Micro Motion Field-Mount Transmitter - Model RFT9739 Manuals & Guides

Model RFT9739 Field-Mount Transmitter
Instruction Manual
Version 3 Transmitters
February 2000
Model RFT9739
Copyright ©2000, Micro Motion, Inc. All rights res erved.
Micro Motion, ELITE, and ProLink are registered trademarks of Micro Motion, Inc., Boulder, Colorado. Rosemount and SMART FAMILY are registered tradema r k s of Rosemount, Inc., Eden Prair i e, Minn eso ta . Fis her -Rosemount is a trademark o f Fisher-Rosemount, C layton, Missouri. HART is a registered trademar k of the HART Communication Foundation, Austin, Texas. Modbus is a registered tra dem ark of Modicon, Inc., North Andover, Massachusetts. Tefzel is a registered trademark of E.I. Du Pont de Nemours Co., Inc., Wilmington, Delaware.
Field-Mount Transmitter
Instruction Manual
Version 3 Transmitters
For technical assistance, phone the Micro Motion Customer Service Department:
• In the U.S.A., phone 1-800-522-6277, 24 hours
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155

Contents

1 Before You Begin
1.1 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 About the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 Getting Started
2.1 Hazardous area installations. . . . . . . . . . . . . . . . . . . . 3
Installations in Europe. . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Configuration, calibration, and characterization . . . . . 4
2.3 Switch settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Security modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Security mode 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Communication settings . . . . . . . . . . . . . . . . . . . . . . . 9
Milliamp output scaling . . . . . . . . . . . . . . . . . . . . . . . . 9
3 Transmitter Mounting
3.1 General guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Mounting to a wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.3 Mounting to an instrument pole. . . . . . . . . . . . . . . . . . 13
4 Power-Supply and Sensor Wiring
4.1 General guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installations in Europe. . . . . . . . . . . . . . . . . . . . . . . . . 17
4.2 Power supply and grounding. . . . . . . . . . . . . . . . . . . . 18
Power-supply options . . . . . . . . . . . . . . . . . . . . . . . . . 18
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3 Sensor wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cable connections to sensor and transmitter . . . . . . . 21
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
1
3
11
15
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
i
Contents
continued
5 Output Wiring
5.1 General guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.2 Maximum wire length. . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.3 Primary and secondary mA outputs. . . . . . . . . . . . . . . 27
Connections for HART
5.4 Frequency/pulse output . . . . . . . . . . . . . . . . . . . . . . . . 30
Default configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Configuration for increased current . . . . . . . . . . . . . . . 31
Configuration for constant current . . . . . . . . . . . . . . . . 32
Configuration for open collector mode. . . . . . . . . . . . . 33
5.5 Control output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Control output in open collector mode . . . . . . . . . . . . . 36
5.6 Peripheral device wiring. . . . . . . . . . . . . . . . . . . . . . . . 38
5.7 Pressure transmitter wiring . . . . . . . . . . . . . . . . . . . . . 44
5.8 Remote-zero switch . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.9 RS-485 multidrop network . . . . . . . . . . . . . . . . . . . . . . 47
5.10 Bell 202 multidrop network. . . . . . . . . . . . . . . . . . . . . . 48
6Startup
6.1 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.2 Using the optional display . . . . . . . . . . . . . . . . . . . . . . 51
6.3 Custody transfer event registers . . . . . . . . . . . . . . . . . 56
6.4 Flowmeter zeroing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.5 Totalizer control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
6.6 Process measurement. . . . . . . . . . . . . . . . . . . . . . . . . 61
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initialization with display. . . . . . . . . . . . . . . . . . . . . . . . 51
Adjusting the sight window. . . . . . . . . . . . . . . . . . . . . . 52
Process variables mode. . . . . . . . . . . . . . . . . . . . . . . . 52
Communication configuration mode . . . . . . . . . . . . . . 54
Zeroing procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Diagnosing zero failure . . . . . . . . . . . . . . . . . . . . . . . . 59
Additional information about flowmeter zeroing. . . . . . 59
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
®
communication devices. . . . . 29
25
51
ii
RFT9739 Field-Mou nt Tra nsm i t t er Instruction Manual
Contents
continued
7 Troubleshooting
7.1 General guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
7.2 Transmitter diagnostic tools. . . . . . . . . . . . . . . . . . . . . 64
Diagnostic LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Fault outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Diagnostic messages . . . . . . . . . . . . . . . . . . . . . . . . . 65
7.3 Interrogation with a HART
7.4 Troubleshooting using the transmitter display. . . . . . . 68
Not configured. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Transmitter failure messages . . . . . . . . . . . . . . . . . . . 68
Overrange and sensor error messages. . . . . . . . . . . . 69
Slug flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Output saturated messages . . . . . . . . . . . . . . . . . . . . 69
Informational messages . . . . . . . . . . . . . . . . . . . . . . . 71
7.5 Power supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
7.6 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
7.7 Master reset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.8 Additional information about troubleshooting . . . . . . . 76
7.9 Customer service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
®
device . . . . . . . . . . . . . . . 66
Appendixes
Appendix A RFT9739 Specifications . . . . . . . . . . . . . . . . . . 77
Appendix B Ordering Information. . . . . . . . . . . . . . . . . . . . . 85
Appendix C Theory of Operation . . . . . . . . . . . . . . . . . . . . . 87
Appendix D HART
Appendix E Label Maintenance and Replacement . . . . . . . 95
Appendix F Transmitter Version Identification. . . . . . . . . . . 97
Appendix G Replacing Older Transmitters. . . . . . . . . . . . . . 99
Appendix H Return Policy . . . . . . . . . . . . . . . . . . . . . . . . . . 105
®
Communicator Menu Trees. . . . . . . . . 91
63
Index
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
107
iii
Contents
continued
Tables
Table 2-1 Security modes . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 2-2 Communications configuration . . . . . . . . . . . . . 10
Table 4-1 Terminal designations . . . . . . . . . . . . . . . . . . . . 22
Table 5-1 Output wiring terminal designations . . . . . . . . . 26
Table 5-2 Peripheral wiring diagrams . . . . . . . . . . . . . . . . 38
Table 5-3 Sensors affected by pressure . . . . . . . . . . . . . . 44
Table 6-1 Display screens. . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 6-2 Parameters that affect event registers . . . . . . . 56
Table 6-3 Effect of security modes on flowmeter zeroing . 59 Table 6-4 Effect of security modes on totalizer control . . . 60
Table 7-1 Conditions indicated by diagnostic LED . . . . . . 64
Table 7-2 Fault output levels. . . . . . . . . . . . . . . . . . . . . . . 65
Table 7-3 Using transmitter failure messages. . . . . . . . . . 68
Table 7-4 Using overrange and sensor error messages. . 70 Table 7-5 Using slug flow and output saturated messages 70
Table 7-6 Using informational messages . . . . . . . . . . . . . 72
Table 7-7 Normal resistance for flowmeter circuits . . . . . . 73
Table 7-8 Default values after a master reset . . . . . . . . . . 75
Tables in appendixes
Table G-1 Resistance values for determining RTD type . . 100
Table G-2 RE-01 to RFT9739 terminal conversions . . . . . 102
Table G-3 RFT9712 to RFT9739 terminal conversions . . . 103
iv
RFT9739 Field-Mou nt Tra nsm i t t er Instruction Manual
Contents
continued
Figures
Figure 1-1 RFT9739 exploded view. . . . . . . . . . . . . . . . . . 2
Figure 2-1 Hazardous area approvals tag . . . . . . . . . . . . . 3
Figure 2-2 Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 3-1 RFT9739 dimensions . . . . . . . . . . . . . . . . . . . . 12
Figure 3-2 Instrument-pole mounting. . . . . . . . . . . . . . . . . 13
Figure 4-1 RFT9739 exploded view. . . . . . . . . . . . . . . . . . 16
Figure 4-2 Lockout clamp for CENELEC transmitters . . . . 17
Figure 4-3 Power-supply wiring terminals . . . . . . . . . . . . . 19
Figure 4-4a Grounding detail — typical . . . . . . . . . . . . . . . . 20
Figure 4-4b Grounding detail — European installations . . . 20 Figure 4-5 Wiring to ELITE Figure 4-6 Wiring to F-Series, Model D, and DL sensors . 23
Figure 4-7 Wiring to Model DT sensors . . . . . . . . . . . . . . . 23
Figure 5-1 Output terminals . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 5-2 4-20 mA output performance . . . . . . . . . . . . . . 27
Figure 5-3 Primary and secondary mA output wiring. . . . . 28
Figure 5-4 HART
®
Communicator, ProLink® PC-Interface,
and AMS modem connections . . . . . . . . . . 29
Figure 5-5 Frequency/pulse output wiring . . . . . . . . . . . . . 31
Figure 5-6 Frequency/pulse output wiring for increased
current . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 5-7 Frequency/pulse output wiring for constant
current . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 5-8 Frequency/pulse output wiring for open
collector mode . . . . . . . . . . . . . . . . . . . . . . 34
Figure 5-9 Location of resistor R14 (R1) on output board . 34
Figure 5-10 Control output wiring. . . . . . . . . . . . . . . . . . . . . 35
Figure 5-11 Control output wiring for open collector mode . 37 Figure 5-12 Location of resistor R15 (R2) on output board . 37
Figure 5-13 Wiring to DMS. . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 5-14a Wiring to DRT with LED . . . . . . . . . . . . . . . . . . 39
Figure 5-14b Wiring to DRT with LCD . . . . . . . . . . . . . . . . . . 39
Figure 5-15a Wiring to FMS-3 with LED . . . . . . . . . . . . . . . . 40
Figure 5-15b Wiring to FMS-3 with LCD . . . . . . . . . . . . . . . . 40
Figure 5-16 Wiring to NFC . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 5-17a Wiring to AC-powered NOC . . . . . . . . . . . . . . . 42
Figure 5-17b Wiring to DC-powered NOC . . . . . . . . . . . . . . . 42
Figure 5-18a Wiring to Model 3300 with screw-type or
solder-tail terminals . . . . . . . . . . . . . . . . . . 43
Figure 5-18b Wiring to Model 3300 with I/O cable. . . . . . . . . 43
Figure 5-19 Wiring to Model 3350 . . . . . . . . . . . . . . . . . . . . 43
Figure 5-20a Wiring to pressure transmitter — analog input . 45 Figure 5-20b Wiring to pressure transmitter — external
power, analog input . . . . . . . . . . . . . . . . . . 45
Figure 5-20c Wiring to pressure transmitter — digital
communications . . . . . . . . . . . . . . . . . . . . . 46
Figure 5-21 Wiring to remote-zero switch . . . . . . . . . . . . . . 46
Figure 5-22 RS-485 wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 5-23 Typical HART
Figure 6-1 Diagnostic LED and zero button. . . . . . . . . . . . 58
®
CMF sensors . . . . . . . . . . . . 22
®
network wiring . . . . . . . . . . . . . 49
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
v
Contents
continued
Figure 7-1 Diagnostic LED and communicator loops . . . . . 64
Figure 7-2 HART
®
Communicator, ProLink® PC-Interface,
and AMS modem connections . . . . . . . . . . 67
Figures in appendixes
Figure C-1 Coriolis mass flow sensor . . . . . . . . . . . . . . . . . 87
Figure D-1 On-line menu. . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Figure E-1 Label number 3002168 . . . . . . . . . . . . . . . . . . . 95
Figure F-1 Switches on RFT9739 transmitters. . . . . . . . . . 97
Figure G-1 RFT9739 terminals . . . . . . . . . . . . . . . . . . . . . . 101
Figure G-2 RE-01 Remote Electronics Unit terminals. . . . . 102
Figure G-3 RFT9712 Remote Flow Transmitter terminals . 103
vi
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual

1 Before You Begin

1.1 About this manual

1.2 About the transmitter

This instruction manual explains how to:
• Install the Micro Motion use with Micro Motion Coriolis flow sensors, including instructions for:
-
Transmitter mounting
-
Power-supply, sensor, and output wiring
• Initialize the transmitter
• Diagnose and troubleshoot problems with the transmitter
For information about Micro Motion sensors, see the appropriate sensor instruction manuals.
Instructions in this manual pertain to Version 3 transmitters. Do not use this manual for transmitters shipped before January 1996. To identify the transmitter version, see
Micro Motion sensors and transmitters with enhanced EMI immunity comply with EMC directive 89/336/EEC and low-voltage directive 73/23/EEC, when properly installed in accordance with the guidelines and instructions in this manual.
The Model RFT9739 transmitter is a microprocessor-based transmitter for fluid process measurement. The transmitter works with Micro Motion sensors to measure mass or volume flow, density, and temperature.
An optional display is available, and comes installed on the removable housing cover. Scroll and Reset knobs on the cover enable the user to perform the following operations (see
• View flow rate, density, temperature, mass and volume totals and inventory levels, and status messages
• Set the transmitter's flow totalizers
• Reset communication paramete rs
• Zero the flowmeter
®
Model RFT9739 field-mount transmitter for
Appendix F
, page 97.
Section 6.2
, page 51):
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
Components of the transmitter are shown in
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Figure 1-1
, page 2.
1
continued
Before You Begin
Figure 1-1. RFT9739 exploded view
Removable cover
of housing
Hinged cover of
electronics module
Diagnostic LED
Electronics modu le
Intrinsically safe
terminals for wiring
to sensor
Partition (safety barrier)
Must be in place during
operation of transmitter
Housing base
Switches 1 through 10
Zero button
Non-intrinsically safe output termina l s
Power-supply wiring and equipment ground terminals
2
RFT9739 Field-Mou nt Tra nsm i t t er Instruction Manual

2 Getting Started

Hazardous area approvals tag

2.1 Hazardous area installations

WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion.
• Install the transmitter in an environment that is compatible with the hazardous area specified on the approvals tag. See
• For intrinsically safe inst allati ons , use this docu me nt with Micro Motion UL, CSA, or SAA installation instructions.
• For hazardous area installations in Europe, refer to standard EN 60079-14 if nation al standards do not apply.
• Read the approvals tag before installing the RFT9739. The approvals tag is attached to the transmitter housing. See
• For a complete list of UL, CSA, SAA, and European approvals, see page 82.
• For intrinsically safe installations, use this manual with the appropriate Micro Motion intrinsically safe installation instructions:
-
UL-D-IS Installation Instructions
-
CSA-D-IS Installation Instructions
-
SAA-D-IS Installation Instructions
• In Europe, refer to standard EN60079-14 if national standards do not apply. To comply with CENELEC standards, see page 4.
Figure 2-1
.
Figure 2-1
.
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
Figure 2-1. Hazardous area approvals tag
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
3
Getting Started
continued

Installations in Europe

2.2 Configuration, calibration, and characterization

To comply with CENELEC standards for hazardous area installations in Europe, adhere to the following CENELEC conditions for safe use.
Cable glands and conduit seals
• Use 3/4"-14 NPT cable glands or conduit fittings, rated flameproof for EEx d IIC areas and certified by an authorized test station. Flameproof glands supplied by Micro Motion meet these requirements.
• Conduit openings that are not used should be sealed with blanking plugs of type PLG 2.
• For installation in a nonhazardous area, cable glands or conduit fittings that do not carry a flameproof rating are acceptable.
Potential equalization
To achiev e potential equalization, the RFT9739 ground conductor should be connected to the appropriate ground terminals within the hazardous area, using a potential equalizing line.
Output wiring
Nonintrinsically-safe connections between the RFT9739 and other devices may be made or equal to 250 V.
The following information explains the differences among configuration, calibration, and characterization. Certain parameters might require
configuration
even when
only
to devices that maintain a voltage less than
calibration
is not necessary.
Configuration parameters
measurement units, flow direction, damping values, slug flow parameters, and span values for the milliamp and frequency outputs. If requested at time of order, the transmitter is configured at the factory according to customer specifications.
Calibration
density, and temperature. Field calibration is optional.
Characterization
density, and temperature directly into transmitter memory. Calibration factors can be found on the sensor serial number tag and on the certificate that is shipped with the sensor.
For configuration, calibration, or characterization procedures, see one of the following communications manuals:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
You can also use Fisher-Rosemount™ Asset Management Solutions (AMS) software for configuration, calibration, and characterization. For more information, see the AMS on-line help.
A basic software tree for the HART Communicator is shown in
Appendix D
accounts for an individual sensor’s sensitivity to flow,
is the process of entering calibration factors for flow,
, page 91.
include items such as flowmeter tag,
4
RFT9739 Field-Mou nt Tra nsm i t t er Instruction Manual
Getting Started
continued

2.3 Switch settings

Security modes

Switches 1 through 10 on the electronics module control the following transmitter functions:
• Baud rate
• Stop bits and parity
• Data bits, communication protocol, and physical layer
• mA outputs
• Zeroing method
• Write-protection of transmitter configuration Switches 1 through 10 are illustrated in
Figure 2-2
, and described in the
following sections. Normally, switch settings do not require adjustment.
Switches 1, 2, and 3 are security switches, which enable the user to disable flowmeter zeroing, disable resetting of totalizers, and write­protect all configuration and calibration parameters.
Switch settings enable any of eight possible security modes. Different modes determine which functions are disabled and whether configuration and calibration parameters are write-protected. The following functions can be disabled:
• Flowmeter zeroing using digital communications
• Flowmeter zeroing using the zero button and, if the transmitter has a display, the Scroll and Reset knobs
• Totalizer reset, with flow, using digital communications
• Totalizer reset, with flow, using the Scroll and Reset knobs, if the transmitter has a display
• Totalizer control, with zero flow, using digital communications
• Totalizer control, with zero flow, using the Scroll and Reset knobs, if the transmitter has a display
• Ability to change configuration or calibration factors
Pow er-Supply and
Sensor Wiring
Table 2-1
are disabled for each security mode. Security modes 1 through 7 are entered immediately when switches 1 through 3 are set.
For information about security mode 8, see pages 6 through 8.
Figure 2-2. Switches
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
lists the parameters that are write-protected and functions that
Switches 1 through 10 at left are shown in the OFF position.
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
5
continued
Getting Started
Table 2-1. Security modes
Switch settings
Switch 1 Switch 2 Switch 3
Function/ parameter
Flowmeter zeroing
Totalize r control, no flow
Totalize r control, with flow
Configuration and calibration parameters
* C hanging the settings of switches 1, 2, and 3 does not immediately impl em ent security mode 8. For more information about
security mode 8, see pages 6 through 8.
Performed with
Zero but t on or Reset knob
HART or Modbus
Scroll and Reset knobs
HART or Modbus
Scroll and Reset knobs
HART or Modbus
Mode
1
OFF OFF OFF
Mode
1
Mode
2
OFF OFF
ON
Mode
2
Disabled Disabled Disabled Disabled Disabled Disabled Disabled
Disabled Disabled Disabled Disabled
Disabled Disabled Disabled Disabled Disabled Disabled Disabled
Mode
3
OFF
ON
OFF
Mode
3
Disabled Disabled Disabled Disabled
Disabled Disabled Disabled
Disabled Disabled Disabled Disabled Disabled Disabled
Write-
protected
Mode
4
OFF
ON ON
Mode
4
Write-
protected
Mode
5
ON OFF OFF
Mode
5
Write-
protected
Mode
6
ON
OFF
ON
Mode
6
Write-
protected
Mode
7
ON ON
OFF
Mode
7
Write-
protected
Mode
8*
ON ON ON
Mode
8
Write-
protected

Security mode 8

When transmitter security is set for mode 8, the transmitter meets security requirements for custody transfer described in National Institute of Standards and Technology (NIST) Handbook 44.
Once the transmitter is configured for security mode 8, the security mode cannot be changed unless a master reset is performed. A master reset causes all configuration parameters to return to their default values, and
requires complete characterization and reconfiguration
of the trans m i tt e r.
If the user attempts to enter a new security mode or change the transmitter configuration after entering security mode 8:
• Internal totalizers stop counting
• The frequency/pulse output goes to 0 Hz
• mA outputs go to 4 mA
• The optional display reads, "SECURITY BREACH; SENSOR OK"
• Custody transfer event registers record changes made to defined configuration and calibration parameters. (For a list of these parameters, see
Table 6-2
, page 56.)
The security breach continues, and totalizers and outputs remain inactive, until the transmitter is reconfigured for security mode 8, or until a master reset has been performed. Custody transfer ev ent registers are not affected by a master reset.
• For information about event registers, see
• To perform a master reset, see instructions in
Section 6.3
Section 7.7
, page 56.
, page 74.
6
RFT9739 Field-Mou nt Tra nsm i t t er Instruction Manual
Getting Started
continued
Milliamp output trim, milliamp output test, and frequency/pulse output test procedures cannot be performed after security mode 8 is entered.
Before entering security mode 8,
perform milliamp trim and/or test procedures, if necessary , as described in any of the following manuals or in AMS on-line help:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
To enter security mode 8:
1. Note the position of switch 5.
2. Set switch 10 to the ON position. The diagnostic LED on the
transmitter electronics module flashes on 3 times and pauses, which indicates the transmitter is in the configuration mode.
3. Set switches 1, 2, and 3 to the ON position.
4. Set switches 4, 5, and 6 to the OFF position.
5. Locate the ZERO button on the transmitter electronics module.
6. Press and hold the ZERO button for five seconds. The diagnostic LED
will remain on for two to three seconds to indicate security mode 8 has been entered.
7. Reset switch 5 to the desired position (as noted in Step 1).
8. Reset switch 10 to the OFF (OPERATE) position. The diagnostic LED
flashes on once per second (25% on, 75% off), which indicates the transmitter is in the normal operating mode.
9. Leave switches 1, 2, and 3 in the ON position to remain in security
mode 8.
Pow er-Supply and
Sensor Wiring
To verify the transmitter is in security mode 8:
• If the transmitter has a display, use the Scroll knob to scroll through
process variable screens to event register screens. If event register screens appear, the transmitter is in security mode 8. For more information about using the Scroll knob and transmitter display, see
Section 6.2
, page 51.
• If the transmitter does not have a display:
1. Configure the transmitter.
2. Wait until the diagnostic LED blinks ON once per second.
3. Move switch 1, 2, or 3 to the OFF position.
4. If the diagnostic LED blinks ON 4 times per second, the transmitter is in security mode 8.
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
7
Getting Started
continued
To make changes to configuration or calibration parameters once security mode 8 is entered:
1. Set switches 1, 2, and 3 to the OFF position.
2. Make changes through digital communication or, if the transmitter has a display, with the Scroll and Reset knobs (see "Communication configuration mode," page 54). Custody transfer event registers record changes made to defined configuration and calibration parameters (see
Table 6-2
, page 56). For more information about digital com m uni cati ons , see th e following ins truc tion m an ual s or AM S on-line help:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
3. Set switches 1, 2, and 3 to the ON position.
To reenter security mode 8:
If security mode 8 has been established previously, and the security mode has been temporarily changed, it is not necessary to use the ZERO button to reenter security mode 8. In such a case, resetting switches 1, 2, and 3 to the ON position will reenter security mode 8 immediately.
If a master reset has been performed, it is necessary to use the ZERO button method to reenter security mode 8. See procedure, page 7.
To change from security mode 8 to another security mode:
1. Perform a master reset (see
Section 7.7
, page 74, for master reset
procedure).
2. Perform characterization and reconfiguration procedures as described in any of the following instruction manuals:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
3. Set switches 1, 2, and 3 to the desired positions (see
Table 2-1
,
page 6).
8
RFT9739 Field-Mou nt Tra nsm i t t er Instruction Manual
Getting Started
continued

Communication settings

Switch 5 enables the user to choose the standard communication configuration or user-defined parameters. With switch 10 in the ON (CONFIG) position, switches 1 through 6 can be used for setting user­defined communication parameters.
Standard communication setting
To use the standard communication configuration, set switch 5 to the STD COMM position. Setting the switch in this position establishes the following communication parameters:
• HART protocol on the Bell 202 standard, at 1200 baud, on the primary mA output
• Modbus protocol in RTU mode, at 9600 baud, on the RS-485 output
• 1 stop bit, odd parity
For RFT9739 software versions 3.6 and later, if switch 5 is in the STD COMM position, and the RFT9739 has a display, an error message will appear on the display when an attempt is made to change the communication configuration using the RFT9739 display controls.
User-defined communication settings
To establish user-defined settings, set switches as instructed in
Table 2-2
, page 10. With switches 1 through 6, the user can set baud rate; stop bits and parity; data bits, protocol, and physical layer. The default settings are HART protocol, over RS-485, at 1200 baud, with 1 stop bit and odd parity.
Pow er-Supply and
Sensor Wiring

Milliamp output scaling

Switches 7, 8, and 9 allow the user to choose 0-20 mA or 4-20 mA scaling for mA outputs, and upscale or downscale fault outputs.
Switch 7 defines the primary mA output scaling. Switch 8 defines the secondary mA output scaling. Either switch may be set in the 0-20 position or the 4-20 position.
• The mA outputs are NAMUR compliant when switches 7 and 8 are in
the 4-20 position. See
Section 5.3
, page 27.
• Communication using the HART protocol over the primary mA output
requires switch 7 to be set in the 4-20 position.
• If switch 7 is in the 0-20 mA position, communication may be lost if
output is less than 2 mA. T o re-establish communication, move s witch 7 to the 4-20mA position.
Switch 9 defines the RFT9739 fault outputs. Fault outputs can be set for downscale or upscale levels.
• If switch 9 is set to the DWNSCALE position, mA outputs go to 0 mA if
they produce a 0-20 mA current, or to 0-2 mA if they produce a 4-20 mA current; the frequency/pulse output goes to 0 Hz.
• If switch 9 is set to the UPSCALE position, mA outputs go to 22-24 mA;
the frequency/pulse output goes to 15-19 kHz.
• For more information, see "Fault outputs," page 65.
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
9
continued
Getting Started
Table 2-2. Communications configuration
Instructions
Before beginning, make note of the positions of switches 1, 2, and 3. Then, for each setting:
1. Begin with switch 10 in the CONFIG position, and switches 1 through 6 in the OFF position. The LED flashes ON 3 times and pauses, which indicates th e transm i t te r is i n th e communication configuration mo de.
2. Set designated switches to the ON position as indicated below.
3. Press and hold the ZERO button for five seconds, until the LED remains ON for 3 seconds, which indicates the setting ha s been accepted by the transmitter.
When done:
1. Reset switches 1, 2, and 3 to the appropriate positions.
2. Set switch 5 to the USER DEFINED position.
3. Set switches 4 and 6 to the OFF position.
4. Set switch 10 to the OPERATE position.
Note
If switches 4, 5, 6, and 10 are left in the ON position after configuration, a master reset will occur the next time power to the transmitter is shut off and the n re st or ed. To avoid an unexpected mast er reset, make sure switches 4, 6, and 10 are left in the OFF position after con fig urati on.
Baud rate
1200 baud ON ON 2400 baud ON ON ON 4800 baud ON ON 9600 baud ON ON ON 19,200 baud ON ON ON 38,400 baud ON ON
Stop bits and parity
1 stop bit, no parity ON 1 stop bit, odd parity ON ON 1 stop bit, even parity ON ON ON 2 stop bits, no parity ON ON 2 stop bits, odd parity ON ON ON 2 stop bits, even parity ON ON
Data bits, protocol, physical layer
HART on primary mA ON ON ON ON HART on RS-485 ON ON ON Modbus RTU mode (8 bits) on RS-485 ON ON Modbus ASCII mode (7 bits) on RS-485 ON ON ON Modbus RTU mode (8 bits) on RS-485
and HART on primary mA Modbus ASCII mode (7 bits) on RS-485
and HART on primary mA
Switch
1
Switch
1
Switch
1
ON ON ON
ON ON ON ON
Switch
2
Switch
2
Switch
2
Switch
3
Switch
3
Switch
3
Switch
4
Switch
4
Switch
4
Switch
5
Switch
5
Switch
5
Switch
6
Switch
6
Switch
6
10
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual

3 Transmitter Mounting

3.1 General guidelines

Follow these guidelines when installing the field-mount RFT9739 transmitter:
• Locate the transmitter where it is accessible for service and calibration.
• In hazardous areas, install the transmitter in a location that is specified
Section 2.1
in
• Total length of cable from the sensor to the transmitter must not exceed 1000 feet (300 meters).
• Locate the transmitter where the ambient temperature remains between –22 and 131°F (–30 and 55°C). If the transmitter has a display, the display might become difficult to read below 14°F (–10°C).
• Mount the transmitter to a stable, flat surface or instrument pole.
• The cover of the transmitter housing requires 11½ inches (292 mm) clearance for removal. If the transmitter has a display, the cover requires 13 3/16 inches (335 mm) clearance.
The base of the transmitter has three ¾-inch NPT female conduit openings (see keep the transmitter watertight.
, page 3.
Figure 3-1
, next page), which must remain sealed to
CAUTION
Failure to seal transmitter housing could cause a short circuit, which w ould result i n measuremen t err or or flowmeter failure.
Pow er-Supply and
Sensor Wiring
To avoid risk of condensation or excessive moisture entering the transmitter housing, fully seal all conduit openings when installing the transmitter.
• Install conduit that allows a complete seal with the conduit openings.
• If possible, orient the transmitter with its conduit openings pointed downward. If this is not possible, seal the conduit to prevent condensation and other moisture from entering the housing.
• To comply with CENELEC standards for hazardous area installations in Europe:
-
Use cable glands or conduit fittings rated flameproof for EEx d IIC areas and certified by an authorized test station. Flameproof glands supplied by Micro Motion meet these requirements.
-
Conduit openings that are not used should be sealed with blanking plugs of type PLG 2.
-
For installation in a nonhazardous area, cable glands or conduit fittings that do not carry a flameproof rating are acceptable.
• If the transmitter has a display, the display will be right-side-up only if the transmitter is oriented with its conduit openings pointed downward.
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
11
Transmitter Mounting
continued

3.2 Mounting to a wall

Figure 3-1. RFT9739 dimensions
4X Ø
inches
(mm)
2 13/16
(71)
23/64
(9)
Dimensions in
Follow these guidelines and refer to
Figure 3-1
to mount the transmitter
to a wall or other flat, rigid surface.
• Use four 5/16-inch diameter (or M8) bolts and nuts to mount the transmitter to a wall or other flat, rigid surface. Use bolts and nuts that can withstand the process environment. Micro Motion does not supply bolts or nuts (such bolts and nuts are available as an option).
• To minimize stress on the housing, secure all four mounting bolts to the same structure, which should be flat and should not vibrate or move excessively. Do not secure bolts to separate girders, beams, or wall studs, which can move independently.
7 19/64
(185)
Optional
display
8 3/8
9 11/64
(213)
4 33/64
(115)
(233)
Sensor cable
conduit opening
3/16
(5)
7 15/64
(184)
2 3/8
(60)
2 3/8
(60)
Power-supply wiring conduit opening
Output wiring conduit opening
3x
3/4"-14 NPT conduit opening
1 17/32
(39)
9 1/8
(232)
Removal of cover required for access to wiring compartments
With
display
13 3/16
(335)
Without
display
11 1/2
(292)
12
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Transmitter Mounting
continued

3.3 Mounting to an instrument pole

Figure 3-2. Instrument-pole mounting
Dimensions in
inches
(mm)
4X
5/16
(8)
2X
2 13/16
(71)
Follow these guidelines and refer to
Figure 3-2
to mount the transmitter
to an instrument pole:
• Use two 5/16-inch U-bolts for 2-inch pipe, and four matching nuts, to mount the transmitter to a rigid instrument pole. Use U-bolts and nuts that can withstand the process environment. Micro Motion does not supply U-bolts or nuts.
• The instrument pole should extend at least 12 inches (305 mm) from a rigid base, and be no more than 2 inches (50.8 mm) in diameter.
2-inch pipe
Pow er-Supply and
Sensor Wiring
2X
8 3/8 (213)
Output wiring
conduit
Sensor cable wiring conduit
Power-supply wiring conduit
5/16"-18 U-bolt
2X
for 2-inch pipe
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
13
14
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
4 Power-Supply and Sensor
Wiring

4.1 General guidelines

WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion.
Sensor wiring is intrinsically safe.
• Keep intrinsically safe sensor wiring separated from power-supply wiring and output wiring.
• For intrinsically safe sensor inst allations, use this document with Micro Motion UL, CSA, or SAA installat ion instructions.
• For hazardous area installations in Europe, refer to standard EN 60079-14 if nation al standards do not apply.
• Make sure the safety barrier partition is in place before operating the transmitter.
CAUTION
Failure to seal transmitter housing and sensor junction box could cause a short circuit, which would result in measurement error or flowmeter failure.
To avoid risk of condensation or excessive moisture in the junction box or transmitter housing:
• Seal all conduit openings.
• Install drip legs in cable or conduit.
• Ensure integrity of gaskets and O-rings, and fully tighten all covers.
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
A removable partition on the electronics module keeps intrinsically safe wiring to the sensor separated from nonintrinsically safe output wiring. The module has a hinged, clear plastic cover. To access power-supply wiring terminals, unlatch the cover of the module, then remove the partition.
Figure 4-1
• the sensor, output wiring terminals, and power-supply wiring terminals.
• Terminal blocks may be unplugged from the module for easier installation of wiring.
• Install cable and wiring to meet local code requirements.
• A switch may be installed in the power-supply line. For compliance with low-voltage directive 73/23/EEC, a switch in close proximity to the transmitter is required for AC-powered transmitters.
• Do not install AC power cable or unfiltered DC power cable in the same conduit or cable tray as sensor cable or output wiring.
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
, page 16, shows the locations of the terminals for wiring to
15
continued
Power-Supply and Sensor Wiring
Figure 4-1. RFT9739 exploded view
Hinged cover of
electronics module
The base of the transmitter has three ¾-inch NPT female conduit openings, indicated in
Figure 4-1
, which must rem ain seal ed to k eep the
transmitter watertight.
• Use conduit that allows a complete seal with the conduit openings.
• If possible, orient the transmitter with its conduit openings pointed downward. Seal the conduit to prevent condensation and other moisture from entering the housing.
• To comply with requirements for explosion-proof installations approved by UL or CSA, install approved explosion-proof conduit seals on all three conduit openings.
• To comply with CENELEC requirements for installations in Europe, see page 17.
Intrinsically safe
terminals for wiring
to sensor
Partition (safety barrier)
Must be in place during
operation of transmitter
Housing base
Sensor wiring
conduit opening
Power-supply
conduit opening
Electronics module
Non-intrinsically safe output terminals
Power-supply wiring and equipment ground terminals
Output wiring conduit opening
16
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Power-Supply and Sensor Wiring
Housing cover
Lip
Clamp
Mounting screw
Cap
Threaded hole
Housing base
continued

Installations in Europe

Figure 4-2. Lockout clamp for CENELEC transmitters
To comply with CENELEC standards for hazardous area installations in Europe, adhere to the following CENELEC conditions for safe use:
• Use 3/4"-14 NPT cable glands or conduit fittings, rated flameproof for EEx d IIC areas and certified by an authorized test station. Flameproof glands supplied by Micro Motion meet these requirements.
• Conduit openings that are not used should be sealed with blanking plugs of type PLG 2.
• For installation in a nonhazardous area, cable glands or conduit fittings that do not carry a flameproof rating are acceptable.
A CENELEC-compliant RFT9739 includes a lockout clamp on the transmitter housing. See
Figure 4-2
. The clamp adds secondary protection against accessing the power-supply terminals, and is required to meet CENELEC standards.
Pow er-Supply and
Sensor Wiring
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
17
Power-Supply and Sensor Wiring
continued

4.2 Power supply and grounding

Power-supply options

Wiring

CAUTION
Incorrect vol tage, or install ation with po wer s upply on, will cause transmitter damage or failure.
• Turn off power before installing transmitter.
• Match power-supply voltage with voltage indicated in transmitter power terminals compartment.
The AC transmitter accepts an 85 to 250 VAC power supply. The DC transmitter accepts a 12 to 30 VDC power supply.
• A label inside the power-supply wiring compartment indicates the correct power-supply voltage.
Figure 4-3
• terminals in the base of the transmitter housing.
• A lockout clamp on the transmitter housing (see provides secondary protection against accessing the power-supply terminals, and is required by CENELEC.
To install power-supply wiring, follow these steps:
1. To access power-supply wiring, unlatch the hinged cover of the
module, then remove the partition that separates intrinsically safe sensor wiring from non-intrinsically safe output wiring.
2. Make input power connections at the two labeled terminals, as
indicated in labeled as follows:
• If the terminals are labeled "L" (line) and "N" (neutral), install an 85 to 250 VAC power supply.
• If the terminals are labeled "+" (positive) and "–" (negative), install a 12 to 30 VDC power supply.
3. Ground the transmitter as instructed on page 19.
(next page) shows the location of power-supply wiring
Figure 4-3
Figure 4-2
(next page). The power supply terminals are
, page 17)
18
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Power-Supply and Sensor Wiring
Equipment
ground
Power-supply conduit opening
Equipment ground
Transmitter power rating
Terminal
labels
85-250 VAC 50/60 H z L N 12-30 VDC +
Figure 4-3. Power-supply wiring terminals
continued

Grounding

WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion.
• T he transmitter must be properly grounded.
• Follow the instructions below to ground the transmitter.
• For hazardous area installations in Europe, refer to standard EN 60079-14 if nation al standards do not apply.
To ensure proper grounding:
• If the installation must comply with UL, CSA, or SAA standards, refer to the instructions in one of the following Micro Motion documents:
-
UL-D-IS Installation Instructions
-
CSA-D-IS Installation Instructions
-
SAA-D-IS Installation Instructions
• In most installations, install grounding as illustrated in (next page).
• For installations in Europe, and to comply with CENELEC standards, install grounding as illustrated in
Figure 4-4b
(next page).
• To achieve potential equalization and comply with CENELEC standards for hazardous area installations in Europe, the RFT9739 external ground terminal (see
Figure 4-4b
) should be connected to the appropriate ground terminals within the hazardous area, using a potential equalizing line.
Figure 4-4a
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
19
continued
Power-Supply and Sensor Wiring
Figure 4-4a. Grounding detail — typical
I.S. ground
terminals
Internal
case ground
terminal
Power ground terminal
Earth ground
Figure 4-4b. Grounding detail — European installations
I.S. ground
terminals
If national standards are not in e ffect, adhere to these guidelines for grounding:
• Use copper wire, 14 AWG (2.5 mm²) or larger wire size.
• Keep all ground leads as short as pos si ble, less than 1 ohm impe dance.
• Connect I.S. ground terminals di r ect l y to in te rnal case ground termi nal.
• Connect ground lead from power ground terminal directly to earth ground.
• Follow plant standards, instead of this standard, if a separate high-integrit y in trinsically safe ground scheme is used.
Internal
case ground
terminal
External ground
terminal
20
Earth ground
Power ground terminal
If national standards ar e not in effect, adhere to these guidelines for grounding:
• Use copper wire, 14 AWG (2.5 mm²) or larger wire size.
• Keep all ground leads as short as possible, less than 1 ohm impedance.
• A factory-installed ground wire, connecting the I.S. ground and internal case-ground terminals, must remain i n p l ace.
• Connect ground lead from power ground terminal directly to earth ground.
• Follow plant standards, instead of this standard, if a separate high-integr ity intrinsically safe ground scheme is used.
• To achieve potential equalization and comply with CENELEC standar ds for hazardous area installations in Europe, connect the external ground terminal to the appropriate ground terminals withi n t he hazardous area, using a potential equalizing line.
• For hazardous area installation in Europe, use standard EN 60079-1 4 as a guideline.
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Power-Supply and Sensor Wiring
continued

4.3 Sensor wiring

Cable connections to sensor and transmitter
The instructions in this section explain how to connect a fully prepared Micro Motion flowmeter cable to the RFT9739 and a sensor. The sensor can be a Micro Motion ELITE, F-Series, Model D, DT, or DL sensor.
• The procedure for preparing Micro Motion flowmeter cable and cable glands is described in the instructions that are shipped with the cable.
• Install cable and wiring to meet local code requirements.
• Use Micro Motion color-coded cable.
• Total length of cable from the sensor to the transmitter must not exceed 1000 feet (300 meters).
WARNING
Operating the transmitter without covers in place exposes electrical hazards that can cause property damage, injury, or death.
Make sure the safety barrier partition, electronics module cover, and housing cover are securely in place before operating the transmitter.
CAUTION
Failure to seal sensor junction box and transmitter housing could cause a short circuit, which would result in measurement error or flowmeter failure.
Pow er-Supply and
Sensor Wiring
To avoid risk of condensation or excessive moisture in the junction box or transmitter housing:
• Seal all conduit openings.
• Install drip legs in conduit or cable.
• Ensure integrity of gaskets and O-rings, and fully tighten all housing covers.
CAUTION
Improper installation of cable or conduit could cause inaccurate measurements or flowmeter failure.
Keep cable away from devices such as transformers, motors, and power lines, which produce large magnetic fields.
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
21
Power-Supply and Sensor Wiring
continued
The wiring procedure is the same for the sensor and transmitter. Refer to the hazard statements on page 21 and the wiring diagrams below and on page 23, and follow these steps:
1. Insert the stripped ends of the individual wires into the terminal blocks. No bare wires should remain exposed.
• At the sensor, connect wiring inside the sensor junction box.
• At the transmitter, connect wiring to the transmitter's intrinsically
safe terminals for sensor wiring, as numbered in
Table 4-1
Transmitter terminal blocks can be unplugged for easier connection of wiring.
.
Table 4-1. Terminal designations
Figure 4-5. Wiring to ELITE
®
CMF sensors
2. Locate the wires by color as indicated in
Table 4-1
.
3. Tighten the screws to hold the wires in place.
4. Tightly close the sensor junction-box cover and transmitter housing. On an ELITE sensor junction box, tighten all four cover screws.
Wire color
Black* Brown11Drive + Red22Drive – Orange 3 3 T em perature – Yell ow 4 4 Temperature return Green 5 5 Left pickoff + Blue 6 6 Ri gh t pickoff + Violet 7 7 Temperature + Gray 8 8 Right pickoff – White 9 9 Left pickoff –
* C ombined drain wires from brown/re d, green /wh ite, and gray/blue pairs, and
yellow/orange/violet triplet.
Sensor terminal
Transmitter terminal Function
No connection 0 Drain wires*
22
ELITE® sensor
terminals
Green
White
Brown
Violet
Yellow
Orange
Blue Gray Red
Brown
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Red
Green
White
Blue Gray
Orange
Violet
Yellow
Flowmeter
cable
Maximum cable length 1000 ft. (300 m)
Prepare cable in accordance with the
instructions that are shipped with the cable
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Black (Drains from all wire sets)
Brown Red
Green White
Blue Gray
Orange Violet Yellow
Field-mount
RFT9739 terminals
Brown
Orange
Green
Violet White
Gray
Blue
Yellow
Red
Black (Drains)
continued
Power-Supply and Sensor Wiring
Figure 4-6. Wiring to F-Series, Model D, and DL sensors
F-Series, Model D
or DL sensor
terminals
Brown Red Orange Yellow Green Blue Violet Gray White
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
Maximum cable length 1000 ft. (300 m)
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Prepare cable in accordance with the
instructions that are shipped with the cable
Figure 4-7. Wiring to Model DT sensors
Model DT
sensor terminals
User-supplied*
metal junction box with
terminal block
1 2 3 4 5 6 7 8
Sensor wire number
9
Brown Red Orange Yellow Green Blue Violet Gray White
Earth ground
Clip drain wire back
Clip drain wire back
Clip drain wire back
Clip drain wire back
*In Europe, the DT-sensor junction box is supplied by the factory.
Brown
Red
Green
White
Blue
Gray
Orange
Violet
Yellow
Prepare cab l e in accor dan ce wi th t he in struc tio ns
Flowmeter
cable
Flowmeter
cable
Maximum cable length 1000 ft. (300 m)
that are shipped with the cable
Black (Drains from all wire sets)
Brown Red
Green White
Blue Gray
Orange Violet Yellow
Black (Drains from all wire sets)
Brown Red
Green White
Blue Gray
Orange Violet Yellow
Field-mount
RFT9739 terminals
Brown
Orange
Green
Violet White
Gray Blue
Yellow
Red
Black (Drains)
Field-mount
RFT9739 terminals
Brown
Orange
Green
Violet White
Gray Blue
Yellow
Red
Black (Drains)
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
23
24
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual

5 Output Wiring

5.1 General guidelines

WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion.
Output wiring is not intrinsically safe.
• Keep output wiring separated from power-supply wiring and intrinsically safe sensor wiring.
• Follow all output wiring instructions to ensure transmitter and any connected devices will operate correctly.
• Make sure the safety barrier partition is in place before operating the transmitter.
A removable partition on the RFT9739 electronics module keeps intrinsically safe wiring to the sensor separated from nonintrinsically saf e output wiring. Use the upper and lower blocks on the right side of the partition for output wiring connections. page) describe terminal designations for the output terminals. Terminal blocks can be unplugged from the module f or easier installation of wiring.
• The RFT9739 has separate conduit openings for power-supply wiring and output wiring.
• To avoid possible electrical interference, do not install output wiring in the same conduit or cable tray as sensor cable or power-supply wiring.
• Use individually shielded pairs of 22 AWG (0.3 mm²) or larger wires for connections between the RFT9739 and any peripheral device.
• Shields and/or drain wires must be terminated outside the transmitter housing, or left floating, as required by the installation.
• To comply with CENELEC standards for hazardous area installations in Europe, nonintrinsically-safe connections between the RFT9739 and other devices may less than or equal to 250 V.
only
be made to devices that maintain a voltage
Figure 5-1
and
Table 5-1
(next
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting

5.2 Maximum wire length

RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Currently, there is no system for accurately estimating the maximum length of wire between the RFT9739 and a connected peripheral device.
Most applications will be able to use wire lengths up to 500 feet for 22 AWG wire (150 meters for 0.3 mm² wire), 50 feet for 28 AWG wire (15 meters for 0.1 mm² wire), between the transmitter and any peripheral device. However, these distances are estimates only.
Prior to commissioning the transmitter, a loop-test is recommended as a means for determining whether or not output signals are being received correctly at the receiving device.
25
continued
Output Wiring
Figure 5-1. Output terminals
Table 5-1. Output wiring terminal designations
Terminal Function
14 Frequency out put, DC supply voltage 15 and 16 Frequency/pulse output 17 and 18 Primary variable (PV) mA output 19 and 20 Secondary variable (SV) mA output 21 and 16 Remote zero input 22 and 16 Control output 23 Signal ground 24 and 23 Temperature output 25 and 23 Tube period output 26 and 27 RS-485 I/O P DC power to pressure or DP transmitter S mA input from pressure or DP transm i tter HART Communicator hookup loo ps, sam e as PV mA output circuit
26
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Output Wiring
continued
5.3 Primary and secondary mA outputs
The RFT9739 primary and secondary mA output signals can be independently configured, and can represent flow, density, temperature, event 1 or event 2. With a pressure transmitter, the primary and secondary output signals can also represent pressure. For information on configuring mA outputs for events, see any of the following manuals or AMS on-line help:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
• The mA outputs can produce a user-selected 0-20 or 4-20 mA current.
(See "Milliamp output scaling," page 9).
• When configured to produce 4-20 mA current, the mA output loop can supply loop-powered process indicators.
For transmitters with software version 3.8 or higher,
when configured to produce 4-20 mA current, the mA outputs are compliant with the NAMUR NE43 standard. (All RFT9739 transmitters shipped after November 1999 have software version 3.8 or higher.)
CAUTION
Milliamp output range has changed.
When configured for 4-20 mA, milliamp outputs will not output live signals between 2.0 and 3.8 mA, or between
20.5 and 22 mA.
Pow er-Supply and
Sensor Wiring
In compliance with the NAMUR NE43 standard:
• 4-20 mA outputs will produce a live signal from 3.8 to 20.5 mA.
• 4-20 mA outputs will not produce a signal between 2.0 and 3.8 mA, or
• 4-20 mA output performance is illustrated in
Figure 5-2. 4-20 mA output performance
Downscale fault indication level
Systems that rely on milliamp output signals in the ranges listed above might not perform as expected. For RFT9739 transmitters shipped after November 1999, outputs will saturate at 3.8 and 20.5 mA, unlike previous versions of these instruments.
Reconfigure systems as necessary.
between 20.5 and 22 mA.
Figure 5-2
Upscale
fault indication level
Operating range (live si gnal)
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
.
2 3.8 2220.5
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Output, mA
27
continued
Output Wiring
Use RFT9739 terminals 17 and 18 for the primary mA output. Use terminals 19 and 20 for the secondary mA output. See
• Primary and secondary mA output loops are isolated and floating. Additional grounding will result in optimum performance, and optimum HART communication on the primary mA output. Ensure that mA output loops are grounded properly, either at the transmitter end, or at the external device.
• The maximum allowable length for mA signal wiring is determined by measuring resistance over the signal wires and through the receiver device. Total loop resistance must not exceed 1000 ohms.
• The primary mA output must be set to the 4-20 mA mode for the Bell 202 physical layer. The Bell 202 layer will not work with the primary mA output configured as a 0-20 mA output.
• The mA output cannot be converted from active to passive.
Figure 5-3. Primary and secondary mA output wiring
PV+ (signal line) PV– (return)
Figure 5-3
.
RFT9739 output terminals
SV+ (signal line) SV– (return)
PV = Primary variable SV = Secondary variable
28
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Output Wiring
continued
Connections for HART® communication devices
Figure 5-4
ProLink PC-Interface adaptor, or an AMS serial modem to the RFT9739
illustrates how to connect a HART Communicator, the
for digital communication over the primary mA output. For information about using the HART Communicator or ProLink program, see the appropriate instruction manual. For AMS software, use the AMS on-line help:
Figure 5-4. HART® Communicator, ProLink® PC-Interface, and AMS modem connections
Field-mount
RFT9739
PV terminals
17 and 18
Communicator loops
(same circuit as PV terminals)
HART
Communicator,
ProLink PCI,
or AMS modem
PV+
Communicator loops
or PV terminals
PV–
R1
(Note 1)
R3
(Note 3)
R2
Pow er-Supply and
Sensor Wiring
DCS or PLC
with internal
resistor
(Note 2)
1. If necessary, add resistance in the loop by installing resistor R1. SMART FAMILY® devices require a minimum loop resistance of 250 ohms. Loop resistance must not exceed 1000 ohms, regardless of the communication setup.
CAUTION
Connecting a HART device to the RFT9739 primary variable milliamp output loop could cause transmitter output error.
If the primary variable (PV) analog output is being used for flow control, connecting a HART device to the output loop could cause the transmitter 4-20 mA output to change, which would affect flow control devices.
Set control devices for manual operation before connecting a HART device to the RFT9 739 primary variable milliamp output loop.
2. The DCS or PLC must be configured for an active milliamp signal.
3. Resistor R3 is required if the DCS or PLC does not have an internal resistor.
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
29
Output Wiring
continued

5.4 Frequency/pulse output

The RFT9739 frequency/pulse output represents the flow rate or flow total, independent of the primary and secondary mA outputs. The frequency/pulse output can be used with any Micro Motion peripheral device except the DMS Density Monitoring System and the PI 4-20 Process Indicator, which do not have frequency inputs.
The frequency/pulse output can be configured to provide any one of the following:
• Mass flow rate
• Volume flow rate
• Mass flow total
• Volume flow total Mass flow total and volume flow total are not available with some
RFT9739 transmitters shipped prior to 1998. Use RFT9739 terminals 15 and 16 for the frequency/pulse output. The
frequency/pulse output, control output, and external zero input share terminal 16 as a common return. See
Figure 5-5
, page 31.
• The frequency/pulse output loop is isolated and floating from other circuits except the control output and external-zero input circuits. Ensure that the frequency/pulse output loop is grounded properly, either at the transmitter end, or at the external device.
• The frequency output circuit uses a 2.2 kohm resistor tied to a 15-volt source that limits the current to 7 mA. The output circuit is rated to 30 VDC, with 0.1 ampere maximum sinking capability, when used in the open collector mode. Open collector mode is described on page 33.
• Transmitter output is a nominal +15 V square wave, unloaded. Any load will decrease the peak voltage level.
• Output impedance is 2.2 kohm.
• For use with receivers other than Micro Motion peripheral devices, check the instruction manual for the receiver to make sure its input­voltage and electrical-current ratings match the RFT9739 frequency/pulse output ratings.
30
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Output Wiring
continued

Default configuration

When the RFT9739 is shipped from the factory, the frequency/pulse output is internally powered by an isolated 15-volt source via a 2.2 kohm pull-up resistor. This internal current is limited to approximately 7 mA. See

Configuration for increased current

In some applications, it might be necessary to increase the current in the frequency/pulse output circuit. See current, add a 1 to 3 kohm resistor across terminals 14 and 15, as illustrated in
Figure 5-5. Frequency/pulse output wiring
Figure 5-5
.
Figure 5-6
FREQ+ (signal line)
RETURN (ground)
RFT9739 output terminals
Section 5.2
, page 25. For increased
.
PLC
or
pulse counter
Pow er-Supply and
Sensor Wiring
Figure 5-6. Frequency/pulse output wiring for increased current
FREQ+ (signal line)
RETURN (ground)
1 to 3 kohm
resistor
RFT9739 output terminals
PLC
or
pulse counter
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
31
Output Wiring
continued

Configuration for constant current

Applications with high capacitance loading will benefit by wiring the frequency/pulse output circuit to maintain a constant current source of 50 mA for any load between 0 and 220 ohms. This configuration renders the control output circuit inoperable.
For constant current, add a jumper across terminals 14 and 15, and a 100 to 250 ohm resistor at the PLC or pulse-counter end of the cable, as illustrated in
Adding a jumper across terminals 14 and 15 renders the control output circuit inoperable.
Do not attempt to use the control output circuit after you add a jumper across terminals 14 and 15.
Figure 5-7
The control output can be reconfigured to function properly, independent of this frequency/pulse wiring procedure. See "Control output in open collector mode," page 36.
Figure 5-7. Frequency/pulse output wiring for constant current
.
CAUTION
FREQ+ (signal line)
100 to 250 ohm
RETURN (ground)
RFT9739 output terminals
PLC
or
pulse counter
resistor
32
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Output Wiring
continued

Configuration for open collector mode

The RFT9739 provides current to the frequency/pulse output circuit. In applications where this current must be permanently suspended, and for receiving devices that require input voltage higher than approximately 10 volts, the frequency/pulse output circuit can be used in open collector mode.
To configure the output for open collector mode, a resistor must be clipped as described below.
This procedure will permanently alter the
transmitter and cannot be reversed.
• Clip resistor R14 (R1 on models with enhanced EMI immunity) and add an external DC power supply and a pull-up resistor. See
Figure 5-8
.
• The pull-up resistor must be of sufficient value to limit loop current to less than 0.1 ampere, depending on the total loop resistance at the transmitter.
• Resistor R14 (R1) is located on the RFT9739 output board, behind the output terminal blocks, as illustrated in
Figure 5-9
. To access resistor
R14 (R1), unplug the output terminal blocks from the transmitter.
CAUTION
Clipping resistor R14 or R1 will eliminate the internal voltage source from the transmitter.
After clipping resi stor R14 or R 1, an external power supply is required to use the transmitter’s frequency/pulse output.
Pow er-Supply and
Sensor Wiring
Before permanently altering any equipment, contact the Micro Motion Customer Service:
• In the U.S.A., phone 1-800-522-6277
• Outside the U.S.A., phone 303-530-8400
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
33
continued
Output Wiring
Figure 5-8. Frequency/pulse output wiring for open collector mode
FREQ+ (signal line)
RETURN (ground)
Resistor
(See note)
RFT9739 output terminals
Resistor must be of sufficient value to limit loop current to less than 0.1 ampe re, depending on total loop resistan ce.
Figure 5-9. Location of resistor R14 (R1) on output board
CAUTION: After clipping resistor R14 or R1, an external power supply is required to use the transmitter’s frequency pulse output. See page 33.
PLC
or
pulse counter
DC power supply
Resistor R14 or R1
Connectors behind output terminal blocks
34
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Output Wiring
continued

5.5 Control output

The control output can indicate flow direction, transmitter zeroing in progress, pressure input failure, faults, event 1 or event 2. For information on configuring the control output for events, see any of the following manuals or AMS on-line help:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
Use RFT9739 terminals 22 and 16 for the control output. The control output, frequency/pulse output, and external zero input share terminal 16 as a common return. See
Figure 5-10
.
• When configured to indicate flow direction, the output is high (+15 V) when indicating forward flow, and low (0 V) when indicating reverse flow .
• When configured to indicate transmitter zeroing in progress, the output is low (0 V) when zeroing is in progress and high (+15 V) at all other times.
• When configured to indicate faults, the output is low (0 V) when a fault condition exists and high (+15 V) during normal operation.
• When configured to indicate event 1 or event 2, the output switches ON (0 V) or OFF (+15 V) when the flow rate, flow total, density, temperature, or pressure of the process fluid achieves a programmed setpoint.
• The output circuit is rated to 30 VDC, with 0.1 ampere maximum sinking capability, when used in open collector mode. Open collector mode is described on page 36.
• Transmitter output is nominal 0 or +15 V, unloaded.
• Output impedance is 2.2 kohm.
Pow er-Supply and
Sensor Wiring
Figure 5-10. Control output wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 output terminals
RETURN (ground) CONTROL (signal line)
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
35
Output Wiring
continued

Control output in open collector mode

The RFT9739 provides current to the control output circuit. In applications where this current must be permanently suspended, and for receiving devices that require input voltage higher than approximately 10 volts, the control output circuit can be used in open collector mode.
If the frequency/pulse output is configured for constant current (see "Configuration for open collector mode," page 33), the control output is rendered inoperable. To reconfigure the control output to function properly, independent of this frequency/pulse output configuration, the control output circuit can be configured for open collector mode.
To configure the control output for open collector mode, a resistor must be clipped as described below.
This procedure will permanently alter
the transmitter and cannot be reversed.
• Clip resistor R15 (R2 on models with enhanced EMI immunity) and add an external DC power supply and a pull-up resistor. See
Figure 5-11
,
page 37.
• The pull-up resistor must be of sufficient value to limit loop current to less than 0.1 ampere, depending on the total loop resistance at the transmitter.
• Resistor R15 (R2) is located on the RFT9739 output board, behind the output terminal blocks, as illustrated in
Figure 5-12
, page 37. To access resistor R15 (R2), unplug the output terminal blocks from the transmitter.
CAUTION
Clipping resistor R15 or R2 will eliminate the internal voltage source from the transmitter.
After clipping resi stor R15 or R 2, an external power supply is required to use the transmitter’s control output.
Before permanently altering any equipment, contact the Micro Motion Customer Service:
• In the U.S.A., phone 1-800-522-6277
• Outside the U.S.A., phone 303-530-8400
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155
36
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
continued
Output Wiring
Figure 5-11. Control output wiring for open collector mode
Resistor
(See note)
Resistor must be of sufficient value to limit loop current to less than 0.1 ampe re, depending on total loop resistan ce.
Receiving
device
DC power supply
RFT9739 output terminals
Figure 5-12. Location of resistor R15 (R2) on output board
CAUTION: After clipping resistor R15 or R2, an external power supply is required to use the transmitter’s frequency pulse output. See page 36.
Pow er-Supply and
Sensor Wiring
Resistor R15 or R2
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
Connectors behind output terminal blocks
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
37
Output Wiring
continued

5.6 Peripheral device wiring

Table 5-2. Peripheral wiring diagrams
Figure 5-13. Wiring to DMS
RFT9739
output terminals
The wiring diagrams listed in
Table 5-2
illustrate connections from the
transmitter to Micro Motion peripheral devices.
Micro Motion peripheral device Figure Page
DMS Density Monitoring System 5-13 38 DRT Digital Rate Totalizer with LED display 5-14a 39 DRT Digital Rate Totalizer with LCD display 5-14b 39 FMS-3 Flow Monitoring System with LED display 5-15a 40 FMS-3 Flow Monitoring System with LCD display 5-15b 40 NFC Net Flow Computer 5-16 41 NOC Net Oil Computer with AC power supply 5-17a 42 NOC Net Oil Computer with DC power supply 5-17b 42 Model 3300 Discrete Controller with screw/solder terminals 5-18a 43 Model 3300 Discrete Controller with I/O cable 5-18b 43 Model 3350 Discrete Co nt ro ller 5-19 43
DMS
terminals
1. Clip shields at this end.
2. This wire not terminated.
Note 2
Note 1
Note 1
Note 2
Earth
ground
38
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
continued
Output Wiring
Figure 5-14a. Wiring to DRT with LED
RFT9739 output terminals
Clip shields at this end
Figure 5-14b. Wiring to DRT with LCD
DRT LED
terminals
Earth ground
RFT9739 output terminals
Clip shields at this end
Earth ground
DRT LCD terminals
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
39
continued
Output Wiring
Figure 5-15a. Wiring to FMS-3 with LED
RFT9739 output terminals
Clip shields at this end
Figure 5-15b. Wiring to FMS-3 with LCD
FMS-3 LED
terminals
Earth
ground
RFT9739 output terminals
Clip shields at this end
FMS-3 LCD
terminals
Earth
ground
40
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
continued
Output Wiring
Figure 5-16. Wiring to NFC
RFT9739 output terminals
NFC
terminals
Note 1
Note 2
1. Clip shields at this end.
2. This wire not terminated.
Note 1
Note 1
Note 2
Earth
ground
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
41
continued
Output Wiring
Figure 5-17a. Wiring to AC-powered NOC
RFT9739 output terminals
Note 1
Note 2
Note 1
NOC
terminals
Note 1
Note 2
Earth
ground
1. Clip shields at this end.
2. This wire not terminated.
Figure 5-17b. Wiring to DC-powered NOC
RFT9739 output terminals
Note 1
Note 2
Note 1
Note 1
NOC
terminals
Note 2
1. Clip shields at this end.
2. This wire not termi nat e d.
42
Earth ground
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
continued
Output Wiring
Figure 5-18a. Wiring to Model 3300 with screw-type or solder-tail terminals
RFT9739 output terminals
Model 3300
terminals
Clip shields at this end
Earth
ground
Figure 5-18b. Wiring to Model 3300 with I/O cable
Clip shields at this end
Earth ground
RFT9739 output terminals
Figure 5-19. Wiring to Model 3350
RFT9739 output terminals
Clip shields at this end
Pow er-Supply and
Sensor Wiring
Model 3300 terminals
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
Model 3350
terminals
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Earth ground
43
Output Wiring
continued

5.7 Pressure transmitter wiring

WARNING
Failure to comply with requirements for intrinsic safety in a hazardous area could result in an explosion.
Pressure transmitter wiring is not intrinsically safe.
• Keep pressure transmitter wiring separated from power­supply wiring, intrinsically safe sensor wiring, and any other intrinsically safe wiring.
• Make sure the safety barrier partition is in place before operating the transmitter.
The RFT9739 accepts input signals from a pressure transmitter for pressure compensation.
• If a pressure transmitter connected to a host controller measures gauge pressure at the sensor input, the RFT9739 can compensate for the pressure effect on the sensor. Pressure compensation is required only for sensor models listed in
• Instructions for wiring the RFT9739 to a pressure transmitter are provided below. Instructions for configuring the RFT9739 for pressure compensation are provided in the following instruction manuals and in the AMS on-line help:
-
Using the HART Communicator with Micro Motion Transmitters
-
Using ProLink Software with Micro Motion Transmitters
-
Using Modbus Protocol with Micro Motion Transmitters
Table 5-3
.
Table 5-3. Sensors affected by pressure
The RFT9739 pressure input terminals (P and S) are intended for use with a pressure transmitter, and should not be connected to a control system.
If the RFT9739 is configured for pressure compensation, flowmeter measurement will not be compensated for pressure during a pre ssure input failure. If the signal from the pressure transmitter fails, both of the following occur:
• The RFT9739 continues to operate in non-fault mode.
• A "Pressure Input Failure" message is shown on the transmitter display (if it has one), a HART Communicator with the latest memory module, ProLink software version 2.4 or higher, or AMS software.
ELITE F-Series Model D and DL
CMF025 (density only ) CMF050 (density only ) CMF100 CMF200 CMF300 CMF400
F025 (density only) F050 F100 F200
D300 standard model D300 Tefzel D600 DL100 DL200
®
model
44
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
continued
Output Wiring
If the pressure transmitter requires a power supply less than or equal to 11.75 V,
the RFT9739 can power the pressure transmitter. Use RFT9739 terminals P and S. Terminal P (MA PWR OUT) is the power output to the pressure transmitter, and terminal S (MA SIG IN) is the signal input to the RFT9739, as shown in
If the pressure transmitter requires a power supply greater than
11.75 V,
or if other loop devices are required, an external source can power the pressure transmitter. Use RFT9739 terminals S and 23. Terminal S (MA SIG IN) is the signal input to the RFT9739, and terminal 23 (SIGNAL GND) is the return, as shown in
If digital communication between the pressure transmitter and the RFT9739 is required,
as shown in
Figure 5-20c
Figure 5-20a. Wiring to pressure transmitter — analog input
WARNING: Pressure transmitter wiring is not intrinsically safe
Figure 5-20a
Figure 5-20b
.
.
use RFT9739 terminals 17 (PV+) and 18 (PV–),
, page 46.
RFT9739
output terminals
Figure 5-20b. Wiring to pressure transmitter — external power, analog input
WARNING: Pressure transmitter wiring is not intrinsically safe
RFT9739
output terminals
Pressure
transmitter
Pressure
transmitter
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
Optional
loop device(s)
4-20 mA
Terminal 23 must be connected directly to the negative (–) terminal of the external power supply .
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
24 VDC
Power
supply
45
continued
Output Wiring
Figure 5-20c. Wiring to pressure transmitter — digital communications
WARNING: Pressure transmitter wiring is not intrinsically safe
250 ohm ±5%, 0.5 W
Pressure transmitter
SMART only (1150 or 3051)
250 ohm ±5%,
0.5 W

5.8 Remote-zero switch

The tran smitter can be confi gured to allow transmitter zeroing from an external switch. The switch must be a momentary-type contact, normally open, and must carry 1 mA of current in the closed position. The open circuit voltage is 5 VDC.
Use terminals 21 and 16 for the remote switch. The remote-switch input, frequency/pulse output, and control output share terminal 16 as a common return. See
Section 6.4
Figure 5-21. Wiring to remote-zero switch
RFT9739
output terminals
Figure 5-21
.
24 VDC
Power
supply
, page 57, describes the flowmeter zeroing procedure.
Remote
switch
RETURN (ground)
46
RFT9739 output terminals
ZERO+ (signal line)
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Output Wiring
continued

5.9 RS-485 multidrop network

The RFT9739 can be configured to communicate for any one of the following options:
• HART protocol over the RS-485 standard
• HART protocol over the Bell 202 standard
• Modbus protocol over the RS-485 standard
• Modbus protocol over the RS-485 standard and HART protocol over
the Bell 202 standard
For communications configuration instructions, see "Communication settings," page 9. For Bell 202 network wiring, see
Section 5.10
,
page 48. Multiple transmitters can participate in an RS-485 multidrop network that
uses HART or Modbus protocol.
• Under HART protocol, an almost unlimited number of transmitters can
participate in the network. Each transmitter must have a unique tag name. If polling addresses are used, up to 16 transmitters can have unique polling addresses from 0 to 15.
• Under Modbus protocol, up to 247 transmitters can participate in the
network. Each transmitter must have a unique polling address from 1 to 247.
To connect the transmitter to an RS-485 network, use RFT9739 terminals 27 and 26.
Figure 5-22
shows how to connect one RFT9739 or multiple RFT9739 transmitters to a host controller for RS-485 serial communication.
• Install twisted-pair, shielded cable, consisting of 24 AWG (0.25 mm²) or
larger wire, between the RFT9739 and an RS-485 communication device. Maximum cable length is 4000 feet (1200 meters).
• Some installations require a 120-ohm, ½-watt resistor at both ends of
the network cable to reduce electrical reflections.
Pow er-Supply and
Sensor Wiring
For information on communication protocol requirements for implementing an RS-485 network, phone the Micro Motion Customer Service Depa rtment:
• In the U.S.A., phone 1-800-522-6277, 24 hours
• Outside the U.S.A., phone 303-530-8400, 24 hours
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
47
continued
Output Wiring
Figure 5-22. RS-485 wiring
One RFT9739 and a host controller
Host
controller
Multiple RFT9739s and a host controller
Host
controller
A B
A B
See note
See note
See note
See note
See note
27 26
27 26
RFT9739
RFT9739
27 26
RFT9739
For long-distance communication, or if noise from an external source interferes with the signal, install 120-ohm ½-watt resistors across terminals of both end devices.
5.10 Bell 202 multidrop network
The RFT9739 can be configured to communicate for any one of the following options:
27 26
RFT9739
• HART protocol over the RS-485 standard
• HART protocol over the Bell 202 standard
• Modbus protocol over the RS-485 standard
• Modbus protocol over the RS-485 standard and HART protocol over the Bell 202 standard
For communications configuration instructions, see "Communication settings," page 9. For RS-485 network wiring, see
Devices in a Bell 202 multidrop network communicate by sending and receiving signals to and from one another. HART protocol supports up to 15 transmitters in a Bell 202 multidrop network. The actual maximum number depends upon the type of transmitters, the method of installation, and other external factors. Other Rosemount SMART FAMILY transmitters can also participate in a HART-compatible network.
• A Bell 202 multidrop network uses twisted-pair wire, and allows only digital communication. Digital communication requires a sample rate of 2 to 31 seconds at 1200 baud.
• A HART Communicator or other HART-compatible control system can communicate with any device in the network over the same 2-wire pair.
Section 5.9
, page 47.
48
Using multiple transmitters in a HART-compatible network requires assigning a unique address from 1 to 15 to each transmitter.
• Assigning an address of 1 to 15 to the transmitter causes the primary mA output to remain at a constant 4 mA level.
• The primary mA output must produce a 4-20 mA current for the Bell 202 physical layer . The Bell 202 lay er will not work with the primary mA output configured as a 0-20 mA output when the current output is 0mA.
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
continued
Output Wiring
To connect the transmitter to a Bell 202 network, use RFT9739 terminals 17 and 18. See
• SMART FAMILY devices require a minimum loop resistance of 250 ohms. Loop resistance must not exceed 1000 ohms.
• Connect the mA outputs from each transmitter together so they terminate at a common load resistor, with at least 250 ohms impedance, installed in series.
Figure 5-23. Typical HART® network wiring
Figure 5-23
.
HART
Communicator,
ProLink PCI,
or AMS modem
250 ohm
load
4-20mA
IFT9701
For optimum HART communication, make sure the output loop is single-point grounded to instrument grade ground.
RFT9739
field-mount
PV+17PV–
18
4-20mA
R-Series
RFT9739
rack-mount
PV+
PV–
CN2-
CN2-
Z30
D30
SMART
FAMILY
trans­mitter
DC source required for other HART 4-20mA passive transmitters
SMART
FAMILY
trans­mitter
24
DC
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
49
50
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual

6 Startup

6.1 Initialization

Initialization with display

After wiring has been connected, power can be supplied to the transmitter. During initialization, the diagnostic LED on the electronics module remains on continuously, while the transmitter performs a self­diagnostic. After initialization is completed, the LED blinks ON once per second to indicate proper operation of the transmitter.
For DC-powered transmitter s
must provide a minimum of 1.6 ampere of inrush current at a minimum of 12 volts at the transmitter's power input terminals.
If the transmitter has a display, during initialization the display will show, sequentially:
1. All pixels on
2. All pixels off
3. All eig hts
4. All pixels off
5. Copyright notification
After the self-test is complete, one of ten possible process variable screens, such as the one depicted below, appears:
If the flowmeter is operating properly, the blinking "Msg" (message) indicator appears in the bottom right corner of the screen to indicate power has been cycled.
• To clear the "Msg" indicator, repeatedly rotate the Scroll knob until the display reads "Sensor OK *POWER / RESET*".
• To clear the message, rotate the Scroll knob.
, at startup, the transmitter power source
INV: GRAMS:
38450.5 Msg
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
If the message does not clear, or if error messages appear, refer to
Section 7.4
error messages.

6.2 Using the optional display

RFT9739 Field-Mount Tra nsm it te r Instruction Manual
The optional RFT9739 display enables the user to:
• View process variables, flow totals and inventory levels, and status messages (see page 52)
• Set communication parameters (see page 54)
• Zero the flowmeter (see page 57)
• Reset the transmitter's flow totalizers (see page 60)
Use the Scroll and Reset knobs to operate the display.
, page 68, which provides an overview of diagnostic and
51
Startup
continued

Adjusting the sight window

The sight window in the transmitter housing cover enables the user to view the LCD on the electronics module inside the housing. After the cover has been put in place, the sight window might not be properly aligned for viewing the display. To align the sight window, rotate the adjustable faceplate in either direction until the entire display is visible.
Micro Motion recommends mounting the transmitter with its conduit openings pointed downward. In such installations, the sight window will be properly aligned when it is directly above the Scroll and Reset knobs.
CAUTION
Rotating the transmitter housing cover or adjustable faceplate could cause the display to change, the flowmeter to be zeroed, or totalizers to be reset.
Rotating the transmitter cover actuates the Scroll and Reset knobs, whic h w i ll af fect the screen that is displ ayed, and could zero the flowmeter or reset the transmitter flow totalizers.
Adjustable faceplate
Transmitter housing cover

Process variables mode

• Do not rotate the transmitter housing cover or adjust the faceplate while R ATE, TO T, or INV screens are displ ayed.
• Security settings that prevent the use of scroll and reset knobs also prevent this situation from occurring. See
Section 2.3
, page 5.
After power to the transmitter is turned off and on, or "cycled," the transmitter is in the process variables mode. The first screen that appears is the last process variable screen that was viewed before power was cycled. In the process variables mode, each screen indicates the value and measurement unit for a process variable.
As the user scrolls through the process variable screens, they appear in the order listed in
Table 6-1
, page 53.
52
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Startup
continued
Table 6-1. Display screens
Screen Process variable
1 M a ss flow rate (RATE) 2 Volume flow rate (RATE) 3 Density (DENS) 4 Temperature (TEMP) 5 Mass total 6 Volume total 7 Mass inventory 8 Volume inventory 9 Differential pr essure or
10 Configuration event register 11 Cal i brati on event register 12 Display test 13 M es sage (if any)
1
While reading total (TOT) or inventory (INV) screens, use the unit of measur e in the
gauge pressure
[1]
[1]
[1]
[1]
[2]
[3]
[3]
Abbreviation in upper left corner of screen
(TOT) (TOT) (INV) (INV) (DP) or
(P)
[3]
(CONFIG REG) (CALIBRATE REG) (DISPLAY TEST)
– –
lower left corner to dist inguish between mass and volume.
2
Screen appears only when transmitter is configured to indicate pressure.
3
Screen appears only when transmitter is configured for securi t y m od e 8. S ee Section 2.3, page 5, for information ab out security modes.
When displaying total (TOT) or inventory (INV) screens, display resolution is 10 places, including the decimal point. The position of the decimal point is fixed, and depends on the flow calibration factor and units of measure. If totalizers exceed the maximum display capability, the display reads "*********". Clear the message with the Reset knob.
Pow er-Supply and
Sensor Wiring
If a message exists, the blinking "Msg" (message) indicator appears in the bottom right corner of each screen, indicating any of the following conditions:
• Power to the transmitter has been cycled.
• The flowmeter has been zeroed.
• An error condition exists. To read a message, scroll past all process variable screens to the
message screen (see
Table 6-1
). Uncorrected status conditions remain in the message queue. Other messages are cleared when the Scroll knob is used to scroll past the message screen to the flow rate screen.
If power to the transmitter has been cycled and the transmitter is operating properly, the message reads
For more information about messages, refer to
"Sensor OK *POWER/RESET*"
Section 7.4
, page 68.
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
.
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
53
Startup
continued
Communication configuration mode
Switch 5 on the transmitter electronics module allows the user to select the standard communication configuration or establish a user-defined configuration. The communication configuration mode allows the user to configure the transmitter's digital output using the display and the Scroll and Reset knobs.
• If switch 5 is in the USER DEFINED position (see page 5), enter the communication configuration mode from any process variable screen by rotating and holding the Scroll knob, then rotating the Reset knob. In the communication configuration mode, "M1", "M2", or "M3" appears in the upper left corner of the screen.
• For RFT9739 software versions 3.6 and later, if switch 5 is in the STD COMM position, an error message will be displayed if an attempt is made to change the communication configuration using the RFT9739 display controls.
• Hardware switches can also be used for configuring the transmitter's digital communication output. For more information about using hardware switches, see
M1 — Baud rate
To set the baud rate:
1. Rotate and release the Scroll knob to view each baud rate option.
Choose from 1200, 2400, 4800, 9600, 19200, or 38400 baud.
2. Rotate and hold the Reset knob to select the displayed baud rate.
Release the Reset knob when the display stops flashing.
Section 2.3
, page 5.
Section 2.3
,
3. When the selected baud rate flashes again, rotate and release the
Reset knob to move to the M2 screen.
M2 — S=Stop bits, P=Parity
To set the stop bits and parity:
1. Rotate and release the Scroll knob to view each stop bit (S) option.
Choose 1 stop bit or 2 stop bits.
2. Rotate and hold the Reset knob to select the displayed stop bit.
Release the Reset knob when the display stops flashing.
3. When the selected stop bit flashes again, rotate and release the
Reset knob to move to the parity (P) options.
4. Rotate and release the Scroll knob to view each parity (P) option.
Choose from odd parity (O), even parity (E), or no parity (N). HART protocol requires odd parity; Modbus protocol requires odd parity, even parity, or no parity, depending on the host controller.
5. Rotate and hold the Reset knob to select the displayed parity.
Release the Reset knob when the display stops flashing.
6. When the selected parity flashes again, rotate the Reset knob to
move to the M3 screen.
54
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Startup
continued
M3 — Data bits, protocol, and physical layer
The M3 screen enables selection of 7-bit or 8-bit mode for Modbus protocol, or 8-bit mode for HART protocol.
• The HART protocol can use either the Bell 202 or RS-485 physical layer.
• Using HART protocol over the primary mA output requires the Bell 202 physical layer.
CAUTION
Changing the protocol or data bits will cause the process to shut down and the transmitter to initialize as described on page 51, which could result in switching of flow loop control devices.
Set control devices for manual operation before changing the communications protocol.
To set the data bits and protocol:
1. Rotate and release the Scroll knob to view each data bits (D) option.
Choose from 7 data bits or 8 data bits. HART protocol requires 8 data bits; Modbus protocol requires 7 data bits for ASCII mode or 8 data bits for RTU mode.
Pow er-Supply and
Sensor Wiring
2. Rotate and hold the Reset knob to select the displayed data bits.
Release the Reset knob when the display stops flashing.
3. When the selected data bits flashes again, rotate and release the
Reset knob to move to the protocol and physical layer options.
4. Rotate and release the Scroll knob to view each protocol/physical
layer option. Choose from the following:
• HART protocol over the Bell 202 physical layer (HART/202)
• HART protocol over the RS-485 physical layer (HART/485)
• Modbus protocol over the RS-485 physical layer (Modbus/485)
• Modbus protocol over the RS-485 physical layer and HART protocol over the Bell 202 physical layer (Modbus/202)
5. Rotate and hold the Reset knob to select the displayed protocol/physical layer. Release the Reset knob when the display stops flashing.
6. When the selected protocol/physical layer flashes again, rotate and release the Reset knob to restart the transmitter. If the protocol/physical layer was not changed, the transmitter will not restart, and display will return to the process variable screen.
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
55
Startup
continued

6.3 Custody transfer event registers

Event registers are provided for security requirements for custody transfer applications. When the transmitter is configured for security mode 8 (see
Section 2.3
, page 5), the transmitter meets security requirements for custody transfer described in National Institute of Standards and Technology (NIST) Handbook 44.
Custody transfer event registers record one change for each change "session." A change session begins when the transmitter is taken out of security mode 8, and ends when security mode 8 is reentered. To begin a change session, set switches 1, 2, and 3 to the OFF position. A change session ends when switches 1, 2, and 3 are reset to the ON position. After a change session is ended, security event registers will increase by one (1) if any of the parameters listed in
Table 6-2
have
been changed.
• Each register will increase up to 999, then roll over to zero.
• Custody transfer event registers cannot be reset. View the security event registers using any of the following methods:
• With the RFT9739 display. If the transmitter has a display, event
registers can be viewed from the CONFIG REG and CALIBRATE REG screens when the transmitter is configured for security mode 8.
• With a HART Communicator.
• With a HART-compatible or Modbus-compatible master controller.
• With ProLink software version 2.3 or higher. Refer to on-line help for
instructions.
• With AMS software. Refer to on-line help for instructions.
Table 6-2. Parameters that affect event registers
Configuration register
Mass flow cutoff Flow damping Volume flow cutoff Flow direction Primary m A scaling factors Secondary mA scaling factors
Calibration regist er
Mass flow units Volume flow units Auto zero calibration Density calibration Flow calibration factor Meter factors Frequency output scaling factors
• Freque nc y
•Rate
Primary m A output trim Secondary mA output trim Primary m A output assignment Secondar y m A out put assignment Control output assignment Master reset
Density calibration factors
• Density A and Density B
• K1, K2, and FD
• Density temperature coefficie nt Pressure compensa tion factors
•Flow factor
• Density factor
• Flow calibration pressure
56
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Startup
continued

6.4 Flowmeter zeroing

Zeroing procedure

CAUTION
Failure to zero the flowmeter at initial startup could cause the transmitter t o produce inaccurate signals.
Zero the flowmeter before putting the flowmeter in operation.
Flowmeter zeroing establishes flowmeter response to zero flow and sets a baseline for flow measurement.
To zero the transmitter, follow these steps:
1. Prepare the flowmeter for zeroing: a. Install the sensor according to the sensor instruction manual. b. Apply power to the transmitter, then allow it to warm up for at least
30 minutes.
c. Ensure the transmitter is in a security mode that allows flowmeter
zeroing (see "Security modes," page 5).
d. Run the process fluid to be measured through the sensor until the
sensor temperature reading approximates the normal process operating temperature.
e. Ensure that the sensor is completely filled with fluid.
Pow er-Supply and
Sensor Wiring
2. Close the shutoff valve downstream from the sensor.
3. Ensure zero flow through the sensor.
CAUTION
Flow through the sensor du ring flo wmeter zer oin g will result in an inaccurate zero setting.
Make sure the sensor tubes are completely full and fluid flow through the sensor is completely stopped during flowmeter zeroing.
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
57
Startup
continued
4. Zero the transmitter in any of five ways:
• Press and hold the ZERO button for at least ten seconds or until the LED remains on continuously.
Figure 6-1
, page 58, shows the
location of the button on the electronics module.
• If the transmitter has a display , use the Scroll knob to advance to the mass flow rate screen or volume flow rate screen, then rotate and hold the Reset knob for at least ten seconds. (In the rate screens, "RATE" appears in the upper left corner of the screen.)
• An external contact closure can be used for transmitter zeroing. (Refer to
Section 5.8
, page 46, for wiring instructions.) Close the
contact for at least ten seconds.
• Issue an auto zero command using a HART Communicator, a HART-compatible or Modbus-compatible master controller, or the ProLink software program.
• Issue a "zero trim" command with the AMS program.
During transmitter zeroing, the diagnostic LED remains on continuously.
Figure 6-1
See
. If the transmitter has a display , it reads "Sensor OK CAL IN PROGRESS". (It might be necessary to scroll through the process variable screens more than once to view this message.) The default zero time will range from 20 to 90 seconds, depending on the sensor.
Figure 6-1. Diagnostic LED and zero button
After the zeroing procedure has been completed, the LED again blinks ON once per second to indicate normal operation. If the transmitter has a display, the mass flow rate or volume flow rate screen reappears, and the blinking "Msg" (message) indicator appears in the lower right corner. To clear the message indicator, scroll to the message screen, which should read "Sensor OK *ERROR CLEARED*".
Diagnostic LED
Zero button
58
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Startup
continued

Diagnosing zero failure

Additional information about flowmeter zeroing
If zeroing fails, the LED blinks ON four times per second to indicate an error condition. If the transmitter has a display, the blinking "Msg" (message) indicator appears. The message screen will indicate the zero failure with a message such as "*ZERO ERROR*", "*ZERO TOO HIGH*", or "*ZERO TOO LOW*".
An error condition could indicate:
• Flow of fluid during transmitter zeroing
• Partially empty flow tubes
• An improperly mounted sensor To clear a zeroing error, cycle power to the transmitter, ensure that the
tubes are full and the flow has stopped, and rezero again.
Flowmeter zeroing can be disabled using the transmitter’s security modes. affect flowmeter zeroing. Refer to
Table 6-3
describes how RFT9739 security modes 1 through 8
Section 2.3
, page 5, for more
information about security modes. The transmitter has a programmable zeroing time (number of
measurement cycles), and enables the user to set the standard deviation limits. For more information, see any of the following instruction manuals:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
Pow er-Supply and
Sensor Wiring
Table 6-3. Effect of security modes on flowmeter zeroing
Per formed with
Reset knob
HART or Modbus device
Mode
1
Mode
2
Disabled Disabled Disabled Disabled Disabled Disabled Disabled
Mode
3
Disabled Disabled Disabled Disabled
Mode
4
Mode
5
Mode
6
Mode
7
Mode
8
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
59
Startup
continued

6.5 Totalizer control

The transmitter's mass totalizer and volume totalizer can be started, stopped, and reset using any of the following:
• A HART Communicator
• ProLink software version 2.4 or higher
• A Modbus device
•AMS software In addition, the totalizer can be reset using the Scroll and Reset knobs
on the transmitter housing cover, if the RFT9739 has a display.
WARNING
When the totalizers are stopped, the frequency/pulse output is disabled.
If the frequency/pulse output is used for process control, failure to set control devices for manual operation could affect process control.
• Before stopping the totalizers, set process control devices for manual operation.
• To enable the frequency/pulse output, restart the totalizers.
Totalizer functions can be disabled, depending on the RFT9739 security mode. See
Table 6-4
.
Mass and volume totalizers cannot be reset independently. When one totalizer is reset, the other is also reset. To reset the transmitter's mass totalizer and volume totalizer using the Scroll and Reset knobs:
1. Use the Scroll knob to view the process variable screens until either totalizer screen appears. (In the totalizer screens, "TOT" appears in the upper left corner.)
2. Rotate and hold the Reset knob until the screen is blank, then release.
Table 6-4. Effect of security modes on totalizer control
Flow condition
No flow Scroll and
With flow Scroll and
Resetting the totalizer has no ef fect on the mass or volume inventory. For more information about security modes, refer to Section 2.3, page 5.
Performed with
Reset knobs HART or
Modbusdevice
Reset knobs HART or
Modbusdevice
Mode
1
Mode
2
Disabled Disabl ed Disabled Disabled
Disabled Disabled Disabled Disabled Disabled Disabled Disabled
Mode
3
Disabled Disabled Disabled
Disabled Disabled Disabled Disabled Disabled Disabled
Mode
4
Mode
5
Mode
6
Mode
7
Mode
8
60
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Startup
continued

6.6 Process measurement

WARNING
Operating the transmitter without covers in place exposes electrical hazards that can cause property damage, injury, or death.
Make sure the safety barrier partition, electronics module cover, and housing cover are securely in place before operating the transmitter.
After flowmeter zeroing has been completed as described in
Section 6.4
, page 57, the flowmeter is ready for process measurement.
Pow er-Supply and
Sensor Wiring
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
61
62
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual

7 Troubleshooting

7.1 General guidelines

Troubleshooting a Micro Motion flowmeter is performed in two parts:
1. Tests of wiring integrity
2. Observation of the transmitter's diagnostic tools, which include the diagnostic LED, diagnostic messages, and fault output levels
CAUTION
During troublesho oting, the trans mitter could pr oduce inaccurate flow signals.
Set control devices for manual operation while troubleshooting the flowmeter.
CAUTION
Rotating the transmitter housing cover or adjustable faceplate could cause the display to change, the flowmeter to be zeroed, or totalizers to be reset.
Rotating the transmitter cover actuates the Scroll and Reset knobs, whic h w i ll af fect the screen that is displ ayed, and could zero the flowmeter or reset the transmitter flow totalizers.
Adjustable faceplate
Pow er-Supply and
Sensor Wiring
Output Wiring Startup TroubleshootingBefore You Begin Getting Started Mounting
• Do not rotate the transmitter housing cover or adjust the faceplate while RATE, TOT, or INV screens are displayed.
• Security settings that prevent the use of scroll and reset knobs also prevent this situation from occurring. For information about security modes, see page 5.
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Transmitter housing cover
Section 2.3
,
63
Troubleshooting
continued
Follow these general guidelines when troubleshooting a Micro Motion flowmeter:
• Before beginning the diagnostic process, become familiar with this instruction manual and with the instruction manual for the sensor.
• While troubleshooting a problem, leave the sensor in place, if possible. Problems often result from the specific environment in which the sensor operates.
• Check all signals under both flow and no-flow conditions. This procedure will minimize the possibility of overlooking some causes or symptoms.

7.2 Transmitter diagnostic tools

Diagnostic LED

Table 7-1. Conditions indicated by diagnostic LED
Figure 7-1. Diagnostic LED and communicator loops
In some situations, troubleshooting requires use of the transmitter's diagnostic tools, which include the diagnostic LED, diagnostic messages, and fault output levels. The diagnostic LED and communicator hookup loops are shown in
Table 7-1
describes the transmitter operating conditions indicated by the
Figure 7-1
.
diagnostic LED.
Diagnostic LED does this: Condition
Blinks ON once per second (25% ON, 75% OFF)
Remains ON continuous ly Startup and i ni t ialization, zero in progress Blinks ON three times, then OFF
for 1 second Blinks OFF once per second
(75% ON, 25% OFF) Blinks ON 4 times per second Fault condition
Normal operation
Communication config urati on m ode (switch 10 in ON position)
Slug flow (density below or above user­defined limits)
Diagnostic LED
64
Communicator hookup loops
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Troubleshooting
continued
Before You Begin Getting Started Mounting

Fault outputs

The RFT9739 has downscale and upscale fault outputs. (See "Milliamp output scaling," page 9.) Fault output levels are listed in
Table 7-2
Table 7-2. Fault output levels
Output Operating condition Downscale Upscale
0-20 mA Alarm 0 mA 22 mA
EPROM, RAM, or RTI error; transmitter failure 0 mA 24 mA
4-20 mA Alarm 2 mA 22 mA
EPROM, RAM, or RTI error; transmitter failure 0 mA 24 mA
Frequency/pulse Alarm 0 Hz 15 kHz
EPROM, RAM, or RTI error; transmitter failure 0 Hz 19 kHz

Diagnostic messages

The transmitter provides diagnostic messages, which can be viewed on the display of a HART Communicator, or in the Status window of the ProLink software program. Messages are described in the following instruction manuals, and in AMS on-line help:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
• Use a HART Communicator with the latest memory module, a Modbus
host controller, or ProLink software version 2.3 or higher, to view the following parameters:
•Drive gain
• Tube frequency
• Left and right pickoff voltages
•"Live zero"
.
Pow er-Supply and
Sensor Wiring
If the transmitter has a display:
• Many of the messages that can be read with a HART Communicator, the ProLink program, or AMS software can be read from the transmitter display. These messages are described in
Section 7.5
, page 73.
• Modbus host controllers use status bits as diagnostic messages.
• In the event of a display readback failure while using a HART Communicator, the ProLink program, a Modbus host controller, or AMS software, cycle power to the transmitter (turn power OFF, then ON).
Output Wiring Startup Troubleshooting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
65
Troubleshooting
continued
7.3 Interrogation with a HART® device
Connect a HART Communicator to the communicator hookup loops indicated in communicate with the transmitter.
• If the HART Communicator does not offer RFT9739 "Dev v4" as a device description, the communicator memory module needs to be upgraded.
• Use ProLink software version 2.3 or higher.
• Contact the Micro Motion Customer Service Department to upgrade your HART Communicator or ProLink program:
-
In the U.S.A., phone 1-800-522-6277, 24 hours
-
Outside the U.S.A., phone 303-530-8400, 24 hours
-
In Europe, phone +31 (0) 318 549 443
-
In Asia, phone 65-770-8155
Figure 7-2
the ProLink PC Interface adaptor, or the AMS serial modem to the RFT9739. For more information, see the HART Communicator or ProLink software instruction manual, or AMS on-line help.
Fault detection indicates an interruption in the functional integrity of the sensor and the electronics, including the sensor pickoff coils, drive coil, and RTD. Faults, such as a short or an open circuit, are detected by the HART device.
The transmitter runs continuous self-diagnostics. If these diagnostics reveal a f ailure, the HART de vice displays an error message. Self-testing allows the transmitter to check its own circuitry.
Figure 7-1
(next page) explains how to connect a HART Communicator,
, or use the ProLink or AMS programs to
The transmitter works with a Micro Motion flow sensor to provide flow information. Therefore, many of the troubleshooting checks pertain only to the sensor. However, a HART Communicator, the ProLink program, and AMS software enable the user to perform other tests:
• Performing an specified current output of 0 to 22 mA.
• Performing a to produce a user-specified frequency output between 0.1 and 15,000 Hz.
• Performing an secondary mA outputs against a highly accurate external standard such as a digital multimeter (DMM) or receiving device.
Perform mA trim and/or test procedures, if necessary, as described in the HART Communicator or ProLink software instruction manuals, or in AMS on-line help.
• If the transmitter is in security mode 8, mA output test, mA output trim, and frequency/pulse output test procedures cannot be performed. For more information, see "Security mode 8," page 6.
• If the transmitter is in fault condition, an mA output test cannot be performed.
• If the transmitter is not properly connected to a sensor, or if the sensor is in fault condition, an mA output test cannot be performed.
mA output test
forces the transmitter to produce a user-
frequency/pulse output test
mA output trim
allows adjustment of the primary and
forces the transmitter
66
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
continued
Troubleshooting
Figure 7-2. HART® Communicator, ProLink® PC-Interface, and AMS modem connections
Field-mount
RFT9739
PV terminals
17 and 18
Before You Begin Getting Started Mounting
Communicator loops
(same circuit as PV terminals)
HART
Communicator,
ProLink PCI,
or AMS modem
PV+
Communicator loops
or PV terminals
PV–
R1
(Note 1)
R3
(Note 3)
R2
DCS or PLC
with internal
resistor
(Note 2)
1. If necessary, add resistance in the lo op by installing resistor R1. SMART FAMILY devices require a m ini m u m loo p resis­tance of 250 ohms. Loop resistance must not exceed 1000 ohms, regardless of the communication setup.
CAUTION
Connecting a HART device to the RFT9739 primary variable milliamp output loop could cause transmitter output error.
Pow er-Supply and
Sensor Wiring
If the primary variable (PV) analog output is being used for flow control, connecting a HART device to the output loop could cause the transmitter 4-20 mA output to change, which would affect flow control devices.
Set control devices for manual operation before connecting a HART device to the RFT9 739 primary variable milliamp output loop.
2. The DCS or PLC must be configured for an active milliamp signal.
3. Resistor R3 is required if the DCS or PLC does not have an internal resistor.
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Output Wiring Startup Troubleshooting
67
Troubleshooting
continued
7.4 Troubleshooting using the transmitter display

Not configured

Transmitter failure messages

If the transmitter has a display, use the message screen and refer to the following sections to troubleshoot the flowmeter:
• Overrange and sensor error messages
• Transmitter failure messages
• Slug flow and output saturated messages
• Informational messages
After the user performs a master reset, the message display reads "NOT CONFIGURED", indicating the flowmeter requires complete characterization and reconfiguration. Use a HART Communicator or the ProLink program to configure the transmitter. To perform a master reset,
Section 7.8
see
, page 76.
If a transmitter failure occurs, the display produces one of the following messages:
• "Xmtr Failed"
• "(E)eprom Error "
• "RAM Error"
•"RTI Error"
Table 7-3
describes transmitter failure messages.
CAUTION
Transmitter failures are critical, and could cause unintentional switching of process control devices.
The transmitter does not have any parts that are serviceable by the us er. If a transmitt er failure is indicated, phone the Micro Motion Customer Service Department:
• In the U.S.A., phone 1-800-522-6277, 24 hours
• Outside the U.S.A., phone 303-530-8400, 24 hours
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155
Table 7-3. Using transmitter failure messages
Message Condition Corrective action
Xmtr Failed Transmitter hard ware failure Phone the Micro Motion Customer Servi ce De partment: (E)EPROM error EPROM checksum failure RAM Error RAM diagnostic failure RTI Error Real-time interrupt failure
• In the U.S.A., phone 1-800-522-6277, 24 hours
• Outside the U.S.A., phone 303-530-8400, 24 hour s
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155
68
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Troubleshooting
continued
Before You Begin Getting Started Mounting
Overrange and sensor error messages

Slug flow

If a sens or f a ilure occur s, if t he sen sor c ab le is f aul ty, or if measur ed fl ow, measured temperature, or measured density go outside the sensor limits, the display produces one of the following messages:
• "Sensor Error"
• "Drive Overrng"
• "Input Overrange"
• "Temp Overrange"
• "Dens Overrng" To interpret overrange and sensor error messages, use the transmitter's
fault output levels, a digital multimeter (DMM) or other reference device, and refer to
Table 7-4
for corrective actions.
Unplug terminal blocks from the transmitter electronics module to check circuits.
Programmed slug flow limits enable transmitter outputs and the display to indicate conditions such as slug flow (gas slugs in a liquid flow stream). Such conditions adversely affect sensor performance by causing erratic vibration of the flow tubes, which in turn causes the transmitter to produce inaccurate flow signals.
If the user programs slug limits, a slug flow condition causes the following to occur:
1. The message display reads "SLUG FLOW".
2. The frequency/pulse output goes to 0 Hz.
3. mA outputs indicating flow rate go to the level that represents zero flow .
Pow er-Supply and
Sensor Wiring

Output saturated messages

The flowmeter resumes normal operation when liquid fills the flow tubes and when density stabilizes within the programmed slug flow limits.
The user can also program a slug duration, from 0 to 60 seconds, into the configuration of an RFT9739. If process density goes outside a slug flow limit, flow outputs hold their last measured value for the period of time established as the slug duration.
Table 7-5
summarizes possible slug flow errors and lists typical
corrective actions.
If an output variable exceeds its upper range limit, the display message reads "Freq Overrange", "mA 1 Saturated" or "mA 2 Saturated". The message can mean the output variable has exceeded appropriate limits for the process, or can mean the user needs to change measurement units.
Table 7-5
summarizes possible output saturated messages and lists
typical corrective actions.
Output Wiring Startup Troubleshooting
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
69
continued
Troubleshooting
Table 7-4. Using overrange and sensor error messages
Instructions
1. Turn off power to the transmitter.
2. Unplug termin al blocks from transm itt er ele ctr oni cs module to check circuits
Message Other symptoms Causes Corrective actions
Drive Overrng or Input Overrange
Sensor Error • Transmitter prod uces fault outputs
Drive Overrng or Dens Overrng
Temp Overrange • Tran sm it te r pr oduces fault outputs
• Transmitter produces fault outputs
• At the transmitter, DMM indicates open or short circu it f rom r ed wire to brown wire
• At the sensor, DMM indicates open or short circuit from red wire to brown wire
• Transm i t te r produces fault outputs
• At the transmitter, DMM indicates open or short circu it f rom gre en wi r e to w hi te wire
• At the sensor, DMM indicates open or short circuit from green wire to wh ite wi re
• At the transmitter, DMM indicates open or short circu it f rom blue wir e to gray wire
• At the sensor, DMM indicates open or short circuit from blue wire to gray wire
Transmitter produces fault outputs • Moisture i n sensor
Transmitter produces fault outputs • Inappropriate density
• At the transmitter, DMM indicates open or short circuit from yellow wire to orange wire
• At the sensor, DMM indicates open or short circuit from yellow wire to orange wire
• Transm i t te r produces fault outputs
• At the transmitter, DMM indicates open or short circuit from violet wire to yellow wire
• At the sensor, DMM indicates open or short circuit from violet wire to yellow wire
• Flow rate outside sensor limit
• Faulty cab l e
• Open or short drive coil in sensor
• Flow rate outside sensor limit
• Faulty cab l e
• Open or short left pickoff in sensor
• Faulty cab l e
• Open or short right pickoff in sensor
case
factors
• Process density > 5.0000 g/cc
• Severely erratic or complete cessatio n of flow tube vibration due to gas slugs or solids in process fluid
• Plugged flow tube
• Temperature outside sensor limit
• Faulty cab l e
• Open or short lead length compensator
• Faulty cab l e
• Open or short RTD in sensor
• Fill sensor with process fluid
• Bring flow rate within sensor limit
• Monitor flow rate
• If open or short at transmitter, reconnect wiring or repair cable
• If open or short at sensor, return sensor to Micro Motion
• If open or short at transmitter, reconnect wiring or repair cable
• If open or short at sensor, return sensor to Micro Motion
• Replace conduit and/or conduit seals
• Repair cable
• Return sensor to Micro Motion
• Calibrate for density
• Correct density factors
• Monitor density
• Bring density within sensor limit
• Purge flow tubes with steam, water, or purging chemical
• Bring temperature within sensor limit
• Monitor temperature
• If open or short at transmitter, reconnect wiring or repair cable
• If open or short at sensor, return sensor to Micro Motion
Table 7-5. Using slug flow and output saturated messages
Message Condition Correctiv e action(s)
Slug flow • Gas slugs causing process den si t y to go below low slug flow limit
Freq overrange Flow rate driving output from terminals 15 (FREQ+) and
mA 1 saturated Outpu t fro m terminals 17 (PV+) and 18 (PV–) = 0, 3.8, or 20.5 mA • Change value of variable at 20 mA mA 2 saturated Output from terminals 19 (SV+) and 20 (SV–) = 0, 3.8, or 20.5mA
70
• Solids causing process den sit y to go above high slug flow limit
16 (RETURN) to 0 or 15 kHz
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
• Monitor density
• Enter new slug flow limits
• Enter new slug duration
• Change flow measurement uni ts
• Rescale frequency/pulse output
• Reduce flow rate
• Alter fluid process
Troubleshooting
continued
Before You Begin Getting Started Mounting

Informational messages

Information messages are described below.
Table 7-6
summarizes
informational messages and lists typical corrective actions.
Power Reset
indicates a power failure, brownout, or power cycle has interrupted operation of the transmitter. The transmitter has a nonvolatile memory, which remains intact despite power interruptions.
Cal in Progress
indicates flowmeter zeroing in progress or density
calibration in progress.
Zero Too Noisy
indicates mechanical noise has prevented the transmitter from setting an accurate zero flow offset during transmitter zeroing.
Zero Too High or Zero Too Low
indicates flow was not completely shut off during sensor zeroing, so the transmitter has calculated a zero flow offset that is too great to allow accurate flow measurement. Zero Too Low indicates the zero flow offset is negative.
Burst Mode
indicates the user has configured the transmitter to send data in burst mode while operating under HART protocol. In burst mode, the transmitter sends data at regular intervals.
mA 1 Fixed or mA 2 Fixed
indicates one of several conditions:
• The mA output trim or test was not completed. The output remains
fixed at the assigned level until the user completes the output trim or test procedure.
• The user has assigned a polling address other than 0 to the transmitter
for Bell 202 communication. The output remains fixed at 4 mA until the user assigns the transmitter a polling address of 0.
Pow er-Supply and
Sensor Wiring
Event 1 On or Event 2 On
output switches the output ON.
• With mass or volume total assigned to the event, the event switches
ON and OFF according to the low or high configuration of the alarm. With a LOW alarm, the event switches ON when the user resets the totalizer. With a HIGH alarm, the event switches OFF when the user resets the totalizer.
• With flow, density, temperature, or pressure assigned to the event, the
event switches OFF or ON whenever the process variable crosses the setpoint.
Security Breach
changed from security mode 8. Clear the message by reentering security mode 8 or by performing a master reset.
Error Cleared
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
switches ON if an event tied to an RFT9739
Output Wiring Startup Troubleshooting
indicates the transmitter security mode has been
indicates a previous message has been cleared.
71
continued
Troubleshooting
Table 7-6. Using informational messages
Message Condition Corrective action(s)
Pow er Reset • Power failur e
Cal in Progress • Flowmeter zeroing in progress
Zero Too Noisy Mechanical noise prevented accurate zero flow
Zero Too High Zero Too Low
Burst Mode Transmitter configured to send data in burst mode
mA 1 Fixed Communi cation failure during test or trim of mA
mA 2 Fixed Communi cation failure during test or trim of
Event 1 On Event (alarm) 1 is ON • If totalizer assigned: Event 2 On Event (alarm) 2 is ON
Security Breach Security mode change d f ro m mo de 8 • Re-enter security mode 8
•Brownout
• Power cycling
• Density calibration in progress
setting during auto zero Flow not completely shut off during auto zero Completely shut off flow, then rezero Moisture in sensor junct i on box caused zero drift Ensure interior of junction box is completely dr y,
under HART protocol
output from term inal s 17 (PV+) and 18 (PV–) Polling address of 1 to 15 assigned to RFT9739
for HART in Bell 202
output from term inal s 19 (SV+) and 20 (SV–)
Check accuracy of totalizers
• If Cal in Progress disappears, no action
• If Cal in Progress reappears after zeroing is completed:
-
Check flowmeter cable
-
Eliminate noise, then rezero or recalibrate
Eliminate mechanical noise, if possible, then rezero
then rezero Switch burst mode OFF
Complete trim or test
• Change polling address to zero (0)
• Use RS-485 communicat ion st andard
Complete trim or test
-
Low alarm switches event ON at totalizer reset
-
High alarm switches event OFF at totalizer reset
• If other variable assigned, event switches ON/OFF when variable crosses setpo in t
• Perf orm master reset
72
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Troubleshooting
continued
Before You Begin Getting Started Mounting

7.5 Power supply

7.6 Wiring

Check for specified power at the transmitter terminals.
• If the transmitter power terminals are labeled "L" (line) and "N" (neutral), the transmitter accepts an 85-250 VAC power supply.
• If the transmitter power terminals are labeled "+" (positive) and "–" (negative), the transmitter accepts a 12-30 VDC power supply.
• Check all fuses.
For transmitter wiring instructions, refer to and Sensor Wiring," page 15; and
Chapter 5
Chapter 4
, "Power-Su ppl y
, "Output Wiring," page 25.
Wiring problems are often incorrectly diagnosed as a faulty sensor. At initial startup of the transmitter, always check the following:
1. Proper sensor cable, and use of shielded pairs
2. Proper wire termination
a. Wires on correct terminals b. Wires making good connections at transmitter terminals c. Wires making good connections at the sensor terminals d. Wires properly connected at any intermediate terminal junction,
such as the user-supplied junction box between a Model DT sensor and transmitter
If a fault condition is indicated, follow these instructions:
1. Disconnect the transmitter's power supply.
2. Unplug the terminal blocks from the transmitter electronics module.
3. Use a digital multimeter (DMM) to measure resistance between wire
pairs at the transmitter terminals:
• Drive coil, check terminals 1 and 2 (brown and red)
• Left pickoff coil, check terminals 5 and 9 (green and white)
• Right pickoff coil, check terminals 6 and 8 (blue and gray)
• RTD, check RFT9739 terminals 3 and 7 (yellow and violet)
4. If the measured resistance is outside the range listed in
Table 7-7
,
repeat the measurements at the sensor terminals.
5. Reinsert the terminal blocks and restore power to the transmitter.
6. Use the DMM to troubleshoot the flowmeter.
Pow er-Supply and
Sensor Wiring
Output Wiring Startup Troubleshooting
Table 7-7. Normal resistance for flowmeter circuits
Notes
• Te m perat ure sensor value increases 0.3867 5 oh ms per °C increase in temperatur e.
• Nominal resistance values will vary 40% per 100°C. However, confirming an open coil or shorted coil is more impor tant than any slight deviation from the resistance values pre sented below.
• Resistance across terminals 6 and 8 (right pickoff) should be w i th in 10% of re si st ance across terminals 5 and 9 (left pickoff).
• Resistance values depend on the sensor model and date of manufacture.
Circuit Wire colors Sensor terminals Nominal resistance range
Drive coil Brown to red 1 to 2 8 to 2650 Left pickoff Green to white 5 to 9 15.9 to 300 Right pickoff Blue to gray 6 to 8 15.9 to 300 Temperature sensor Orange to violet 3 to 7 100Ω at 0°C + 0.38675Ω per °C Lead length compensat or Yel low to vio le t 4 to 7 100Ω at 0°C + 0.38675Ω per °C
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
Ω Ω
73
Troubleshooting
continued

7.7 Master reset

CAUTION
All configuration data will be lost by performing a master reset.
Before performing a master reset, phone the Mi cro Mot ion Customer Service Departme nt:
• In the U.S.A., phone 1-800-522-6277, 24 hours
• Outside the U.S.A., phone 303-530-8400, 24 hours
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155
Use the switches on the transmitter electronics module to perform a master re set. A mast er res et ca uses comm unic ation opti ons to default to the setup used by HART Communicators, causes all other configuration options to return to their default values, and
characterization and reconfiguration of the transmitter.
Table 7-8
lists master reset defaults for characterization and
configuration variables. To perform a master reset:
1. Note the position of switch 5.
2. Shut off power to the transmitter.
3. Set switches 1, 2, and 3 to the OFF position.
4. Set switches 4, 5, 6, and 10 to the ON position.
5. Restore power. Wait until the diagnostic LED blinks ON three times followed by a 1-second pause.
6. Set switches 4, 6, and 10 to the OFF position.
7. Return switch 5 to its original position.
8. Shut off power to the transmitter. Wait 30 seconds.
9. Restore power.
requires complete
74
If switches are left in the ON position, another master reset will occur the next time power to the transmitter is shut off and then restored.
an unintentional master reset
, set switches 4, 6, and 10 to the OFF
T o avoid
position after performing a master reset. After the user performs a master reset, the diagnostic LED on the
electronics module blinks ON four times per second until the user characterizes the transmitter to the sensor. To characterize the sensor and configure the transmitter, use a HAR T communicator, the ProLink program, or a Modbus host. For more information, see
Section 2.2
, page 4. After characterization is completed, the LED blinks ON once per second to indicate normal operation.
If the transmitter has a display, the blinking "Msg" indicator appears in the lower right corner to indicate the presence of a status message. If the user scrolls to the message screen, it reads "NOT CONFIGURED", indicating the transmitter memory contains default variables. After characterization is completed, the message screen reads "Sensor OK *ERROR CLEARED*", and the transmitter is ready for normal operation.
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
continued
Troubleshooting
Table 7-8. Default values after a master reset
Character i zation variables
Default Default
Flow calibration factor 1.00005.13 Mass flow factor 1.0 Density Volume flow factor 1.0
Density A 0.0000 g/cc Density factor 1.0 K1 density constant 5000.00 Pressure Density B 1.0000 g/cc Pressure polling No K2 density constant 50000.00 Field device tag DP CELL! Density temperature coeff i ci ent 4.44% p er 100° C Pressure input at 4 m A 0 .0 0 psi FD density constant 0.000 Pressure input at 20 mA 1000.00 psi
Temperature calibration factor 1.00000T0000.0 Pressure correction for flow 0.00% per psi
Pressure correction for density 0.00 g/cc per psi Flow calibration pressure 0.00 psi
Measurement units
Default Default
Mass flow unit g/sec Temperature unit °C Volume flow unit l/s ec Pressure un it psi Density unit g/cc
Before You Begin Getting Started Mounting
Field device variables
Default Default
Mass flow cutoff 0.00 g/sec Low slug flow limit 0.0000 g/cc Volume flow cutof f 0.0000 l/sec High slug flow limit 5.0000 g/cc Flow direction Forward only Internal da m pi ng o n density 2.00 sec Internal damp ing on flow 0.80 sec Internal da m pi ng on temperature 4.00 sec
Transmitter output variables
Default Default
Primary m A output variable M ass flow Frequency/pulse output variable Mass flow Upper range value 160.00 g/sec Frequency 10000.00 Hz Lower range value –160.00 g/sec Rate 15000.00 g/sec Added damping 0.00 sec Maximum pulse width 0.50 sec Secondary mA output variable Temperature Control output Flow direction Upper range value 450.00°C Slug duration 1.00 sec Lower range value –240.00°C Polling address 0 Added damping 0.00 sec Burst mode Off
Device information
Default Default
Transmitter tag name Description Message
Date 01/
M. RESET CONFIGURE XMTR MASTER RESET
DATA DESTROYED
JAN
-
/1995
ALL
Sensor model Unknown Sensor flow tube material Unknown Sensor flange type Unknown Sensor flow tube liner material None
Pow er-Supply and
Sensor Wiring
Output Wiring Startup Troubleshooting
Communication settings
Default with switch 5* set to STD COMM Default with switch 5* set to USER DEF
Stop bits and parity 1 stop bit, odd parity 1 stop bit, odd parity Protocol, physical layer, baud rate HART Bell 202 on primary mA at 1200 baud,
and Modbus RTU on RS-485 at 9600 baud
HART on RS-485 at 1200 baud
* For informat i on a bout switches and switch settings, see Section 2.3, page 5 .
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
75
Troubleshooting
continued

7.8 Additional information about troubleshooting

7.9 Customer service

For more information about troubleshooting the RFT9739 transmitter, see any of the following instruction manuals or AMS on-line help:
Using the HART Communicator with Micro Motion Transmitters
Using ProLink Software with Micro Motion Transmitters
Using Modbus Protocol with Micro Motion Transmitters
For technical assistance, phone the Micro Motion Customer Service Department:
• In the U.S.A., phone 1-800-522-6277, 24 hours
• Outside the U.S.A., phone 303-530-8400, 24 hours
• In Europe, phone +31 (0) 318 549 443
• In Asia, phone 65-770-8155
76
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Appendix
A RFT9739 Specifications
Performance specifications
Sensor model Mass flow accuracy*
ELITE liquid ±0.10% ± [(zero stability / flow rate) x 100]% of rate
gas ±0.50% ± [(zero stability / flow rate) x 100]% of rate
F-Series liquid ±0.20% ± [(zero stability / flow rate) x 100]% of rate
gas ±0.70% ± [(zero stability / flow rate) x 100]% of rate
D (except DH38), DT and DL liquid ±0.15% ± [(zero stability / flow rate) x 100]% of rate
gas ±0.65% ± [(zero stability / flow rate) x 100]% of rate
DH38 liquid ±0.15% ± [(zero stability / flow rate) x 100]% of rate
gas ±0.50% ± [(zero stability / flow rate) x 100]% of rate
Sensor model Mass flow repeatability
ELITE liquid ±0.05% ± [½(zero stability / flow rate) x 100]% of rate
gas ±0.25% ± [(zero stability / flow rate) x 100]% of rate
F-Series liquid ±0.10% ± [½(zero stability / flow rate) x 100]% of rate
gas ±0.35% ± [(zero stability / flow rate) x 100]% of rate
D (except DH38), DT and DL liquid ±0.05% ± [½(zero stability / flow rate) x 100]% of rate
gas ±0.30% ± [(zero stability / flow rate) x 100]% of rate
DH38 liquid ±0.05% ± [½(zero stability / flow rate) x 100]% of rate
gas ±0.25% ± [(zero stability / flow rate) x 100]% of rate
Density ac cu racy Density repeatability
Sensor model
ELITE (except CMF010P) liquid only ±0.0005 ±0.5 ±0.0002 ±0.2 ELITE CMF010P liquid only ±0.002 ±2.0 ±0.001 ±1.0 F-Series liquid only ±0.002 ±2 .0 ±0.001 ±1.0 D6, D12, D25, D40, DH100, DH150 liquid only ±0.002 ±2.0 ±0.001 ±1.0 DH6, DH12, DH38 liquid only ±0.004 ±4.0 ±0.002 ±2.0 D65, DL65, DT65, D100, DT100,
D150, DT150, DH300 D300, D600, DL100, DL200 liquid only ±0.0005 ±0.5 ±0.002 ±2.0
Sensor model Temperat ure accuracy Temperature repeatability
All sensors ±1°C ± 0.5% of reading in °C ±0 .02°C
liquid only ±0.001 ±1.0 ±0.0005 ±0 .5
g/cc kg/m
*
3
g/cc kg/m
3
* Flow accuracy includes the combined effects of repeatability, linearity, and hysteresis. All specifications for liquids are based on
reference conditions of water at 68 to 77°F (20 to 25°C) and 15 to 30 psig (1 to 2 bar), unless otherwise noted. For values of zero
stability, refer to product speci f ic at ions for each sensor.
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
77
continued
RFT9739 Specifications
Functional specifications
Output Signals Analog
Two independently configured analog outputs, designated as primary and secondary, can represent mass or volumetric flow rate, density, temperature, event 1 or event 2. These outputs cannot be changed from active to passive. With a pressure transmitter, outputs can also provide indication for pressure. Internally powered, can be selected as 4-20 mA or 0-20 mA current outputs. Galvanically isolated to ±50 VDC, 1000 ohm load limit. Out-of-range capability: 0-22 mA on 0-20 mA output;
3.8-20.5 mA on 4-20 mA output.
Milliamp (mA) output rangeability
Flow
Maximum span determined by sensor specifications. Range limit determined by sensor maximum rate. Minimum recommended span (% of nominal flow range):
ELITE sensors 2.5% F-Series sensors 10% D, DT, and DL sensors 10% D300 and D600 sensors 5% High-pressure (DH) sensors 20% typical
Density
Range limit 0 to 5 g/cc (0 to 5000 kg/m³) Minimum span 0.05 g/cc (50 kg/m³)
Temperature
Range limit –400 to 842°F (–240 to 450°C) Minimum span 36°F (20°C)
Frequency
One frequency/pulse output can be config ured to ind icate mass flo w rate , volumetric flow rate, mass total (inventory), or volume total (inventory), independent of analog outputs. Internally powered, 0-15 V square wave, unloaded; 2.2 k ohm impedance at 15 V, galvanically isolated to In open collector configuration: sinking capability, 0.1 amps in "on" condition (0 volt level), 30 VDC compliance in "off" condition. Signal can be scaled up to 10,000 Hz. Out-of-range capability to 15,000 Hz. Programmable pulse width for low frequencies.
Control
One control output can represent flow direction, fault alarm, zero in progress, event 1 or event 2. Internally powered, digital level, 0 or 15 V,
2.2 kohm pull-up, galvanically isolated to ±50 VDC. In open collector configuration: sinking capability, 0.1 amps in "on" condition (0 volt lev el), 30 VDC compliance in "off" condition.
±50 VDC
.
78
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
RFT9739 Specifications
Additional outputs Sensor frequency
continued
Communication
Switch allows selection of preset or user-defined settings.
• Default preset-settings: HART protocol over Bell 202, on the primary mA output, 1200 baud; Modbus protocol in RTU mode, on the RS-485 output, 9600 baud; 1 stop bit, odd parity.
• Default user-defined settings: HART protocol, on the RS-485 output, 1200 baud, 1 stop bit, odd parity.
Bell 202 signal is superimposed on primary variable mA output, and is available for host system interface. Frequency 1.2 and 2.2 kHz, amplitude 0.8 V peak-to-peak, 1200 baud. Requires 250 to 1000 ohms load resistance.
RS-485 signal is a ±5 V square wave referenced to transmitter ground. Baud rates between 1200 baud and 38.4 kilobaud can be selected.
For use with Micro Motion peripheral devices, 8 V peak-to-peak at sensor natural frequency, referenced to sensor ground, 10 kohm output impedance.
Sensor temperature
For use with Micro Motion peripheral devices, 5 mV/°C, referenced to signal ground, 10 kohm output impedance.
API gravity
API gravity references to 60°F (15°C). Uses correlation based on API equation 2540 for Generalized Petroleum Products.
Accuracy of corrected density calculation relative to API-2540 from 0 to 300°F:
Process fluid g/cc kg/m
3
°API
Diesel, heater, and fuel oils ±0.0005 ±0.5 ±0.2 Jet fuels, kerosenes, and solvents ±0.002 ±2.0 ±0.5 Crude oils and JP4 ±0.004 ±4.0 ±1.0 Lube oils ±0.01 ±10 ±2.0 Gasoline and naphthenes ±0.02 ±20 ±5.0
Minimum 4-20 mA span: 10°API
Standard volume
Outputs standard volume at 60°F or 15°C for Generalized Petroleum Products when °API is selected as density unit of measure. Accuracy of standard volume measurements depends on accuracies of mass flow rate, density, temperature and temperature-corrected °API calculation, and can be estimated using the root mean square method. Standard volume accuracy of ±0.5% of rate is typically attainable for Generalized Petroleum Products such as fuel oils, jet fuels, and kerosenes.
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
79
RFT9739 Specifications
continued
Pressure compensation
The analog input can accept a signal from a pressure transmitter for pressure compensation of flow and density. Range, 0-25 mA. Can be used to power independent pressure or differential pressure transmitter. Voltage sourcing capability, 15 V. Input impedance, 100 ohms.
Low-flow cutoff
Flow values below the low-flow cutoff cause digital and frequency outputs to default to zero flow levels. Each mA output may be configured for an additional low-flow cutoff.
Slug-flow limits
Transmitter senses density outside limits. Flow output remains at last measured value, for a programmed time of 0 to 60 seconds, before defaulting to zero flow.
Damping
Wide range of programmed filter time constants for damping on flow, density, and temperature. Additional damping may be applied to mA outputs.
Fault indication
Faults can be indicated by user-selected downscale (0-2 mA, 0 Hz) or upscale (22-24 mA, 15-19 kHz) output lev els. The control output can also be configured to indicate a fault condition at 0 V.
Output testing
Output testing can be conducted with a HART Communicator, the ProLink program, a Modbus host, or AMS software.
Current source
Transmitter can produce a user-specified current between 0 and 22 mA on a 0-20 mA output, or between 2 and 22 mA on a 4-20 mA output.
Frequency source
Transmitter can produce a user-specified frequency between 0.1 and 15,000 Hz.
Local display (optional)
Display is a 2-line, 16-character, alphanumeric liquid crystal display (LCD). Using the transmitter’s scroll function, the user can view flow rate, density, temperature, mass and volume totals and inventory levels, and status messages on the LCD . A reset button allows the user to reset the transmitter’s flow totalizers and communication parameters, and perform the flowmeter zeroing procedure.
80
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
RFT9739 Specifications
continued
Power supply opti o n s and fuses
85 to 250 VAC, 48 to 62 Hz, 10 watts typical, 15 watts maximum, fused with IEC 127-3 400mA/250V, time-lag, subminiature. All AC-powered RFT9739 transmitters comply with low-voltage directive 73/23/EEC per IEC 1010-1 with Amendment 2.
12 to 30 VDC, 7 watts typical, 14 watts maximum, fused with IEC 127-3
1.6A/125V, time-lag, subminiature. At startup, transmitter power source
must provide a minimum of 1.6 amperes of short-term current at a minimum of 12 volts at the transmitter's power input terminals.
Environmental limits Ambient temperature limits
Without display
Operating: –22 to 131°F (–30 to 55°C) Storage: –40 to 176°F (–40 to 80°C)
With optional display
Operating: 14 to 131°F (–10 to 55°C) Storage: –4 to 158°F (–20 to 70°C)
Humidity limits
Meets SAMA PMC 31.1-1980
Vibration limits
Meets SAMA PMC 31.1-1980, Condition 2
Environmental effects EMI effect
Field-mount RFT9739 transmitters with enhanced EMI immunity meet the requirements of the EMC directive 89/336/EEC per EN 50081-1 (January 1992) and EN 50082-2 (March 1995) when operated at nominal rated flow measurement range. Enhanced EMI immunity is required for transmitters installed in the European Community after 1 January 1996. For specific EMC effects within the EC, the Technical EMC file may be reviewed at Fisher-Rosemount Veenendaal.
All RFT9739 transmitters meet the requirements of SAMA PMC 33.1 (October 1978), Class 1, A, B, C (0.6% span) at nominal flow rate. All RFT9739 transmitters meet the recommendations of ANSI/IEEE C62.41 (1991) for surge and EFT.
To meet the above specifications, the transmitter must be installed with an approved Micro Motion sensor, and the sensor cable must be either doubly shielded with full contact glands, or installed in continuous, fully bonded metallic conduit. The transmitter and sensor must be directly connected to a low-impedance (less than 1 ohm) earth ground. Transmitter outputs must be run in standard twisted-pair, shielded instrument wire.
Ambient temperature effect on transmitter
On mA outputs: ±0.005% of span/°C On temperature output: ±0.01°C/°C On mA input: ±0.01% of span/°C
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
81
RFT9739 Specifications
continued
Hazardous area classifications
Without display
With optional display
When properly installed with an approved sensor, the RFT9739 field­mount transmitter can be installed in the following areas:
UL and CSA
Transmitter: Class I, Div. 1, Groups C and D. Class II, Div . 1, Groups E, F, and G explosion proof when installed with approved conduit seals. Otherwise, Class I, Div. 2, Groups A, B, C, and D.
Outputs: Provides nonincendive sensor outputs for use in Class I, Div. 2, Groups A, B, C, and D; or intrinsically safe sensor outputs for use in Class I, Div. 1, Groups C and D, or Class II, Div. 1, Groups E, F, and G.
UL Division 2 nonincendive parameters for analog and frequency outputs for transmitters without or with a display are listed below.
CENELEC
EEx d [ib] IIC T6 flameproof when installed with approved cable glands. Connections to sensor are intrinsically safe in [EEx ib] IIC areas.
SAA
Exd [ib] IIC T4 IP66
UL and CSA
Transmitter: Class I, Div. 2, Groups A, B, C, and D.
UL Division 2 nonincendive parameters
Outputs: Provides nonincendive sensor outputs for use in Class I, Div. 2, Groups A, B, C, and D; or intrinsically safe sensor outputs for use in Class I, Div. 1, Groups C and D, or Class II, Div. 1, Groups E, F, and G.
UL Division 2 nonincendive parameters for analog and frequency outputs for transmitters without or with a display are listed below.
CENELEC
Safe area only. Connections to sensor are intrinsically safe in [EEx ib] IIC areas.
SAA
Ex [ib] IIC IP66
Parameter
V
OC
I
SC
C
a
L
a
Analog output
(Terminals 17- 18, 19-20)
36.5 V 16 V 22 mA 51 mA
0.135 µf1.5 100 mH 37 mH
Frequency/pulse output
(Terminals 14-16)
µ
f
82
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
RFT9739 Specifications
continued
Physical specifications
Housing
NEMA 4X (IP65) epoxy polyester painted cast aluminum
Weight
12.5 lb (5.7 kg)
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
83
84
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Appendix

B Ordering Information

RFT9739 model number matrix
Code Transmitter model
RFT9739 RFT9739 transmitter
Code Housing options
E Field mount, without display, NEMA 4X, explosion-proof D
Field mount, with display, NEMA 4X
Code Power supply
4 85 to 250 VAC 5 20 to 30 VDC
Code Configuration
S Standard E Enhanced EMI immuni ty (CE compliant) — requires install atio n w ith Mic ro Motion
cable type CPLTJ or CFEPJ installed in conduit, or type CPLTS, CPLT A, CFEPS, or CFEPA installed with appr oved cable glands
Code Approval
M Micro Motion standard — no approvals U UL intrinsically safe — U.S.A. approvals agency C CSA — Canadian approvals agency B CENELEC intrinsically safe sensor outputs — Europea n standards
F C EN ELEC intrinsically safe sensor outputs /flam eproof transmitter —
S SAA — Australian approvals agency; not available with Model DL65,
organization
European standards organization; not available with housing code D
D600, or DT sensors
Code Glands
Available with approval codes M, C, B, F, and S Available with approval code U only with housing code D
A No fittings or glands
Available only with approval code U and housing code E
J 1X explosion-proof seal fit ting (any cable) K 3X explosion-proof seal fitting (any cable)
Available only with approval code B (non-EExd)
B 1X gland, nickel-plated bra ss ( 7- 12. 5 m m ) C 3X gland, nickel-plated brass (7-12.5 mm)
Available only with approval code F (flameproof EExd) and housing c ode E
D 1X gland, nickel-plated brass (8-12 mm/10.5-16 mm) E 1X gland, SS (8-12 mm/10.5-16 mm) F 3X gland, nickel-plated brass (8-12 mm/10.5-16 mm) G 3X gland, SS (8-12 mm/10.5-16 mm)
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
85
continued
Ordering Information
Micro Motion instruction manuals
Sensors
Transmitters
Communications
•ELITE® Sensor Instruction Manual
• R-Series Flowmeter Instruction Manual
• R-Series Flowmeter with F
OUNDATION
fieldbus
• T-Series Flowmeter Instruction Manual
• F-Series Sensor Instruction Manual
• Model D and DT Sensors Instruction Manual
• Model DL Sensor Instruction Manual
•ALTUS™ Installation Manual
•ALTUS
•ALTUS
•ALTUS
• Installing Relays for the ALTUS
Detailed Setup Manual
Density Applications Manual
Net Oil Computer Manual
Applications Platform
• RFT9739 Field-Mount Transmitter Instruction Manual
• RFT9739 Rack-Mount Transmitter Instruction Manual
• IFT9701 Transmitter Instruction Manual
• Model 5300 Transmitter with F
OUNDATION
fieldbus
• RFT9709 Transmitter Instruction Manual
• RFT9712 Remote Flow Transmitter Instruction Manual
• Using ProLink® Software with Micro Motion® Transmitter s
• Using the HART
• Using Modbus
®
Communicator with Micro Motion® Transmitters
®
Protocol with Micro Motion® Transmitters
• RFT9739 Transmitter-Specific Command Specification
• RFT9709 Transmitter-Specific Command Specification
• RFT9712 Transmitter-Specific Command Specification
Peripheral products
Wiring instructions
• DMS Density Monitoring System Instruction Manual
• DRT Digital Rate Totalizer LCD Instruction Manual
• DRT Digital Rate Totalizer LED Instruction Manual
• FMS-3 Flow Monitoring System LCD Instruction Manual
• FMS-3 Flow Monitoring System LED Instruction Manual
• NFC Net Flow Computer Instruction Manual
• NOC Net Oil Computer Instruction Manual
• PI 4-20 Process Indicator
• 9-Wire Flowmeter Cable Preparation and Installation
• Cable Gland Assembly Instructions
• UL-D-IS Installation Instructions
• CSA-D-IS Installation Instructions
• SAA-D-IS Installation Instructions
• Power-Supply Wiring for the D600 Sensor
• Input Signal Wiring for Peripheral Devices
86
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Appendix

C Theory of Operation

The flow tubes of the Coriolis mass flow sensor are driven to vibrate at their natural frequency by a magnet and drive coil attached to the apex of the bent tubes (see in the transmitter reinforces the signal from the sensor’s left velocity pickoff coil to generate the drive coil voltage. The amplitude of this drive coil voltage is continuously adjusted by the circuit to maintain a constant, low amplitude of flow tube displacement, minimizing stress to the tube assembly.
Figure C-1. Coriolis mass flow sensor
Figure C-1
). An AC drive control amplifier circuit
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
87
Theory of Operation
continued
Mass flow measurement
Density measurement
The vibrating motion of the flow tube, combined with the momentum of the fluid flowing through the tubes, induces a Coriolis force that causes each flow tube to twist in proportion to the rate of mass flow through the tube during each vibrational cycle. Since one leg of the flow tube lags behind the other leg during this twisting motion, the signals from sensors on the two tube legs can be compared electronically to determine the amount of twist. The transmitter measures the time delay between the left and right pickoff signals using precision circuitry and a high frequency crystal controlled clock. This "delta time" value is digitally filtered to reduce noise and improve the measurement resolution.
Delta time is multiplied by the flow calibration factor to determine the mass flow rate. Since temperature affects flow tube stiffness, the amount of twist produced by the Coriolis force will be affected by the flow tube temperature. The measured flow rate is continuously adjusted by the transmitter, which monitors the output of a platinum element resistance temperature detector (RTD) attached to the outside surface of the flow tube. The transmitter measures the sensor temperature using a three­wire RTD bridge amplifier circuit. The voltage out of the amplifier is converted to a frequency and is digitized by a counter read by the microprocessor.
The Coriolis mass flow sensor also functions as a vibrating tube density meter. The natural frequency of the tube assembly is a function of tube stiffness, tube geometry, and the mass of the fluid the tube contains. Therefore, fluid density can be derived from a measurement of tube frequency.
API gravity
The transmitter measures the time period of each vibrational cycle using a high-frequency clock. This measurement is digitally filtered, and density is calculated using the density calibration factors for the sensor after compensating the sensed natural frequency for known changes in the tube stiffness due to operating temperature. The transmitter calculates volumetric flow by dividing the measured mass flow by the measured density.
If °API is selected as the density unit, the transmitter calculates standard volume for Generalized P etroleum Products according to API-2540. The transmitter calculates volume flow and volume total at 60°F or 15°C, depending on the temperature unit:
• If degrees Fahrenheit or degrees Rankine is selected as the temperature unit, the transmitter calculates volume at 60°F.
• If degrees Celsius or Kelvin is selected as the temperature unit, the transmitter calculates volume at 15°C.
From the operating density (fluid density at line conditions) and operating temperature of a given petroleum fluid, the standard density (density at 60°F or 15°C) can be determined directly from API thermal expansion tables, or by using API equation API-2540:
88
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Theory of Operation
continued
=
ρ
o
ρ
s*
exp[–α∆T
(1 + 0.8
α∆
T
)]
where:
ρ
= operating density
o
ρ
= standard density
s
T= α =
temperature difference from base (standard) temperature
K
/(ρs)2 +
0
K
1/ρs
, where
K
and
0
K
are constants
1
The equation is iterative, and requires significant calculation time to generate one reading. The transmitter software contains a simplification of this correlation to maximize sampling frequency of the measurement. Accuracy of the Micro Motion correlation is ±0.0005 g/cc (±0.5 kg/m
3
) relative to the API-2540 equation. After temperature correction to 60°F (15°C), the density is converted to °API by the following expression:
Degrees API = (141.5/standard specific gravity) – 131.5
The
K
and
0
K
terms in the API-2540 equation are constants
1
characteristic of different types of Generalized Petroleum Products. Separate API tables exist for crude oils, distillates, gasolines, lube oils, and other products. The correlation in the RFT9739 is based on the API constants for Generalized Petroleum Products from 2 to 95°API over an operating temperature range of 0 to 300°F. As fluid density or operating temperature extends beyond these values, the RFT9739 correlation error will increase. Density calibration must be performed in units of g/cc for the API correlation to be correct.
API standard volume
If °API is selected as the density unit, the RFT9739 automatically calculates standard volume at 60°F or at 15°C based on the following expression:
Standard volume = mass flow/standard density
Accuracy of standard volume measurement is based on the accuracies of the following factors:
• Mass rate measurement
• Operating density measurement
• Temperature measurement
• RFT9739 correlation to API tables The accuracy of each factor varies based on the process operating
conditions and fluid that is being measured. For Generalized Petroleum Products, standard volume will be accurate within ±0.5% of the flow rate. Because the temperature correction correlations for density are based on API equations, the RFT9739 standard volume output can be used only for Generalized Petroleum Products or materials that exhibit the same thermal expansion characteristics as Generalized Petroleum Products.
RFT9739 Field-Mount Tra nsm it te r Instruction Manual
89
Theory of Operation
continued
Pressure compensation
Output variables
A pressure transmitter can be connected to the RFT9739 for pressure compensation. The RFT9739 or an external source can supply power to the pressure transmitter.
If the input is configured to indicate gauge pressure, the transmitter uses the pressure input to account for effects of pressure on the flow tubes of certain sensors. Not all sensors are affected by pressure. In this mode, the pressure effect is calculated as the percent change in the flow rate per psi change in pressure and/or the amount of change in density, in g/cc, per psi change in pressure.
Measured variables can be output in a variety of ways from the RFT9739. Mass or volume flow rate can be output as an isolated 4-20 or 0-20 mA signal over either of two sets of output terminals. Alternatively, either mA output can be configured to indicate temperature, density, pressure, event 1 or event 2.
Mass or volume flow pulses from the isolated frequency output terminals can be scaled to 10,000 Hz for compatibility with PLCs, batch controllers, and totalizers.
All measured variables, including totalizers for batch and inventory, can be accessed digitally . The transmitter can use the Bell 202 physical layer at 1200 baud superimposed on the primary mA signal and/or the RS-485 physical layer at 1200 baud to 38.4 kilobaud. The transmitter can use HART protocol over the Bell 202 or RS-485 physical layer, Modbus protocol over the RS-485 physical layer, or HART over the Bell 202 layer and Modbus over the RS-485 layer.
A logic output can be programmed to indicate the flow direction, a fault alarm, or a zero in progress condition. The transmitter operational status is also indicated on the transmitter display.
90
RFT9739 Field-Mou nt Tra nsm i t t er Instr uc t io n M anual
Loading...