Micatrone MDT-2000 Installation Manual

MDT-2000
Dok.nr: Mi-229gb / 2006-02-09
APPLICATION
MDT-2000 is a temperature controller (digital ther
­mostat), which is intended for controlling stage burners in combustion plants. The controller is also suitable for controlling heating pumps, electric ele
­ments in ventilation plants etc.
FUNCTION
MDT-2000 measures the outgoing water tempera­ture from a heating boiler with a temperature sen­sor. The controller has two set limits for disconnec­tion of power stages with associated temperature hysteresis.
If there is no 230 VAC signal connected to terminal 3, the controller is blocked. Terminal 5 and 6 respec­tive terminal 8 and 9 are connected to each other via relay contacts.
If permission to operate is given, i.e. a 230 VAC sig
­nal on terminal 3, and the temperature is below set value for "Stage 1 OFF" minus the temperature hys
­teresis for stage 1, the first relay switches, breaks connection between terminal 5 and 6 and connects terminal 4 with 5. When the temperature exceeds "Stage 1 OFF", the first relay switches back, breaks connection between terminal 4 and 5 and connects terminal5with6.
During permission to operate, if the temperature falls below value for "Stage 2 OFF" minus the tem
­perature hysteresis for stage 2, the second relay switches, breaks connection between terminal 8 and 9 and connects terminal 7 with 8. When the temperature exceeds "Stage 2 OFF", the second re
­lay switches back, breaks connection between ter
­minal 7 and 8 and connects terminal 8 with 9.
MDT-2000 can also be operated manually using the hand operation.
SELF-SUPERVISION
MDT-2000 monitors the measuring signal from the temperature sensor to be within the measuring range of 0...150 °C.
If the measuring signal is outside the measuring range the operation is blocked and the display start toflash"----",relaysswitch-overandterminal5 and 6 with terminal 8 and 9 closes.
The run-time self-supervision stops the operation under the following circumstances:
q
No temperature sensor is connected
q
Faulty connected temperature sensor
q
Short-circuit in the temperature sensor
q
Break inside the temperature sensor
q
Malfunctioning wiring between the temperature sensor and MDT-2000
MDT-2000 returns to normal operation as soon as the measuring signal is within the measuring range again.
DESIGN
MDT-2000 is equipped with three connected printed circuit boards, I/O-board, sensor-board and dis­play-board. The display-board consists of a 4-digit indicator, 6 LED’s for indication and 4 keys for pro­gramming. The enclosure is of ABS plastic and pro­vided with four threaded holes for cable fittings. For fitting on DIN-rail a mounting kit is used. MDT-2000 can be programmed without opening the enclosure.
INSTALLATION
MDT-2000 is mounted via 4 screws, max Æ4 mm. The location of the holes is shown back of the enclo
­sure. Do not place the unit on a warm surface. Connect power supply according to the electrical connection. Check that the controller is marked with the correct power supply voltage. If using cable glands without a nut on the inside, glands with grommet must be used to avoid damage to the threads on the enclosure. Remember to remove the transparent protective cover from the front panel af
­ter finished installation.
INSTALLING THE TEMPERATUR SENSOR
The temperature sensor can be connected with two or four wires. The best result is received with a 4-wire connection. A 2-wire connection is easier to install but results in a risk for measurement error in connections with long wires.
Ex. a 10m 2x0,25 mm
2
Cu-cable gives an error in measurement with approximately 3,5 °C. Shielded cable is recommended.
© AB MICATRONE 2006-02-09 [H:\ Apps \ Typeset \ Mima \ mi-229gb_060209.vp]
Temperature Controller with comprehensive run-time self-supervision
c
a
t
ron
e
®
Operating and installation manual
PGM
ESC
Prog. mode
Stage 1
Stage 2
Blocked
Hand
°C
0083
Hand
TEMPERATURE SENSOR
The choice of sensor, measuring place and installation are very important to achieve an accu
­rate and representative temperature measurement. The factors to consider are:
q
Good circulation.
q
Good thermal contact between sensor and me
-
dium.
q
The time constant (the response time for tem
-
perature changes) should be as short as possi
-
ble.
q
The sensor should not be exposed to heat radi
-
ation.
q
The sensor should not be exposed to vibra
-
tions.
q
The water flow should not be to high for the sensor
Micatrone delivers the sensors MG-3000-DV-120, MG-3000-DRT-125 and MG-3000-DRT-225 for temperature measuring in liquid.
MG-3000-DV-120
This sensor shall be installed without a pocket, but with a compression fitting. This means that it is pos­sible to disconnect the sensor with water in the sys­tem. It can also be used for tubes with different kind of lengths. With this construction a very good thermal contact with the media is achieved and the time constant (the response time for temperature change) be­comes short. The sensor pipe has a small diameter why the radi­ation is small. The sensor application is limited due to the water velocity, may not exceed 2 m/s, and that the system pressure not exceeds 10 bar (1 MPa). The sensor is also sensitive against vibrations. If these restrictions not are applicable the use of MG-3000-DV-120 is recommended.
MG-3000-DRT-125 / -225
These sensors are provided with pockets and are used when MG-3000-DV-120 can't be used. The sensors, with a pocket, has a restricted thermal contact with the media and this gives a longer time constant. To reduce this the sensors shall always be installed upright so the pocket can be filled with glycerine. With glycerine in the pocket the time con
­stant will be reduced to less than half.
Installation of sensors on water pipes
In order the get a quick response, the sensor should be placed close to the outlet from the boiler. If water is supplied from different directions the sensor should be placed a least 0.2 meters from the mixing point so a blend of the water can occur.
In pipes with small diameters there is a problem with placement of sensors. The sensors pipe or pocket must be installed in the waterpipe with minimum twice the lenght of the mesurement element.
For MG-3000-DV-120: 2 x 20 mm = min. 40 mm
For MG-3000-DRT-xxx: 2 x 35 mm = min. 70 mm
Following figures shows a suitable installation in water pipes with small diameters, either in a pipe curve or in an angle against the flow.
Notice! MG-3000-DRT-xxx must be installed from above so the pocket can be filled with glycerine.
MG-3000-DV-120 do not require an installation from above, due to that it does not have a pocket which needs to be filled with glycerine.
2
© AB MICATRONE 2006-02-09 [H:\ Apps \ Typeset \ Mima \ mi-229gb_060209.vp]
figure 1
Installation of MG-3000-DRT-xxx.
figure 2
Alternative installation of MG-3000-DRT-xxx.
figure 3
Installation of MG-3000-DV-120
figure 4
Alternative installation of MG-3000-DV-120
Pipes with larger diametres (Ø 150 and bigger) the sensors can be installed according to figure 5.
Notice! Never install a temperature sensor with only the tip in the water or the sensor in the flange.
3
© AB MICATRONE 2006-02-09 [H:\ Apps \ Typeset \ Mima \ mi-229gb_060209.vp]
Pt-100 = 100 W at 0 °C. All values in W.
°C -9 -8 -7 -6 -5 -4 -3 -2 -1 0
-40
80,65 81,04 81,44 81,83 82,23 82,63 83,02 83,42 83,81 84,21
-30
84,61 85,00 85,40 85,79 86,19 86,59 86,98 87,38 87,77 88,17
-20
88,57 88,96 89,36 89,75 90,15 90,55 90,94 91,34 91,73 92,13
-10
92,52 92,92 93,31 93,71 94,10 94,49 94,89 95,28 95,68 96,07
0
96,46 96,86 97,25 97,64 98,04 98,43 98,82 99,21 99,61 100,00
°C +0 +1 +2 +3 +4 +5 +6 +7 +8 +9
0
100,00 100,39 100,78 101,17 101,56 101,95 102,34 102,73 103,12 103,51
10
103,90 104,29 104,68 105,07 105,46 105,85 106,24 106,63 107,02 107,40
20
107,79 108,18 108,57 108,96 109,35 109,73 110,12 110,51 110,90 111,28
30
111,67 112,06 112,45 112,83 113,22 113,61 113,99 114,38 114,77 115,15
40
115,54 115,93 116,31 116,70 117,08 117,47 117,85 118,24 118,62 119,01
50
119,40 119,78 120,16 120,55 120,93 121,32 121,70 122,09 122,47 122,86
60
123,24 123,62 124,01 123,39 124,77 125,16 125,54 125,92 126,31 126,69
70
127,07 127,45 127,84 128,22 128,60 128,98 129,37 129,75 130,13 130,51
80
130,89 131,27 131,66 132,04 132,42 132,80 133,18 133,56 133,94 134,32
90
134,70 135,08 135,46 135,84 136,22 136,60 136,98 137,36 137,74 138,12
°C +0 +1 +2 +3 +4 +5 +6 +7 +8 +9
100
138,50 138,88 139,26 139,64 140,02 140,39 140,77 141,15 141,53 141,91
110
142,29 142,66 143,04 143,42 143,80 144,17 144,55 144,93 145,31 145,68
120
146,06 146,44 146,81 147,19 147,57 147,94 148,32 148,70 149,07 149,45
130
149,82 150,20 150,57 150,95 151,33 151,70 152,08 152,45 152,83 153,20
140
153,58 153,95 154,32 154,70 155,07 155,45 155,82 156,29 156,57 156,94
150
157,31 157,69 158,06 158,43 158,81 159,18 159,55 159,93 160,30 160,67
160
161,04 161,42 161,79 162,16 162,53 162,90 163,27 163,65 164,02 164,39
170
164,76 165,13 165,50 165,87 166,24 166,61 166,98 167,35 167,72 168,09
180
168,46 168,83 169,20 169,57 169,94 170,31 170,68 171,05 171,42 171,79
190
172,16 172,53 172,90 173,26 173,63 174,00 174,37 174,74 175,10 175,47
table 1
Table for the resistance in Pt-100 temperature sensor (acc. DIN 43760)
figure 6
Incorrect installation
Incorrect !
figure 5
PROGRAMMING
Press the PGM-key for, at least, 3 seconds and the display will change from actual value to the parame
­ter list’s first parameter P00. The parameter list comprises five parameters. It's not possible to change the first one.
Press the
¹¸
-keys to show P00, P01, P02, P03
and P04.
By pressing the PGM-key, the set value is displayed for the present parameter.
To change the set value, press the PGM-key once and the left digit starts to flash. To change the digit, use the
¹¸
-keys and press the PGM-key to store
the selected digit. Now the next digit to the right starts to flash and can be programmed. Repeat with the remaining digits for the entire row and press a fi
­nal time on the PGM-key. The display will flash three times with the programmed value as a receipt of ac
­complished programming.
Present programming can be interrupted before the last digit through pressing the ESC-key.
When a value has been programmed a return to the parameter list occurs automatic.
Par. nr:
Parameter list Range Factory
default
P00 Software version XXX
P01 Stage 1 OFF 0...150 90 °C
P02 Hysteresis stage 1 1...99 10 °C
P03 Stage 2 OFF 0...150 82 °C
P04 Hysteresis stage 2 1...99 5 °C
During programming, the LED ”Prog. mode” is lit. Return to indication of actual value occurs by press
­ing the ESC-key, at which the LED “Prog. mode” is put out and the LED “°C” is lit. If MDT-2000 is left in position “Prog.mode” and no keys has been pressed during 5 minutes, MDT-2000 will auto
­maticly return to showing the actual value.
RUN IN HAND OPERATION
Press both PGM- and ESC-key for, at least, 3 sec
-
onds. The LED ”Hand” is lit and the controller is dis
-
abled. By pressing
¹¸
-keys, wanted power stage
can be chosen, se table below.:
Power stage Relay 1 Relay 2
Stopped Terminal 5 and 6
connected
Terminal 8 and 9 connected
Stage 1 Terminal 4 and 5
connected
Terminal 8 and 9 connected
Stage 2 Terminal 4 and 5
connected
Terminal 7 and 8 connected
SUPERVISION DURING HAND OPERATION
If the temperature exceeds the set value in parame
-
ter P01, "Stage 1 OFF", MDT-2000 switches to Stopped immediately. Another power stage can be selected, by pressing the
¸
-key when the tempera
-
ture is below set value in parameter P01.
Notice! Position hand operation do not consider set temperature hysteresis.
STOP HAND OPERATION
Hand operation can be stopped in two ways:
Pressing the ESC-key.
If no keys has been pressed during the past 30 minutes.
The LED ”Hand” is put out and the MDT-2000 re­verts to normal operation.
4
© AB MICATRONE 2006-02-09 [H:\ Apps \ Typeset \ Mima \ mi-229gb_060209.vp]
100
90
99
80
82
70
77
Protection temperature limiter
P01, Stage 1 OFF
P03, Stage 2 OFF P02, Hysteresis stage 1 (stage 1 ON)
P04, stage 2 (stage 2 ON)Hysteresis
°C
Example for 2-stage burners (factory default):
figure 7
TECHNICAL DATA
Power supply voltage:
230 VAC ±10% 50Hz
Power consumption: 7.5 VA
Ambient temperature: 0...55 °C
Indication: 4 7-segments LED's and
6 function LED’s.
Programming: 4 keys
Temperature sensor: Pt-100
Connection to the tem
-
perature sensor:
4-wire or 2-wire
Measuring range: 0..150° C (calibrated at
50 and 100 °C)
Measurement error:
± 1° C
Number of set limits: 2, one for each stage,
0..150 °C
Temperature hysteresis: 2, one for each set limit,
1..99 °C
Output relays: 2 pcs, one for each
stage.
Max. load, relays:
230 VAC 2A cosj =1
Signal for operation conditions:
230 VAC Notice! The same line as terminal 1
Electrical connections:
- power supply voltage:
- relays:
- sensor:
2x1,5 mm
2
/terminal
2x1,5 mm
2
/terminal
2x0,75 mm
2
/terminal
Cable lead-through: 4 threaded holes,
(2 pcs M16 + 2 pcs M20)
Degree of protection: IP65
Dimensions: [WxHxD]: 120 x 200 x 57 mm
Weight: 0,75 kg
CONNECTING SHIELDED CABLE TO SENSOR
If a shielded cable is used (recommended), the shield should be connected to ground in MDT-2000.
This is easiest done by connecting incoming ground wire with the shield to the terminal on the circuit board marked with ground symbol.
This terminal is not connected anywhere else on the circuit board or in MDT-2000. For safety reasons the terminal is not to be used for anything else other then to connect the ground wire to the cable shield for the temperature sensor.
5
© AB MICATRONE 2006-02-09 [H:\ Apps \ Typeset \ Mima \ mi-229gb_060209.vp]
Terminals MDT-1000
Terminals MDT-2000
C
onvertingfrom to MDT-2000MDT-1000
12
3
4
56
7
89
11 12 13 14
12
3
4
56
7
89
10 11
Stage 1
Power
supply
230 VAC
Stage 2
Neutral
Line
{
{
{
Protectional earth
for functional grounding
230 VAC
figure 8
Converting from MDT-1000 to MDT-2000
ELECTRICAL CONNECTION
6
© AB MICATRONE 2006-02-09 [H:\ Apps \ Typeset \ Mima \ mi-229gb_060209.vp]
AB Micatrone Telephone: +46 8-470 25 00 Åldermansvägen 3 Fax: +46 8-470 25 99 SE-171 48 SOLNA Internet: www.micatrone.se SWEDEN E-mail: info@micatrone.se
12
3
4
56
7
89
11 12 13 14 15
Stage 1
Start
In
Stop
Start
In
Stop
Terminals in burner (EUROSTECKER)
MDT-2000
Stage 2
Operation
230 VAC
Pt-100 4-wire
Pt-100 2-wire
{
Power
supply
230 VAC
Neutral
Line
{
{
+
Relay contacts for MDT-2000 are drawn as:
No power on terminal 1 No power on terminal 3 Temperature higher than Stage 1 OFF and Stage 2 OFF
1.
2.
3.
F
Flow monitor
*)
°C
P
L
Protection temperature limiter
Protection pressure limiter
Protection waterlevel limiter
**)
L
N
T2 T1
T6
T8
T7
*) Sequence controller, for instance MVP-300 or MVP-3000
**) Limit switch at burner flange
figure 9
Electrical connection