Ultramax PB Supplementary Information For AGU2.511
Communication Clip Installation Including LMU64 Controller
reprogramming. (Part Code. 96.38000-7005)
Following the installation of the AGU2.5 communication clip (complete with base mounted wiring
connection) onto the front of the LMU64 controller a number of operational parameters within the unit
must be altered to ensure the clips operates as required.
LMU64 Pictured above with AGU2.511 and OCI420 communication clips.
A number of parameters will require altering within the LMU64 controller from their standard default
setting to allow the AGU2.511 communication clip to operate correctly.
Access is gained to the H parameters by pressing the PROG ! buttons simultaneously for 3 seconds
unit H 90 appears on the screen. The required H parameters can then be reached by using the PROG
. Or PROG !buttons. Once at the required H parameter the required setting is achieved by using the
+ - buttons. To save the alteration in the controller the INFO button must be pressed.
Parameter # Description Default New Setting
H618 Input control configuration
Input value interpretation affected by H622 or H623
Dependant upon control requirement. (4 is recommended.)
0 4. Predefined Temperature set point
5. Predefined Boiler Output
6. Low Loss Header Sensor
H622 Maximum Temperature Via X51 input 0-10 Volt 85 85
H623 Maximum Temperature Via X51 input 0-20mA 5 85
H619 Relay designation for Output from Orange Plug
Left Terminal Live.
Right Terminal Neutral.
Output rated at 240 Volts 0.5 Amp
0 0. Hydraulic Diagram Derived.
1. LPG SSOV Output.
2. Boiler Fault Output.
3. Boiler Operating Output.
4 -12 Non supported Output.
H620 Relay designation for Output from Clear Plug
Left Terminal Live.
Middle Terminal Neutral.
Output rated at 240 Volts 0.5 Amp
0 0. Hydraulic Diagram Derived.
1. LPG SSOV Output.
2. Boiler Fault Output.
3. Boiler Operating Output.
4 -12 Non supported Output.
H621 Relay designation for Output from Clear Plug
Right Terminal Live.
Output rated at 240 Volts 0.5 Amp
0 0. Hydraulic Diagram Derived.
1. LPG SSOV Output.
2. Boiler Fault Output.
3. Boiler Operating Output.
4 -12 Non supported Output.
L AGU
X52 must be connected to X1:02
utilising the supplied lead.
(Discard the existing blue plug.)