Micro Motion Fisher-Rosemount RFT9709 Instruction Manual

Model RFT9709 Transmitter
Instruction Manual
March 1999
Model RFT9709 Transmitter
Instruction Manual
For technical assistance, phone the Micro Motion Customer Service Department:
• Outside the U.S.A., phone 303-530-8400, 24 hours
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155
Copyright ©1999, Micro Motion, Inc. A l l rights reserved.
Micro Motion, ELITE, BASIS and ProLink are registered trademarks of Micro Motion, Inc., Boulder, Colorado. Rosemount and SMART FAMILY are registered trademarks of Rosemount, Inc., Ede n Prai rie, Minnesota. HART is a registered tradem ark of the HART Communication Foundation, Austin, Texas. Modbus is a registered trademark of Modicon, Inc., North Andover, Massachusetts.
Table of Contents
Before You Begin
About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About the transmitter. . . . . . . . . . . . . . . . . . . . . . . . 1
Configuration and calibration . . . . . . . . . . . . . . . . . 1
Proving the Coriolis flowmeter . . . . . . . . . . . . . . . . 2
Step 1 Mounting
1.1 Location requirements. . . . . . . . . . . . . . . . . . . . . . . 3
Hazardous area installations. . . . . . . . . . . . . . . . . . 3
1.2 Mounting options. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Installation in user-supplied enclosure . . . . . . . . . . 4
1.4 Optional NEMA-housing installation . . . . . . . . . . . . 5
Step 2 Wiring
2.1 General guidelines . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Power supply wiring and grounding . . . . . . . . . . . . 8
2.3 Sensor wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Output wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Remotely-installed temperature detector . . . . . . . . 11
Cable connections to sensor and RFT9709 . . . . . . 12
Primary and secondary mA outputs . . . . . . . . . . . . 18
HART multidrop network wiring. . . . . . . . . . . . . . . . 19
RS-485 output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Frequency/pulse output. . . . . . . . . . . . . . . . . . . . . . 21
Control output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
External zero switch wiring . . . . . . . . . . . . . . . . . . . 23
Viscosity measurement or pressure
compensation . . . . . . . . . . . . . . . . . . . . . . . . . . 24
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
3
7
RFT9709 Transmitter Inst ruction Manual
Step 3 Startup
3.1 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.2 Flowmeter zeroing. . . . . . . . . . . . . . . . . . . . . . . . . . 27
Zeroing procedure. . . . . . . . . . . . . . . . . . . . . . . . . . 28
Diagnosing zero failure . . . . . . . . . . . . . . . . . . . . . . 28
3.3 Event registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.4 Totalizer reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.5 Process measurement . . . . . . . . . . . . . . . . . . . . . . 30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
i
Table of Contents
continued
Troubleshooting
4.1 General guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.2 Transmitter diagnostic tools. . . . . . . . . . . . . . . . . . . 32
Diagnostic LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Fault outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.3 Interrogation with the ProLink
Output test and trim . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.4 Power supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.5 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.6 Master reset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.7 Customer service. . . . . . . . . . . . . . . . . . . . . . . . . . . 37
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
®
program . . . . . . . . . 33
Appendixes
Appendix A RFT9709 Specifications . . . . . . . . . . . . . . . . . . 39
Appendix B Ordering Information . . . . . . . . . . . . . . . . . . . . . 45
Appendix C Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . 47
Appendix D Open Collector Configuration . . . . . . . . . . . . . . 53
Appendix E Decontamination and Return Goods
Policy – USA. . . . . . . . . . . . . . . . . . . . . . . . 55
Appendix F Decontamination and Return Goods
Policy – Europe. . . . . . . . . . . . . . . . . . . . . . 57
31
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
59
ii
RFT9709 Transmitter Ins truction Manual
Table of Contents
continued
Tables
Table 2-1 Sensor-wiring terminal designations. . . . . . . . . 13
Table 2-2 Output-wiring terminal designations . . . . . . . . . 17
Table 2-3 Sensors affected by pressure. . . . . . . . . . . . . . 24
Table 3-1 Parameters that affect event registers . . . . . . . 29
Table 4-1 Conditions indicated by diagnostic LED . . . . . . 32
Table 4-2 Normal resistance for flowmeter circuits. . . . . . 36
Table 4-3 Input and output ratings . . . . . . . . . . . . . . . . . . 36
Table 4-4 Default values after a master reset. . . . . . . . . . 38
Table A Performance specifications. . . . . . . . . . . . . . . . 39
Table B RFT9709 model number matrix . . . . . . . . . . . . 45
Table C-1 Communications configuration . . . . . . . . . . . . . 48
Table C-2 Security modes. . . . . . . . . . . . . . . . . . . . . . . . . 49
Figures
RFT9709 components . . . . . . . . . . . . . . . . . . . 2
Figure 1-1 RFT9709 approvals tag . . . . . . . . . . . . . . . . . . 3
Figure 1-2 RFT9709 dimensions . . . . . . . . . . . . . . . . . . . . 4
Figure 1-3 Factory-supplied NEMA-housing dimensions. . 6
Figure 2-1 RFT9709 wiring terminals. . . . . . . . . . . . . . . . . 7
Figure 2-2 Power-supply wiring and grounding
connections . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 2-3 Cable types. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 2-4 Terminating flowmeter cable. . . . . . . . . . . . . . . 10
Figure 2-5 RFT9709 terminals for sensor wiring . . . . . . . . 13
Figure 2-6 Wiring to ELITE Figure 2-7 Wiring to BASIS
DL sensors. . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 2-8 Wiring to Model DT sensors . . . . . . . . . . . . . . . 16
Figure 2-9 Terminating output-wiring shields and drains. . 17
Figure 2-10 mA output terminals . . . . . . . . . . . . . . . . . . . . . 18
Figure 2-11 Typical HART
Figure 2-12 RS-485 wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 2-13 Frequency/pulse output terminals. . . . . . . . . . . 21
Figure 2-14 Control output terminals . . . . . . . . . . . . . . . . . . 22
Figure 2-15 Remote-zero switch wiring . . . . . . . . . . . . . . . . 23
Figure 2-16a Pressure transmitter wiring, internally
powered . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 2-16b Pressure transmitter wiring, externally powered
(multidrop network) . . . . . . . . . . . . . . . . . . 25
Figure 3-1 Diagnostic LED and zero button. . . . . . . . . . . . 27
Figure 4-1 Diagnostic LED. . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 4-2 ProLink
®
PC-Interface connections . . . . . . . . . 34
Figure 4-3 Power-supply wiring and grounding terminals . 35
Figure C-1 Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure C-2 Diagnostic LED and zero button. . . . . . . . . . . . 51
Figure D-1 Configuring open collector mode . . . . . . . . . . . 53
®
CMF sensors . . . . . . . . . . . . 14
®
F, Model D, and
®
network wiring . . . . . . . . . . . . . 19
RFT9709 Transmitter Inst ruction Manual
iii
iv
RFT9709 Transmitter Ins truction Manual
Before You Begin
About this manual
About the transmitter
Configuration and calibration
This instruction manual explains how to install the Micro Motion® Model RFT9709 transmitter for use with Micro Motion Coriolis flow sensors. For more information about the sensor, see the appropriate sensor instruction manual.
CAUTION
Improper installation could cause measurement error or transmitter failure.
For personal and system safety, follow all instructions to ensure transmitter will operate correctly.
The Model RFT9709 transmitter is a microprocessor-based transmitter for fluid process measurement. The transmitter works with Micro Motion sensors to measure mass or volume flow, density, and temperature.
Components of the transmitter are illustrated on the following page.
An RFT9709 transmitter and a sensor are ordered together as a Coriolis flowmeter. The factory can provide any of three standard configuration options:
• Gross volume, API table 5A
• Gross standard volume, API table 5A
• Not configured
Wiring Startup TroubleshootingBefore You Begin Mounting
RFT9709 Transmitter Inst ruction Manual
For specific configuration details, see the calibration certificate that is shipped with the sensor. To meet API requirements, the user must supply an external RTD that is accurate to ±0.1°F. The external RTD calibration must be configured in the transmitter. The factory can configure the transmitter if the RTD calibration is provided.
Changes to the configuration are possible with a custom version of Micro Motion’s ProLink RFT9709.
• The standard ProLink software cannot be used with the RFT9709. Contact the factory for additional ProLink information.
• The Rosemount with the RFT9709.
®
software program, designed specifically for the
®
hand-held HART® Communicator cannot be used
1
Before You Begin
continued
Proving the Coriolis flowmeter
RFT9709 components
Sensor cable
wiring connector
Mounting
boss
Zero button
Proving Micro Motion flowmeters can be accomplished using conventional proving methods. Micro Motion publishes a comprehensive applications manual, which describes in detail how to prove Coriolis meters. For additional information, contact the Micro Motion Customer Service Depa rtment:
• In the U.S.A., phone
1-800-522-MASS
(1-800-522-6277)
• Outside the U.S.A., phone 303-530-8400
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155
Diagnostic LED
Configuration switches
Output wiring connector
Wiring access cover shown open
Mounting boss
Channel for
routing
sensor cable
Slots for cable ti e
16-pin connector for future application
Power-supply wiring ter m in al s
2
RFT9709 Transmitter Ins truction Manual
Installation
Step 1 Mounting
1.1 Location requirements
Hazardous area installations
• Mount the RFT9709 in a user-supplied or factory-supplied NEMA-4 (IP65) enclosure.
• Locate the RFT9709 where it is accessible for service.
• Locate the RFT9709 where the ambient temperature remains between –40 and 122°F (–40 and 50°C).
• Locate the RFT9709 where humidity is less than 90%.
• Total length of cable from the sensor to the RFT9709 must not exceed 1000 feet (300 meters).
• In hazardous areas, install the RFT9709 as described below.
Read the RFT9709 approvals tag before installing the transmitter. The approvals tag is attached to the RFT9709 housing. See Figure 1-1.
WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion.
• Install the RFT9709 in an env iron me nt th at i s c om pat ible with the hazardous area specified on the approvals tag.
• For installations that require intrinsic safety, use this document with Micro Motion UL installation instructions.
Wiring Startup TroubleshootingBefore You Begin Mounting
Figure 1-1. RFT9709 approvals tag
RFT9709 Transmitter Inst ruction Manual
• For a complete list of approvals, see page 4 3.
• For an intrinsically safe or hazardous area installation, use this manual with Micro Motion UL-D-IS Installation Instructions.
Hazardous area approvals
Approvals tag
,
3
Mounting
continued
1.2 Mounting options
1.3 Installation in user­supplied enclosure
Figure 1-2. RFT9709 dimensions
2 15/16
(74)
3 1/4
(83)
inches
(mm)
6 1/8 (156)
5 9/16
(141)
Dimensions in
2X
2X
The RFT9709 has these installation options for mounting on any flat surface:
• For mounting in a user-supplied NEMA-4 (IP65) enclosure
• Pre-installed by the factory in an optional NEMA-4 (IP65) enclosure
• Install the RFT9709 with two screws to a flat mounting surface. Micro Motion does not supply mounting screws.
• Install with wiring terminals facing away from the mounting surface.
• RFT9709 dimensions are provided in Figure 1-2.
1 13/16
(46)
1 11/32
(34)
Mounting boss
2X
Use #8-32 (M4) screws with flat washers and lock washers for mounting
3 5/32
(80)
Minimum
clearance
to open
access cover
5 1/4
(134)
4
Mounting
2X
boss
RFT9709 Transmitter Ins truction Manual
Mounting
continued
1.4 Optional NEMA-housing installation
An optional NEMA-4 (IP65) housing is available from the factory, or the enclosure may be user-supplied.
Factory-supplied housing
If the RFT9709 is ordered with the factory-supplied NEMA-4 (IP65) housing, Micro Motion installs the transmitter in the enclosure.
• Install the NEMA enclosure with four bolts. Micro Motion does not supply mounting bolts.
• Mount to any flat, stable surface.
• NEMA housing dimensions are provided in Figure 1-3, page 6.
User-supplied housing
Any user-supplied NEMA-4 (IP65) enclosure of an appropriate size may be used to house the RFT9709. Dimensions of the RFT9709 are provided in Figure 1-2, page 4.
Conduit openings
Whether the optional NEMA housing is supplied by the user or the factory, the user must add three conduit openings for power-supply wiring, input wiring, and output wiring.
• Locate the housing so these openings are accessible for installation of wiring and so the housing cover can be fully opened for access to the RFT9709 inside.
• To help prevent moisture from entering the housing, install the housing so conduit openings are pointed downward, if possible. To maintain the enclosure’s NEMA rating, all conduit openings must be fully sealed after wiring is installed.
• Recommended size for conduit openings is 3/4-inch (20 mm).
Wiring Startup TroubleshootingBefore You Begin Mounting
CAUTION
Failure to protect the RFT9709 from moisture could cause a short circuit, which would result in measurement error or flowmeter failure.
To avoid risk of condensation of excessive moisture in the NEMA housing:
• Seal all con duit openings.
• Install drip legs in cable or conduit.
• Close and fully tighten all NEMA-housing covers.
RFT9709 Transmitter Inst ruction Manual
5
Mounting
continued
Figure 1-3. Factory-supplied NEMA-housing dimensions
Dimensions in
10 7/16
2X
(266)
Minimum
clearance
to open
access cover
11 7/8
(301)
inches
(mm)
2X
2X
2X
8 7/16
(215)
5 11/16
(145)
7 3/16
(183)
9 11/16
(247)
2X
Cover hinge
0.31
4X Ø
(8)
9 3/16
(234)
7 11/16
(196)
11 11/16
(297)
Mounting feet can be installed in optional orientation as shown
5 5/16
(136)
1/4
2X
(6)
4X 5/16-18 UNC for mounting feet
1 3/8
4X
(35)
flat head screw
(included)
cover-access
2X
screw
Housing requires instal l ati on of three conduit openings for power-supply wiring, input wiring, and output wiring. Recommended opening size: 3/4-inch (20 mm).
6
RFT9709 Transmitter Ins truction Manual
Installation
Step 2 Wiring
2.1 General guidelines
Figure 2-1. RFT9709 wiring terminals
Sensor cable
wiring connector
Figure 2-1 illustrates the locations of the terminals for power-supply wiring, wiring to the sensor, and output wiring.
• Terminal blocks may be unplugged from the RFT9709 (after removing two screws) for easier installation of wiring. Always tighten screws after re-installing terminal blocks.
• Install all conduit, cable and wiring to meet local code requirements.
For an RFT9709 installed in a NEMA enclosure:
• The RFT9709 may be installed in a user-supplied or factory-supplied NEMA-4 (IP65) enclosure, as described in Section 1.4, page 5. The enclosure requires three separate conduit openings for power-supply wiring, sensor wiring, and output wiring.
• Conduit openings must remain sealed to maintain the NEMA-4 (IP65) rating. Use conduit seals or cable glands that provide a complete seal with the conduit openings.
Wiring Startup TroubleshootingBefore You Begin Mounting
Output wiring connector
Wiring access cover shown open
Channel for
routing
sensor cable
Slots for cable tie
RFT9709 Transmitter Inst ruction Manual
16-pin connector for future application
Power-supply wiring ter m in al s
7
Wiring
continued
2.2 Power supply wiring and grounding
For power-supply wiring and grounding, follow these guidelines:
• The RFT9709 requires an 11 to 30 VDC power supply.
• Do not install unfiltered DC power cable in the same conduit or cable tray as sensor cable or output wiring.
• If the sensor installation must comply with UL standards, refer to Micro Motion UL-D-IS Installation Instructions.
• Refer to the wiring diagram presented in Figure 2-2.
WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion.
Po wer-supply wiring is not intrinsically safe.
• Keep power-supply wiring separated from intrinsically safe sensor wiring and outpu t wiring.
• For intrinsically safe sensor installations, use this document with Micro Motion UL installation instructions.
CAUTION
Installation with power supply on could cause transmitter damage or failure.
Turn off power before connecting power supply wiring.
Figure 2-2. Power-supply wiring and grounding connections
#6-32 ground nut
#6-32 ground nut
Mounting boss
If equipment ground is not established via mounting, connect a low-im pedance ground at either ground nut.
11–30 VDC power supply
Terminal Function
If national standards are not in effect , adhere to these standards for ground wiring:
Use copper wire, 14 AWG (2.5 mm²) or lar ger wire size for grounding.
Keep all ground leads as shor t as po ssi ble, less than 1 ohm i m pedance.
Connect power-supply ground lead directly to earth ground , or follow plant standards if a separate high-integrity intrinsically safe ground scheme is used.
23 DC– 24 DC+ 25
8
RFT9709 Transmitter Ins truction Manual
Wiring
continued
2.3 Sensor wiring
The instructions in this section explain how to connect a fully prepared Micro Motion flowmeter cable to the RFT9709 and a sensor. The sensor can be a Model D, DL, DT, ELITE
®
, or BASIS® sensor.
• The procedure for preparing Micro Motion flowmeter cable and cable glands is described in the instructions that are shipped with the cable.
• Install cable and wiring to meet local code requirements.
• Use Micro Motion color-coded cable.
• Total length of cable from the sensor to the RFT9709 must not exceed 1000 feet (300 meters).
WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion.
Sensor wiring is intrinsically safe.
• Keep intrinsically safe sensor wiring separated from power-supply wiring and output wiring.
• For intrinsically safe sensor installations, use this document with Micro Motion UL installation instructions.
CAUTION
Improper installation of cable or conduit could cause inaccurate measurements or flowmeter failure.
Wiring Startup TroubleshootingBefore You Begin Mounting
Keep sensor cable away from devices such as transformers, motors, and power lines, which produce large magnetic fields.
RFT9709 Transmitter Inst ruction Manual
9
Wiring
continued
Cable types
Figure 2-3. Cable types
Micro Motion supplies 9-wire jacketed, shielded, or armored cable, as illustrated in Figure 2-3.
• All cable types are acceptable for cable tray installation.
• All cable types must have the jacket extend under the wiring terminals access cover, as illustrated in Figure 2-4.
• Shielded and armored cable must have the braided shield terminated as illustrated in Figure 2-4.
Jacketed cable
Jacket
Shield e d o r armored cable
Braided shield
Outer jacket
Figure 2-4. Terminating flowmeter cable
Jacket
Mounting boss
Braided shield
For shielded or armored flowmeter cable, connect braided shield at mounting boss
Jacket must extend under access cover
10
RFT9709 Transmitter Ins truction Manual
Wiring
continued
Remotely-installed temperature detector
A temperature signal is transmitted to the RFT9709 from a temperature detector (RTD) on the flow tube inside the sensor case. This signal is carried by three wires of the flowmeter cable: the yellow, orange and violet wires (see Table 2-1, page 13).
To meet API requirements, a user-supplied external temperature detector can be installed remotely by the user. This external temperature detector, instead of the RTD inside the sensor, is wired to the RFT9709.
• The external RTD must be accurate to ±0.1°F (±0.05°C).
• RTD calibration information must be configured in the RFT9709.
Requirements for installing a user-supplied external temperature detector:
• Locate the external temperature detector as close to the sensor as possible.
• Use an individually shielded 3-wire cable of 22 AWG (0.3 mm²) or larger wires to connect the external temperature detector to the flowmeter.
• Wiring diagrams are provided in Figure 2-6, Figure 2-7, and Figure 2-8 on pages 14 through16.
Procedure for installing the user-supplied external temperature detector:
1. At the sensor junction box, before connecting the flowmeter cable,
identify the yellow, orange and violet wires that come from inside the sensor.
2. Disconnect these wires from the terminal block, and tie all three
together with a wire nut to protect exposed wire ends.
3. Connect three wires from the external temperature detector to the
terminals, as illustrated in Figure 2-6, Figure 2-7, or Figure 2-8. If the temperature detector has a fourth wire, it remains unconnected.
4. Make flowmeter cable connections as illustrated in Figure 2-6,
Figure 2-7, or Figure 2-8.
Wiring Startup TroubleshootingBefore You Begin Mounting
RFT9709 Transmitter Inst ruction Manual
11
Wiring
continued
Cable connections to sensor and RFT9709
Wiring connections from the sensor to the RFT9709 are made at the RFT9709 terminals indicated in Figure 2-5. Instructions for wiring the sensor and transmitter are provided below and on the following pages.
The wiring procedure is the same for the sensor and RFT9709. Refer to the wiring diagrams on pages 14 through 16, and follow these steps:
1. Insert the stripped ends of the individual wires into the terminal blocks. No bare wires should remain exposed.
• At the sensor, connect wiring inside the sensor junction box.
• At the RFT9709, connect wiring to the intrinsically safe terminals for
sensor wiring, indicated in Figure 2-5. The flowmeter cable outer jacket must extend under the RFT9709 wiring terminals access cover.
• For easier connection of wiring, terminal blocks can be unplugged
from the RFT9709. Two captive screws hold each terminal block in place.
2. Locate the wires by color as indicated in Table 2-1.
3. Tighten the screws to hold the wires in place.
4. Tightly close all housing covers.
• Tighten the sensor junction-box cover. Tighten all four cover screws.
• Close the RFT9709 sensor-wiring access cover and tighten the
screw that holds it in place.
• If the RFT9709 is installed in a NEMA enclosure, tightly close all
NEMA housing covers.
CAUTION
Exposing the RFT9709 to moisture, or failure to seal the sensor junction box, could cause a short circuit.
A short circuit would result in measurement error or flowmeter failure.
To avoid risk of condensation or excessive moisture:
• Seal all con duit openings.
• Install drip legs in cable or conduit.
• Fully tighten sensor j unction box cover.
• Close and tighten all NEMA housing covers.
12
RFT9709 Transmitter Ins truction Manual
Wiring
continued
Figure 2-5. RFT9709 terminals for sensor wiring
Table 2-1. Sensor-wiring terminal designations
Drain wires
* Drive + Drive –
Temperature –
Temperature return
Left pickoff + Right pickoff + Temperature +
Right pickoff –
Left pickoff –
9 8 7 6 5 4 3 2 1 0
*Combined drain wir es.
Wire color
Black*
Sensor terminal
RFT9709 terminal Function
No connection** 0 Drain wires* Brown11Drive + Red22Drive – Orange 3 3 Temperature – Yellow 4 4 Temperature return Green 5 5 Left pickoff + Blue 6 6 Right pickoff + Violet 7 7 Temperature + Gray 8 8 Right pickoff – White 9 9 Left pickoff –
* C ombined drain wires f ro m brown / red, green/white, and gray/blue pairs, and
yellow/orange/violet tr ip let .
**Cut off drain wires and prote ct from shorting to any meta l or te rminals.
Wiring Startup TroubleshootingBefore You Begin Mounting
RFT9709 Transmitter Inst ruction Manual
13
Wiring
continued
Figure 2-6. Wiring to ELITE® CMF sensors
ELITE® sensor
Green
White
Brown
Violet
Yellow
Orange
terminals
Flowmeter
cable
Maximum cable length 1000 ft. (300 m)
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Prepare cable in accordance with the instructions
that are shipped with the cable
Blue Gray Red
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Optional remote temperature detector (RTD) wiring (required for API)
3-wire or 4-wire
RTD
No connection
Violet
Yellow
Orange
ELITE
terminals
®
sensor
Blue Gray Red
Green White Brown
1. In the sensor junction box, identify the violet, yellow, and orange wires that come from the sensor.
2. Disconnect these wires from the terminal block, then tie all three together with a wire nut to protect exposed wire ends.
3. Connect three wires from the external RTD to the terminals from Step 2, as illustrated at left. If the RTD has a fourth wire, it remains unconnected.
Black (Drains from all wire sets)
Brown Red
Green White
Blue Gray
Orange Violet Yellow
RFT9709
terminals
Black (drains)
Brown
Red
Orange
Yellow Green
Blue
Violet
Gray
White
0 1 2 3 4 5 6 7 8 9
14
RFT9709 Transmitter Ins truction Manual
Wiring
continued
Figure 2-7. Wiring to BASIS® F, Model D, and DL sensors
BASIS®, Model D
or DL sensor
terminals
Brown Red Orange Yello w Green Blue Violet Gray White
3-wire or 4-wire
Flowmeter
cable
Maximum cable length 1000 ft. (300 m)
Black (Drains from all
Brown
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Red
Green
White
Blue Gray
Orange
Violet
Yellow
wire sets)
Brown Red
Green White
Blue Gray
Orange Violet Yellow
Optional remote temperature detector (RTD) wiring (required for API)
BASIS®, Model D or DL
sensor terminals
RTD
No connection
D600 sensor
terminals
Brown
RFT9709
terminals
Black (drains)
Red
Orange
Y ellow
Green
Blue
Violet
Gray
White
Brown
Red
Orange
Yellow Green
Blue
Violet
Gray
White
0 1 2 3 4 5 6 7 8 9
Wiring Startup TroubleshootingBefore You Begin Mounting
No connection
3-wire or 4-wire
RTD
1. In the sensor junction box, identify the violet, yellow, and orange wires that come from inside the sensor.
2. Disconnect these wires from the terminal block, then tie all three together with a wire nut to protect exposed wire ends.
3. Connect three wires from the external RTD to the terminals from Step2, as illustrated above. If the RTD has a fourth wire, it remains unconnected.
RFT9709 Transmitter Inst ruction Manual
15
Loading...
+ 51 hidden pages