas, install the RFT9709 as described below.
Read the RFT9709 approvals tag before installing the transmitter. The
approvals tag is attached to the RFT9709 housing. See Figure 1-1.
WARNING
Failure to comply with requirements for intrinsic
safety in a hazardous area could result in an
explosion.
• Install the RFT9709 in an env iron me nt th at i s c om pat ible
with the hazardous area specified on the approvals tag.
• For installations that require intrinsic safety, use this
document with Micro Motion UL installation instructions.
WiringStartupTroubleshootingBefore You BeginMounting
Figure 1-1.
RFT9709 approvals tag
RFT9709 Transmitter Inst ruction Manual
• For a complete list of approvals, see
page 4 3.
• For an intrinsically safe or hazardous area installation, use this manual
with Micro Motion UL-D-IS Installation Instructions.
Hazardous area approvals
Approvals tag
,
3
Mounting
continued
1.2Mounting options
1.3Installation in usersupplied enclosure
Figure 1-2. RFT9709 dimensions
2 15/16
(74)
3 1/4
(83)
inches
(mm)
6 1/8
(156)
5 9/16
(141)
Dimensions in
2X
2X
The RFT9709 has these installation options for mounting on any flat
surface:
• For mounting in a user-supplied NEMA-4 (IP65) enclosure
• Pre-installed by the factory in an optional NEMA-4 (IP65) enclosure
• Install the RFT9709 with two screws to a flat mounting surface. Micro
Motion does not supply mounting screws.
• Install with wiring terminals facing away from the mounting surface.
• RFT9709 dimensions are provided in Figure 1-2.
1 13/16
(46)
1 11/32
(34)
Mounting boss
2X
Use #8-32 (M4)
screws with flat
washers and lock
washers for
mounting
3 5/32
(80)
Minimum
clearance
to open
access cover
5 1/4
(134)
4
Mounting
2X
boss
RFT9709 Transmitter Ins truction Manual
Mounting
continued
1.4Optional NEMA-housing
installation
An optional NEMA-4 (IP65) housing is available from the factory, or the
enclosure may be user-supplied.
Factory-supplied housing
If the RFT9709 is ordered with the factory-supplied NEMA-4 (IP65)
housing, Micro Motion installs the transmitter in the enclosure.
• Install the NEMA enclosure with four bolts. Micro Motion does not
supply mounting bolts.
• Mount to any flat, stable surface.
• NEMA housing dimensions are provided in Figure 1-3, page 6.
User-supplied housing
Any user-supplied NEMA-4 (IP65) enclosure of an appropriate size may
be used to house the RFT9709. Dimensions of the RFT9709 are
provided in Figure 1-2, page 4.
Conduit openings
Whether the optional NEMA housing is supplied by the user or the
factory, the user must add three conduit openings for power-supply
wiring, input wiring, and output wiring.
• Locate the housing so these openings are accessible for installation of
wiring and so the housing cover can be fully opened for access to the
RFT9709 inside.
• To help prevent moisture from entering the housing, install the housing
so conduit openings are pointed downward, if possible. To maintain the
enclosure’s NEMA rating, all conduit openings must be fully sealed
after wiring is installed.
• Recommended size for conduit openings is 3/4-inch (20 mm).
WiringStartupTroubleshootingBefore You BeginMounting
CAUTION
Failure to protect the RFT9709 from moisture could
cause a short circuit, which would result in
measurement error or flowmeter failure.
To avoid risk of condensation of excessive moisture in the
NEMA housing:
• Seal all con duit openings.
• Install drip legs in cable or conduit.
• Close and fully tighten all NEMA-housing covers.
Mounting feet can be installed in
optional orientation as shown
5 5/16
(136)
1/4
2X
(6)
4X 5/16-18 UNC
for mounting feet
1 3/8
4X
(35)
flat head screw
(included)
cover-access
2X
screw
Housing requires instal l ati on of three conduit openings
for power-supply wiring, input wiring, and output wiring.
Recommended opening size: 3/4-inch (20 mm).
6
RFT9709 Transmitter Ins truction Manual
Installation
Step 2Wiring
2.1General guidelines
Figure 2-1. RFT9709 wiring terminals
Sensor cable
wiring connector
Figure 2-1 illustrates the locations of the terminals for power-supply
wiring, wiring to the sensor, and output wiring.
• Terminal blocks may be unplugged from the RFT9709 (after removing
two screws) for easier installation of wiring. Always tighten screws after
re-installing terminal blocks.
• Install all conduit, cable and wiring to meet local code requirements.
For an RFT9709 installed in a NEMA enclosure:
• The RFT9709 may be installed in a user-supplied or factory-supplied
NEMA-4 (IP65) enclosure, as described in Section 1.4, page 5. The
enclosure requires three separate conduit openings for power-supply
wiring, sensor wiring, and output wiring.
• Conduit openings must remain sealed to maintain the NEMA-4 (IP65)
rating. Use conduit seals or cable glands that provide a complete seal
with the conduit openings.
WiringStartupTroubleshootingBefore You BeginMounting
Output wiring
connector
Wiring
access
cover
shown
open
Channel for
routing
sensor cable
Slots for cable tie
RFT9709 Transmitter Inst ruction Manual
16-pin connector for
future application
Power-supply
wiring ter m in al s
7
Wiring
continued
2.2Power supply wiring and
grounding
For power-supply wiring and grounding, follow these guidelines:
• The RFT9709 requires an 11 to 30 VDC power supply.
• Do not install unfiltered DC power cable in the same conduit or cable
tray as sensor cable or output wiring.
• If the sensor installation must comply with UL standards, refer to
Micro Motion UL-D-IS Installation Instructions.
• Refer to the wiring diagram presented in Figure 2-2.
WARNING
Failure to comply with requirements for intrinsic
safety in a hazardous area could result in an
explosion.
Po wer-supply wiring is not intrinsically safe.
• Keep power-supply wiring separated from intrinsically
safe sensor wiring and outpu t wiring.
• For intrinsically safe sensor installations, use this
document with Micro Motion UL installation instructions.
CAUTION
Installation with power supply on could cause
transmitter damage or failure.
Turn off power before connecting power supply wiring.
Figure 2-2. Power-supply wiring and grounding connections
#6-32 ground nut
#6-32 ground nut
Mounting boss
If equipment ground is not established via
mounting, connect a low-im pedance ground at
either ground nut.
11–30 VDC power supply
TerminalFunction
If national standards are not in effect , adhere to these standards for
ground wiring:
•
Use copper wire, 14 AWG (2.5 mm²) or lar ger wire size for grounding.
•
Keep all ground leads as shor t as po ssi ble, less than 1 ohm i m pedance.
•
Connect power-supply ground lead directly to earth ground , or follow plant
standards if a separate high-integrity intrinsically safe ground scheme is used.
23DC–
24DC+
25
8
RFT9709 Transmitter Ins truction Manual
Wiring
continued
2.3Sensor wiring
The instructions in this section explain how to connect a fully prepared
Micro Motion flowmeter cable to the RFT9709 and a sensor. The sensor
can be a Model D, DL, DT, ELITE
®
, or BASIS® sensor.
• The procedure for preparing Micro Motion flowmeter cable and cable
glands is described in the instructions that are shipped with the cable.
• Install cable and wiring to meet local code requirements.
• Use Micro Motion color-coded cable.
• Total length of cable from the sensor to the RFT9709 must not exceed
1000 feet (300 meters).
WARNING
Failure to comply with requirements for intrinsic
safety in a hazardous area could result in an
explosion.
Sensor wiring is intrinsically safe.
• Keep intrinsically safe sensor wiring separated from
power-supply wiring and output wiring.
• For intrinsically safe sensor installations, use this
document with Micro Motion UL installation instructions.
CAUTION
Improper installation of cable or conduit could cause
inaccurate measurements or flowmeter failure.
WiringStartupTroubleshootingBefore You BeginMounting
Keep sensor cable away from devices such as
transformers, motors, and power lines, which produce
large magnetic fields.
RFT9709 Transmitter Inst ruction Manual
9
Wiring
continued
Cable types
Figure 2-3.
Cable types
Micro Motion supplies 9-wire jacketed, shielded, or armored cable, as
illustrated in Figure 2-3.
• All cable types are acceptable for cable tray installation.
• All cable types must have the jacket extend under the wiring terminals
access cover, as illustrated in Figure 2-4.
• Shielded and armored cable must have the braided shield terminated
as illustrated in Figure 2-4.
Jacketed cable
Jacket
Shield e d o r
armored cable
Braided shield
Outer jacket
Figure 2-4.
Terminating flowmeter
cable
Jacket
Mounting boss
Braided shield
For shielded or
armored flowmeter
cable, connect
braided shield at
mounting boss
Jacket must extend
under access cover
10
RFT9709 Transmitter Ins truction Manual
Wiring
continued
Remotely-installed
temperature detector
A temperature signal is transmitted to the RFT9709 from a temperature
detector (RTD) on the flow tube inside the sensor case. This signal is
carried by three wires of the flowmeter cable: the yellow, orange and
violet wires (see Table 2-1, page 13).
To meet API requirements, a user-supplied external temperature
detector can be installed remotely by the user. This external temperature
detector, instead of the RTD inside the sensor, is wired to the RFT9709.
• The external RTD must be accurate to ±0.1°F (±0.05°C).
• RTD calibration information must be configured in the RFT9709.
Requirements for installing a user-supplied external temperature
detector:
• Locate the external temperature detector as close to the sensor as
possible.
• Use an individually shielded 3-wire cable of 22 AWG (0.3 mm²) or
larger wires to connect the external temperature detector to the
flowmeter.
• Wiring diagrams are provided in Figure 2-6, Figure 2-7, and Figure 2-8
on pages 14 through16.
Procedure for installing the user-supplied external temperature
detector:
1. At the sensor junction box, before connecting the flowmeter cable,
identify the yellow, orange and violet wires that come from inside the
sensor.
2. Disconnect these wires from the terminal block, and tie all three
together with a wire nut to protect exposed wire ends.
3. Connect three wires from the external temperature detector to the
terminals, as illustrated in Figure 2-6, Figure 2-7, or Figure 2-8. If the
temperature detector has a fourth wire, it remains unconnected.
4. Make flowmeter cable connections as illustrated in Figure 2-6,
Figure 2-7, or Figure 2-8.
WiringStartupTroubleshootingBefore You BeginMounting
RFT9709 Transmitter Inst ruction Manual
11
Wiring
continued
Cable connections to
sensor and RFT9709
Wiring connections from the sensor to the RFT9709 are made at the
RFT9709 terminals indicated in Figure 2-5. Instructions for wiring the
sensor and transmitter are provided below and on the following pages.
The wiring procedure is the same for the sensor and RFT9709. Refer to
the wiring diagrams on pages 14 through 16, and follow these steps:
1. Insert the stripped ends of the individual wires into the terminal
blocks. No bare wires should remain exposed.
• At the sensor, connect wiring inside the sensor junction box.
• At the RFT9709, connect wiring to the intrinsically safe terminals for
sensor wiring, indicated in Figure 2-5. The flowmeter cable outer
jacket must extend under the RFT9709 wiring terminals access
cover.
• For easier connection of wiring, terminal blocks can be unplugged
from the RFT9709. Two captive screws hold each terminal block in
place.
2. Locate the wires by color as indicated in Table 2-1.
3. Tighten the screws to hold the wires in place.
4. Tightly close all housing covers.
• Tighten the sensor junction-box cover. Tighten all four cover screws.
• Close the RFT9709 sensor-wiring access cover and tighten the
screw that holds it in place.
• If the RFT9709 is installed in a NEMA enclosure, tightly close all
NEMA housing covers.
CAUTION
Exposing the RFT9709 to moisture, or failure to seal
the sensor junction box, could cause a short circuit.
A short circuit would result in measurement error or
flowmeter failure.
To avoid risk of condensation or excessive moisture:
* C ombined drain wires f ro m brown / red, green/white, and gray/blue pairs, and
yellow/orange/violet tr ip let .
**Cut off drain wires and prote ct from shorting to any meta l or te rminals.
WiringStartupTroubleshootingBefore You BeginMounting
RFT9709 Transmitter Inst ruction Manual
13
Wiring
continued
Figure 2-6. Wiring to ELITE® CMF sensors
ELITE® sensor
Green
White
Brown
Violet
Yellow
Orange
terminals
Flowmeter
cable
Maximum cable length 1000 ft. (300 m)
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Prepare cable in accordance with the instructions
that are shipped with the cable
Blue
Gray
Red
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Optional remote temperature detector (RTD) wiring (required for API)
3-wire or 4-wire
RTD
No connection
Violet
Yellow
Orange
ELITE
terminals
®
sensor
Blue
Gray
Red
Green
White
Brown
1. In the sensor junction box, identify the violet, yellow, and
orange wires that come from the sensor.
2. Disconnect these wires from the terminal block, then tie
all three together with a wire nut to protect exposed wire
ends.
3. Connect three wires from the external RTD to the
terminals from Step 2, as illustrated at left. If the RTD has
a fourth wire, it remains unconnected.
Black
(Drains from all
wire sets)
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
RFT9709
terminals
Black (drains)
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
0
1
2
3
4
5
6
7
8
9
14
RFT9709 Transmitter Ins truction Manual
Wiring
continued
Figure 2-7. Wiring to BASIS® F, Model D, and DL sensors
BASIS®, Model D
or DL sensor
terminals
Brown
Red
Orange
Yello w
Green
Blue
Violet
Gray
White
3-wire or 4-wire
Flowmeter
cable
Maximum cable length 1000 ft. (300 m)
Black
(Drains from all
Brown
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
wire sets)
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Optional remote temperature detector (RTD) wiring (required for API)
BASIS®, Model D or DL
sensor terminals
RTD
No connection
D600 sensor
terminals
Brown
RFT9709
terminals
Black (drains)
Red
Orange
Y ellow
Green
Blue
Violet
Gray
White
Brown
Red
Orange
Yellow
Green
Blue
Violet
Gray
White
0
1
2
3
4
5
6
7
8
9
WiringStartupTroubleshootingBefore You BeginMounting
No connection
3-wire or 4-wire
RTD
1. In the sensor junction box, identify the violet, yellow, and orange wires that come from inside the sensor.
2. Disconnect these wires from the terminal block, then tie all three together with a wire nut to protect
exposed wire ends.
3. Connect three wires from the external RTD to the terminals from Step2, as illustrated above. If the RTD
has a fourth wire, it remains unconnected.
RFT9709 Transmitter Inst ruction Manual
15
Loading...
+ 51 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.