Micro Motion F Operating Manual

Installation Manual
20002298, Rev CG
Micro Motion® F-Series Coriolis Flow and Density Sensors
January 2019
Safety and approval information
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion Customer Service department.
Emerson Flow customer service
Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States 800-522-6277 U.K. 0870 240 1978 Australia 800 158 727
Canada +1 303-527-5200 The Netherlands +31 (0) 704 136
Mexico +41 (0) 41 7686
111
Argentina +54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682
Brazil +55 15 3413 8000 Italy 8008 77334 China +86 21 2892 9000
Europe and Middle East Asia Pacific
666
France 0800 917 901 India 800 440 1468
Central & Eastern +41 (0) 41 7686
111
Russia/CIS +7 495 981 9811 South Korea +82 2 3438 4600
Egypt 0800 000 0015 Singapore +65 6 777 8211
Oman 800 70101 Thailand 001 800 441 6426
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444 0684
New Zealand 099 128 804
Japan +81 3 5769 6803
2
Installation Manual Contents
20002298 January 2019

Contents

Chapter 1 Planning........................................................................................................................ 5
1.1 Installation checklist.........................................................................................................................5
1.2 Best practices................................................................................................................................... 6
1.3 Temperature limits...........................................................................................................................6
Chapter 2 Mounting.......................................................................................................................9
2.1 Mount the sensor............................................................................................................................. 9
2.2 Attach extended electronics...........................................................................................................10
Chapter 3 Wiring......................................................................................................................... 13
3.1 Options for wiring...........................................................................................................................13
3.2 Connect 4-wire cable......................................................................................................................14
3.3 Connect the 9-wire cable ............................................................................................................... 18
Chapter 4 Grounding....................................................................................................................21
Chapter 5 Supplementary information.........................................................................................23
5.1 Purge the sensor case .................................................................................................................... 23
5.2 Pressure relief.................................................................................................................................24
Installation Manual 3
Contents Installation Manual
January 2019 20002298
4 Micro Motion F-Series
Installation Manual Planning
20002298 January 2019

1 Planning

1.1 Installation checklist

Make sure that the hazardous area specified on the approval tag is suitable for the
environment in which the meter will be installed.
Verify that the local ambient and process temperatures are within the limits of the
meter.
If your sensor has an integral transmitter, no wiring is required between the sensor and
transmitter. Follow the wiring instructions in the transmitter installation manual for signal and power wiring.
If your transmitter has remote-mounted electronics, follow the instructions in this
manual for wiring between the sensor and the transmitter, and then follow the instructions in the transmitter installation manual for power and signal wiring.
Table 1-1: Maximum cable lengths
Cable type To transmitter Maximum length
Micro Motion 9-wire 9739 MVD transmitter 1,000 ft (305 m)
All other MVD transmitters 60 ft (18 m)
Micro Motion 4-wire All 4-wire MVD transmitters 1,000 ft (305 m) without
Ex-approval
500 ft (152 m) with IIC
rated sensors
1,000 ft (305 m) with IIB
rated sensors
Table 1-2: Maximum lengths for user-supplied 4-wire cable
Wire function Wire size Maximum length
Power (VDC) 22 AWG (0.326 mm²) 300 ft (91 m)
20 AWG (0.518 mm²) 500NaN ft (NaN m)
18 AWG (0.823 mm²) 1,000 ft (305 m)
Signal (RS-485) 22 AWG (0.326 mm²) or larger 1,000 ft (305 m)
For optimal performance, install the sensor in the preferred orientation. The sensor will
work in any orientation as long as the flow tubes remain full of process fluid.
Table 1-3: Preferred sensor orientation
Liquids
Installation Manual 5
Planning
January 2019 20002298
Table 1-3: Preferred sensor orientation (continued)
Gases
Slurries and self-draining applications
Installation Manual
Install the meter so that the flow direction arrow on the sensor case matches the actual
forward flow of the process. (Flow direction is also software-selectable.)

1.2 Best practices

The following information can help you get the most from your sensor.
There are no pipe run requirements for Micro Motion sensors. Straight runs of pipe
upstream or downstream are unnecessary.
If the sensor is installed in a vertical pipeline, liquids and slurries should flow upward
through the sensor. Gases should flow downward.
Keep the sensor tubes full of process fluid.
For halting flow through the sensor with a single valve, install the valve downstream
from the sensor.
Minimize bending and torsional stress on the meter. Do not use the meter to align
misaligned piping.
The sensor does not require external supports. The flanges will support the sensor in
any orientation.

1.3 Temperature limits

Sensors can be used in the process and ambient temperature ranges shown in the temperature limit graphs. For the purposes of selecting electronics options, temperature limit graphs should be used only as a general guide. If your process conditions are close to the gray area, consult with your Micro Motion representative.
Note
In all cases, the electronics cannot be operated where the ambient temperature is
below -40 °F (-40.0 °C) or above 140 °F (60.0 °C). If a sensor is to be used where the ambient temperature is outside of the range permissible for the electronics, the electronics must be remotely located where the ambient temperature is within the permissible range, as indicated by the shaded areas of the temperature limit graphs.
Temperature limits may be further restricted by hazardous area approvals. Refer to the
hazardous area approvals documentation shipped with the sensor or available from the Micro Motion web site (www.emerson.com/flowmeasurement).
6 Micro Motion F-Series
-40 (-40)
-148 (-100)
T
amb
T
proc
A
B
140 (60)
-40
(-40)
662
(350)
Installation Manual
Planning
20002298 January 2019
The extended-mount electronics option allows the sensor case to be insulated without
covering the transmitter, core processor, or junction box, but does not affect temperature ratings. When insulating the sensor case at elevated process temperatures (above 140 °F (60.0 °C)), please ensure electronics are not enclosed in insulation as this may lead to electronics failure.
Ambient and process temperature limits for standard-temperature models: 316L stainless steel (S), nickel alloy C22 (H), and high pressure (P)
140 (60)
T
amb
–40 (–40)
–148 (–100)
–148
(–100)
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
140 (60)
A
B
T
proc
B
81 (27)
400
(204)
A = All available electronic options B = Remote mount electronics only
Ambient and process temperature limits for high-temperature models: 316L stainless steel (A), nickel alloy C22 (B)
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
A = All available electronic options B = Remote mount electronics only
Installation Manual 7
Planning Installation Manual
January 2019 20002298
8 Micro Motion F-Series
Loading...
+ 18 hidden pages