MHS Boilers STRATA1, STRATA1 38, STRATA1 38 COMBI, STRATA1 46 COMBI Instructions Manual

Page 1
STRATA1
38 & 38/46 COMBI
WALL MOUNTED, GAS FIRED,
ULTRA HIGH EFFICIENCY CONDENSING BOILERS
INSTRUCTIONS FOR INSTALLATION,
SERVICING & OPERATION OF
THE MODEL 38 BOILER & THE 38/46 COMBI
Page 2
2
STRATA1
38 & 38/46 COMBI
Index
page section
3
. . . . . . . . . . .
1.0
General Notes
4
. . . . . . . . . . .
2.0
Product Description
5
. . . . . . . . . . .
2.0
Product Description (contd)
6
. . . . . . . . . . .
3.0
Technical Data & Dimensions
7
. . . . . . . . . . .
4.0
Delivery Consignment/Unpacking The Boiler
. . . . . . . . . . . .
5.0
Boiler Location
. . . . . . . . . . . .
6.0
Installation Clearances
8
. . . . . . . . . . .
7.0
Wall Mounting
. . . . . . . . . . . .
8.0
Gas Connection
9
. . . . . . . . . . .
9.0
Water Connections
. . . . . . . . . . .
10.0
Condense Waste Connection
10
. . . . . . . . .
10.0
Condense Waste Connection (contd)
. . . . . . . . . . .
11.0
Flue Combustion Air Connection - General
11
. . . . . . . . .
12.0
Conventional Flue Installation
12-18
. . . . . . .
13.0
Room Sealed Flue Installations
19
. . . . . . . . .
14.0
Examples of Calculating Flue Pressure Loss
20
. . . . . . . . .
14.1
Calculating Flue Resistance
. . . . . . . . . . .
15.0
Flue Terminal Positions
21
. . . . . . . . .
15.0
Flue Terminal Positions (contd)
22-23
. . . . . . .
16.0
Ventilation Requirements Single Appliances
24-33
. . . . . . .
17.0
Hydraulic System Design (circuit diagrams)
33
. . . . . . . . .
17.1
Filling The System
. . . . . . . . . . .
17.2
Water Treatment System Cleaning
34
. . . . . . . . .
17.3
Care With The Use of Soldering Flux
. . . . . .17.4
Domestic Hot Water - Combi
. . . . . . . . . . .
17.5
Combi Boiler - Prevention of scale in
. . . . . . . . . . . . . . water to water heat exchanger
35-36
. . . . . . .
17.6
Combi Boiler Hot Water
. . . . . . . . . . . . . . System Pipework Pressure Drop
. . . . . . . . . . .
17.7
Combi Boiler - Domestic Hot Water
. . . . . . . . . . . . . . System Design Considerations
36-48
. . . . . . .
18.0
Electrical Connections
49
. . . . . . . . .
19.0
Commissioning The Strata 1 Boiler
. . . . . . . . . . .
19.1
Pre-Commissioning Checks
. . . . . . . . . . .
19.2
LPG Conversion Procedure
50
. . . . . . . . .
19.3
Control Panel
51-52
. . . . . . .
19.4
First Firing
52-54
. . . . . . .
19.5
Setting The Control Panel
54-60
. . . . . . .
19.6
Installer Programming of Control Panel
61
. . . . . . . . .
19.7
Output For Charging Hot Water
. . . . . . . . . . .
20.0
Setting The Boiler To Work
. . . . . . . . . . .
21.0
Servicing Instruction
. . . . . . . . . . .
21.1
Inspection
61-62
. . . . . . .
21.1
Inspection (contd)
. . . . . . . . . . .
21.2
Maintenance
63
. . . . . . . . .
21.2
Maintenance (contd)
63-65
. . . . . . .
22.0
Screen Display/Diagnosis Of Faults
65-66
. . . . . . .
22.1
(Possible) Causes Of Fault & Corrective Action
67
. . . . . . . . .
23.0
Instructing The User
. . . . . . . . . . .
23.1
To Turn on the Appliance
. . . . . . . . . . .
23.2
To Turn off the Appliance
68-70
. . . . . . .
24.0
Parts List
Page 3
3
STRATA1
38 & 38/46 COMBI
1.0 general
notes
These instructions are intended to assist the installer, commissioning engineer, maintenance engineer and user with the installation, maintenance and usage of the Strata 1-38 gas fired condensing boiler and the Strata 1-38/46 gas fired condensing combination boiler.
Please read this manual fully before commencing the installation of the appliance. The Strata 1 must only be installed by persons deemed to be competent i.e. Corgi Registered. This manual must be handed to the appliance user following completion of the installation. The appliance must not be left to operate with the outer casing removed.
conformity statement
Strata 1 38 & 38/46 Combi boilers are manufactured to the highest standard of quality, performance and safety, in accordance with EC standards. Strata 1 45, 60 & 75 boilers carry the CE mark
installation requirements
The installation of Strata 1 boilers must be in accordance with the relevant requirements of Gas Safety (Installation and Use) Regulations 1994, Health & Safety at Work Act, Building Regulations, I.E.E. Regulations, Construction (Design & Management) Regulations 1994, Local Authority Bye-Laws, Local and National Water Bye-Laws, Fire Authority Regulations and Insurance Company requirements.
The following Codes of Practice are also applicable:-
BS6798: 1987 Specification for installation of gas fired hot water boilers of rated input not
exceeding 60kW.
BS6880 Code of Practice for low temperature, hot water heating systems of output greater than
45kW. Parts 1, 2 and 3: 1988.
CP342 Part 2: 1974 Code of Practice for centralised hot water supply.
BS6644 1991 Specification for gas fired hot water boilers of rated inputs between 60kW and 2MW.
IGE/UP/2 Gas installation pipework, boosters and compressors on industrial and commercial
premises.
CIBSE Guide Reference sections B7, B11 and B13.
BS5440 Installation of flues and ventilation for gas appliances of rated input not exceeding 60kW.
Part 1: 1990 Specification for the installation of flues.
BS5440-2: 2000 Installation and maintenance of flues and ventilation for gas appliances of rated input
not exceeding 70kW net (1st, 2nd and 3rd family gases) Part 2: Specification for installation and
maintenance of ventilation for gas appliances.
IGE/UP/10 Installation of gas appliances in industrial and commercial premises. Part 1: Flued appliances.
Page 4
4
STRATA1
38 & 38/46 COMBI
2.0 product
description
The Strata 1 range of wall mounted gas fired condensing boilers are state of the art appliances which
include a comprehensive range of features. The appliance must only be used on sealed and pressurised systems. System design must take into account the boiler operating t of 20°C.
wall mounted with compact dimensions
At 900H x 458W x 355D, the Strata 1 boiler provides maximum heat from minimum dimensions
without compromising serviceability.
fully modulating heat output
The output of the boiler is fully variable, sliding between (approx.) 20% to 100%, which automatically and instantly adjusts to match the needs of the system. The percentage of power at any given time can be dictated by either outside air temperature, flow temperature, return temperature, stored or instantaneous domestic hot water temperature, or room temperature, or a combination of the aforementioned.
fully condensing stainless steel heat exchanger
The Strata 1 boiler is designed with extended heat exchange surface area and is fabricated from corrosion resistant long-life stainless steel. The unique Spiranox heat exchanger will return operating efficiencies from 88% gross (96% nett) at 60°C return temperature, up to 96% gross (104% nett), at 30°C return temperature.
extremely low harmful emissions
The boiler utilises 100% pre-mix gas/air fed at positive pressure to the metal fibre sheathed radiant burner. The combustion system incorporates internal flue gas re-circulation and this combined with the precise nature of pre-mix fuel/air control, gives ultra low emissions to satisfy the most stringent emission regulations in the world currently. That is: < 20mg/kWh NOx (14 ppm DAF) and < 14mg/kWh CO (13 ppm DAF). The fully modulating nature of the appliance also reduces emissions by avoiding repeated start/stops and the associated increase in emissions, which occurs with burner on/off cycling.
accurate variable burner output control
The pre-mix burner fan has a low voltage direct current drive motor with pulse relay counting. This system allows precise control over fan speed/combustion air volumes. Coupled with a gas valve system set to provide proportionately measured volumes of fuel to air, this allows extremely accurate and instant variable burner output control to be achieved.
high domestic hot water flow rate – combi boiler
The combi boiler includes a high performance water to water heat exchanger which coupled with a variable output up to 46kW provides up to 0.21 l/s of hot water raised through 50°C. The water to water heat exchanger contains 10 litres of primary water which is maintained at the required domestic hot water temperature so ensuring prompt delivery of hot water.
energy saving
In addition to the extremely efficient burner and heat exchanger system employed in the Strata 1, each appliance includes a modulating speed boiler primary pump.
This feature allows the boiler to self-maintain a 20°C t across the heat exchanger, optimising the heat exchanger efficiency and reducing also the electrical consumption of the pump motor. The result is a seasonal increase in boiler efficiency of a further 7-10% and a reduction in pump electricity consumption of up to 70%.
Page 5
5
STRATA1
38 & 38/46 COMBI
2.0 product description (contd)
natural gas or LPG
Appliances can be supplied for use with natural gas (G20) or LPG (G31).
comprehensive microprocessor control
The boiler control panel includes a user friendly microprocessor control centre which manages the
entire function of the appliance and encompasses:-
1. Management of the essential safety functions of burner ignition and flame monitoring.
2. Water high temperature and flue gas high temperature safety cut out.
3. Modulation of the boiler output and pump speeds in conjunction with operating temperature control.
4. LCD display screen with two lines of text to continuously display operational or fault status.
5. In built weather compensator to provide direct-on boiler VT flow temperature (if required).
6. Remote stored hot water temperature control and when using optional temperature sensor gives the option of regular anti-legionella programme (not combi).
7. In built 2 stage boiler frost protection program.
8. In built pump exercising program to avoid standstill seizure.
9. Cold start boost facility.
10. PC compatibility with data logging which allows communication with the boiler via a lap-top computer to review/modify operational parameters and access operational history as an aid to fault finding and preventative maintenance.
11. Range rate adjustment which allows the power to be set to accurately match the maximum needs of the system, with the facility to set a different firing rate for heating. Output to hot water self adjusts to the heat transfer capability of the calorifier or the instantaneous demand (combi boiler).
12. Facility to connect optional matched control components which allow the boiler to control a heating circuit pump, *HWS primary pump or *diverter valve and an underfloor circuit mixing valve and pump, (MR03) plus the ability for the boiler to be controlled by a remote multi function modulating room unit. (RE2132) Multiple boilers may be connected to a modulating Kaskade manager (KKM2) or controlled via a 0-3 or 0-10v* signal (*via adaptor) which further enhances the operating efficiency of a larger load modular boiler system. (*Not combi).
13. Inbuilt time switch (3 on - 3 off/24hr) for heating control and *separate channel for hot water time control. (*Not combi).
room sealed option
If required, the boiler may be installed to be completely room sealed, taking combustion air directly
from outside the building, using a 125/80 concentric air duct/flue duct system. Inherent safety is afforded by the negative pressure within the boiler casing, which in the event of incorrect sealing results in safe inward air leakage only.
extended flue lengths
The excess fan pressure from the combustion system is 100 Pa, which allows the appliance to be
exhausted using small diameter PPS plastic flue components, over long distances, allowing for complete flexibility in boiler siting.
designed for ease of maintenance
Although compact, the Strata 1 does not compromise serviceability. The appliance has been engineered
to be easy to maintain with even the most major of service operations being able to be completed easily and quickly with the minimum of tools.
guarantee
The heat exchanger carries a five year guarantee against manufacturing or material defect. All other
parts carry a one year warranty against manufacturing or material defect.
Page 6
6
STRATA1
38 & 38/46 COMBI
3.0 technical data
& dimensions
Dimensions in millimetres
229
458
155
355
3
4
6
7
8109
5
60
60
60
110
50
50
950
front view
plan view
underside - 38/46 combi
145 145
100 100
40
1
2
38/46 Combi
DN125
DN80 22mm 22mm 22mm 22mm
3
/4" BSP-M
15mm
— —
38
DN125
DN80 22mm
— —
22mm
3
/4" BSP-M
15mm
— —
Connection Strata 1
1. Combustion Air Inlet
2. Flue Gas
3. Flow
4. Hot Water (Out)
5. Cold Water (In)
6. Return
7. Condense Waste Outlet
8. Gas Connection
9. Condense Syphon Cleaning Point
10. Glanded Cable Entries
Model Strata 1 Input Range Central Heating Net kW CH Modulating Output 80/60°CkW CH Modulating Output 50/30°CkW Min Working Pressure CH Bar Max Working Pressure CH Bar Max Flow Temperature CH °C Total Primary Capacity Litre Available CH Pump Pressure at
kPa
38kW & 20°C ∆t Input Range Domestic Hot Water Net
kW
HW Modulating Output kW Domestic Hot Water Flow at 50° ∆t l/min Domestic Hot Water Flow at 35° ∆t l/m Max Working Pressure
Bar
Domestic HW Max Flue Gas Volume (Hot) m
3
/h
Gas Consumption (Nat Gas G20) m
3
/h Min/Max Gas Inlet Pressure mbar Average Electrical Consumption Watts Power Supply V Weight Empty kg
38/46 Combi
6.4 - 36.0
6.2 - 34.6
7.0 - 37.8
0.5
3.0 85
12.4
23.5
6.4 - 46.0
6.4 - 46.0
13.14
18.77
10.0
65.13
0.68 - 4.77 18/60
60
230
50
38
6.4 - 36.0
6.2 - 34.6
7.0 - 37.8
0.5
3.0 85
2.4
32.5
6.4 - 46.0
6.4 - 46.0
— —
65.13
0.68 - 4.77 18/60
60
230
39
underside - model 38
100 100
145 145
40
50
60
10 3 10 8
67
9
Page 7
4.0 delivery consignment
/unpacking the boiler
The boiler is delivered as a consignment of a palleted carton containing the boiler and associated
fittings, plus any other optional ancillary flue or control components in separate cartons.
The boiler carton contains:-
Assembled boiler.
Wall mounting bracket.
Fittings bag including: condense waste outlet hose union assembly, outside air temperature sensor c/w
wall fixings and 1/2" BSP inlet 3/4" BSP outlet safety pressure relief valve set 3 bar.
To unpack the boiler, the palleted carton should be laid on the floor. Carefully cut the nylon bands and lift away fibre board protective panel. Open carton top and lift out wall hanging bracket and fittings bag. Remove packing material and lift away bottomless carton. With 2 men, carefully lift boiler from palette by holding grey rear chassis only.
To remove the casing from the boiler, slacken the screw in the underside of the casing, unlatch left and right hand catches on underside of case, pull casing slightly to the front and lift upwards to disengage casing hooks from rear chassis and then remove casing to the front.
5.0 boiler
location
The Strata 1 Boiler is not suitable for installation external to a building. The position chosen for the boiler must be a structurally sound wall capable of supporting the weight of the boiler and any ancillaries. The position should allow for access to a condense waste drain nearby or an alternative is to install a condense sump receptacle and condense disposal pump which should remove the condense waste water to a remote drain. The wall mounting position of the boiler must allow the boiler to be true plumb vertical to ensure correct operation of the internal gravity flow condense system. The position for the boiler must satisfy the requirements of BS6798:1987 or BS6644:1991 as appropriate.
6.0 installation
clearances
For ease of installation, commissioning and maintenance the following minimum clearances should be observed:-
Sides 50mm Above 250mm Below 150mm Front 450mm
STRATA1
38 & 38/46 COMBI
7
Page 8
8
STRATA1
38 & 38/46 COMBI
7.0 wall
mounting
The Strata 1 boiler mounts to the wall via a wall mounting bracket which interlocks to a rail mounted upon the rear of the boiler. The wall mounting bracket should be firmly fixed to the wall using suitable fixings. The wall mounting bracket positioning detail is shown in fig 1. The boiler must be carefully offered up to the wall so that the rail on the rear of the boiler is just above the wall mounting bracket and then the boiler should be lowered to engage the bracket and rail. Lifting is advised with 2 persons. Do NO
T lift the boiler by the internal parts of the appliance.
Important Note
When viewed from the side, the north/south axis of the boiler must be vertical. The appliance must not be inclined out from the top, if necessary adjust the positioning of the boiler using the adjustable wall bearing assemblies located at the bottom rear left and right hand of the appliance back panel.
8.0 gas
connection
The gas connection is located at the base of the appliance rear centre, see fig 2.
The pipe size used to supply the appliance must not be smaller than the gas connection size on the appliance.
The connection to the appliance must include a suitable method of disconnection and a gas control cock must be installed adjacent to the appliance for isolation purposes.
The gas pipe used to supply the appliance must not allow a pressure drop of greater than 1mbar from the meter to the appliance.
The nominal inlet working gas pressure measured at the appliance should be
20.0 mbar for Nat Gas (G20) or 37 mbar for LPG (G31). The installer should install a pressure test point adjacent to the gas inlet connection.
Gas Connection
15mm
Fig 2.
Fig 1.
458
50
3 x ø 7.0
165
165
103
797 900
Page 9
Note the Strata 1 boiler must only be installed on sealed and pressurised systems. The maximum working pressure of the boiler = 3 bar. A safety valve set 3.0 bar is supplied with the boiler and must be installed onto the flow pipe adjacent to the boiler. It is recommended that the final working pressure (hot) of the system does not exceed 2.3 bar. Note – the appliance does NOT include an expansion vessel. A suitable vessel must be connected to the system.
The central heating flow and return connections are 22mm OD, located at the base of the appliance (see fig 3) and should be connected to the system pipework using compression type fittings. DO NOT make soldered connections onto the appliance.
The COMBI BOILER includes domestic hot and cold water connections located at the base of the appliance see fig 4. These connections are 22mm and should be connected using compression type fittings. DO NOT make soldered connections onto the appliance.
The flow, return and domestic cold supply pipework should include isolation valves and all pipes should include means of disconnection.
9
9.0 water
connections
10.0 condense
waste connection
The condense waste connection is located at the underside rear of the appliance see fig 5.
The condense syphon cleaning point is factory fitted with a heavy grade black plastic cap which MUST NOT BE REMOVED (see fig 5) apart from routine maintenance cleaning operations and must be in place whenever the appliance is in operation. WARNING operating the appliance with the cap removed from the syphon cleaning point will cause products of combustion to be discharged from the cleaning point.
The condense waste connection is a
3
/4" BSP Male threaded stub fabricated from
plastic. The installer must connect to this stub, a condense waste pipe fabricated from plastic tube and fittings (
3
/4", 22mm, overflow pipe is considered suitable).
Copper Tube is not acceptable. The condense waste pipe must fall continuously from the appliance to suitable nearby drain.
If any part of the condense waste pipe is to be run external to the building or is at risk of freezing, then the pipe must be suitably insulated to protect from freezing.
If a suitable drain for accepting the condense waste is not available nearby to, and below the boiler, (e.g. boiler installed in a basement below ground level location), then a suitable condense sump receptacle with a discharge pump should be installed below the boiler to remove the condense to a remote drain.
STRATA1
38 & 38/46 COMBI
Flow
22mm
Fig 3.
Fig 4.
Return 22mm
Cold Water Inlet 22mm Combi only
Hot Water
Outlet 22mm
Combi only
Page 10
10
STRATA1
38 & 38/46 COMBI
10.0 condense waste connection (contd)
Fig 5.
Condense Waste Connection
Syphon Cleaning
Point Must
Remain Capped
When making the condense waste pipe connection to the boiler, do not use adhesives, it is recommended to lightly apply a suitable jointing tape (PTFE or similar) and use only light pressure to connect fittings to the appliance to avoid damage to the condense waste outlet assembly.
It is recommended that the condense waste pipework should include a method of disconnection and cleaning points.
11.0 flue/combustion
air connection - general
The flue connection and combustion air inlet to the appliance are located on the top of the appliance see fig 6. These connections are arranged concentrically with the 80mm flue gas connection centrally within the 125mm air inlet connection.
There are two options for flueing the Strata 1 boiler:
i) Conventionally, using flue gas tube only and air for combustion from the room or compartment
in which the appliance is installed. If using a conventional flue arrangement then the room or
compartment must be ventilated in accordance
with the requirements of BS5440. For guidance
on ventilation see section 16.
ii) Room sealed using concentric 80/125
components or two seperate tubes, where air
for combustion is taken from outside of the
building. When using a room sealed flue, where
air for combustion is provided from outside of
the building directly to the appliance, ventilation
to a compartment may still be required - See
section 16 for general space cooling.
Multiple Boilers
For detail and advice on common flues serving multiple boilers, contact MHS Boilers Ltd.
Important Note
Where the Strata 1 is to be installed in an application where the combustion air is likely to be contaminated with oxidising agents, such as swimming pool areas, special industrial processes etc, then the appliance must be room sealed.
Air Inlet
Flue Gas Connection
Fig 6.
typical modular
flue arrangement
Inspection Area
Page 11
11
STRATA1
38 & 38/46 COMBI
12.0 conventional
flue installation
The Strata 1 boiler has an excess pressure combustion system, which coupled with the very low flue gas temperatures produced allows the appliance to exhausted over considerable distances using 80mm Polypropylene PPS flue pipe and fittings. Suitable flue pipe and fittings are available from MHS Boilers Ltd and are listed below.
The flue should be installed to have at least a 3° fall to the boiler to allow any condense formed in the flue to run back to the boiler.
The flue system used must be gas and water tight and must be adequately supported over its entire length. Support at 1 metre intervals. It is not necessary to install a terminal to the flue system, however, a mesh guard should be included to prevent blockage or entry of foreign material. Straight lengths may be cut to size with any surplus cut from the plain end. Tube ends should be cut square and de-burred.
Care should be taken when selecting a position for a low level discharge or discharge adjacent to windows etc as the flue terminal will plume heavily and the white water vapour discharge may cause a visual nuisance.
Flue components available from MHS Boilers Ltd
80 mm PPS Flue Tube x 1000 mm long (effective length 945 mm) 80 mm PPS Flue Bend x 93° 80 mm PPS Flue Bend x 45° 80 mm Wall Fixing Bracket - Aluminium 80 mm Bird Mesh Cap - Plated Steel
The above flue components are light grey self coloured Polypropylene moulded com­ponents with push together spigot and socket joints with integral seal ring located in the socket.
If fire stop seals are required to be installed where PPS plastic flue components pass through walls, floors or ceilings then suitable fire stop seals are available from:-
Nullifire Ltd Torrington Avenue Coventry CV4 9TJ
Tel 02476 855000 Fax 02476 469547
Dufaylite Developments Ltd Cromwell Road, St Neots Huntingdon PE19 1QW
Tel 01480 215000 Fax 01480 405526
Quelfire PO Box 35, Altrincham Cheshire WA14 5QA Tel 0161 928 7308
1000 mm
Effective Length 945mm
137
125
ø80
ø80
50
65
75
ø80
50
100
150
50
80 ø PPS Flue Tube x 1000 long
80 ø PPS Flue Bend x 93º
80 ø PPS Flue Bend x 45º
80 ø Wall Fixing Bracket
ø5 Woodscrew fitting
100 mm PPS Flue Tube x 1000 Long (Effective Length 945 mm) 100 mm PPS Flue Bend x 93° 100 mm PPS Flue Bend x 45° 100 mm Wall Fixing Bracket 100 mm Bird Mesh Cap - Plated Steel 80 x 100 mm Increaser
80 ø PPS flue components
100 ID
56
50
150
80 x 100 PPS Increaser
End Slip
80
Page 12
12
STRATA1
38 & 38/46 COMBI
13.0 room sealed
flue installations
The Strata 1 boiler has an excess pressure combustion system, which coupled with the very low flue gas temperatures produced allows the appliance to be exhausted and supplied with room sealed combustion air using a concentric flue arrangement of 80 mm PPS polypropylene flue pipe within a 125 mm outer painted metal air tube over considerable distances. A range of concentric flue components are available from MHS Boilers Ltd and are listed below. Alternatively, two seperate tubes, one carrying combustion air and one carrying flue gas may be used in conjunction with the appropriate adaptor.
The concentric flue system should be installed to have at least a 3° fall to the boiler to allow any condense formed in the flue to run back to the boiler.
The flue system must be gas and water tight and must be adequately supported over its entire length. Support at 1.5m intervals. Horizontal Discharge and Vertical Discharge Terminal Sets are available.
Care should be taken when selecting a position for a low level discharge or discharge adjacent to windows etc as the flue terminal will plume heavily and the white water vapour discharge may cause a visual nuisance.
Concentric flue components have push together spigot and socket joints. Both the inner PPs flue gas tube and the outer air tube have soft seal rings located in the socket components.
To aid assembly and assurance that the joints have been fully pushed home, the seal rings and make ends of tubes/fittings should be lightly lubricated with silicone grease.
list of concentric flue components
80/125 concentric wall terminal set:- comprises 845 mm straight length with made on terminal, 90°
concentric bend and wall bezel plates.
80/125 concentric roof terminal set:- comprises 1000 mm straight length with made on terminal and
1Nr 125 wall bracket.
125 pitched roof tile flashing for use with concentric roof terminal set, adjustable between 25° to 50°.
125 flat roof flashing for use with concentric roof terminal set.
80/125 concentric flue tube set x 1000 mm.
80/125 concentric flue tube set x 500 mm.
80/125 concentric 93° bend.
80/125 concentric 45° bend.
125 Wall bracket assembly.
80/125 concentric vertically extendible discharge room sealed wall terminal assembly (610 mm long
(*850) - For use where a standard wall terminal may cause visual flue gas pluming nuisance. Includes 90°
Concentric bend, wall bezel plates and silicone mastic. Used in conjunction with additional 80 mm pps
flue gas tube and fittings listed on page 10.
80/125 concentric to 2 x 80 mm separate tubes adaptor.
80/125 to 100/150 concentric increaser (not shown).
100/150 concentric wall terminal (not shown).
100/150 concentric roof terminal (not shown).
100/150 concentric flue tube set x 1000 mm (not shown).
100/150 concentric flue tube set x 500 mm (not shown).
100/150 concentric 93°C bend (not shown).
100/150 concentric 45°C bend (not shown).
Page 13
13
STRATA1
38 & 38/46 COMBI
13.0 room sealed flue installations (contd)
497
1000
Effective Length 950 mm
994
Effective Length 450mm
125
80
125
110
75
40
75
40
80
178
75
ø 7mm "Drive In" Fixing C/W Wall Plug
90
125
125
110
40
40
80
125
93º
80
80/125 Concentric Tube x 500mm
80/125 Concentric Bend x 45º
ø125 Wall Fixing Bracket
80/125 Concentric Tube x 1000mm
80/125 Concentric bend x 93º
491
80/125 concentric roof terminal & accessories
80/125 Concentric Roof Terminal Assembly
80
125
1170
513 513
130
390
500
500
Circular 125 Spun Aluminium Flat Roof Flashing
Pitched Roof Flashing - Adjustable 25-38º & 37-50º
125 Pitched Roof Adjustable Flashing. Adjustable between 25-38º and 37-50º
Lead Apron 1.3mm
458
229
355178900
155
120
80 80
plan
80/125 Concentric to 2 x 80 mm Tubes Adaptor
Flue Gas
Air for
Combustion
Page 14
14
STRATA1
38 & 38/46 COMBI
13.0 room sealed flue installations (contd)
installation of standard wall terminal
In order to determine the length of concentric tube required to correctly terminate a side outlet arrangement, the following procedure should be followed:
1. Measure wall thickness W in mm - see fig 7.
2. Measure distance between side of appliance and inside face of wall L1 in mm see fig 7.
3. Mark off and cut flue tubes following guidance shown in fig 8 below. Flue tubes should be cut to length
TL in mm. Both inner and outer tubes should be cut flush with each other, square and any
burrs removed.
Where TL required, is greater than 845 mm, then additional lengths (as appropriate) of 80/125 concentric tube will be required to extend the standard wall terminal. A fall of 3˚ is required along the length of the flue towards the appliance.
detail for marking out for
cutting flue hole for side flue,
room sealed horizontal
arrangement
Cut Flue Hole ø 130mm
Line-Top of
Appliance C
hassis
155
170
side outlet
170
L1
W
Plain Section Installed Uppermost
Wall Bezel Plates
Required Length Cutting Line
measure from this point
TL (mm)
TL = W+L1+235mm
concentric wall terminals
945
610
850*
845
Standard Horizontal Discharge Wall Terminal (supplied with 80/125 Concentric 90º bend and wall bezel plates not shown)
Horizontal Wall Terminal With Extendible Vertical Discharge (supplied with 80/125 Concentric 90º bend and wall bezel plates not shown)
ø125
ø80
ø125
ø80
Fig 7.
Fig 8.
Fig 9.
side outlet
(3
˚ fall to
appliance)
Page 15
15
STRATA1
38 & 38/46 COMBI
installation of standard wall terminal
In order to determine the length of concentric tube required to correctly terminate a rear outlet
arrangement, the following procedure should be followed.
1. Measure wall thickness W in mm - see fig 10.
2. Mark off and cut flue tubes following guidance shown in fig 11 below.
Flue tubes should be cut to length TL in mm. Both inner and outer tubes should be cut flush with each
other, square and any burrs removed.
Where TL required, is greater than 845 mm, then additional lengths (as appropriate) of 80/125 concentric tube will be required to extend the standard wall terminal. A fall of 3˚ is required along the length of the flue towards the appliance.
13.0 room sealed flue installations (contd)
rear outlet rear outlet
170
W
Plain Section Installed Uppermost
Wall Bezel Plates
Required Length Cutting Line
measure from this point
TL (mm)
TL = W+161mm
170
c
L
cut flue hole ø130
detail for marking out for cutting flue hole for rear flue, room sealed horizontal arrangement
Fig 10. Fig 11.
Fig 12.
Page 16
16
STRATA1
38 & 38/46 COMBI
method of assembly of horizontal concentric flue system using standard wall terminal
1. Lubricate male ends of concentric bend with silicone grease and locate bend into flue and air tube connection sockets on the top of the boiler and gently push fully home.
2. Slip flue tube and terminal assembly through prepared hole in the outside wall.
3. Locate wall bezel plate loosely onto air tube.
4. Lubricate male ends of concentric flue tube and female sockets of flue bend lightly with silicone grease. Insert concentric tubes into bend and gently push fully home. Ensure plain section of external part of air inlet tube is located uppermost.
5. Make good internally and externally gap between air tube and prepared hole through wall.
6. Slip on external wall bezel plate.
7. Fix internal and external wall bezel plates with fixings provided.
Where a flue terminal discharges through a wall within 2m of ground level or balcony etc then
the terminal should be fitted with an appropriate sized terminal guard to prevent that the terminal may be touched.
extending the flue gas discharge vertically away from a room sealed wall terminal
The Strata 1 boiler is a fully condensing appliance with very low flue gas temperatures. Consequently,
the flue gas discharge is commonly seen as a white vapour plume, Whereas this is not harmful when properly discharged into the atmosphere outside of a building from a correctly operating appliance, the white vapour plume may cause, in certain applications a visual nuisance.
It must also be considered that a flue termination will drip condense water and may cause an ice hazard
below the terminal position
If it is considered that pluming or dripping from the end of a standard wall terminal may create a
nuisance, then as an alternative, the vertically extendible discharge wall terminal is available see figs 14 and
16. This creates a local room sealed intake for combustion air but allows the installer to extend the 80 mm
PPS flue gas tube to a point where pluming or dripping discharge will not cause a visual nuisance or hazard.
installation of vertical discharge wall terminal
In order to determine the length of concentric tube required to correctly terminate a side outlet
extended vertical discharge arrangement, the following procedure should be followed.
1. Measure wall thickness W in mm - see fig 14 overleaf.
2. Measure distance between side of appliance and inside face of wall L1 in mm - see fig 14 overleaf.
3. Mark off and cut flue tubes following guidance shown in fig 15 overleaf. Flue tubes should be cut to length TL in mm. Both inner and outer tubes should be cut flush with each other, square and any burrs removed.
Where TL required, is greater than 610 mm, (*850mm) then additional lengths (as appropriate) of
80/125 concentric tube will be required to extend the vertical discharge wall terminal. A fall of 3˚ is required along the length of the flue towards the appliance.
13.0 room sealed flue installations (contd)
13
4
6
2
Plain Section Uppermost
Fig 13.
Page 17
17
STRATA1
38 & 38/46 COMBI
installation of vertical discharge wall terminal with rear outlet
In order to determine the length of concentric tube required to correctly terminate a rear outlet
extended vertical discharge arrangement, the following procedure should be followed.
1. Measure wall thickness W in mm - see fig 16.
2. Mark off and cut flue tubes following guidance shown in fig 17 below.
Flue tubes should be cut to length TL in mm. Both inner and outer tubes should be cut flush with each
other, square and any burrs removed.
Where TL required is greater than 610 mm, (*850) then additional lengths (as appropriate) of 80/125 Concentric tube will be required to extend the vertical discharge wall terminal. A fall of 3˚ is required along the length of the flue towards the appliance.
installation of vertical discharge wall terminal with side outlet
170
W
ø80 PPS 90º Bend
ø80 Bird Mesh
ø80 PPS Tube
Exhaust Outlet Installed vertically Upwards on same wall aspect
Wall Bezel Plates
Required Length Cutting Line
measure from this point
TL (mm)
TL = W+262mm
side outlet
170
W
ø80 PPS 90º Bend
ø80 Bird Mesh
ø80 PPS Tube
Exhaust Outlet Installed vertically Upwards on same wall aspect
Wall Bezel Plates
Required Length Cutting Line
measure from this point
TL (mm)
TL = W+L1+260mm
Fig 14. Fig 15.
side outlet
rear outlet rear outlet
Fig 16.
Fig 17.
13.0 room sealed flue installations (contd)
Page 18
18
STRATA1
38 & 38/46 COMBI
method of assembly of extendible vertical discharge wall terminal assembly
See fig 18.
1. Lubricate male ends of concentric bend with silicone grease and locate bend into flue and air tube connection sockets on the top of the boiler and gently push fully home.
2. Slip flue tube and terminal assembly through prepared hole in the outside wall.
3. Locate internal wall bezel plate loosely onto air tube.
4. Lubricate male ends of concentric flue tubes and female sockets of flue bend lightly with silicone grease. Insert concentric tubes into bend and gently push fully home. Ensure flue gas discharge is positioned vertically upwards.
5. Made good internally and externally gap between air tube and prepared hole through wall.
6. Fit external 2 piece wall bezel and secure both internal and external wall bezels using fixings provided.
7. Seal air tube to exhaust discharge with a bead of silicone rubber mastic (mastic supplied) to create
weather seal to avoid entry of rain water into air tube.
8. Extend flue gas discharge to chosen position using 80 mm PPS flue tube fittings. Flue gas discharge must discharge on same face of building as air inlet to avoid wind caused imbalance in flue system.
1
7
6
2
4
3
Extend using 80ø
PPS tube
Flue discharge Vertically
upwards on same wall aspect
8
Fig 18.
13.0 room sealed flue installations (contd)
Page 19
19
STRATA1
38 & 38/46 COMBI
14.0 examples of calculating
flue pressure loss
example 1
A Strata 1-38/46 combination boiler is proposed to be installed with a room sealed concentric flue taking an all horizontal route to a wall terminal that has the flue gas duct extended to a more acceptable termination position to avoid a potential visual nuisance problem with flue gas pluming.
Flue system comprises: 3 x 90° concentric bends 8 metres concentric flue tube 3 x 80mm 90° flue gas elbows 3 metres 80mm flue gas tube Concentric wall terminal
Resistance = 1 x 80/125 concentric wall terminal @ 5.0 Pa = 5.0 3 x 80/125 90° concentric bends @ 4.0 Pa = 12.0 8 x 1m lengths 80/125 concentric tube @ 4.0 Pa = 32.0 3 x 90° DN80 bends @ 2.5 Pa = 7.5 3 x 1m lengths DN80 PPS tube @ 2.5 Pa = 7.5 1 x DN80 open termination with mesh @ 2.5 Pa = 2.5
Total Resistance = 66.5 Pa
conclusion: Total resistance is less than 100 Pa therefore there will be no effect on boiler output. System may be installed as proposed.
example 2
A Strata 1-38/46 combination boiler is proposed to be installed with a room sealed concentric flue taking a part horizontal (6m) and part vertical (10m) route to a vertical concentric roof terminal set. The flue system includes 3 Nr 90° concentric bends and is installed to run within the building.
Resistance = 3 x 80/125 90° concentric bends @ 4.0 Pa = 12.0 16 x 1m lengths 80/125 concentric tube @ 4.0 Pa = 64.0 1 x 80/125 concentric roof terminal with cap @ 7.5 Pa = 7.5
Total Resistance = 83.5 Pa
There is 10 m of vertical flue which will create an updraught of 33 Pa. Therefore final operating resistance = 83.5 - 33 = 50.5 Pa.
conclusion: Total resistance is less than 100 Pa therefore there will be no effect on boiler output. System may be installed as proposed.
0
29
31
33
35
37
39
41
50 100 200150 250 300 350 400 450 500
Strata 1 - 38. 38/46 Combi
effect of flue
system resistance
on boiler output
Boiler Output kW at: Flow 80°C Return 60°C
Flue System Resistance - Pa
0 2 6 10 14 18 22 26 30 34 38
0
10
30
50
70
90
110
130
20
40
60
80
100
120
140
48 1612 20 24 28 32 36 40
thermal updraught when
flue gas temp 80°C and
outside temp -5°C
Draught - Pa
Vertical Flue Lengths - metres
A = Insulated or within the building B = Uninsulated and exterior to the building
A
B
Page 20
20
STRATA1
38 & 38/46 COMBI
14.1 calculating
flue resistance
If a flue terminal is positioned within 2 m above ground level or any upper part of a building where
people have general access (e.g. balcony etc) then the terminal should be fitted with an appropriate guard.
The flue terminal of a Strata 1 boiler will plume heavily and care must be taken when selecting a
terminal position to ensure that a "nuisance situation" is not created.
15.0 flue
terminal positions
flue terminal positions
H,I
J
N
A
G
F D
E
A
Q
P
G
N
B,C
F
F
L
K
L
K
N
M
7.5
7.5
11.25
5.5
5.5
2.75
5.0
5.0
2.5
7.0
2.0
2.0
1.0
4.0
2.0
3.5
4.0
4.0
2.0
Component.
80/125 Concentric Wall Terminal 80/125 Concentric Roof Terminal
Without Rain Cap 80/125 Concentric Roof Terminal
With Rain Cap 1m Length 80/125 Concentric Tube 93° 80/125 Concentric Bend 45° 80/125 Concentric Bend 1m Length DN 80 PPS Flue Tube (Fluegas) 93° DN 80 PPS Flue Bend (Fluegas) 45° DN 80 PPS Flue Bend (Fluegas) Room Sealed Chimney Cap 1m Length DN 100 PPS Flue Tube 93° DN 100 PPS Flue Bend (Fluegas) 45° DN 100 PPS Flue Bend (Fluegas) DN 80 Open Termination with Mesh DN 100 Open Termination with Mesh 80/125 Concentric to 2 x 80 Tubes Adaptor 1m length DN80 PPS Tube (Air) 93° DN 80 PPS Bend (Air) 45° DN 80 PPS Bend (Air)
The excess pressure available for overcoming the
frictional resistance of a flue system is 100 Pa.
The adjacent table of flue component resistances will assist the designer in calculating total flue system frictional loss.
If the total installed flue system resistance exceeds 100 Pa, then the result will be a reduction in boiler output. Reference to the Effect of Flue System Resistance On Boiler Output, graphs will assist. If the resistance of a proposed flue system has an unacceptable effect on boiler output, then a larger diameter flue tube should be selected.
Thermal up-draught is generated in a vertical flue system, reducing the resistance of the system. Reference to the Thermal Updraught Graph will provide a figure in Pa, which may be deducted from the total calculated flue system resistance.
NOTE: Does not apply to horizontal sections of a flue system.
Resistance Pa Strata 38 38/46
Fig 19.
Page 21
21
STRATA1
38 & 38/46 COMBI
minimum dimensions of flue terminal positions
See fig 19.
Dimension Terminal Balanced flue Non room
position room sealed sealed
A Directly below an opening, air 300mm 300mm
brick, windows etc. Not recommended.
B Below gutters, soil pipes or 75mm 75mm
drain pipes.
C Below eaves. 200mm 200mm
D Below balconies or car port 200mm 200mm
roof. Not recommended.
E From a vertical drain pipe or 150mm 150mm
soil pipe.
F From an internal or 300mm 200mm
external corner.
G Above ground, intersecting 300mm 300mm
roof or balcony level.
H From a surface facing 2000mm 2000mm
the terminal.
I From a terminal facing 2000mm 2000mm
the terminal.
J From an opening in the car port 1200mm 1200mm
(e.g. door, window) into dwelling.
K Vertically from a terminal on the 1500mm 1500mm
same wall.
L Horizontally from a terminal on 300mm 300mm
the same wall.
M From a vertical structure on 500mm N/A
the roof.
N Above intersection with roof. 500mm 150mm
P Directly above an opening, air brick, 300mm 300mm
window etc.
Q Horizontally to an opening, air brick, 500mm 500mm
window etc.
15.0 flue terminal positions (contd)
but installation not recommended.
but installation not recommended.
but installation not recommended.
but installation not recommended.
but installation not recommended.
but installation not recommended.
Page 22
22
STRATA1
38 & 38/46 COMBI
16.0 ventilation requirements
single appliances
Table 1 Room installation - non room sealed flue.
Natural ventilation direct to outside air.
Ventilation openings free area cm
2
220
Table 2 Room Installation - Non Room Sealed Flue
Natural ventilation from adjacent room which is directly ventilated to outside air.
Ventilation openings free area cm
2
220
With adjacent room similarly ventilated direct to outside air
Table 3 Room Installation - Room Sealed Flue
There are no specific requirements for a room to be ventilated where the appliance is room sealed. However, consideration should be given to providing ventilation for general cooling,
Table 4 Compartment Installation - Non room sealed flue
Natural Ventilation Direct to outside air
Ventilation openings free area cm
2
High Level Low Level
230 460
Table 5 Compartment Installation - Non room sealed flue
Natural Ventilation from Adjacent room
Ventilation openings free area cm
2
High Level Low Level
460 920
With adjacent room having a ventilation opening of not less than 220cm
2
direct to outside air.
The room or space in which the Strata 1 boiler is installed may require to be ventilated in accordance with BS5440: Part 2: 2000, or BS6644:1991 as a appropriate.
The following tables must be read to ascertain the amount of ventilation required for the installation of a single appliance and has been calculated from BS 5440: Part 2: 2000.
Page 23
23
STRATA1
38 & 38/46 COMBI
16.0 ventilation requirements (contd)
Table 6 Compartment Installation - Room sealed flue
Natural Ventilation direct to outside air
Ventilation openings free area cm
2
High Level Low Level
230 230
Table 7 Compartment Installation - Room Sealed Flue
Natural Ventilation from Adjacent Room
Ventilation openings free area cm
2
High Level Low Level
460 460
Multiple Appliances Installed in the Same Room or Space
Where multiple Strata 1 boilers are installed in the same room or space then the aggregate of the appliance inputs must be taken to determine (from the following data) the amount of ventilation required.
Appliance Gross Heat Inputs Should be taken as:-
51.1kW
Table 8 Non Room Sealed Flue Installations
Natural Ventilation Direct to Outside Air.
Low Level (Inlet): 540cm2 plus 4.5cm
2
per kW in excess of 60kW total rated input.
High Level (Outlet): 270cm2 plus 2.25cm
2
per kW in excess of 60kW total rated input.
Table 9 Room Sealed Flue Installations
Natural Ventilation Direct to Outside Air (Ventilation recommended for cooling purposes)
Low Level (Inlet): 4.5cm
2
per kW of total rated input.
High Level (Outlet): 4.5cm
2
per kW of total rated input.
Page 24
24
STRATA1
38 & 38/46 COMBI
17.0 hydraulic system
design
The Strata 1 boiler can be operated to serve a heating load in a number of ways:
1. Constant flow temperature, with the option to set either high temperature (85°C), medium temperature (70°C) or low temperature (55°C).
2. Direct-on-boiler weather compensated flow temperatures, with adjustable maximum flow temperature.
3. Underfloor heating coils via a VT mixing valve with a maximum flow temperature of 55°C plus a second circuit (eg. radiators) operating with direct-on-boiler weather compensated temperatures.
Flow to return drop (∆t). The microprocessor controls monitor return temperature and the facility to operate at a set t (by pump speed modulation) is a standard and most important feature and will, where possible, maintain the t across the boiler at 20°C, as the lower the return temperature, the higher the operating efficiency. HT and MT systems should be designed for t 20°C and LT (underfloor coils via a mixing valve) systems t 10°C. Designing for a t 20°C gives the added cost saving advantage of smaller pipe sizes and pumps.
The Strata 1 includes an in built primary pump with a residual head pressure as listed below.
Appliances may be installed as single units or in multiples.
Single units may or may not require additional system pumps which will be dictated by the system
configuration and by the index resistance.
Multiple units (and single units which require additional pumps), must always be installed with a low loss mixing header or similar arrangement. - see table below.
The Strata 1/38 boiler has in built domestic hot water (remote stored) temperature control ability, and if required, the in built pumps may be used to provide the primary flow to a nearby indirect cylinder or calorifier with the boiler controlling a diverter valve in the main flow or return pipework.
Provision within the system design must allow for: Low water pressure cut off device and water pressure gauge.
Boiler Power kW
Up to 38
76 114 152
Design t 20°C
40mm 50mm 65mm 65mm
low velocity
mixing header
diameter sizing guide
Tube diameters refer to steel pipe and calculated using data from
CIBSE Guide C4
The following system schematics show a number of typical installation types to which the Strata 1 boiler
may be connected.
The Strata 1 is not limited to just the systems shown, and may be used in conjunction with many
commercially available control items.
For further advice or guidance on schematic designs or control options contact MHS Boilers Ltd.
Boiler Model
Strata 1/38
Strata 1/38-46 Combi
Pressure Metres wc
3.3
2.4
Boiler Model
Strata 1/38
Strata 1/38-46 Combi
Pressure Metres wc
1.0
1.0
in-built boiler pumps
approx residual head
pressure at max speed
in-built boiler pumps
approx residual head
pressure at min speed
Page 25
25
STRATA1
38 & 38/46 COMBI
OS = Outside air temperature sensor,
used where direct-on-boiler weather compensated flow temperatures are required.
C = Room Controls, either RE2132
modulating room unit from MHS Boilers or a room thermostat.
PS = Low water pressure cut off switch.
system type 1
Typical single Strata 1 boiler installation serving heating only where the boiler's own in­built circulating pump is used to circulate the water around the system (used only where system index resistance < pump residual head - see page 24). Flow temperature may be fixed/constant or weather variable.
17.0 hydraulic system design (contd)
Waste
Condense
DOC
Expansion
Vessel
CWM
OS
Strata 1- 38 Boiler
or
Strata 1- 38/46 Combi
C
PS
LSV
IV
SV
IV
Strainer
IV
Heating Load
Filling Point
IV
DOC
DOC
Page 26
26
STRATA1
38 & 38/46 COMBI
OS = Outside air temperature sensor,
used where direct-on-boiler weather compensated flow temperatures are required.
C = Room controls, either RE2132
modulating room unit from MHS Boilers or a room thermostat.
S/T = Hot water temperature controls,
either:- S, an HWS temperature sensor from MHS Boilers or “T”, a cylinder thermostat.
PS = Low water pressure cut off switch.
Divertor valve must be so installed to spring return to heating.
Divertor valve will require SPDT relay if not spring return.
system type 2
Typical single Strata 1 boiler installation serving domestic hot water (not Combi) and heating where hot water has priority via a divertor valve. The in-built circulating pump within the boiler is used to circulate the system (used only where system index resistance < pump residual head - see page 24). Flow temperature to hot water is constant and flow temperature to heating may be constant or weather variable.
17.0 hydraulic system design (contd)
Waste
Condense
Calorifier/Indirect
Hot Water Cylinder
S
T
Strata 1- 38 Boiler
OS
DOC
IV
Expansion
Vessel
DOC
PS
IV
C
IV
Strainer
IV
SV
Heating Load
LSV
DOC
Divertor
Valve
IV
IV
IV
Filling
Point
IV
DOC
CWM
Page 27
27
STRATA1
38 & 38/46 COMBI
OS = Outside air temperature sensor.
Used where direct-on-boiler weather compensated flow temperatures are required.
C = Room controls, either RE2132
modulating room unit from MHS Boilers or a room thermostat.
PS = Low water pressure cut off switch.
System pump to be no greater than 2 amps
system type 3
Typical Single Strata 1 boiler installation serving heating only and using a low velocity mixing header where system index resistance exceeds in-built boiler pump residual head ­see page 24. Flow temperature may be fixed/constant or weather variable.
17.0 hydraulic system design (contd)
Waste
Condense
Expansion
Vessel
DOC
Point
Filling
CWM
OS
Strata 1- 38 Boiler
or
Strata 1- 38/46 Combi
C
LSV
PS
Strainer
IV
IV
SV
AAV
IV
DOC
Vertical
Low Velocity
2A Max.
Heating Pump
IV
Mixing Header
Max Velocity 0.5m/s
DOC
IV
Strainer
IV
Heating Load
DOC
Page 28
28
STRATA1
38 & 38/46 COMBI
OS = Outside air temperature sensor. Used where
direct-on-boiler weather compensated flow temperatures are required.
C = Room controls, either RE2132 modulating room
unit from MHS Boilers or a room thermostat.
S/T = Hot water temperature controls, either: “S”, an
HWS temperature sensor from MHS Boilers or T, a cylinder thermostat.
PS = Low water pressure cut off switch.
Divertor valve must be so installed to spring return to heating.
Divertor valve will require SPDT relay if not spring return.
System pump to be no greater than 2 amps.
system type 4
Typical Single Strata 1 boiler installation serving heating & domestic hot water (not Combi). Hot water is priority and is served via a divertor valve and the boiler's in built circulating pump where index loss through HWS primaries is less than boiler pump residual head*. Heating circuit index loss exceeds boiler pump residual head* and is served via a low velocity mixing header and a separate pump. Heating flow temperature may be fixed/constant or weather variable.
* See page 24
17.0 hydraulic system design (contd)
Waste
Condense
Calorifier/Indirect
Hot Water Cylinder
S
T
Strata 1- 38 Boiler
OS
C
PS
Strainer
IV
SV
Heating Load
Divertor
AAV
IV
IV
Valve
Expansion
Vessel
DOC
LSV
DOC
IV
Vertical
Low Velocity
2A Max.
Heating Pump
IV
IV
IVIV
Mixing Header
Strainer
Max Velocity 0.5m/s
DOC
DOC
DOC
CWM
Filling
Point
Page 29
29
STRATA1
38 & 38/46 COMBI
OS = Outside air temperature sensor.
Used where direct-on-boiler weather compensated flow temperatures are required.
C = Room controls, either RE2132
modulating room unit from MHS Boilers or a room thermostat.
S/T = Hot water temperature controls,
either S, an HWS sensor from MHS Boilers or “T”, a cylinder thermostat.
PS = Low water pressure cut off switch.
System pumps to be no greater than 2 amps
system type 5
Typical Single Strata 1 boiler installation serving heating & domestic hot water (not Combi) with hot water priority. Hot water & heating circuits both have index resistance exceeding boiler pump residual head* & are served by independent pumps from a low velocity mixing header. Heating flow temperature may be fixed/constant or weather variable.
* See page 24
17.0 hydraulic system design (contd)
Expansion
DOC
Condense Waste
Vessel
Filling Point
OS
C
Strata 1-38Boiler
Strainer
2 A Max.
IV
LSV
NRV
IV
DOC
Vertical Low Velocity
Mixing Header
Max Velocity
0.5 m/s
NRV
IV
HWS Primary
Pump 2 A Max.
S
T
DOC
IV
Strainer
IV
DOC
PS
IV
SV
AAV
Heating Pump
Heating Load
Calorifier/Indirect
Hotwater Cylinder
DOC CWM
Page 30
30
STRATA1
38 & 38/46 COMBI
system type 6
Typical Single Strata 1 boiler installation serving domestic hotwater (not Combi) and radiator heating zone and an underfloor coil zone all via a low velocity mixing header. The HWS will always have priority. The 2Nr heating zones may operate independently via 2 Nr separate room units. The 2 Nr heating zones will always be weather compensated but may have differing compensation slopes.
17.0 hydraulic system design (contd)
OS = Outside air temperature sensor. Provides outside air temperature reference for both heating zones.
MRO3 =Pumps and mixer regulation control box from MHS Boilers provides pump control for both heating zones i.e.
auto operation, frost protection and summer stand still protection running. Provides drive for underfloor coil zone VT mixing valve with max flow temperature limitation set at 55ºC. Includes controls for compensation of under floor coils. Max pump motor loads 2A.
RC1 = RE2132 modulating room unit from MHS Boilers provides Time & Temperature control for radiator heating zone.
RC2 = As RC1 but for underfloor coil zone. Only to be used when RCI is used.
VS = Underfloor zone VT flow sensor (supplied with MR03).
S/T = Hot water temperature controls, either “S”, an HWS temperature sensor from MHS Boilers or “T”,
a cylinder thermostat.
PS = Low water pressure cut off switch.
* Not applicable to Strata 1 - 38/46 Combi
*
S/T
*
Calorifier or
T
Radiator Zone
Indirect Cylinder*
DOC
DOC
OS
1
RC
A Max.
Radiator
Zone Pump 1
AAV
Combi
Boiler or
Strata 1-38
Strata 1-38/46
HWS Primary
Pump* 2 A Max.
NRV
NRV
SV
Under Floor Zone
VT Pump
VS
U/Floor VT 1 A Max.
Vertical
NRV
MRO3
PS
IV
Waste
Condense
RC
Mixing Valve
Low Velocity
Mixing Header
V Max 0.5m/s
2
Strainer
DOC
IV
LSV
Under Floor
Coils Zone t 10ºc
DOC
DOC
Vessel
Expansion
IV
Strainer
IV
IV
DOC
Point
Filling
CWM
Page 31
31
STRATA1
38 & 38/46 COMBI
OS = Outside air temperature sensor,
used where direct-on-boiler weather compensated flow temperatures are required.
C = Room temperature controls e.g.
RE2132 modulating room unit from MHS Boilers, or, separate time clock & room thermostat.
FS = Flow temperature sensor
RS = Return temperature sensor
S = Hot water temperature sensor or
thermostat
KKM2 = Modulating Kaskade Manager. Up
to 9Nr boilers may be controlled using 2Nr linked KKm2's.
PS = Low water pressure cut off switch.
* Not applicable to Strata 1 - 38/46 Combi
1* = Filling point. In accordance with BS
6644, automatic pressurisation unit must be installed when the boilers input is greater than 60kW.
system type 7
Typical Multiple Strata 1 installation. Boilers controlled by modulating Kaskade manager which also has the facility to control heating & domestic hot water production. Heating flow temperature may be fixed/constant or weather variable. Hot water has priority.
17.0 hydraulic system design (contd)
DOC
C
OS
KKM 2
Heating Load
NRV
AAV
Heating Pump
2A. Max
NRV
Strata 1
Strata 1
HWS Primary
Pump
FS
Boiler
Boiler
*
2A. Max
DOC
SV
DOC
SV
DOC
Hot Water
Calorifier or
Indirect Cylinder
Low Velocity
Mixing Header
Max Velocity 0.5m/s
NRV
NRV
NRV
*
*
S
DOC
Expansion
LSV
DOC
Filling
Vessel
Point
CWM
Strainer
IV
IV IV
RS
Strainer
IVIV
PS
1*
IVIV
IVIV
Boiler
Strata 1
SV
Waste
Condense
Page 32
32
STRATA1
38 & 38/46 COMBI
typical schematic arrangement where
system has multiple pumps that will
operate at the same time
WC = Wiring Centre/Junction Box
RS = Room Thermostat
CS = Cylinder Thermostat
PS = Low water pressure cut off switch.
OS = Outside Air Sensor, install when
weather compensated heating flow temperatures are required
system type 8
Typical Single Strata 1 boiler installation serving heating and domestic hotwater via a system pump and 2Nr 2Port motorised valves with conventional controls i.e. programmer, room stat & cylinder stat.
17.0 hydraulic system design (contd)
RS
Heating Load
CH
M/Valve
HW
M/Valve
System Pump
CS
Reg Valve
Indirect Cylinder/Calorifier
IVIV
Strainer
OS
WC
AAV
PS
SV
Condense
Waste
Flow Header
AAV
LSV
DOC
DOC
IV
Vertical Low Velocity
IV
Strainer
Expansion
Vessel
Mixing Header
Max Velocity
0.5 m/s
DOC
IV
DOC
Filling Point
CWM
Boiler/s
Circuit Pumps That Can/Will Run At The Same Time
Low Velocity Mixing Header
Max Velocity 0.5m/s
Page 33
33
STRATA1
38 & 38/46 COMBI
17.2 water treatment
system cleaning
The entire primary system must be thoroughly cleansed and flushed to remove debris, flux residues etc before opening the boiler isolation valves & flooding the boiler. Particular care must be taken where the Strata boiler is being retro-fitted into an old/existing system, as system silt or magenite can be very damaging to the new boiler.
Following cleansing and flushing the system must be dosed with a good quality water treatment to prevent corrosion and the formation of scale. Failure to observe these requirements will render the guarantee on the product void. Cleansing, flushing and water treatment must be carried out in accordance with the requirements of BS 7593:1992 prior to commissioning the unit.
Repeated draining and refilling of the system must be avoided as this is very damaging to the boiler. The boiler must not be operated without the system water being correctly and adequately dosed with an appropriate corrosion inhibitor.
For specific guidance on water treatment, direct contact is advisable with:-
Betz Dearborn Limited Fernox Widnes Tandem House Cheshire Marlowe Way, Croydon WA8 8UD Surrey CR0 4XS Telephone: 0151 495 1861 Telephone: 0208 665 6666
For Category 4 systems, the approved method of filling must comprise of the following components in the arrangement shown;
Control Valve
Strainer
Verifiable Backflow Device with
Reduced Pressure Zone (RPZ Valve).
Incorporating a 'Type BA' air gap.
Tundish
Control Valve
Further more, in accordance with BS6644, for boiler/s with an input greater than 60kW, an automatic pressurisation unit must be installed to automatically replenish any lost or evpourated water.
The pressurisation unit must comprise of the following components;
A Cistern fitted with a Float Operated Valve incorporating either a 'Type AG' (C-3), or 'Type AF' (C-4)
air gap.
A Presssure Booster Pump fitted with a Single Check Valve
A Pressure Reducing Valve
A Pressure Switch
For information on a comprehensive range of pressurisation units please contact MHS Sales.
17.1 filling the system
The initial filling of a sealed heating system, and subsequent refilling, must be by a method that has been approved by the Water Regulation Advisory Scheme (WRAS) for that type of heating system. ie. Domestic (In-house) Fluid Category 3 (C-3). Non Domestic (Other than In-House) Fluid Category 4 (C-4).
For Category 3 systems, the approved method of filling must comprise of the following components in the arrangement shown;
Control Valve incorporating a Double Check
Valve on the mains cold water pipework.
Temporary Connecting hose, which must
be disconnected after use.
Control Valve, on the heating system.
MCWS
CV
DCV HOSE
CV
Heating System
MCWS
CV CV
Strainer
Heating System
Tundish
RPZ
Page 34
34
STRATA1
38 & 38/46 COMBI
17.4 hydraulic system design
domestic hot water - Combi
typical hot/cold water installation using Strata 1-38/46 combination boiler
typical multiple Strata 1-38/46 combination boiler
domestic hot water installation
DOC
DOC
To Hot Water
Draw Off Points
To Cold Water
Draw Off Points
To Hot Water
Draw Off Points
To Cold Water
Draw Off Points
Stop
Valve
To Heating System
Fill Point
BS1010
Stop Valve
BS1010
Stop Valve
Incoming Cold Water Main
Important Note:
1. From the incoming cold water main to the cold inlet connection on the boiler there must be no non return valves or loose jumper type valves.
2. Under no circumstances must there be installed a secondary return circulation arrangement.
Important Note:
Cold water feed and hot water flow out connections must be reverse return as shown. See also notes 1 and 2 above.
DOC
Stop Valve
Stop Valve
DOC
DOC
CWM
Strata 38/46
Strata 38/46Strata 38/46
17.5 Combi boiler - prevention of scale
in water to water heat exchanger
In hard water supply areas, it is highly recommended to install a suitable proprietary in-line scale reducing device into the cold supply pipe serving the Strata 1/38-46 combi boiler. The scale reducing device should be installed in accordance with the instructions supplied with the device.
17.3 care with the use of
soldering flux
The Strata 1 boiler has a primary heat exchanger fabricated from 316L stainless steel. It is most important that the compatibility of any flux is checked with the flux supplier before use, and that any flux manufacturers recommendations are strictly followed with regards to use in conjunction with stainless steel.
IV
IV IV
Page 35
35
STRATA1
38 & 38/46 COMBI
17.6 Combi boiler hot water
system pipework pressure drop
guidance on hot water pipework pressure drop
25m 20m
15m 10m
5m
Domestic Hot Water Flow Rate Litres/minute
Flow Rate - Pressure Drop - Distance Chart For Installation Utilising all 15mm Copper Tube
Approximate Pressure Drop - bar
For every 90° change in direction allow 1m
Total length of pipe, from incoming cold water main to appliance and from appliance to hot water draw off point
}
Domestic hot water temperature rise 50°C
Domestic hot water temperature rise 35°C
25m 20m 15m 10m 5m
Domestic Hot Water Flow Rate Litres/minute
Flow Rate - Pressure Drop - Distance Chart For Installation Utilising all 22mm Copper Tube
Approximate Pressure Drop - bar
For every 90° change in direction allow 1m
Total length of pipe, from incoming cold water main to appliance and from appliance to hot water draw off point
}
Domestic hot water temperature rise 50°C
Domestic hot water temperature rise 35°C
Example:
A wash hand basin is to be served and the length of pipe involved is 20m. The entire installation is in 15mm copper tube and reference to the graph right shows that the pressure drop when delivering water at a temperature rise of 35°C (hand hot) will be 1.5 bar.
Ensure adequate working water pressure and flow rate availability.
Consider that not only is water volume required for instantaneous production of hot water, but cold
water most likely will be required simultaneously ie: shower blending, hot and cold taps running together, toilet flushing etc.
Consider that as an absolute minimum the cold water main must be capable of supplying 18
litres/minute into the property. The required working water pressure will be dependent on the length of run to the draw off, the pipe size and any resistance at the drawoff (resistance of mixer taps, blenders etc). Reference to the flow rate/pressure drop charts will give guidance with regards to the hot water installation pipework (the resistance of the boilers water to water heat exchanger is included in the pressure drops indicated). The additional working water pressure required for simultaneous cold water flow can be calculated by reference to CIBSE Guide C4.
17.7 Combi boiler - domestic hot water
system design considerations
3.0
2.5
2.0
1.5
1.0
0.5
0
10
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
12 14 16 18 20
12 14 16 18 20
10
Page 36
36
STRATA1
38 & 38/46 COMBI
18.0 electrical
connections
The electrical connections to the Strata 1 boiler are made via a plug/socket arrangement (mains) and labelled terminal rails which are located within the boiler case and to the left of the gas valve assembly. Connections must only be made using appropriate diameter multi strand flex cables and cable entry must only be via the rubber glanded cable entry points located at the bottom rear l/h side of the appliance. If the boiler is to be room sealed flued then care must be taken to ensure the cable entries are reasonably air tight. For electrical connection rail detail see fig 20.
The low voltage rail is mounted in front of the mains voltage rail. To access the mains voltage rail, pull the quick release pins located diagonally either side of the low voltage rail.
RE2132
X 42
= Cylinder Thermostat or HWS Temperature Sensor (Not Combi)
Low Voltage Connection Rail
= Outside Air Temperature
= RE 2132 Modulating Room Unit
= Has No Function
= Earth Connection Rail
= External Gas Safety Shut Off Valve - LPG Only. Or External Central Heating Pump - Install LINK As Shown.
= Room Thermostat / MRO3 Mixer Control
= HWS Primary Pump or Divertor Valve
RE2132
24V dc
T
T
T
T
+
+
+
+
+
+
12 3 4R1R2R3 5 6
X 42
Mains Voltage Connection Rail
230 VAc - 50 Hz
-230V
LINK
Plug/Socket Supply 230V
L1 PE N
L1 N L1
N
L2 L1 N
Fig 20.
17.7 system design considerations (contd)
Be generous with pipe sizing to keep pressure loss to a minimum.
Consider that water will always take the least line of resistance and will take preference to an opened
drawoff closest to the boiler whilst perhaps ignoring/starving a simultaneous draw off further away
from the appliance.
Consider installing flow restrictors into both hot and cold water draw off points to ensure reasonable
distribution of water around the building at times of multipoint draw off.
Cable Entry Glands
Page 37
STRATA1
38 & 38/46 COMBI
37
18.0 electrical connections (contd)
plan of internal electrical connections
J6
J5
PE
230 VAC
FUSE 24V
FURIMAT 762
X8
456
123
X7
X6
F
X4 X5
1
2
3
6
5
4
HSP TOP
4
5
6
4
6
16
16
PE
14
253
PE
N
L
PE
4
3
L
N
3
L
N
1
3
1
8
PE
7
6
12
ALARM CONTACT
K13
K20 K20
K17 K19
K12 K18
K8
K8
K9
K9
K3
K2
K14
2
1
X9
2
PE
3
41
L
N
L
PE
N
X51
51
B
S
X47
B
S
X19
B
S
X18
B
S
X17
2 (X)
FUSE
X30 X31 X31
+SO PW-
Fan
STBA
STBW
EL
1
B
S
B
S
X29
B
X28
B
X27
B
S
B
S
X26
Fan 24 VDC
Limit Thermostat
Fluegas
Limit Thermostat 1
M-T M-T
Water
Pump
Transformer
S
S
PE
Ignition/
Ionisation
IO
Boiler
Three way Valve
(Combi Only)
Gas Valve
B
-+
B
S
B
S
X22
X41
Supply
1
PE
4
X25
S
2
1
3
2
5
6
7
X23
230V AC
N
N
PE
PE
L
L
B
S
PE
Mains Voltage Rail
N
HWS Primary Pump/Divertor Valve (L1+L2)+PE
L1 L2
N
L1
N
L1
Room Thermostat (L1+L2)+PE
MRO3 (L1+N)+PE
+++
KO = White K2 = Brown K3 = Green K4 = Gray K5 = Orange K6 = Blue K7 = Red K8 = Black K9 = Violet K12 = Yellow/White K13 = Braun/White K14 = Green/White K17 = Blue/White K18 = Red/White K19 = Black/White K20 = Violet/White
External LPG Solenoid Valve (L1+N) + PE
or Heating Pump
X16
1
6
Low Voltage Rail
MRO3
MIXER
5
10
11
1
X2 X3
20
10
4
1
X1
RS232
3
2
K3
K7
K0 K6
K8
B
K4
K0
K0 1
K7 K7
K6 K6
K5
K5
SSS
X13
STE
212 12 12 12 12
1
BTE
K7
RTE
VTE
B
S
X14
B
S
X12
B
S
X10
Cold Water Inlet Temperature
S5
Sensor (Combi only)
Instantaneous H.W. Flow
S3
Temperature Sensor (Combi only)
Return Temperature Sensor
S4
Flow Temperature Sensor
S1
R3
R2
R1
4
3
2
No Function
RE2132
T
T
Room Unit (R1+R2+R3)
Outside Air Temperature Sensor (3+4)
Cylinder Thermostat or
Hot Water Temperature Sensor (1+2)
Page 38
38
STRATA1
38 & 38/46 COMBI
18.0 electrical connections (contd)
typical electrical connection schematic
to suit system type 1
Once all controls are installed please refer to page 57/58 to ensure the correct function number is programed into the control panel.
N
PE
Weiland
Plug/Socket
L1
Earth Rail
Low Pressure Switch
break on Pressure Fall
Supply 230V 3A
+
+
230V ac - 50 Hz
+
RE2132
24V dc
T
Room Thermostat volt free enable
L1 N L1 N L2 L1 N
QAW 44 Optional Remote Sensor
Has No Function
+24V
PWM
GND
51 34
2
RE2132 Modulating Room Unit
Install only if direct-on-boiler weather compensated
flow temperature is required.
Install only one method of room temperature control.
If a modulating room unit is required, then do not
install also a room thermostat and vice versa.
2
OS
1
234R1R2R356
T
1
Outside Air Sensor
Page 39
STRATA1
38 & 38/46 COMBI
39
18.0 electrical connections (contd)
typical electrical connection schematic
to suit system type 2 (not Combi)
Once all controls are installed please refer to page 57/58 to ensure the correct function number is programed into the control panel.
N
Supply 230V 3A
Weiland
Plug/Socket
PE
L1
Earth Rail
Divertor Valve
Motor Open/ Motor Shut Type
Close
Earth Rail
+
+
230V ac - 50 Hz
+
Low Pressure Switch
break on Pressure Fall
Divertor Valve
Spring Return
Type
Room
Thermostat
L1 N L1 N L2 L1 N
Has No
Function
+
+
230V ac - 50 Hz
+
L1 N L1 N L2 L1 N
QAW 44 Optional Remote Sensor
O
p
e
n
SPDT Relay
Alternative arrangement
to Spring Return HWS
primary Divertor Valve
using motor open, motor
shut type valve.
24V dc
RE2132
T
T
234R1R2R356
1
+24V
PWM
GND
HWS Sensor
51 34
2
RE2132 Modulating Room Unit
Cylinder Stat
Install only if direct-on-boiler weather compensated
flow temperature is required.
Install only one method of room temperature control.
If a modulating room unit is required, then do not
install also a room thermostat and vice versa.
Install only one method of HWS temperature control.
2
OS
1
(not Combi)
Outside Air Sensor
Page 40
40
STRATA1
38 & 38/46 COMBI
18.0 electrical connections (contd)
typical electrical connection schematic
to suit system type 3
Once all controls are installed please refer to page 57/58 to ensure the correct function number is programed into the control panel.
N
Supply 230V 3A
break on Pressure Fall
Weiland
Earth Rail
PE
Plug/Socket
L1
Low Pressure Switch
+
+
230V ac - 50 Hz
+
RE2132
24V dc
T
Room Thermostat
Link
Heating
+24V
GND
Pump 2A Max
51 34
2
L1 N L1 N L2 L1 N
Has No Function
PWM
volt free enable
QAW 44 Optional Remote Sensor
RE2132 Modulating Room Unit
Install only if direct-on-boiler weather compensated
flow temperature is required.
Install only one method of room temperature control.
If a modulating room unit is required, then do not
install also a room thermostat and vice versa.
2
OS
1
234R1R2R356
T
1
Outside Air Sensor
Page 41
41
STRATA1
38 & 38/46 COMBI
18.0 electrical connections (contd)
typical electrical connection schematic
to suit system type 4 (not Combi)
Once all controls are installed please refer to page 57/58 to ensure the correct function number is programed into the control panel.
N
Supply 230V 3A
Earth Rail
Weiland
Plug/Socket
PE
L1
Divertor Valve
Motor Open/ Motor Shut Type
Close
Earth Rail
+
+
230V ac - 50 Hz
+
Low Pressure Switch
break on Pressure Fall
Divertor Valve
Spring Return
Type
Room
Thermostat
L1 N L1 N L2 L1 N
Has No Function
+
+
230V ac - 50 Hz
+
L1 N L1 N L2 L1 N
QAW 44 Optional Remote Sensor
Open
SPDT Relay
Alternative arrangement
to Spring Return HWS
primary Divertor Valve
using motor open, motor
shut type valve.
Install only if direct-on-boiler weather compensated
flow temperature is required.
Install only one method of room temperature control.
If a modulating room unit is required, then do not
install also a room thermostat and vice versa.
Install only one method of HWS temperature control.
(not Combi)
The 3 way valve must be installed to spring return to
open the heating circuit.
24V dc
RE2132
T
T
234R1R2R356
1
+24V
PWM
GND
HWS Sensor
51 34
2
RE2132 Modulating Room Unit
Cylinder Stat
2
OS
1
Outside Air Sensor
Page 42
42
STRATA1
38 & 38/46 COMBI
18.0 electrical connections (contd)
typical electrical connection schematic
to suit system type 5 (not Combi)
Once all controls are installed please refer to page 57/58 to ensure the correct function number is programed into the control panel.
N
PE
Weiland
Plug/Socket
L1
Earth Rail
Low Pressure Switch
break on Pressure Fall
Supply 230V 3A
+
+
230V ac - 50 Hz
+
RE2132
24V dc
T
HWS Primary Pump 2A Max
Room Thermostat
Link
Heating
L1 N L1 N L2 L1 N
Has No Function
+24V
PWM
GND
Pump 2A Max
QAW 44 Optional Remote Sensor
51 34
2
RE2132 Modulating Room Unit
volt free enable
2
1
Install only if direct-on-boiler weather compensated
flow temperature is required.
Install only one method of room temperature control.
If a modulating room unit is required, then do not
install also a room thermostat and vice versa.
Install only one method of HWS temperature control.
OS
234R1R2R356
T
1
HWS Sensor
Cylinder Stat
Outside Air Sensor
Page 43
43
STRATA1
38 & 38/46 COMBI
18.0 electrical connections (contd)
typical electrical connection schematic
to suit system type 6
Once all controls are installed please refer to page 57/58 to ensure the correct function number is programed into the control panel.
N
Supply 230V 3A
L
PE
N
Rad Zone
Pump 1A max
Weiland
Earth Rail
PE
Plug/Socket
L1
Low Pressure Switch
break on Pressure Fall
Pump #2
Underfloor Zone
VT Pump
1A Max. Pump #3
N
PE L
Underfloor Zone
VT Mixing Valve
NPEL2
L1
+
+
230V ac - 50 Hz
+
RE2132
24V dc
T
T
L1 N L1 N L2 L1 N
234R1R2R356
1
2A Max
Has No Function
HWS Sensor (not Combi)
HWS Primary Pump (not Combi)
+24V
PWM
GND
1
621
Moulded Plugs
QAW 44 Optional Remote Sensor
RE2132 Modulating
51 34
Room Unit (Rad Zone)
2
MRO3
X3X16
R6 R5 R4
5
10
Cylinder Stat (not Combi)
Underfloor Zone VT Flow Sensor
+24V
PWM
G
N
D
2
OS
1
Outside Air Sensor
NOTE: All connections into MR03 are made
Via labelled factory fitted cables with the
exception of the underfloor Zone RE2132
which is cabled by the installer.
RE2132 Modulating Room Unit (U/floor circuit)
43251
QAW 44 Optional Remote Sensor
Install only one method of HWS temperature control.
X3,X16 = Controls Sockets on Control panel.
MR03 has factory made on plugs and leads
for these connections.
If system only has 1Nr RE2132 unit installed, then this
must be connected to the boiler 24V dc rail.
Page 44
44
STRATA1
38 & 38/46 COMBI
18.0 electrical connections (contd)
typical electrical connection schematic
to suit system type 7
Once all controls are installed please refer to page 57/58 to ensure the correct function number is programed into the control panel.
NOTE:
No connections,
other than those
shown are to be
37
38
35
36
26 28 30 32 34
23 25 27 29 31 33
X2 X4
14 16 18 20 22 24
11 13 15 17 19 21
made to the boilers.
Boilers
Not Used Additional
+24V
GND
PMW
* Outside Air Sensor
* HWS Sensor
Return sensor
Flow Sensor
No3
No2
No1
1 1 1
N PE L1
N PE L1
N PE L1
QAW44 Optional
*
Remote Sensor
Supply 230V
Supply 230V
Supply 230V
R1/1 R1/2 R1/3
* External Controls For Heating Circuit
N
Relay R1
L
Low Pressure Switch
break on Pressure Fall
R3
Boiler
R2
R3
Boiler
R2
R3
Boiler
R2
LVTR LVTR LVTR
RE2132 Modulating
*
Room Unit
43521
X2
16 18 20 22
13 15 17 19 21
* Cylinder Stat/HWS Time Switch
Control Options
Alternative External
X1
4 6 10 12
= Low Voltage Terminal Rail on Boilers
= Weiland Plugs/Sockets on Boilers
1
LVTR
13579
= Terminal Rails on KKM2 Kaskade Manager
2
X1, X2, X4
PE
N L
PE
N
L
PE
N L
Supply 230V
*
Heating Circuit Pump 230V 2A Max
HWS Primary
*
Pump 230V 2A max
- If Required
*
Page 45
45
STRATA1
38 & 38/46 COMBI
18.0 electrical connections (contd)
typical electrical connection schematic
to suit system type 8
Once all controls are installed please refer to page 57/58 to ensure the correct function number is programed into the control panel.
N
PE
Weiland
Plug/Socket
L1
Low Pressure Switch
Earth Rail
break on Pressure Fall
Supply 230V 3A
+
+
230V ac - 50 Hz
+
RE2132
24V dc
T
L1 N L1 N L2 L1 N
Has No Function
Outside Air Sensor
Junction
Box
L567L910LLNNEE
123
Room Stat
Cylinder Stat
(not Combi)
HW-MV & CH-MV
= Typical spring return type motorised valves
with end switches
Install only if direct-on-boiler weather compensated
flow temperature to heating circuit is required (recommended).
M
M
HW-MV CH-MV
LN
System
Pump Max 2A
2 3 4 R1 R2 R3 5 6
T
1
Page 46
46
STRATA1
38 & 38/46 COMBI
18.0 electrical connections (contd)
domestic hot water temperature sensor
If a hot water temperature sensor (from MHS Boilers) is used to sense the temperature of stored hot water, then this should be inserted into a pocket or surface mounted to measure the water temperature at approximately 1/3 of the height of the hot water vessel up from the base of the vessel.
remote fault indication
The Strata 1 boiler includes a built in fault alarm relay with volt free contacts for interface with, if required a remote alarm indicator. The volt free contacts within the boiler control panel will close in the event that the boiler goes to a fault resulting in boiler lockout. The volt free contacts indicate “common alarm” upon closing. The actual fault description will be displayed upon the LCD screen of the boiler. Connection to the volt free contacts is made via an alarm plug and lead assembly available from MHS Boilers Ltd. The alarm plug and lead connects to socket x9 located behind the cover plate on the top front of the control panel. To release cover plate, pull quick release pins located at either side.
outside air temperature sensor
If weather compensated flow temperature (recommended for best seasonal efficiency and comfort) is required, then the supplied air sensor must be installed and electrically connected to the boiler. The outside air sensor should be installed on the exterior face of a north facing wall, away from any artificial influences such as ventilation discharge grilles or in direct sunlight. Ø 5mm wall fixings and screws are provided.
Length m
Up to 35 35 to 70
70 to 140
Cable Diameter mm
2
0.25
0.5
1.0
X9 Socket (on control panel)
12
X9 Alarm Plug & Lead Assembly
Remote Aarm Circuit
Cable Detail
Length m
Up to 35
35 to 70
70 to 140
Cable Diameter mm
2
0.25
0.5
1.0
Cable Detail
52
TOP
50
28
Outside Air Temperature Sensor
Page 47
STRATA1
38 & 38/46 COMBI
47
In addition to the ability of the boiler to be connected to traditional industry standard control systems, MHS Boilers can supply a range of dedicated matched controls which not only simplify the selection of controls but in addition enhance the efficiency of the boiler and comfort conditions within the building.
combination pump and underfloor system mixing valve control
MRO3 module: For single boiler applications. A small and neat wall mounted control box which allows the boiler to control two different heating circuits.
Circuit 1 - A variable temperature circuit with pump and mixing valve (240v) for use with underfloor
coils where the maximum flow temperature = 55°C.
Circuit 2 - A pumped heating circuit (eg radiators) where the flow temperature is direct-on-boiler
weather compensated variable. The MRO3 has the facility to connect an RE2132 modulating room unit to provide modulating room temperature and time control over the underfloor circuit. A second RE2132 unit may be connected directly to the boiler to control Circuit No.2.
modulating room temperature control
RE2132 room unit: A compact digital room temperature control that will modulate boiler power according to room temperature requirements.
key features
In-built optimising time control and temperature sensor.
Three temperature levels including frost protection.
Holiday programmable.
Can be used as a remote control for parallel shift of compensation slope.
Self learning.
Can be connected to an individual boiler, on MR03 (underfloor) control or a KKM2
sequence controller.
QAW44 an additional tamper proof sensor can be wired to the RE2132 to allow sensing of remote
areas away from RE2132.
optional matched controlsoptional matched controls
Page 48
48
STRATA1
38 & 38/46 COMBI
optional matched controls (contd)
multiple boiler Kaskade manager
KKM2 modulating sequence controller:
A comprehensive compact wall mounted microprocessor control panel which allows the control of up to five Strata 1 boilers. The KKM2 provides fully modulating control over the connected boilers ensuring precise output control and maximum efficiency.
In addition to boiler control, the KKM2 can provide the drive signal for a heating circuit pump and can provide control for stored domestic hot water (with priority over heating). Domestic hot water may be charged using either a diverter valve or primary pump, either of which are driven from the sequencer.
External control input is via either a volt free contact (eg time switch), 0-3v or 10v input, or an RE2132 modulating room unit plus necessary temperature sensors. Heating flow temperatures may be either constant temperature or direct-on-boiler weather compensated variable (by means of the in-built compensator). If more than five boilers are required to be controlled, then additional KKM2s may be slaved to the first control with slave capacity of four boilers per each additional sequencer. Standard features include pump overrun, boiler load rotation, frost protection and pump exercise program.
0-3/0-10 volt control
The Strata 1 can be operated via 0-3 volt or 0-10 volt control. The connection details are shown in fig 22. For further details on 0-3 or 0-10 volt control please contact the Technical Department.
0-10 Volt Control 0-3 Volt Control
24V dc
-
RE2132
+
T
T
2 3 4 R1 R2 R3 5 6
1
Has No
Function
T
234R1R2R356
1
24V dc
T
-
0V
RE2132
+
0 - 3 Volt
0 - 10 Volt
Control
Adaptor
-
+
0
v
V
0 - 10 Volt
Control
Has No
Function
Page 49
49
STRATA1
38 & 38/46 COMBI
a) Ensure system has been thoroughly cleansed and flushed, any strainers have been cleaned and that the
appropriate water treatment has been added to the system to prevent corrosion, scale formation etc. Failure to comply with this will void all warrantee applied to the boiler.
b) Ensure the system and boiler has been properly fully flooded and vented of air and the cold fill pressure at
the boiler is at a minimum 0.5 bar. Air vent for primary heat exchanger is located to the right hand side of the top of the boiler chassis.
c) Check that the pump within the boiler is free to rotate by removing the vent screw in the end of pump
motor and checking that the impeller shaft rotates freely when turned with an appropriate sized
screwdriver. Replace vent screw. d) Ensure the appliance has been converted to burn the type of gas available on site. e) Ensure Gas supply has been purged and there is the availability of working inlet pressure of nominal 20mbar
(Nat gas) or 37 mbar (LPG), and that the appliance supplied is suitable for the gas type
being used. If the boiler is required to be converted to an alternative you must contact MHS Boilers for
assistance. f) Check that the flue installation has been properly made. g) Check that a condense waste pipe (in plastic - copper tube is not acceptable) has been connected to the
boiler and that the syphon cleaning point cap is in place. h) Where the appliance is taking air for combustion from the room in which it is installed - ensure an adequate
provision for ventilation has been made. i) Ensure that there is an adequate heat load available. j) Ensure that the electrical connections have been made correctly. k) Combi boiler – ensure domestic hot water pipework is flushed and fully flooded. l) Combi boiler – ensure primary side of water to water heat exchanger is fully vented by releasing air from
vent located on the top right hand side of the insulated heat exchanger. It is recommended to vent heat
exchanger several times during initial commissioning. m) Set the low pressure switch to operate at 0.5 bar.
19.0 commissioning
the Strata 1 boiler
The Strata 1 boiler should be expertly commissioned by a competent engineer who will need, in addition to standard hand tools, a U tube manometer and a combustion analyser.
Before attempting to set the Strata 1 38 or 38/46 combi boiler to work, the following check list must be worked through. See 19.1.
The data badge of the appliance must be marked to indicate the conversion has been undertaken. Refer to the commissioning section for guidance on Combustion Adjustment.
Boiler Type White Premix Air Box Hole White Premix Air Box Hole Strata 1 38 Boiler Plug with 15mm Plugs Leave Open Strata 1 38/46 Combination Boiler Plug with 15mm Plugs Plug with 13mm Plug
19.1 Pre-commissioning
checks
19.2 LPG Conversion
Procedure
The Strata 1 38 and 38/46 combination boilers can be converted to operate on LPG. (G31). Only the parts supplied in conversion kit# 250158 must be used. The 3.5mm injector must be installed into the inlet of the gas valve and the 5.7mm injector in to the outlet of the gas valve. Using the plastic plugs supplied the aeration holes in the white premix air box mounted on the inlet of the combustion fans must be plugged according to the table below.
Page 50
50
STRATA1
38 & 38/46 COMBI
19.3 control
panel
The user interfaces on the boiler control panel include a double pole on/off switch, 4Nr membrane button switches with click response, an LCD display screen with backlight and a mechanical dial type pressure gauge to indicate heating system water pressure.
The membrane button switches (with the exception of the test button) are multi-function and have varying operation depending upon the operational mode of the boiler.
When requiring to use the membrane button switches, light but firm finger pressure must be exerted on the appropriate circular marking until a click response is felt/heard.
display
The back lit LCD display screen has two lines. The normal text displayed is:-
a) Upper Line – Indicates current status of boiler, e.g. HW DEMAND, and either “S” (summer) or “W”
(winter) / “D” (day) or “N” (night). b) Lower Line – Indicates current flow temperature of boiler and real time.
menu/reset button
Gives access to the various menus
Scrolls through the current operational status
messages.
Confirms an entry during controls programming.
Resets the boiler following a lockout”.
button
Advances (Scrolls forward) through menu.
Increases a value to be edited.
Sets controls to either summer (heating off) or
winter (heating on) operation.
button
Reverses (scrolls backward) through menu.
Reduces a value to be edited
Sets appliance (for 10 minutes) into Engineers
mode for commissioning or checking purposes.
test button
Checks overheat safety circuit (during a burner
on mode; will cause burner to be shut down and then re-ignited).
Checks boiler pump operation (during a burner
off mode; will cause pump to be operated at 100% speed for approx 2 seconds.
"+"
"-"
Fig 21.
Plus "+"/ Summer-Winter
Button
Display
MENU
RESET TEST
Menu / Reset Button
STATUS
+
-
Minus "-"/Engineers
Button
Test Button
On/Off
Switch
1
0
Gauge For Heating
System Water Pressure (bar)
2
3
1
04
Page 51
51
STRATA1
38 & 38/46 COMBI
19.4 first
firing
a) Attach a “U” tube manometer to a gas pressure
test point on the supply pipe (by installer) adjacent to the gas inlet connection on the appliance.
b) Turn on (purged) gas and electricity supplies.
c) Switch on boiler at on/off switch (see fig 21).
Screen display will show Deaeration and boiler pump will pulse on and off for approx 60 seconds. Following which, the boiler will revert to either standby or DHW demand (combi).
d) Press menu/reset button repeatedly until
screen display shows Revolu..R/S (see fig 21).
e) Press minus/engineers button twice. Screen
display will show 10 min test. (see fig 21). Burner should ignite. (If after four attempts the burner fails to ignite, then the appliance will lockout and show ignit fault. Press menu/reset button. Boiler will activate Deaeration programme following which:­remove cover screw from gas valve adjustment (2) Q min and turn adjustment screw half turn clockwise see fig 22. Now repeat operations d and e until burner ignites.
f) Check working inlet gas pressure should be
nominal 20mbar for NG or 37mbar for LPG.
g) Using the “+” and “-“ buttons adjust burner fan speed to approx 1200 Revolutions. (see fig 21).
h) Observe the colour of the burner, correct colour should be dull red. Using adjustment (2) Q min (see
fig 22), set burner at correct colour. Turning screw clockwise increases brightness; anti clockwise reduces brightness of burner. Turn the screw very slowly and just a few degrees at a time – the adjustment is very sensitive. Following this procedure will avoid poisoning your combustion analyser.
i) Remove flue gas analysis test point cap (top-front-right of combustion chamber shell) and insert probe
of combustion analyser. Adjust as necessary (2) Q min to obtain required CO
2
% value – see Table 10. Make adjustments slowly and wait at least 2 minutes for analyser reading to stabilise before re-adjusting. Turning (2) Q min clockwise increases CO
2
%. Turning (2) Q min anti-clockwise decreases CO2%.
j) Using the “+” and “-“ buttons (see fig 21) increase burner fan speed to approx 6000 revolutions.
k) Check working inlet gas pressure again – see f above.
l) Check CO
2
% value in accordance with values shown in table 10. If adjustment is required, then turn screw (3) Q max (see fig 22). Turning (3) Q max clockwise decreases CO
2
%. Turning (3) Q max anti-clockwise increases CO2%.
NOTE: Adjustment of either (2) Q min or (3) Q max will affect the other adjustment to a lesser or greater extent. Following the adjustment of either Q min or Q max, check the CO2% value at the other setting and correct as necessary.
Nat Gas G20
9.5
9.0
LPG G31
11.5
11.0
Gas Type
CO
2
% at 1200 Revs
CO
2
% at 6000 Revs
Table 10 Flue gas CO2% settings
gas valve
Q max
Q min
Burner offset pressure test point
Adjustments
Turning 2 clockwise increases min output & CO
2
%
Turning 3 Anti clockwise increases max output & CO2%
Fig 22.
3
2
1
Page 52
52
STRATA1
38 & 38/46 COMBI
19.5 setting
the control panel
19.4 first firing (contd)
m) Repeat operations g, I, j and l and check/adjust settings as necessary.
n) Press “Test button (see fig 21) to stop the burner.
o) Repeat operations d, e, g, i, j, and l and check/adjust settings as necessary. Refit (2) Q min cover screw.
p) Press “Test button (see fig 21) to stop the burner.
q) Remove analyser test probe and re-fit test point cap hand tight. Ensure rubber seal disc is in place
inside cap.
r) Turn off gas supply and remove U tube manometer from inlet pressure test point and re-fit test point
screw and tighten. Turn on gas supply and check test point for gas soundness using leak detection fluid.
NOTE: Test period expires after 10 minutes. If this period expires before or whilst adjustments are being made/completed, then return to required adjustment position by repeating d, e, etc.
s) Check operation of flame failure system by turning off gas supply and then attempt to ignite burner.
After 4 unsuccessful ignition attempts, the boiler should lockout and display ignit fault. Restore gas supply and press reset button.
The control panel has a number of parameters that need to be set to the requirements of the attached
system and the needs of the user. The control parameters are accessed via a scrolling menu.
MENU/RESET Button press and hold for approximately 3 seconds (see fig 20).
The screen will briefly display -MENU- and will then display a menu option.
To scroll through the menu options, use the + or “-“ buttons, simply stop at the required option and
follow specific instructions to programme as appropriate.
menu options
1. party
This is a user function and allows the user to extend normal heating operation (on an as and when
required basis) beyond the normal heating period.
To access the “Party” option press the “Menu” button once. “——— hours will flash on the screen, press + or - to enter a value and then press Menu to confirm the entry. Range 0 to 24 hours. Default 0 hours.
2. temp DHW
This is a user function and allows the user to programme the required stored hot water temperature where the boiler is serving a hot water cylinder (not combi boiler) and where the temperature control is via a sensor. If temperature control is via a cylinder thermostat then this function is not operative.
To access the TEMP DHW option press the “Menu” button once. “———°C” will flash on the screen, press “+” or “-“ to raise or lower the value and then press “Menu” to confirm the entry. Range 40­60°C. Default 60°C.
Page 53
STRATA1
38 & 38/46 COMBI
3. day temperat (day temperature)
This option is only displayed when the outside air temperature sensor (supplied with the boiler) is
installed and operation with direct-on-boiler weather compensated flow temperatures is required.
This is a user function and allows the user to raise or lower the room temperature for adjustment of
the comfort level.
Raising or lowering the set value will cause parallel displacement of the heating slope line which will
result in raising or lowering of the heat emitter temperatures.
The default value for this setting = 20°C.
4. day/time
This is a user function and at this option the real day of the week and time should be set.
To set clock:­a) Press “Menu” button b) Use + or - to set day c) Press “Menu” button d) Use + or - to set hour (24 hour clock) e) Press “Menu” button f) Use + or - to set minutes g) Press “menu” button to effect settings.
5. set CH timer
This is a user function and at this option the on/off times for normal heating may be set. 3 ON and 3
OFF Periods may be set each day.
IMPORTANT: If the heating circuit is being controlled by a remote timeswitch or BMS system then the
1st on time must be set to 0000 and the 1st off time must be set to 2400 for each day.
To set operational times:­a) Press “Menu” – “Monday >” is displayed on screen. b) Press MenuCopy SU>MO is displayed on screen, (ignore this) c) Press “+”, “Switch on 1” is displayed on screen d) Press “Menu” – (hours will flash) use “+” or “-“ to set required hour e) Press “Menu” – (minutes will flash) use “+” or “-“ to set required minute f) Press “Menu” to confirm settings g) Press “+”, “switch off 1” is displayed on screen h) Repeat d to f input 1st switch off time. i) At this point, press either “+” to programme 2nd heating period, in which case, repeat d to h for 2nd
period, and then if 3rd heating period is required, repeat c to h for 3rd period or press “+” until <back is displayed, then press Menu to advance to next day.
j) At this point, press either “Menu” to copy programme to next day or press “+” to allow individual day
programming. If individual day programming is required then repeat d to j as appropriate.
k) Continue programming/copying each day until each day has been programmed ending with Sunday and
screen display “<Back”.
l) Press “Menu” to return to main menu.
Default setting – on 0.600 – off 23.00
6. set HW timer
This is a user function, and at this option the on/off times for hot water production may be set. NOTE: This function is not appropriate to the Combi boiler and may be ignored. Hot water production
with the combi boiler is instantaneous and is available at all times.
Hot water production always takes priority over heating and the heating function will be temporarily suspended whilst hot water is being generated. This applies to both the Strata 1-38 boiler and Strata 1-38/46 Combi.
To set operational times for hot water charging follow the procedure as described in 19.4.5 a to l. Default – on 0.600 – off 23.00.
19.5 setting the control panel (contd)
53
Page 54
STRATA1
38 & 38/46 COMBI
7. set MV timer
This is a user function and at this option, the on/off times for an under floor coil circuit (that is
controlled by an MR03 mixing valve regulation control box from MHS Boilers) may be set.
To set operational times for under floor circuit operation, follow the procedure as described in 19.4.5
a to l. Default on 0.600 – off 23.00.
8. setback
This is a user function and sets the reduction in room temperature for overnight operation. This is a
reduction in temperature from that which is set in 19.4.3 – Day temperature. Default value 5°C.
To programme set back temperature:­a) With SETBACK displayed on the screen press Menu. b) “___°C” will flash on the screen, press “+” or “-“ to raise or lower the value to the required setting
and then press “Menu” to confirm the entry.
9. holiday
This is a user function and allows up to 255 days of holiday period to be programmed. During this period the heating will operate (if in winter mode) at “setback” temperature see 19.4.8 and
the domestic hot water will be maintained at a minimum of 20°C.
After the number of “holiday” days has expired, the unit will revert back to the normal operation.
NOTE: If the heating circuit is being controlled by an RE2132 modulating room unit, then this piece of control equipment should also be “holiday” programmed. See instructions supplied with the RE2132 unit. Default setting 0 days.
To programme a holiday period:­a) With holiday displayed on the screen press Menu. b) “___days” will flash on the screen press “+” or “-“ to input the required number of days in the holiday
period and then press “Menu” to confirm the entry.
The holiday period should be programmed on the day that the holiday begins.
10. installer
This function should not be accessed by the user and is code protected. For Installer programming instructions see 19.6.
11. back
This is the end of the menu. Press “Menu” to exit.
19.5 setting the control panel (contd)
19.6 installer programming
of control panel
A number of operational options are available to the installer. These can only be accessed by means of a pass code. If the correct code is entered at 19.4.10 then the following parameters may be set, see 19.5.2.
(For installer code no see bottom right hand corner of page).
1. to enter installer programming menu:-
a) With INSTALLER> displayed on the screen press Menu. b) Code: 0 will flash on the screen press “+” or “-“ to input the installer code and then press “Menu” to
confirm the entry and access the installer menu.
2. installer programme menu
Scroll through menu using “+” or “-“ buttons. The current setting for any parameter will be displayed
under the particular parameter title.
Installer
Code
= 21
Page 55
55
STRATA1
38 & 38/46 COMBI
a) CURV 20°C CH (Default setting = 0°C)
This option is only displayed when the outside air sensor is installed for direct on boiler weather
compensation.
Shift adjustment of the weather compensated flow temperature (if active – see 19.5.2l) at +20°C
outside air temperature.
At this setting, the installer may add or subtract up to 20°C to or from the factory set 20°C flow temperature. In other words, the flow temperature at outside air temperature 20°C may set between 0°C and 40°C. See figs 22-25.
To make an adjustment:-
Press “Menu” button once, the current setting will flash on the screen, press “+” or “-“ to input a new value between –20°C and +20°C and then press “Menu” button to confirm the entry.
NOTE: Settings a and b are only relevant if the supplied outside air temperature sensor has been installed and outside air control selected in 19.5.2l.
b) CURV 1°C CH (Default setting = 0°C)
This option is only displayed when the outside air sensor is installed for direct on boiler weather compensation.
Shift adjustment of the weather compensated flow temperature (if active – see 19.5.2l) at –1°C outside air temperature.
At this setting, the installer may add or subtract up to 20°C to or from the set maximum central heating flow temperature. (the base setting for the maximum central heating flow temperature is made in 19.5.2l)
NOTE: The maximum flow temperature is 85°C. If a shift adjustment is made that asks for 85°C to be exceeded, the curve will flatten at flow temperature 85°C but the result will be, that the maximum flow temperature of 85°C will be achieved at a higher outside air temperature. See figs 22-25.
To make an adjustment:-
Press “Menu” button once, the current setting will flash on the screen, press “+” or “-“ to input a new value between –20°C and +20°C and then press “Menu” button to confirm the entry.
c) PUMP MIN (Default setting = 35%)
Setting for the lowest (minimum) speed that the inbuilt modulating speed pump can operate at. Recommended setting 35%.
To make an adjustment:-
Press “Menu” button once, the current setting will flash on the screen, press “+” or “-“ to input a new value between 35% and PUMP MAX and then press “Menu” to confirm the entry.
d) PUMP MAX (Default setting = 100%)
Setting for the highest (maximum) speed that the inbuilt modulating speed pump can operate at. Recommended setting 100%.
To make an adjustment:-
Press “Menu” button once, the current setting will flash on the screen, press “+” or “-“ to input a new value between PUMP MIN and 100% and then press “Menu” to confirm the entry.
e) SERVICE IN
The control panel includes a countdown service timer and at this setting will initially show the number of days left until the boiler should be serviced and at which time the screen display will show exclusively Service. The boiler will continue to function but the user should arrange for a service visit.
To reset the service counter to the default value of 365 days press “Menu” button twice. If another value between “off ” (service counter inactive) and 1500 days (Recommended setting not greater than 365 days) is required, then press “Menu” button once, input a new value using either the “+” or “-“ buttons and then press “Menu” to confirm the entry.
f) PUMP CONTINUE (Default setting = off)
At this setting, the inbuilt pump and any connected external pump may be operated continuously during winter mode. Recommended setting = off.
To alter the setting:-
Press “Menu” button once, press either “+” or “-“ to alter the setting to “on or off ” and then press Menu to confirm the entry.
19.6 installer programming (contd)
Page 56
56
STRATA1
38 & 38/46 COMBI
19.6 installer programming (contd)
g) ECO + (Default setting = on)
The inbuilt modulating speed pump will automatically modulate in order to maintain the design 20°C
t across the boiler flow and return temperatures.
If ECO+ is set to off , the pump speed is free to modulate at any return water temperature with
the exception of the first start-up in the morning.
To alter the setting:­Press “Menu” button once, press “+” or “-“ to input the required setting and then press “Menu to
confirm the entry.
h) POSTRUN HW (Default setting 1 min)
At this setting the post running time (overrun) of the inbuilt boiler pump and any connected HW primary charging pump may be set. The pump/s will overrun for the set time at the end of a HW demand period.
This setting is only applicable for Combi boilers, and standard boilers serving a domestic hot water cylinder or calorifier. Recommended settings:
Combi boiler = 1 minute
Model 38 boiler = Not less than 1 minute
To alter the setting:-
Press “Menu” button once, the current setting will flash on the screen, press “+” or “-“ to input a new value between 1 and 5 minutes and then press “Menu” to confirm the entry.
i) POSTRUN CH (Default setting 3 min)
At this setting the post running time (overrun) of the inbuilt boiler pump and any connected CH circulation pump may be set. The pump/s will overrun for the set time at the end of a CH demand period.
Recommended setting = not less than 3 minutes.
To alter the setting:-
Press “Menu” button once, the current setting will flash on the screen, press “+” or “-“ to input a new value between 3 to 20 minutes and then press “Menu” to confirm the entry.
j) MIN POWER (Default setting 17%)
This is the minimum power for both central heating and hot water demands that the burner may modulate down to.
Recommended setting = not less than 17%.
To alter the boiler minimum power:-
Press “Menu” button once, the current setting will flash on the screen, press “+” or “-“ to input a new value between 17 to 100% and then press “Menu” to confirm the entry.
k) MAX POWER CH (Default setting 100%)
At this setting, the maximum output of the boiler for a central heating demand may be set. This adjustment is only relevant to those market places where national or local regulations demand that a boiler must be accurately set to meet design load.
The Strata 1-38 and 38 combi boilers are fully modulating appliances and automatically adjust to suit load conditions and for the UK market it is recommended to leave the setting at 100%.
To alter the boiler maximum CH power, press “menu” button once, the current setting will flash on the screen, press “+” or “-“ to input a new value between Min Power and 100% and then press “Menu” to confirm the entry.
l) FUNCTION NR (Default setting = 9)
At this setting the boiler is programmed to suit the needs of the attached system.
Select the appropriate Function No from the following tables and then enter the required number.
To input Function No”:-
Press “menu” button once, the current setting will flash on the screen, press “+” or “-“ to input the appropriate number and then press “menu” to confirm the entry.
NOTE: Take care to enter the correct function number as relevant to the system configuration. Entry of an incorrect function number may result in an error (fault) message being displayed on the control panel screen and or incorrect or unwanted operation of the boiler and system.
m) <BACK
To exit the installer menu, press “menu” button twice when screen display shows “<back”.
Page 57
57
STRATA1
38 & 38/46 COMBI
19.6 installer programming (contd)
System Type Room Controls Type
CH Flow Function Temperature Number
Outside air temperature controlled, With RE2132 modulating room unit Max 55°C1 without a secondary underfloor Max 70°C2 mixing circuit Max 85°C3
With room thermostat/volt free switch Max 55°C4
Max 70°C5 Max 85°C6
Without room controls Max 55°C7
Max 70°C8 Max 85°C9
Outside air temperature controlled, With 2Nr RE2132 room units Primary 70°C10 with a secondary underfloor Primary 85°C11 mixing circuit and MR03 controller With 1Nr RE2132 modulating room unit Primary 70°C12
Primary 85°C13
With room thermostat/volt free switch Primary 70°C14
Primary 85°C15
Without room controls Primary 70°C16
Primary 85°C17
No outside air temperature control, With RE2132 modulating room unit Max 55°C18 and without secondary underfloor Max 70°C19 mixing circuit Max 85°C20
With room thermostat/volt free switch Max 55°C21
Max 70°C22 Max 85°C23
No outside air temperature control, With 2Nr RE2132 modulating room units Primary 70°C24 and with secondary Underfloor Primary 85°C25 mixing circuit and MR03 controller With 1Nr RE2132 modulating room unit Primary 70°C26
Primary 85°C27
With room thermostat/volt free switch Primary 70°C28
Primary 85°C29
Fixed constant flow temperature with no outside air temperature control and without room controls.
Without secondary underfloor mixing circuit Max 55°C30
Max 70°C31
Max 85°C32 With secondary underfloor mixing circuit Primary 70°C33 and MR03 controller Primary 85°C34
Table 11
Valid for Combi boilers and standard boilers where primary hot water control is via a 3 way
divertor valve.
Table 12
Valid for combi and standard Strata 1-38 boilers. Multiple boiler installation with boilers controlled by
a cascade manager.
System Type
Function
Number KKM2 Modulating Kaskade Manager 35 Analog cascade manager with signal 0-3v or 0-10v* 36
* Boilers must be fitted with optional extra 0-10v interface
Page 58
58
STRATA1
38 & 38/46 COMBI
19.6 installer programming (contd)
Table 13
Valid for standard Strata 1-38 boilers only (NOT COMBI) where the domestic hot water cylinder (if fitted) is charged via an additional hot water primary pump and the pump is electrically connected to the boiler.
glossary of terms
Outside Air Temperature The (supplied) outside air temperature sensor has been installed and Controlled direct-on-boiler weather compensated flow temperature is required.
Max Maximum flow temperature either fixed or weather variable.
Primary Maximum flow temperature either fixed or weather variable with reference
to the boiler supply side of an under floor coil mixing valve and any primary radiator zone.
RE2132 Modulating Intelligent (time and temperature) room controller from MHS Boilers. For Room Unit specific details see either Technical Sales Literature or specific
installation/user guide.
MR03 Controller Interface control box giving the ability for the boiler to control the space
temperature and coil temperature of an under floor heating coil zone.
System Type Room Controls Type
CH Flow Function Temperature Number
Outside air temperature controlled, With RE2132 modulating room unit Max 55°C 37 without a secondary underfloor Max 70°C38
mixing circuit Max 85°C39
With room thermostat/volt free switch Max 55°C 40
Max 70°C41 Max 85°C42
Without room controls Max 55°C43
Max 70°C44 Max 85°C45
Outside air temperature controlled With 2Nr RE2132 modulating room units Primary 70°C46 with a secondary underfloor Primary 85°C47 mixing circuit and MR03 controller With 1Nr RE2132 modulating room unit Primary 70°C48
Primary 85°C49
With room thermostat/volt free switch Primary 70°C50
Primary 85°C51
Without room controls Primary 70°C52
Primary 85°C53
No outside air temperature controls With RE2132 modulating room unit Max 55°C54 and without secondary underfloor Max 70°C55
mixing circuit Max 85°C56
With room thermostat/volt free switch Max 55°C 57
Max 70°C58 Max 85°C59
No outside air temperature controls With 2Nr RE2132 modulating room units Primary 70°C60 and with a secondary underfloor Primary 85°C61 mixing circuit and MR03 controller With 1Nr RE2132 modulating room unit Primary 70°C 62
Primary 85°C63
With room thermostat/volt free switch Primary 70°C64
Primary 85°C65
Fixed constant flow temperature with no outside air temperature control and without room controls.
Without secondary underfloor mixing circuit Max 55°C66
Max 70°C67
Max 85°C68 With secondary underfloor mixing circuit Primary 70°C69 and MR03 controller Primary 85°C70
Page 59
59
STRATA1
38 & 38/46 COMBI
default compensation slope
Max Flow Temperature
Boiler Flow Temperature ºC
Outside Air Temperature ºC
Boiler Flow Temperature ºC
Outside Air Temperature ºC
range of parallel displacement of slope A
When compensation required outside sensor must be installed and appropriate function No. selected.
Slope A - Max/Primary 85°C
Slope B - Max/Primary 70°C
Slope C - Max 55°C
19.6 installer programming (contd)
Fig 22.
Fig 23.
90
80
70
60
A
B
50
40
30
20
10
-20 -15 -10 -5
CURV -1ºC CH
90
80
70
-20 +20
C
+5 +10 +15 +20 +250
-1
*
60
50
40
30
20
10
-20
-15 -10 -5
-1
default
+20
*
-20
+5 +10 +15 +20 +250
CURV 20ºC CH
Page 60
60
STRATA1
38 & 38/46 COMBI
Boiler Flow Temperature ºC
Outside Air Temperature ºC
Boiler Flow Temperature ºC
Outside Air Temperature ºC
range of parallel displacement of slope B
range of parallel displacement of slope C
19.6 installer programming (contd)
Fig 24.
Fig 25.
90
80
70
60
50
40
30
20
10
-20
-15 -10 -5
CURV -1ºC CH
-20 +20
*
+5 +10 +15 +20 +250
-1
default
+20
*
-20
CURV 20ºC CH
90
80
70
60
50
40
30
20
10
-20
-15 -10 -5
CURV -1ºC CH
-20 +20
*
+5 +10 +15 +20 +250
-1
+20
*
-20
CURV 20ºC CH
Page 61
61
STRATA1
38 & 38/46 COMBI
19.7 output for
charging hot water
20.0 setting the boiler
to work
There is no adjustment necessary or possible, as the boiler controls are self learning and will self adapt the optimum output to hot water according to the heat transfer capabilities of the connected hot water calorifier or cylinder, or the rate of hot water usage (combi boiler).
WARNING: This appliance must not be left to operate with the outer casing removed.
1. To fit casing to boiler ensure hooks on top rear edge of boiler case engage properly into rear chassis
assembly. Latch bottom case fixings and tighten central locking screw.
2. Turn ON on/off switch and set any external controls to auto operation.
3. With boiler operating (burner on) press “Test button on boiler control panel to test overheat controls
in the boiler. The boiler must shut-down and then re-ignite.
4. Before handing over the appliance to the user, check again and clean strainers/filters.
21.0 servicing
instruction
21.1 inspection
general
In general, maintenance/inspections should take place:
a) When the display on the unit indicates that inspection is required (status shows “SERVICE”) normally
after 365 days.
or b) At least every 12 months.
Before carrying out any maintenance the unit must be inspected.
a) Ask the user about any problems with the boiler unit or any other comments. b) Check the water pressure of the installation. c) Remove the casing of the unit and inspect all pipes and connections for water leaks. d) Inspect the top of the casing and/or the top of the heat exchanger for water leaks or signs of water
from the flue air supply tube. e) If you have a notebook computer, connect it and check the service page for any errors, messages, starts
and successful restarts. (Special communication lead and service software required) f) Run the unit at maximum capacity and measure the input and the CO
2
%.
g) Run the unit at minimum capacity and measure the input and the CO
2
%.
h) Listen to the sound of the in built pump.
Page 62
62
STRATA1
38 & 38/46 COMBI
21.1 inspection (contd)
i) Turn off the boiler and disassemble the burner by removing the six M6 nuts around the burner door,
removing the ignition cable and pulling the burner forwards. When the burner has been pulled forwards to halfway across the burner area, the plug on the fan cable must be removed from the fan motor. Check the interior of the heat exchanger.
j) Open the syphon cleaning rinsing point at the base of the unit with suitable receptacle below to collect
syphon contents. Refit rinse point cap after flushing. k) Disassemble the plastic box at the suction side of the fan, inspect the fan blades. l) Check the distance between the electrode and the burner earthing rod; this should be 4 to 5 mm. m) Check water treatment dosage level.
21.2 maintenance
Depending on the results of the inspection, carry out any maintenance and if necessary any preventive maintenance. Possible actions following inspection (21.1) include:
at a) The remarks and comments of the client must be taken seriously and the cause(s) of any faults or
problems must be found.
at b) The pressure of the installation must be between 1 and 2 bar when hot (not less than 0.5 bar cold):
any possible leaks in the system must be identified; if necessary, have a pipework engineer solve the problem.
at c) Possible leaks or weeping must be resolved immediately.
at d) In case of water leakage or ingress from the air supply pipe, the cause must be found and rectified.
at e) Draw your conclusions from the service screen of the service software program (available from
MHS Boilers spares department) and attend to those parts that have caused any faults.
at f ) and at g)
If necessary, adjust the gas setting on the gas valves.
at h) If the in built pump makes an un-natural noise, and in particular if the pump is more than 5 years
old, it is recommended that the pumps should be replaced by way of preventive action.
NOTE: The pump is modulating and does have characteristic yet yet noise which is normal at low speeds.
at i) NEVER CLEAN THE BURNER ITSELF.
If the interior of the heat exchanger is contaminated and/or there is a deposit on the surfaces of the coiled stainless steel pipes, the latter must be removed with a natural bristle brush. Strata heat exchanger cleaning granuals can be obtained from MHS Boilers spares department. (DO NOT USE A STEEL BRUSH !) Then remove any dirt with a vacuum cleaner.
at j) The syphon must be rinsed. With the burners removed, use a filling hose to insert water into the
heat exchanger, which will automatically reach the siphon. Allow the water to run clear prior to refitting the rinse point cap.
at k) If dirt has deposited on the fan blades, each blade must be carefully cleaned, until the blade material
is visible again. If this is not done evenly the fan will not rotate properly and be out of balance.
at l) Carefully bend the electrode without touching the burner, until the correct distance has been
reached. Adjust only the angle of the bend nearest the ceramic insulator. Do not use tools. Firm finger pressure is all that is required.
Page 63
63
STRATA1
38 & 38/46 COMBI
21.2 maintenance (contd)
at m) check and top up as necessary water treatment to required %.
Important Note
IF ANY WATER CARRYING JOINT WITHIN THE BOILER IS DISASSEMBLED THEN THE “O” RING SEAL MUST ALWAYS BE REPLACED, LIKEWISE IF ANY OTHER SEAL IS NOTED TO BE DEFORMED THEN THEY SHOULD ALSO BE REPLACED. WATER SEALING “O” RINGS ARE A ONE TIME USE ONLY AND SHOULD NOT BE RE-USED.
cancelling the “service” message
Following the maintenance operations, the service message (when displayed) must be cancelled See 19.6).
22.0 screen display/
diagnosis of faults
The control panel of the Strata 1 boiler has an LCD screen, displaying two lines of data. This screen provides information about the operation of the appliance; it shows operation messages (non flashing) and fault messages (flashing display). The first line contains text information about the status of the unit.
It shows:
status messages (non flashing) for normal operation
No Demand No heat demand (boiler not required to be on).
Pre-purge Combustion chamber is being pre-ventilated with air from the burner fan.
Ignition The ignition sequence of the burner is initiated.
CH Demand The boiler is operating in central heating mode.
HW Demand The boiler is operating to produce domestic hot water.
Chimney The boiler is operating in test mode at mid output to enable flue gas emissions to be
checked (auto expires after 10 min).
10 min Test The boiler is operating in engineers test mode for adjustment purposes (auto expires
after 10 min).
Post-Purge Combustion chamber is being post-ventilated with air following boiler operation.
Limit F/R The flow and/or return temperature is too high (currently).
Fan High The burner fan is running too fast (currently).
Fan Low The burner fan is running too slow (currently)
Fault R/U There is a fault with the modulating unit (RE2132) or kascade manager (KKM2) or a
fault in the wiring to these controls (in the case of the RE2132 the boiler runs continuously in heating mode to protect the building).
OTS Fault There is a fault in the outside air sensor or in the wiring to the sensor or the function
Nr is incorrectly set to ask the boiler to look for an outside sensor when there is none installed.
Service The service interval time has expired and the boiler should now be maintained.
Deaeration The in built pumps are operating to remove any possible collection of air from the heat
exchanger. (Occurs when power turned off/on and after reset of fault).
Page 64
64
STRATA1
38 & 38/46 COMBI
22.0 screen display/diagnosis of faults (contd)
The second line of text displays values such as temperature, percentages etc and the reset button may be used to scroll through (for information) the values of the various sensors that are/may be connected in the boiler plus fan speed and pump speed etc.
status messages (flashing display) indicating a fault
A flashing display indicates a fault and that the boiler has shutdown (lockout). The boiler will not attempt to operate until the “red” reset button is pressed.
Any repetitive flashing fault message should be investigated, the cause found and corrective action taken. For each flashing display message there is a possible cause, see list of cause numbers following the flashing status list.
Display Message Meaning Cause Number/s Flashing
STB-Supply Heat exch high limit stat has tripped. 5, 6, 7, 8, 21, 24, 25, 26, 31, 36
STB-Flue Gas Flue limit stat has tripped. 2, 5, 6, 7, 21, 24, 25, 31, 36
Fan Spd high Burner fan speed is too high. 9, 11, 29, 31, 33
Fan Spd low Burner fan speed during pre-purge is too low. 9, 10, 11, 14, 18, 29, 31, 33
Fan Spd oper Burner fan is detected as 4, 11, 29, 31
operating when should be idle.
Ignit Fault Ignition to burner has not 11, 12, 13, 15, 16, 17, 19, 22,
been successful after 4 attempts. 23, 27, 29, 30, 31, 35, 37, 38
No Flame Flame at burner has been lost on 13, 15, 16, 17, 20, 22, 23
4 consecutive occasions during operation.
False Flame Flame is detected at the burner when 17, 19, 30
there should be no flame.
S1 Disconnect Heat exch flow temperature sensor interrupted. 3, 5, 33
S3 Disconnect Combi boiler - hot water flow 3, 5, 33
temperature sensor interrupted.
S4 Disconnect Return temperature sensor interrupted. 3, 5, 33
S7 interrupt Mixed flow temperature sensor interrupted. 1, 3, 5, 33
Only when MR03 unit installed.
Program end Follows reprogramming of control panel with
laptop PC, not a fault - just press reset button.
Gas valve High resistance in the electrical circuit to 26, 28, 29, 31, 33, 37
and including the gas valve is detected.
Soft W Fault Error in software in the control. 29
Display Message Meaning Cause Number/s Flashing
Page 65
65
STRATA1
38 & 38/46 COMBI
22.0 screen display/diagnosis of faults (contd)
Reset Key There is a fault with the reset button. 29, 31, 34
Eeprom There is a fault in the EEPROM in the control. 29
Intern Fault There is an internal fault in the control panel.
Test Fault There is a fault with the test button. 29, 31
22.1 (possible) causes of fault
& corrective action
Cause No. Reason/Action
1. Operational function No. not set correctly / Check and correct settings. See tables 11, 12, 13.
2. Unsound electrical connections to flue limit stat / Check and correct.
3. Sensor not correctly connected or sensor defective/Check connections and or replace sensor.
4. Short circuit in wiring / Check and rectify.
5. Short circuit in wiring to sensor / Check and rectify.
6. Boiler pump not rotating (seized or defective)/Free seized shaft or if defective replace pump.
7. System lacks water / Investigate, refill and vent.
8. Connections to heat exchanger limit stat unsound /check & rectify.
9. Unsound electrical connection to fan / Check integrity of fan connection plug.
10. Fan blades heavily contaminated / Clean fan.
11. Fan is defective / Replace fan.
12 . There is no gas supply available / Investigate, restore gas supply.
13. Low gas pressure / Investigate and rectify.
14. Fuse defective / Check fuses and replace as necessary.
15. Gas valve min output setting is incorrect / Check and adjust min output CO
2
%.
16. Oxidation on burner mounting screws / Loosen and retighten screws.
17. Poor ignition lead connection to electrode or damp connection or lead damaged and shorting to earth / Check and rectify.
Page 66
66
STRATA1
38 & 38/46 COMBI
Cause No. Reason/Action
18 . Transformer defective / Replace transformer / loose connection.
19. Condense siphon is blocked or condense waste blocked or frozen / Clear siphon or waste pipe.
20. Flue gas leakage from connection at rear of heat exchanger / Check, reposition or replace seal.
21. System strainer blocked ?, isolation valve closed ? Or some other interruption to water flow / Check and rectify.
22. Unacceptably high resistance in flue or air supply tubes or flue blocked / Check flue for suitability or clear obstruction.
23. Leakage of flue gas from flue gas tube into air tube vitiating the combustion air / Strip out flue system and remake joints.
24. Zone pumps not running / Check and rectify.
25. Heat exchangers fouled internally with silt or scale / Clean, descale heat exchangers and system and re-dose system with water treatment.
26. Heat exchanger high limit stat defective / Replace limit stat.
27. Boiler set for wrong gas type / Convert boiler to burn the gas being supplied.
28. Flue gas limit stat defective / Replace limit stat.
29. Boiler control panel defective / Replace control panel.
30. Incorrect position of ignition electrode / Reset gap 4-5mm.
31. moisture in-on electrical connections or components / Dry carefully using warm air from a hair dryer.
32. Incorrect electrical connection / Check and rectify.
33. Wiring interrupted (broken wire) / Check and rectify.
34. reset button stuck / Press button in attempt to free sticking contacts. If no success then replace control panel.
35. Ignition electrode damaged or broken / Replace electrode.
36. Unsound electrical connections to pump / Check and rectify.
37. Gas valve defective / Replace gas valve.
37. Gas valve defective / Replace gas valve.
38. Reversed polarity on incoming power supply.
22.1 (possible) causes of fault (contd)
Page 67
67
STRATA1
38 & 38/46 COMBI
23.0 instructing
the user
The installer should inform the user about the operation and use of the Strata 1 boiler and in particular
point out:-
Any safety provisions.
The need to carry out regular maintenance when the screen display shows a SERVICE message.
The installer must provide the user with all documentation relating to the Strata 1 boiler and any
ancillary items.
23.1 to turn on
the appliance
23.2 to turn off
the appliance
1. Ensure the manometer indicates a pressure within the system of not less than 0.5bar.
2. Ensure the gas supply is turned on.
3. Switch on the on/off switch on the appliance control panel.
4. If all controls connected to the appliance are calling for heat the screen with display DHW demand or CH demand.
5. If all controls are in the off position the screen will display standby.
6. Allway check the setting of the summer/winter switch marked with
1. Switch off the on/off switch on the appliance control panel.
2. Turn off the gas supply.
NOTE: Turning off the appliance will leave the system at risk of freezing during winter months and will put out of action the automatic pump exercising routine. If the only reason for shutdown is that normal heating is not required, then it is recommended to leave the boiler on and turn off or turn down any external controls.
"+"
Page 68
68
STRATA1
38 & 38/46 COMBI
24.0 parts list
Strata 1 38 parts 1
Page 69
69
STRATA1
38 & 38/46 COMBI
24.0 parts list
(contd)
Strata 1 38 parts 2
Page 70
70
STRATA1
38 & 38/46 COMBI
24.0 parts list
(contd)
Strata 1 38 parts 3
Page 71
QW/0102/4576
35 Nobel Square, Burnt Mills Industrial Estate, Basildon, Essex SS13 1LT Tel: 01268 591010 Fax: 01268 728202
www.mhsboilers.com
This publication is issued subject to alteration or withdrawal without notice.
The illustrations and specifications are not binding in detail. All offers and sales are subject to the Company's current terms and conditions of sale.
A member of the Modular Heating Group Plc
Loading...