010705
Ultramax PB Supplementary Information For AGU2.511
Communication Clip Installation Including LMU64 Controller
reprogramming. (Part Code. 96.38000-7005)
Following the installation of the AGU2.5 communication clip (complete with base mounted wiring
connection) onto the front of the LMU64 controller a number of operational parameters within the unit
must be altered to ensure the clips operates as required.
LMU64 Pictured above with AGU2.511 and OCI420 communication clips.
A number of parameters will require altering within the LMU64 controller from their standard default
setting to allow the AGU2.511 communication clip to operate correctly.
Access is gained to the H parameters by pressing the PROG ! buttons simultaneously for 3 seconds
unit H 90 appears on the screen. The required H parameters can then be reached by using the PROG
. Or PROG !buttons. Once at the required H parameter the required setting is achieved by using the
+ - buttons. To save the alteration in the controller the INFO button must be pressed.
Parameter # Description Default New Setting
H618 Input control configuration
Input value interpretation affected by H622 or H623
Dependant upon control requirement. (4 is recommended.)
0 4. Predefined Temperature set point
5. Predefined Boiler Output
6. Low Loss Header Sensor H622 Maximum Temperature Via X51 input 0-10 Volt 85 85 H623 Maximum Temperature Via X51 input 0-20mA 5 85 H619 Relay designation for Output from Orange Plug
Left Terminal Live.
Right Terminal Neutral.
Output rated at 240 Volts 0.5 Amp
0 0. Hydraulic Diagram Derived.
1. LPG SSOV Output.
2. Boiler Fault Output.
3. Boiler Operating Output.
4 -12 Non supported Output.
H620 Relay designation for Output from Clear Plug
Left Terminal Live.
Middle Terminal Neutral.
Output rated at 240 Volts 0.5 Amp
0 0. Hydraulic Diagram Derived.
1. LPG SSOV Output.
2. Boiler Fault Output.
3. Boiler Operating Output.
4 -12 Non supported Output.
H621 Relay designation for Output from Clear Plug
Right Terminal Live.
Output rated at 240 Volts 0.5 Amp
0 0. Hydraulic Diagram Derived.
1. LPG SSOV Output.
2. Boiler Fault Output.
3. Boiler Operating Output.
4 -12 Non supported Output.
L AGU
X52 must be connected to X1:02 utilising the supplied lead. (Discard the existing blue plug.)
Page 35
060405
Ultramax PB Supplementary Information For OCI420 LPB Communication Installation Including LMU64 and RVA47
Controller reprogramming. (Part Code. 96.38000-7004)
Following the installation of the OCI420 LPB communication clip (complete with base mounted wiring
connection) onto the front of the LMU64 controller a number of operational parameters within the unit
must be altered to ensure the clips operates as required.
LMU64 Pictured above with AGU2.511 and OCI420 communication clips.
A number of parameters will require altering within the LMU64 controller from their standard default
setting to allow the OCI420 communication clip to operate correctly.
Access is gained to the H parameters by pressing the PROG ! buttons simultaneously for 3 seconds
unit H 90 appears on the screen. The required H parameters can then be reached by using the PROG
. Or PROG !buttons. Once at the required H parameter the required setting is achieved by using the
+ - buttons. To save the alteration in the controller the INFO button must be pressed.
LMU
Parameter #
Description Default New Setting
H516 External temperature at which the boiler ceases to operate in
heating mode. Summer / Winter changeover temperature.
18 30
H552 System hydraulic configuration. (Streamline 16 & 31) = 67
(Streamline 31 & 47 Combi) = 70
(Streamline 47 & 75) = 66
80 81 80
H605 Boiler positioning in cascade 1 Boiler # 1 = 2
Boiler # 2 = 3
etc up to boiler #12 = 13
A number of parameters will require altering within the RVA47 cascade controller from their standard
default setting to allow the RVA47 to operate correctly.
Access is gained to the operational parameters of the RVA47 cascade controller by pressing the PROG
! buttons simultaneously for 3 seconds unit 51 appears on the screen. The required parameters can
then be reached by using the PROG . Or PROG !buttons. Once at the required parameter the
required setting is achieved by using the + - buttons. To save the alteration in the controller the AUTO
button must be pressed.
RVA47
Parameter #
Description Default New Ssetting
16 External temperature at which the boilers cease to operate in
heating mode. Summer / Winter changeover temperature.
17 30
140 Cascade Communication Master Configuration 1 1 141 Cascade communication Master Configuration 0 0 148 Cascade communication Clock Configuration 3 3
Please note that the QAC32 outside air sensor must be connected to the RVA47 cascade controller.
L OCI.
Cascade wiring connection point X41. Polarity must be observed.
Page 36
010805
Ultramax PB Supplementary Information For AGU2.500
Additional Heating Zone Clip Installation Including LMU64
Controller reprogramming. (Part Code. 96.38000-7003)
Following the installation of the AGU2.500 Additional Heating Zone (Mixing Zone) clip (complete
with base mounted wiring connection) onto the front of the LMU64 controller a number of operational
parameters within the unit must be altered to ensure the clips operates as required.
LMU64 Pictured above with AGU2.500 and OCI420 communication clips.
A number of parameters will require altering within the LMU64 controller from their standard default
setting to allow the AGU2.500 communication clip to operate correctly.
Access is gained to the H parameters by pressing the PROG ! buttons simultaneously for 3 seconds
unit H 90 appears on the screen. The required H parameters can then be reached by using the PROG
. Or PROG !buttons. Once at the required H parameter the required setting is achieved by using the
+ - buttons. To save the alteration in the controller the INFO button must be pressed.
Parameter # Description Default New Setting
Heating Zone Without Mixing Valve and Flow
Sensor (QAD36)
H554. bit 5 Activation of fault indication of flow sensor not
installed
1 0 = Fault code indication
suppressed
Heating Zone With Mixing Valve and Flow
Sensor (QAD36)
No Alterations Required.
L AGU2.500
X52 must be connected to X1:02 utilising the supplied lead. (Discard the existing blue plug.)