MHS Boilers Strata 2 Instructions Manual

GAS FIRED HIGH EFFICIENCY/
CONSDENSING ULTRA LOW NOx BOILER
SINGLE UNIT OUTPUT 120kW
INSTRUCTIONS FOR INSTALLATION,
SERVICING & OPERATION
STRATA2
STRATA2
Index
page section
3
. . . . . . . . .
1.0
General
1.1
Product Description
1.2
Certification Details
3-5
. . . . . .
2.0
Product Description
6
. . . . . . . . .
3.0
Technical Details
3.1
Technical Data
7
. . . . . . . . .
3.2
Critical Dimensions
8
. . . . . . . . .
3.3
System Guidance
3.4
Flue Options
4.0
Appliance Installation Requirements
4.1
Statutory Requirements
8-9
. . . . . .
4.2
Boiler Position
9-15
. . . .
4.3
Flue Options & Terminal Position
15
. . . . . . .
4.4
Ventilation Requirements
16-17
. .
4.5
Hydraulic System Design
17
. . . . . . .
4.6
Gas Supply
4.7
Electrical Supply
18
. . . . . . .
5.0
Installation Instructions
5.1
Unpacking the Boiler
5.2
Positioning the Boiler
5.3
Air Supply & Exhaust Connections
5.4
Gas Connection
19
. . . . . . .
5.5
Water Connections
5.6
Condense Waste Connections
5.7
Electrical Connections ­General
5.7.1
Connecting the Power Supply
20
. . . . . . .
5.7.2
Connecting of System Safety Interlocks
20-23
. .
5.7.3
Connecting of System Safety Interlocks Connection Diagrams
24
. . . . . . .
5.7.4
Electrical Wiring Diagrams
25
. . . . . . .
5.7.5
Connecting Remote Fault Alarms
5.8
Connecting Additional Boilers
5.8.1
Connecting Third, Fourth, Fifth, Sixth, Seventh and Eighth Units
page section
25
. . . . . . .
5.8.2
Boiler Manager RVA 47 Installation Procedure (Normally Factory Fitted)
26
. . . . . . .
5.8.3
Mixing Valve Controller RVA 46 Installation Procedure
5.9
Connecting a Condensate Pump
27
. . . . . . .
5.9.1
Condensate Receptacle and Pump ­Model No. KHPI
6.0
Commissioning and Testing
6.1
Filling the Boiler
28
. . . . . . .
6.2
Appliance Operation Left Switch Panel
6.2.1
Left Switch Panel
6.2.2
Module Control Panels
29
. . . . . . .
6.2.3
DIP Switches
30
. . . . . . .
6.3
Firing the Appliance
6.3.1
Initial Start Up
6.4
Setting and Adjusting the Load
31
. . . . . . .
6.4.1
Setting Minimum Load
6.4.2
Setting Maximum Load
6.4.3
Setting Maximum/ Minimum Load for Upper Module
6.5
Setting for Propane Gas
32
. . . . . . .
6.6
Setting Domestic Hot Water
6.7
Switching Off the Appliance
7.0
Boiler Control Settings
32-33
. .
7.1
End User Parameter Settings
33-36
. .
7.2
Heating Engineer Parameter Setting
37-38
. .
7.3
OEM Parameter Setting
38
. . . . . . .
8.0
Maintenance and Inspection
8.1
Inspection
39
. . . . . . .
8.2
Maintenance
9.0
Fault Diagnosis
9.1
Control Panel
39-40
. .
9.1.1
Operation Indicator
9.1.2
Fault Indicator
41
. . . . . . .
9.1.3
System Faults
9.2
RVA 47 Fault Indication
42
. . . . . . .
10.0
Parts List
11.0
Guarantees
1.0 general
STRATA2
1.1 general notes
These instructions are intended to assist the installer, commissioning engineer, maintenance engineer
and user with the installation, maintenance and usage of the Strata 2-120 gas fired condensing boiler.
Please read this manual fully before commencing the installation of the appliance. MHS Boilers Ltd shall
not be responsible for any damage resulting from failure to carefully observe the instructions given.
The Strata 2-120 must only be installed by persons deemed to be competent i.e. Corgi Registered. This
manual must be handed to the user following completion of the installation.
1.2 certification details
The Strata 120-2 complies with all relevant European Directives and has been independently certified
to comply with the requirements of prEN 483 for use in GB and IE with Gas Category II2H3P.
(Natural gas G20 @ 20 mbar inlet pressure).
The flue classification (depending upon the required flue option) is either B23; C13X; C33X; C43X;
C53X; C63X; C83X.
CE
0063AT3426-98
2.0 product
description
The Strata 2-120 boiler is a gas-fired, fully condensing floor standing appliance with a fully modulating output of 12.2 to 119.7 kW at 30ºC return water temperature. The appliance may be used singularly or in multiples serving the needs of LTHW systems up to a maximum flow temperature of 85ºC.
Each Strata 2-120 boiler incorporates two modules, each module accommodates its own burner, combustion fan, gas valve, ignition/ionisation, electrode and burner control with safety circuits.
Each module contributes 50% of the total output, and can be operated independently. Each heat exchanger has a modulating capacity of 20% to 100%. If a fault should occur with one of the burner/heat exchanger modules, the other will continue to operate.
The boiler includes, as standard, matched modulating speed pumps which automatically adjust the primary flow rate for the heat exchangers to (where possible) maintain the design temperature difference. The pumps have residual duty to convey the boiler mass flow rate to the installers system low loss manifold, ensuring correct flow rates through the boiler at all times and reduces installer involvement in this critical area.
The Strata 2-120 incorporates comprehensive microprocessor controls. A RVA47 (CLI) cascade manager is used to translate the heat demand of the installation into a boiler load for each module. The first RVA47 (CLI) manager has the potential to control up to four modules (burner/heat exchangers) in modulating/cascading fashion. Therefore when installing Strata 2-120 boiler in twin form, all serving the same system, an RVA47 (CLI) controller is only required and supplied in the first boiler.
The RVA47 (CLI) controller in boiler no.1 is always the ‘master’ and every subsequent controller must be set as a ‘slave’.
In addition to the RVA47 (CLI) controller, each Strata 2-120 boiler incorporates individual burner/heat exchanger safety controls which provide the essential safety functions of burner ignition and flame monitoring, overheat cut off devices for excessive water or flue gas temperature, an LCD display screen to indicate run or fault status codes, and individual burner on/off switches.
Room Sealed Option
When required, the Strata 2-120 boiler, may be installed as a room sealed appliance, taking air for combustion from outside the building. This option is recommended for installations where air from within the building may be contaminated with oxidising agents, which occur in appliances such as swimming pool plant rooms, dry cleaners and in various manufacturing and industrial process environments etc.
STRATA2
2.0 product description (contd)
Extended Flue Lengths and Difficult Flue Routes
The excess fan pressure from the combustion system is in the order of 100Pa which allows the appliance to be exhausted using small diameter flue components over long distances or awkward routes, which allows a considerable degree of flexibility in boiler siting.
As the efficiency of this unit is extremely high, high grade plastic flue components can be utilised because the temperature of the flue gas will at all times remain below 80ºC. (To protect the plastic discharge pipe against excessive temperatures, a safety thermostat is employed set at 80ºC, which is fitted inside the plastic discharge pipe in the unit, immediately above the upper heat exchanger).
Note: These flue components are available exclusively from MHS.
The Strata 2-120 includes a wealth of enhanced operating facilities and features as standard:
Floor mounted with compact dimensions (provides maximum heat from a minimal
footprint).
Fully modulating heat output: The output is fully variable across the twin burner/heat
exchanger arrangement providing a 10:1 turn down ratio, sliding between 10% and 100% of output
which automatically and instantly adjusts to meet the needs of the system. The percentage of power
at any given time may be dictated by flow temperature, outside air temperature, room temperature,
stored domestic hot water temperature or a combination of these.
Fully condensing stainless steel heat exchanger. The Strata 2-120 boiler features a heat
exchanger which deliver exceptional heat transfer, and is fabricated from corrosion resistant, long life,
stainless steel. The uniquely designed Spiranox heat exchanger will return operating efficiencies of up
to 105% nett (95.5% gross) with a return water temperature of 30ºC.
Extremely low harmful emissions. The boiler utilises 100% premixed gas/air fed at positive
pressure to the metal fibre sheathed radiant burners. The optimum amount of gas/air is mixed before
the combustion fan, and then blown into the burner.
Single/double heat exchanger operation for maximum flexibility of operation.
A spring loaded non-return valve has been fitted in the air intake to the combustion fan, preventing flue
gases from a firing module from entering the air intake of the non firing module. Also a hydraulic non-
return valve is fitted in each heat exchanger return pipe to prevent circulation of water if one of the
heat exchangers is not functioning.
Low CO and NOx emissions. The advanced burner and controls allows extremely clean and
efficient combustion to be achieved, which in turn gives extremely low emissions certified in
accordance with DIN 4702, CO 15mg/kWh (14ppm) – Nox 11mg/kWh (8.0ppm).
Accurate variable burner output control. The premix fans have very accurate speed control
which allows precise control over combustion air volumes. This system facilitates great accuracy and
instantly provides variable burner output. The nature of the variable rate fans allows, in the case of a
lower heat demand, the fan to run at a slower speed, resulting in lower power consumption.
Each boiler incorporates LCD display screens to display current operational status and
operational parameters. Each RVA controller provides cascade modulating burner output control,
hours run counters for each burner and programmable lead/lag sequencing.
STRATA2
2.0 product description (contd)
The ‘master RVA47 (CLI) controller provides:
Overall modulating output in accordance with the demands of the system.
Inbuilt weather compensation giving direct-on-boiler VT control if required.
Remote stored domestic hot water temperature control
Domestic hot water primary pump or diverter valve control. (2 Amps max)
Heating system pump control. (2 Amps max)
Inbuilt heating system time control with 35 on and 35 off programmable set points within 7 days.
Inbuilt DHW time control with 3 on and 3 off sets points per day.
An option to control the boiler/s from external 0-10V input, or volt free switching.
Programmable frost protection.
The additional option to connect remote control devices.
The additional option to connect VT zone controllers. (RVA46)
Designed for Ease of Maintenance
The appliance has been designed and engineered to be easy to maintain, with most major service
operations being quick and easy to complete with the minimum of tools.
Each module can operate independently, without affecting the service of the other modules within
the system.
To facilitate the annual inspection and cleaning of the syphon, there is a rinsing pipe at the back of the unit. The condense is led through a built-in syphon to a plastic connection at the back, where a suitable connection can be made to the termination point.
Operational Data Logging
Each burner assembly has a data logging facility to record operational actions, which can be accessed via an RS232 communication from a PC. This facility provides a useful service tool as it allows a record of operation to be viewed and any faults to be identified.
STRATA2
3.0 technical
details
3.1 technical data
Table 1
Model Strata 2
No. of Boilers No. of Burners/
Ht Exchangers No. of Cascade RVA Controllers
Master & Slaves Output Turn Down Ratio
Max
kW
Heat Output at Min 80°C Flow - 60°C Return Max Btu/h
Min x 1000 Max
kW
Heat Output at Min 50°C Flow - 30°C Return Max Btu/h
Min x 1000
Nominal Heat
Nett
kW
Input Max Btu/h Input Rate m
3
/h
NatGas Max ft
3
/h Flow Temperature Max °C Max Operating Pressure Bar Min Operating Pressure Bar Flue Gas Volume
m
3
/h
Max Hot Combustion
m
3
/h
Air Volume Max Flue Gas
°C
Temperature Max Gas Inlet Pressure
mbar
(NatGas) Min/Max Flow & Return
BSP-M
Connections Gas Connection BSP-M Flue Connection mm Air Tube Connection
mm
(for room sealing)
Weight
Empty
kg
Full Water Content L Electrical Supply 1 Phase Electrical Load Max Watts Condense Waste
BSP-M Connection
Single
120
1
2
1 master
10:1
107.8
11.1 367
37
119.7
12.2 408
41
114
388,968
12.06 426
85
4.0
0.5
170
130
80
15/60
11/4"
1"
110
110
155 170
15
1 x 230V
260
3
/4"
240
2
4
1 master
20:1
215.6
11.1 735
37
239.4
12.2 816
41
228
777,936
24.12 852
85
4.0
0.5
340
260
80
15/60
11/4" (x2)
1" (x2)
110 (x2)
110 (x2)
310 340
30
2 x 230V
2 x 260
3
/4" (x2)
360
3
6
1 master
+ 1 Slave
30:1
323.4
11.1
1,103
37
359.1
12.2
1,225
41
342
1,166,904
36.18 1278
85
4.0
0.5
510
390
80
15/60
11/4" (x3)
1" (x3)
110 (x3)
110 (x3)
465 510
45
3 x 230V
3 x 260
3
/4" (x3)
480
4
8
1 master
+ 2 Slave
40:1
431.2
11.1
1,471
37
478.8
12.2
1,633
41
456
1,555,872
48.24 1704
85
4.0
0.5
680
520
80
15/60
11/4" (x4)
1" (x4)
110 (x4)
110 (x4)
620 680
60
4 x 230V
4 x 260
3
/4" (x4)
600
5
10
1 master
+ 3 Slave
50:1
539
11.1
1,839
37
598.5
12.2
2,042
41
570
1,944,840
60.3
2130
85
4.0
0.5
850
650
80
15/60
11/4" (x5)
1" (x5)
110 (x5)
110 (x5)
775 850
75
5 x 230V
5 x 260
3
/4" (x5)
Multiple Boilers Multiple Boilers
STRATA2
600
150
725
97
108
58
A
C
B
D
222
162
50
690
410
279
35
66
36
F
E
G
B
A
40 50
275
1570
1370
220
G
B
A
E F
plan
rear
side
A Return (R11/4") B Flow (R1
1
/4") C Flue Outlet 110 Dia D Air Inlet 110 Dia
E Condense-Outlet
(R
3
/4") F Syphon clean point G Gas (R1")
Dimensions in millimetres
Note:
Re flow and return connections. Each boiler is equipped with 2Nr flow and 2Nr return connections. The installer may use either both top or both rear or one of each.
Clearances mm
Front min 500 - recommended 750 Rear min 450 Top min 500
AB
Boiler to boiler - none A - None when B = 450 B - None when A = 450
3.2 critical dimensions
appliance dimensions
installation clearances
Fig 3.2a
Fig 3.2b
STRATA2
3.3 system guidance
In summary, the Strata is designed for use with a sealed pressurised hydronic circuit operating upon a design temperature difference of 20ºC. The integral primary pumps have approximately 1m head available to overcome a primary loop incorporating a low velocity mixing header. Full details regarding suitable system designs are given in section 4.3.
3.4 flue options
The Strata 2-120 may be used with either an open or room sealed flue and air system. Approximately 100Pa is available as residual flue pressure at the exit from the appliance. Full details regarding flue specification are given in section 4.3.
4.0 appliance
installation requirements
4.1 statutory requirements
Gas Safety (Installation and Use) Regulations (Current Issue)
It is the law that all gas appliances are installed by a registered person, in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution. It is in your own interest, and that of safety, to ensure that the law is complied with.
In addition to the above regulations, this appliance must be installed in accordance with the current IEE Wiring Regulations for electrical installation, (BS 7671), Local Building Regulations, the Building Standards (Scotland) (Consolidation) Regulations, Bye laws of the Local Water Undertaking and Health and Safety Document No. 635 The Electricity at Work Regulations 1989’.
It should also be in accordance with the relevant recommendations in the current editions of the following British Standards and Codes of Practice, plus any others that are relevant to the proposed installation: BS5449, BS5546, BS5440:1, BS6798, BS6891, BS6644, BS6880, IGE/UP/2, IGE/UP/7, & IM11. Clean Air Act Memorandum on Chimney Heights.
Important Note: Manufacturers instructions must NOT be taken in any way as overriding statutory obligations.
4.2 boiler position
The following considerations must be observed when siting the Strata 2-120:
The boiler is not suitable for external installation. The position selected for installation should be within the building, unless otherwise protected by a suitable enclosure, and MUST allow adequate space for installation, servicing, and operation of the appliance, and for air circulation around it. (Refer to figure 4.3e). In a multiple set-up (modular set-up), the sides of the units may be placed against one another, without any room in between.
This position MUST allow for a suitable flue system and terminal position (Refer to sections 4.3). A connection to a suitable termination point for the discharge of condense must be available . If this is not present, a condensation pump with an elevation level of 5 metres may be fitted to the appliance. The Strata 2-120 must be installed on a flat horizontal floor which is capable of supporting the boiler and any ancillaries (circa 200kg).
If the appliance is to be fitted in a timber framed building it should be fitted in accordance with the British Gas publication Guide for Gas Installations In Timber Frame Housing, Reference DM2. If in doubt, advice must be sought from the Gas Supplier.
If the appliance is to be installed in a room containing a bath or a shower, any electrical switch or control utilising mains electricity must be so situated that it cannot be touched by a person using the bath or shower. Attention is drawn to the requirements of BS7671 (the current I.E.E. Wiring Regulations), and in Scotland the electrical provisions of the Building Regulations applicable in Scotland.
A compartment used to enclose the appliance MUST be designed and constructed specifically for this purpose. An existing cupboard, or compartment, may be used provided it is modified accordingly. BS 5376:2 gives details of the essential features of cupboard/compartment design, including airing cupboards.
4.2 boiler position (contd)
STRATA2
Where installation will be in an unusual location, special procedures may be necessary. BS6798 gives
detailed guidance on this aspect.
The unit cannot be used in the vicinity of chlorine, halogen or sulphur as may be the case in environments such as swimming pools, coolant filling stations etc. In such cases the appliances MUST be room sealed to take air for combustion from outside of the building.
DN100 PPS tube x 1000mm
DN100 PPS bend x 90°
DN100 PPS bend x 45°
DN100 wall bracket
DN125 PPS tube x 1000mm
DN125 PPS bend x 90°
DN125 PPS bend x 45°
DN125 wall bracket
DN150 PPS tube x 1000mm
DN150 PPS bend x 90°
DN150 PPS bend x 45°
DN150 PPS tee with 45° branch
DN100 x 125 PPS increaser
DN125 x 150 PPS increaser
DN150 wall bracket
100/100 to 100/150 concentric adaptor
100/150 concentric tube x 1000mm
100/150 concentric bend x 90°
100/150 concentric bend x 45°
100/150 concentric horizontal terminal effective
length 975mm
100/150 concentric vertical terminal effective
length 500mm
DN100 flat roof flashing
DN100 pitched roof flashing
DN125 flat roof flashing
DN125 pitched roof flashing
DN150 flat roof flashing
DN150 pitched roof flashing
Flat roof for 100/150 concentric terminal
Adjustable pitched roof flashing for 100/150
concentric terminal
4.3 flue options &
terminal position
The Strata 2 has an excess pressure combustion system that allows the appliance to be exhausted over extended distances using small OD flue components.
The flue gas temperature is extremely low (typically the same as the flow water temperature), which allows the use of easy to install PPS (polypropylene) flue pipe and fittings.
The appliance can take combustion air from the room in which it is installed (conventional application) or can be room sealed (fanned balanced flue) using a concentric flue arrangement of a 100mm PPS flue duct within a 150mm galvanised metal air duct, finished in off-white RAL 7035. A full range of flue pipe and air duct components including roof and wall terminals is available from MHS Boilers.
list of flue components
calculating flue resistance
The excess pressure available for overcoming the frictional resistance of a flue system is 100 P.a. The table of flue component resistances will assist the designer in calculating total flue system frictional loss.
If the total installed flue system resistance exceeds 100 P.a., then the result will be a reduction in boiler output. Reference to the Effect of Flue System Resistance On Boiler Output, graphs will assist. If the resistance of a proposed flue system has an unacceptable effect on boiler output, then a larger diameter flue tube should be selected. Thermal up-draught is generated in a vertical flue system, reducing the resistance of the system. Reference to the Thermal Up-draught Graph will provide a figure in P.a., which may be deducted from the total calculated flue system resistance.
Note: Does not apply to horizontal sections of a flue system.
10
STRATA2
4.3 flue options & terminal position (contd)
PPS Component Resistance Pa For Single Boiler 1m Length DN100 Flue Gas tube 7.0 1m Length DN100 Tube Carrying Air 4.0 90° Bend DN100 Carrying Flue Gas 7.0 90° Bend DN100 Carrying Air 4.0 45° Bend DN100 Carrying Flue Gas 4.0 45° Bend DN100 Carrying Air 2.0 1m Length 100/150 Concentric Tube 12.0 90° 100/150 Concentric Bend 12.0 45° 100/150 Concentric Bend 6.0 100/150 Concentric Terminal
15.0
Vertical or Horizontal 100/100 to 100/150 Concentric Adaptor 2.0 DN100 Open Termination with Bird Mesh 7.0 DN100 Air Tube Termination with Rain Cap 8.0 DN125 Air Tube Termination with Rain Cap 5.0
PPS Component Resistance Pa For Single Boiler DN150 Air Tube Termination with Rain Cap 2.0 1m Length DN125 Flue Gas tube 2.5 1m Length DN125 Tube Carrying Air 1.5 90° Bend DN125 Carrying Flue Gas 2.5 90° Bend DN125 Carrying Air 1.5 45° Bend DN125 Carrying Flue Gas 1.5 45° Bend DN125 Carrying Air 1.0 DN125 Open Termination with Bird Mesh 2.5 DN150 Open Termination with Bird Mesh 1.0 1m Length DN150 Flue Gas tube 1.0 1m Length DN150 Tube Carrying Air 0.5 90° Bend DN150 Carrying Flue Gas 1.0 90° Bend DN150 Carrying Air 0.5 45° Bend DN150 Carrying Flue Gas 0.5 45° Bend DN150 Carrying Air 0.5
Table 3
examples of calculating flue pressure loss
140 130 120 110 100
90 80 70 60 50 40 30 20 10
0
0246810121416182022242628303234363840
B
A
Vertical Flue Lengths - metres
A = Insulated or within the building B = Uninsulated and exterior to the building
Draught - Pa
example 1
A single Strata 2-120 boiler is to be installed with a conventional flue arrangement (taking combustion air from the plantroom) which takes an all vertical internal route to roof termination using DN100 flue components.
Length of flue = 10m
Resistance = 10 x 1m lengths DN100 tube @ 7.0Pa = 70 1 x DN100 open termination @ 7.0Pa = 7
Total Resistance = 77Pa
Take into account that 10m of internal vertical flue will generate approximately 33Pa of draught then final operating resistance is 77 - 33 = 44Pa
conclusion: Operating resistance is less than 100Pa therefore no alternative design is required as flue system has no effect on boiler output.
thermal updraught when
flue gas temp 80°C and outside temp -5°C
11
STRATA2
example 2
A single Strata 2-120 boiler is to be installed with a room sealed flue using separate air and flue gas tubes of DN100.
The flue gas tube takes a part horizontal, part vertical internal route to a roof termination. The air tube takes a similar route. Flue gas route vertical section = 3m, horizontal section = 2m. System includes 2 x 90º bends.
Resistance of flue gas tube = 5 x 1m lengths DN100 tube @ 7.0Pa = 35 2 x DN100 90º bends @ 7.0Pa = 14 1 x open termination @ 7.0Pa = 7
Flue gas tube resistance = 56Pa.
Take into account 3m of vertical tube will generate 10Pa. Therefore operating resistance of flue gas tube = 56 – 10 = 46Pa.
Now calculate air tube resistance which must be added to flue gas tube operating resistance to obtain final resistance.
Air tube length = 6.5m (no consideration is given to whether vertical or horizontal). System includes 2 x 90º bends.
Resistance of air tube =
6.5 x 1m lengths DN100 tube @ 4.0Pa = 26 2 x DN100 90º bends @ 4.0Pa = 8 1 x DN100 termination with rain cap @ 8.0Pa = 8
Air tube resistance = 42
Total operating resistance = 56 + 42 = 98Pa
conclusion: Final operating resistance is less than 100Pa, therefore no alternative design is required as flue system has no effect on boiler output.
example 3
A single Strata 2-120 is to be installed using 100/150 concentric flue components. The flue route is all horizontal, to a horizontal wall termination
Length of flue = 4m
System includes 1 x 90º bend + 2 x 45º bends.
Resistance = 4 x 1m lengths 100/150 concentric tube @ 12Pa = 48 1 x 100/150 90º concentric bends @ 12Pa = 12 2 x 100/150 45º concentric bends @ 6Pa = 12 1 x 100/100 to 100/150 concentric adaptor @ 2Pa = 2 1 x 100/150 concentric terminal @ 15Pa = 15
Total resistance = 89Pa.
conclusion: Total flue system resistance is less than 100Pa, therefore no alternative design is required as flue system has no effect on boiler output.
examples of calculating flue pressure loss
Flue System Resistance - Pa
120
118
116
114
112
110
108
106
104
102
100
98
96
94
92
0 50 100 150 200 250 300 350 400 450
Boiler Output kW at: Flow 50°C Return 30°C
effect of
flue system resistance
on boiler output
12
STRATA2
4.3 flue options & terminal position (contd)
multiple flue system calculation
For flue component resistance for multiple boiler installations refer to graph below. Volume flue gas per boiler = 170m
3
/h
Volume combustion air per boiler = 130
3
/h Assume resistance of 45° bend = 0.5 tube Assume resistance of 90° bend or tee = 1.0m tube
150100
22 21 20 19 18 17 16 15 14 13 12 11 10
9 8 7 6 5 4 3 2 1 0
200 250 300 350 400 450 500 550 600
resistance flue tubes
tube DN125
tube DN150
tube DN200
Resistance - Pa/m
Volume - m3/h
For larger volumes or resistance of alternative tube sizes, contact MHS Boilers Flue Department
flueing possibilities
typical conventional
flue installation.
Air for combustion taken from
the boiler room.
Boiler room MUST be
ventilated in accordance
with BS 6644:1991
flue system layouts
13
STRATA2
flueing possibilities
single boiler room sealed
concentric flue
with horizontal discharge
flueing possibilities
typical room sealed flue
installations - single boiler
flueing possibilities
room sealed flue installation
serving multiple boilers,
where air from combustion is
taken from annular space in
brick chimney
Note: Whereas no ventilation is required for combustion air when boiler is room sealed, consideration must be given to general boiler plant room cooling and it is recommended to ventilate to provide:- 4.5cm/kW input at both high and low level direct to outside.
Room Sealed Concentric
Room Sealed Separate Air and Flue Gas Tubes
1200
min
Note: Whereas no ventilation is required for combustion air when boiler is room sealed, consideration must be given to general boiler plant room cooling and it is recommended to ventilate to provide:- 4.5cm/kW input at both high and low level direct to outside.
Air Air
Fall on Flue 3°
Towards Boilers
Inspection Access
flue system layouts
4.3 flue options & terminal position (contd)
Fig 4.3b
Fig 4.3c
Fig 4.3d
14
STRATA2
Additional Notes for Room Sealed Appliances:
The Clean Air Act Memorandum prevents the use of balanced flue appliances discharging at low level where the total heat input to the plant room exceeds 150kW. Where the Clean Air Act does not prevent installation, the following rules must be applied.
Note: Detailed recommendations for flue installation are given in BS5440:1
The following points are for general guidance:
The boiler must be installed so that the terminal is exposed to external air.
It is important that the position of the terminal allows free passage of air across it at all times.
It is essential to ensure that products of combustion discharging from the terminal cannot re-enter the
building or any other adjacent buildings, through ventilators, windows, doors, other sources of natural
air infiltration, or forced ventilation/air conditioning.
The minimum acceptable dimensions from the terminal to obstructions and ventilation openings are
specified in figure 4.3e.
If the terminal discharges into a pathway or passageway check that combustion products will not cause
nuisance and that the terminal will not obstruct the passageway.
Where the lowest part of the terminal is fitted less than 2m (78ins) above ground, above a balcony
or above a flat roof to which people have access, the terminal MUST be protected by a purpose
designed guard.
Where the terminal is fitted within 850mm (34ins) of a plastic or painted gutter, or 450mm (18ins)
of painted eaves, an aluminium shield at least 750mm long must be fitted to the underside of the
painted surface.
The air inlet/flue outlet duct MUST NOT be closer than 25mm (1in) to combustible material.
Note: Under most weather conditions the terminal will emit a plume of steam. This is normal but positions where this would cause a nuisance should be avoided.
In the case of horizontal flue gas discharge pipes, an angle of 3º must be observed in the direction of the boiler (5.0cm for every metre of pipe length) with a fall towards the boiler, to allow condense in the flue gases to return to the unit.
Minimum dimensions of flue terminal positions:
flue terminal positions
H,I
J
P
A
G
F D
E
A
G
P
B,C
F
F
L
K
L
K
P
N
4.3 flue options & terminal position (contd)
15
STRATA2
4.4 ventilation requirements
Detailed recommendations for air supply are given in BS 6644:1991. The following notes are for general guidance. If the combustion air is to be taken from the room in which the unit is located, a guard must be placed over the air intake to prevent the entry of any foreign bodies.
Room Sealed Installations Only:
If the boiler is to be installed in a cupboard or compartment, permanent air vents may be required for cooling purposes in the cupboard or compartment. It is essential to ensure that the minimum clearances as stated in figure 3.2b are maintained.
Water must not be allowed to enter the air intake, as this may affect the performance and behaviour of the combustion fans.
Dimension Terminal Balanced Flue Non room
Position Room Sealed Sealed
A Directly below an opening, 300mm 300mm
air brick, window etc Not recommended Not recommended B Below gutters, soil pipes or drain pipes 75mm 75mm C Below eaves 200mm 200mm D Below balconies or 200mm 200mm
carport roof Not recommended Not recommended E From a vertical drain pipe or soil pipe 75mm 75mm F From an internal or external corner 300mm 200mm G Above ground, intersecting roof or balcony level 300mm 300mm H From a surface facing the terminal 2000mm 2000mm I From a terminal facing the terminal 2000mm 2000mm J From an opening in the carport 1200mm 1200mm
e.g. door into dwelling Not recommended Not recommended K Vertically from a terminal on the same wall 1500mm 1500mm L Horizontally from a terminal on the same wall 300mm 300mm M From the wall on which the terminal is mounted N/A 50mm N From a vertical structure on the roof 500mm N/A P Above intersection with roof 500mm 150mm
4.3 flue options & terminal position (contd)
Table 4
16
STRATA2
4.5 hydraulic system design
Important Note: Strata 2 boilers must only be installed on sealed and pressurised systems. A sealed
system must only be filled by a competent person. Instructions for filling the system are supplied in section 6.0. A low pressure cut off switch must be installed into the system.
All systems must be thoroughly cleansed prior to the connection of the boiler. The system water should be treated to prevent general system corrosion and the deposition of scale or sludge in the boiler waterways. Faliure to observe this requirement will render all guarantees on the product void.
If installing the boiler onto an
old system, it is recommended to install a spirotech or similar dirt arrester/filter.
If plastic pipes are used for the flow and return lines, for radiators or underfloor heating, a plate exchanger should be considered between the system water and the boiler water. If such a separator is not used, the MHS guarantee on all boiler parts will become null and void, unless it can be proved that the plastic pipes used have a vapour tight layer.
The connection of the flow and return are located at the top and the rear of the unit. With regards to servicing, it is a requirement that isolation valves are installed.
For specialist advice and water treatment products, contact:
Betz Dearborn Fernox, Britannica Works
Widnes, Cheshire WA8 8UD Clavering, Essex CB11 4QZ
Tel: 0151 424 5351 Tel: 01799 550811
AAV
Outside Air Temperature Sensor
Room Unit RE3231
Strata 2 - 120
Boiler
Condensate Waste
Low Pressure Switch
Exapnsion Vessel
Filling Point
CWM
DOC
DOC
LSV
IV
SV
IV
IV
Strainer
DOC
Return Sensor
Return from Load Circuits
Temperature Sensor (Boiler)
Low Velocity Mixing Header
Max Velocity
0.5m/s
Flow to Load Circuits
eg. Heating Circuit & HWS Calorifier
To HWS Sensor
recommended system design
typical single Strata 2 - 120 boiler installation
Fig 4.5a
17
STRATA2
AAV
Outside Air Temperature Sensor
Room Unit RE3231
Strata 2 - 360
(3 x 120 Boiler)
Condensate
Waste
Low Pressure
Cut Out Switch
Exapnsion Vessel
Filling Point
CWM
DOC
DOC
LSV
IVsIV’sIV’s
SV SV SV
IV IV
Strainer
DOC DOC
Return Sensor
Return from Load Circuits
Temperature Sensor (Boiler)
Low Velocity Mixing Header
Max Velocity
0.5m/s
Flow to Load Circuits
eg. Heating Circuit & HWS Calorifier
To HWS Sensor
recommended system design
typical multiple Strata 2 boiler installation
DOC
4.6 gas supply
The Strata 2-120 is designed and set for Natural Gas group G20. The Gas Supplier should be consulted at the installation planning stage in order to establish the availability of an adequate supply of gas.
An existing service pipe MUST NOT be used without prior consultation with the gas supplier. A gas
meter can only be connected by the gas supplier or by their contractor.
An existing meter and/or pipework should be of sufficient size to carry the maximum boiler input plus the demand of any other installed appliance. (BS 6891:1988). A minimum of 1 BSP diameter pipework is required to within 1 metre of the appliance gas cock.
The governor at the meter must give a constant outlet pressure of 20 mbar (8 in. wg) when the appliance is running.
The gas supply should be purged in accordance with IGE/UP/1&2. WARNING: Before purging open all doors and windows, also extinguish any cigarettes, pipes and any other naked lights.
4.7 electrical supply
A 240 Volt single phase supply must be present at the proposed boiler location. Wiring external to the appliance must be in accordance with BS7671 (the current I.E.E. Wiring Regulations) for electrical installation and any local regulations which apply.
The mains cable must be at least 0.75mm? (24/0.2mm) PVC insulated to BS6500 table 16. The method of connection to the mains supply must facilitate complete electrical isolation of the appliance. Either a 5A fused three pin plug and un-switched shuttered socket outlet, both complying with BS1363, or a 5A fused double pole switch having a 3mm contact separation in both poles and serving only the boiler (and its external controls) may be used.
WARNING: THIS APPLIANCE MUST BE EARTHED.
(Failure to provide a satisfactory Earth connection would be a safety hazard and may also result in appliance malfunction).
Fig 4.5b
4.5 hydraulic system design (contd)
18
STRATA2
5.0 installation
intructions
5.1 unpacking the boiler
The boiler is delivered in a palletted carton containing the boiler and associated fittings, plus any other
optional ancillary flue or control components in separate cartons.
The boiler carton contains:
Fully assembled boiler.
The Strata 2-120 is also delivered with the following items:
User manual and operating instructions.
Installation and Servicing instructions for the Engineer.
Built into each unit are the following:
A gas stop cock for each heat module.
Three way return water cut-off.
RVA 47 control unit (master and slave boilers), 1 outside air sensor, 1 flow sensor and 1 return sensor.
The unit must be inspected immediately after delivery. Any damage to the consignments must be
reported within 3 days.
To unpack the boiler, carefully cut away the outer packaging and open the carton top. Lift off the
bottomless carton. By holding the chassis only lift the appliance away from the palette.
To remove the casing from the boiler:
Remove the two screws on the bottom front edge of the top casing panel.
Remove panel to the front.
5.2 positioning the boiler
Move the appliance to the desired location, making sure that all clearance dimensions as stated in section 3.2 are adhered to. Level the appliance in a vertical position by turning the adjustable feet underneath the base of the unit. Check that the appliance is in a true vertical position by using a spirit level. Once the appliance is in a true vertical position, the adjustable feet must be secured by locking the nuts.
5.3 air supply and exhaust connections
The unit has two connections, one for the supply of combustion air and the other for the discharge of the products of combustion. Each connection is clearly labelled and located at the rear top of the appliance.
5.4 gas connection
The Gas connection is located at the rear of the appliance. The gas supply should be sized, installed, tested and purged in accordance with IGE/UP/1&2.
The connection to the appliance must include a suitable method of disconnection and a gas control cock must be installed adjacent to the appliance for isolation purposes.
The gas pipe used to supply the appliance must not allow a pressure drop of greater than 1 mbar from the meter to the appliance. The nominal inlet working gas pressure measured at the appliance should be
20.0 mbar for Nat Gas (G20). The installer should install a pressure test point adjacent to the gas inlet connection. The gas supply line should be purged.
WARNING: Before purging open all doors and windows, also extinguish any cigarettes, pipes and any other naked lights.
19
STRATA2
5.5 Water Connections
The central heating flow and return connections are 11/4" BSP male. Two sets of flow and return connections are provided and located on the rear top of the appliance and the rear of the appliance. The installer may use both top or both rear connections or one of each for connection of the flow and return pipes.
A suitable safety valve must be installed onto the boiler flow pipe between the boiler and any isolation valve. The boiler flow and return pipes must include a method of disconnection and must include isolation valves.
5.6 condense waste connections
The condense waste connection is located at the lower rear of the appliance. The condense syphon cleaning point is factory fitted with a heavy grade black plastic cap which MUST NOT BE REMOVED. Operating the appliance with the cap removed from the syphon cleaning point will allow products of combustion to be discharged from the cleaning point.
The condense waste connection is a
3
/4" BSP male threaded stub fabricated from plastic. The installer
must connect to this stub, a condense waste pipe fabricated from plastic tube and fittings (
3
/4", 22mm overflow pipe is considered suitable). Only plastic components must be used for the condensation discharge. Metal pipes are not acceptable due to the acidic nature of the condensate.
The built in syphon allows the unit to be connected directly to a drain system. If any part of the condense waste pipe is to be run external to the building or is at risk of freezing, then the pipe must be suitable insulated to protect from freezing.
If a suitable drain for accepting the condense waste is not available nearby to and below the boiler (e.g. if the boiler is installed in a basement below ground level), then an (optional extra) condensate receptacle and pump can be installed into the free space at the base of the appliance. This will collect and remove condense water to a remote drain up to 5 metres height difference above the receptacle position.
Note: Blockage of the waste discharge will cause the unit to switch off by means of a built in level switch.
When making the condense waste pipe connection to the boiler, do not use adhesives, it is recommended to lightly apply a suitable jointing tape (PTFE or similar) and use only light pressure to connect fittings to the appliance to avoid damage to the condense waste outlet assembly. It is recommended that the condense waste pipework should include a method of disconnection and cleaning points.
5.7 electrical connections – general
The Strata 2-120 has a number of standard connection points. In addition, a number of panel locations have been reserved for the installation controller, which can be mounted in the spaces provided after removing the blank panels.
At the top of the boiler, behind the controllers, is a connector plate stretching across the entire width of the boiler, flanked by three cable clamp brackets. All electrical connections are made via plugs and sockets and to avoid mistakes during the connection of the cables, each plug has its own colour.
5.7.1 connecting the power supply
The incoming power supply (230V) must be connected to the black 3 pin Weiland plug located at the far left hand side of the connectors mounting plate in the top area of the boiler. The unit has a 2-pole on/off switch for the power supply of the entire boiler and all the connected controllers, pumps and valves.
Determine the cross sectional area of the power supply cable and take into account the power usage of the combined components connected to the control units.
In addition each burner module has a single pole-switch to switch off one burner unit while the second unit may continue to function. The main switch is protected by a 6.3 AT fuse.
CAUTION: The main power supply for the boiler must have a higher fuse value.
20
STRATA2
5.7.2 connecting of system safety interlocks
These switches are connected to the dark green 3 pole plug. The central pole provides the common output (230V AC). The left hand terminal enables the lower module and the right hand terminal enables the upper module.
5.7.3 connecting remote run indication lamps
Connection points have been provided for the connection of run indication lamps (20W max). See Electrical Connection Details fig 5.7a, for terminal positions.
CAUTION: These outputs must not be linked together as this will result in false lockout being experienced by the burner control panels.
Legend
PPS. Connection for the Master boiler to a second boiler -
Note screened cable must be used
.
LPB. Connection for the Master RVA 47 controller to subsequent
RVA 47 controllers -
Note screened cable must be used
.
VFO. Connection for the system flow sensor.
SF. Connection for the DHW sensor.
AF. Connection for the outside air sensor.
RE. Connection for the room unit.
HI. Connection for remote enabling volt free or 0-10 Volt control signal.
RFO. Connection for the system return sensor.
SLP. Connection for the DHW 3 way valve or charging pump. (Max 2A).
HKP. Connection for the Heating pump. (Max 2A).
AF1/AF2. Connection for another outside air sensor dedicated for the RVA 46 if required.
If a dedicated sensor is not required the RVA 46 will use the RVA 47 outside air sensor.
RE1/RE2. Connection for the room unit/thermostat dedicated to the RVA 46 VT circuits
VF1/VF2. Connection for the mixed flow sensor of the RVA 46 VT circuits
P1/P2. Connection for the pump of the RVA 46 VT circuits.
M1/M2. Connection for the 3 way mixing valve of the RVA 46 VT circuits.
PPS N L N L AF1 RE1 VF1 AF2 RE2 VF2
LPB VFO SF AF RE H1 RFO
SLP
NEL NEL NEO
HKP P1 M1
NEL
NEL NEO
P2 M2
electrical connection details
Run Indication
230 Volt Output
Note: Do Not Link
240V
Supply
Fault VF
Connections
OptionalRemote Safety Hi/Lo Interlocks etc
Boiler Power & Communications RVA 47 Boiler Controller Connections RVA 46 VT Controller Connections
Fig 5.7a
21
STRATA2
suggested wiring arrangement for high/low
pressure switches and Strata 2 boilers
Strata 2/120 Boiler
Low Pressure
Switch
Break on
Pressure Fall
Break on
Pressure Rise
High Pressure
Switch
Supply
Remote Safety
Interlocks
240 Volts out from centre tapping return to either side for complete boiler operation interlock required for each boiler
Contactor
N
suggested wiring arrangement for high/low
pressure switches and multiple Strata 2 boilers
Strata 2/120 BoilerStrata 2/120 Boiler
Low Pressure
Switch
Break on
Pressure Fall
Break on
Pressure Rise
High Pressure
Switch
Supply
Remote Safety
Interlocks
Remote Safety
Interlocks
240 Volts out from centre tapping return to either side for complete boiler operation interlock required for each boiler
Contactor
N
5.7.3 connection diagrams
Fig 5.7c
Fig 5.7.d
22
STRATA2
suggested hydraulic layout and basic wiring for
Strata 2 120 condensing boilers
AF Outside Sensor
Boiler No.1 Boiler No.2
(if installed)
RFO Return
Sensor
HKP
SLP
VFO Flow Sensor
SF HWS Sensor/ Stat
Low Loss Header Max Velocity
0.5 m/s
PPS
SLP
NE L
LPB VFO SF AF RE H1 RFO
PPS LPB VFO SF AF RE H1 RFO
HK
NE L
SLP
NE LHKNE L
HWS Sensor (by MHS) or Volt Free Cylinder Stat
HWS Pump/Starter
2A Max
Heating Pump/Starter
2A Max
Boiler No.1
RVA 47 Boiler Controller Connections
RE3231 Room Unit if Required
Remote Enable if Required
(Volt Free) or 0-10 Volt
Boiler No.2
Connections (if Installed)
Valves, Fittings and Anciliary Equipment Not Shown for Clarity
5.7.3 connection diagrams
Flow
Sensor
Return Sensor
Outside
Sensor
23
STRATA2
5.7.3 connection diagrams
suggested wiring and component layout
for multiple Strata 2 120 installations up to 960kW
Outside Air Sensor
230 Perm Supply
With Local Isolators
RVA 47 RVA 47 RVA 47 RVA 47 RVA 47 RVA 47 RVA 47
H1 Remote Enable (Volt Fee)/or 0-10 volt
PPS
HWS Sensor
System Flow Sensor
Boiler Return Sensor
LPB
Safety Interlocks
Note: PPS & LPB cables must be screened
5.7.4 electrical wiring diagram
24
STRATA2
PUMP GAS VALVE
X43 3
1
PE N L
gnd
pwm
pls
V+
1
5
BV1
BV2
FAN
BP BG
LPEN LPEN
1
N
1
N
X44 X45
BD
FURIMAT 310
DU312
1
4
5
8
1
4
5
8
BX8 BX9
1212
34
12
BX4
1921
1
4
6
7
9
3
5
1
8
10
X27
2
4
14
BX1
LN
X52
X32
X21
X20
X26
X33
X25
X28
X24
X23
LPEN
8
916
BX3
BX2
CONDENSE
PUMP
RVA47 (46)
POWER SUPPLY
J1
BX7
PPS
ON1
IGM20
Heat­exchanger
F1
6,3AT
X22
X42
FLOW
SENSOR
N
1
2
S3
X29 X30 X31
3
1
X54
X53
X55
X56
1
4
12L
N
12L
N
1 2
X40 X41
1
4 1
3
ST3
ST2 ST1
7
1
X24
M-T
X38
STB
WATER
M-T
X39
STB
WATER
X37 X36 X35
CONDENSE
LEVEL
FLOW
SENSOR
1
2
S2
S1
PPS
M-T
STB
EXHAUST
X34
X48
1 2
Frame at the top
Frame under
AX1
X49
X50
X51
14291812 121214
58
14
58
34
916
AX2
J1
AX3
AX4
AD
AX7
AX8 AX9
FURIMAT 310
DU312
PUMP GAS VALVE
X46
3
1
PE
N
L
gnd
pwm
pls
V+
1
5
AV1
AV2
FAN
AP AG
LPEN LPEN
1
N
1
N
X47
X45
14
ON2
IGM20
Heat­exchanger
AX1-1 = Purple AX1-2 = Green AX1-3 = Light Blue AX1-4 = Grey AX2-2 = Blue AX2-3 = Black AX2-4 = Blue AX2-5 = Black AX2-6 = Black AX2-7 = Blue AX2-8 = Black AX2-9 = Blue AX3-4 = Red AX3-5 = Purple/White AX3-8 = Red/White AX3-9 = Blue/White AX3-10= Black/White AX3-11= Yellow/White AX3-12= Red AX3-14= Brown/White AX3-15= Purple AX7-1 = Yellow/Red AX7-2 = Red/Blue AX7-3 = Yellow/Black AX7-4 = Orange/Black AX7-5 = Yellow/Red AX7-6 = Red/Blue AX7-7 = Yellow/Black AX7-8 = Orange/Black AX9-1 = Black AX9-2 = Black BX1-1 = Purple BX1-2 = Green BX1-3 = Light Blue
BX1-4 = Grey BX2-2 = Blue BX2-3 = Black BX2-4 = Blue BX2-5 = Black BX2-6 = Black BX2-7 = Blue BX2-8 = Black BX2-9 = Blue BX3-4 = Orange BX3-5 = Purple/White BX3-8 = Red/White BX3-9 = Blue/White BX3-10 = Black/White BX3-11 = Yellow/White BX3-12 = Orange BX3-14 = Brown/White BX3-15 = Purple BX7-1 = Yellow/Red BX7-2 = Red/Blue BX7-3 = Yellow/Black BX7-4 =Orange/Black BX7-5 = Yellow/Red BX7-6 = Red/Blue BX7-7 = Yellow/Black BX7-8 = Orange/Black BX9-1 = Black BX9-2 = Black X3-16 = Grey X8-1 = Grey X8-2 = Orange X20 = Black X21 = Black X22 = Black
X23 = Black X24 = Black X25 = Black X26 = Blue X27 = Blue X28 = Blue X29 = Black X30 = Green/Yellow X31 = Blue X32 = Green/Yellow X33 = Black X34 = Grey X35 = Brown/White X36 = Brown/White X37 = White X38 = White X39 = White X40 = Grey X41 = Orange X42 = Blue X43 = Green/Yellow X44 = Green/Yellow X45 = Green/Yellow X46 = Green/Yellow X47 = Green/Yellow X48 = Orange X49 = Green/Yellow X50 = Green/Yellow X51 = Green/Yellow X52 = Green/Yellow X53 = Black X54 = Blue X55 = Black X56 = Blue
25
STRATA2
Table 5
5.7.5 connecting remote fault alarms
The boiler includes a normally open volt free contact for each module, which closes in the event of a
lockout failure. See Electrical Connection Details section 5.7.
5.8 connecting additional boilers
A second boiler unit does not require an additional RVA 47 manager, as the manager in the first unit is capable of controlling up to 4 burners. Connect the power supply to the second unit. Install a pair of screened wires between the PPS connectors of boilers 1 and 2. Observe polarity.
Note: PPS connector = light blue.
5.8.1 connecting third, fourth, fifth, sixth, seventh and eighth units
These boilers must have RVA 47 managers. To connect RVA 47 manager in additional boilers; the LPB terminals in each boiler that includes an RVA 47 manager must be linked, i.e. all left hand LPB terminals must be linked on to another, and all right hand LPB terminals must be linked one to another. Do not link any left hand terminal to any right hand terminal. Screened cables required.
5.8.2 boiler manager RVA 47 installation procedure (normally factory fitted)
Complete the following steps to install the manager:
Remove the blank panel to the right of the display panel.
Unpack the RVA 47 and insert it in the opening of the control panel.
Place the first wiring harness with 6-pin connector in the bottom of the RVA 47 and click the other end
into the wiring upstand at the rear of the boiler.
Place the second wiring harness with the 8-pin connector in the top of the RVA 47 and click the other
end into the wiring upstand at the rear of the boiler.
Connect the boiler power supply (3 pin male connector) to the RVA 47 unit.
Connect the PPS communication wire (Orange/Grey) to the female plug connected to the (Blue/
Grey) wire.
The following can now be connected as necessary:
SLP DHW pump or 3-way valve Beige HKP Heating system pump Yellow PPS Connection to second boiler Blue LPB Connection to subsequent RVA 47 Mauve VFO Flow sensor White SF DHW sensor Clear AF Outside air sensor or resistor substitute (620 Ω) Black REO Room unit or thermostat Light blue H1 Remote enable or (volt free) 0-10 Volt Orange RFO Return Sensor Clear
* = Compulsory connections. All other connections as necessary.
*
*
26
STRATA2
5.9 connecting a condensate pump
If a suitable drain for condensate disposal is located too high to be able to discharge the condense
water from the boiler, a condense pump must be installed within the base of the boiler.
This condensate pump has a built-in safety device. If the pump outlet is blocked, the water level in the pump reservoir will rise to just below the rim – if the level rises any further, the power to the boiler will be switched off.
At the right hand side, in the area of the boiler base, there is a socket – if no condensate pump is used, there will be a plug with a control link in place. The condensate pump (KHP1) must be wired into this plug once the link wire has been removed.
condensate receptacle & pump
model No. KHPI
KHPI
Blue - Neutral
Brown 230V Live out to boiler interlock. Supply fails if condense level too high
Black Permanent Live 230V
Remove Link
Strata 2 Condense Pump Plug
N
I
L
Fig 5.9a
5.8.3 mixing valve controller RVA 46 installation procedure
Complete the following steps to install the RVA 46:
Remove the blank panel beside the manager.
Unpack the RVA 46 and insert it in the opening of the control panel.
Place the wiring harness with 7-pin connector in the bottom of the RVA 46 and click the other end into
the wiring upstand at the rear of the boiler.
Place the wiring harness with the 6-pin connector in the top of the RVA 46 and click the other end into
the wiring upstand at the rear of the boiler.
Connect the controller power supply from RVA 47 loom.
Connect LPB circuit (pink and mauve) from RVA 47 loom.
The following can now be connected if necessary:
P1 Pump for mixed circuit Brown M1 Three way mixing valve Brown AF1 Outside air sensor Black RE1 Room unit or thermostat Light-blue VF1 Mixed flow sensor White
Table 6
27
STRATA2
The Strata 2-120 should be commissioned by a competent engineer. Before commissioning the appliance, the whole gas installation including the meter MUST be purged and tested for gas soundness in accordance with BS6891:1988.
CAUTION: Open all doors and windows, extinguish naked lights and DO NOT SMOKE whilst purging the gas line.
The entire system must be thoroughly cleansed and flushed to remove debris, flux residues etc before opening the boiler isolation valves and flooding the boiler. Particular care must be taken where the appliance is being retro-fitted into and old/existing system, as system silt or magenite can be very damaging to the new boiler.
Following cleansing and flushing the system must be dosed with a good quality water treatment to prevent corrosion and the formation of scale. Failure to observe these requirements will render the guarantee on the product void.
Cleansing, flushing and water treatment must be carried out in accordance with the requirements of BS7593:1992.
The return pipework must include some method of filtering or straining. The filter or strainer must be fitted with isolation valves to allow easy cleaning with the minimum amount of water loss and water replenishment.
A low water pressure switch must be included within the system design and interlocked to the boiler to shut the boiler down in the event of the water pressure falling below 0.5 bar.
Note: The Strata 2 boiler has heat exchangers fabricated from 316L stainless steel. It is most important that the compatibility of any flux is checked with the flux supplier before use, and that any flux manufacturers recommendations are strictly followed with regards to use in conjunction with stainless steel.
6.1 Filling the Boiler
The Strata 2-120 and the central heating installation must be filled by a competent person using one of the approved methods in BS 6644:1991 and using the filling/draining cock in the installation.
The unit has a manometer, which indicates the filling pressure. Fill the installation and vent the boiler. Continue to fill the installation until the correct central heating water pressure has been reached.
Minimum static head – 5m.
6.0 commissioning
and testing
5.9.1 Condensate Receptacle and Pump – Model No. KHP1
The KHP1 condensate pump is designed to collect and pump away condensate water produced by condensing boilers and is particularly suitable for use with the Strata 2.
The KHP1 may be installed directly inside the base area of the Strata 2 making a concealed installation. The receptacle includes a permanently wet sump area where pH adjustment granules may be dosed to neutralise the pH of the condensate water.
technical data
Pump Transfer Height 5m Transfer Volume/cycle 2 litres (approx) Transfer Time/cycle 17 seconds (approx) Power Supply 230V 50Hz Pump 12V dc Pump Outlet 10mm OD Male Spigot Capacity pH Granules 7kg Dimensions 465W x 380D x 120H Supply Cable Length 1.8m 10mm Discharge Hose Length 5m Condense Inlet open aperture in unit top
28
STRATA2
6.2.1 left switch panel
Refer to Figure 6.2a
The switch panel contains the main switch (A), this switches the entire power supply to the unity and all connected controllers on and off. The main switch also disconnects the power to all connected pumps and valves etc.
The second switch (B) only switches the lower heat exchanger on and off, allowing the upper heat exchanger to continue functioning.
The third switch (C) only switches the upper heat exchanger on and off allowing the lower heat exchanger to continue functioning.
At the right hand side is a glass fuse (D) protecting the entire unit and all connected components. This is a 6.3AT type fuse.
At the bottom of this panel is a manometer (E) which indicates the pressure in the central heating system that is connected to the boiler.
Note: The minimum pressure must be above 0.5 bar, while the maximum pressure is 4 bar.
6.2.2 module control panels
This control panel is divided into two sections, the left hand section serving the lower heat exchanger module and the right hand section which serves the upper heat exchanger module.
Each section has the following controls:
Reset Button – In case of a fault, the unit can be restarted by pressing this button. In general the
fault must be rectified prior to restarting.
Chimney Sweep Button (Commissioning button) – Pressing this button once will activate the
burner at minimum capacity (10kW). A letter ‘L’ will appear in the display window. Pressing this button
twice will increase the capacity of the burner up to its maximum (60kW). A letter ‘H’ will appear in the
display window. Pressing this button a third time will return the unit to its previous operating condition.
If the button is not pressed a third time, the unit will fire at the chosen level for a period of 10 minutes,
following which it will revert to auto operation.
Test Button – Pressing this button will stop the unit burning. Releasing the button will allow the unit
to restart again after a short time. The purpose of this button is to provide a simple method of testing
the start-up behaviour of the unit and to test the safety circuit.
Note: If the unit does not switch off, the wiring harness must be checked for short circuits, or the
maximum thermostat or the printed circuit of the burner must be replaced.
Display – The display will always show one of the following situations.
Supply Temperature
Operating messages:- these are always indicated by one digit
Faults:- these are always indicated by two flashing digits
If there are no faults present in the unit, the display will show the supply temperature. When the burner is firing and functioning properly, a ‘dot’ is shown beside the supply temperature – indicating a correct rectification signal.
0
1
2
3 4
ABC DHII
EF G
A Double pole on/off switch (main) B Lower burner on/off switch C Upper burner on/off switch D Fuse holder E Altitude gauge
F Lower burner status panel G Upper burner status panel H RVA 47 cascade control manager I Knockout for additional
optional controls
Fig 6.2a
6.2 appliance operation
29
STRATA2
Table 8 DIP Switches 1-4
If the unit is converted to liquid gas, DIP switch 8 must be set to ON; this automatically lowers the
maximum speed of the combustion fan, to obtain the required capacity.
If the unit is fitted with Grundfos Pumps DIP switch 5 should be switched on, to allow the pumps to
modulate. If modulation is not required DIP switch 5 should be switched off.
If the RAV 47 has malfunctioned, DIP switch 6 may be switched to ON, as an emergency measure, after which the unit will be kept at a steady 70ºC, independent of the heat demand. When the replacement controller has been installed, DIP switch 6 must be set to OFF again.
6.2.3 DIP switches
The unit has a number of DIP switches that must always be set. These switches have different functions. To access the DIP switches, the cover plate over the circuit boards must be removed.
1. Remove the two fixing screws on the lower edge of the top cover panel.
2. Slide the panel towards the front of the boiler and lift away.
3. The DIP switches are easily accessible at the left side of each control circuit board.
The RVA 47 must be set to the number of boilers installed on one system; in bus terms, each module
has its own address number, which must be set.
The master RVA 47 manager is capable of controlling up to four burners, and if four burners are
actually installed, four addresses must be set.
Subsequent RVA 47 controllers are capable of controlling 2 burners – the address must be set for
each unit.
If only one boiler is installed, two addresses must be set.
The first four DIP switches control the PPS number allocated to the burner module.
To enable the master RVA 47 to control modules 3 and 4, the PPS connection between boilers 1 and
2 must be installed with the correct polarity.
The suggested numbering format for the boiler modules are as follows:
Boiler with control fitted Left Circuit Board Lower Module Number 1
Right Circuit Board Upper Module Number 2
Boiler without control module Left Circuit Board Lower Module Number 3
Right Circuit Board Upper Module Number 4
Subsequent boilers with control fitted Left Circuit Board Lower Module Number 1
Right Circuit Board Upper Module Number 2
Table 7
Module Number 1 On Off On On Known as PPS #4 Module Number 2 On Off On Off Known as PPS #5 Module Number 3 On Off Off On Known as PPS #6 Module Number 4 On Off Off Off Known as PPS #7
30
STRATA2
6.3 firing the appliance
At the time of starting the appliance, the working gas pressure must be measured:
The inlet working gas pressure must be measured at the inlet test nipple of the gas control valve.
(see fig 6.4a).
Nominal pressure should be 20 mbar for the Natural gas and 37 mbar for LPG (Propane).
6.3.1 initial start up
Ensuring that the installation has been fully tested and having found everything in order, power can be applied to the unit by switching the main switch (fig 6.2a) to the ON position. Now place the switch for the lower module in the ON position. To be independent from the heat demand from the installation, press the Chimney Sweep button ONCE. The lower burner should ignite. If the appliance fails to start up, first check whether all gas taps, including the one on the unit have been opened.
Electrically, there is fourfold start-up procedure, after which a fault is reported (by flashing warning on the status display); press the RESET button for additional start up attempts. If the unit fails to start up correctly, the adjustment screw (2) (see fig 6.4a) on the gas valve must be turned clockwise
1
/4turn, and
then attempt to restart the appliance.
Note: If the display fails to show a figure, the RESET button should be pressed.
The start-up cycle has the following stages:
The combustion fan carries out an initial speed test at low speed – after which it will immediately
switch to:
Start Speed; when this has been reached, the gas valve will open and the unit will start up at 50% of its
capacity.
The safety time is 5 seconds, after which there is a stabilisation period for the flames, also lasting 5
seconds; this is followed by the units output being controlled via the RVA 47 cascade manager.
6.4 setting and adjusting the load
For checking purposes, or after installing a new gas control valve, there are two methods for setting the correct load.
By measuring the CO2percentage.
Checking by means of the gas rate measuring method.
Emissions must be measured in the opening, in the upper front right of the heat exchanger module, by first removing the test point cap. Refit test point cap when emissions checks have been completed.
Table 9 Unit Settings
For Natural Gas G20
Gas measuring method:
Maximum load per Heat Exchanger 213ft3/hour.
Minimum load per Heat Exchanger 42.6ft3/hour.
Note: Values measured at a boiler water temperature of circa 60ºC.
Type of Gas Natural Gas G20 Propane Gas Wobbe (MJ/m3) 49.79 76.06 Calorific Value Gross (MJ/m3) 38.63 93.87 CO
2
Max Load (%) 9 11
CO
2
Min Load (%) 9.5 11.5
31
STRATA2
3
2
1
gas valve
Q max
Q min
Burner offset pressure test point
Adjustments
Turning 2 clockwise increases min output & CO
2
%
Turning 3 Anti clockwise increases max output & CO2%
6.4.2 setting maximum load
The correct CO2combustion on low fire should now have been achieved. To set the maximum load:
Press the ‘Chimney Sweep button a second time, the letter H will appear in the display and the unit
will begin to operate at maximum capacity.
Again check the combustion figures.
If the CO2content is below the stated figure, increase the gas throughput by turning the adjusting screw
(3) counter-clockwise.
If the CO2content is above the stated figure decrease the gas throughput by turning the adjusting screw
(3) clockwise.
Pressing the ‘Chimney Sweep button a third time will return the unit to automatic mode, and the
display will show the flow temperature.
Note: Adjusting the high fire, has a marked effect on the low fire figures, whereas adjusting the low fire has little effect on the high fire figures.
It is therefore suggested that once the initial set-up has been carried out, a check is made of the two
settings before returning the unit to complete automatic operation.
6.4.3 setting maximum/minimum load for upper module
Repeat operations described in 6.4.1 and 6.4.2 – but applied to the upper module.
6.5 setting for propane gas
To set the unit for propane gas, complete the following steps:
Disassemble the gas pipe between the gas valve and the gas air pipe.
Install a propane nozzle with a diameter of 7mm on the outlet of the gas valve.
Reconnect the gas pipe.
To obtain the correct capacity, the combustion fan speed must be adapted for propane gas, by placing
the DIP switch 8 in the ON position.
Fig 6.4a
6.4.1 setting minimum load
To set the minimum load refer to figure 6.4a and follow the instructions below:
Press the ‘Chimney Sweep button once, the
letter L will appear in the display and the unit will commence operation at minimum capacity, for up to 10 minutes.
Check the combustion figures with those
stated above.
If the CO2content is below the stated figure,
increase the gas throughput by turning the adjusting screw (2) clockwise.
If the CO2content is above the stated figure,
decrease the gas throughput by turning the adjusting screw (2) counter-clockwise.
32
STRATA2
6.6 setting domestic hot water
The RVA 47 cascade manager can be set to control the temperature of the DHW either by means of a dedicated sensor or thermostat.
6.7 switching off the appliance
It is recommended to leave the appliance running throughout the year in order to prevent the unit from freezing, or moving parts from becoming blocked by corrosion. In order to avoid this, set the RVA 47 controller to the ‘standby’ position.
In this mode, the central heating unit will run the attached pumps for 1 minute in every 24 hours, while the frost protection may remain operative.
Table 10
(Prog#) Description of Prog # Range Inputs Preset
Time of Day
1 Time of day 0-23:59 Hr/Min 00:00 2 Weekday 17Day 1
Time Switch Program Heating
5 Every day the same 1-7 Day
Every day different 1…7Day 6 1st On time -24:00 Hr/Min 06:00 7 1st On time -24:00 Hr/Min 22:00 8 2nd On time -24:00 Hr/Min – 9 2nd On time -24:00 Hr/Min – 10 3rd On time -24:00 Hr/Min – 11 3rd On time -24:00 Hr/Min
Hot Water Service
13 Required DHW temperature 40-60 ºC55
Heating Circuit
14 Night set back temperature 10-30 ºC16 15 Frost protection temperature 4-15 ºC10 16 Summer/winter switching 8-30 ºC17 17 Slope of heating curve -/2.5.40 ºC32
7.0 boiler
control settings
Consult the descriptions provided with the various Seimens (Landis Steafa) control units, for full instructions on application and usage. In the absence of full control instructions the following abridged instructions will be useful.
7.1 end user parameter settings
To enter the End User Parameter Program, the door on the RVA 47 must be opened and one of the
UP or DOWN prog buttons must be depressed.
A number between 1 and 50 will appear in a bracket on the left of the display window. These can be
paged through by using the UP or DOWN buttons.
To alter or input the required data in the selected program line # use the + or – buttons.
To leave the End User Parameter Setting Menu press the AUTO button.
The defaults indicated below are for standard systems. If additional control features are required
alteration will have to be made. Please refer to the RVA 47 manual for additional details.
#, –, – – – Indicates where an input can be made if required.
● – – Indicates where an input cannot be made and a sensed/attenuated figure is displayed.
OFF will be displayed if the +/- buttons are used.
33
STRATA2
7.2 heating engineer parameter setting
To enter the Heating Engineer Parameter Program, the door on the RVA 47 must be opened and
the UP and DOWN Prog buttons must be depressed for at least 3 seconds until #51 appears in the window.
A # between 51 and 173 will appear in a bracket on the left of the display window. These can be paged
through by using the UP and DOWN buttons.
To alter or input the required data in the selected program line # use the + or – buttons.
To leave the Heating Engineer Parameter Setting Menu press the AUTO button.
Table 10
7.1 end user parameter settings (contd)
(Prog#) Description of Prog # Range Inputs Preset
Actual Values
18 Actual room temperature – – 19 Actual outside temperature -50. +50 ºC – –
(Pressing the + and – buttons simultaneously until the display stops flashing will reset the averaged value)
Maintenance
23 Restore factory presets 0/1 0
Press + and – together for 3 seconds
Time Switch Program DHW
29 Every day the same 1-7 Day
Every day different 1…7Day 30 1st Ontime -24:00 Hr/Min 06:00 31 1st Ontime -24:00 Hr/Min 22:00 32 1st Ontime -24:00 Hr/Min – 33 1st Ontime -24:00 Hr/Min – 34 1st Ontime -24:00 Hr/Min – 35 1st Ontime -24:00 Hr/Min
Service Indications
49 Module error code 1..4/0..255 – –
(Not always displayed) 50 Indication of faults 0…255 – –
34
STRATA2
(Prog#) Description of Prog# Range Preffered Setting
Service Values
51 Output test 0…30
0 Automatic control 1 All outputs off 2 DHW pump/valve on 3 Circulating pump on
52 Input test 0.5 0
0 Return temperature value 1 DHW temperature value 2 Flow temperature value 3 Outside temperature value 4 Room temperature value
5 0-10 V equiv. Temp 53 Plant Type # refer to drawings at rear of manual * 27…36 – – 54 Display of PPS communication details 1..12/0255
Actual Values
55 Actual value of module temperature 1..4/0..140 – – 56 Actual value of system flow temperature 0…140 – – 57 Actual value of system return temperature 0…140 – – 58 Actual value of Buffer temperature 0…140 – – 59 Actual value of DHW temperature 0…140 – – 60 Attenuated outside air temperature -50..+50 – – 61 Comp outside air temperature – –/– –– – 62 Outside air temperature source 00.01/14.16 – –
RVA 47 Dictated Set Points
65 Maximum flow module temperature 1..4/0..140 – – – 66 Maximum system flow temperature 8-85 – –
affected by external inputs 69 Display DHW temperature possible when operating 8-85 – – 70 Nominal room temperature set point 0.0/35.0 – – 71 Set point of room temperature 0.0/35.0 – – 72 Display of flow temperature set point 0…140 – –
Heat Generation Values
75 Modules available in cascade 00.1/16.3 – – – 76 Lead module in cascade 00.1/16.3 – – 77 Hours to run prior to sequence change 0..990 – – 80 Module #1 total operating hours 0.65535 – – 81 Module #2 total operating hours 0.65535 – – 82 Module #3 total operating hours 0.65535 – – 83 Module #4 total operating hours 0.65535 – – 90 Minimum system water temperature (not always displayed) 0..95 – – 91 Maximum output of module #1 0-255 55 92 Maximum output of module #2 0-255 55 93 Maximum output of module #3 0-255 55 94 Maximum output of module #4 0-255 55
Configuration of Plant
95 HKP pump output function 1…52
1 Pump operates as internal pump
2 Pump operates heating pump only
3 Pump operates as primary loop pump
4 Pump operates as DHW pump
5 Pump operates as H1 pump 97 Operation of RFO sensor 1..2 1
1 Sensor used for return temperature
2 Sensor used for buffer tank temperature
Table 11
7.2 heating engineer parameter setting (contd)
* = Full controls equipment manual
35
STRATA2
Table 11
7.2 heating engineer parameter setting (contd)
(Prog#) Description of Prog# Range Preffered Setting
Space Heating
100 Displacement of heating curve -4.5..+4.5 0 101 Gain factor for room temperature influence 0..1 1
0 Active 1 Inactive
102 Room temperature pump switching differential – – –/0.5..4 0.0
Higher = Less stable temperature
Lower = More stable temperature 103 Minimum limitation of flow temperature 8…95 8 104 Maximum limitation of system flow temperature 8…95 82 105 Type of build construction 0/1 1
0 Heavy
1 Light 106 Adaption of heating curve 0/1 1
0 Inactive
1 Active
DHW
120 Reduced DHW set point 8-70 40 121 DHW time control 0..2 1
0 24 hours per day
1 As heating times with 1 hour shift
2 As DHW time settings 122 Pump operation 0..1 1
0 Heating timeswitch settings apply
1 DHW timeswitch settings apply 123 DHW control in cascade system 0..2 2
0 Controlled via master RVA 47
1 Controlled via all RVA 47s in segment
2 Controlled via all RVA 47s in LPB system 124 DHW charging cycles per 24 hour period 0..1 1
0 One per day with 2.5 hour forward shift
1 Several per day with 1 hour forward shift 125 DHW sensor type 0..1 0
0 Sensor
1 Thermostat switch 126 Flow temperature boost in DHW mode 0..30 20 127 DHW Priority/Shifting 0…31
0 Absolute priority
1 Shifting priority heating reduced to
increase recovery on DHW
2 No priority DHW and heating operate
3 Shifting/Absolute heating switched off,
mixing circuit decreased to increase recovery of DHW. 129 DHW reduced set point priority 0..1 1
0 No, heat taken from heating circuit to
increase DHW temperature
1 Yes, DHW boosted in isolation.
Cascade Settings
130 Hours run prior to sequence rotation 10.990 100 131 Rotation sequence program 0..3 0
0 No exemptions
1 The first module is exempt
2 The last module is exempt
3 The first and last modules are exempt 132 Lead module fixed/sequenced. 00.1…16.3 – – –
Allows one module to be lead unit 133 Cascade delay time 1..120 2 134 Anti cycling time 0..1800 180
36
STRATA2
(Prog#) Description of Prog# Range Preffered Setting
LPB communication setting
140 LPB control device address 0..16 1
0 Standalone single RVA 47 1 Master RVA 47 cascade manager with sensors attached 216 Slave RVA 47s operating from master RVA 47 (ie House No.) (Each subsequent RVA 47 should be given consecutive numbers)
141 LPB control segment addres 0..14 0
0 Heat generator (ie Street name) 1.14 Heat consumer
142 LPB Bus power supply 0..1 1
0 Off
1 On 143 Operation of LPB power supply On/Off – – 144 Display of LPB communication On/Off – – 145 Change over via LPB connection 0..1 1
0 All controllers in same segment
1 All controllers in LPB system 146 Summer/Winter change over function 0..1 0
0 Local control only
1 Entire control via LPB 147 Central Standby switching 0..1 0
0 Deactivated
1 Activated 148 Clock mode 0..3 2
0 Autonomous Clock Individual controller
can have different times
1 System time, time will match system
cannot be adjusted
2 Systems time with adjustment
3 System clock, master.
There can only be one master on system
Input H1
170 Operation of H1 terminals 0..4 0
0 Changeover of operation when switch is made.
(DHW stopped)
1 Changeover of operation when switch is made.
(DHW released)
2 Minimum flow temperature maintained (set at 171)
3 Heat generation stopped when switch is made.
(Frost Active)
4 0-10 Volt control to vary flow temperature.
(Curve set at 172) 171 Minimum temperature set point for H1 8..95 80 172 Maximum temperature set point for H1 5…130 82 173 Operating action of H1 control contacts 0..1 1
0 The contact is normally closed
1 The contact is normally open
The RVA 47 will operate according to its internal time switches and presets. If a remote BMS is
controlling the RVA 47 via a Volt Free switch across H1 ‘0’ should be inserted.
This will allow the boilers to operate when the Volt Free switch is made and stopped (blocked), when
the switch is opened.
If you are controlling the lead (master) RVA/Boiler via a volt free switch across H1, all slave modules
should be left with ‘1’ as the input. This will allow the AUTO light and the OFF light to indicate their
operational mode dictated by the lead (master) RVA/Boiler.
Table 11
7.2 heating engineer parameter setting (contd)
STRATA2
37
Table 12
7.3 OEM parameter setting
To enter the OEM Parameter Program, the door of the RVA 47 must be opened and the UP and
DOWN Prog buttons must be depressed for at least 10 seconds until 00000 appears in the window.
The 00000 display must be changed to 11111 by inputting a password. The password for the RVA 47
is DOWN, DOWN, PLUS, MINUS, UP.
A # between 2 and 92 will appear in a bracket on the left of the display window. These can be paged
through by using the UP and DOWN buttons.
To alter or input the required data in the selected program line # use the + or – buttons.
To leave the OEM Parameter Setting Menu press the AUTO button.
(Prog #) Description of Prog # Range Preferred setting
Heat source OEM
1 Minimum module temperature (manual operation) 8..95 8 2 Maximum module temperature (manual operation) 8..120 82 8 HKP, SLP Pump overrun timer 0..20 5 22 Minimum limitation of boiler return temperature 8..95 8
(not always displayed) 25 Calibration of module #1 -100..+100 13 26 Calibration of module #2 -100..+100 13 27 Calibration of module #3 -100..+100 13 28 Calibration of module #4 -100..+100 13
Space Heating OEM
30 Room influence gain factor 0..20 4 31 Quick setback constant 0..20 2
(room sensor dependant)
Increase. Setback will become longer
Decrease. Setback time will become shorter 32 Boost of room temperature set point 0..20 5
(room sensor dependant)
Increase. Heat up time reduced
Decreased. Heat up time increased 33 Frost protection program 0..1 1
0 Frost protection program switched. Off
1 Frost protection program switched. On 34 Over temperature pump protection 0..1 1
0 Deactivated
1 Activated 35 Heat gains -2…+4 0
Increase. If gains are high
Decrease. If gains are low 36 Curve Adaptation 1 sensitivity 1…15 15
Outside air range between 4-12ºC 37 Curve Adaptation 2 sensitivity 1…15 15
Outside air range below 4ºC
DHW OEM
40 Maximum DHW set point 8…80 60 41 DHW switching differential (sensor only) 0..20 5 42 Legionella protection program 0..1 1
0 Inactive
1 Activated (every Monday morning) (oem43) 43 Legionella temperature 8..95 70 44 DHS discharge protection 0..2 2
0 Protection not active
1 Protection active
2 Protection active when heating is locked
(not always displayed)
Cascade Setting OEM
50 Cascade management strategy 1…62
1 Automatic
2 Automatic
3 Automatic
4 Fixed
5 Fixed
6 Fixed
38
STRATA2
(Prog #) Description of Prog # Range Preferred setting 51 Minimum output % reached prior to 5..100 40
cascade switching modules Off
52 Maximum output % reached prior to 5..100 80
cascade switching modules On
56 Time spent by module on ignition rate prior 0..1200 0
to modulation. (delay time between modules)
60 Minimum temperature difference between
flow and return temperature 0..20 2
Configuration of Plant OEM
90 Display default 0..1 0
0 Day # Time of day
1 System flow temperature 91 Software version 00.0…99.9 – – 92 RVA 47 controller operation hours 0.500,000 – –
Table 12
7.3 OEM parameter setting (contd)
8.0 maintenance
and inspection
The frequency of servicing will depend upon particular conditions and usage, however for general guidance, maintenance/inspections should take place at least every 12 months. Prior to carrying out any required maintenance, the unit must be inspected.
8.1 inspection
Complete the following steps before commencing inspection:
Ask the user for any problems with the Central Heating unit or any other comments regarding the
appliance.
Check the water pressure and treatment level of the installation.
Remove the casing of the unit and inspect all pipes and connections for water leaks.
Open the syphon rinsing pipe at the back of the boiler.
Run the unit at maximum capacity and measure the load or the CO2.
Run the unit at minimum capacity and measure the load or the CO2.
Listen to the sound of the module pump.
Disassemble the burner by removing the six M6 bolts, removing the ignition cable and disassembling
the two combustion fan cables.
Inspect the combustion fan blades.
Check the spark between the electrode and the burner this should be between 5 and 6mm.
Check the interior of the heat exchanger for any contamination.
STRATA2
39
8.2 maintenance
Any maintenance must be carried out as a result of faults noted in the inspection. Remarks and
comments made by clients must be considered and the causes of any faults or problems must be found.
Note: The pressure of the installation must be not less than 0.5 bar, any leakage within the system will affect the pressure and so must be identified.
If the module pump makes an un-natural noise, and in particular if the pump is more than 5 years old,
the pump should be replaced by way of preventative action.
If the interior of the heat exchanger is contaminated and/or there is a deposit on the stainless steel pipes, the latter must be removed with a hand brush or citric acid (do not use a steel brush). Remove any dirt created with a vacuum cleaner.
Note: Never clean the burner itself.
The Condense syphon must be rinsed. This can be done by removing the burner and using a filling hose, insert water into the heat exchanger, which will automatically reach the syphon.
If dirt has deposited on the combustion fan blades, each blade must be carefully cleaned, until the blade material is visible again. If this is not done evenly, the combustion fan will rotate out of balance.
9.1 control panel
The control panel is divided into two sections, the left hand section serves the lower heat exchanger and the right hand section serves the upper heat exchanger.
The two digital displays provide the following information regarding the functioning of the Strata 2-120:
Normal operating situations, the display always shows the flow temperature of the boiler water.
Operating messages, which are always indicated by one digit.
Fault messages, which are always indicated by flashing two digits.
System faults in the FMT 310 module control unit.
9.1.1 operation indicator
An operating message means that the burner of the heat exchanger concerned is not operational, the reason being reported in the operating message. If this situation has resolved itself after some time, the unit will automatically restart.
0. Unit prevented from operating. Styphon monitoring active.
If the water level in the syphon has dropped, the unit will automatically restart.
1. Unit prevented from operating. Water temperature too high, measured by the
boiler thermostat.
If the water temperature drops by more than 20ºC within 30 seconds, the unit will start to operate,
if this is not the case, the unit will lock out.
OR
1. Unit prevented from operating. Condensate syphon overfill.
If the condensate produced by the unit is not allowed to pass from the unit to a suitable drain
point the level switch located in the base of the flue gas tube will activate and prevent the unit
from operating.
9.0 fault
diagnosis
40
STRATA2
2. Unit prevented from operating. Water temperature too high, measured by the flow sensor.
When the water temperature drops by more than 20ºC the unit will start to operate.
3. Unit prevented from operating. Anti-cycling time.
When the anti-cycling time (3 minutes has expired, the unit will automatically fire up again).
5. Unit prevented from operating. Combustion fan speed too high.
The combustion fan has been switched off, but a speed indication is still detected. The Strata 1-120 will be blocked and after 3 minutes, a locking (flashing) fault will be shown with the same text. If, however, the situation is resolved within 3 minutes, the unit will return to normal operating mode.
7. Unit prevented from operating. Combustion fan speed too low.
If this code appears, the Strata 1-120 will be blocked. If the speed has not returned to the normal value within 3 minutes, locking will take place. If the situation is resolved within this period, the unit will resume normal operation.
8. Unit prevented from operating. Flame simulation.
Although the burner is not operative, a possible flame is being detected. If this code is shown, the burner control will be blocked. After five seconds, the burner control will be locked.
9. Unit prevented from operating. Limit temperature flue gases.
If the flue gas temperature drops by more than 20ºC, the unit will automatically fire up again, if this is not the case, the unit will lock out.
da Communication between burner control and RVA 27 interrupted (PPS).
The burner in question will not operate until the circuit is re-established - check all PPS wiring connections for security. Apply contact cleaner to all PPS connections. Check voltage on PPS connections should be 10-15vdc.
db Communication between burner control and the ignition control
board interrupted.
The burner in question will not operate until the circuit is re-established.
9.1.2 fault indicator (flashing)
The unit automatically makes several attempts to resolve any malfunctions in the system, if these
attempts prove unsuccessful the unit is switched off. The fault is indicated by means of a flashing code.
The type of fault is indicated by a two digit code, the first digit shows when the fault occurs, the second
digit shows the nature of the fault. This means that any combination of digits may show, but some combinations will never occur.
Refer to the tables below for fault types:
9.1.1 operation indicator (contd)
1. System Test
2. Stand by
3. Pre Purge
4. Pre Ignition
5. Ignition
6. Operation
7. Post Purge
1. Maximum thermostat open, or water level in syphon too high
2. Flue gas thermostat open
3. Resistance in the flue gas tube is too high
4. Unused figure
5. Combustion fan speed too low
6. Combustion fan speed too high
7. No flame signal
Table 13 First Digit
Table 14 Second Digit
For example, if the flashing fault code 6 7 appears, this means that the flame has disappeared several
times during operation.
41
STRATA2
9.1.3 system faults
These faults are indicated with a letter, occasionally followed by a number. To avoid confusion in the
indication, the letters and numbers are fixed as follows:
9.2 RVA 47 Fault Indication
If the sensor or burner modules connected to the RVA 47 controller fail or are removed from the
circuit, an error message will be displayed on the left of the LCD screen.
Error Message Notation ER
Once an error message is present the cause of the error can be traced by accessing function (50).
To access function (50), open the flap of the controller and press down arrow button twice. (50)
should appear in the left-hand side of the LCD display.
The figure shown in the centre of the screen is the fault identification number. The display can hold a
number of faults but will only display 2 at any one time. The second error can be accessed by pressing the + or – buttons.
Once a fault has been rectified the error number will disappear or be replaced with another fault
number if further attention is required.
The fault identification numbers are detailed below:
E1 Fault with flow sensor E2 Fault with cable for gas valve or gas valve coil E3 Fault with rectification circuit E4 Burner control circuit board has a fault – – Communication via RS232 connection possible E5 Parameter fault E6 Communication fault
Table 15
Blank No Fault 10 Outside air temperature sensor 26 System flow temperature sensor 46 Boiler circuit return temperature sensor 50 DHW temperature sensor 58 DHW control thermostat 61 Fault room unit 81 Short circuit on LPB connection 82 Address conflict on LPB circuit 86 Short circuit on PPS connection 100 Two clock masters present 145 Wrong device connected 146 Unrecognisable plant configuration 147 No burner module connected 150 General burner module fault
Table 16
42
STRATA2
11.0 guarantees
The boiler body and exhaust system both carry a five year material guarantee.
The burners and all electrical components and other component parts carry a one year guarantee.
The guarantee starts at the day of delivery.
This guarantee only applies if regular maintenance has been carried out.
In addition, no guarantee is made for damages which have arisen from:
Unsuitable and inappropriate utilisation.
Erroneous assembly and/or start of operation by unqualified persons.
Operational wear.
Erroneous or careless treatment.
Incorrect burner adjustment.
Lack of, or unsuitable water treatment additives.
Non-observance of the installation, start of operation and maintenance instructions
Inappropriate changes or repair works carried out by the customer or third parties.
Contaminated combustion air.
Waterside contamination (fouling, scaling etc).
10.0 parts list
The Parts List is for service purposes. If no numbers have been listed, the parts concerned are non
serviceable parts.
Short spaces parts list:
Description of Part Part Number Water temperature sensor 252014 Limit thermostat 250083 Fan 252013 Pump 130160 Gas valve 251166 Ignition electrode 251095 Ignition transformer 252033 Control PCB, Fmt 310 252032 Fuse 6.3A 250V 252037 Manometer 0-4 bar 252027 O-ring set O-ring kit
STRATA2
QW/04/01
This publication is issued subject to alteration or withdrawal without notice.
The illustrations and specifications are not binding in detail. All offers and sales are subject to the Company's current terms and conditions of sale.
35 Nobel Square, Burnt Mills Industrial Estate, Basildon, Essex SS13 1LT Tel: 01268 591010 Fax: 01268 728202
http://www.modular-heating-group.co.uk
A member of the Modular Heating Group Plc
Loading...