Micro Motion F Operating Manual

Installation Manual
20002298, Rev CG
Micro Motion® F-Series Coriolis Flow and Density Sensors
January 2019
Safety and approval information
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 704 136
Mexico +41 (0) 41 7686
111
Argentina +54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy 8008 77334 China +86 21 2892 9000
Europe and Middle East Asia Pacific
666
France 0800 917 901 India 800 440 1468
Central & Eastern +41 (0) 41 7686
111
Russia/CIS +7 495 981 9811 South Korea +82 2 3438 4600
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
New Zealand 099 128 804
Japan +81 3 5769 6803
2
Installation Manual Contents
20002298 January 2019

Contents

Chapter 1 Planning........................................................................................................................ 5
1.1 Installation checklist.........................................................................................................................5
1.2 Best practices................................................................................................................................... 6
1.3 Temperature limits...........................................................................................................................6
Chapter 2 Mounting.......................................................................................................................9
2.1 Mount the sensor............................................................................................................................. 9
2.2 Attach extended electronics...........................................................................................................10
Chapter 3 Wiring......................................................................................................................... 13
3.1 Options for wiring...........................................................................................................................13
3.2 Connect 4-wire cable......................................................................................................................14
3.3 Connect the 9-wire cable ............................................................................................................... 18
Chapter 4 Grounding....................................................................................................................21
Chapter 5 Supplementary information.........................................................................................23
5.1 Purge the sensor case .................................................................................................................... 23
5.2 Pressure relief.................................................................................................................................24
Installation Manual 3
Contents Installation Manual
January 2019 20002298
4 Micro Motion F-Series
Installation Manual Planning
20002298 January 2019

1 Planning

1.1 Installation checklist

Make sure that the hazardous area specified on the approval tag is suitable for the
environment in which the meter will be installed.
Verify that the local ambient and process temperatures are within the limits of the
meter.
If your sensor has an integral transmitter, no wiring is required between the sensor and
transmitter. Follow the wiring instructions in the transmitter installation manual for signal and power wiring.
If your transmitter has remote-mounted electronics, follow the instructions in this
manual for wiring between the sensor and the transmitter, and then follow the instructions in the transmitter installation manual for power and signal wiring.
Table 1-1: Maximum cable lengths
Cable type To transmitter Maximum length
Micro Motion 9-wire 9739 MVD transmitter 1,000 ft (305 m)
All other MVD transmitters 60 ft (18 m)
Micro Motion 4-wire All 4-wire MVD transmitters 1,000 ft (305 m) without
Ex-approval
500 ft (152 m) with IIC
rated sensors
1,000 ft (305 m) with IIB
rated sensors
Table 1-2: Maximum lengths for user-supplied 4-wire cable
Wire function Wire size Maximum length
Power (VDC) 22 AWG (0.326 mm²) 300 ft (91 m)
20 AWG (0.518 mm²) 500NaN ft (NaN m)
18 AWG (0.823 mm²) 1,000 ft (305 m)
Signal (RS-485) 22 AWG (0.326 mm²) or larger 1,000 ft (305 m)
For optimal performance, install the sensor in the preferred orientation. The sensor will
work in any orientation as long as the flow tubes remain full of process fluid.
Table 1-3: Preferred sensor orientation
Liquids
Installation Manual 5
Planning
January 2019 20002298
Table 1-3: Preferred sensor orientation (continued)
Gases
Slurries and self-draining applications
Installation Manual
Install the meter so that the flow direction arrow on the sensor case matches the actual
forward flow of the process. (Flow direction is also software-selectable.)

1.2 Best practices

The following information can help you get the most from your sensor.
There are no pipe run requirements for Micro Motion sensors. Straight runs of pipe
upstream or downstream are unnecessary.
If the sensor is installed in a vertical pipeline, liquids and slurries should flow upward
through the sensor. Gases should flow downward.
Keep the sensor tubes full of process fluid.
For halting flow through the sensor with a single valve, install the valve downstream
from the sensor.
Minimize bending and torsional stress on the meter. Do not use the meter to align
misaligned piping.
The sensor does not require external supports. The flanges will support the sensor in
any orientation.

1.3 Temperature limits

Sensors can be used in the process and ambient temperature ranges shown in the temperature limit graphs. For the purposes of selecting electronics options, temperature limit graphs should be used only as a general guide. If your process conditions are close to the gray area, consult with your Micro Motion representative.
Note
In all cases, the electronics cannot be operated where the ambient temperature is
below -40 °F (-40.0 °C) or above 140 °F (60.0 °C). If a sensor is to be used where the ambient temperature is outside of the range permissible for the electronics, the electronics must be remotely located where the ambient temperature is within the permissible range, as indicated by the shaded areas of the temperature limit graphs.
Temperature limits may be further restricted by hazardous area approvals. Refer to the
hazardous area approvals documentation shipped with the sensor or available from the Micro Motion web site (www.emerson.com/flowmeasurement).
6 Micro Motion F-Series
-40 (-40)
-148 (-100)
T
amb
T
proc
A
B
140 (60)
-40
(-40)
662
(350)
Installation Manual
Planning
20002298 January 2019
The extended-mount electronics option allows the sensor case to be insulated without
covering the transmitter, core processor, or junction box, but does not affect temperature ratings. When insulating the sensor case at elevated process temperatures (above 140 °F (60.0 °C)), please ensure electronics are not enclosed in insulation as this may lead to electronics failure.
Ambient and process temperature limits for standard-temperature models: 316L stainless steel (S), nickel alloy C22 (H), and high pressure (P)
140 (60)
T
amb
–40 (–40)
–148 (–100)
–148
(–100)
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
140 (60)
A
B
T
proc
B
81 (27)
400
(204)
A = All available electronic options B = Remote mount electronics only
Ambient and process temperature limits for high-temperature models: 316L stainless steel (A), nickel alloy C22 (B)
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
A = All available electronic options B = Remote mount electronics only
Installation Manual 7
Planning Installation Manual
January 2019 20002298
8 Micro Motion F-Series
Installation Manual
20002298 January 2019
Mounting

2 Mounting

2.1 Mount the sensor

Use your common practices to minimize torque and bending load on process connections.
About this task
Tip
To reduce the risk of condensation problems, do not orient transmitters or sensor junction boxes with their conduit openings pointing upward.
CAUTION Do not lift the sensor by the electronics or purge connections. Lifting the sensor by the electronics or purge connections can damage the device.
Figure 2-1: Mounting the sensor
Notes
Do not use the sensor to support the piping.
The sensor does not require external supports. The flanges will support the sensor in
any orientation.
Installation Manual 9
G
H
E
D
C
A
B
F
Mounting
January 2019 20002298
Installation Manual

2.2 Attach extended electronics

If your installation has a sensor with extended electronics, you will need to install the extender onto the sensor case.
About this task
Note
Extended core processors are matched at the factory to specific sensors. Keep each core processor together with the sensor with which it was shipped.
CAUTION Keep the extender and feedthrough clean and dry. Moisture or debris in the extender or feedthrough can damage electronics and result in measurement error or flowmeter failure.
Procedure
1. Remove and recycle the plastic cap from the feedthrough on the sensor.
Figure 2-2: Feedthrough and extender components
A. Transmitter or core processor B. Extender C. O-ring
D. Feedthrough
E. Clamping ring
F. Clamping screw G. Plastic plug H. Plastic cap
2. Loosen the clamping screw and remove the clamping ring. Leave the O-ring in place on the feedthrough.
10 Micro Motion F-Series
3. Remove and recycle the plastic plug from the extender.
Installation Manual Mounting
20002298 January 2019
4. Fit the extender onto the feedthrough by carefully aligning the notches on the bottom of the extender with the notches on the feedthrough.
5. Close the clamping ring and tighten the clamping screw to 13 in lbf (1.47 N m) to 18 in lbf (2.03 N m).
Installation Manual 11
Mounting Installation Manual
January 2019 20002298
12 Micro Motion F-Series
Installation Manual
20002298 January 2019
Wiring

3 Wiring

3.1 Options for wiring

The wiring procedure you follow depends on which electronics option you have.
Table 3-1: Wiring procedures by electronics option
Electronics option Wiring procedure
Integral transmitter The transmitter is already connected to the sensor. No wiring is
required between sensor and transmitter. See the transmitter installation manual for wiring the power and signal cable to the transmitter.
Extended electronics The electronics are separated from the sensor by an extender and
must be attached as described in Attach extended electronics. There is no wiring required because the physical connection includes the electrical connection.
MVD™ Direct Connect
There is no transmitter to wire. See the Micro Motion MVD Direct Connect Meters manual for wiring the power and signal cable between the sensor and the direct host.
Integral core processor with remote transmitter
Remote core processor attached to transmitter
Remote core processor separate from transmitter –
double-hop
The core processor is already connected to the sensor. Connect a 4-wire cable between the core processor and transmitter. Refer to Connect 4-wire cable.
Connect a 9-wire cable between the sensor and the transmitter/ core processor. Refer to Connect the 9-wire cable , as well as the Micro Motion Micro Motion 9-Wire Flowmeter Cable Preparation and Installation Guide.
Connect a 4-wire cable between the core processor and
transmitter. Refer to Connect 4-wire cable.
Connect a 9-wire cable between the sensor and the core
processor. Refer to Connect the 9-wire cable , as well as the Micro Motion Micro Motion 9-Wire Flowmeter Cable Preparation
and Installation Guide
DANGER Make sure the hazardous area specified on the sensor approval tag is suitable for the environment in which the sensor will be installed. Failure to comply with the requirements for intrinsic safety in a hazardous area could result in an explosion.
CAUTION Fully close and tighten all housing covers and conduit openings. Improperly sealed housings can expose electronics to moisture, which can cause measurement error or flowmeter failure. Inspect and grease all gaskets and O-rings.
Installation Manual 13
Wiring
January 2019 20002298
Installation Manual

3.2 Connect 4-wire cable

3.2.1 4-wire cable types and usage

Micro Motion offers two types of 4-wire cable: shielded and armored. Both types contain shield drain wires.
The cable supplied by Micro Motion consists of one pair of red and black 18 AWG (0.823 mm²) wires for the VDC connection, and one pair of white and green 22 AWG (0.326 mm²) wires for the RS-485 connection.
User-supplied cable must meet the following requirements:
Twisted pair construction.
Applicable hazardous area requirements, if the core processor is installed in a
hazardous area.
Wire gauge appropriate for the cable length between the core processor and the
transmitter, or the host.
Table 3-2: Wire gauge
Wire gauge Maximum cable length
VDC 22 AWG (0.326 mm²) 300 ft (91 m)
VDC 20 AWG (0.518 mm²) 500 ft (152 m)
VDC 18 AWG (0.823 mm²) 1,000 ft (305 m)
RS-485 22 AWG (0.326 mm²) or larger 1,000 ft (305 m)

3.2.2 Prepare a cable with a metal conduit

Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Run the conduit to the sensor.
3. Pull the cable through the conduit.
4. Cut the drain wires and let them float at both ends of the conduit.
3.2.3

Prepare a cable with user-supplied cable glands

Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Pass the wires through the gland nut and gland body.
14 Micro Motion F-Series
Installation Manual
20002298 January 2019
A. Gland body B. Gland nut
3. Terminate the RS-485 shield and drain wires to the housing internal grounding screw.
4. Assemble the gland according to vendor instructions.
Wiring

3.2.4 Prepare a cable with Micro Motion-supplied cable glands

Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Pass the wires through the gland nut and clamping insert.
A. Gland nut B. Clamping insert
3. Strip the cable jacket.
Option
NPT gland type Strip 4.5 in (114 mm)
M20 gland type Strip 4.25 in (108 mm)
4. Remove the clear wrap and filler material.
5. Strip most of the shielding.
Option
NPT gland type Strip all but 0.75 in (19 mm)
M20 gland type Strip all but 0.5 in (13 mm)
6. Wrap the drain wires twice around the shield and cut off the excess drain wires.
Description
Description
A. Drain wires wrapped around shield
7. For foil (shielded cable) only:
Installation Manual 15
Wiring
January 2019 20002298
Installation Manual
Note
For braided (armored cable) skip this step and contine to the next step.
Option Description
NPT gland type
a. Slide the shielded heat shrink over the drain wires. Ensure that
the wires are completely covered.
b. Apply 250 °F (121.1 °C) heat to shrink the tubing. Do not burn
the cable.
c. Position the clamping insert so the interior end is flush with the
braid of the heat shrink.
A. Shielded heat shrink B. After heat is applied
M20
Trim 0.3 in (8 mm). gland type
A. Trim
8. Assemble the gland by folding the shield or braid back over the clamping insert and
0.125 in (3 mm) past the O-ring.
A. Shield folded back
9. Install the gland body into the conduit opening on the core processor housing.
10. Insert the wires through the gland body and tighten the gland nut onto the gland body.
A. Shield folded back B. Gland body
16 Micro Motion F-Series
A
B
D
C
AA
Installation Manual
20002298 January 2019
Wiring

3.2.5 Connect the wires to the core processor terminals

After the 4-wire cable has been prepared and shielded (if required), connect the individual wires of the 4-wire cable to the terminals on the core processor.
Procedure
1. Connect the wires to the core processor terminals.
If you are connecting to a standard core processor, use the following image and
connections:
A. Terminal 1 (Power supply +): Red wire B. Terminal 2 (Power supply -): Black wire C. Terminal 3 (RS-485/A): White wire
D. Terminal 4 (RS-485/B): Green wire
Installation Manual 17
D
A
B
C
Wiring
January 2019 20002298
If you are connecting to an enhanced core processor, use the following image
and connections:
Installation Manual
A. Terminal 1 (Power supply +): Red wire B. Terminal 2 (Power supply -): Black wire C. Terminal 3 (RS-485/A): White wire
D. Terminal 4 (RS-485/B): Green wire
2. Reinstall the core processor cover.
3. Torque the cover screws to:
10 in lbf (1.13 N m) to 13 in lbf (1.47 N m) for an aluminum housing
minimum 19 in lbf (2.15 N m) for a stainless steel housing
If properly seated, there will be no gap between cover and base.
4. Connect the wires to the transmitter terminals using the transmitter installation manual.

3.3 Connect the 9-wire cable

Procedure
1. Prepare and install the cable according to the instructions in the Micro Motion 9-Wire Flowmeter Cable Preparation and Installation Guide.
2. Insert the stripped ends of the individual wires into the terminal blocks of the junction box. Ensure that no bare wires remain exposed.
3. Match the wires color for color. For wiring at the transmitter or remote core processor, refer to the transmitter documentation.
18 Micro Motion F-Series
4. Tighten the screws to hold the wires in place.
Installation Manual Wiring
20002298 January 2019
5. Ensure integrity of gaskets, then tightly close and seal the junction box cover and all housing covers.
6. Refer to the transmitter installation manual for signal and power wiring instructions.
Installation Manual 19
Wiring Installation Manual
January 2019 20002298
20 Micro Motion F-Series
Installation Manual
20002298 January 2019
Grounding

4 Grounding

The meter must be grounded according to the standards that are applicable at the site. The customer is responsible for knowing and complying with all applicable standards.
Prerequisites
Use the following guides for grounding practices:
In Europe, IEC 79-14 is applicable to most installations, in particular Sections 12.2.2.3
and 12.2.2.4.
In the U.S.A. and Canada, ISA 12.06.01 Part 1 provides examples with associated
applications and requirements.
If no external standards are applicable, follow these guidelines to ground the sensor:
Use copper wire, 14 AWG (2.08 mm²) or larger wire size.
Keep all ground leads as short as possible, less than 1 Ω impedance.
Connect ground leads directly to earth, or follow plant standards.
CAUTION Ground the flowmeter to earth, or follow ground network requirements for the facility. Improper grounding can cause measurement error.
Procedure
Check the joints in the pipeline.
If the joints in the pipeline are ground-bonded, the sensor is automatically
grounded and no further action is necessary (unless required by local code).
If the joints in the pipeline are not grounded, connect a ground wire to the
grounding screw located on the sensor electronics.
Tip
The sensor electronics may be a transmitter, core processor, or junction box. The grounding screw may be internal or external.
Installation Manual 21
Grounding Installation Manual
January 2019 20002298
22 Micro Motion F-Series
Installation Manual Supplementary information
20002298 January 2019

5 Supplementary information

5.1 Purge the sensor case

Prerequisites
Make sure the following are available before beginning the purge procedure:
Teflon™ tape
Argon or nitrogen gas sufficient to purge the sensor case
About this task
Whenever a purge plug is removed from the sensor case, you must repurge the case.
Procedure
1. Shut down the process, or set control devices for manual operation. Before performing the case purging procedure, shut down the process or set the control devices for manual operation. Performing the purge procedure while the flowmeter is operating could affect measurement accuracy, resulting in inaccurate flow signals.
2. Remove both purge plugs from the sensor case. If purge lines are being used, open the valve in the purge lines.
DANGER
Stay clear of the rupture disk pressure relief area. High-pressure fluid
escaping from the sensor can cause severe injury or death. The sensor must be oriented so that personnel and equipment will not be exposed to any discharge along the pressure relief path.
Take all necessary precautions when removing purge plugs. Removing a
purge plug compromises the secondary containment of the sensor and could expose the user to process fluid.
Improper pressurization of the sensor case could result in personal injury.
CAUTION Be sure to use thread protectors when removing the purge fitting so as not to damage the disk membrane surrounding the rupture disk.
3. Prepare the purge plugs for reinstallation by wrapping them with 2–3 turns of Teflon tape.
4. Connect the supply of nitrogen or argon gas to the inlet purge connection or open inlet purge line. Leave the outlet connection open.
Exercise caution to avoid introducing dirt, moisture, rust, or other contaminants
into the sensor case.
If the purge gas is heavier than air (such as argon), locate the inlet lower than the
outlet, so that the purge gas will displace air from bottom to top.
Installation Manual 23
Supplementary information Installation Manual
January 2019 20002298
If the purge gas is lighter than air (such as nitrogen), locate the inlet higher than
the outlet, so that the purge gas will displace air from top to bottom.
5. Make sure that there is a tight seal between the inlet connection and sensor case, so that air cannot be drawn by suction into the case or purge line during the purging process.
6. Run purge gas through the sensor.
The purge time is the amount of time required for full exchange of atmosphere to inert gas. The larger the line size, the greater amount of time is required to purge the case. If purge lines are being used, increase the purge time to fill the additional volume of the purge line.
Note
Keep the purge gas pressure below 7.25 psi (0.5 bar).
Table 5-1: Purge time
Sensor model Purge rate Time, in minutes
F025 20 ft3/h (566.3 l/h) 4 1/2
F050 20 ft3/h (566.3 l/h) 4 1/2
F100 20 ft3/h (566.3 l/h) 6
F200 20 ft3/h (566.3 l/h) 15
F300 20 ft3/h (566.3 l/h) 25
7. At the appropriate time, shut off the gas supply, then immediately seal the purge outlet and inlet connections with the purge plugs.
Avoid pressurizing the sensor case. If pressure inside the case elevates above atmospheric pressure during operation, the flowmeter density calibration will be inaccurate.
8. Make sure that the purge fitting seals are tight so that air cannot be drawn by suction into the sensor case.

5.2 Pressure relief

F-Series sensors, except high-temperature (base model codes A and B), are available with a rupture disk installed on the case. Rupture disks are meant to vent process fluid from the sensor case in the unlikely event of a flow tube breach. Some users connect a pipeline to the rupture disk to help contain escaping process fluid. For more information about rupture disks, contact Micro Motion Customer Service.
If the sensor has a rupture disk, it should remain installed at all times as it would otherwise be necessary to re-purge the case. If the rupture disk is activated by a tube breach, the seal in the rupture disk will be broken, and the Coriolis meter should be removed from service.
The rupture disk is located as follows on the meter, and the warning sticker shown is placed next to it.
24 Micro Motion F-Series
Installation Manual Supplementary information
20002298 January 2019
DANGER Stay clear of the rupture disk pressure relief area. High-pressure fluid escaping from the sensor can cause severe injury or death.
The sensor must be oriented so that personnel and equipment will not be exposed to any discharge along the pressure relief path.
Important
If a rupture disk is used, the housing can no longer assume a secondary containment function.
WARNING Removing the Purge Fitting, Blind Plug, or Rupture Disks compromises the Ex-i Safety Certification, the Ex-tc Safety Certification, and the IP-rating of the Coriolis meter. Any modification to the Purge Fitting, Blind Plug, or Rupture Disks must maintain a minimum of IP66/IP67 Ratings.
Installation Manual 25
*20002298*
20002298
Rev. CG
2019
Micro Motion Inc. USA
Worldwide Headquarters 7070 Winchester Circle Boulder, Colorado USA 80301 T +1 303-527-5200 T +1 800-522-6277 F +1 303-530-8459
www.emerson.com
Micro Motion Asia
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 Republic of Singapore T +65 6363-7766 F +65 6770-8003
©
2019 Micro Motion, Inc. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Automation Solutions family of companies. All other marks are property of their respective owners.
Micro Motion Europe
Emerson Automation Solutions Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 70 413 6666 F +31 (0) 318 495 556
www.micromotion.nl
Micro Motion United Kingdom
Emerson Automation Solutions Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U.K. T +44 0870 240 1978 F +44 0800 966 181
Loading...