MHS Boilers Ltd ©
230307
28
10 - 11 Boiler enable (240 V). When these terminals are connected the primary pump will
be started and the boiler will be enabled. When there is an open circuit between
them the boiler will be shut down. The pump will also stop after the set run on
time. These terminals can be used, among other things, for set ting the boilers
to standby during the summer months whilst continuing to provide domestic hot
water priority.
12 - 13 Operating signal (240 V, 50 Hz, 1 A, N.O.). The operating signal falls off if a fault
has occurred more than 2 times within 6 minutes (the fault code will appear in
the display with a “3”) or if a fault is longer than 6 minutes active.
14 - 15 Control voltage for an external gas valve. This output begins to provide 240 V
before the boiler starts up; the voltage ceases after the boiler shuts down. This
output can be used to open hydraulic valves or to operate boiler room ventilation.
16 - 17 Calorifier thermostat (240 V). When these terminals are interconnected the boiler
will try to provide the set flow temperature programmed for the boiler. This input
only functions if terminals 34 - 35 are interconnected. The calorifier temperature
can also be regulated by a sensor (terminals 35-36).
18 - 19 Interlock input (240 V). If the connection between these terminals is interrupted
the boiler will be deactivated and wait until the connection is restored (after 6
minutes or if the same fault has occurred three times within 6 minutes, this input
will be interlocked).
20 - 21 Lockout input (240 V). If the connection between these terminals is interrupted
the boiler will lockout. Reinstate the connection and press reset.
30 - 31 External sensor* (2-wire 1,01 kΩ PTC). After a suitable sensor has been connected
it will be automatically recognised when the power supply is switched on.
32 - 33 Low velocity header sensor* (2-wire 1,01 kΩ PTC). This sensor can measure the
temperature of a low velocity header.
35 - 36 Calorifier temperature sensor* (2-wire 1,01 kΩ PTC). After a suitable sensor
has been connected it will be automatically recognised when the power supply
voltage is switched on. The terminals 34 - 35 must not be interconnected. The
purpose of this function, in comparison with the calorifier thermostat, is to make
possible a night time temperature reduction and an anti-legionella switching
(only with BME, E6 or KKM).
37 - 38 External influence* (2 – 10 VDC = +10°C – +90°C). At voltages below 2 V the
boiler will switch to “constant supply temperature operation”.
39 - 40
Output capacity signal*. This signal provides information for a capacity display.
0 – 100% = 0 – 10 VDC. The maximum current is 5 mA.
For higher currents or long connecting wires (›5 m) the use of a signal amplifier is
recommended.
41 - 42 SCOM bus connection (use the correct polarity).