Terminal: Description:
L1-N-Earth Supply for the boiler should be installed with 6A fuse protection. If miniature
circuit breakers are used, these should have C Rated characteristics.
1-3 Lockout circuit (240 Vac from boiler, 1A). If the connection between the two terminals
is broken, the boiler will immediately go into a lockout condition and will
remain out of operation until this connection is restored and has been reset using
the lockout reset button.
4-5 On/Off. By connecting the two terminals to each other, the boiler is switched
from the standby mode to the operating mode and can start when there is a heat
requirement. These terminals can be used for thermostatic functions for the
boiler. If the circuit is interrupted, the boiler goes into the stand-by mode, except
for hot water generation.
6-7 A hot water temperature sensor can be connected to these terminals. This is
recognised automatically by the boiler controller when the supply voltage is
switched on. The reading from this sensor is used for controlling the hot water
temperature.
(If a Volt free enable is used in place of a HWS sensor use terminals 21-22 and not 6-7.)
8-9 External flow temperature adjustment. A 0-5 Vdc (-10 to+90°C) analogue signal
can be applied at these terminals. If the voltage is less than 1 Vdc, it will change
over to the internal set flow temperature (set at P1).
10-11 Connection terminals for the 2-wire bus signal (scom-bus). Pay attention to the
polarity: namely, terminal 10 is earth and 11 is positive.
ST 1.1-1.2 An OK (appliance healthy) signal is available at these terminals (240 Vac from
external, 1A, NO). This circuit will be interrupted if more than 2 identical faults occur
within 6 minutes (the display will show an error code with a “3” appearing above it) or
if a fault remains for more than 6 minutes.
ST 2.1-2.2 An outdoor sensor can be connected to these terminals. The automatic control
unit of the boiler will automatically detect this connection when the supply voltage
is switched on. The reading from this sensor is used for frost protection and
for weather-dependent control of the flow temperature of the boiler when fitted
with the optional BM8, E8.1121, or KKM8 5064.
ST 9.3-9.4 Interlock circuit (240 Vac from boiler, 1A). If the connection between the two
terminals is broken, the boiler will go into a fault condition and remain out of
operation until this connection is restored.
Attention! If the situation lasts for more than 6 minutes, or if it occurs more than twice within 6
minutes, the boiler will go into a lockout fault and remain out of operation until this connection
is restored and is reset using the reset button.
ST 11.1-11.2 Control for the hot water primary pump (240 Vac from boiler, 1A), of which terminal
11.2 is the phase (L) wire and terminal 11.1 is the neutral (N) wire.