Micro Motion® F-Series Coriolis Flow and
Density Sensors
January 2019
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration
of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available
on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion
Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States800-522-6277U.K.0870 240 1978Australia800 158 727
1.2 Best practices................................................................................................................................... 6
1.3 Temperature limits...........................................................................................................................6
□ Make sure that the hazardous area specified on the approval tag is suitable for the
environment in which the meter will be installed.
□ Verify that the local ambient and process temperatures are within the limits of the
meter.
□ If your sensor has an integral transmitter, no wiring is required between the sensor and
transmitter. Follow the wiring instructions in the transmitter installation manual for
signal and power wiring.
□ If your transmitter has remote-mounted electronics, follow the instructions in this
manual for wiring between the sensor and the transmitter, and then follow the
instructions in the transmitter installation manual for power and signal wiring.
Table 1-1: Maximum cable lengths
Cable typeTo transmitterMaximum length
Micro Motion 9-wire9739 MVD transmitter1,000 ft (305 m)
All other MVD transmitters60 ft (18 m)
Micro Motion 4-wireAll 4-wire MVD transmitters— 1,000 ft (305 m) without
Ex-approval
— 500 ft (152 m) with IIC
rated sensors
— 1,000 ft (305 m) with IIB
rated sensors
Table 1-2: Maximum lengths for user-supplied 4-wire cable
Wire functionWire sizeMaximum length
Power (VDC)22 AWG (0.326 mm²)300 ft (91 m)
20 AWG (0.518 mm²)500NaN ft (NaN m)
18 AWG (0.823 mm²)1,000 ft (305 m)
Signal (RS-485)22 AWG (0.326 mm²) or larger 1,000 ft (305 m)
□ For optimal performance, install the sensor in the preferred orientation. The sensor will
work in any orientation as long as the flow tubes remain full of process fluid.
□ Install the meter so that the flow direction arrow on the sensor case matches the actual
forward flow of the process. (Flow direction is also software-selectable.)
1.2Best practices
The following information can help you get the most from your sensor.
• There are no pipe run requirements for Micro Motion sensors. Straight runs of pipe
upstream or downstream are unnecessary.
• If the sensor is installed in a vertical pipeline, liquids and slurries should flow upward
through the sensor. Gases should flow downward.
• Keep the sensor tubes full of process fluid.
• For halting flow through the sensor with a single valve, install the valve downstream
from the sensor.
• Minimize bending and torsional stress on the meter. Do not use the meter to align
misaligned piping.
• The sensor does not require external supports. The flanges will support the sensor in
any orientation.
1.3Temperature limits
Sensors can be used in the process and ambient temperature ranges shown in the
temperature limit graphs. For the purposes of selecting electronics options, temperature
limit graphs should be used only as a general guide. If your process conditions are close to
the gray area, consult with your Micro Motion representative.
Note
• In all cases, the electronics cannot be operated where the ambient temperature is
below -40 °F (-40.0 °C) or above 140 °F (60.0 °C). If a sensor is to be used where the
ambient temperature is outside of the range permissible for the electronics, the
electronics must be remotely located where the ambient temperature is within the
permissible range, as indicated by the shaded areas of the temperature limit graphs.
• Temperature limits may be further restricted by hazardous area approvals. Refer to the
hazardous area approvals documentation shipped with the sensor or available from the
Micro Motion web site (www.emerson.com/flowmeasurement).
6Micro Motion F-Series
-40 (-40)
-148 (-100)
T
amb
T
proc
A
B
140 (60)
-40
(-40)
662
(350)
Installation Manual
Planning
20002298January 2019
• The extended-mount electronics option allows the sensor case to be insulated without
covering the transmitter, core processor, or junction box, but does not affect
temperature ratings. When insulating the sensor case at elevated process
temperatures (above 140 °F (60.0 °C)), please ensure electronics are not enclosed in
insulation as this may lead to electronics failure.
Ambient and process temperature limits for standard-temperature models: 316L
stainless steel (S), nickel alloy C22 (H), and high pressure (P)
140 (60)
T
amb
–40 (–40)
–148 (–100)
–148
(–100)
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
140 (60)
A
B
T
proc
B
81
(27)
400
(204)
A = All available electronic options
B = Remote mount electronics only
Ambient and process temperature limits for high-temperature models: 316L stainless
steel (A), nickel alloy C22 (B)
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
A = All available electronic options
B = Remote mount electronics only
Installation Manual 7
PlanningInstallation Manual
January 201920002298
8Micro Motion F-Series
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.