thermostat has been incorporated into the control system.
2. Do not obstruct the airvents, grilles or other air openings in the boiler room, and ensure
a clear path of combustion and ventillation air to the burner.
3. Do not store objects on or near the burner, boiler, and flue.
4. Do not use propellant sprays or chemicals particularly chlorine based chemicals in the
vinicity of the boiler.
5. The boiler must be serviced at regular intervals by competant persons.
To re-start 1. Check that the gas supply or oil isolating valve is open.
the boiler 2. Switch on the electrical supply, set the control thermostats to the desired setting and
ensure any external controls (time/temperature controls) are turned on and calling for heat.
3. The burner should now start pre-ventillation and then fire.
1. If there is fuel leakage from your boiler, first stop the system and shut down the oil
valve at the outlet of the fuel tank. If a gas leak is suspected (e.g. Odour in the boiler room)
Fuel leakage do not use a naked flame to locate the leak, or turn on or off any electrical switches.
Immediately contact your gas supplier, details should be on the notice at the gas meter.
2. If there is leakage from an oil tank, it must be removed and replaced.
Electrical The boiler will not work, if the electricity is cut off. The boiler should start automatically
failure when the electircity is restored.
Boiler If the burner does not operate; check that there is enough fuel in the tank, and the gate
operational valve at the outlet of the tank is opened (oil fired installations).
failures Ensure that any controls are calling for heat. Check/reset the burner lockout reset button.
Ensure that the system pumps are running and that the boiler overheat safety thermostat
is not tripped (see "safety thermostat fault" below.
If burner still fails to operate, seek expert assistance from your service company.
If the raditaors can not be heated; refer to followings:
System 1. There may be air in the circuit; it must be removed.
heating problem 2. There may be pressure drop in the circuit. If the pressure gauge on the manometer of
the heating system is below the minimum safe value, water must be added to the circuit.
3. The thermostat setpoint may be rather low; the setpoint degree must be increased.
4. The room unit or programmable timer on the control panel may be in service. The
adjustments of these devices must be checked again.
Safety In the case of safety thermostat lock-out; first check to make sure that the water level is
thermostat correct. If there is any water loss from the system investigate and remedy, adding more
fault water treatment as necessary. Reset the overheat safety themostat by pressing the reset
button under the removable cap. If the boiler should go to overheat safety lockout again
or the thermostat fails to reset, then seek expert assistance from your service company.
Flue gas leakage 1. The leakage may be due to damaged/ineffective seals on the cleaning covers.
from boiler 2. Check the condition of the fibreglass ropes between each section, also check the
body seals between the front door and front section.
3. Check the effectiveness of the chimney and ensure no restrictions.
END-USER INSTRUCTIONS