ULTRA HIGH EFFICIENCY CONDENSING BOILER
INSTRUCTIONS FOR INSTALLATION, SERVICING
& OPERATION FOR MODELS 45, 60 & 75
STRATA1
L 102
2
STRATA1
Index
pagesection
3
. . . . . . . . . . . . .
1.0
General Notes
4-5
. . . . . . . . . . . .
2.0
Product Description
6
. . . . . . . . . . . . .
3.0
Technical Data & Dimensions
7
. . . . . . . . . . . . .
4.0
Delivery Consignment/Unpacking The Boiler
. . . . . . . . . . . . . .
5.0
Boiler Location
. . . . . . . . . . . . . .
6.0
Installation Clearances
8
. . . . . . . . . . . . .
7.0
Wall Mounting
. . . . . . . . . . . . . .
8.0
Gas Connection
9
. . . . . . . . . . . . .
9.0
System Flow & Return Connections
. . . . . . . . . . . . . .
10.0
Condense Waste Connection
10
. . . . . . . . . . . .
10.0
Condense Waste Connection (contd)
. . . . . . . . . . . . . .
11.0
Flue Combustion Air Connection - General
11
. . . . . . . . . . . .
12.0
Conventional Flue Installation
12-18
. . . . . . . . . .
13.0
Room Sealed Flue Installations
19
. . . . . . . . . . . .
14.0
Examples of Calculating Flue Pressure Loss
20
. . . . . . . . . . . .
14.1
Calculating Flue Resistance
20-21
. . . . . . . . . .
15.0
Flue Terminal Positions
22-23
. . . . . . . . . .
16.0
Ventilation Requirements Single Appliances
24-32
. . . . . . . . . .
17.0
Hydraulic system Design (circuit diagrams)
33
. . . . . . . . . . . .
17.1
Filling The System
. . . . . . . . . . . . . .
17.2
Water Treatment System Cleaning
34
. . . . . . . . . . . .
17.3
Inclusion of Strainers
. . . . . . . . . . . . . .
17.4
Low Water Pressure Protection
. . . . . . . . . . . . . .
17.5
Care With The Use of Soldering Flux
. . . . . . . . . . . . . .
18.0
Electrical Connections
35-43
. . . . . . . . . .
18.0
Electrical Connections (contd)
44-45
. . . . . . . . . .
18.1
Optional Matched controls
46
. . . . . . . . . . . .
18.2
0-3/0-10 Volt Control
. . . . . . . . . . . . . .
19.0
Commissioning The Strata 1 Boiler
47
. . . . . . . . . . . .
19.1
Pre-Commissioning Checks
. . . . . . . . . . . . . .
19.2
LPG Conversion Procedure
. . . . . . . . . . . . . .
19.3
First Firing
48
. . . . . . . . . . . .
19.1.1
Dip Switch Settings
49
. . . . . . . . . . . .
19.3
First Firing (contd)
50
. . . . . . . . . . . .
19.3
First Firing (contd)
50-52
. . . . . . . . . .
19.4
Setting Weather Compensation
53
. . . . . . . . . . . .
19.5
Setting Domestic Hot Water Temperature
. . . . . . . . . . . . . .
19.6
Service Button/Setting Heating Output
54
. . . . . . . . . . . .
19.6
Service Button/Setting Heating Output (contd)
. . . . . . . . . . . . . .
19.7
Output For Charging Hot Water
. . . . . . . . . . . . . .
20.0
Setting The Boiler To Work
55
. . . . . . . . . . . .
21.0
Servicing Instruction
. . . . . . . . . . . . . .
21.1
Inspection
55-56
. . . . . . . . . .
21.2
Maintenance
57-59
. . . . . . . . . .
22.1
Screen Display/Diagnosis Of Faults
59-60
. . . . . . . . . .
22.2
(Possible) Causes Of Fault & Corrective Action
61
. . . . . . . . . . . .
23.0
Instructing The User
. . . . . . . . . . . . . .
23.1
To Turn On the Appliance
. . . . . . . . . . . . . .
23.2
To Turn Off the Appliance
62
. . . . . . . . . . . .
24.0
Strata 1 45, 60, 75 Expploded View
3
1.0 general
notes
STRATA1
These instructions are intended to assist the installer, commissioning engineer, maintenance engineer
and user with the installation, maintenance and usage of Strata 1, 45, 60 and 75 models gas fired
condensing boilers.
Please read this manual fully before commencing the installation of the appliance. The Strata 1 must
only be installed by persons deemed to be competent i.e. Corgi Registered. This manual must be handed
to the appliance user following completion of the installation.
conformity statement
Strata 1 45, 60, & 75 boilers are manufactured to the highest standard of quality, performance and
safety, in accordance with EC standards. Strata 1 45, 60 & 75 boilers carry the CE mark.
installation requirements
The installation of Strata 1 45, 60 & 75 boilers must be in accordance with the relevant requirements
of Gas Safety (Installation and Use) Regulations 1994, Health & Safety at Work Act, Building Regulations,
I.E.E. Regulations, Construction (Design & Management) Regulations 1994, Local Authority Bye-Laws,
Local and National Water Bye-Laws, Fire Authority Regulations and Insurance Company requirements.
The following Codes of Practice are also applicable:-
•BS6798: 1987 Specification for installation of gas fired hot water boilers of rated input not
exceeding 60kW.
•BS6880 Code of Practice for low temperature, hot water heating systems of output greater than
45kW. Parts 1, 2 and 3: 1988.
•CP342 Part 2: 1974 Code of Practice for centralised hot water supply.
•BS5440-1:2000 1991 Specification for gas fired hot water boilers of rated inputs between 60kW
and 2MW.
•IGE/UP/2 Gas installation pipework, boosters and compressors on industrial and
commercial premises.
•CIBSE Guide Reference sections B7, B11 and B13.
•BS5440-1:2000 - Installation of flues and ventilation for gas appliances of rated input not exceeding
70kW nett (1st, 2nd and 3rd family gases). Part 1: Specification for the installation of flues.
•BS5440-2: 2000 Installation and maintenance of flues and ventilation for gas appliances of rated input
not exceeding 70kW nett (1st, 2nd and 3rd family gases) Part 2: Specification for installation and
maintenance of ventilation for gas appliances.
•IGE/UP/10 Installation of gas appliances in industrial and commercial premises.
4
STRATA1
2.0 product
description
The Strata 1 range of wall mounted gas fired condensing boilers are state of the art appliances which
include a comprehensive range of features. The appliance must only be used on sealed and pressurised
systems. System design must take into account the boiler operating ∆t of 20°C.
wall mounted with compact dimensions
At 900H x 458W x 435D, the Strata 1 boiler provides maximum heat from minimum dimensions
without compromising serviceability.
fully modulating heat output
The output of the boiler is fully variable, sliding between (approx.) 20% to 100%, which automatically
and instantly adjusts to match the needs of the system. The percentage of power at any given time can be
dictated by either outside air temperature, flow temperature, return temperature, stored domestic hot
water temperature, or room temperature, or a combination of the aforementioned.
fully condensing stainless steel heat exchanger
The Strata 1 boiler is designed with extended heat exchange surface area and is fabricated from
corrosion resistant long-life stainless steel. The unique Spiranox heat exchanger will return operating
efficiencies from 86% gross (96% nett) at 60°C return temperature, up to 97% gross (107% nett), at 30°C
return temperature.
extremely low harmful emissions
The boiler utilises 100% pre-mix gas/air fed at positive pressure to the metal fibre sheathed radiant
burners. The combustion system incorporates internal flue gas re-circulation and this combined with the
precise nature of pre-mix fuel/air control, gives ultra low emissions to satisfy the most stringent emission
regulations in the world currently. That is: < 20mg/kWh NOx (14 ppm DAF) and < 14mg/kWh CO (13
ppm DAF). The fully modulating nature of the appliance also reduces emissions by avoiding repeated
start/stops and the associated increase in emissions, which occurs with burner on/off cycling.
accurate variable burner output control
The pre-mix burner fans have low voltage direct current drive motors with pulse relay counting. This
system allows precise control over fan speed/combustion air volumes. Coupled with a gas valve system set
to provide proportionately measured volumes of fuel to air, which allows extremely accurate and instant
variable burner output control to be achieved.
energy saving
In addition to the extremely efficient burner and heat exchanger system employed in the Strata 1, each
appliance includes modulating speed boiler primary pumps.
This feature allows the boiler to self-maintain a 20°C ∆t across the heat exchanger, optimising the heat
exchanger efficiency and reducing also the electrical consumption of the pump motors. The result is a
seasonal increase in boiler efficiency of a further 7-10% and a reduction in pump electricity consumption of
up to 70%.
5
STRATA1
2.0 product description (contd)
natural gas or LPG
Appliances can be supplied for use with natural gas (G20) or LPG (G31).
comprehensive microprocessor control
The boiler control panel includes a user friendly microprocessor control centre which manages the
entire function of the appliance and encompasses:-
1. Management of the essential safety functions of burner ignition and flame monitoring.
2. Water high temperature and flue gas high temperature safety cut out.
3. Modulation of the boiler output and pump speeds in conjunction with operating temperature control.
4. LCD display screen with two lines of text to continuously display operational or fault status.
5. In built weather compensator to provide direct-on boiler VT flow temperature (if required).
6. Remote stored hot water temperature control.
7. In built 2 stage boiler frost protection program.
8. In built pump exercising program to avoid standstill seizure.
9. Cold start boost facility.
10. PC compatibility with data logging which allows communication with the boiler via a lap-top computer
to review/modify operational parameters and access operational history as an aid to fault finding and
preventative maintenance.
11. Range rate adjustment which allows the power to be set to accurately match the maximum needs of
the system, with the facility to set a different firing rate for heating. Output to hot water self adjusts to
the heat transfer capability of the calorifier.
12. Facility to connect optional matched control components which allow the boiler to control a heating
circuit pump, (PR01) HWS primary pump or diverter valve and an underfloor circuit mixing valve and
pump (MR03), plus the ability for the boiler to be controlled by a remote multi function modulating
room unit (RE2132). Multiple boilers may be connected to a modulating Kaskade manager (KKM2) or
controlled via a 0-3 or 0-10v * signal (*via adaptor) which further enhances the operating efficiency of
a larger load modular boiler system.
room sealed option
If required, the boiler may be installed to be completely room sealed, taking combustion air directly
from outside the building, using a 125/80 concentric air duct/flue duct system. Inherent safety is afforded
by the negative pressure within the boiler casing, which in the event of incorrect sealing results in safe
inward air leakage only.
extended flue lengths
The excess fan pressure from the combustion system is 100 Pa, which allows the appliance to be
exhausted using small diameter PPS plastic flue components, over long distances, allowing for complete
flexibility in boiler siting.
designed for ease of maintenance
Although compact, the Strata 1 does not compromise serviceability. The appliance has been engineered
to be easy to maintain with even the most major of service operations being able to be completed easily
and quickly with the minimum of tools.
guarantee
The heat exchanger carries a five year guarantee against manufacturing or material defect. All other
parts carry a one year warranty against manufacturing or material defect.
/h
Minimum/Maximum Gas Pressure mbar
Flue Gas Volume (Hot)m
3
/h
Pressure at Flue OutletPa
Maximum Working PressureBar
Minimum Working PressureBar
Maximum Flow Temperature°C
Power SupplyV
Fuse RatingA
Average Power ConsumptionWatts
Water ContentL
Weight (Dry)kg
Design ∆t°C
45
43
41.3
45.2
4.7
1.76
18/60
64
100
3.0
0.5
85
230
3.0
115
6
60
20
60
57
54.7
59.9
5.9
2.33
18/60
81
100
3.0
0.5
85
230
3.0
115
7
66
20
75
72
69.1
75.6
7.6
2.95
18/60
104
100
3.0
0.5
85
230
3.0
115
8
73
20
38
108
229
458
55
231
435
123
4
50
950
front - all models
plan - models 45/60/75
125 67 8
38
108
193
238
35
24
55
underside - models 45/60/75
pH of Condense Water 4 to 5.5
Connection Strata 1
1. Return
2. Flow
3. Flue Gas (OD)
4. Air Duct (OD)
5. Condense Syphon
Cleaning Point (capped)
6. Condense Waste
7. Cable Entries
8. Gas
45
11/4" BSP-M
1
1
/4" BSP-M
80mm
125mm
3
/4" BSP
3
/4" BSP-M
3
/4" BSP-M
60
11/4" BSP-M
1
1
/4" BSP-M
80mm
125mm
3
/4" BSP
3
/4" BSP-M
3
/4" BSP-M
75
11/4" BSP-M
1
1
/4" BSP-M
80mm
125mm
3
/4" BSP
3
/4" BSP-M
3
/4" BSP-M
Multiple Grometts
77
STRATA1
4.0 delivery consignment
/unpacking the boiler
The boiler is delivered as a consignment of a carton containing the boiler and associated fittings, plus
any other optional ancillary flue or control components in separate cartons.
The boiler carton contains:-
● Assembled boiler
● Wall mounting bracket
● Fittings carton including 2Nr 11/4” x 11/4” x 1/2” BSP Tees, 2Nr 11/4” x 1/2” BSP reducing sockets,
1Nr 3/4” BSP Inlet x 1” BSP outlet safety valve set 3.0 bar, 1Nr 3/4” x 1/2” BSP reducing nipple (for
safety valve inlet) and 1Nr outside air temperature sensor.
To unpack the boiler, the palleted carton should be laid on the floor. Carefully cut the nylon bands and
lift away fibre board protective panel. Open carton top and lift out wall hanging bracket and fittings bag.
Remove packing material and lift away bottomless carton. With 2 men, carefully lift boiler from palette by
holding grey rear chassis only.
To remove the casing from the boiler, slacken the screw in the underside of the casing, unlatch left and
right hand catches on underside of case, pull casing slightly to the front and lift upwards to disengage casing
hooks from rear chassis and then remove casing to the front.
5.0 boiler
location
The Strata 1 Boiler is not suitable for installation external to a building. The position chosen for the
boiler must be a structurally sound wall capable of supporting the weight of the boiler and any ancillaries.
The position should allow for access to a condense waste drain nearby or an alternative is to install a
condense sump receptacle and condense disposal pump which should remove the condense waste water
to a remote drain. The wall mounting position of the boiler must allow the boiler to be true plumb vertical
to ensure correct operation of the internal gravity flow condense system. The position for the boiler must
satisfy the requirements of BS6798:1987 or BS6644:1991.
6.0 installation
clearances
For ease of installation, commissioning and maintenance the following minimum clearances should
be observed:-
Sides50mm
Above250mm
Below150mm
Front450mm
8
STRATA1
7.0 wall
mounting
The Strata 1 boiler mounts to the wall via
a wall mounting bracket which interlocks to a
rail mounted upon the rear of the boiler. The
wall mounting bracket should be firmly fixed
to the wall using suitable fixings with
countersunk heads. The wall mounting
bracket positioning detail is shown in fig 1.
The boiler must be carefully offered up to the
wall so that the rail on the rear of the boiler
is just above the wall mounting bracket and
then the boiler should be lowered to engage
the bracket and rail. Lifting is advised with 2
persons. Do NO
T lift the boiler by the
internal parts of the appliance.
important Note
When viewed from the side, the
north/south axis of the boiler must be
vertical. The appliance must not be inclined
out from the top, if necessary block or shim
behind the bottom rear of the boiler to
achieve a vertical installation.
8.0 gas
connection
The gas connection is located at the base
of the appliance rear r/h side, see fig 2.
The pipe size used to supply the
appliance must not be smaller than the gas
connection size on the appliance.
The connection to the appliance
must include a suitable method of
disconnection and a gas control cock must be
installed adjacent to the appliance for
isolation purposes.
The gas pipe used to supply the appliance
must not allow a pressure drop of greater
than 1m bar from the meter to the appliance.
The nominal inlet working gas pressure
measured at the appliance should be
20.0 mbar for Nat Gas (G20) or 37 mbar for
LPG (G31).
A gas pressure test point should be
installed between the gas control cock and
the appliance, so that nominal inlet gas
pressure test can be undertaken.
Gas Connection
3
/4" BSP Male
Fig 2.
Fig 1.
3 x ø 7.0
170
458
50
165
170
735900
STRATA1
9
Note The Strata 1 boiler must only be installed on sealed and pressurised systems. The maximum
working pressure of the boiler = 3 bar. A safety valve set 3.0 bar is supplied with the boiler and must be
installed onto the flow pipe adjacent to the boiler. It is recommended that the final working pressure (hot)
of the system does not exceed 2.3 bar.
The boiler is equipped with 2 sets of 1
1
/4" BSP Male flow & return connections which are located top
rear L/h side & bottom rear L/h side. See figs 3&4.
The installer may choose to use both top connections or both bottom connections or one of each (e.g.
flow-top, return-bottom). The appliance is supplied complete with 2Nr 1
1
/4" x 1/2" BSP reducing sockets
(see fig 3. item A) which may be used either at the top of the appliance (when flow and return connections
are made to the lower boiler connections) to install air vents or be used at the bottom flow and return
connections (when system connecting are to the top of the appliance) to install drain cocks.
The appliance is supplied with 2Nr 1
1
/4" x 1 1/4" x 1/2" BSP Tees (see fig 4. item B) which may be used
to connect the supplied safety valve into the flow pipe adjacent to the appliance and either a system filling
point/expansion vessel or a draincock. The flow and return pipework should include isolation values and a
method of disconnection local to the boiler.
9.0 system flow
& return connections
10.0 condense
waste connection
Return
A
B
Fig 3.
Fig 4.
Flow
Flow
Return
The condense waste connection is located at the underside rear of the appliance see fig 5. The
condense syphon cleaning point is factory fitted with a heavy grade black plastic cap which MUST NOT BE
REMOVED (see fig 5) apart from routine maintenance cleaning operations and must be in place whenever
the appliance is in operation. WARNING operating the appliance with the cap removed from the syphon
cleaning point will cause products of combustion to be discharged from the cleaning point.
The condense waste connection is a
3
/4" BSP Male threaded stub fabricated from
plastic. The installer must connect to this stub, a condense waste pipe fabricated
from plastic tube and fittings (
3
/4", 22mm, overflow pipe is considered suitable).
Copper Tube is not acceptable. The condense waste pipe must fall continuously
from the appliance to suitable nearby drain.
10
STRATA1
10.0 condense waste connection (contd)
If any part of the condense waste pipe is to be
run external to the building or is at risk of freezing,
then the pipe must be suitably insulated to protect
from freezing.
If a suitable drain for accepting the condense
waste is not available nearby to, and below the
boiler, (e.g. boiler installed in a basement below
ground level location), then a suitable condense
sump receptacle with a discharge pump should be
installed below the boiler to remove the condense
to a remote drain.
When making the condense waste pipe
connection to the boiler, do not use adhesives, it is
recommended to lightly apply a suitable jointing
tape (PTFE or similar) and use only light pressure to connect fittings to the appliance to avoid damage to
the condense waste outlet assembly.
It is recommended that the condense waste pipework should include a method of disconnection and
cleaning points.
11.0 flue/combustion
air connection - general
The flue connection and combustion air inlet
to the appliance are located on the top of
the appliance see fig 6. These connections are
arranged concentrically with the 80mm flue gas
connection centrally within the 125mm air inlet
connection. There are two options for flueing the
Strata 1 boiler.
i) Conventionally, using flue gas tube only and
air for combustion from the room or
compartment in which the appliance is installed. If
using a conventional flue arrangement then the
room or compartment must be ventilated in
accordance with the requirements of BS 6644 or
BS5440 as appropriate. For guidance on ventilation
see section 16.
ii) Room sealed using concentric 80/125
components or two seperate tubes where air for
combustion is taken from outside of the building.
When using a room sealed flue, where air for
combustion is provided from outside of the building
directly to the appliance, ventilation to a
compartment may still be required - See section 16
for general space cooling.
Multiple Boilers
On common flues serving multiple boilers, contact MHS Boilers Ltd.
Important Note
Where the Strata 1 is to be installed in an application where the combustion air
is likely to be contaminated with oxidising agents, such as swimming pool areas,
special industrial processes etc, then the appliance must be room sealed.
typical modular
flue arrangement
Inspection
Area
Air Inlet
Flue gas
Connection
Fig 6.
Condense
Waste
Connection
Syphon Cleaning Point
MUST
remain capped
Fig 5.
11
STRATA1
12.0 conventional
flue installation
The Strata 1 boiler has an excess pressure combustion system, which coupled with the very low flue
gas temperatures produced allows the appliance to exhausted over considerable distances using 80mm
Polypropylene PPS flue pipe and fittings. Suitable flue pipe and fittings are available from MHS Boilers Ltd
and are listed below.
The flue should be installed to have at least a 3˚ fall to the boiler to allow any condense formed in the
flue to run back to the boiler.
The flue system used must be gas and water tight and must be adequately supported over it’s entire
length. Support at 1 metre intervals. It is not necessary to install a terminal to the flue system, however, a
mesh guard should be included to prevent blockage or entry of foreign material. Straight lengths may be
cut to size with any surplus cut from the plain end. Tube ends should be cut square and de-burred.
Care should be taken when selecting a position for a low level discharge or discharge adjacent
to windows etc as the flue terminal will plume heavily and the white water vapour discharge may cause a
visual nuisance.
Flue components available from MHS Boilers Ltd.
80 mm PPS Flue Tube x 1000 mm long
(effective length 945 mm)
80 mm PPS Flue Bend x 90°
80 mm PPS Flue Bend x 45°
80 mm Wall Fixing Bracket - Aluminium
80 mm Bird Mesh Cap - Plated Steel
The above flue components
are light grey self coloured
Polypropylene moulded components with push together
spigot and socket joints with
integral seal ring located in the
socket.
If fire stop seals are required
to be installed where PPS plastic
flue components pass through
walls, floors or ceilings then
suitable fire stop seals are
available from:-
Nullifire Ltd
Torrington Avenue
Coventry CV4 9TJ
Tel 02476 855000
Fax 02476 469547
Dufaylite
Developments Ltd
Cromwell Road, St Neots
Huntingdon PE19 1QW
Tel 01480 215000
Fax 01480 405526
Quelfire
PO Box 35, Altrincham
Cheshire WA14 5QA
Tel 0161 928 7308
1000 mm
Effective Length 945mm
137
125
ø80
ø80
50
65
75
ø80
50
100
150
50
80 ø PPS
Flue Tube
x 1000
long
80 ø
PPS Flue
Bend
x 90º
80 ø
PPS Flue
Bend
x 45º
80 ø Wall
Fixing Bracket
ø5 Woodscrew
fitting
100 mm PPS Flue Tube x 1000 Long (Effective Length 945 mm)
100 mm PPS Flue Bend x 90°
100 mm PPS Flue Bend x 45°
100 mm Wall Fixing Bracket
100 mm Bird Mesh Cap - Plated Steel
80 x 100 mm Increaser
80 ø PPS Flue Components
100 ID
56
50
150
80 x 100 PPS
Increaser
End Slip
80
12
STRATA1
13.0 room sealed
flue installations
The Strata 1 boiler has an excess pressure combustion system, which coupled with the very low flue
gas temperatures produced allows the appliance to be exhausted and supplied with room sealed
combustion air using a concentric flue arrangement of 80 mm PPS polypropylene flue pipe within a 125 mm
outer painted metal air tube over considerable distances. A range of concentric flue components are
available from MHS Boilers Ltd and are listed below. Alternatively, two seperate tubes, one carrying
combustion air and one carrying flue gas may be used in conjunction with the appropriate adaptor.
The concentric flue system should be installed to have at least a 3° fall to the boiler to allow any
condense formed in the flue to run back to the boiler.
The flue system must be gas and water tight and must be adequately supported over it’s entire length.
Support at 1.5m intervals. Horizontal Discharge and Vertical Discharge Terminal Sets are available.
Care should be taken when selecting a position for a low level discharge or discharge adjacent to
windows etc as the flue terminal will plume heavily and the white water vapour discharge may cause a
visual nuisance.
Concentric flue components have push together spigot and socket joints. The inner PPS flue gas tube
has seal rings located in the socket component. The outer air tube has EPDM rubber seal rings located in
the socket component.
To aid assembly and assurance that the joints have been fully pushed home, the seal rings and make
ends of tubes/fittings should be lightly lubricated with silicone grease.
list of concentric flue components
● 80/125 Concentric wall terminal set:- comprises 500 mm (845 mm*) straight length with made on
terminal, 90° concentric bend and wall bezel plates.
● 80/125 Concentric roof terminal set:- comprises 1000 mm straight length with made on terminal and
1Nr 125 wall bracket.
● 125 pitched roof tile flashing for use with concentric roof terminal set, adjustable between 25° to 50°.
● 125 flat roof flashing for use with concentric roof terminal set.
● 80/125 Concentric flue tube set x 1000 mm.
● 80/125 Concentric flue tube set x 500 mm.
● 80/125 Concentric 93° Bend.
● 80/125 Concentric 45° Bend.
● 125 Wall bracket assembly.
● 80/125 Concentric Vertically Extendable Discharge Room Sealed Wall Terminal Assembly - For use
where a standard wall terminal may cause visual flue gas pluming nuisance. Includes 90° Concentric
bend, wall bezel plates and silicone mastic. Used in conjunction with additional 80 mm pps flue gas tube
and fittings listed on page 10.
● 80/125 Concentric to 2 x 80 mm Separate Tubes Adaptor.
● 80/125 to 100/150 Concentric Increaser (Not Shown).
● 100/150 Concentric Wall Terminal (Not Shown).
● 100/150 Concentric Roof Terminal (Not Shown).
● 100/150 Concentric Flue Tube Set x 1000 mm (Not Shown).
● 100/150 Concentric Flue Tube Set x 500 mm (Not Shown).
125 Pitched Roof
Adjustable Flashing.
Adjustable between 25-38º
and 37-50º
Lead Apron 1.3mm
458
229
355178900
155
120
8080
plan
80/125
Concentric
to 2 x 80 mm
Tubes
Adaptor
Flue
Gas
Air for
Combustion
14
STRATA1
13.0 room sealed flue installations (contd)
installation of standard wall terminal with
side outlet
In order to determine the length of concentric tube required to correctly terminate a side outlet
arrangement, the following procedure should be followed:
1. Measure wall thickness W in mm - see fig 7.
2. Measure distance between side of appliance and inside face of wall L1 in mm see fig 7.
3. Mark off and cut flue tubes following guidance show in fig 8 below. Flue tubes should be cut to length
TL in mm. Both inner and outer tubes should be cut flush with each other, square and any
burrs removed.
Where TL required, is greater than 845 mm, then additional lengths (as appropriate) of 80/125
concentric tube will be required to extend the standard wall terminal. A fall of 3˚ is required along the
length of the flue towards the appliance.
Concentric Wall Terminals
945
610
850*
845
Standard Horizontal
Discharge Wall Terminal
(supplied with 80/125
Concentric 90º bend and
wall bezel plates not
shown)
Horizontal Wall Terminal
With Extendable Vertical
Discharge (supplied with
80/125 Concentric 90º
bend and wall bezel plates
not shown)
* From 01/10/00
Note: 3˚ fall towards appliance required if additional lengths are
used
ø125
ø80
ø125
ø80
Detail For Marking Out For
Cutting Flue Hole For Side Flue,
Room Sealed Horizontal
Arrangement
Cut Flue Hole
ø 130mm
Line-Top of
Appliance C
hassis
(3
˚ fall to
appliance)
231
170
Fig 9.
Side Outlet
170
L1
W
Plain
Section
Installed
Uppermost
Wall Bezel
Plates
Required Length
Cutting Line
measure from
this point
TL (mm)
TL = W+L1+235mm
Fig 7.
Fig 8.
15
STRATA1
installation of standard wall terminal with
rear outlet
In order to determine the length of concentric tube required to correctly terminate a rear outlet
arrangement, the following procedure should be followed.
1. Measure wall thickness W in mm - see fig 10.
2. Mark off and cut flue tubes following guidance shown in fig 11 below.
Flue tubes should be cut to length TL in mm. Both inner and outer tubes should be cut flush with each
other, square and any burrs removed.
Where TL required, is greater than 845 mm, then additional lengths (as appropriate) of 80/125
concentric tube will be required to extend the standard wall terminal. A fall of 3˚ is required along the
length of the flue towards the appliance.
13.0 room sealed flue installations (contd)
Rear Outlet
170
W
Fig 10.
Plain
Section
Installed
Uppermost
Wall Bezel
Plates
Required Length
Cutting Line
measure from
this point
TL (mm)
TL = W+237mm
Fig 11.
170
c
L
cut flue hole
ø130
Fig 12.
Detail For Marking
Out For Cutting
Flue Hole For
Rear Flue, Room
Sealed Horizontal
Arrangement
16
STRATA1
13.0 room sealed flue installations (contd)
Extending the flue gas discharge vertically away
from a room sealed wall terminal.
The Strata 1 boiler is a fully condensing appliance with very low flue gas temperatures.
Consequently, the flue gas discharge is commonly seen as a white vapour plume, Whereas this is not
harmful when properly discharged into the atmosphere outside of a building from a correctly operating
appliance, the white vapour plume may cause, in certain applications a visual nuisance.
It must also be considered that a flue termination will drip condense water and may cause an ice hazard
below the terminal position
If it is considered that pluming or dripping from the end of a standard wall terminal may create a
nuisance, then as an alternative, the vertically extendable discharge wall terminal is available see figs 14 and
16. This creates a local room sealed intake for combustion air but allows the installer to extend the 80 mm
PPS flue gas tube to a point where pluming or dripping discharge will not cause a visual nuisance or hazard.
1. Lubricate male ends of concentric bend
with silicone grease and locate bend into
flue and air tube connection sockets on
the top of the boiler and gently push fully
home.
2. Slip flue tube and terminal assembly
through the prepared hole in the
outside wall.
4. Lubricate male ends of concentric flue
tube and female sockets of flue bend
lightly with silicone grease. Insert
concentric tubes into bend and gently
push fully home. Ensure plain section of
external part of air inlet tube is located
uppermost.
5. Make good internally and externally gap between air tube and prepared hole through wall.
6. Slip on external wall bezel plate.
7. Fix internal and external wall bezel plates with fixings provided.
Where a flue terminal discharges through a wall is within 2m of ground level or balcony etc then
the terminal should be fitted with an appropriate sized terminal guard.
Installation of Vertical Discharge Wall Terminal
with side outlet
In order to determine the length of concentric tube required to correctly terminate a side outlet
extended vertical discharge arrangement, the following procedure should be followed.
1. Measure wall thickness W in mm - see fig 14 overleaf.
2. Measure distance between side of appliance and inside face of wall L1 in mm - see fig 14 overleaf.
3. Mark off and cut flue tubes following guidance shown in fig 15 overleaf. Flue tubes should be cut to
length TL in mm. Both inner and outer tubes should be cut flush with each other, square and any burrs
removed.
Where TL required, is greater than 610 mm, (*850mm) then additional lengths (as appropriate) of
80/125 concentric tube will be required to extend the vertical discharge wall terminal. A fall of 3˚ is
required along the length of the flue towards the appliance.
method of assembly of horizontal concentric flue
system using standard wall terminal.
13
4
6
2
Fig 13.
Plain
Section
Uppermost
17
STRATA1
Installation of Vertical Discharge Wall Terminal
With Rear Outlet
In order to determine the length of concentric tube required to correctly terminate a rear outlet
extended vertical discharge arrangement, the following procedure should be followed.
1. Measure wall thickness W in mm - see fig 16.
2. Mark off and cut flue tubes following guidance shown in fig 17 below.
Flue tubes should be cut to length TL in mm. Both inner and outer tubes should be cut flush with each
other, square and any burrs removed.
Where TL required is greater than 610 mm, (*850mm) then additional lengths (as appropriate) of
80/125 Concentric tube will be required to extend the vertical discharge wall terminal. A fall of 3˚ is
required along the length of the flue towards the appliance.
* available 01/10/00
Installation of Vertical Discharge Wall Terminal
With Side Outlet
Rear Outlet
Fig 16.
170
W
ø80 PPS
90º Bend
ø80
Bird Mesh
ø80
PPS Tube
Exhaust
Outlet
Installed
vertically
Upwards
on Some
Wall
Aspect
Wall Bezel
Plates
Fig 17.
Required Length
Cutting Line
measure from
this point
TL (mm)
TL = W+262mm
Side Outlet
Fig 14.
170
W
ø80 PPS
90º Bend
ø80
Bird Mesh
ø80
PPS Tube
Exhaust
Outlet
Installed
vertically
Upwards
on Some
Wall
Aspect
Wall Bezel
Plates
Fig 15.
Required Length
Cutting Line
measure from
this point
TL (mm)
TL = W+L1+260mm
18
STRATA1
See fig. 18
1. Lubricate male ends of concentric bend with silicone grease and locate bend into flue and air tube
connection sockets on the top of the boiler and gently push fully home.
2. Slip flue tube and terminal assembly through prepared hole in the outside wall.
3. Locate internal wall bezel plate loosely onto air tube.
4. Lubricate male ends of concentric flue tubes and female sockets of flue bend lightly with silicone
grease. Insert concentric tubes into bend and gently push fully home. Ensure flue gas discharge is
positioned vertically upwards.
5. Made good internally and externally gap between air tube and prepared hole through wall.
6. Fit external 2 piece wall bezel and secure both internal and external wall bezels using fixings
provided.
7. Seal air tube to exhaust discharge with a bead of silicone rubber mastic (mastic supplied) to create
weather seal to avoid entry of rain water into air tube.
8. Extend flue gas discharge to chosen position using 80 mm PPS flue tube fittings.
1
7
6
2
4
3
Extend using 80ø
PPS tube
Flue discharge
vertically upwards
on some wall aspect
8
Fig 18.
Method of assembly of extendable vertical
discharge wall terminal assembly.
19
STRATA1
14.0 examples of calculating
flue pressure loss
0
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
50 100200150250 300 350 400 450 500
Strata 1 - 75
Strata 1 - 60
Strata 1 - 45
0 261014182226303438
0
10
30
50
70
90
110
130
20
40
60
80
100
120
140
48 1612202428323640
example 1
A Strata 1-60 boiler is installed with a concentric flue
system which takes an all horizontal route to a wall
terminal. Length of flue = 3m including one 90° bend.
Resistance =
3 x 1m length 80/125 concentric tube @ 8.5 Pa = 25.5
1 x 90° 80/125 concentric bend @ 8.5 Pa = 8.5
1 x 80/125 concentric wall terminal @ 11.0 Pa = 11.0
Total Resistance = 45 Pa
conclusion: Total resistance is less than 100 Pa,
therefore, no alternative design required and no effect on
boiler output, or positioning required.
example 2
A Strata 1-45 boiler is installed with a concentric flue
system which takes a part horizontal, part vertical route
to a roof terminal with rain cap.
Length of horizontal section = 3m, vertical section =
12m, system includes 3x90° bends.
Resistance =
15 x 1m lengths 80/125 concentric tube @ 5.5 Pa = 82.5
3 x 90° 80/125 concentric bend @ 5.5 Pa = 16.5
1 x 80/125 roof terminal @ 11.25 Pa = 11.25
Total Resistance - 110.25 Pa
Take into account that 12m of vertical (assume uninsulated, as air for combustion direct from outside air
surrounds the flue gas tube) flue creates 20 Pa of
up-draught,
then final resistance = 110.25 - 20 = 90.25 Pa.
conclusion: Final operating resistance is less than 100
Pa, therefore, no alternative design required and no effect
on boiler output.
example 3
A Strata 1-75 boiler is installed (non room sealed) with a
proposed flue using DN 80 PPS single skin flue
components which takes a part horizontal, part vertical
route to a vertical open termination with bird mesh.
Length of horizontal section = 4m, length of vertical (uninsulated) section = 11m with 4 x 90° bends,
and 2 x 45° bends.
Resistance =
15 x 1m lengths DN 80 PPS tube @ 8.0 Pa = 120
4 x 90° DN 80 PPS bends @ 8.0 Pa = 32
2 x 45° DN 80 bends @ 4.0 Pa = 8.0
1 x DN 80 open termination @ 8.0 Pa = 8.0
Total Resistance: 168 Pa
Take into account that 11m of vertical un-insulated flue
creates 18 Pa of up-draught, then final resistance would
be 168 - 18 = 150 Pa.
Reference to the graph of resistance effect on boiler
output shows the output would be reduced to
approximately 67kW. If this is unacceptable, then the
flue resistance must be re-calculated using a larger size
flue tube as shown below or consideration given to
moving the boiler position.
Re-calculating proposed flue installation using DN100.
15 x 1m lengths DN 100 PPS tube @ 3.0 Pa = 45
4 x 90° DN 100 bends @ 3.0 Pa = 12
2 x 45° DN 100 bends @ 1.5 Pa = 3.0
1 x DN 100 open termination @ 4.0 Pa = 4.0
Total Resistance: 64 Pa
Take into account thermal up-draught created (as before)
18 Pa. Therefore, operating resistance = 64 - 18 = 46 Pa,
with no effect on boiler output.
thermal up-draught when
flue gas temp 80°C and outside temp -5°C
effect of flue system resistance
on boiler output
Draught - Pa
Vertical Flue Lengths - metres
A = Insulated or within the building
B = Un-insulated and exterior to the building
A
B
Boiler Output kW at: Flow 80°C Return 60°C
Flue System Resistance - Pa
20
STRATA1
14.1 calculating
flue resistance
The excess pressure available for
overcoming the frictional resistance of a flue
system is 100 Pa.
The adjacent table of flue component
resistances will assist the designer in calculating
total flue system frictional loss.
If the total installed flue system resistance
exceeds 100 Pa., then the result will be a
reduction in boiler output. Reference to the
“Effect of Flue System Resistance On Boiler
Output”, graphs will assist. If the resistance of a
proposed flue system has an unacceptable
effect on boiler output, then a larger diameter
flue tube should be selected.
Thermal up-draught is generated in a
vertical flue system, reducing the resistance of
the system. Reference to the “Thermal Updraught Graph” will provide a figure in Pa.,
which may be deducted from the total
calculated flue system resistance.
NB. Thermal updraught does not apply to
horizontal sections of a flue system.
If a flue terminal is positioned within 2 m above ground level or any upper part of a building where
people have general access (e.g. balcony etc) then the terminal should be fitted with an appropriate guard.
The flue terminal of a Strata 1 boiler will plume heavily and care must be taken when selecting a
terminal position to ensure that a "nuisance situation" is not created.
Component Resistance P.a.
456075
80/125 Concentric Wall Terminal7.511.016.0
80/125 Concentric Roof Terminal Without Rain Cap7.511.016.0
80/125 Concentric Roof Terminal With Rain Cap11.2516.524.0
1m length 80/125 Concentric Tube5.58.512.0
93° 80/125 Concentric Bend5.58.512.0
45° 80/125 Concentric Bend2.754.256.0
80/125 Concentric To 2 x 80 Tubes Adaptor4.06.010.0
80/125 Concentric Wall Terminal With Vertical Discharge7.511.016.0
80/125 To 100/150 Concentric Increaser2.03.05.0
100/150 Concentric Wall Terminal3.04.07.0
100/150 Concentric Roof Terminal3.04.07.0
1m length 100/150 Concentric Tube2.03.05.0
93° 100/150 Concentric Bend2.03.05.0
45° 100/150 Concentric Bend2.02.03.0
Boiler Model
15.0 flue
terminal positions
Flue Terminal Positions
Fig. 19
H,I
J
M
A
G
F D
E
P
Q
A
G
N
B,C
F
F
L
K
L
K
N
M
21
STRATA1
Minimum dimensions of flue terminal positions see fig 19
DimensionTerminal PositionBalanced flueNon room
room sealedsealed
ADirectly below an opening, air
brick, windows etc. Not
Recommended.300 mm300 mm
BBelow gutters, soil pipes or
drain pipes75 mm75 mm
CBelow eaves200 mm200 mm
DBelow balconies or car port
roof. Not Recommended.200 mm200 mm
EFrom a vertical drain pipe or
soil pipe150 mm150 mm
FFrom an internal or external
corner300 mm200 mm
GAbove ground, intersecting
roof or balcony level300 mm300 mm
HFrom a surface facing the
terminal2000 mm2000 mm
IFrom a terminal facing the
terminal2000 mm2000 mm
JFrom an opening in the car port
(e.g. door, window) into dwelling1200 mm1200 mm
KVertically from a terminal on the
same wall1500 mm1500 mm
LHorizontally from a terminal on
the same wall.300 mm300 mm
MFrom a vertical structure on the
roof500 mmN/A
NAbove intersection with roof500 mm150 mm
PDirectly above an opening,300 mm300 mm
air brick, window etc
QHorizontally to an opening,500 mm500 mm
air brick, window etc
15.0 flue terminal positions (contd)
but installation
not recommended.
but installation
not recommended.
but installation
not recommended.
but installation
not recommended.
but installation
not recommended.
but installation
not recommended.
22
STRATA1
16.0 ventilation requirements
single appliances
Table 1Room Installation - Non
Room Sealed Flue.
Natural Ventilation Direct to Outside Air
Boiler ModelVentilation Openings Free Area cm
2
Strata 1/45180 For position see BS 5440: Part 2: 2000
Strata 1/60250 For position see BS 5440: Part 2: 2000
Strata 1/75319 High Level637 Low Level
Table 2Room Installation - Non Room Sealed Flue
Natural Ventilation From Adjacent Room
Boiler ModelVentilation Openings Free Area cm
2
Strata 1/45180cm2with adjacent room equally
ventilated direct to outside air.
Strata 1/60250cm
2
with adjacent room equally
ventilated direct to outside air.
Strata 1/75Ventilation from adjacent room not permitted - See Table 1 above.
Table 3Room Installation - Room Sealed Flue.
There are no specific requirements for a room to be ventilated where
the appliance is room sealed. However, consideration should be given
to providing ventilation for general cooling, (BS6644 specifies room
temperature limits).
Table 4Compartment Installation - Non room sealed flue
Table 5Compartment Installation - Non room sealed flue
Natural Ventilation from Adjacent room
Boiler ModelVentilation Openings Free Area cm
2
High LevelLow Level
Strata 1/45430860
with adjacent room ventilated at
180cm
2
direct to outside air.
Strata 1/605701140
With adjacent room ventilated at
250cm
2
direct to outside air.
Strata 1/75Ventilation from adjacent room not permitted - See Table 1 above.
The room or space in which the Strata 1 boiler is installed may require to be ventilated in accordance
with BS5440: Part 2: 2000 or BS 6644: 1991 as appropriate to the boiler input. Alternative guidance may
be found in IGE/UP/10. The guidance given in this publication is based on information in the above
mentioned BS publications.
The following tables must be read to ascertain the amount of ventilation required.
23
STRATA1
16.0 ventilation requirements single appliances (contd)
Strata 1/45430430
Strata 1/60570570
Strata 1/75Ventilation from adjacent room not permitted - See Table 1 above.
Multiple Appliances Installed in the Same Room or Space
Where multiple Strata 1 boilers are installed in the same room or space then
the aggregate of the appliance inputs must be taken to determine (from the
following data) the amount of ventilation required.
plus 4.5cm2per kW in excess of 60kW total rated input.
High Level (Outlet):
270cm
2
plus 2.25cm2per kW in excess of 60kW total rated input.
Ta b l e . 9Room Sealed Flue Installations
Natural Ventilation Direct to Outside Air
(Ventilation recommended for cooling purposes)
Low Level (Inlet): 4.5cm
2
per kW of total rated input.
High Level (Outlet): 4.5cm
2
per kW of total rated input.
24
STRATA1
17.0 hydraulic system
design
● The Strata 1 boiler can be operated to serve a heating load in a number of ways:
1. Constant flow temperature, with the option to set either high temperature (85°C), medium
temperature (70°C) or low temperature (55°C).
2. Direct-on-boiler weather compensated flow temperatures, with adjustable maximum flow
temperature.
3. Underfloor heating coils via a VT mixing valve with a maximum flow temperature of 55°C plus a
second circuit (eg. radiators) operating with direct-on-boiler weather compensated temperatures.
● Flow to return drop (∆t). The microprocessor controls monitor return temperature and the facility
to dictate a set ∆t (by pump speed modulation) is a standard and most important feature
and will where possible maintain the ∆t across the boiler at 20°C, as the lower the return temperature,
the higher the operating efficiency. Designing for a ∆t 20°C gives the added cost saving advantage of
smaller pipe sizes and pumps.
● The Strata 1 includes ‘in built’ primary pumps with a residual head pressure as listed below.
● Appliances may be installed as single units or in multiples.
● Single units may or may not require additional system pumps which will be dictated by the system
configuration and by the index resistance.
● Multiple units (and single units which require additional pumps), must always be installed with a low
loss mixing header or similar arrangement. - see table below.
● The Strata 1 boiler has in built domestic hot water (remote stored) temperature control ability, and if
required, the in built pumps may be used to provide the primary flow to a nearby indirect cylinder or
calorifier with the boiler controlling a diverter valve in the main flow or return pipework.
● BS 6644 Requires that the following devices shall be installed, and provision within the system design
must allow for: Low water pressure cut off device, water pressure gauge and a temperature gauge.
Boiler Power kW
Up to 45
75
100
120
150
200
250
270
300
340
Design ∆t 20°C
40mm
50mm
65mm
65mm
80mm
80mm
100mm
100mm
100mm
100mm
low velocity
mixing header
diameter
sizing guide
Tube diameters refer to steel pipe and calculated using data from
CIBSE Guide C4
The following system schematics show a number of typical installation types to which the Strata 1 boiler
may be connected.
The Strata 1 is not limited to just the systems shown, and may be used in conjunction with many
commercially available control items.
For further advice or guidance on schematic designs or control options contact MHS Boilers Ltd.
Boiler Model
45
60
75
Pressure Metres wc
3.1
3.0
2.6
in-built boiler pumps
approx residual
head pressure at
max speed
Residual head pressure, at minimum speed all
models 1.0 metres W.C.
25
STRATA1
17.0 hydraulic system
design
Typical single Strata 1 boiler installation serving heating only
where the boiler's own in-built circulating pumps are used to
circulate the water around the system (used only where system
index resistance < pump residual head - see page 24). Flow
temperature may be Fixed/constant or weather variable
OS= Outside air temperature sensor, used where
direct-on-boiler weather compensated flow
temperatures are required
C=Room temperature & time controls e.g.
RE2132 modulating room unit from MHS
Boilers, or, separate time clock & room
thermostat
PS= Low water pressure cut off switch.
*1= Filling Point. In accordance with BS 6644,
automatic pressurisation unit must be
installed when the boiler input is greater
than 60kW.
See item 17.1
System Type 1
DOC
OS
AAV
Boiler
Strata 1
C
Heating Load
SV
PS
LSV
DOC
Condense
IV
Strainer
Waste
IV
IV
DOC
Vessel
Expansion
IV
Filling Point
1*
CWM
26
STRATA1
17.0 hydraulic system
design
OS= Outside air temperature sensor, used where
direct-on-boiler weather compensated flow
temperatures are required
C=Room temperature controls
e.g. RE2132 modulating room unit from
MHS Boilers, or, separate time clock &
room thermostat
S=HWS sensor from MHS Boilers. Gives 24Hr
HWS operation
W/T= Alternative to "S" where "W" is a time
switch in series with a cylinder thermostat
"T". Allows for timed HWS.
Divertor valve will require SPDT relay if not
spring return.
Divertor valve must be so installed as to
spring return to heating.
PS= Low water pressure cut off switch.
*1= Filling Point. In accordance with BS 6644,
automatic pressurisation unit must be
installed when the boiler input is greater
than 60kW.
See item 17.1
Typical single Strata 1 boiler installation serving domestic hot
water and heating where hotwater has priority via a divertor
valve. The in-built circulating pumps within the boiler are used to
circulate the system (used only where system index resistance
< pump residual head - see page 24). Flow temperature to
hotwater is constant and flow temperature to heating may be
constant or weather variable.
System Type 2
DOC
OS
AAV
C
Strata 1
Boiler
Heating Load
Divertor
Valve
SV
IV
PS
W
Strainer
Waste
Condense
IV
IV
DOC
IV
LSVDOC
Vessel
Expansion
ST
IV
Filling
Point
IV
DOC
Calorifier/Indirect
Hot Water Cylinder
CWM
1*
27
STRATA1
17.0 hydraulic system
design
OS= Outside air temperature sensor, used where
direct-on-boiler weather compensated flow
temperatures are required.
C=Room temperature controls e.g. RE2132
modulating room unit from MHS Boilers, or,
separate time clock & room thermostat.
PRO1=Pump regulation module from MHS Boilers.
Allows heating pump to be driven from
boiler, providing for auto operation, frost
protection running & summer standstill
exercising.
Must be used
where RE2132 modulating
room unit is installed.
Max pump motor load 2A
PS= Low water pressure cut off switch
*1= Filling Point. In accordance with BS 6644,
automatic pressurisation unit must be
installed when the boiler input is greater
than 60kW.
See item 17.1
Typical Single Strata 1 boiler installation serving heating only and
using a low velocity mixing header where system index resistance
exceeds in-built boiler pump residual head - see page 24. Flow
temperature may be fixed/constant or weather variable.
System Type 3
DOC
OS
AAV
C
Strata 1
Boiler
Heating Load
PRO 1
SV
IV
PS
LSV
DOC
Waste
Condense
AAV
Strainer
Heating Pump
IV
IV
DOC
Vessel
Expansion
Low Velocity
Mixing Header
Max Velocity 0.5m/s
IV
Point
Filling
1*
IVIV
CWM
Strainer
DOC
28
STRATA1
17.0 hydraulic system
design
OS= Outside air temperature sensor, used where
direct-on-boiler weather compensated flow
temperatures are required.
C=Room temperature controls e.g. RE2132
modulating room unit from MHS Boilers, or,
separate time clock & room thermostat.
S=HWS sensor from MHS Boilers.
Gives 24hr HWS operation
W/T= Alternative to "S" where "W" is a time
switch in series with a cylinder thermostat
"T". Allows for timed HWS.
PRO1=Pump regulation module from MHS Boilers.
Allows heating pump to be driven from
boiler, providing for auto operation, frost
protection running & summer standstill
exercising.
Must be used
where RE2132 modulating
room unit is installed.
Max pump motor load 2A
Divertor valve wil require SPDT relay if not
spring return.
Divertor valve must be so installed as to
spring return to heating.
PS= Low water pressure cut off switch
*1= Filling Point. In accordance with BS 6644,
automatic pressurisation unit must be
installed when the boiler input is greater
than 60kW.
See item 17.1
Typical Single Strata 1 boiler installation serving heating & domestic hot water. Hot water is priority and is served
via a divertor valve and the boiler's in built circulating pump where index loss through HWS primaries is less
than boiler pump residual head*. Heating circuit index loss exceeds boiler pump residual head* and is served via
a low velocity mixing header and a separate pump. Heating flow temperature may be fixed/constant or weather
variable.
* See page 24
System Type 4
Heating Load
OS
AAV
C
Boiler
Strata 1
PRO 1
W
AAV
IV
PS
Waste
Condense
SV
Heating Pump
Valve
Divertor
IV
Strainer
IV
Low Velocity
IV
LSV
DOC
DOC
Mixing Header
Max Velocity 0.5m/s
IV
Vessel
Expansion
IV
ST
Strainer
IVIV
DOCDOC
1*
Point
Filling
CWM
DOC
Calorifier/Indirect
Hot Water Cylinder
29
STRATA1
17.0 hydraulic system
design
OS= Outside air temperature sensor, used where
direct-on-boiler weather compensated flow
temperatures are required.
C=Room temperature controls e.g. RE2132
modulating room unit from MHS Boilers, or,
separate time clock & room thermostat.
S=HWS sensor from MHS Boilers.
Gives 24hr HWS operation
W/T= Alternative to "S" where "W" is a time
switch in series with a cylinder thermostat
"T". Allows for timed HWS.
PRO1=Pump regulation module from MHS Boilers.
Allows heating pump to be driven from
boiler, providing for auto operation, frost
protection running & summer standstill
exercising.
Must be used where RE2132 modulating
room unit is installed.
Max pump motor load 2A
PS= Low water pressure cut off switch
*1= Filling Point. In accordance with BS 6644,
automatic pressurisation unit must be
installed when the boiler input is greater
than 60kW.
See item 17.1
Typical Single Strata 1 boiler installation serving heating &
domestic hot water with hot water priority. Hotwater &
heating circuits both have index resistance exceeding boiler
pump residual head* & are served by independent pumps
from a low velocity mixing header. Heating flow temperature
may be fixed/constant or weather variable.
* See page 24
System Type 5
DOC
Heating Load
C
Calorifier/Indirect
Cylinder
OS
AAV
Boiler
Strata 1
W
PRO 1
AAV
SV
PS
LSV
DOC
Condense Waste
IV
DOC
Vessel
Expansion
TS
HWS Primary
Pump Max 1A.
Heating Pump
Low Velocity
Mixing Header
IV
IVDOC
0.5m/s
Max Velocity
IV
Strainer
1*
Point
Filling
CWM
IV
Strainer
DOCIV
30
STRATA1
17.0 hydraulic system
design
OS= Outside air temperature sensor, used where
direct-on-boiler weather compensated flow
temperatures are required.
C=Room temperature controls e.g. RE2132
modulating room unit from MHS Boilers, or,
separate time clock & room thermostat.
FS= Flow temperature sensor
RS= Return temperature sensor
S=Hot water temperature sensor or
thermostat
KKM2=Modulating Kaskade Manager. Up to 9Nr
boilers may be controlled using 2Nr linked
KKm2's.
PS= Low water pressure cut off switch
*1= Filling Point. In accordance with BS 6644,
automatic pressurisation unit must be
installed when the boilers input is greater
than 60kW.
See item 17.1
Typical Multiple Strata 1 installation. Boilers controlled by modulating Kaskade manager which also has
the facility to control heating & domestic hot water production. Heating flow temperature may be
fixed/constant or weather variable. Hot water has priority.
System Type 6
DOC
C
OS
KKM 2
Heating Load
AAV
AAV'sAAV'sAAV's
Heating Pump
2A. Max
Strata 1
Strata 1
Strata 1
HWS Primary
Pump
FS
Boiler
Boiler
Boiler
2A. Max
SVSVSV
DOCDOCDOC
Hot Water
Calorifier or
Indirect Cylinder
Low Velocity
Mixing Header
Max Velocity 0.5m/s
NRVNRVNRV
Waste
Condense
DOC
IV
RS
Strainer
IV
Strainer
Expansion
Vessel
IV
LSV DOC
Filling
1*
Point
CWM
IV IV
S
IVIV
PS
IVIVIVIVIVIV
31
STRATA1
17.0 hydraulic system
design
OS= Outside air temperature sensor. Provides outside
air temperature reference for both heating zones
MRO3=Pumps and mixer regulation control box from
MHS Boilers provides pump control for both
heating zones i.e. auto operation, frost protection
and summer stand still protection running.
Provides drive for underfloor coil zone VT mixing
valve with max flow temperature limitation set at
55ºC. Includes ratio setter for compensation of
under floor coils. Max pump motor loads 2A
RC1= RE2132 modulating room unit from MHS Boilers
provides Time & Temperature control for radiator
heating zone.
RC2= As RC1 but for underfloor coil zone.
VS= Underfloor zone VT flow sensor (supplied with MR03)
S=HWS sensor from MHS Boilers. Gives 24hr operation.
W/T= Alternative to "S" where "W" is a time switch in series
with a cylinder thermostat "T". Allows for timed HWS.
PS= Low water pressure cut off switch
*1= Filling Point. In accordance with BS 6644,
automatic pressurisation unit must be
installed when the boiler input is greater
than 60kW.
See item 17.1
Typical Single Strata 1 boiler installation serving domestic hotwater and radiator heating zone and an
underfloor coil zone all via a low velocity mixing header. The HWS will always have priority. the 2Nr
heating zones may operate independently via 2 Nr separate room units. The 2 Nr heating zones will
always be weather compensated but may have differing compensation slopes
System Type 7
S
Calorifier or
T
W
Radiator Zone
Indirect Cylinder
DOC
DOC
OS
RC
AAV's
1
Under Floor Zone
VT Pump
VS
U/Floor VT
HWS Primary
SV
Pump
DOC
PS
MRO3
IV
IV
Waste
Condense
Low Velocity
Boiler
Strata 1
Radiator
AAV
Pump
Zone
2
RC
Mixing Valve
Mixing Header
V Max 0.5m/s
Strainer
IVIV
Under Floor
Coils Zone ∆t 10ºc
IV
DOC
IV
LSV
Expansion
IV
DOC
Vessel
Strainer
IV
DOC
1*
Point
Filling
CWM
32
STRATA1
17.0 hydraulic system
design
P=Programmer
WC= Wiring Centre/Junction Box
RS= Room Thermostat
CS= Cylinder Thermostat
PS= Low water pressure cut off switch
*1= Filling Point. In accordance with BS 6644,
automatic pressurisation unit must be
installed when the boiler input is greater
than 60kW.
See item 17.1
Typical Single Strata 1 boiler
installation serving heating and
domestic hotwater via a system
pump and 2Nr 2Port motorised
valves with conventional controls
i.e. programmer, room stat &
cylinder stat.
NOTE: system temperature will
be fixed constant and direct-onboiler weather compensation is
not possible.
System Type 8
Typical Schematic
Arrangement Where
System Has Multiple
Pumps That Will
Operate At The
Same Time.
Heating Load
CS
RS
AAV
HW
CH
M/Valve
P
WC
SV
LSV
DOC
AAV
PS
Condense
Waste
M/Valve
IV
DOC
Expansion
Vessel
System Pump
Reg Valve
Indirect Cylinder/Calorifier
IVIV
Strainer
Low Velocity
Mixing Header
Max Velocity
0.5 m/s
DOC
IV
Strainer
IV
1*
Filling Point
CWM
Boiler/s
Flow Header
Low Velocity
Mixing Header
Max Velocity 0.5m/s
Circuit Pumps
That Can/Will Run
At The Same Time
33
STRATA1
17.2 water treatment system cleaning
The entire system must be thoroughly cleansed and flushed to remove debris, flux residues etc before
opening the boiler isolation valves & flooding the boiler. Particular care must be taken where the Strata
boiler is being retro-fitted into an old/existing system, as system silt or magenite can be very damaging to
the new boiler.
Following cleansing and flushing the system must be dosed with a good quality water treatment to
prevent corrosion and the formation of scale.
For specific guidance on water treatment, direct contact is advisable with:-
Betz Dearborn LimitedFernox
WidnesTandem House
CheshireMarlowe Way
WA8 8UDCroydon
Surrey CR0 4XS
Telephone: 0151 495 1861Telephone: 0208 665 6666
Failure to observe these requirements will render the guarantee on the product
void. Cleansing, flushing and water treatment must be carried out in accordance
with the requirements of BS 7593:1992.
For Category 4 systems, the approved method of filling must comprise of the following components in
the arrangement shown;
● Control Valve
● Strainer
● Verifiable Backflow Device with
Reduced Pressure Zone (RPZ Valve).
Incorporating a 'Type BA' air gap.
● Tundish
● Control Valve
Further more, in accordance with BS6644, for boiler/s with an input greater than 60kW, an automatic
pressurisation unit must be installed to automatically replenish any lost or evpourated water.
The pressurisation unit must comprise of the following components;
● A Cistern fitted with a Float Operated Valve incorporating either a 'Type AG' (C-3), or 'Type AF' (C-4)
air gap.
● A Presssure Booster Pump fitted with a Single Check Valve
● A Pressure Reducing Valve
● A Pressure Switch
For information on a comprehensive range of pressurisation units please contact MHS Sales.
17.1 filling the system
The initial filling of a sealed heating system, and subsequent refilling, must be by a method that has been
approved by the Water Regulation Advisory Scheme (WRAS) for that type of heating system. ie. Domestic
(In-house) Fluid Category 3 (C-3). Non Domestic (Other than In-House) Fluid Category 4 (C-4).
For Category 3 systems, the approved method of filling must comprise of the following components in
the arrangement shown;
● Control Valve incorporating a Double Check
Valve on the mains cold water pipework.
● Temporary Connecting hose, which must
be disconnected after use.
● Control Valve, on the heating system.
MCWS
CV
DCVHOSE
CV
Heating System
MCWS
CVCV
Strainer
Heating System
Tundish
RPZ
34
STRATA1
17.5 care with the use of soldering flux
18.0 electrical
connection
The electrical connections to the Strata 1 boiler are made via discreet plugs and sockets (Weiland Type)
which are located within the boiler case and below the control panel.
Connections must only be made using appropriate diameter multi strand flex cables and cable entry
must only be via the rubber glanded cable entry points located at the bottom rear r/h side of the appliance.
If the boiler is to be room sealed flued then care must be taken to ensure the cable entries are reasonably
air tight.
For electrical connection plug/socket function and location see fig 20.
The Strata 1 boiler has heat exchangers fabricated from 316L stainless steel. It is most important that
the compatibility of any flux is checked with the flux supplier before use, and that any flux manufacturers
recommendations are strictly followed with regards to use in conjunction with stainless steel.
Cable entry glands
14
3265
Position of Weiland Plugs
Weiland Plug
Nr.: 1
Weiland Plug
Nr.: 4
Permanent
Supply
(L1+PE+N)
Outside Air Sensor
(A1+A2)
RE2132 Room Unit
(R1+R2+R3)
KKM2 Kaskade Manager
(R2+R3)
0-10v via an adapter ‘+’ R2 ‘-’ R1
0-3v ‘+’ R2, ‘-’ R1
Weiland Plug
Nr.: 3
Weiland Plug
Nr.: 2
Weiland Plug
Nr.: 6
Weiland Plug
Nr.: 5
Fig. 20
Room Thermostat
Volt free enable
(L2+L1)
PRO1/MRO3
(N+PE+L1)
External Gas
Safety Shut off
Valve-LPG only
(if req'd)
(N+PE+L1)
HWS Divertor
Valve or HWS
Primary Pump
(N+PE+L1)
HWS Sensor or
Volt free
Thermostat
17.4 low water pressure protection
A low water pressure switch must be included within the system design and interlocked to the boiler
to shut the boiler down in the event of the water pressure falling below 0.5 bar.
17.3 inclusion of strainers
The return pipework must include some method of filtering or straining. The Filter or strainer must be
fitted with isolation valves to allow easy cleaning with the minimum amount of water loss and water
replenishment.
typical electrical connection schematic
to suit system type 1
1
Outside sensor
installed. Room
stat & time
switch installed.
No outside
sensor. Room
stat & time
2
Outside sensor
installed. RE2132
switch installed.
modulating room
unit installed.
No outside
sensor. RE2132
modulating room
unit installed.
51
106
Not Used
N
PE
L1
2
1
R3
R2
R1
A2
A1
L2
N
3456X3X16
= Controls Sockets on Control panel
= Weiland Plugs/Sockets
PE
L1
2
1
Boiler Dip Switch Settings
Sensor
*
OS
Outside Air
* *
+24V
PMW
GND
3251
4
Room Unit
Modulating
RE2132
or Volt free Switch
And Time switch
Room Thermostat
* *
Remote Sensor
Optional
QAW44
3 4 5 6
1
X3,X16
1
N
PE
L1
Low Pressure
Switch break
on Pressure Fall
230 V
Supply
Install only if direct-on-boiler weather
compensated flow temperature are
required.
Install only one method of external time
and room temperature control. If room
stat and time switch are required, then
*
* *
Weiland plug Nr2-not shown. Used only
on LPG installations where an additional
do not install RE2132 room unit and
vice versa.
remote gas safety shut off valve is req'd.
2
STRATA1
37
typical electrical connection schematic
to suit system type 2
Outside sensor
installed. Room
stat & time
switch installed.
No outside
sensor. Room
stat & time
switch installed.
Outside sensor
installed. RE2132
modulating room
unit installed.
No outside
sensor. RE2132
modulating room
unit installed.
1
X16
2
Boiler Dip Switch Settings
Not Used
51
106
N
PE
L1
2
1
R3
R2
R1
A2
A1
2
1
HWS Sensor
OS
6
3
C2
+24V
PMW
GND
*
Sensor
Outside Air
N
PE
L1
L2
N
PE
L1
3251
4
SPDT Relay
Valve - Spring Return Type.
HWS Primary Divertor
And Time switch
Cylinder Thermostat
Room Unit
**
Modulating
RE2132
Close
Open
open, motor shut type valve.
Divertor Valve using motor
to Spring Return HWS Primary
Alternative arrangement
Sensor
Remote
Optional
QAW44
Weiland plug Nr2-notshown. Used only
on LPG installations where an additional
remote gas safety shut off valve is req'd.
2
L2
N
PE
= Controls Sockets on Control panel
= Weiland Plugs/Sockets
X3,X16
1 3 4 5 6
L1
N
PE
13456X3
L1
C1
Low Pressure
Switch break
on Pressure Fall
**
230 V
Supply
Or Volt Free Switch
And Time switch
Room Thermostat
Install only if direct-on-boiler weather
compensated flow temperature is
*
required.
Install only one method of external time
and room temperature control. If room
stat and time switch are required, then
do not install RE2132 room unit and
vice versa.
Install only one method of HWS
temperature control. The use of an HWS
Sensor will allow no time control over
hotwater production. If timed hotwater
* *
control is req'd then do not install an HWS
sensor, but install only a timeswitch & cylinder
T/stat.
38
STRATA1
typical electrical connection schematic
to suit system type 3
into PRO1 are made
via labelled factory
fitted cables.
NOTE: All connections
1
X16
2
Heating
L
Pump
2A Max
PEPRO1
Outside sensor
installed. Room
stat & time
switch installed.
No outside
sensor. Room
N
Outside sensor
stat & time
switch installed.
installed. RE2132
modulating room
unit installed.
No outside
sensor. RE2132
modulating room
unit installed.
Moulded Plug Assembly
51
106
N
PE
L1
Not Used
2
1
R3
R2
R1
A2
A1
L2
N
PE
= Controls Sockets on Control panel
= Weiland Plugs/Sockets
L1
Boiler Dip Switch Settings
+24V
PWM
GND
*
2
1
OS
Sensor
Outside Air
**
3251
4
**
Room Unit
Modulating
RE2132
Or Volt Free Switch
And Time Switch
Room Thermostat
Sensor
Remote
Optional
QAW 44
Weiland plug Nr2-notshown. Used only
on LPG installations where an additional
remote gas safety shut off valve is req'd.
2
1 3 4 5 6
X3,X16
N
PE
13456X3
L1
Low Pressure
Switch break
on Pressure Fall
230 V
Supply
Install only if direct-on-boiler weather
compensated flow temperature is
required.
Install only one method of external time
and room temperature control. If room
stat and time switch are required, then
do not install RE2132 room unit and
vice versa.
*
* *
STRATA1
39
typical electrical connection schematic
to suit system type 4
Outside sensor
installed. Room
stat & time
switch installed.
No outside
sensor. Room
NOTE: All connections
into PRO1 are made Via
labelled factory fitted cables.
stat & time
switch installed.
Outside sensor
installed. RE2132
modulating room
unit installed.
No outside
sensor. RE2132
modulating room
unit installed.
1
2
Moulded Plug Assembly
106
N
PE
6X3X16
L1
2
1
R3
R2
R1
A2
A1
Heating
L
51
Boiler Dip Switch Settings
Pump
2A Max
N
PEPRO1
36
HWS sensor
2
1
OS
Close
N
PE
L1
L2
N
PE
L1
+24V
PWM
GND
3251
Sensor
*
4
Outside Air
Open
SPDT Relay
Return Type
Valve - Spring
HWS primary Divertor
And Time switch
Cylinder Stat
Room Unit
**
Modulating
RE2132
open, Shut type valve.
Divertor Valve Using Motor
spring Return HWS Primary
Alternative arrangement to
Weiland plug Nr2-notshown. Used only
on LPG installations where an additional
remote gas safety shut off valve is req'd.
2
Sensor
Remote
Optional
QAW44
Install only one method of HWS
temperature control. The use of an HWS
Sensor will allow no time control over
hotwater production. If timed hotwater
control is req'd then do not install an HWS
sensor, but install only a timeswitch & cylinder
T/stat.
L2
N
PE
= Weiland Plugs/Sockets
= Controls Sockets on Control panel. PRO1 has factory made on plugs and leads for these connections
X3,X16
1 3 4 5 6
L1
N
PE
1345
L1
Low Pressure
Switch break
on Pressure Fall
230 V
Supply
**
Or Volt Free Switch
And Time switch
Room Thermostat
Install only if direct-on-boiler weather
compensated flow temperature are
required.
*
Install only one method of external time
and room temperature control. If room
stat and time switch are required, then
do not install RE2132 room unit and
vice versa.
* *
40
STRATA1
typical electrical connection schematic
to suit system type 5
Outside sensor
installed. Room
stat & time
switch installed.
No outside
sensor. Room
Heating
Pump
1
2A Max
stat & time
switch installed.
Outside sensor
installed. RE2132
modulating room
unit installed.
No outside
sensor. RE2132
modulating room
unit installed.
2
Moulded Plug Assembly
106
N
PE
L1
2
1
R3
R2
R1
A2
A1
L
51
N
PEPRO1
NOTE: All connections
into PRO1 are made Via
labelled factory fitted cables.
LPEN
HWS sensor
2
1
OS
Boiler Dip Switch Settings
Pump 2A Max
HWS Primary
C2
+24V
PWM
GND
Sensor
3251
*
Outside Air
4
And Time switch
Cylinder Stat
Room Unit
**
Modulating
RE2132
Weiland plug Nr2-notshown. Used only
on LPG installations where an additional
remote gas safety shut off valve is req'd.
2
Sensor
Remote
Optional
QAW44
Install only one method of HWS
temperature control. The use of an HWS
Sensor will allow no time control over
hotwater production. If timed hotwater
L2
N
PE
13456X3X16
L1
C1
N
PE
L1
Low Pressure
Switch break
on Pressure Fall
= Weiland Plugs/Sockets
= Controls Sockets on Control panel. PRO1 has factory made on plugs and leads for these connections
X3,X16
1 3 4 5 6
230 V
Supply
**
Or Volt Free Switch
And Time switch
Room Thermostat
Install only if direct-on-boiler weather
compensated flow temperature are
required.
Install only one method of external time
*
control is req'd then do not install an HWS
sensor, but install only a timeswitch & cylinder
T/stat.
and room temperature control. If room
stat and time switch are required, then
do not install RE2132 room unit and
vice versa.
* *
41
STRATA1
typical electrical connection schematic
to suit system type 6
NOTE:
No connections,
other than those
shown are to be
37
38
35
36
2628 303234
232527293133
X2X4
made to the boilers.
Boiler Dip Switch Settings -
repeat on each boiler
Boilers
Not UsedAdditional
+24V
GND
PMW
43521
R3
R2
R3
R2
R3
R2
44
4
No3
No2
No1
Room Unit
*
Modulating
RE2132
Boiler
Boiler
Boiler
N
PE
L1
N
PE
L1
N
PE
111
L1
R 1/1R 1/2R 1/3
Remote Sensor
Optional
QAW44
230 V
Supply
N
230 V
Supply
230 V
Supply
Relay R1
L
Low Pressure Switch
break on Pressure Fall
*
1416 18202224
111315171921
X1
461012
= Weiland Plugs/Sockets on boilers
= Terminal Rails on KKM2 Kaskade Manager
1 4
X1,X2,X4
13579
2
* Outside Air Sensor
* HWS Sensor
Return sensor
Flow Sensor
X2
16 182022
13151719 21
PE
N
L
PE
N
L
PE
230V
N
L
Supply
2A Max
Pump 230V
*
Heating Circuit
2A max
Pump 230V
*
HWS Primary
- If Required
*
For Heating Circuit
* External Controls
Time Switch
* Cylinder Stat/HWS
Control Options
Alternative External
42
STRATA1
typical electrical connection schematic
to suit system type 7
Pump #2
Radiator
Zone Pump
2A Max
L
N
PE
1
2
Moulded Plug Assembly
51
106
N
PE
L1
Pump #1
Underfloor
Zone VT
Pump 2 A Max
L
N
PE
MRO3
LPEN
Underfloor
L1NPE
R6
R5
R4
Zone VT
Mixing Valve
L2
NOTE: All connections
into MRO3 are made Via
labelled factory fitted cables with
the exception of the underfloor
Zone RE2132 which is cabled by
the installer
VT Flow sensor
Underfloor Zone
+24V
PWM
GND
43251
Pump 2A Max
HWS Primary
Boiler Dip Switch Settings
being controlled via RE2132
Only possible if the boiler is
Unit For Underfloor Zone
RE2132 Modulating Room
2
1
HWS sensor
OS
Low Pressure
Switch break
on Pressure Fall
Time Switch
Sensor
Outside Air
230 V
Supply
+24V
PWM
GND
43251
Stat
Cylinder
Radiator Zone
Room Unit For
RE2132 Modulating
Sensor
Remote
Optional
QAW 44
Weiland plug Nr2-notshown. Used only
on LPG installations where an additional
remote gas safety shut off valve is req'd.
2
Install only one method of HWS
temperature control. The use of an HWS
Sensor will allow no time control over
2
1
R3
R2
R1
A2
A1
L2
N
PE
13456X3X16
L1
N
PE
L1
= Weiland Plugs/Sockets
= Controls Sockets on Control panel. MRO3 has factory made on plugs and leads for these connections
X3,X16
1 3 4 5 6
hotwater production. If timed hotwater
control is req'd then do not install an HWS
sensor, but install only a timeswitch & cylinder
T/stat.
43
STRATA1
typical electrical connection schematic
to suit system type 8
1
X16
2
51
106
N
PE
L1
NOT USED
2
1
R3
R2
R1
A2
A1
L2
N
PE
= Controls Sockets on Control panel
= Weiland Plugs/Sockets
L1
Boiler Dip Switch Settings
M
HW M\V
M
CH M\V
HW M/V & CH M/V
Junction
Box
NE E
LL34567N
= typical spring return
type motorised valves
with end switches
System Pump
Max 2A
LPEN
R/Stat
Cyl Stat
Weiland plug Nr2-notshown. Used only
on LPG installations where an additional
remote gas safety shut off valve is req'd.
2
CH
ON
CH
OFF
ON
HW
OFF
HW
Typical Programmer
LNE
1 3 4 5 6
X3,X16
N
PE
13456X3
L1
Low Pressure
Switch break
on Pressure Fall
230 V
Supply
44
STRATA1
In addition to the ability of the boiler to be connected to traditional industry standard control systems,
MHS Boilers can supply a range of dedicated matched controls which not only simplify the selection of
controls but in addition enhance the efficiency of the boiler and comfort conditions within the building.
system pump control
PRO1 module: for single boiler applications. A small and neat wall mounted control box which allows
the boiler to control a system heating pump. The use of this device allows the boiler to start/stop the
system pump according to the dictates of any external controls that may be connected to the boiler with
the additional features of pump overrun, daily pump exercising and frost protection running. Maximum load
2A 230 Vac.
combination pump and underfloor system
mixing valve control
MRO3 module: For single boiler applications. A small and neat wall mounted control box which allows
the boiler to control two different heating circuits.
Circuit 1 - A variable temperature circuit with pump and mixing valve (240v) for use with underfloor
coils where the maximum flow temperature = 55°C.
Circuit 2 - A pumped heating circuit (eg radiators) where the flow temperature is direct-on-boiler
weather compensated variable. The control of the pumps has the same features as the PRO1
module described above. The MRO3 has the facility to connect an RE2132 modulating room
unit to provide modulating room temperature and time control over the underfloor circuit.
A second RE2132 unit may be connected directly to the boiler to control Circuit No.2.
modulating room temperature control
RE2132 room unit: A compact digital room temperature control that will modulate boiler power
according to room temperature requirements.
key features
● In-built optimising time control and temperature sensor.
● Three temperature levels including frost protection.
● Holiday programmable.
● Can be used as a remote control for parallel shift of compensation slope.
● Possibility to connect a remote sensor to give temperature averaging.
● Self learning.
● Can be connected to an individual boiler, on MR03 (underfloor) control or a KKM2
sequence controller.
● QAW44 an addition tamper proof sensor can be wired to the RE2132 to allow sensing of remote
areas away from RE2132.
18.1 optional matched
controls
multiple boiler Kaskade manager
KKM2 modulating sequence controller:
A comprehensive compact wall mounted microprocessor control panel which allows the control of up
to five Strata 1 boilers. The KKM2 provides fully modulating control over the connected boilers ensuring
precise output control and maximum efficiency.
In addition to boiler control, the KKM2 can provide the drive signal for a heating circuit pump and can
provide control for stored domestic hot water (with priority over heating). Domestic hot water may be
charged using either a diverter valve or primary pump, either of which are driven from the sequencer.
External control input is via either a volt free contact (eg time switch) 0-3 or 0-10 Volt input or an
RE2132 modulating room unit plus necessary temperature sensors. Heating flow temperatures may be
either constant temperature or direct-on-boiler weather compensated variable (by means of the in-built
compensator). If more than five boilers are required to be controlled, then additional KKM2’s may be
slaved to the first control with slave capacity of four boilers per each additional sequencer. Standard
features include pump overrun and boiler load rotation.
18.1 optional matched controls (contd)
outside air
temperature sensor
If weather compensated flow temperature
(recommended for best seasonal efficiency and
comfort) is required, then the supplied air sensor
must be installed and electrically connected to the
boiler. The outside air sensor should be installed on
the exterior face of a north facing wall, away from
any artificial influences such as ventilation discharge
grilles or in direct sunlight. Ø 5mm wall fixings and
screws are provided.
domestic hot water
temperature sensor
If a hot water temperature sensor (from MHS
Boilers) is used to sense the temperature of stored
hot water, then this should be inserted into a
pocket or surface mounted to measure the water
temperature at approximately 1/3 of the height of
the hot water vessel up from the base of the vessel.
52
TOP
50
28
Outside Air Temperature Sensor
Length m
Up to 35
35 to 70
70 to 140
Cable Diameter mm
2
0.25
0.5
1.0
Cable Detail
Length m
Up to 35
35 to 70
70 to 140
Cable Diameter mm
2
0.25
0.5
1.0
Cable Detail
STRATA1
45
Remote Fault
Indication
The Strata 1 boiler includes a built in fault
alarm relay with volt free contacts for interface
with, if required a remote alarm indicator.
The volt free contacts within the boiler
control panel will close in the event that the
boiler goes to a fault resulting in boiler lockout.
The volt free contacts indicate “common alarm”
upon closing. The actual fault description will be
displayed upon the LCD screen of the boiler.
Connection to the volt free contacts is made
via an alarm plug and lead assembly available
from MHS Boilers Ltd.
The alarm plug and lead connects to socket
x9 located in the lower area of the boiler
control panel.
19.0 commissioning
the strata 1 boiler
The Strata 1 boiler should be expertly commissioned by a competent engineer who will need, in addition
to standard hand tools, a U tube manometer and a combustion analyser.
Before attempting to set the Strata 1 boiler to work, the following check list must be worked through.
See 19.1.
18.2
0-3/0-10 volt control
The Strata 1 can be operated via 0-3 volt or 0-10 volt control. The connection details are shown in fig 22.
For further details on 0-3 or 0-10 volt control please contact the Technical Department.
0-3 volt control direct to boiler plug
Nr: 4 without adaptor.
0-10 volt control via 0-10 volt adapter
(optional extra).
Fig. 22
46
STRATA1
To Boiler Socket Nr: 4
Weiland Plug
Nr: 4
0-10 volt Adapter
R1
A1 A2
R3
R2
0vV+
Weiland Connection Plug
Nr: 4
X9 Socket
12
X9 Alarm Plug
& Lead Assembly
Remote
Alarm Circuit
STRATA1
47
19.1 pre-commissioning
checks
a)Ensure system has been thoroughly cleansed and flushed, any strainers have been cleaned and
that the appropriate water treatment has been added to the system to prevent corrosion,
scale formation etc.
b)Ensure the system and boiler has been properly and fully flooded and vented of air and the cold
fill pressure at the boiler is at a minimum 0.5 bar.
c)Check that the pumps within the boiler are free to rotate by removing the vent screw in the end
of both pump motors and checking that the impeller shafts rotate freely when turned
with an appropriate sized screwdriver. Replace vent screws.
d)Ensure the appliance has been converted to burn the type of gas available on site.
e)Ensure Gas supply has been purged and there is the availability of working inlet pressure of
nominal 20 mbar (Nat gas) or 37 mbar (LPG).
f) Check that the flue installation has been properly made.
g) Check that a condense waste pipe
(in plastic - copper tube is not
acceptable) has been connected to
the boiler and that the syphon
cleaning point cap is in place.
h)Where the appliance is taking air
for combustion from the room in
which it is installed - ensure an
adequate provision for ventilation has
been made in accordance within British Standards BS6644 (1991) and 5440-2 (2000).
i)Ensure that there is an adequate heat load available.
j)Ensure that the electrical connections have been made correctly.
k)Ensure that the appliance has been correctly configured via the Dip switches located on the
bottom right hand side of the control panel. See Dip switch setting table in 19.1.1.
19.3 first
firing
Notes
The Strata 1 boiler has 2Nr Heat Exchange and Burner Assemblies. The Lower Assembly is referred to as
No1 and the upper as No2. There are two gas valves - one for each burner; the left hand gas valve serves
the lower assembly (No1), and the right hand gas valve serves the upper assembly (No2).
a)Ensure gas & electricity supplies are turned on to the appliance.
b)Switch on the boiler at the on/off switch. (See figure 20) The appliance will purge both
combustion chambers with air from the burner fans and then will pulse the pumps on/off
(venting) to push away any air that may be remaining in the heat exchangers.
19.2 LPG conversion
procedure
The Strata 1 45, 60 and 75 boilers can be converted to operate on LPG. (G31)
Only the parts supplied in conversion kit# 251588 must be used.
The 5.7mm injector must be installed into the outlet of each of the gas valves.
The 3.5mm injectors must only be installed into the inlet of the gas valves where there is a Metering station
prior to the appliance. (When installed the single inlet injector in gas valve #1 should be discarded).
Using the plastic plugs supplied the aeration holes in the white premix air box mounted on the inlet of the
combustion fans must be plugged according to the table below.
The data badge of the appliance must be marked to indicate the conversion has been undertaken.
Refer to the commissioning section for guidance on Combustion Adjustment.
Boiler TypeWhite Premix Air Box Front Hole White Premix Air Box Rear Hole
Strata 1 45Plug with 8mm PlugsNo Rear Hole
Strata 1 60Plug with 10mm PlugsNo Rear Hole
Strata 1 75Plug with 10mm PlugsPlug Both Holes with 15mm Plugs
Dip Switches
48
STRATA1
19.1.1 dip switch
settings
OFF
No Mixing Valve Control Fitted
or
OFF
No Outside Air Sensor Fitted
OFF
Modulating Room Unit Installed
OFF
Analogue Unit 0-3V
OFF
Cascade not fitted
ON
Cascade controls fitted
OFF
* Room unit as Remote Control ONLY
* Remote = Room unit with temperature
sensor turned off and unit acting
just as a remote controller
Room unit with temperature sensor active
ON
PWM Unit (RE2132)
ON
* Room unit with Sensor
OFF
Pump
ON
Divertor valve
OFF
No External
controls
(Method of charging DHW cylinder)
ON
On/off
Room Stat
Time Clock
OFF
0-3 volt control or
0-10 volt control
via adaptor
ON
PWM
cascade
(KKM2)
ON
No external controls fitted.
On/Off controls fitted.
Cascade controls for multiple boilers.
ON
Outside Air Sensor Fitted
OFF
Radiator Circuit (mt 70/50ºC)
OFF
1 x Room Unit (RE2132)
(wired directly to the boiler)
ON
2 x Room Units (RE2132)
Off Off Remote / Remote
On Off Sensor / Remote *
On On Sensor / Sensor
Dip Switches 3 & 4
ON
Radiator Circuit (ht 85/65ºC)
ON
Underfloor Zone Mixing Valve Control Fitted (MR03)
Dip Switches 6 & 7 (system operating temperature)
Dip Switch 6
Dip Switch 2
Dip Switch 5
Dip Switch 4Dip Switch 4
Dip Switch 4
Dip Switch 5
Dip Switch 1
Dip Switch 3
Dip Switch 8
Dip Switch 7
6 OFF 7 OFF Low Temp 55/45ºC
6 OFF 7 ON Med Temp 70/50ºC
6 ON 7 OFF High Temp 85/65ºC
6 ON 7 ON High Temp 85/65ºC
34
Sensor=
49
STRATA1
19.3 First Firing (contd)
c)Turn the green potentiometer
(HWS) fully clockwise(60ºC).
d)Attach U tube manometer to the
gas pressure test point on the gas
supply prior to the appliance. The
nominal pressure should be
20mb for NG or 37mb for LPG.
(See section 8.0 page 7).
e)Press the “Engineers” test button
twice - the screen should/must
display “10 min Low”. The
boiler should now ignite and
following stabilisation of the
flame, will turn down to and hold
at minimum output. In the event
that ignition of one or both
burners does not occur after 4
attempts the appliance will go to
ignition failure lockout. Remove
the cover cap screws from Qmin
adjustment on gas valves
(See figure 21 (2)) turn
adjustment screw half turn
clockwise.
Press reset button, appliance will
post purge and vent again.
Press Engineers test button twice
to reset appliance to “10 min
Low” and ignition sequence will
start again. If ignition fails again
after 4 attempts, then further
increase Qmin (2) on each gas
valve by half turn until burners
ignite.
f)Observe the colour of both
burner flames - correct colour
should be dull red. Adjust colour
of burner flames using Qmin (2)
until flame colours are correct.
Following this procedure will
avoid poisoning your combustion
analyser.
g)Remove flue gas analysis test point cap or plug (from top right of combustion chamber) of the
lower heat exchanger and insert probe of combustion analyser. Adjust as necessary Q min (2)
of left hand valve to obtain required CO
2
% value. (See table 1) Make adjustments slowly and
wait at least 2 minutes for reading to stabilise before re-adjusting. Remove analyser and refit
cap/plug to test point. Repeat above procedure with upper heat exchanger and right hand gas
valve.
Control Panel
Fig. 20
Table 1.
Display
Gas Valve
Fig. 21
Q max
Q min
Burner offset
pressure
test point
Adjustments
Turning 3 clockwise increases min output & CO2%
Turning 4 Anti clockwise increases max output & CO2%
ECO/ECO
Plus Switch
On/Off
Switch
Reset
Button
Engineers
Button
Test
Button
Flue gas CO2 % Settings
Gas TypeNat Gas G20LPG G31
CO
2
% at min output9.511.5
CO
2
% at max output9.011
RESETTEST
STATUS
ECO
PLUS
ECO
3
2
1
50
STRATA1
a)If direct-on-boiler weather compensated flow temperatures are required, then ensure the
(supplied) outside air temperature sensor has been installed on a north facing wall away from
possible heat sources and Dip switch No2 has been set to “on”.
The boiler is supplied with the compensation slope shown overleaf set as a default.
NOTE: The default slope is obtained when the red and blue potentiometers are set in the vertical position.
b)If the default settings are not applicable to the needs of the system user, then the angle of the
slope may be changed by adjustment of either the blue or red potentiometers or both.
Adjustment of the red potentiometer raises or lowers the flow temperature at low outside (design)
air temperature.
Adjustment of the blue potentiometer raises or lowers the flow temperature at the end point (high)
outside air temperature.
Each potentiometer has the range of +20ºC and -20ºC about the default point but with a limiting
factor that the maximum flow temperature is 85’C.
See graphs following showing range of parallel displacement of the compensation slopes.
19.3 First Firing (contd)
19.4. setting weather
compensation
NOTE: Test period expires after 10 minutes - if this expires whilst commissioning is still in progress,
press Engineers button twice to reset and carry on with necessary checks and adjustments. To exit “10
min Low” test period - press Engineers button once, this will set controls to auto.
h)Turn the green potentiometer (whilst still in “10 min Low” operation) fully anti-clockwise (20ºC).
This will set the burners to maximum output.
i)Check CO
2
% of upper heat exchanger and adjust as necessary screw (3) Q max of right hand
valve, to obtain required value. (See table 1)
NOTE: Adjustment of either (2) Q min or (3) Q max will affect the other adjustment to a lesser or
greater extent. Following either adjustment of (2) or (3) check the effect on the setting of the other
adjustment and correct as necessary.
j)Remove analyser from upper heat exchanger and refit cap/plug to test point.
k)Repeat operations described in i) and j) but on lower heat exchanger and left hand gas valve.
l)Press Engineer ’s test button once to exit 10 minute test mode.
m) Turn off electricity and gas supplies and remove manometer from inlet pressure test point and
refit test point screw.
n)Turn on gas and electricity supplies.
51
STRATA1
Default Compensation Slope
Max Flow Temperature
Boiler Flow Temperature ºC
Outside Air Temperature ºC
Range of Parallel Displacement of Slope A
Boiler Flow Temperature ºC
Outside Air Temperature ºC
Dip Switch Settings
When compensation req'd outside sensor must be
installed and dip switch No.2 set to "ON".
Slope A - Dip 6 ON & Dip 7 OFF or 6 ON 7 ON
Slope B - Dip 6 OFF & Dip 7 ON
Slope C - Dip 6 OFF & Dip 7 OFF
90
80
70
60
A
B
50
40
30
20
10
-20-15 -10-5
-1
RED
90
80
70
-20+20
*
C
+5 +10 +15 +20 +250
1
-10
-20
*
RED
+10
K
+20
BLUE
2
-10
-20
*
BLUE
+10
K
+20
60
50
40
30
20
10
-20
-15-10
-5
-1
default
+5 +10
+15 +20
+20
*
-20
+250
52
STRATA1
Range of Parallel Displacement of Slope B
Boiler Flow Temperature ºC
Outside Air Temperature ºC
Range of Parallel Displacement of Slope C
Boiler Flow Temperature ºC
Outside Air Temperature ºC
1
*
-10
90
80
70
60
50
40
30
20
10
-20
-15-10-5
RED
-20+20
*
+5 +10 +15 +20 +250
-1
default
+20
*
-20
2
BLUE
-20
-10
-20
RED
*
BLUE
+10
K
+20
+10
K
+20
90
80
70
60
50
40
30
20
10
-20
-15-10-5
RED
-20+20
*
+5 +10 +15 +20 +250
-1
+20
*
-20
1
2
BLUE
-10
-20
-10
-20
*
RED
*
BLUE
+10
K
+20
+10
K
+20
53
STRATA1
19.5 setting domestic
hot water temperature
19.6 service button/setting
heating output,
pump speeds and minimum
mixed flow temperature.
A) With HWS sensor in/on DHW Calorifier.
1)Set desired stored hotwater temperature by using the “green” potentiometer on the boiler
control panel. This arrangement will give the potential to charge hot water continuously (24
hour/day) with priority over the heating demand. This arrangement is recommended only
with high/quick recovery type calorifiers.
B)With cylinder thermostat in/on DHW Calorifier.
1)Set desired stored hot water temperature by the adjustment of the cylinder thermostat.
With this arrangement the “green” potentiometer on the boiler control panel has no function.
With this arrangement time control of hot water charging is possible by installing a time switch
in series with the cylinder thermostat, but hot water charging always takes priority over the
heating demand.
The service button is located adjacent to the Dip switch block (bottom right hand of control panel) and
has a number of functions.
a)Setting maximum output to heating.
The output to heating may be limited if required and may be set between 20% and 100%, by
performing the following:
i)Press “red” reset button once.
Press service button once.
Screen display will show “Mxhea”???>??%
The figures to the left of the “>” symbol are the current settings for maximum heating output as
a percentage of the maximum output of the boiler.
ii)To change the output, turn the “red” potentiometer and the figures to the right of the “>”
symbol will change. Set the required % output by adjusting the “red” potentiometer. - - equals
100%.
iii)To “store” the new setting; press the service button once.
iv)If no further adjustments are required then set “red” potentiometer back to it’s original position
as this affects the compensation slope setting if compensation is active.
b)Setting maximum pump speed. (Normal setting 100%)
If it is required to limit the maximum speed of the in built boiler pumps then this may be done by
the following:
i)Press “red” reset button once.
Press service button once.
Press “red” reset button twice.
Screen display will show “Mx pum”???>??%.
ii)To change maximum pump speed (not recommended, normally left at - - (100%) follow
procedure as in a) ii)-iv) above.
54
STRATA1
19.6 Service button/setting heating output. (contd)
19.7 output for charging
hot water
20. setting the boiler
to work
c)Setting minimum pump speed.
If it is required to limit the minimum pump speed of the in built boiler pumps then this may be done
by the following:
i)Press “red” reset button once.
Press service button once.
Press “red” reset button three times.
Screen display will show “Mn pum”???<??%
ii)To change minimum pump speed then follow procedure as in a) ii)-iv) above.
d)Setting minimum mixed flow temperature.
Only applicable where MR03 underfloor zone controller is installed.
If it is required to set a minimum mixed flow temperature at the outlet of underfloor zone VT value,
then this may be done by the following:
i)Press “red” reset button once.
Press service button once.
Press “red” reset button four times.
ii)To set minimum mixed flow temperature follow procedure as in a) ii)-iv) above.
e)Clearing “service” message from screen display.
After a default of 365 days of an electrical supply being applied to the boiler, a message to the user is
shown on the screen displaying “service”, reminding the user that the appliance should now be
serviced.
Following a service visit by the specialist engineer, the service message may be cancelled by pressing
and holding the service button for approximately 10 seconds.
There is no adjustment necessary or possible, as the boiler controls are self learning and will self adapt the
optimum output to hot water according to the heat transfer capabilities of the connected hot water
calorifier or cylinder.
1. To fit casing to boiler ensure hooks on top rear edge of boiler case engage properly into rear chassis
assembly.
Latch bottom case fixings and tighten central locking screw.
2.Turn ON on/off switch and set any external controls to auto operation.
3.Set ECO/ECO plus switch to ECO position for systems without additional heating circuit pump
OR Set ECO/ECO plus switch to ECO plus position for systems with a local low velocity header and
additional heating circuit pump.
4.With boiler operating (burners on) press “Test” button on boiler control panel to test overheat
controls in the boiler. The boiler must shut-down and then re-ignite.
55
STRATA1
21. servicing
instruction
21.2 maintenance
21.1 inspection
GENERAL
In general, maintenance/inspections should take place:
a)When the display on the unit indicates that inspection is required (status shows “SERVICE”).
b)At least every 12 months, before carrying out any maintenance the unit must be inspected.
a)Ask the user about any problems with the boiler unit or any other comments.
b)Check the water pressure of the installation.
c)Remove the casing of the unit and inspect all pipes and connections for water leaks.
d)Inspect the top of the casing and/or the top of the upper heat exchanger for water leaks or signs
of water from the flue air supply tube.
e)Open the siphon cleaning rinsing point at the base of the unit and drain syphon into a
suitable receptacle.
f)If you have a notebook computer, connect it and check the service page for any errors,
messages, starts and successful restarts. (Special communication lead and service software
required)
g)Run the unit at maximum capacity and measure the input and the CO
2
%.
h)Run the unit at minimum capacity and measure the input and the CO
2
%.
i)Listen to the sound of the in built pumps.
j) Disassemble each burner by removing the six M6 nuts around the burner door, removing the
ignition cable and pulling the burner forwards.
When the burner has been pulled forwards to halfway across the burner area, the plug on the
fan cable must be removed from the fan motor.
Check the interior of the heat exchanger.
k)Disassemble the plastic box at the suction side of the fan, inspect the fan blades.
l)Check the distance between the electrode and the burner; this should be 4 to 5 mm.
m) Check water treatment dosage level.
Depending on the results of the inspection, carry out any maintenance and
if necessary any preventive maintenance.
Possible actions include:
ata) The remarks and comments of the client must be taken seriously and the cause(s) of any faults
or problems must be found.
56
STRATA1
21.2 maintenance (contd)
atb)The pressure of the installation must be between 1 and 2 bar: any possible leaks in the system
must be identified; if necessary, have a pipework engineer solve the problem.
atc) Possible leaks or weeping must be resolved immediately.
at d)In case of water leakage or ingress from the air supply pipe, the cause must be found.
at e)The siphon must be rinsed. With the burners removed, use a filling hose to insert water into
the heat exchanger, which will automatically reach the siphon. Rinse volume should be a
minimum of 2 litres.
atf)Draw your conclusions from the service screen and attend to those parts that have caused any
faults.
at g)and at h)
If necessary, adjust the gas setting on the gas valves.
at i)If the in built pumps make an un-natural noise, and in particular if the pumps are more than 5
years old, it is recommended that the pumps should be replaced by way of preventive action.
Note the pumps are fully modulating and do have characteristic “yet yet” noise which is normal at low
speeds.
atj)NEVER CLEAN THE BURNER ITSELF.
If the interior of the heat exchanger is contaminated and/or there is a deposit on the surfaces
of the coiled stainless steel pipes, the latter must be removed with a hard brush or citric acid.
(DO NOT USE A STEEL BRUSH !) Then remove any dirt with a vacuum cleaner.
at k)If dirt has deposited on the fan blades, each blade must be carefully cleaned, until the blade
material is visible again. If this is not done evenly the fan will not rotate properly and be out of
balance.
at l)Carefully bend the electrode without touching the burner, until the correct distance has been
reached.
IMPORTANT NOTE
IF ANY WATER CARRYING JOINT WITHIN THE BOILER IS DISASSEMBLED THEN THE “O” RING
SEAL MUST ALWAYS BE REPLACED, LIKEWISE IF ANY OTHER SEAL IS NOTED TO BE DEFORMED
THEN THEY SHOULD ALSO BE REPLACED.
WATER SEALING “O” RINGS ARE A ONE TIME USE ONLY AND SHOULD NOT
BE RE-USED.
Cancelling the Service Message
Following the maintenance operations, the service message (when
displayed) must be cancelled. This is done by pressing and holding in the
service button for at least 10 seconds.
57
STRATA1
22. screen display/
diagnosis of faults
22.1 Screen display
The control panel of the Strata 1 boiler has an LCD screen, displaying two lines of data. This screen
provides information about the operation of the appliance; it shows operation messages (non flashing) and
fault messages (flashing display). The first line contains text information about the status of the unit.
It shows:
STATUS MESSAGES (NON FLASHING) FOR NORMAL OPERATION
StandbyNo heat demand (boiler not required to be on)
Pre-purgeCombustion chambers are being pre-ventilated with air from the burner fans
IgnitionThe ignition sequence of the burners is initiated
Heat-operateThe boiler is operating in central heating mode
Tap-operateThe boiler is operating to produce domestic hot water
Flue-emissionThe boiler is operating in test mode at mid output to enable flue gas emissions to be
checked (auto expires after 10 min)
10 min LowThe boiler is operating in engineers test mode for adjustment purposes (auto expires
after 10 min)
Post-purgeCombustion chambers are being post-ventilated with air following boiler operation
Limit F/RThe flow and/or return temperature is too high (currently)
Fan 1 highThe lower burner fan is running too fast (currently)
Fan 1 lowThe lower burner fan is running too slow (currently)
Fault room uThere is a fault with the modulating unit (RE2132) or Cascade manager (KKM2) or a
fault in the wiring to these controls (in the case of the RE2132 the boiler runs
continuously in heating mode to protect the building)
Fault outsidThere is a fault in the outside air sensor or in the wiring to the sensor or the dip
switches are incorrectly set to ask the boiler to look for an outside sensor when there
is none installed
ServiceThe service interval time has expired and the boiler should now be maintained
Serv. ButtonThe service button is being depressed
Fan 2 highThe upper burner fan is running too fast (currently)
Fan 2 lowThe upper burner fan is running too slow (currently)
VentingThe in built pumps are operating to remove any possible collection of air from the heat
exchangers. (Occurs when power turned off/on and after reset of fault)
The second line of text displays values such as temperature, percentages etc and the red reset button may
be used to scroll through (for information) the values of the various sensors that are/may be connected
in the boiler plus fan speeds and pump speed etc.
58
STRATA1
22.1 screen display/diagnosis of faults (contd)
STATUS MESSAGES (FLASHING DISPLAY) INDICATING A FAULT
A flashing display indicates a fault and that the boiler has shutdown (lockout). The boiler will not attempt
to operate until the “red” reset button is pressed.
Any repetitive flashing fault message should be investigated, the cause found and corrective action taken.
for each flashing display message there is a possible cause, see list of cause numbers following the “flashing
status” list.
DISPLAY MESSAGEMEANINGCAUSE NUMBER/S
FLASHING
Wat 1 LockoutLower ht/exch high limit stat has5,6,7,8,21,24,25,26,31
tripped.
Wat 2/Flue LoUpper ht/exch high limit or flue2,5,6,7,8,21,24,25,26,31
limit stat has tripped
Fan 1 highLower burner fan speed is too high9,11,29,31,33
Fan 1 lowLower burner fan speed during
pre-purge is too low9,10,11,14,18,29,31,33
Fan 1 operLower burner fan is detected as 3,4,11,29,31
operating when should be idle
Ignit 1 faultIgnition to lower burner has not12,13,15,16,17,19,22,
been successful after 4 attempts23,27,29,30,31,35
Flame 1 outFlame at lower burner has been13,15,17,19,20,23
lost on 4 consecutive occasions
during operation
Flame 1 on w/Flame is detected at the lower17,19,30
burner when there should be no
flame
S1 interruptLower ht/exch flow temperature
sensor interrupted3,5,33
S3 interruptUpper ht/exch flow temperature 3,5,33
sensor interrupted
S4 interruptReturn temperature sensor3,5,33
interrupted
S7 interruptMixed flow temperature sensor1,3,5,33
interrupted. Only when MR03 unit
installed
Program endFollows reprogramming of control
panel with laptop PC, not a fault
- just press reset button
Fan 2 highUpper fan speed too high9,11,29,31,33
59
STRATA1
Fan 2 lowUpper burner fan speed too low 9,10,11,14,18,29,31,33
during pre-purge
Fan 2 operUpper burner fan is detected as 4,11,29,31
operating when should be idle
Flame 2 on/wFlame is detected at the upper17,30
burner when there should be no
flame
Ignit 2 faultIgnition to upper burner has not12,13,15,16,17,20,22
been successful after 4 attempts23,27,29,30,31,35
Flame 2 outFlame at upper burner has been 13,15,17,20,23
lost on 4 consecutive occasions
during operation
Gas valveConnection to gas valve interrupted26,28,29,31,33
Soft faultError in software in the control29
Reset buttonThere is a fault with the reset 29,31,34
button
EepromThere is a fault in the EEPROM29
in the control
22.1 screen display/diagnosis of faults (contd)
22.2 (possible) causes of fault
& corrective action
CAUSE REASON/ACTION
No.
1 -Dip switches not set correctly / Check and correct settings
2 -Unsound electrical connections to flue limit stat / Check and correct
3 - Sensor not correctly connected or sensor defective/Check connections and or
replace sensor
4 - Short circuit in wiring / Check and rectify
5 - Short circuit in wiring to sensor / Check and rectify
6 - Boiler pumps not rotating (seized or defective)/Free seized shaft or if defective replace
pump
7 -System lacks water / Investigate, refill and vent
8 - Connections to heat exchanger limit stat unsound /check & rectify
9 - Unsound electrical connection to fan / Check integrity of fan connection plug
10 - Fan blades heavily contaminated / Clean fan
60
STRATA1
22.2 (possible) Causes of fault (contd)
11 - Fan is defective / Replace fan
12 - There is no gas supply available / Investigate, restore gas supply
13 - Low gas pressure / Investigate and rectify
14 - Fuse defective / Check fuses and replace as necessary
15 - Gas valve min output setting is incorrect / Check and adjust min output CO
2
%
16 - Oxidation on burner mounting screws. Loosen and retighten screws.
17 -Poor ignition lead connection to electrode or damp connection or lead damaged
and shorting to earth / Check and rectify
18 - Transformer defective / Replace transformer
19 - Condense siphon is blocked or condense waste blocked or frozen / Clear siphon or
waste pipe
20 -Flue gas leakage from connection at rear of heat exchanger / Check, reposition or
replace seal
21 -System strainer blocked ?, isolation valve closed ? Or some other interruption to water
flow / Check and rectify
22 - Unacceptably high resistance in flue or air supply tubes or flue blocked / Check flue
for suitability or clear obstruction
23 -Leakage of flue gas from flue gas tube into air tube vitiating the combustion air / Strip
out flue system and remake joints
24 - Zone pumps not running / Check and rectify
25 - Heat exchangers fouled internally with silt or scale / Clean, descale heat exchangers
and system and re-dose system with water treatment
26 - Heat exchanger high limit stat defective / Replace limit stat
27 - Boiler set for wrong gas type / Convert boiler to burn the gas being supplied
28 -Flue gas limit stat defective / Replace limit stat
29 -Boiler control panel defective / Replace control panel
30 -Incorrect position of ignition electrode / Reset gap 4-5mm
31 -moisture in-on electrical connections or components / Dry carefully using warm air
from a hair dryer
32 - Incorrect electrical connection / Check and rectify
33 - Wiring interrupted (broken wire) / Check and rectify
34 - reset button stuck / Press button in attempt to free sticking contacts. If no success
then replace control panel
35 -Ignition electrode damaged or broken / Replace electrode23. User instructions
61
STRATA1
The installer should inform the user about the operation and use of the Strata 1 boiler and in particular
point out:-
- Any safety provisions
-The need to carry out regular maintenance when the screen display shows a “SERVICE” message
The installer must provide the user with all documentation relating to the Strata 1 boiler and any ancillary
items.
23.1 To turn on the appliance
1 - Ensure the pressure gauge indicates a pressure within the system of not less than 0.5bar.
2 - Ensure the gas supply is turned on.
3 - Switch on the on/off switch on the appliance control panel.
4 - If all controls connected to the boiler are calling for heat the screen will display
Heat-Operat or Tap Operat.
5 - If all controls are in the off position the screen will display standby.
23.2 To turn off the appliance
1 - Switch off the on/off switch on the appliance control panel.
2 - Turn off the gas supply.
NOTE: Turning off the appliance will leave the system at risk of freezing during winter months and will put
out of action the automatic pump exercising routine. If the only reason for shutdown is that normal heating
is not required, then it is recommended to leave the boiler on and turn off or turn down any external
controls.
This publication is issued subject to alteration or withdrawal without notice.
The illustrations and specifications are not binding in detail. All offers and sales are subject to the Company's current terms and conditions of sale.
A member of the Modular Heating Group Plc
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.